Energieverbrauch von Netzwerkkomponenten
|
|
- Aubrie Ford
- 6 years ago
- Views:
Transcription
1 Bundesamt für Energiewirtschaft Forschungsprogramm Elektrizität ENGLISCHE VERSION Energieverbrauch von Netzwerkkomponenten Messbericht
2 Verteiler: 26/11/97 MK Ingenieure und Planer AG, Mitglied SIA/ASIC Forchstrasse 395, CH-8029 Zürich, Telephon 01 / , Telefax 01 /
3 Contents Abstract 1 1. Objectives and procedures 1 2. Description of networks Topology of B&H network, Rehalp/Esslingen Topology of SIG network, Geneva 2 3. Measurement concept Structure of measurements / analyzed devices (B&H) Structure of measurements / analyzed devices (SIG) 6 4. Results Weekly & daily measurements (B&H) Weekly measurement (SIG) 9 Measurement 1 (B&H, Rehalp EDP centre) Measurement 2 (B&H, Rehalp PABX centre) Measurement 3 (B&H, Esslingen EDP centre) Measurement 4 (SIG, Geneva, EDP centre) 5. Implementation Acknowledgements 33 Appendices 35 Distribution list:messers Brüniger, Kistler, Huser, members of supporting group , E Version 1, MK/CF/sf Ingenieure und Planer AG, Mitglied SIA/ASIC Forchstrasse 395, CH-8029 Zürich, Telephon 01 / , Telefax 01 /
4
5 Abstract Measurements of electricity consumption of network components (router, switch, multiplexer, micro repeater, media converter) were carried out in two modern networks with 82 and 1200 users respectively. It was established that the recorded power was constant in terms of time and does not depend on the data-flow quantity or network topology. The measured power was approx. 30% of the specifications in the product descriptions, and this could give rise to an over-dimensioning of infrastructure systems such as air-conditioning plants and uninterruptible power supply (UPS) units. 1. Objectives Goal The goal of this project is to record the electricity consumption of active network components and list initial criteria for improving energy efficiency. To achieve this, the electrical supply of major network components (switches, routers, multiplexers, micro-repeaters and media converters) was measured in an Ethernet and an ATM network. Procedure Measurements of the electrical power of network components were carried out during periods of high (daytime) and low (night-time) network system loads. The measurements were carried out on two networks: Basler & Hofmann (CISCO products) and Service Industriels de Genève (BAY products), in collaboration with Basler & Hofmann and Teleinform. 1
6 2. Description of networks 2.1 Topology of Rehalp / Esslingen network (B&H) Description of topology This description covers the application of the examined components in the B&H network: - The topology of Rehalp corresponds to that of Esslingen. A switch (2901) is used in the backbone, to which the individual storey switches are connected. The individual segments have been set up according to 10Base2 standard and linked via media converters (transceivers) with the storey switch (2802). - In the Esslingen topology, the storey switches (2802) are linked with the backbone switch (2901) via fibre. Since the CISCO switch does not possess any fibre ports, the individual uplinks opto-converters (transceivers) are pre-switched. (See diagram in Appendix A) Cabling, Rehalp In Rehalp, the cabling has been carried out by means of ThinWire-Ethernet. The individual strands are fed to distributors which are connected to the central node in the server room by means of fibre. Cabling, Esslingen In Esslingen, universal cabling infrastruction was used for wiring the building. The central node point is located in the server room. The storeys are cabled using fibre, and the individual storeys are linked via copper (category 5) from the distributors located on each storey. 2.2 Topology of (SIG) network, Geneva Description of topology The ATM backbone of the SIG network consists of 8 Centillion 100 and a number of 5000DN models manufactured by Bay Networks. For redundant reasons, two ATM C100 switches have been installed in the computer centre. The C100 switches in the basement and 3 rd storey provide switched Ethernet connections to the 5000DN Bay model. An ATM router (VNR) permits connection between the various virtual LANs. (See diagram in Appendix B). 3. Measurement concept 3.1 Structure of measurements / measured equipment in B&H network Overview 2
7 The tested components are depicted in colour in the B&H Network Topology diagram in Appendix A. Measurement 1 (yellow) Components Measurement 1 was carried out in the server room (SS) Rehalp: - CISCO 2514 router (VAX link) - CATALYST 2802 switch (storey switch) - CATALYST 2901 switch (backbone switch) - MR micro-repeater 122T transceiver Media converter Measurement 2 (green) Measurement 2 was carried out in the PABX centre (basement), Rehalp: - CISCO 2503 router (Esslingen link) - CISCO 2503 router (Internet link) IDNX Micro20 multiplexer (WAN link) Measurement 3 (blue) Measurement 3 was carried out in the server centre (basement), Esslingen: - CISCO 2503 router (Rehalp link) - CATALYST 2901 switch (storey switch) - IDNX Micro20 multiplexer (WAN link) Echo cancellor Choice of components Throughout the world, approximately 88% of Internet links use CISCO routers. Of these, some 60% concern the CISCO 2500 model (personal guess from M. Kistler). This indicates that the measurements were carried out on the most widely-used type of router. Measuring devices Each active component is connected to two measuring devices. This redundant method of measuring serves as a cross-comparison for precise measurement as well as helping to verify the measurement. The evaluation of the measurements was mainly based on the readings at the electrical clamps. Device 1 Connection of the clamps to the measuring wires, and link to a data logger. Device 2 Connection of EMU 1.x1M measuring device via direct wiring to the various components. Both measuring arrangements were transferred to a laptop via an interface, and recorded and displayed in table form. 3
8 Diagram of measuring arrangement Arrangement Duration of measurement Measurement cycle The intention was to carry out two measurements: Daily measurement: Measurement was carried out in the smallest possible intervals of 1 second. The readings were averaged, stored and recorded every 30 seconds. Weekly measurement: Measurements were carried out in the smallest possible intervals of 1 second. The readings were averaged, stored and recorded every 5 minutes. With both cycles, the maximum and minimum levels were also recorded for each active component. Evaluation For each of the three measurements an average was calculated using the integral. The course of the measurements was recorded graphically and the power was shown in watts [W]. Comparisons were made between the same components in the different topologies. Measurement periods Measurement 1 June 12 to 23, 1997 Measurement 2 July 24 June to 2, 1997 Measurement 3 July 2 to 11, 1997 Measured variable 4
9 Variable measured with the Chauvin Arnoux clamps: output 100 mv (=) / A (- ). With EMU energy metres, the variable was measured in kwh. 5
10 3.2 Structure of measurements and examined SIG devices Overview The measurement is depicted in colour in the SIG Network Topology in Appendix B. Components Measurement 4 (red) Measurement 4 was carried out in the computer centre of Service Industriels de Genève. Measurement period Measurement 4 June 23 to 30,
11 4. Results 4.1 Weekly and daily measurements (B&H) Measurement capacity Explanations It was possible to measure five devices simultaneously. Measurement 1 It was only possible to use five channels for controlling the measurements obtained at the clamps. Only five EMU devices were available for carrying out measurements. Measurement 3 It was not possible to feed the IDNX multiplexer via an EMU for carrying out measurements. Similar readings as for measurement 2. Accuracy of EMU These devices are capable of measuring currents up to 32 A. The EMU is classified in precision category 2, i.e. +/- 0.5% tolerance. Accuracy of clamps The clamps used are capable of measuring currents up to 150 A. Their tolerance is 3%, though clamps show a greater deviation tendency with very low current levels. Power consumption Results, B&H network The results of the measurements were as follows The power consumption of the devices in permanent operation remains practically constant, regardless of the data-flow quantities, time of day or day of the week. It should also be noted that no significantly greater consumption fluctuations occur at weekends. The power consumption of the individual devices does not depend on the topology in which they are used. The readings obtained are approximately equivalent to 30% of the specifications indicated in the product descriptions. Comparison, B&H The table below shows the components used in the Basler & Hofmann network: 7
12 Model Indicated power Measured power Micro-repeater Media converter 3W 6W Catalyst 2802 switch 110W 40W Catalyst 2901 switch 264W 80W CISCO 2503 router 40W 15W CISCO 2514 router 40W 15W IDNX multiplexer 400W 110W Echo cancellor 12W In connection with these comparisons it should be noted that the components are not completely installed, but the power supply is indicated for completion installation. Comparison of power, Basler & Hofmann Work-desk devices Servers Active components Active components 30.0 kw, 10 hrs/day operation 1.5 kw, 24 hrs/day operation 2.3 kw (specified), 24 hrs/day operation 1.0 kw (measured) Since work-desk devices are switched off at night, their operating time is reduced, and their energy consumption is correspondingly lower. The proportion of the network components in the Basler & Hofmann network that was tested is equivalent to around 15% of the total annual consumption of the network. Significance Throughout Switzerland, operators of networks should be made increasingly aware of the annual energy consumption of network components. This means 8
13 that the application of energy management systems in networks should be more actively promoted. 4.2 Weekly measurement (SIG) Measurement 4 Explanations For cost reasons, Teleinform was unable to carry out daily measurements. No EMU devices were used in Geneva for cross-comparison purposes. Comparison, SIG The table below shows the components used in the Service Industriels de Genève network Mode 1 Indicated power Measured power ATM switch 300/600W 130W (redundant power supply) Bay model 950W 170W Power consumption Results, SIG network The results of the measurements were as follows: The power consumption of the devices in permanent operation remains practically constant, regardless of the data-flow quantities, time of day or day of the week. It should also be noted that no significantly greater consumption fluctuations occur at weekends. The power consumption of the individual devices does not depend on the topology in which they are used. The readings obtained are approximately equivalent to a quarter to a third of the specifications indicated in the product descriptions. With the Bay 5000 DN, the difference between specified and measured power is even more pronounced. 9
14 Measurement 1 Basler & Hofmann (Rehalp, EDP centre) 10
15 11
16 12
17 13
18 14
19 15
20 Measurement 2 Basler & Hofmann (Rehalp, PABX centre) 16
21 17
22 18
23 19
24 20
25 21
26 Measurement 3 Basler & Hofmann (Esslingen, EDP centre) 22
27 23
28 24
29 25
30 26
31 27
32 Measurement 4 Service industriels de Genève (computer centre) 28
33 29
34 30
35 31
36 5. Implementation Data The measurement data should be submitted to the two manufacturers (Cisco and Bay) for examination and evaluation purposes. In the same connection, the manufacturers should also be queried about possible developments. Should any relevant power variations exist between the manufacturers, a labelling procedure could be introduced in the same way as for end devices. Components which meet the criteria would be awarded a quality label, which would enhance transparency on the market. 6. Acknowledgements Swiss Federal Office of Energy At this juncture we wish to thank the Swiss Federal Office of Energy as principal for incorporating Basler & Hofmann into this project. Teleinform We would also like to thank Teleinform for its valuable assistance in connection with the various measurements carried out on the B&H network. Support group We received valuable tips and assistance from Messrs R. Bruniger and A. Huser. 32
37 33
38 Appendices A Diagram: Topology of B&H network B Diagram: Topology of SIG network 34
39 35
40 36
IT CONTINUITY, BACKUP AND RECOVERY POLICY
IT CONTINUITY, BACKUP AND RECOVERY POLICY IT CONTINUITY, BACKUP AND RECOVERY POLICY Effective Date May 20, 2016 Cross- Reference 1. Emergency Response and Policy Holder Director, Information Business Resumption
More informationVendor Questions and Responses Ongwanada RFP #08-06
Vendor Questions and Responses Ongwanada RFP #08-06 1, 2, 3 yr options can only be offered on all EWP service agreements. Will you revise the RFP and accept these as compliant since the Manufactures will
More informationThe Solution Requirements and considerations
Annex A TERMS OF REFERENCE Virtual Private Network (VPN) tunnel installation and Very Small Aperture Terminal (VSAT) internet connectivity for Migration Information and Data Analysis Systems (MIDAS) at
More informationHigher National Unit specification: general information
Higher National Unit specification: general information Unit code: H17A 34 Superclass: CB Publication date: March 2012 Source: Scottish Qualifications Authority Version: 01 Unit purpose This Unit is designed
More informationInternet Architecture and Protocol
Internet Architecture and Protocol Set# 04 Wide Area Networks Delivered By: Engr Tahir Niazi Wide Area Network Basics Cover large geographical area Network of Networks WANs used to be characterized with
More information19CSP075 Broadband Network Upgrade. Appendix C Final Acceptance Checklist (Example) Site Name: Inspector Name: Inspection Date: Acceptance Signature:
19CSP075 Broadband Network Upgrade Site Name: Inspector Name: Inspection Date: Acceptance Signature: Appendix C Final Acceptance Checklist (Example) This form is to be used by AISD personnel to document
More informationWhite paper adaptive IT infrastructures
Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationNetwork Service Assurance
Service Assurance Embedded 'Always-On' Ethernet Devices for Circuit 'Turn-Up' Testing & In-Service Assurance for Layer- 2 and Layer-3 infrastructures Ethernet (L-2) - Typical Scenario HQ & Operations Centre
More informationANSI/TIA/EIA-568-B Cabling Standard
83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on
More informationConfiguring Network Proximity
CHAPTER 9 This chapter describes how to configure a Global Site Selector to perform network proximity to determine the best (most proximate) resource for handling global load-balancing requests. This chapter
More informationInternetworking Switching and Routing MODULE LEVEL 7 MODULE CREDIT POINTS 30 SI MODULE CODE (if known) Computer Systems & Networks
MODULE DESCRIPTOR MODULE TITLE Internetworking Switching and Routing MODULE LEVEL 7 MODULE CREDIT POINTS 30 SI MODULE CODE (if known) 12-7952 MODULE JACS CODE G410 SUBJECT GROUP Computer Systems & Networks
More informationQINEO DATA MANAGER. Perfect welding machine management
QINEO DATA MANAGER Perfect welding machine management Artificial Intelligence! Software 2 CLOOS: Your brand for innovative welding technology! Providing added value for our customers! This is the motivational
More informationNZQA unit standard version 2 Page 1 of 6. Demonstrate basic knowledge of telecommunications concepts
Page 1 of 6 Title Demonstrate basic knowledge of telecommunications concepts Level 2 Credits 10 Purpose This unit standard covers basic telecommunications principles and is intended for telecommunications
More information1 Energy Efficient Protocols in Self-Aware Networks
Energy Efficient Protocols in Self-Aware Networks Toktam Mahmoodi Centre for Telecommunications Research King s College London, London WC2R 2LS, UK Stanford NetSeminar 13 December 2011 1 Energy Efficient
More informationTHE INTERCONNECTED NETWORK
THE INTERCONNECTED NETWORK The Interconnected Network The number of applications / Services on a network increases from year to year. New applications are permanently in preparation. Server and Server
More informationCisco CISCO Data Center Networking Infrastructure Design Specialist. Practice Test. Version
Cisco 642-971 CISCO 642-971 Data Center Networking Infrastructure Design Specialist Practice Test Version 1.1 QUESTION NO: 1 Cisco 642-971: Practice Exam Which service module configuration is recommended
More informationGPON Gigabit Passive Optical Network
GPON Gigabit Passive Optical Network A comprehensive product portfolio for high demand networks. Datacom products meet the various requirements for fiber optical network solutions, providing outstanding
More informationWRTU54G-TM. Release Notes. Software Version (Maintenance Release 9) Wireless Router with Home Phone Adapter
WRTU54G-TM Wireless Router with Home Phone Adapter Release Notes Software Version 1.00.25 (Maintenance Release 9) June 8, 2010 Table of Contents 1. INTRODUCTION 1 1.1 SOFTWARE VERSIONS 1 1.2 VERSION VARIATIONS
More informationLecture: Chapter 1, Introduction to Computer Data
IT220 Agenda & Assignments Lab Assignments MUST be signed off by your instructor for credit. Labs & Assignments submitted late are subject to penalties. Make sure you label each lab assignment with the
More informationDC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications
DC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications DC POWER OVERVIEW BROCHURE NETSURE APPLICATIONS yradio Base Station / Microwave Site ywireless & Wireline Access
More informationModule 15: Network Structures
Module 15: Network Structures Background Topology Network Types Communication Communication Protocol Robustness Design Strategies 15.1 A Distributed System 15.2 Motivation Resource sharing sharing and
More informationQuestions and Answers for Request for Proposal #03588
1. Is 10GB a requirement? Questions and Answers for Request for Proposal #03588 Vendors are welcome to quote on both 10GB and 1GB options. 2. The RFP indicates that you would like to replace the 5 2 nd
More informationContents. One Introduction 2. Two Installation 3 Front Panel Connecting Ports LEDs
Contents One Introduction 2 Two Installation 3 Front Panel Connecting Ports LEDs Three Configuration and Installation Guidelines 7 Hub/Network Configuration Ports and Connectors Typical Use for the Megaswitch
More informationCoolAVR TM New 3 rd party SCADA system For Basler DECS excitation control systems
CoolAVR TM New 3 rd party SCADA system For Basler DECS excitation control systems CoolAVR - SCADA Generator control powered by Press Ctrl+L for Full Screen MBAVR_V1.0 Introduction CoolAVR is a 3 rd party,
More informationS5 Communications. Rev. 1
S5 Communications Rev. 1 Page 1 of 15 S5 Communications For a complete understanding of the S5 Battery Validation System (BVS) communication options, it is necessary to understand the measurements performed
More informationDistributed System Chapter 16 Issues in ch 17, ch 18
Distributed System Chapter 16 Issues in ch 17, ch 18 1 Chapter 16: Distributed System Structures! Motivation! Types of Network-Based Operating Systems! Network Structure! Network Topology! Communication
More informationCommunication Technologies
Unit 29: Communication Technologies Unit code: F/601/7264 QCF Level 3: BTEC Specialist Credit value: 10 Guided learning hours: 60 Aim and purpose The aim of this unit is to ensure learners understand the
More informationGETTING CONNECTED Installation instructions for your NBN Modem Sagemcom 5356
GETTING CONNECTED Installation instructions for your NBN Modem Sagemcom 5356 This guide is designed to help you get started with your new modem. It relates to services being delivered over NBN FTTN connections.
More informationANLEITUNG / MANUAL EMU ALLROUNDER EMU PROFESSIONAL. Quality that counts. Made in Switzerland
ANLEITUNG / MANUAL EMU ALLROUNDER EMU PROFESSIONAL Quality that counts. Made in Switzerland EMU products all from one source EMU provides everything from the energy meter to a complete energy-monitoring
More informationHigher National Unit specification: general information
Higher National Unit specification: general information Unit code: FR23 35 Superclass: CB Publication date: August 2011 Source: Scottish Qualifications Authority Version: 01 Unit purpose The purpose of
More informationIT Services Performance Report
UCD IT Services IT Services Performance Report January December 2010 Prepared by: UCD IT Services Date: 9 th February 2011 Ms. Mary Crowe Chief Information and Technology Officer Contents Background 1
More informationChapter 4: Network Access. Introduction to Networks v5.1
Chapter 4: Network Access Introduction to Networks v5.1 4.0 Introduction 4.1 Physical Layer Protocols 4.2 Network Media 4.3 Data Link Layer Protocols 4.4 Media Access Control 4.5 Summary 2013 Cisco and/or
More informationNetwork+ Guide to Networks 7 th Edition
Network+ Guide to Networks 7 th Edition Chapter 4 Structured Cabling and Networking Elements 2016 Cengage Learning. May not be scanned, copied or duplicated, or posted to a publicly accessible website,
More informationMaster of Engineering in Internetworking Laboratory Guide
Master of Engineering in Internetworking Laboratory Guide Copyright Internetworking Program, Dalhousie University i TABLE OF CONTENTS LIST OF TABLES... III LIST OF FIGURES... IV LIST OF SYMBOLS AND ABBREVIATIONS...
More information2. Site Planning lists the prerequisites and physical requirements for installing the 289H M LSS monitor.
289H M LSS Installation & Operations Manual Overview Section 1 INTRODUCTION This manual provides procedures for installing and operating the 289H M Loop Surveillance System (LSS) monitor. It addresses
More informationBooking a space on campus through Resource Booker
Resource Booker How to SWINBURNE STUDENT LIFE The have introduced a new, more efficient way to selfmanage your bookings and events on campus. While the policies for booking space have not changed, the
More informationUniversity of San Francisco Course Syllabus and Outline
College of Professional Studies BSIS 340 Business Data Networks and Telecommunications University of San Francisco Fall Semester 2008 Robert C. Hughes, M.S. Email: rchughes3@usfca.edu Enrolled Student
More informationPRACTICAL ROUTERS and SWITCHES for ENGINEERS and TECHNICIANS
PRACTICAL ROUTERS and SWITCHES for ENGINEERS and TECHNICIANS Objectives At the end of this workshop participants will: Be able to configure, maintain and manage routers have a clear practical understanding
More informationMDC-20. Maximum Demand predictive Control. Description
Description The MDC-20 is a unit designed to control the maximum demand of an installation. It means that the unit connects and disconnects the installation s electrical loads (non-priority loads) to ensure
More informationApplied Information and Communication Technology
Write your name here Surname Other names Edexcel GCE Centre Number Candidate Number Applied Information and Communication Technology Unit 9: Communications and Networks COVER SHEET 6 May 0 Paper Reference
More informationThe Threaded Case Study
Cisco Networking Academy Program Semesters III and IV Instructor: Chris Widmer The Threaded Case Study OBJECTIVE The purpose of the Threaded Case Study is to allow you to apply the knowledge that you have
More informationGigabit-capable Passive Optical Networks (G-PON): Physical Media Dependent (PMD) layer specification Amendment 2
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU G.984.2 Amendment 2 (03/2008) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Digital
More informationPreparing for JT Fibre
Preparing for JT Fibre What to expect when switching to Fibre JT Fibre for Business Switching to JT Fibre for Business This guide will provide you with further information on the installation process,
More informationInternetworking Basics
Assignment 1: Case Study Part 2 Deadline: 24/01/06 (3 weeks) Student Name Date handed in: Grading Criteria It is possible to achieve credits for the following from this assignment. Grading Criteria Tick
More informationSIMEAS Q80 quality recorder: Voltage quality starts with measurement.
SIMEAS Q80 quality recorder: Voltage quality starts with measurement. Answers for energy. 1 Energy with quality crucial for utilities and for industry A reliable supply of electrical power is the backbone
More informationConfiguring Online Diagnostics
Finding Feature Information, page 1 Information About, page 1 How to Configure Online Diagnostics, page 2 Monitoring and Maintaining Online Diagnostics, page 6 Configuration Examples for Online Diagnostic
More informationPeter Sharp RCDD IBI Group
Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member
More informationNZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers
Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on
More informationWAN/MPLS SLA Fault Reporting
WAN/MPLS SLA Fault Reporting How to report a fault to us Call: 0 550 - Option, Option 5 Email: fixedlinefaults@onecom.co.uk We ll need the below information to log your fault: Company name and your name
More informationData Communications. Connecting Devices
Data Communications Connecting Devices Connecting Devices Networks do not normally operate in isolation. They are connected to one another or to the Internet. To connect LANs, or segments of LANs, we use
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationLevel 1 Interconnection Services at MIX Annex A Technical and Organizational Specifications
Level 1 Interconnection Services at MIX Annex A Technical and Organizational Specifications Page 1 of 8 DOCUMENT CODE : MIX-109E VERSION : 3.0 ENGLISH TRANSLATION DEPARTMENT : BOARD OF DIRECTORS STATUS
More informationA network is two or more computers, or other electronic devices, connected together so that they can exchange data.
Computer Networks What is a Network? A network is two or more computers, or other electronic devices, connected together so that they can exchange data. For example; a network allows computers to share
More informationMinnesota No-Fault Arbitration A Guide to the AAA s New Online Scheduling System Effective June 1, 2018
Minnesota No-Fault Arbitration A Guide to the AAA s New Online Scheduling System Effective June 1, 2018 Table of Contents Introduction... 2 Platform... 2 Types of Online Calendars... 2 Per Case Calendars...
More informationSenior Technical Consultant
Senior Technical Consultant Department Service Department Reporting to Service Manager Our Company Wanstor is an IT Solutions Company celebrating their 16 th year in business. The company has grown year
More informationApplications & Tools. Configuration Examples for SIMATIC S7-400H with PROFINET. SIMATIC S7-400H as of V6.0. Application Description January 2013
Cover Configuration Examples for SIMATIC S7-400H with PROFINET SIMATIC S7-400H as of V6.0 Application Description January 2013 Applications & Tools Answers for industry. Siemens Industry Online Support
More informationIT 341 Fall 2017 Syllabus. Department of Information Sciences and Technology Volgenau School of Engineering George Mason University
Department of Information Sciences and Technology Volgenau School of Engineering George Mason University Fall 2017 IT 341 Data Communications and Networking Principles Syllabus (Revised 08/14/2017) Section
More informationChapter 9 Introduction to Networks
Chapter 9 Introduction to Networks 9.1 Uses of a network Networks are used in many situations. We can see networks in places like offices, airports and factories. In fact we use networks in many situations
More informationModule 16: Distributed System Structures. Operating System Concepts 8 th Edition,
Module 16: Distributed System Structures, Silberschatz, Galvin and Gagne 2009 Chapter 16: Distributed System Structures Motivation Types of Network-Based Operating Systems Network Structure Network Topology
More informationDiscussion of GPON technology application in communication engineering Zhongbo Feng
2nd International Conference on Electronics, Network and Computer Engineering (ICENCE 2016) Discussion of GPON technology application in communication engineering Zhongbo Feng School of Physics and Electronic
More informationSCS. PoE Technology. - Milind Tamhane Vice President Manufacturing D-Link (India) Limited D-Link (I) Ltd. All rights reserved.
SCS PoE Technology - Milind Tamhane Vice President Manufacturing D-Link (India) Limited Introduction Power over Ethernet (PoE) is a revolutionary technology that integrates data and power on standard Ethernet
More informationFig. 1 Voice and data growth
Modern society is continually making new demands on telecommunications. In the foreseeable future, for example, it will have to be possible to access great volumes of data and process them anywhere and
More informationExcel Power Distribution
www.excel-networking.com Excel Power Distribution Section 7 In this Section: Pages Power Distribution Units 154 Efficiency Measurements 154 Excel Modular PDU Range 155 Excel Standard PDUs 156 Excel Intelligent
More informationComparison Of Network Topologies For Optical Fiber Communication
Comparison Of Network Topologies For Optical Fiber Communication Mr. Bhupesh Bhatia Department of Electronics and Communication, Ms. Ashima Bhatnagar Bhatia Department of Computer Science, Guru Prem Sukh
More informationThis course prepares candidates for the CompTIA Network+ examination (2018 Objectives) N
CompTIA Network+ (Exam N10-007) Course Description: CompTIA Network+ is the first certification IT professionals specializing in network administration and support should earn. Network+ is aimed at IT
More informationDiagnosing Network Connectivity Problems
CHAPTER 6 Diagnosing Network Connectivity Problems A common network problem is loss of IP connectivity. This scenario takes you through one example, guiding you through each action and interpreting specific
More informationLab Subnetting Network Topologies (Instructor Version)
(Instructor Version) Instructor Note: Red font color or Gray highlights indicate text that appears in the instructor copy only. Objectives Parts 1 to 5, for each network topology: Determine the number
More informationQUALITY OF SERVICE AND THE EFFECTS OF DATA ENCRYPTION ON VSAT NETWORKS (GOVERNMENT NETWORKS)
QUALITY OF SERVICE AND THE EFFECTS OF DATA ENCRYPTION ON VSAT NETWORKS (GOVERNMENT NETWORKS) Bruno VO VAN, Updated: June 2006 Page 1 de 6 SUMMARY 1 PREAMBLE....3 2 TECHNICAL CRITERIA...3 2.1 QUALITY TO
More informationBob Warden. IP Metering and the Smart Grid WAN Revolution October 27, 2008
Bob Warden IP Metering and the Smart Grid WAN Revolution October 27, 2008 Creating a Digital Grid A Smart Grid is the foundation for a next-generation utility: The central nervous system." A single NETWORK
More informationList of Abbreviations
IPv6 over xdsl List of Abbreviations Asynchronous Transfer Mode BB-RAR Broadband Remote Access Router DHCP Dynamic Host Configuration Protocol DSL Digital Subscriber Line DSLAM DSL Access Multiplexer NAT
More informationUNIT OUTLINE. Network Engineering 304. Mr Iain Murray. Department of Electrical and Computer Engineering Curtin Engineering
305682 Network Engineering 304 Mr Iain Murray Department of Electrical and Computer Engineering Curtin Engineering UNIT OUTLINE Semester 2 2009 CRICOS (Perth - 00301J) (Sydney - 02637B) Table of Contents
More informationADC KRONE. Data Centre Design Considerations. TrueNet Engineered for Uptime
ADC KRONE Data Centre Design Considerations Data Centre Building Layout Data centre design should follow set rules Data Centre Logical Layout Data Centre Zones There are four basic designs for cabling
More informationIntroduction to Computer Networks INTRODUCTION TO COMPUTER NETWORKS
INTRODUCTION TO COMPUTER NETWORKS Computer Networks Computer network connects two or more autonomous computers. The computers can be geographically located anywhere. LAN, MAN & WAN Network in small geographical
More informationTrying to save power and putting Gigabit to the edge
Trying to save power and putting Gigabit to the edge Simon Palmer Systems Development Officer at Coleg Sir Gar (Carmarthenshire College) simon.palmer@colegsirgar.ac.uk Me Interest in Green issues Saving
More informationRoom Booking Instructions
Contents How to use the Room Booking system 1 Accessing the Room Booking system... 1 Making a Room Booking... 2 Viewing or Cancelling a Room Booking... 6 How to use the Room Booking system This guide is
More informationECM-1220 User s Manual
1 ECM-1220 User s Manual Table of Contents ECM-1220 User s Manual...1 Table of Contents...1 Introduction / How It Works...2 Safety...4 Quick Start...5 Verifying / Changing Settings...6 Installation...8
More information289H LSS Installation & Operations Manual Overview
289H LSS Installation & Operations Manual Overview Chapter 1 INTRODUCTION This manual explains the procedures for installing and operating the 289H Loop Surveillance System (LSS). It addresses both new
More informationiscsi Technology Brief Storage Area Network using Gbit Ethernet The iscsi Standard
iscsi Technology Brief Storage Area Network using Gbit Ethernet The iscsi Standard On February 11 th 2003, the Internet Engineering Task Force (IETF) ratified the iscsi standard. The IETF was made up of
More informationListing Space & Serviced Office Gotthardstrasse 26, 6300 Zug
Listing Space & Serviced Office Gotthardstrasse 26, 6300 Zug Agenda 1 2 3 4 Zug a global small town The Lakeside Business Center Offices & working spaces Services 2016 Lakeside Business Center - Listing
More informationApplication Note. Data Center Standards and Layouts
Application Note Data Center Standards and Layouts 1. Data Center Standards In earlier times, a room in which one or more servers, a telephone system and active network components were located was often
More informationCOMPUTER NETWORKING. By: Dr. Noor Dayana Abd Halim
COMPUTER NETWORKING By: Dr. Noor Dayana Abd Halim Defining Computer Network Computer network is a collection of computers and other hardware devices so that network users can share hardware, software,
More informationSilicon Valley Power Data Center Program Rebate Application
Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account
More informationBCS THE CHARTERED INSTITUTE FOR IT BCS HIGHER EDUCATION QUALIFICATIONS BCS Level 5 Diploma in IT COMPUTER NETWORKS APRIL 2015 EXAMINERS REPORT
BCS THE CHARTERED INSTITUTE FOR IT BCS HIGHER EDUCATION QUALIFICATIONS BCS Level 5 Diploma in IT COMPUTER NETWORKS APRIL 2015 EXAMINERS REPORT General Comments The performance in this session is arguably
More informationProvisioning: Configuring QoS for IP Telephony
CHAPTER 7 In an Architecture for Voice, Video, and Integrated Data (AVVID) network, you must configure QoS for IP telephony to ensure voice quality. The following topics provide information about the need
More informationLinchPin. Managed Service For IP VPN Networks. Web Site Telephone
LinchPin Managed Service For IP VPN Networks Web Site www.linchpinnetworks.co.uk Email info@linchpinnetworks.co.uk Telephone 01284 830 841 Introduction The LinchPin CPE Managed Service for IP VPN Networks
More informationPART IV. Internetworking Using TCP/IP
PART IV Internetworking Using TCP/IP Internet architecture, addressing, binding, encapsulation, and protocols in the TCP/IP suite Chapters 20 Internetworking: Concepts, Architecture, and Protocols 21 IP:
More informationAll configuration in this document refers to the EZ Setup section.
Management Access Configuring the HAR11 first requires connecting to its Web Interface. To do this, connect a PC to the LAN port using a straight-thru Ethernet cable. Configure the PC and launch the web
More informationEXECUTIVE SUMMARY. Our Pedigree
LORDS VIEW INDUSTRIAL PARK TECHNOLOGY OVERVIEW 2013 EXECUTIVE SUMMARY As part of the commitment from the developer to provide only the latest and most exciting services, the developer, together with IT
More informationSpecial Provision No. 683S27 June 2017
GATEWAY ROUTERS - Item No. Special Provision No. 683S27 June 2017 1. SCOPE This Special Provision covers the requirements for the installation of Gateway Routers with integrated digital subscriber line
More informationFt Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work
Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive
More informationChart recorder. DS 400 mobile Affordable, mobile chart recorder. Flow Pressure / Vacuum Temperature Moisture / Dew point Optional third-party sensors
DS 400 mobile Affordable, mobile chart recorder Flow Pressure / Vacuum Temperature Moisture / Dew point Optional third-party s Internal rechargeable Li-Ion batteries, approx. 8 h continous operation Easy
More informationBUILDING AUTOMATION OF THE FUTURE
BUILDING AUTOMATION OF THE FUTURE BUILDING AUTOMATION OF THE FUTURE Building automation over IP: With its revolutionary Smart Building concept, MICROSENS enables building automation at low cost. Because,
More informationEthernet DIA SLA Fault Reporting
Ethernet DIA SLA Fault Reporting How to report a fault to us Call: 0 550 - Option, Option Email: fixedlinefaults@onecom.co.uk We ll need the below information to log your fault: Company name and your name
More informationConfiguring UDLD. Understanding UDLD CHAPTER
CHAPTER 9 This chapter describes how to configure the UniDirectional Link Detection (UDLD) protocol. Release 12.2(33)SXI4 and later releases support fast UDLD, which provides faster detection times. For
More informationECE 333: Introduction to Communication Networks Fall 2001
ECE : Introduction to Communication Networks Fall 00 Lecture : Routing and Addressing I Introduction to Routing/Addressing Lectures 9- described the main components of point-to-point networks, i.e. multiplexed
More informationE-Seminar. Storage Networking. Internet Technology Solution Seminar
E-Seminar Storage Networking Internet Technology Solution Seminar Storage Networking Internet Technology Solution Seminar 3 Welcome 4 Objectives 5 Storage Solution Requirements 6 Storage Networking Concepts
More informationLow Profile Hub. User Manual
16 + 2 Low Profile Hub User Manual 1 Contents One Introduction 2 Two Installation 3 Front Panel Connecting Ports LEDs Three Configuration and Installation Guidelines 5 Hub/Network Configuration Ports and
More informationSyllabus Revised 08/21/17
Department of Information Sciences and Technology Volgenau School of Engineering George Mason University Fall 2017 IT 445 Advanced Networking Principles II Syllabus Revised 08/21/17 Instructor: Pouyan
More informationJewish Federation of Metropolitan Chicago. Author DP 3/23/2010 5/17/2010 2/6/2012 Reviewer Approver Publisher
VIRTUALL EVENT MANAGEMENT SYSTEM EVENT MANAGEMENT SYSTEM TRAINING RELEASE 2. 0 Jewish Federation of Metropolitan Chicago 30 South Wells Chicago, IL 60606 Jewish Federation of Metropolitan Chicago Rev 1
More information