Telecommunication Cabling Standards to address IoT and power delivery. 5 October
|
|
- Alexina Campbell
- 5 years ago
- Views:
Transcription
1 Telecommunication Cabling Standards to address IoT and power delivery 1 5 October
2 In a nut shell Out for comment NOW AS/NZS (General requirements) AS (Office) AS (Industrial) AS (Homes) AS (Data Centres) AS (Distributed Building Services) AS (Bonding) AS (Component testing-safety) SA TS ISO/IEC (Remote powering) Out for comment soon (2-3 weeks) AS/CA S008 (Mandatory product requirements) AS/CA S009 (Mandatory installation requirements)
3 Drivers for change IoT Powering over telecommunications cabling 5 October
4 Power over telecommunications cabling Industry trends 25 Watts per pair over 4 pair 800 Watts to 1000 Watts per pair over telecommunications cabling Issue related to heat rise Bundling Installation conditions Circuit activated Conductor Size Ambient temperature 5 October
5 Requirements Power Internet of Thing Communications New and emerging Standard to address IoT Distributed building services (AS ) Modular Plug Terminated Links MPTL (AS/NZS ) One pair cabling delivering power and communications New Energy Classifications (ES1, 2 & 3) New remote power classification (RP1,2 & 3) New cable bundling requirements (1 & 4 Pr) 5 October
6 How are standards in Australia addressing the issues Performance Safety AS Standards AS/NZS Standards ISO/IEC Standards SA Technical Specifications SA Technical Reports AS/CA Standards Minimum requirement- Safety may not be assured Engineered solutions 5 October
7 What's changing with Standards for customer cabling NEW MANDATORY STANDARDS PROPOSED AS/CA S009 and AS/CA S008 Changing of voltage classification to new requirements based on new Energy source classifications ES1, ES2 & ES3 ES3 is hazardous No Maximum Voltage No Maximum Current LV Telecommunication falls under ES3 Addressing remote powering Minimum conductor sizes Mandatory earthing 5 October
8 AS/NZS Audio/video information and communication technology equipment Part 1: Safety requirements Published 15 February 2018 Replaces (overlap under regulation) AS/NZS :2015, Information technology equipment Safety, Part 1: General requirements (IEC , Ed. 2.2 (2013), MOD) Ordinary Person applies to all persons other than instructed person and skilled person Instructed Person applies to all persons who have been instructed and trained by a skilled person or are supervised by a skilled person Skilled person applies to persons who have training or experience in the equipment technologies particularly in knowing the various energies and energy magnitudes used in the equipment 5 October
9 Mandatory Standards- Safety AS/CA S008 Requirements for customer cabling products Cable Product requirements MANDATORY AS/CA S009 Installation requirements for Customer Cabling Telecommunication cabling requirements MANDATORY 5 October
10 What's changing with Standards for customer cabling PERFORMANCE STANDARDS Based on ISO/IEC series Modular plugs terminated links in Australia and New Zealand One pair cabling to 1000m Coming soon Retiring of AS/NZS 3080 New Bonding (earthing) requirements New Distributed Building Services Standards (IoT) 5 October
11 New Customer Cabling Standard (AS/NZS 3080) Performance Standard AS/NZS Standard Descriptor Minimum Class General requirements Cable Distributors to Outlet Coverage AS Office premises Class E Cat 6 CD-BD-FD-CP-TO 2,000m AS Industrial premises Class D Cat 5 CD-BD-FD-ID-CP-TO 10,000m AS Homes Class D Cat 5 PHD-SHD-BO/TO 100m AS Data centres Class E A Cat 6 A (ENI)-MD-ID-ZD-LDP- EO AS Distributed building services 2,000m Class E A Cat 6 A CD-BD-SD-SCP-SO 10,000m 5 October
12 New Support standards ISO/IEC Information technology -- Implementation and operation of customer premises cabling -- Part 2: Planning and installation AS/NZS 3084 Telecommunications installations - Telecommunications pathways and spaces for commercial buildings ISO/IEC Information technology -- Telecommunications bonding networks for buildings and other structures AS/NZS Information technology -- Implementation and operation of customer premises cabling -- Part 3: Testing of optical fibre cabling IEC (AS/NZS version to withdrawn) Specification for the testing of balanced and coaxial information technology cabling - Part 1: Installed balanced cabling as specified in ISO/IEC and related standards Addresses Installation and quailty plans Pathways and spaces Earthing requirements for telecommunication systems In-field Optical fibre testing In-field Twisted Pair testing Performance Performance Performance Performance Performance 5 October
13 General Design Principle Backbone Cable Backbone Cable Horizontal Cable C C C C C C C C Campus Distributor CD Building Distributor BD Floor Distributor FD Consolidation Point TE Outlet Subsystem Cable 4 Subsystem Cable 3 Subsystem Cable 2 Cable Z Cable Y Terminal Equipment Cord C C C C C C C C C C Distributor 4 Distributor 3 Distributor 2 Distributor 1 Consolidation Point TE Outlet 5 October
14 Disconnect under load-100 watts Load Carried over 8 conductors Load Carried over 2 conductors 5 October
15 Modular Plug Terminated Link - MPTL SCP Patch Panel Plug 5 October
16 MPTL to be specified within AS/NZS MPTL Testing Channel testing is not appropriate as it does not test the plug on the end of the cable High dependency links Poor connector choice means high chance of failure Poor termination means high chance of failure Least tested links installed 5 October
17 Applications 5 October
18 Twisted Pair Applications Giga Bits Class Category Channel Permanent Link 1 Class D Cat 5 100m 90m 2.5 Class E A Cat 6 A 100m 90m 5 Class E A Cat 6 A 100m 90m 10 Class E A Cat 6 A 100m 90m 25 Class I Cat m 26m 40 Class I Cat m 26m Mitigation and other techniques may allow for the application to run over a lower class but there is NO guarantee 5 October
19 Remote Power over Twisted Pair watts of delivery DC unbalance may affect the operation of a device DC unbalance testing may be called up as an additional field test Recommended infield tests to do for cabling supporting PoE Direct current (DC) resistance unbalance within a pair Direct current (DC) resistance unbalance between pairs Recommended infield tests DO NOT SPECIFY COUPLING ATTENUATION 5 October
20 Remote powering PoE 100 Watts ISO/IEC TS Technical specification information technology Telecommunication cabling requirements for remote powering of terminal equipment 500mA per conductor (1 Amps per pair) Digital Electricity (Digital power) 1000 Watt per pair metres VoltServer Safe to touch (ES2) 5 October
21 Remote power category - Proposed RP1 212 ma Controls required Attachment of remote power equipment Planning of subsequent cabling installation RP2 >212 ma and 500 ma Controls required Average current restricted to a value between 212 ma and 500 ma Attachment of remote power equipment Planning of subsequent cabling installation RP3 500 ma Controls required Planning of subsequent cabling installation Bundling is better than loose lay for addressing heat rise Gaps in bundles reduce heat rise Channel lengths are likely to be reduced from 100 metres to address heat rise
22 One Pair cabling Generic cabling links in support of one pair cabling Long reach Not intended to replace four pair 1000 metre reach PAM 3 signalling Power delivery Industrial 15 metre reach Indications from the IEEE802.3 liaison was that the IEEE 802.3bt draft had included a warning against using smaller than 26AWG cabling (90m). However, now the text indicates compliance with local, national and regional codes is required. Including NFPA70 in US (NEC) AS/CA S009 is likely to recommend 24 AWG as a minimum for twisted pair cabling 5 October
23 Remote powering over one pair Work started on heat rise in one pair cabling in Paris February 2018 Australian expert requested heat rise in multicore cables be taken into account Heat rise in multi-core cables would be useful to address the impact on safety in AS/CA S009 ISO/IEC TS provide some useful methods of calculation 5 October
24 Security of cabling (Physical Network Security) Work started on addressing Issues related to the physical security of cabling and network infrastructure at the Washington meeting of SC25 WG3 in September 2018 The proposed standard objectives are to address Conformance requirements (Tiered) Risk assessment and security objectives Design Planning Monitoring system
25 Optical Fibre 5 October
26 Optical Fibre Cabling Application dependent on Cable type Connector type, polarity Pin in/pin out Key up-key up Key down Key down Number of cores Length (Propagation delay) Optical Attenuation of Channel Limit Cable selection Multi-mode OM3, OM4 and OM5 Multi-mode OM1 and OM2 to be grandfathered Single mode OS1a and OS2 (OS1a replaced by OS1) 5 October
27 New Standards Dependency on technology and supporting infrastructure IoT Convergence Power Delivery of Telecommunications Cabling Lack of understanding of risk What Changed Lack of expertise within emerging technology 5 October
28 Risk Mitigation Strategy Risk Mitigation relates to a strategy to reduce exposure to risks or the likelihood of its occurrence based on four primary elements Risk Acceptance Risk Avoidance Risk Limitation Risk Transfer 5 October
29 Are you confident your strategy will address? The validity of your specification Information/Knowledge Dissimulation of your staff Test and acceptance criteria to mitigate risk Address Risks associated with engineered solutions Issues with remote powering The impact of product selection When standards don t guarantee safety 5 October
30 Recommendations Engage with, attend training and seek advice from Industry organisations like BICSI Trusted advisors within your cable system vendors organisations Develop risk mitigation strategies Refresh your organisation specification and identify risk and communicate Develop staff knowledge Have preferred suppliers and contractors with suitable knowledge and understanding of the changes 5 October
31 What the future holds Personal predictions for the next big things 1. Remote power - Now 2. One pair cabling Next 1 to 3 years 3. Security of Physical infrastructure Next 3 to 5 years
32 Q&A Murray Teale Technical Director VTI Services Chair - Communication Alliance WC80 (AS/CA S008 and S009) Chair Standards Australia CT001 (AS/NZS 3080) Australia Expert and head of delegation - JTC1/SC25 WG3 (ISO/IEC 11801) mteale@vti.net.au October
ISO/IEC 11801: (E)
ISO/IEC 11801:2002-09 (E) Information technology_- Generic cabling for customer premises CONTENTS FOREWORD...10 INTRODUCTION...11 1 Scope...13 2 Normative references...13 3 Definitions, abbreviations and
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO/IEC 15018 First edition 2004-06 Information technology Generic cabling for homes ISO/IEC 2004 All rights reserved. Unless otherwise specified, no part of this publication may
More informationISO/IEC SC25 WG3. Who are they & what can they do for 802.3cg? Alan Flatman. Principal Consultant LAN Technologies.
1 ISO/IEC SC25 WG3 Who are they & what can they do for 802.3cg? Alan Flatman Principal Consultant LAN Technologies Email: a_flatman@tiscali.co.uk 2 Who are ISO/IEC SC25 WG3? Ø International systems group
More informationIndustry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"
Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland
More informationKey Items: - Customer Premises Cabling - 1 ISO/IEC SC25/WG3 Meeting Singapore: January 2017
1 ISO/IEC SC25/WG3 Meeting Singapore: 16-20 January 2017 - Customer Premises Cabling - Key Items: 1. ISO/IEC 11801 Ed.3 major revision - DIS ballot positive and progressing to FDIS - final draft (contains
More informationCopper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only
1 Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only Gautier Humbert, RCDD Standards Coordinator Digital Infrastructures Legrand District Chair Mainland Europe BICSI 2 Agenda
More informationAS/NZS 3080:2003 AS/NZS
AS/NZS 3080:2013 (ISO/IEC 11801:2011, MOD) Incorporating Amendment No. 1 Australian/New Zealand Standard Information technology Generic cabling for customer premises Superseding AS/NZS 3080:2003 AS/NZS
More informationNZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers
Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on
More informationINTERNATIONAL STANDARD
ISO/IEC 11801-4 INTERNATIONAL STANDARD Edition 1.0 2017-11 Information technology Generic cabling for customer premises Part 4: Single-tenant homes INTERNATIONAL ELECTROTECHNICAL COMMISSION ICS 35.200
More informationApplication Note. Data Center Standards and Layouts
Application Note Data Center Standards and Layouts 1. Data Center Standards In earlier times, a room in which one or more servers, a telephone system and active network components were located was often
More informationKey Items: - Customer Premises Cabling - 1 ISO/IEC SC25/WG3 Meeting Milan: Sep 2015
1 ISO/IEC SC25/WG3 Meeting Milan: 07-10 Sep 2015 - Customer Premises Cabling - Key Items: 1. ISO/IEC 11801 Ed.3 major revision - 1 st CD has had a thorough review & has been re-issued as 2 nd CD 2. ISO/IEC
More informationPANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY
PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents
More informationPhysical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks
Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Agenda New ISO/IEC 11801 Standard New Fibre standards and encoding methods Higher speeds,
More informationPANGEN SYSTEM WARRANTY. Warranty Guide
PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &
More informationIntroduction to Key Principles of Telecommunications Cabling
Introduction to Key Principles of Telecommunications Cabling Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of
More informationImplementation considerations for cabling supporting remote powering
Implementation considerations for cabling supporting remote powering Table of contents Background...3 Advantages of remote powering using communications cabling...4 CommScope implementation considerations
More informationCopper Cabling Standards
Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals
More informationThe Power of PoE: Converging Power and Control of Intelligent Devices
The Power of PoE: Converging Power and Control of Intelligent Devices Amir Sekhavat Global Director, Copper Product Management and Enterprise Market Development Superior Essex Objectives What drives the
More informationBest Practices to realise the full potential of Remote Powering. Paul Cave Technical Manager Excel Networking
Best Practices to realise the full potential of Remote Powering Paul Cave Technical Manager Excel Networking Benefits of Power over Ethernet (PoE) Remote Powering No requirement for local power outlets
More informationDATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005
DATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005 Mike Gilmore Managing Director, e-ready Building Convenor CENELEC TC215 WG1 Mike Gilmore Standards Activities Member JTC1 SC25 WG3: Generic
More informationThe Cabling Partnership
The author Mike Gilmore, Senior Partner of The Cabling Partnership, is involved at the highest level in UK and European cabling standardisation. Mike is Chairman of the BSI Premises Cabling Experts Panels
More informationThis document is a preview generated by EVS
ISO/IEC 11801-2 INTERNATIONAL STANDARD Edition 1.0 2017-11 Information technology Generic cabling for customer premises Part 2: Office premises ISO/IEC 11801-2:2017-11(en) THIS PUBLICATION IS COPYRIGHT
More information[0.057] 5.8 [0.23]
Product Specification 7 March 13 Rev A1 SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used
More informationINTERNATIONAL STANDARD
ISO/IEC 11801-3 INTERNATIONAL STANDARD Edition 1.0 2017-11 Information technology Generic cabling for customer premises Part 3: Industrial premises INTERNATIONAL ELECTROTECHNICAL COMMISSION ICS 35.200
More information[0.057] 5.8 [0.23]
Product Specification 7 June 13 Rev B SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationINTERNATIONAL STANDARD
ISO/IEC 11801-1 INTERNATIONAL STANDARD Edition 1.0 2017-11 Information technology Generic cabling for customer premises Part 1: General requirements INTERNATIONAL ELECTROTECHNICAL COMMISSION ICS 35.200
More informationCERTIFICATION PLUS SM
CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation
More informationPower Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure
Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Increasing usage of Power over Ethernet (PoE) represents
More informationAtras Network Communications
Atras Network Communications Guide to Information and Communications Technology (ICT) Standards developed and published by the Telecommunications Industry Association (TIA) The Telecommunications Industry
More informationDistributed ConvergeIT Systems. Lee Funnell EMEA Technical Manager
Distributed ConvergeIT Systems Lee Funnell EMEA Technical Manager Introduction Lee Funnell CTP, CDCDP EMEA Technical Manager British Standards Institute - Premises Cabling Experts Panel Data Centre Alliance
More informationConsiderations for the Design & Field Testing of an Optimized High-Power PoE Cabling System
WHITE PAPER Considerations for the Design & Field Testing of an Optimized High-Power PoE Cabling System Why Comprehensive Testing for DCR Unbalance is Critical As Power-over-Ethernet (PoE) becomes the
More informationAMP-TWIST* Modular Jack, UTP, Category 6A
Product Specification 5 July 13 Rev A AMP-TWIST* Modular Jack, UTP, Category 6A 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for TE Connectivity*, 6A UTP AMP-
More informationLaying the groundwork for a new level of Power over Ethernet
Laying the groundwork for a new level of Power over Ethernet October 2018 Table of contents Laying the groundwork for a new level of Power over Ethernet...3 PoE basics...4 PoE standards development...5
More informationANSI/TIA-568-C Cat 6A Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability
More informationAMP-TWIST* 6S Series SL Jack
Product Specification 108-93003 16/Mar/2011 Rev E AMP-TWIST* 6S Series SL Jack 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, AMP- TWIST*
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More informationIEEE P802.3bt Guidelines For Field Deployment
IEEE P802.3bt Guidelines For Field Deployment Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Background Power delivery over BASE-T PHYS with specified operation over TIA/ISO cabling 802.3af,
More informationISO/IEC Edition INFORMATION TECHNOLOGY GENERIC CABLING FOR CUSTOMER PREMISES. Part 1: General requirements CORRIGENDUM 1
ISO/IEC 11801-1:2017/COR1:2018 1 ISO/IEC 11801-1 Edition 1.0 2017-11 INFORMATION TECHNOLOGY GENERIC CABLING FOR CUSTOMER PREMISES Part 1: General requirements CORRIGENDUM 1 Foreword Replace, in list item
More informationLight over PoE. Emanuele Colombo Country Manager R&M Italia October 2017
Light over PoE Emanuele Colombo Country Manager R&M Italia October 2017 Content Introduction Development of PoE Zone cabling according EN50173-6 Digital Ceiling Solution R&M proposals for Digital Ceiling
More informationISO/IEC TR Guidance on 40GBASE-T T Cabling
1 ISO/IEC TR 11801-99 99-1 Guidance on 40GBASE-T T Cabling - a tutorial - Alan Flatman Principal Consultant LAN Technologies Email: a_flatman@tiscali.co.uk 2 Content 1. introduction to ISO/IEC SC25 WG3
More informationWith Great Power Over Ethernet Comes Great Responsibility PRESENTED BY Bob Crain
With Great Power Over Ethernet Comes Great Responsibility PRESENTED BY Bob Crain Pathways and Spaces Planning for a PoE Environment IEC 2018 Bob Crain With Great Power Over Ethernet Comes Great Responsibility
More informationDemonstrate and apply knowledge of computer networking infrastructure principles
Demonstrate and apply knowledge of computer networking infrastructure principles 22713 version 1 Page 1 of 5 Level 4 Credits 15 Purpose This unit standard covers the necessary introductory skills required
More informationFREQUENTLY ASKED QUESTIONS (FAQs)
FREQUENTLY ASKED QUESTIONS (FAQs) Q. What is the standard that governs Power over Ethernet? The standard governing Powered Ethernet is IEEE 802.3af Data Terminal Equipment (DTE) Power via Media Dependent
More informationThe Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling in Modern Building Design
The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling in Modern Building Design Agenda Introduction What is it & What is coming? The Impact Why is it important? Recommendations & Summary
More informationThis document is a preview generated by EVS
TECHNICAL SPECIFICATION ISO/IEC TS 22237-5 First edition 2018-05 Information technology Data centre facilities and infrastructures Part 5: Telecommunications cabling infrastructure Technologie de l information
More informationSingle-pair cabling channel specifications
Single-pair cabling channel specifications IEEE P802.3cg 10SPE Task Force October 25, 2017 Dave Hess, CORD DATA 10/25/2017 hess_10spe_01_1025 1 Overview JMTG organization and scope JMTG projects related
More informationANSI/TIA-568-C Cat 6 Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6 Permanent Links. It is offered as a general guide. Suitability
More informationData Center Design and the ANSI/TIA-942 Standard
Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications
More informationLaying the groundwork for a new level of Power over Ethernet
White paper Laying the groundwork for a new level of Power over Ethernet April 2017 Contents Laying the groundwork for a new level of Power over Ethernet 3 PoE basics 3 PoE standards development 4 Four-pair
More informationHistory of Standards
History of Standards From 10Mbps to 100Gbps Ethernet 12 th May 2014 Gautier Humbert, RCDD Business Development Manager Legrand East and Central Europe Agenda 1- Current standards and their structures
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationCabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring
Cabling to support 802.11ac and beyond Nate Herring Sr. Product Manager Hubbell Premise Wiring IP Traffic Continues to Increase Globally, IP traffic will grow 3-fold from 2014 to 2019, a compound annual
More informationPoE Lighting: Unleashing IoT and Opportunity in the ICT Industry
PoE Lighting: Unleashing IoT and Opportunity in the ICT Industry Bob Allan, MBA, LEED GA Global Business Development Manager Intelligent Buildings and Strategic Alliances @ballan32 There s a Revolution
More informationThe Real Impact of High Power PoE on Your IP Network
The Real Impact of High Power PoE on Your IP Network Jason Finnegan, Product Manager Copper Solutions, Legrand Cindy Montstream, Director of Technical Support & Training, Legrand Amir Sekhavat, Global
More informationThe advantages of the 6-connector channel
APRIL 2007 The advantages of the 6-connector channel The advantage of sticking to standardised rules such as ISO11801 (that define the performance of the components, the performance of the whole cable
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationPOSITION DESCRIPTION
POSITION DESCRIPTION Engagement Manager Unit/Branch, Directorate: Location: Outreach & Engagement, Information Assurance and Cyber Security Directorate Auckland Salary range: H $77,711 - $116,567 Purpose
More informationStandardised precabling,
International Telecommunication Union Standardised precabling, the efficient road to secure and reliable home networks Dr. Walter von Pattay Secretary of ISO/IEC JTC 1/SC 25 ITU-T Workshop on Home Networking
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationLeveraging the Structured Cabling System for Security Applications. Mark Dearing, RCDD Leviton Network Solutions
Leveraging the Structured Cabling System for Security Applications Mark Dearing, RCDD Leviton Network Solutions Trends - Cable Category Mix Source: Leviton projections based on market growth rates Over
More informationCabling for Data Centres. Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari
Cabling for Data Centres Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari Data Center Definition is a facility used to house computer systems and associated components, such as telecommunications
More informationEthernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement
Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement Overview SPE is poised to enable a new class of low power devices that
More informationThe Real Impact of High-Power PoE on Your IP Network
The Real Impact of High-Power PoE on Your IP Network Jason Finnegan, Product Manager Copper Solutions - Legrand Cindy Montstream, RCDD, NTS - Director of Technical Support & Training - Legrand Brian Ensign,
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationDr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant
Is Cable Balancing Efficient i Enough for EMI Mitigation in Data Centers? Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant What are You going to Learn? What are the potential sources
More informationWORLDSKILLS STANDARD SPECIFICATION
WORLDSKILLS STANDARD SPECIFICATION Skill 02 Information Network Cabling WSC2015_WSSS02 THE WORLDSKILLS STANDARDS SPECIFICATION (WSSS) GENERAL NOTES ON THE WSSS The WSSS specifies the knowledge, understanding
More informationHow to Decide on Optical Fibre Termination Options. Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect
How to Decide on Optical Fibre Termination Options Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect Termination Choices Optical Fiber Cabling in Data Center Options available Traditional
More informationPoE Lighting: Unleashing IoT and Opportunity in the ICT Industry
PoE Lighting: Unleashing IoT and Opportunity in the ICT Industry Bob Allan, MBA, LEED GA Global Business Development Manager Intelligent Buildings and Strategic Alliances @ballan32 There s a Revolution
More informationNZQA registered unit standard version 2 Page 1 of 9. Install and maintain information and communications technology (ICT) systems and services
Page 1 of 9 Title Install and maintain information and communications technology (ICT) systems and services Level 4 Credits 25 Purpose This unit standard covers installation and maintenance of information
More informationPower over Ethernet: A Consumer Centric Development Perspective
POWER OVER ETHERNET Power over Ethernet: A Consumer Centric Development Perspective Written by: Roy Kusuma, Engineer, Communications Products Matt Gentile, Product Manager, Communications Products TABLE
More informationBICSI NxtGEN & Global Data Center Standards Update
BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee
More informationCanadian Codes & Standards Updates
Canadian Codes & Standards Updates Canadian Codes & Standards Agenda: Which ones do we need to know? What are the latest versions What s changed in the latest versions? What did you miss? Standards Reference
More informatione-ready Building Next Generation IT infrastructures ϕ The Cabling Partnership Mike Gilmore Managing Director, e-ready Building The Cabling Partnership
eready Building THE ONESTOP SHOP Telecommunications equipment and telecommunications cabling Specification for installation, operation and maintenance THE ONESTOPSHOP FOR INSTALLATION Q.A. Mike Gilmore
More informationPower Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure
Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Power over Ethernet (PoE) represents one of the most meaningful
More informationThe University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels
More informationForeword. (dop) (dow)
Page 2 Foreword This European Standard has been prepared by Technical Committee CENELEC/TC 215 Electrotechnical aspects of telecommunication equipment" under the framework of the Mandates M/212 on Telecommunication
More informationCABLING STRUCTURED Introduction and logic of structured cabling Wiring structure EXAMPLE OF THE STRUCTURE OF A WIRING SYSTEM
1 STRUCTURED CABLING 1.1 - Introduction and logic of structured cabling IT and Telecommunications are at the heart of all activities. They require structures capable of carrying various signals (telephony,
More informationMosaic TM LCS2 Cat. 6 RJ 45 socket
870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics....1 2. Presentation...2 3. Installation...2 4.
More informationCertification for 10G copper cabling
Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards
More information1.2 Normative references
1 General 1.1 Scope Within premises and industrial plants, the importance of the information technology cabling infrastructure is similar to that of other fundamental building utilities such as heating,
More informationClassroom WiFi Network Infrastructure Plan
Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More information(Data Center Networks & Cloud Computing Security)
BPSDC (Data Center Networks & Cloud Computing Security) Lecture 3 Data Center Standars Service Level Agreement 2 Building a Data Center is just a Start What is Service Level Agreement (SLA)? An official
More informationNovember 2010 IEEE 802.3
TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire Vice Chair, TIA TR-42 Vice Chair, TIA TR-42.7 November, 2010 Dallas, TX 1 Introduction to TIA Telecommunications Industry Association www.tiaonline.org TR-42:
More informationHighlights: ISO/IEC SC25/WG3 Meeting Geneva: Sep Customer Premises Cabling -
1 ISO/IEC SC25/WG3 Meeting Geneva: 10-13 13 Sep 2012 - Customer Premises Cabling - Highlights: 1. ISO/IEC 24764 Data Centre Cabling Am.1 approved 2. ISO/IEC 14763-3 OF Testing Ed.2 CD in preparation 3.
More information10 Gigabit Ethernet and Future Cabling for Offices + Data Centres
10 Gigabit Ethernet and Future Cabling for Offices + Data Centres Presentation at Nexans Seminar Scandinavia, May 2006 Dr Alan Flatman Principal Consultant LAN Technologies Topics 1. 10 Gig over optical
More informationConflicts in Data Center Fiber Structured Cabling Standards
Conflicts in Data Center Fiber Structured Cabling Standards By Dave Fredricks, CABLExpress Data Center Infrastructure Architect Various telecommunications and data center (DC)-specific standards are commonly
More informationNZQA unit standard version 2 Page 1 of 5
Page 1 of 5 Title Demonstrate knowledge of installation practices and procedures for telecommunications network equipment Level 3 Credits 10 Purpose This unit standard covers the installation of basic
More informationMayhew Technology Solutions
Mayhew Technology Solutions Business Overview MTS offers design, engineering, and installation services for fiber optic, telecommunications, ISP, OSP, physical security, low voltage, and audio-visual systems.
More informationsonnen Installation Practical
sonnen Installation Practical sonnen Components sonnenbatterie eco 8.0 Single Phase System Components 4 sonnenbatterie eco 8.0 Single Phase System Components 5 sonnenbatterie eco 8.0 Single Phase System
More informationBob Lounsbury Rockwell Automation. Brad Woodman Molex Inc. February 22, 2017
PoE, PoE++, PoDL Enhancements to IEEE 802.3 Bob Lounsbury Rockwell Automation Brad Woodman Molex Inc. February 22, 2017 Abstract The IOT is exploding with far reaching applications such as Automotive,
More informationSuppliers' Information Note BT CHANNEL EXTENSION SERVICE Service Description
SIN 345 Issue 1.6 August 2014 Suppliers' Information Note For The BT Network BT CHANNEL EXTENSION SERVICE 1000 Service Description Each SIN is the copyright of British Telecommunications plc. Reproduction
More informationHP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions
HP UPS R/T3000 G2 Installation Instructions Overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower design and offers power protection for loads up to a maximum of 3300 VA/3000 W
More informationTELECOMMUNICATIONS AND DATA CABLING BUSINESSES
DRAFT for RCWS, ADTIA & ICAA INDUSTRY CODE for TELECOMMUNICATIONS AND DATA CABLING BUSINESSES Registered by the ACMA on XX XXXXX 2016 TABLE OF CONTENTS TABLE OF CONTENTS 2 1. SCOPE AND OBJECTIVES 3 1.1
More informationLAN Standards, News & Trends Update 2017 June 15, 2017
LAN Standards, News & Trends Update 2017 June 15, 2017 Greg Olson Jtech Systems, Inc Infrastructure Specialist Greg@jtechreps.com 425-437-1962 Our Objectives Review new & ongoing applications work in IEEE
More informationCabling Infrastructure
Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements
More informationConnectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture
Connectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture Issue Document Status Date: Prepared: Checked: 6 Cat 6 U/UTP, Optical Fibre and MER/SER Guidelines 29/03/2018
More informationTechnical Data. Dimensions
Model Number Features 50 mm flush -wire DC S Technical Data specifications Switching function Normally open (NO) Output type PNP Rated operating distance s n 50 mm Installation flush Output polarity DC
More informationRonald Tellas, Technology and Applications Manager, Enterprise Networking
Direct Connect Testing Guidelines Ronald Tellas, Technology and Applications Manager, Enterprise Networking Introduction Direct Connect is a viable option for the Digital Building that is being deployed
More information