Westell. Breaker Panel Technical Practice NPDRP1114
|
|
- Scarlett Martin
- 5 years ago
- Views:
Transcription
1 REV F F June 29, 2017 Westell Breaker Panel Technical Practice NPDRP1114 FEATURES DIN rail panel accepts up to 6 DIN rail devices (one surge and 5 breakers) Specific configuration of breakers is determined by the user This panel typically operates at output current determined by the breakers installed Single 1.75 mounting height (single panel space) Steel metal chassis. Mounting brackets are supplied for 1 & 1-3/4 spacing and are universal for 19 and 23 racks, with flush mounting options Ground bonding terminations provided that will accept two hole lugs Breakers and surge suppressors are ordered separately UL Recognized
2 1. GENERAL DESCRIPTION 1.1. The NPDRP1114 Breaker Panel provides up to 5 circuits for the distribution of AC power to equipment. Each of the 5 circuits is protected by a breaker located on the panel's faceplate. The bus is protected by an overvoltage surge protector. The panel is wired in the field by the user for complete flexibility in determining the number of distributions and the number of feeds, within the limit of the 5 breaker positions The power is distributed to the load side equipment through breakers. Each circuit is available for installer connection at the rear of the panel These Breaker Panels are made from steel that s painted off-white. This single rack height panel is shipped with universal brackets (1 & 1-3/4 spacing) that will fit both 19" and 23" wide racks and use only one 1.75" panel space. 2. APPLICATION 2.1. The NPDRP1114 Breaker Panels are designed to be used in the distribution of AC power. They are rack mount panels that can provide AC power to 5 different circuits. Breakers and surge suppressors are ordered separately, consult factory. 2.2 The NPDRP family breaker panels are suitable for installation as part of a Common Bonding Network (CBN, bonded to the equipment rack rails via the rack mounting screws). As well, this family of breaker panels is suitable for restricted access locations in Network Telecommunications Facilities and OSP. 3. INSTALLATION Please read completely before beginning. WARNING: Installation and service should only be performed by an experienced Installer (service person) familiar with AC power distribution systems. An electrician is recommended when working with AC circuits. This equipment is intended to be installed in RESTRICTED ACCESS LOCATIONS by TRAINED SERVICE PERSONNEL ONLY. damage is found, file a claim immediately with the courier, and notify the Customer Service Department Once the panel is unpacked, verify that there are three mounting brackets. The bracket with the vertical slot is used on both 1 and 1-3/4 spacing. There will be two brackets with horizontal slots, these will fit 1 or 1-3/4 spacing. All three brackets are universal for 19 and 23 rack mount spacing (see figure 3.2.1) and can be mounted so the panel can be installed for a flush mounting at front or at rear. Adjust the position and orientation of the correct mounting brackets on the breaker panel, such that it will fit the rack you wish to mount the panel in Mount the panel on the equipment rack using the thread forming #12-24 rack mounting screws and tooth lock washers provided. WARNING: For safety reasons all wiring should be done with the power source removed (when possible). 19" Mounting Position Figure " Mounting Position 3.4. CHASSIS GROUND; For safety reasons, the chassis should be electrically connected to the rack ground. From step 3.3. the panel should already be ground to the rack via the #12-24 thread forming rack screws and outside tooth lock washers. In addition to grounding via the mounting brackets, it is recommended you ground the chassis using a ground cable and the two #10 Studs (on 5/8 centers) and locks on back of chassis (#10 bolt torque; 25 IN-LB). Consult your internal practice or local electric code for AWG sizes. Grounding lugs are not included Unpack and inspect the Breaker Panel for possible damage incurred during shipping. If 2
3 4. SPECIFICATIONS 4.1. Voltage 120 VAC 4.2. Dimensions 1¾ H, 17 W, 3 D (excluding brackets) 4.3. Rack Mounting 19 and 23 Racks for 1 or 1-3/4 Panel Spaces 4.4. Weight Appx 3 Lbs 4.5. Operating Temp. -40 to +65 C (-40 to +149 F) 4.6. Color Off White Compatible Breakers: Square D QOU Series Compatible Surge Suppressors: Transector I 2 R SA Series TVS AC Data DRM Series 5. TECHNICAL SERVICES 5.1 If technical or customer assistance is required, contact Westell by calling or using one of the following options: Voice: (800) global_support@westell.com For additional information about Westell, visit the Westell World Wide Web site at 6. WARRANTY & REPAIRS 6.1 Westell warrants this product to be free of defects at the time of shipment. Westell also warrants this product to be fully functional for the time period specified by the terms and conditions governing the sale of the product. Any attempt to repair or modify the equipment by anyone other than an authorized Westell representative will void the warranty. Ordering Options: NPDRP1114 BR15A240QOU BR30A240QOU BR60A240QOU-2 BRTVS120VAC Blank Din Rail Panel with cover and brackets. Breaker, 15A, 240VAC, 1-Pole Breaker, 30A, 240VAC, 1-Pole Breaker, 60A, 240VAC, 2-Pole Transient voltage suppressor for 120VAC Transient voltage suppressor BRTVS240VAC for 240VAC Additional breaker values are available through Westell or Square D. Contact Technical Services for more information. 6.2 Westell will repair or replace any defective Westell equipment without cost during the warranty period if the unit is defective for any reason other than abuse, improper use, or improper installation. To return defective equipment, first request a Return Material Authorization (RMA) number from Westell by calling or ing (Customer Service) at the address below. Once an RMA number is obtained, return the defective unit (freight prepaid), along with a brief problem description, to the address we will provide to you when you contact us. rgmdept@westell.com Voice: (800) Replacements will be shipped in the fastest manner consistent with the urgency of the situation. Westell will continue to repair or replace faulty equipment beyond the warranty period for a nominal charge. Contact Westell for details. 3
4 4 Noran Tel
5 SURGE PROTECTOR DANGER HIGH VOLTAGE Personnel Only Certified Risk of Electrical Shock Noran Tel 5
Breaker Panel Technical Practice NPDRP1114
030-000218 REV E 1114-03E January 30, 2013 Westell Breaker Panel Technical Practice NPDRP1114 FEATURES DIN rail panel accepts up to 6 DIN rail devices (one surge and 5 breakers) Specific configuration
More information28-Position 23 Rack Mounting Model RM23-20X
001-0048 Rev.00 28-Position 23 Rack Mounting Model RM23-20X SECTION PAGE # 1. GENERAL... 1 2. APPLICATIONS... 1 3. INSTALLATION... 1 4. TESTING... 3 5. CUSTOMER SERVICES... 3 6. WARRANTY AND REPAIRS...
More informationSpecifications, Installation, and Operating Instructions
Specifications, Installation, and Operating Instructions Model: Power Vantage AC Panel Protector CAUTION: The installation of a surge protection device () must be done by qualified electrical personnel.
More informationSurge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL
LoadTrack LTL Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA TEL: 800-647-1911 www.tpssurge.com LOADTRACK LTL INSTALLATION, OPERATION AND
More informationVirtualEdge VEUP-30 Universal Panel, with 3 LGX-Type Positions and 12 Keystone Coupler Positions
Section VEU-P30-20A Equipment Issue A 030-101690 Rev. B, December 2008 VirtualEdge VEUP-30 Universal Panel, with 3 LGX-Type Positions and 12 Keystone Coupler Positions PART # PAGE # 1. GENERAL....................................
More informationVirtualEdge VEUP-BNC6P DS3 Protection Panel
Section VEU-PBN-C6P-20A Equipment Issue A 030-101700 Rev. B, April 2010 VirtualEdge VEUP-BNC6P DS3 Protection Panel PART # PAGE # 1. GENERAL.................................... 1 2. INSTALLATION...............................
More informationWestell DBMA Position DS3 Mounting Assembly
ection DBM-A20-024-201 Equipment Issue 1 030-101669 Rev. B, August 2010 Westell DBMA200-24 24-Position D3 Mounting Assembly CLEI* Code: NCM2YY0DRA CONTENT PAGE # 1. GENERAL....................................
More informationPower Supply (48Vdc, 2.5A)
Telecommunications Group Section 855-180-201 Equipment Issue 1 Fourth Printing, September 2006 8551-80 Power Supply (48Vdc, 2.5A) Compliant with UL Standard 60950, Second Edition* CONTENTS PAGE Part 1.
More informationSVP110 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL
SVP110 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL REVISION: 01/03/03 COPYRIGHT (c) 1995-2000 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE The SVP110 SURGE VOLTAGE PROTECTOR is
More informationInstalling the Cisco MDS 9020 Fabric Switch
CHAPTER 2 This chapter describes how to install the Cisco MDS 9020 Fabric Switch and its components, and it includes the following information: Pre-Installation, page 2-2 Installing the Switch in a Cabinet
More informationJunos WebApp Secure 5.0 Hardware Guide
Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a
More informationWIRESPEED ADSL MODEM (MODEL 2000) User Guide
WIRESPEED ADSL MODEM (MODEL 2000) User Guide Copyright 2001 Westell, Inc. All rights reserved. 030-300187 Rev. A Printed in the United States of America December 2001 CONTENTS 1. PRODUCT DESCRIPTION...
More informationXBDM. 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL BYPASS DISTRIBUTION MODULE
XBDM 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL www.xpcc.com 2013 Xtreme Power Conversion Corporation. All rights reserved. Table of Contents IMPORTANT SAFETY INSTRUCTIONS:... 4 INTRODUCTION...
More informationSpecifications 1 Installation Procedures 2 Wiring Diagrams 3 Installation Checklist 5 Maintenance 5 Warranty Information 6 Material Return Policy 6
CFS Family TITLE PAGE Specifications 1 Installation Procedures 2 Wiring Diagrams 3 Installation Checklist 5 Maintenance 5 Warranty Information 6 Material Return Policy 6 Part Number Model Description A70-00-5006
More informationDual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02
Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02 User Manual 1.1 Overview Telect s 80A, -48 Vdc Low-Voltage Disconnect (LVD) panel is a rack-mounted component with coil-operated contactors. These
More informationOPERATING MANUAL LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES
PRICE: $25.00 LOW-VOLTAGE DISCONNECT PANELS LVD400 & LVD600 SERIES www.unipowertelecom.com Manual No. LVD-201-2 8/29/01/L46Man 2001 UNIPOWER Corp. All Rights Reserved UNIPOWER Telecom, Division of UNIPOWER
More informationto 48V DC Power Supply
Telecommunications Group Section 855-080-201 Equipment Issue 1 Second Printing, July 2007 8550-80 24 to 48V DC Power Supply Compliant with UL Standard 60950, Second Edition* CONTENTS PAGE Part 1. GENERAL.............................................................................
More informationPower Supply Installation
Power Supply Module Overview, on page Installation Guidelines, on page 4 Installing or Replacing an AC Power Supply, on page 6 Installing a DC Power Supply, on page 7 Finding the Power Supply Module Serial
More informationOmnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual
Omnitron Systems Technology, Inc. 1 iconverter 19-Module Managed Power Chassis User s Manual 27 Mauchly, #201, Irvine, CA 92618 Phone: (949) 250-6510; Fax: (949) 250-6514 2 Omnitron Systems Technology,
More informationTotal Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400
Total Protection Solutions SurgeTrack Series: 080, 120, 160, 240, 300 and 400 Surge Protective Devices Installation, Operation and Maintenance Manual SURGETRACK INSTALLATION, OPERATION AND MAINTENANCE
More informationUser s Guide. POWERVAR Single Phase Power Conditioners
POWERVAR Single Phase Power Conditioners User s Guide Industrial Conditioners GPI Series B Conditioners GPI Series 1 Conditioners 2-15 kva Single Phase Conditioners GPI Series 1 Conditioners RoHS Compliant
More informationMIC-3001/8. 3U/4U CompactPCI. Enclosure for Rackmounting
MIC-3001/8 3U/4U CompactPCI Enclosure for Rackmounting Copyright Notice This document is copyrighted, 1999. All rights are reserved. The original manufacturer reserves the right to make improvements to
More informationInstallation Instructions & User Manual
Installation Instructions & User Manual ZONEMASTER PRO AC Panel Transient Voltage Surge Suppressors The Wiremold Company In US: 60 Woodlawn Street, West Hartford, CT 06110 800-621-0049 FAX 860-232-2062
More informationSVP48 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL
SVP48 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL REVISION: 3/03 COPYRIGHT (c) 1995-2003 CAMPBELL SCIENTIFIC, INC. This is a blank page. Warranty and Assistance The SVP48 SURGE VOLTAGE PROTECTOR is warranted
More informationVirtualEdge VELGX 90 Media Panel, with Nine LGX Type Positions, Front Tray, and Top Cover
Section VEL GX9 20A Equipment Issue A 030 300323 Rev. A, June 2014 VirtualEdge VELGX 90 Media Panel, with Nine LGX Type Positions, Front Tray, and Top Cover PART # PAGE # 1. GENERAL... 1 2. INSTALLATION...
More informationInstallation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2
Supersedes 6/2015 Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2 XXCFXXX10-DIN Contents Description Page 1.0 Setup...2 1.1 Before Installation...2 1.2 Installation...3 For AC Applications...3
More informationINSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES
INSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-4B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual
More informationAlways "On" UPS Systems Inc. USER MANUAL
Always "On" UPS Systems Inc. SMART HOME PROTECTOR USER MANUAL Bldg 1-150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext. 451, Fax: (250) 491-9775, Email: sales@alwaysonups.com Web
More informationINSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES
INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-5B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual
More informationObtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx
Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining
More informationUPS READY POWER DISTRIBUTION ASSEMBLY
UPS READY POWER DISTRIBUTION ASSEMBLY FOR TRAFFIC CABINETS with LED Signals INSTALLATION & OPERATOR S MANUAL VERSION 1.2 1 Note The instructions contained in this manual are not intended to cover all of
More informationOwner s Manual. Isolate. Restore. Inspire! Power Conditioners Audio / Video Power Isolation Units Rack Mount / Consumer Series
Owner s Manual 19 Pro Series Rack Mount (RK) Faceplate Isolate. 17 Consumer Series (C) Faceplate Available in Black (B) and Silver (S) Colours Restore. Power Conditioners Audio / Video Power Isolation
More informationMFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company
MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System User s Manual D-M-E Company D-M-E Company MFA-0801 & MFA-1201 Page 1 Copyright D-M-E Company 1995. All rights reserved. D-M-E
More informationInstallation Instructions & User Manual POWERWARE TVSS ZONESENTINEL. AC Panel Transient Voltage Surge Suppressors
Installation Instructions & User Manual POWERWARE TVSS ZONESENTINEL AC Panel Transient Voltage Surge Suppressors INTRODUCTION This document explains how to install the Powerware TVSS ZoneSentinel AC Panel
More informationLiebert MicroPOD 230V
AC Power For Business-Critical Continuity Liebert MicroPOD 230V User Manual TABLE OF CONTENTS 1.0 IMPORTANT SAFETY INSTRUCTIONS...........................................1 2.0 GLOSSARY OF SYMBOLS..................................................2
More informationInstallation and Operation
Installation and Operation G-Type Rack Power Filter G50NETB2 G50NETB-20A2 120 Vac 15 A 20 A General Information Product Features The APC AV G-Type G50NETB2 and G50NETB-20A2 Rack Power Filters protect high-performance
More informationINSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES
INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-7B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual
More informationMIC-3001/8. 3U/4U CompactPCI Enclosure for Rack Mounting. User Manual
MIC-3001/8 3U/4U CompactPCI Enclosure for Rack Mounting User Manual Copyright The documentation and the software included with this product are copyrighted 2004 by Advantech Co., Ltd. All rights are reserved.
More informationUSER MANUAL. MODEL 552 Series. High Speed Telco Surge Protectors. SALES OFFICE (301) TECHNICAL SUPPORT (301)
USER MANUAL MODEL 552 Series High Speed Telco Surge Protectors C E R T I F I E D An ISO-9001 Certified Company Part# 07M552-E Rev. G Revised 01/27/10 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301)
More informationSurge Protective Devices. STV25K Series. Instruction Manual
Surge Protective Devices STV25K Series Instruction Manual Contents 1.0 Installation & Operation... 4 1.1 Environment... 4 1.2 Mechanical Dimensions... 4 1.3 DIN Rail Mounting... 5 1.4 Supplemental Enclosures...
More informationOPERATING MANUAL PDUAC3U SERIES AC POWER DISTRIBUTION UNITS
AC POWER DISTRIBUTIO UITS www.unipowerco.com Manual o. PDUAC3U-3 2017 UIPOWER LLC All Rights Reserved UIPOWER LLC 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA sales@unipowerco.com orth America:
More informationCOOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN
Voltage Regulators MN225074EN Effective March 2017 Supersedes January 2012 (S225-40-7) RS-485 digital communications accessory board installation and operation instructions COOPER POWER SERIES DISCLAIMER
More informationUSER MANUAL MODEL 505M-CHC. Surge Protected DB-25 to RJ-45 Modular Adapter
USER MANUAL MODEL 505M-CHC Surge Protected DB-25 to RJ-45 Modular Adapter C E R T I F I E D An ISO-9001 Certified Company Part# 07M505MCHC-A Doc# 074281U, Rev. B Revised 1/21/08 SALES OFFICE (301) 975-1000
More informationiconverter 2-Module Power Chassis
iconverter 2-Module Power Chassis User Manual 38 Tesla, Irvine, CA 92618 USA Phone: (949) 250-6510; Fax: (949) 250-6514 Page 1 Warning The operating description in this Instruction Manual is for use by
More informationTotal Home Surge Protection for Point-of-Entry. FirstSurge TM. User Manual - Canada (English)
Total Home Surge Protection for Point-of-Entry FirstSurge TM User Manual - Canada (English) www.siemens.ca/surge Introduction Thank you for choosing the Siemens FirstSurge Residential Surge Protective
More informationRE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007
RE-82 RACK MOUNT DIMMER 8 X 2400Watts OWNERS MANUAL Revision 2.4 11/29/2007 Page 2 of 8 RE-82 CONTROL PANEL DESCRIPTION The RE-82 is an 8 channel dimmer with a maximum capacity of 2,400 watts per channel
More informationINSTRUCTION MANUAL. SGB20(D) Transient Protection System. June Copyright 2008 Campbell Scientific (Canada)Corp.
INSTRUCTION MANUAL SGB20(D) Transient Protection System June 2008 Copyright 2008 Campbell Scientific (Canada)Corp. WARRANTY AND ASSISTANCE This equipment is warranted by CAMPBELL SCIENTIFIC (CANADA) CORP.
More informationInstallation Manual. 12 Volt Power Supplies. 18-Port. 9-Port RET18PT RET9PT
12 Volt Power Supplies Installation Manual 9-Port RET9PT 18-Port RET18PT INTRODUCTION Congratulations! The RET9PT 9-Port 12V Power Supply is the perfect solution for your larger security installations.
More informationVRp Three-Phase Precision AC Voltage Regulator
VRp-22500-0338 Three-Phase Precision AC Voltage Regulator INSTALLATION INSTRUCTIONS Inspection and Unpacking Please inspect the wooden crate for obvious shipping damage. Some crates contain up to six (6)
More informationInstallation of the POTS splitter card requires the following steps: Determining the cables you need. Installing the POTS splitter chassis
5910 High Density Lifeline POTS Splitter Installation Instructions Document Number 5910-A2-GZ40-00 May 2005 About the 5910 POTS Splitter The 5910 is a double-density POTS splitter that separates the (Digital
More informationHUBBCOM GSC3000/GSC4000 Flush-Mount Smart Controller Quick Installation Guide
G A I - T R O N I C S C O R P O R A T I O N A H U B B E L L C O M P A N Y HUBBCOM GSC3000/GSC4000 Flush-Mount Smart Controller Quick Installation Guide Important Safety Instructions Read, follow, and retain
More informationRackmount Keyboard Installation Instructions. Revision A A-0000
Rackmount Keyboard Installation Instructions Revision A 22000200A-0000 WARRANTY The following is an abbreviated version of warranty policy for keyboard products. For a complete warranty statement, contact
More informationMODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT
MODEL INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SELECTABLE SIRENTONE-MULTI VOLT INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SELECTABLE SIRENTONE-MULTI VOLT A. GENERAL. The Federal Model is a solid-state
More informationUSER MANUAL. MODEL 56X Series 564, 566, 568, 562. Hub Surge Protectors
USER MANUAL MODEL 56X Series 564, 566, 568, 562 Hub Surge Protectors C E R T I F I E D An ISO-9001 Certified Company Part# 07M560A Doc# 074270U, Rev. B Revised 01/21/08 SALES OFFICE (301) 975-1000 TECHNICAL
More informationINSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)
Surge-Trap STZ-R series Surge Protective Device (SPD) Danger Hazard of Electrical Shock, Explosion or Arc Flash Only qualified licensed electricians should install or service SPDs Verify that all power
More informationModel 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit
More informationPANEL MOUNT INTERCOMS
PANEL MOUNT INTERCOMS INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS AD-26P, AD-27P, AD-56P, and AD-57P Address all communications and shipments to: Electrical Products Division 2645 Federal Signal Drive
More informationDCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies
DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies M51A Option: Isolated Analog Programming Manual Power Supplies Elgar Electronics Corporation 9250 Brown Deer Road San Diego, CA 92121-2294 1-800-73ELGAR
More informationEATON Transformer Module
www.eaton.com EATON Module Quick Start Standard Features When used with standard system, EATON Module provides isolated and Step-down 0/08/0 V AC outputs. Multiple Output receptacles: 0/08/0 V AC. 86-86000-0
More informationMFP5G, MFP8G, & MFP12G D-M-E Smart Series Mainframes
MFP5G, MFP8G, & MFP12G D-M-E Smart Series Mainframes User s Manual D-M-E Company D-M-E Company MFP5G, MFP8G, MFP12G Page 1 Copyright D-M-E Company 1999. All rights reserved. D-M-E Company products are
More informationTOT Series Manual. North American and International Models - without optional faceplate. Receptacle Panel of International Models, CE model shown
TOT Series Manual North American and International Models - without optional faceplate Receptacle Panel of International Models, CE model shown North American Models Table of Content 1. Important Safety
More informationLINE VOLTAGE TESTER CT101 USER S MANUAL. Please read this manual carefully and thoroughly before using this product.
LINE VOLTAGE TESTER USER S MANUAL CT101 Please read this manual carefully and thoroughly before using this product. KEY FEATURES Visual indication of AC or DC voltage Easy to use approved Safe for CAT
More informationQuick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport
PTX5000 Packet Transport Router Quick Start September 2017 Part Number: 530-066788 Revision 01 This document describes how to install the Juniper Networks PTX5000 Packet Transport Router. Contents Quick
More information810D Series FAA L-810 Double Obstruction Light Installation Manual
810D Series FAA L-810 Double Obstruction Light Installation Manual 2562426A REV. A 708 Printed in U.S.A. i Contents Safety Message to Installers, Users, and Maintenance Personnel... 1 Overview... 2 Unpacking
More informationCMSA-100 Manual. Cinema Media Server Automation
CMSA-100 Manual Cinema Media Server Automation 181 Bonetti Drive San Luis Obispo, CA 93401-7397 USA Phone: +1 805 549 0161 Fax: +1 805 549 0163 www.uslinc.com Table of Contents 1. Safety Notice... 3 2.
More informationSAVE THESE INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFEGUARDS! When using electrical equipment, basic safety precautions should always be
More informationVIP-480AL IP One-Way Horn
Issue 1 VIP-480AL IP One-Way Horn Issue 1 INTRODUCTION The VIP-480AL IP One-way Horn provides for one-way communication when used in a Valcom VoIP based intercom/paging system. SPECIFICATIONS Access Methods
More informationInstallation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch
Installation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch PD52 PD52S & PD52DCS PD53-100 te: The PD52S & PD52DCS are provided with LED lights. The GREEN LIGHTS indicate Shore Power
More informationINSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES
INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-6B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual
More informationDANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.
Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,
More informationSurge Protective Devices Installation, Operation and Maintenance Manual. ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400
ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400 Surge Protective Devices Installation, Operation and Maintenance Manual TEL: 800-853-8265 www.innosyspower.com SERVICETRACK ST INSTALLATION,
More informationInstalling the Cisco SFS 3504 Server Switch
CHAPTER 3 This chapter describes how to mount your Cisco SFS 3504 Server Switch on a rack, boot the Cisco SFS 3504 Server Switch, and configure basic services. For advanced configuration information, see
More informationhp uninterruptible power system r12000 xr models installation instructions
hp uninterruptible power system r000 xr models installation instructions Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer
More informationBasketball Shot Clock Set LX2180 Manual
Basketball Shot Clock Set LX2180 Manual 72 Industrial Boulevard Wrightsville, GA 31096 Phone: (800) 445-7843 Fax: (800) 864-0212 www.electro-mech.com LX2180 Revision 5 February 8, 2013 Table of Contents
More informationTitan Media Cart. Installation and Operation Manual
Titan Media Cart Installation and Operation Manual Table of Contents INTRODUCTION SERVICE AND SUPPORT... 1 PRODUCT RETURNS... 1 UNPACKING... 1 TITAN SINGLE MEDIA CART... 2 TITAN DUAL MEDIA CART... 2 BEFORE
More informationSeries Amp Pad Mount Quick Connect Input and Output Power Panels
Series 300 2000-4000 Amp Pad Mount Quick Connect Input and Output Power Panels DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.
More informationSite Preparation CHAPTER
CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies
More informationCisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2
Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2 Cisco CRS 3-Phase AC Power Distribution Unit 2 Revised: November 18, 2016,
More informationUSER MANUAL MODEL 503P & 503PC. Parallel Surge Protectors. SALES OFFICE (301) TECHNICAL SUPPORT (301)
USER MANUAL MODEL 503P & 503PC Parallel Surge Protectors C E R T I F I E D An ISO-9001 Certified Company Part# 07M503P-C Doc# 074201U Rev. D Revised 1/21/08 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT
More informationSECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.
SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:
More informationG5 PDU Installation Guide
G5 PDU Installation Guide 1 Contents Before You Begin... 3 Overview... 3 Important Safety Information... 3 Required Tools... 5 Section 1 Introduction... 6 Classification Overview... 6 Features... 7 Form
More informationPDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL
PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL 1 IMPORTANT SAFETY INSTRUCTION READ FIRST This symbol, whenever it appears, alerts you to the presence of uninsulated dangerous voltage inside the enclosure-voltage
More informationSquare D Homeline Load Centers and Circuit Breakers. Engineered for value
Square D Homeline Load Centers and Circuit Breakers Engineered for value TM From the Square D brand you know and trust, Homeline Load Centers are engineered for value, reliability, and innovation. The
More informationTOT Series Manual. North American CE and UK Models. CE Models. UK Models. North American Models
TOT Series Manual North American CE and UK Models CE Models UK Models North American Models Table of Content 1. Important Safety Instructions 2. Description Shipping Carton & Packing Material Placement
More informationMIC-3002A Series. 3U 6-slot CompactPCI Enclosures with Rear I/O and 6" LCD. User Manual
MIC-3002A Series 3U 6-slot CompactPCI Enclosures with Rear I/O and 6" LCD User Manual Copyright The documentation and the software included with this product are copyrighted 2005 by Advantech Co., Ltd.
More informationSection 4 Ground-Fault Protection Devices
Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that
More informationUser Guide. DMXSM-H18 Splitter. DMXSM-H81 Merger. Document Release Aug Revision B
User Guide DMXSM-H18 Splitter DMXSM-H81 Merger Document Release Aug. 2008 Revision B Warranty Leviton Manufacturing Co Inc. warrants this device to be free of material and workmanship defects for a period
More informationF O R U M S E R I E S
R E V.1 F O R U M S E R I E S INSTRUCTION BOOKLET MODELS FORUM 8, 10, 12, 15, 8M, 15M & FORUM 12SUB & 15SUB F O R T H E C L O S E S T A P P R O A C H T O T H E O R I G I N A L S O U N D TABLE OF CONTENTS
More informationEthernet Test Access Panel (ETAP) User Manual
Ethernet Test Access Panel (ETAP) User Manual Content Page INTRODUCTION............................................................................. 1 Revision History........................................................................
More informationMeasure Ø-N, Ø-Ø, Ø-Gnd with voltmeter to confirm application voltage prior to installation.
Product No. 99-600-91 Rev. B Page 1 of 8 MCG Surge Protection Model 160MXT Installation Instructions Important Warranty Information MCG surge protectors are designed to work at specific voltages and configurations,
More informationC-POWER AC AUTOMATIC CONTROL
Issue 1 Print 1 C-POWER AC AUTOMATIC CONTROL INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model: 93 ACMC100I A Charles Industries, Ltd. All rights reserved. Printed in the United States of America. Issue
More informationSERVICE MANUAL MODEL SSC-301-F (FORMERLY 301-FS) MODEL BLC-301-F (FORMERLY 301-F)
SSC-301-F OR BLC-301-F-ISSUE4.0 SERVICE MANUAL FOR MODEL SSC-301-F (FORMERLY 301-FS) OR MODEL BLC-301-F (FORMERLY 301-F) CHARGE-A-CALL TELEPHONE Serving the Telephone Industry Since 1930 Communication
More informationInstallation RA5112-C-16A-C20. Basic Rack Power Distribution Unit
Installation RA5112-C-16A-C20 Basic Rack Power Distribution Unit Contents Before You Begin........................1 Safety and grounding information..........1 How to Install the Rack PDU...............2
More informationVIP-804 QUAD ENHANCED NETWORK AUDIO PORT
ISSUE 6 VIP-804 QUAD ENHANCED NETWORK AUDIO PORT INTRODUCTION The VIP-804 Quad Enhanced Network Audio Port enables voice access to four zones of one-way paging over an IP network, allowing page zones to
More informationRTD SAMPLER OPERATOR S MANUAL
OPERATOR S MANUAL Contents 1 Product Overview...1.1 Specifications... 1.1 2 Installation & Operation...2.1 Unpacking the RTD Sampler... 2.1 Main Board and Expansion Board... 2.1 Mounting the RTD Sampler...
More informationModel DMX8DIM Installation and Operations Manual
Model DMX8DIM Installation and Operations Manual Doug Fleenor Design, Inc. 396 Corbett Canyon Road Arroyo Grande, CA 93420 (805) 481-9599 Voice and FAX Manual revision June, 2018 Product description The
More informationINSTALLATION INSTRUCTIONS FOR
INSTALLATION INSTRUCTIONS FOR MODEL 3314 LED www.sportablescoreboards.com 1 Table of Contents DESCRIPTION... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:... 3 INSTRUCTIONS FOR REPORTING
More informationInstallation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series
Installation Manual APEX Series Silicon and MOV Panel Protection APEX Series APEX Series Installation Guide 2 Table of Contents Mechanical Installation 3 Table One - Application Rating 3 Figure 1 - Mounting
More informationAVR Manual. Isolate. Restore. Inspire! Audio / Video Power Isolation Units with Automatic Voltage Regulation. 19 Pro Series Rack Mount (RM) Faceplate
AVR Manual Audio / Video Power Isolation Units with Automatic Voltage Regulation 19 Pro Series Rack Mount (RM) Faceplate Isolate. Restore. Inspire! 17 Consumer Series (CS) Faceplate Available in Black
More informationInfinity 1U 19 Converter Shelf Models: J L217 - Individual +24V Inputs Bulk -48V Output L218 - Individual -48V Input Bulk+24V Output
GE Critical Power Quick Start Guide Infinity 1U 19 Converter Shelf Models: J5964803 L217 - Individual +24V Inputs Bulk -48V Output L218 - Individual -48V Input Bulk+24V Output Edge Controller This shelf
More information