CenterPoint Energy P O Box 1700 Houston, TX
|
|
- Ashlyn Black
- 5 years ago
- Views:
Transcription
1 CenterPoint Energy P O Box 1700 Houston, TX IF YOU ARE APPLYING FOR DISTRIBUTED GENERATION, PLEASE FOLLOW THE INSTRUCTIONS IN THE PARAGRAPHS BELOW. YOU WILL NEED TO COMPLETE AND SIGN AND THEN MAIL, FAX, OR THE APPLICATION FOR INTERCONNECTION AND PARALLEL OPERATION OF DISTRIBUTED GENERATION WITH THE UTILITY SYSTEM AND APPLICATION AND STUDY FEES ADDENDUM TO THE ADDRESS, FAX NUMBER, OR ADDRESS LISTED BELOW. DO NOT SEND IN THE AGREEMENT FOR INTERCONNECTION AND PARALLEL OPERATION OF DISTRIBUTED GENERATION AT THIS TIME. IF YOU WERE REQUESTED TO COMPLETE AN AGREEMENT FOR INTERCONNECTION AND PARALLEL OPERATION OF DISTRIBUTED GENERATION, PLEASE COMPLETE THE HIGHLIGHTED AREAS AND THEN PRINT AND SIGN IN THE TWO PLACES AND THEN MAIL, FAX, OR THE AGREEMENT FOR INTERCONNECTION AND PARALLEL OPERATION OF DISTRIBUTED GENERATION TO THE ADDRESS, FAX NUMBER, OR ADDRESS LISTED BELOW. To run any distributed generation (DG) device that is connected to the CenterPoint Energy (CNP) system, you will first have to complete an application. You can go to our website at and do a search for distributed generation. There you will find helpful information. Send hard copies to me at: Bellaire Service Center, CenterPoint Energy, P.O. Box 1700, Houston, TX The fax number is Anything that you have that is electronic can be ed to me at Residential_DG@centerpointenergy.com or Commercial_DG@centerpointenergy.com The application and addendum need to be filled out and returned to me. Two documents are part of the Public Utility Commission of Texas (PUCT) Substantive Rules. One document is an example of a oneline. Please let me know if there are any questions on your part. Your supplier or contractor can be a source of information in filling out the application. Attached for your information are files for prospective customers who are considering installation of DG devices that would be operated directly with the CNP distribution grid. The PUCT has established state-wide rules for any such installation 0-10,000 kw and connected at a voltage up to 60,000 Volts. This would define a project under the PUCT rule requirements. Interconnection to the distribution grid will require review and compliance per the PUCT rules. Basically, all DG projects must have design review prior to installation by CNP for compliance. Normally, there will be a study fee (established in the "CNP_Distributed_Generation_Application.pdf ). We will notify you after the initial review if this is applicable. We will coordinate the technical review of the interconnection equipment. The review package and application should be sent to the address shown in the application. Information should include a one-line diagram showing the relationship of the DG unit tied into a breaker or breakers in the electrical panel and the CNP meter location. The AC disconnect switch should be between the inverter and electrical panel and must be a lockable, external handle, visible and readily accessible disconnect switch and typically installed within 10 feet of the CNP meter. If the AC disconnect switch is installed more than 10 feet from the CNP meter, a weather-resistant, easilyread placard must be installed within 10 feet of the CNP meter, clearly identifying the location of the AC disconnect switch. Manufacturer specifics for the machine (or inverter) and disconnect switch are necessary in the review. Depending on actual conditions at the site, possible CNP system modifications may be required to accommodate the interconnection which would be at customer expense. The determination of any possible modification costs or study fees would be detailed in the report of our review. Finally, once an application has been accepted as being in compliance, you will be notified of our approval of the connection design for construction. A field inspection will be required to demonstrate the installation is built as planned PRIOR TO ACTUAL SYNCHRONIZATION WITH THE CNP
2 GRID. An interconnection agreement will be prepared and must be signed by the customer prior to energization. I hope this initial information will be useful in your further development of the project. Feel free to have your prospective equipment supplier or installer contact us for clarification of technical questions in this review. An internet search for distributed renewable generation or solar panels, suppliers, and contractors in the Houston area should help you locate installers. If you have further questions, please contact me at The address to the PUCT substantive rules web site is included below for your convenience. Jason R. Hulbert Supervising Engineer Distribution System Protection CenterPoint Energy
3 Page 1 of INTERCONNECTION AND PARALLEL OPERATION OF DISTRIBUTED GENERATION DISTRIBUTED GENERATION SERVICE RATE DGS Company shall interconnect distributed generation pursuant to Public Utility Commission of Texas Substantive Rules and A customer seeking interconnection and parallel operation of distributed generation with Company must complete and submit the Application for Interconnection and Parallel Operation of Distributed Generation with the Utility System. PRE-INTERCONNECTION STUDY FEE SCHEDULE Pre-certified distributed generation units that are up to 500 Kw that export not more than 15% of the total load on a single radial feeder and also contribute not more than 25% of the maximum potential short circuit current on a radial feeder are exempt from any pre-interconnection study fees. For all other DG applications, the study fees in the following table will apply. Non-Exporting 0 to 10 kw 10+ to 500 kw 500+ to 2000kW to 10,000 kw 1. Pre-certified, $0 $0 $650 $845 not on network 2. Non pre-certified, $312 $503 $1,210 $1,405 not on network 3. Pre-certified, $272 $640 $1,680 $1,875 on network 4. Not pre-certified, on network $525 $1,150 $2,240 $2,435 Exporting 0 to 10 kw 10+ to 500 kw 500+ to 2000kW to 10,000 kw 1. Pre-certified, $75 $220 $870 $1,065 not on network 2. Non pre-certified, $312 $769 $1,430 $1,625 not on network 3. Pre-certified, $272 $860 $1,900 $2,095 on network 4. Not pre-certified, on network $495 $1,370 $2,460 $2,655
4 Page 2 of 5 Prescribed Form for the Application for Interconnection and Parallel Operation of Distributed Generation Customers seeking to interconnect distributed generation with the utility system will complete and file with the company the following Application for Parallel Operation: APPLICATION FOR INTERCONNECTION AND PARALLEL OPERATION OF DISTRIBUTED GENERATION Return Completed Application to: Attention: Jason R. Hulbert Distribution System Protection P.O. Box 1700 Houston, TX Customer s Name: Address: Contact Person: Address: Telephone Number: Service Point Address: Information Prepared and Submitted By: (Name and Address) Signature The following information shall be supplied by the Customer or Customer s designated representative. All applicable items must be accurately completed in order that the Customer s generating facilities may be effectively evaluated by for interconnection with the utility system.
5 Page 3 of 5 Number of Units: GENERATOR Manufacturer: Type (Synchronous, Induction, or Inverter): Fuel Source Type (Solar, Natural Gas, Wind, etc.): AC Kilowatt Rating (95 F at location) AC Kilovolt-Ampere Rating (95 F at location): Power Factor: Voltage Rating: Number of Phases: Frequency: Do you plan to export power: Yes / NO If Yes, maximum amount expected: Do you wish to report excess generation to your REP? Yes / No Pre-Certification Label or Type Number (e.g., UL-1741 Utility Interactive or IEEE ): Expected Energization and Start-up Date: Normal operation of interconnection: (examples: provide power to meet base load, demand management, standby, back-up, other (please describe)) One-line diagram attached: Yes
6 Page 4 of 5 For systems not using pre-certified inverters (e.g., inverters certified to UL-1741 or IEEE ), does have the dynamic modeling values from the generator manufacturer? Yes No If not, please explain: (Note: For pre-certified equipment the answer is Yes. Otherwise, applicant must provide the dynamic modeling values if they are available) Layout sketch showing lockable, "visible" disconnect device is attached:: Yes
7 Page 5 of 5 Authorized Release of Information List By signing this Application in the space provided below, Customer authorizes CenterPoint Energy Houston Electric, LLC to release Customer s proprietary information to the extent necessary to process this Application to the following persons: Project Manager Name Phone Number Address Electrical Contractor Consultant Other [CUSTOMER NAME] BY: PRINTED NAME: Jason R. Hulbert BY: PRINTED NAME: TITLE: Supervising Engineer Distribution System Protection DATE: TITLE: DATE:
8 APPLICATION AND STUDY FEES ADDENDUM Please provide the following information for the generating facility. (For Solar (PV) Only) Panel Wattage / Number of Panels: ESI ID (from electric bill): Inverter Capacity: kw Inverter peak efficiency rating: % Generation capacity: DC kw Rating Generation maximum output: kw AC (should equal Kilowatt Rating from pg. 5 of the application) NOTE: The application review package shall include a electrical one-line diagram showing the relationship of the generation unit tied into a breaker or breakers in the electrical panel and the CenterPoint Energy (CNP) meter location. The Safety Disconnect switch shall be between the inverter and electrical panel and must be lockable with an external handle, visible and readily accessible, and within 10 feet of the CenterPoint Energy Meter. If Disconnection switch is installed more than 10 feet from the CenterPoint Energy meter, a weather-resistant, easily-read placard shall be install on the CenterPoint Energy meter, clearly identifying the location of the safety switch. Manufacturer specifics for the inverter and the safety disconnect switch are necessary in the application review. If there are any questions, please call us at To submit applications via please use one of the provided below. Residential_DG@centerpointenergy.com Commercial_DG@centerpointenergy.com
9 Example One-Line Diagram For Small Distributed Generation Installations Control Strategy - 59N Relay Utility Visible lockable AC disconnect in close proximity to meter: if further than ten feet or not in line of sight, this will require a placard Utility Meter Complies With PUCT Rule Point of Common Coupling; Ex: Breaker with the following information. Breaker Size, Main Breaker size, Bus Bar rating Main Service Panel Visible Lockable Disc. with external handle if fused need fuse size Not a breaker Inverter: Make/Model PV panels or Wind Turbine General Loads
Oncor Application for Interconnection of Distributed Generation
Oncor Application for Interconnection of Distributed Generation Operating Mode: Parallel Operation Longer than 100 milliseconds (07/11/2018) This application is for generator systems that synchronously
More informationRenewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group
Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group Table of Contents 1. Introduction... 1 2. Purpose... 1 3. Customer Eligibility...
More informationDocument C0. Use for:
Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized
More informationSuperseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 Effective May 27, 2010 Effective December 3, 2011
Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 INTERCONNECTION APPLICATION FOR ALL BUT UL1741 CERTIFIED INVERTER BASED SYSTEMS LESS THAN 10 KW In addition to the information provided below, a complete
More informationLevel 2, 3 and 4 Interconnection Application for Certified, Inverter Based Generating Facilities Not Greater than 2MW
Level 2, 3 and 4 Interconnection Application for Certified, Inverter Based Generating Facilities Not Greater than 2MW The Customer Generator applicant ("Applicant") hereby makes application to the T &
More informationLegal Name of the Customer (or, if an individual, individual's name):
Instructions An Interconnection Customer who requests a Utah Public Service Commission jurisdictional interconnection must submit this Interconnection Request by hand delivery, mail, or delivery service
More informationInterconnection Application
Interconnection Application Member interested in applying for the interconnection of a distributed energy resource to the Utility s distribution system through the Fast Track or Study Processes are to
More informationGreen Power Connection Net Energy Metering Online Application Training
Green Power Connection Net Energy Metering Online Application Training Presented by: Marianne Mannschreck and Joshua Cadoret Date: Welcome Historical Net Energy Metering Application Volume Benefits of
More informationSMALL GENERATOR INTERCONNECTION REQUEST (Application Form)
SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: _Cleco Power LLC Designated Contact Person: Cindy Guillot Address: P.O Box 70, (2180 St. Landry Hwy) St. Landry, LA 71367
More informationA Regulatory Perspective on Distributed Generation
A Regulatory Perspective on Distributed Generation Southwest Electrical Metering Association Spring Meeting Galveston June 10, 2015 Darryl Nelson Rates and Regulatory Agenda Why Rules are Needed Texas
More informationOncor Residential/Small Commercial Project Requirements
Oncor Residential/Small Commercial Project Requirements Revised: March 26, 2018 In Effect: May 1, 2018 Equipment (Including all associated equipment) o Batteries o Utility Meter o Generators o Visible
More informationInstructions. Interconnection Customer declares its intention to interconnect with the AEP Distribution System.
APPLICATION FOR INTERCONNECTION WITH THE Indiana Michigan Power Company INDIANA DISTRIBUTION SYSTEM (Project capacity greater than 10kW) Instructions Interconnection Customer declares its intention to
More informationSMALL GENERATOR INTERCONNECTION REQUEST. (Application Form)
Attachment 2 Transmission Provider: SMALL GENERATOR INTERCONNECTION REQUEST Designated Contact Person: Address: Telephone Number: (Application Form) An Interconnection Request is considered complete when
More informationChecklist for Submission to Utility
Simplified Interconnection Application Persons interested in applying for the interconnection of a distributed energy resource (DER) to the Utility s distribution system through the Simplified Process
More informationFor the State of Washington SMALL GENERATOR INTERCONNECTION REQUEST (Tier 1 [Non-Net Meter], Tier 2, Tier 3) (Application Form)
Electrical Company: PacifiCorp For the State of Washington SMALL GENERATOR INTERCONNECTION REQUEST (Tier 1 [Non-Net Meter], Tier 2, Tier 3) (Application Form) Designated Contact Person: Robin Moore Address
More informationDISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS
STATE OF MINNESOTA DISTRIBUTED GENERATION INTERCONNECTION TABLE OF CONTENTS Foreword 2 1. Introduction 3 2. References 6 3. Types of Interconnections 7 4. Interconnection Issues and Technical Requirements
More informationInterconnection Standards for Delmarva Power & Light Company s Delaware Operating Territory
Interconnection Standards for Delmarva Power & Light Company s Delaware Operating Territory Authority: This Interconnection Standard is filed in compliance with the Delaware Public Utility Commission in
More informationSOUTHERN COMPANY DISTRIBUTION INTERCONNECTION POLICY
SOUTHERN COMPANY DISTRIBUTION INTERCONNECTION POLICY Inverter Based Generators 25 kw and This document contains the interconnection requirements for inverter based generators, 25 kw and smaller, that operate
More informationElmhurst Mutual Power & Light nd Street South Tacoma, WA
Elmhurst Mutual Power & Light 120 132 nd Street South Tacoma, WA 98444-4808 Interconnection Requirements of Member Owned Renewable Electric Generating Facilities of 100 Kilowatts or Less Table of Contents
More informationBulletin Installation of solar photovoltaic systems Rules , , , , and
Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic
More informationMidwest Energy, Inc. Distributed Generation Interconnection Expedited & Standard Process Application
Midwest Energy, Inc. Distributed Generation Interconnection Expedited & Standard Process Application Instructions To submit an application to interconnect a generating facility using the Expedited or Standard
More informationSMALL GENERATING FACILITY PRE-APPLICATION REPORT REQUEST FORM
SMALL GENERATING FACILITY PRE-APPLICATION REPORT REQUEST FORM 1. Instructions By completing this request form, an Interconnection Customer may request a preapplication report from the NYISO regarding the
More informationRapid Shutdown Requirements for NEC 2017
2017 AEESOLAR DEALER CONF. Rapid Shutdown Requirements for NEC 2017 Presented by: Bill Brooks, CMP 4 2017 NEC Statistics for Article 690 Whole article was reduced from 11,000 words to about 8,000 words.
More informationSOUTH TEXAS ELECTRIC COOPERATIVE, INC.
SOUTH TEXAS ELECTRIC COOPERATIVE, INC. P.O. Box 119 Nursery, Texas 77976 (361) 575-6491 Fax (361) 576-1433 Transmission Interconnection Requirements Table of Contents I. Introduction II. Interconnection
More informationINTERCONNECTION STANDARDS FOR GENERATING FACILITIES (GF) CONNECTED TO THE FORT COLLINS DISTRIBUTION SYSTEM. July 2011 UPDATED STANDARDS
INTERCONNECTION STANDARDS FOR GENERATING FACILITIES (GF) CONNECTED TO THE FORT COLLINS DISTRIBUTION SYSTEM July 2011 UPDATED STANDARDS Rev 9.0 July 2011 2 TABLE OF CONTENTS 1.0 SCOPE AND GENERAL REQUIREMENTS...5
More informationBulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010
Ontario Electrical Safety Code - Bulletins 50-1-0 Bulletin 50-1-0 Installation of Solar Photovoltaic Systems Section 50; Rules: 84-020, 84-024, 84-030; Tables 11 and 19 Issued July 2010 Scope (1) Introduction
More informationWN U-60 Original Sheet No. 152
WN U-60 Original Sheet No. 152 Table of Contents INTERCONNECTION WITH ELECTRIC GENERATORS 1) Introduction Sheet 152-A 2) Attachments Sheet 152-A 3) Definitions Sheet 152-B 4) Applicability Sheet 152-H
More informationCONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected Generation (DCG)]
Project Name: Kitchener-Wilmot Hydro Inc. 301 Victoria Street South Kitchener, Ontario, Canada N2G 4L2 Appendix F2: Form DG06 CONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected
More informationU.S. Virgin Islands Water and Power Authority
U.S. Virgin Islands Water and Power Authority REQUIREMENTS AND PROCEDURES FOR INTERCONNECTION OF SOLAR PHOTOVOLTAIC GENERATION TO THE ELECTRICAL DISTRIBUTION SYSTEM Request for Proposals from Independent
More informationPUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System
PUBLIC SERVICE OF NEW HAMPSHIRE Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System September 2013 1.0 Purpose of this document Public Service of New Hampshire
More informationMinnesota DER Interconnection Process Kristi Robinson, P.E.
Minnesota DER Interconnection Process Kristi Robinson, P.E. 6841 Power Lane SW Alexandria, Minnesota Tel 320.762.1697 Fax 320.762.1479 www.star-energy.com eee@star-energy.com Spring 2017: Petition made
More informationSummary. Registration RULE 21 ONLINE PORTAL PILOT PG&E CONTACT DETAILS
PG&E Interconnection Portal Contents List Summary... 1 Registration... 1 Account Details... 2 Starting a New Application... 3 Select Program... 3 Enter Generators... 4 Form Builder... 5 Tab Options...
More informationDISTRIBUTED ENERGY RESOURCES NEM PLUS APPLICATION MANUAL
DISTRIBUTED ENERGY RESOURCES NEM PLUS APPLICATION MANUAL Reference Guide for the NEM Plus Application This guide is intended to help customers and contractors complete and submit an application for the
More informationSuperseding REVISED SHEET NO. 34D-8 REVISED SHEET NO. 34D-8 Effective May 27, 2010 Effective December 3, 2011
Superseding REVISED SHEET NO. 34D-8 REVISED SHEET NO. 34D-8 2. Initial Technical Review a. The following flowchart provides, for illustrative purposes, the major steps in the Initial Technical Review process:
More informationSPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5
Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System
More informationTRANSMISSION ENGINEERING STANDARDS SUBSTATIONS
This standard was reviewed and approved by key managers on. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a generating plant with the Oncor
More informationPower System Network Simulator (PSNsim)
The PSNsim is hardware simulator that simulates all parts of power system from generation to utilization. The PSNsim is a scaled down model of the real power system that provides an experimental environment
More informationGuideline for the Connection of Micro Embedded Generators to the TasNetworks Distribution Network
Tasmanian Networks Pty Ltd ABN 24 167 357 299 Guideline for the Connection of Micro Embedded Generators to the TasNetworks Distribution Network (AS4777 Compliant) NG R PD 09 Version 2.0 July 2014 TABLE
More informationChapter 5A Embedded Generation Information Pack United Energy s guide to the Embedded Generation connection process for of Chapter 5A
Chapter 5A Embedded Generation Information Pack United Energy s guide to the Embedded Generation connection process for of Chapter 5A Public Table of contents 1 Connection Framework... 3 2 Connection Types...
More informationUpdated: 02/15/18. Step by Step Guide to Level 1 Interconnection Applications in PowerClerk
Updated: 02/15/18 Step by Step Guide to Level 1 Interconnection Applications in PowerClerk Welcome to Ameren Illinois PowerClerk for Level 1 Interconnection Applications To Start: You will need to Register
More informationOperation of Photovoltaic Equipment Certification Program
D R A F T FSEC STANDARD Operation of Photovoltaic Equipment Certification Program FSEC Standard 201-10 January 2010 FSEC Standard 201-04 - 0 - Table of Contents 1.0 [Reserved] 2.0 [Reserved] 3.0 [Reserved]
More informationPhotovoltaik ON GRID / OFF GRID
Photovoltaik ON GRID / OFF GRID BST the flexible training system from for building automation based on real components. BST mobile practical safe elabo-ts.com Photovoltaic Off Grid System DC Hybrid AC
More informationSRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016
SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:
More informationSmall Hydro Regulatory and Permitting Requirements California
Small Hydro Regulatory and Permitting Requirements California Lon W. House, Ph.D. 530.409.9702 Water & Energy Small Hydro Regulatory and Compliance FERC QF, Small Hydro License or Exemption EIA Generator
More informationLONG ISLAND POWER AUTHORITY INTERCONNECTION REQUIREMENTS FOR NEW DISTRIBUTED GENERATION GREATER THAN 300 KVA OPERATING IN PARALLEL WITH LIPA S RADIAL
LONG ISLAND POWER AUTHORITY INTERCONNECTION REQUIREMENTS FOR NEW DISTRIBUTED GENERATION GREATER THAN 300 KVA OPERATING IN PARALLEL WITH LIPA S RADIAL DISTRIBUTION SYSTEM Revised and Issued March 2003 I.
More informationSECTION ELECTRIC METERING
SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable
More informationState of Minnesota Interconnection Process for Distributed Generation Systems
State of Minnesota Interconnection Process for Distributed Generation Systems Introduction This document has been prepared to explain the process established in the State of Minnesota, to interconnect
More informationState of Minnesota Interconnection Process for Distributed Generation Systems
State of Minnesota Interconnection Process for Distributed Generation Systems Introduction This document has been prepared to explain the process established in the State of Minnesota, to interconnect
More informationOncor Installer Portal Training Guide
Oncor Installer Portal Training Guide 1 Index 1 Introduction to Portal 2 3 Project Workflow 4 5 Introduction to Tabs in Portals 6 All Web Pages Navigation, Buttons, Features & Functionalities New Installer
More informationGeneration, Transmission, and End User Facilities
Procedures for Interconnection of Generation, Transmission, and End User To the Grand River Dam Authority Transmission System Table of Contents GRDA/SPP Interaction... 3 Standards... 3 Generation... 3
More informationPUBLICLY AVAILABLE SPECIFICATION
IEC/IEEE/PAS 63547 PUBLICLY AVAILABLE SPECIFICATION Edition 1.0 2011-09 Interconnecting distributed resources with electric power systems INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE V ICS 29.240.99
More informationRPS Quick Reference Guide
The RPS Quick Reference Guide was designed to help users navigate through the Renewable Energy Facility Application Tracking System while highlighting important notes and features. Table of Contents Logging
More informationPV Rapid Shutdown device
PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.
More informationFacilities Evaluation Detailed Standards for New Renewable Energy
1/52 Facilities Evaluation Detailed Standards for New Renewable Energy Small Photovoltaic Inverter (Grid-connected, Stand-alone) New & Renewable Energy Assessment Center, Digital Industry Division, Korea
More informationDistributed Generation Interconnection in Illinois
Distributed Generation Interconnection in Illinois David Rearden January 31, 2014 1a In the beginning Electricity system was vertically integrated: the utility generated the electricity, transmitted to
More information1510 MOTOR CONTROLLERS
SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,
More informationPG&E Transmission Interconnection Handbook
Table of Contents TABLE OF CONTENTS... 1 UPDATE HISTORY... UP-1 INTRODUCTION... IN-1 I-1. PURPOSE... IN-1 I-2. INTRODUCTORY DEFINITIONS... IN-1 I-3. HANDBOOK APPLICABILITY... IN-2 I-3.1. New Load, New
More informationFeed-in Tariff application form
For Office Use Only Date received: from Eligibility date: Start read: Version number: V3 Feed-in Tariff application form Please complete and sign this form and send it to us at: Freepost ECOTRICITY (no
More informationAC Solar Warehouse Installation and Commissioning Checklist
AC Solar Warehouse Installation and Commissioning Checklist Installation and Commissioning Checklist AC Solar System Installation and Commissioning Checklist INSTALLATION DETAILS Address of Installation:
More informationMONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES
MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity
More informationLORAIN-MEDINA RURAL ELECTRIC COOPERATIVE, INC. NORTH CENTRAL ELECTRIC COOPERATIVE, INC.
Page 1 LORAIN-MEDINA RURAL ELECTRIC COOPERATIVE, INC. NORTH CENTRAL ELECTRIC COOPERATIVE, INC. RULES AND REGULATIONS FOR DISTRIBUTED RESOURCES (DR) OBJECTIVES To provide for the safety of consumers, Cooperative
More informationUnderstanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing
Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime
More information.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical
Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of
More informationSeries 2400 Paralleling Switchgear
Series 2400 Paralleling Switchgear SERIES 2400 PARALLELING SWITCHGEAR TYPICAL SERIES 2400 MULTIPLE GENERATOR/UTILITY PARALLELING SWITCHGEAR Intelligent, Configurable Switchgear for Distributed Generation,
More informationFORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE
FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.
More informationPUBLIC UTILITY COMMISSION OF OREGON 550 CAPITOL STREET NE, STE. 215 PO BOX 2148 SALEM, OREGON (503) APPLICATION FOR CERTIFICATE OF
PUBLIC UTILITY COMMISSION OF OREGON 550 CAPITOL STREET NE, STE. 215 PO BOX 2148 SALEM, OREGON 97308-2148 (503) 378-8959 APPLICATION FOR CERTIFICATE OF AUTHORITY TO PROVIDE TELECOMMUNICATIONS SERVICE IN
More informationMount Pleasant Waterworks. Cross-Connection Control Program Guidelines October 2010
Mount Pleasant Waterworks Cross-Connection Control Program Guidelines October 2010 1 PREFACE The purpose of this policy is to protect the public water supply from the possibility of contamination. The
More informationMicroinverters And The Solar Industry
Microinverters And The Solar Industry Peter Lum Senior Learning And Development Professional Assistant Professor Skyline College Solar Continues Its Growth 2 Significant Growth Of Microinverters in Solar
More information(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)
Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3
More informationTitle Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)
Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)
More informationMedium Voltage Metal-Enclosed Power Capacitor Banks
66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium
More informationSECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service
More informationSOLAR ACADEMY. The Future of Solar Technology
SOLAR ACADEMY The Future of Solar Technology THE SOLAR ACADEMY: ALWAYS UP TO DATE The SMA Solar Academy offers a comprehensive range of seminars on photovoltaics and provides information on SMA products,
More informationFeed-in Tariff Application Form
Feed-in Tariff Application Form Once you ve completed all the details print off this form, sign it and return to us at Green Energy (UK) plc, Black Swan House, 23 Baldock Street, Ware, SG12 9DH. Scanned
More informationEvaluation of Business Cases for Smart Grid Solutions Kenny Mercado, Senior VP Electric Operations
Evaluation of Business Cases for Smart Grid Solutions Kenny Mercado, Senior VP Electric Operations April 21, 2015 CenterPoint Energy (CNP) Headquartered in Houston, Texas Serving 5.7 million electric &
More informationRobin Hood Energy Feed-In Tariff Application Form
A not for profit company Robin Hood Energy Feed-In Tariff Application Form In order for us to pay the Feed-In Tariff (FIT), we need you to complete this application form fully. Simply fill in the form,
More informationTechnical Guideline For Interconnection Of Generators To The Distribution System
Technical Guideline For Interconnection Of Generators To The Distribution System May 22, 2002 EDTI acknowledges the use of other utility industry and industry committee developed documents as the framework
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationEnergy Storage Systems Utilizing the SunDial Plus 30PV+S Inverter
APPLICATION NOTE 601 Energy Storage Systems Utilizing the SunDial Plus 30PV+S Inverter CONTENTS 1.0 Purpose and Scope.... 1 2.0 Disclaimer.... 1 3.0 Overall Energy Storage System... 1 4.0 Electrical Interfaces...
More informationREQUIREMENTS FOR CONNECTION OF EMBEDDED GENERATORS UP TO 5MW TO THE EVOENERGY NETWORK VERSION SM3201
REQUIREMENTS FOR CONNECTION OF EMBEDDED GENERATORS UP TO 5MW TO THE EVOENERGY NETWORK VERSION 3.1 2018 2018 SM3201 CONTENTS 1. INTRODUCTION 6 2. SCOPE 7 2.1 Types of Embedded generating Systems 7 2.1.1
More informationCity of Azusa Light & Water Department. Interconnection and Net Metering Agreement For Generating Facility 10kW or Less
City of Azusa Light & Water Department Interconnection and Net Metering Agreement For Generating Facility 10kW or Less This Interconnection and Metering Agreement for Solar or Wind Turbine Electric Facilities
More informationQuick Start Installation and User Manual
1 Quick Start Installation and User Manual Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation Settings
More informationPresented by: Oscar Araujo Photovoltaic Solutions Manager. 4 th Canadian German Solar PV Conference March 2 nd 2011
Photovoltaic Solutions Make the most of your solar PV project Presented by: Oscar Araujo Photovoltaic Solutions Manager 4 th Canadian German Solar PV Conference March 2 nd 2011 Agenda Solutions for Renewable
More informationModel Number Electrical Compatibility Module Connector Type M LL-S22 M LL-S22-NA M LL-S23 M LL-S23-NA
M215 Microinverter Installation Planning The Enphase M215 Microinverter The M215 Microinverter is Enphase s most powerful and efficient model yet. This grid-tied microinverter is compatible with most 60-cell
More informationCALIFORNIA INDEPENDENT SYSTEM OPERATOR CORPORATION FERC ELECTRIC TARIFF FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 727 METERING PROTOCOL
FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 727 METERING PROTOCOL FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 728 METERING PROTOCOL Table of Contents MP 1 OBJECTIVES, DEFINITIONS AND SCOPE
More informationSECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
More informationA. Consumer Protection (Safety Requirements) Regulations to be Administered by Enterprise Singapore
Our Ref: Cir 2018-02 Date: 6 April 2018 To: All Registered Suppliers (RS) Subject: Administration of Consumer Protection (Safety Requirements) Regulations and Update of SAFETY Mark This circular is to
More informationBalancing and Settlement Code BSC PROCEDURE
Balancing and Settlement Code BSC PROCEDURE Registration of Transmission System Boundary Points, Grid Supply Points, GSP Groups and Distribution Systems Connection Points BSCP25 Version 8.0 Date: 29 June
More informationJK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A
POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.
More informationWant to make your inspectors happy?
Want to make your inspectors happy? Mark Baldassari Director, Codes and Standards Agenda Inspectors How to make your inspector happy Common Misconceptions Installing Microinverters Disconnect Means Grounding
More informationUSER MANUAL. MODEL 552 Series. High Speed Telco Surge Protectors. SALES OFFICE (301) TECHNICAL SUPPORT (301)
USER MANUAL MODEL 552 Series High Speed Telco Surge Protectors C E R T I F I E D An ISO-9001 Certified Company Part# 07M552-E Rev. G Revised 01/27/10 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301)
More informationRobin Hood Energy Feed-in Tariff Application Form
Robin Hood Energy Feed-in Tariff Application Form In order for us to pay the Feed-In Tariff (FIT), we need you to complete this application form fully. Simply fill in the form, sign it and return it to
More informationILLINOIS DISTRIBUTED GENERATION PROCUREMENT PROGRAM APPLICATION INSTRUCTIONS
ILLINOIS DISTRIBUTED GENERATION PROCUREMENT PROGRAM APPLICATION INSTRUCTIONS AGENDA Company Overview Program Overview SRECTrade Registration and Bidding Process Summary and Q&A This document is protected
More informationC. New or replacement products installed in existing facilities shall be consistent with existing equipment.
September 2012, rev 00 26 2923 Variable Frequency Controllers PART 1. GENERAL 1.01 Description A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width
More informationGreen Power Connection TM. Solar Stakeholder Collaborative for Maryland
Green Power Connection TM Solar Stakeholder Collaborative for Maryland September 6, 2016 1 Welcome Dave Velazquez President and CEO, Pepco Holdings 2 Welcome Donna Cooper President for the Pepco Region
More informationHYBRID PV INVERTERS HySpirit Series. 4kW-10kW. Hybrid Inverter with Battery Backup Smart Energy for Smart Home
HYBRID PV INVERTERS HySpirit Series Hybrid Inverter with Battery Backup Smart Energy for Smart Home 4kW-10kW FSP HySpirit series Offers a more intelligent power solution for our customers to reduce the
More informationPierre Sebellin. Systems Technical Officer International Electrotechnical Commission
Pierre Sebellin Systems Technical Officer International Electrotechnical Commission Introduction IEC is a global organization that publishes consensus-based international Standards and manages Conformity
More informationM215 Microinverter Installation Planning
TECHNICAL BRIEF M215 Microinverter Installation Planning The M215 Microinverter The M215 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60- cell PV modules
More informationCALIFORNIA INDEPENDENT SYSTEM OPERATOR CORPORATION FERC ELECTRIC TARIFF FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 727 METERING PROTOCOL
FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 727 METERING PROTOCOL FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 728 METERING PROTOCOL Table of Contents MP 1 OBJECTIVES, DEFINITIONS AND SCOPE
More informationAppendix 1 Interconnection Request INTERCONNECTION REQUEST
Appendix 1 Interconnection Request INTERCONNECTION REQUEST NO HARD COPY REQUIRED FOR INTERCONNECTION REQUESTS SUBMITTED ELECTRONICALLY VIA RIMS 5 Provide one hard copy of this completed form pursuant to
More information