1 Flow sensor SFAH Operating instructions (Original instructions) Festo AG & Co. KG Ruiter Straße Esslingen Germany [87539] 2.2 General safety information Only use the product in its original condition, without any unauthorised modifications. Only use the product if it is in an excellent technical status. Take into consideration the operating conditions at the location of use. Comply with all applicable national and international regulations. Do not use the product in combination with inflammable, caustic, vapour-emitting or other hazardous media. Check the operating medium to determine compatibility with the materials it contacts. Observe the specifications on the product labelling. Remove all transport packaging. Recycle packaging material. 3 Service Contact the regional Festo contact if you have technical uestions 4 Accessories Accessories 5 Product overview 5. Design Flow sensor SFAH... English About this document This document describes the use of the above-mentioned product. Certain aspects of use are described in other documents and must be observed Further applicable documents.. Further applicable documents For all available product documentation Device description file (IODD) Document Description of flow sensor SFAH Fig. Table of contents Functional description, installation, commissioning, maintenance, description of the IO-Link parameters, technical data A-key 2 button 3 B-key 4 Pneumatic port Identification on the product Fig. 5 Pneumatic port Identification on the product 6 Plug for electrical connection 7 Display 2 Safety 2. Use for intended purpose The SFAH is intended for monitoring the flow of gaseous media in piping systems or terminals in the industry sector. Chapter 4 Technical data. Warning Depending on the functioning of the machine/system, manipulation of signal states may cause serious personal injury. that if the switching status of the s is modified in mode, the new status will be effective immediately. Enable the password protection option (security code) to prevent accidental alteration by an unauthorised third party Chapter 8.5, section Setting the security code. Warning Use of the product in combination with prohibited media can result in personal injury. Do not use the product in conjunction with inflammable gases, corrosive gases, oxygen etc. The product is intended only for measuring the flow of media, which are listed as suitable in Chapter 4 Technical data. Attention Condensation water, oil mist, foreign matter and other dirt in the compressed air can damage the product and cause incorrect measurements and malfunctions. Make sure that the specified air uality class is maintained for the operating medium Chapter 4 Technical data. 5.2 Product variants and type code Characteristic Value Description Type SFAH Flow sensor Flow measuring range -. Max.. l/min -.5 Max..5 l/min - Max. l/min -5 Max. 5 l/min - Max. l/min -5 Max. 5 l/min - Max. l/min -2 Max. 2 l/min Flow input U Unidirectional B Bidirectional Pneumatic connection -Q4 Push-in connector 4 mm -Q6 Push-in connector 6 mm -Q8 Push-in connector 8 mm -G8 G/8 -G4 G/4 Thread type None F Female thread let orientation S Straight AR Angled, alignable Electrical -PNLK PNP or NPN or IO-Link Electrical 2 -PNVBA PNP or NPN or V or 5 V or 4 2 ma Electrical connection -L Plug L -M8 Plug M8 Certificate None +T Test report Fig. 2

2 6 Function The SFAH measures the flow rate (standard flow rate, mass flow rate) with the help of a thermal procedure. Measurements are carried out using a micromechanical sensor element with a following electronic evaluation unit. Connection to higher-level systems is provided by 2 switching s, an analogue and/or an IO-Link interface. The s can be configured as appropriate to the application. The switching s can be configured to monitor a threshold value, signal range or signal change. The s can be set as PNP or NPN and normally open (NO) or normally closed (NC). Via the IO-Link interface, process values can be read out and parameters changed and transmitted to additional devices. Through integration of the flow rate, a volume/load signal can be calculated and via a pulse as well as a cumulated measurement value via IO-Link. SP2 Ref SP 2 t.obs d.sp 3 Reference value Ref is determined 2 Measured value deviates by [d.sp] from the reference value 3 Monitoring range Fig. 7 The parameters [SP], [SP2], [t.obs] and [d.sp] can be configured by the user. The greater [t.obs] is set, the more stable the signal must be to establish the reference value Ref. Fig. 3 SFAH signal structure 6. Operating statuses Operating status Function RUN mode Basic status after the operating voltage is applied Display of the current measured value Display of the selected inputs and s Switchover between the measured variables of flow rate and volume/load SHOW mode Display of current settings of the switching s and analogue Display and resetting of the minimum and maximum values Display of the average flow rate measurement EDIT mode Setting of parameters TEACH mode Acceptance of the current measured value to determine switching points Fig. 4 Operating statuses of the SFAH 6.2 Switching s Switching functions Threshold value comparator in the flow measurement for A or B Function NO (normally open) NC (normally closed) Switching function: switching point (SP) TEACH mode: 2 Teach points (TP, TP2) SP SP = ½ (TP+TP2) TP TP2 TP SP TP2 Fig. 5 Threshold value comparator: setting of switching point [SP] and hysteresis [] Window comparator in the flow measurement for A or B Function NO (normally open) NC (normally closed) Switching function: 2 switching points (SP.Lo, SP.Hi) TEACH mode ) : 2 Teach points (TP, TP2) TP = SP.Lo, TP2 = SP.Hi TP=SP.Lo TP2=SP.Hi TP=SP.Lo TP2=SP.Hi ) SP.Lo = smaller value, SP.Hi = larger value, independent of the Teach seuence Fig. 6 Window comparator: setting of switching points [SP.Lo] and [SP.Hi] and hysteresis [] Auto difference monitoring d_ _ This function permits monitoring of a signal value for constancy. If the applied signal is constant in the range between [SP] and [SP2], the reference signal Ref is automatically determined. The result is a switching operation at the and signalises the start of the signal monitoring procedure. If the signal remains in the monitoring range [d.sp] around Ref, the signal is stable. When the monitoring range is left, the switches back. Function NO (normally open) NC (normally closed) Switching function: d.sp 2 switching points (SP, SP2) d.sp for setting the valid work range switching point (d.sp) for determination of the monitoring area SP Ref SP2 SP Ref SP2 TEACH mode ) : 2 Teach points (TP, TP2) TP = SP, TP2 = SP2 ) SP = smaller signal value, SP2 = larger signal value, independent of the Teach seuence Fig. 8 Change in colour A red colour change can be set in the display for A and B, dependent on the switching status. As a result, the switching status of the sensor can be identified over a large distance. The colour change reacts both on A and on B, depending on the setting. Parameter Meaning blue Display is always blue; the colour change function is switched off. R.On Display is red if the switching is set (High =) or blue if the switching is not set. (Low = ) R.OFF Display is red when the switching is not set. ( Low = ) or blue when the switching is set. ( High = ) Fig. 9 Colour change on the display Volume/load pulse A threshold value SP for the volume or load can be set in the accumulated volume/ load measurement. If the configured threshold value is reached, a switching impulse is emitted at the Pulse ( Fig. 3) for an adjustable period of time. With each switching impulse, the volume/load measurement is started again ( Fig. ). Volume/load pulse with accumulated volume measurement Setting NO (normally open) Setting NC (normally closed) Fig. V SP Pulse t t V SP t t Pulse

3 i 6.3 Offset synchronisation Ensure that operating pressure is applied to the SFAH but there is no flow rate, so the offset synchronisation is without error. H-rail mounting. Mount H-rail mounting on the SFAH. Tightening torue.5 Nm. 2. Hang H-rail mounting in the H-rail. 3. Press the H-rail mounting in the direction of the arrow until the mounting slide catches 2 The sensor has the possibility to make an offset synchronisation for the zero point. This synchronisation affects the display and all s. The offset synchronisation is possible only for Zero Adjust = ON. As a result, the zero range hiding is no longer active. For bidirectional sensor variants, the function Zero Adjust [Z.Adj] is preset to [ON]. As a result, visible offset errors can be set to zero through a Zero Adjust Teach procedure (offset synchronisation). A reuirement for this is that the measured value in the Teach procedure lies in the range +/-3% FS with reference to the original factory adjustment. Wall mounting. Screw wall mounting to SFAH. Tightening torue.5 Nm. 2. Mount wall mounting. Fig Switchover of standard condition for volume values REF / Cond The represented flow rate units can be related to different standard conditions. It is possible to switch between the following standard conditions. In the menu navigation on the display, the corresponding standard is determined by selecting the reference temperature. Fig. 5 REF / Cond Off 5 C 2 C Standard DIN 343 ISO 2533 ISO 6358 Air pressure (absolute) [bar] Temperature [ C] 5 2 Air humidity [%] 65 Status information Option Does not light up Lights up Lights up Correction factor, measurement range limit value Fig. that the calibration of the SFAH refers back to the physical standard conditions in accordance with DIN 343. If a standard other than DIN 343 is selected, the specified measurement range (±% FS) changes in value by the factor specified in Table 9. This change is visualised in the display through [Option]. Changing the reference standard only adjusts the display on the sensor. If necessary, the effect on the nominal measurement range of the respective sensor must also be considered when evaluating the analogue. 7 Installation Installation and commissioning is to be carried out only by ualified personnel. 7. Mechanical Any mounting position is possible but can have an influence on measurement precision ( Chapter 4, Nominal conditions). Fasten the SFAH as follows: Plate mounting Secure the SFAH to the plate by using screws of suitable length. Tightening torue:.5 Nm Front panel mounting kit. Mount H-rail mounting on the SFAH. Tightening torue.5 Nm. 2. Mount accompanying hexagon head screw on the H-rail mounting 3. Push panel frame through cut-out (62 mm x 24 mm +/-. mm). 4. Push sensor through panel frame so that all 4 remaining hooks engage. 5. Push clamping element over hexagon head screw. 6. Attach sensor with accompanying knurled nut. Tightening torue.3 Nm Fig Pneumatic For unidirectional sensors SFAH- U-, the flow is supplied at connection and withdrawn from connection 2. The direction of flow is indicated on the sensor by an arrow. Only for unidirectional types: If the tubing connection of the SFAH is incorrect, the measurement values are presented with the negative minus sign and lie outside the specified measurement range. For the bidirectional sensors SFAH- B-, the flow can be supplied at connection or connection 2. To have a sign that correctly represents the flow direction in the display, the flow direction can be set in the menu and also represented in the sub-display. Connect the sensor as follows: Mount the two hoses to connection and connection 2 Identification on the product. 7.3 Inlet situation The specified accuracies shown in the technical data of the sensor are achieved when the conditions for the inlet section from Fig. 7 are complied with on the sensor. Accessories: Lateral plate mounting. Mount H-rail mounting on the SFAH. Tightening torue.5 Nm. 2. Mount H-rail mounting with washers and M4 screws, tightening torue.5 Nm Fig. 2 Fig. 3 Min. internal diameter of the inlet path Execution of the inlet section Measuring range (e.g. QS4) Any Permitted ) ± 2 % 2) Not permitted 3) 4 (e.g. QS6) Straight 4 (e.g. QS6) Angle directly on sensor Permitted ) ± % 2) 4 (e.g. QS6) Angle at distance ± % 2) of 5-8 cm 6 (e.g. QS8) Any Permitted ) ) Accuracy as specified in the technical data Chapter 4 Technical data 2) Deviation from the specified accuracy. 3) Operation possible. But deviations of more than 2 % must be expected. Fig. 7 Effect of the inlet conditions and connection sizes on the specified accuracy

4 7.4 Electrical Warning Electric voltage Injury caused by electric shock, damage to machine and to system Only use power sources which guarantee reliable electrical isolation of the operating voltage in accordance with IEC/DIN EN Observe the general reuirements for PELV circuits in accordance with IEC/DIN EN Use switched-mode power supplies, which ensure reliable separation in accordance with EN 695/VDE 85. Long signal lines reduce the resistance to interference. Comply with the maximum permissible I/O signal line length of 3 m, 2 m in IO-Link operation The binary s at pin 2 and pin 4 can be wired as PNP or NPN connections as needed. Configure binary s according to your wiring Setting special menu [SPEC] section. Connect the SFAH as follows: Pin Colour ) Allocation Plug L Brown (BN) Operating voltage +24 V DC 2 Black (BK) Switching A, volume/load pulse or IO-Link (C/Q line) 3 White (WH) Switching B or analogue 4 Blue (BU) V ) Colours apply for connecting cables NEBS-L... Fig. 8 Pin Colour ) Allocation Plug M8 x Brown (BN) Operating voltage +24 V 2 White (WH) Switching B or analogue 3 Blue (BU) V 4 Black (BK) Switching A, volume/load pulse or IO-Link (C/Q line) ) Colours apply for connecting cables NEBU- M8... Fig. 9 Circuit diagrams SFAH- -L Fig. 2 8 Commissioning 8. LCD display 2 Main display (e. g. measured value) 2 Status information Example for LCD display put display [A] [A] Meaning SFAH- -M8 3 Lower display (e.g. unit) 4 put display Switching A selected (flashes with active IO-Link.) Switching A set 3 4 Example for LCD display Meaning put display [B] Switching B selected [B] Switching B set [Pulse] Illuminates with reference to the pulse signal at the volume/loadpulse In the RUN mode, displays which signal is allocated to pin 4 (M8) or pin 2 (L) [Anlg] Illuminates with reference to the analogue (flow rate) In the RUN mode, displays which signal is allocated to pin 2 (M8) or pin 3 (L) Status information / signal indicator [LOCK] Security code activated [Spec] Special menu selected [Option] Illuminates when parameters having a special influence on the measured value indicator have been changed (compared to the factory setting): reference condition (standard), gas Fig. 2 Example for LCD display Meaning Main display Lower display Measured value indicator and unit in the RUN mode [.53] [L.Min] Measured value indicator (here: negative value) and unit Menu for the switching s (A and B) [] [bin] [A] / [B]: menu for the switching s (binary) _ [] Threshold value comparator _ _ [] Window comparator d_ _ [] Auto difference monitoring [8.] [SP] Switchpoint value [.8] [SP.Hi] Value of upper switching point [6.45] [SP.Lo] Value of lower switching point [.5] [] Hysteresis value [8] [t.obs] / [MSEC] Time interval for determination of the signal change, which is used to establish the reference value. [.25] [d.sp] Threshold value for determination of the monitoring area [NO] [LOGC] Switching characteristics: [NO] = normally open contact, [NC] = normally closed contact [blue] [COLR] Display colour Extreme values (only SHOW mode) [.64] [MIN] Minimum measured value since switch-on or the last reset [8.5] [MAX] Maximum measured value since switch-on or the last reset [2.8] [AVER] Average of the flow measurement, filter time constants Additional settings (pulse at the ) [] [PULS] Duration of the volume or load pulse at the Analogue [] [ANLG] menu for the analogue [...] [] / [V] put function of the analogue [] [In.Hi] / [%] Scaling of the analogue to the final value of the flow measuring range in percent of FS [-] [In.Lo] / [%] Scaling of the analogue to the start value of the flow measuring range in percent of FS Menu for device settings (Spec) [] [Menu] [Spec]: menu for additional settings [6] [Filt] / [MSEC] Value of the filter time constant for the measurement signal [L.Min] [ Unit] Display unit for flow measurement [ C] [REF] / [Cond] Reference standard for gas volume [Air] [GAS] Selection of the operating medium [->2] [] / [Path] Selection of the flow direction from Port to 2 or vice versa (only for bidirectionally calibrated product variant) [ON] [Z.Adj] Offset synchronisation for display, switching and analogue [Unit] [Sub.d] Settings of the lower display in RUN mode: selected unit or switching point of A or bar graph or gas or flow direction [4] [Eco] / [SEC] Economy mode: period after which the display background lighting is switched off [PNP] [bin] / [] Shift of the switching s (binary) between PNP and NPN [Flow] [bin] / [Pin4] Shift of binary switching or pulse. Pin4 with M8 variant, Pin2 with L variant [bin] [] / [Pin2] Shift of binary switching or analogue to pin 2 in M8 variant, Pin3 with L variant [OFF] [Code] Activation and determination of the security code [OFF] [MASt] Activation of the IO-Link. master function for replication of parameters Fig. 22

5 8.2 Switch on sensor (RUN mode) Switch on the operating voltage. Current measured value is displayed. The sensor is in the basic status (RUN mode). The basic status can be reached from other modes by: Pressing button for 3 seconds Expiration of a monitoring time (timeout) 8.3 Shifting of measured value indicator The measured value indicator is shifted by pressing key A to flow rate measurement or key B to volume measurement. 8.4 Displaying parameters (SHOW mode) Switching A or volume pulse Press the A key twice. The first parameter set is displayed. [] flashing for A or [SP] for Pulse. The subseuent parameters can be displayed by repeatedly pressing the A key ( Fig. 23 ). The averaged flow rate value [AVER] is displayed at the end. Switching B or analogue Anlg Press B-key. The first parameter set is displayed. [] flashes with B or [] with Anlg ( Fig. 23). The subseuent parameters are displayed by repeatedly pressing the B-key ( Fig. 23). For bidirectional product variant -.B-, the flow direction [Path] is displayed at the end. _ or A at _ _ Measured value indicator (RUN mode) VOL/MASS A A B B or d_ _ Pulse at B at See A Anlg at SP SP.Lo SP.lo SP In.Hi SP.Hi SP.Hi In.Lo t.obs PULS LOGC COLR button A or B key MIN MAX AVER d.sp Double-click the A or B key ) Not for G.Min flow unit 2) Only for bidirectional product variant Fig. 23 LOGC Reset Reset 3) Filter Time constant Measured value indicator (RUN mode) REF Cond GAS Path 3) Selectable values: 256, 52, 24 ms ) 2) 8.5 Enter the security code (EDIT mode). Press the button. The EDIT mode is active. If the security code is activated, the parameter entry option is blocked: [Lock] flashes. 2. Enter security code set with A or B key. 3. Press the button briefly. [A] flashes. The parameter entry option is unblocked. 8.6 Configuring switching (EDIT mode) The process is the same for configuring the switching s for [A] and [B]. In the following, the process is described using the switching A. Menu structure LEERER MERKER.. Press the button briefly. [] appears. [A] flashes. 2. Press the button briefly. [] flashes. 3. Select switching function _I or _I I_ or d_i I_ with A or B key. 4. Press the button briefly. The set value is saved. The next adjustable parameter is shown. 5. Set the parameter with A or B key. 6. Repeat points 4 and 5 until all parameters are set. Switching functions Chapter Change device settings (EDIT mode). Press the button briefly. [] appears. [A] flashes. 2. With A or B key, select special menu [Spec]. [Spec] flashes. 3. Press the button briefly. [Filt] / [MSEC] flashes. 4. Set the parameter with A or B key. 5. Press the button briefly. The set value is saved The next adjustable parameter is shown. 6. Repeat points 4 and 5 until all parameters are set. 8.8 Set volume pulse. Press the button briefly. [] appears. [A] flashes. 2. Select [Puls] with the A-key or B-key. 3. Press the button briefly. [SP] / [ Volume unit ] flashes. 4. Set the parameter with A or B key. 5. Press the button briefly. The set value is saved. The next adjustable parameter is shown. 6. Repeat points 4 and 5 until all parameters are set. 8.9 Set analogue (EDIT mode). Press the button briefly. [] appears. [A] flashes. 2. Select [Anlg] with the A-key or B-key. 3. Press the button briefly. [] / [V] flashes. 4. Set the parameter with A or B key. 5. Press the button briefly. The set value is saved. The next adjustable parameter is shown. 6. Repeat points 4 and 5 until all parameters are set. 8. Replicating parameters (EDIT mode) Reuirement: The pre-configured sensor (master sensor) is ready for operation (RUN mode). Master sensor and device sensor have the same design regarding the parameters (same device ID). The master sensor is connected with the device sensor ( Fig. 24). Parameterisation of the device sensor must not be blocked via IO-Link. The device sensor is in an unswitched status (switching PNP, display A off ).

6 Master sensor Fig. 24 Pin allocation for M8 Power supply. Select special menu [Spec] at the master sensor via device settings. 2. Press the button briefly until [MASt] appears. 3. With A or B key, select [ON]. 4. Press the button [REPL] / [RedY] appears. Device sensor 5. Press A- or B-key. [REPL] / [RUN] appears briefly. The parameters are transmitted to the device sensor. [REPL] / [RedY] appears. If an error occurs, an error message appears ( Fig. 26). 6. Repeat point 5 if an additional sensor should be parameterised. 7. Press the button briefly. Switch to the RUN mode. 8. Configure sensor (EDIT mode) Fig. 25 shows the complete menu structure. Some menu options or setting values are not applicable, depending on the product variant and the selected switching function. 8.2 Menu structure (EDIT mode) Messwertanzeige (RUN-Modus) A bin B bin Anlg Puls Spec Menu _ _ _ d_ _ V, 5 V, 4 2 ma SP See tech. data Filt OFF, 2, 4, 8, 6, 32, 64, 24, 248 ms SP SP.Lo SP.Lo - 6 %FS ) In.Hi -8 %FS PULS ms Unit L.Min, L/h, SCFM, SCFh, G.Min 3) SP.Hi SP.Hi - 7 %FS ) In.Lo -...8%FS 2) LOGC NO, NC REF / Cond C, 5 C, 2 C.5 9%FS ) GAS Air, N 2 t.obs ms / Path -> 2, <- 2 4) d.sp.5 2 5%FS ) Z.Adj OFF, ON 5) LOGC NO, NC Sub.d Unit, II II II II, GAS, Path, SP, SP.Lo, SP.Hi, d.sp COLR blue, R.ON, R.OFF Eco di.on, 5,, 2, 4, 8, 6, 32, 64 s bin / PNP, NPN PinX / bin, VOL/MASS 6) PinY / bin, ANLG 7) Code / Lock OFF, 9999 MASt OFF, ON Bold Messwertanzeige (RUN-Modus) = button ) The values refer to the respective measuring range and the selected unit. 2) Default - for bidirectional variant; default for unidirectional variant = A or B key 3) Default L/h for measurement ranges. l/min and.5 l/min; default L/min for all other measurement ranges 4) Menu option only for bidirectional product variant 5) Default OFF for unidirectional; default ON for bidirectional = factory setting 6) For M8 plug: Pin4; for L plug: Pin2 7) For M8 plug: Pin2; for L plug: Pin3 Fig Teach switching points (TEACH mode) The process for Teach is the same for configuring the switching s for A and B. In the following, the process is described using the switching A. The Teach function is only available for flow monitoring. If the security code is activated, the parameter entry option is blocked: [Lock] flashes.. Enter the security code ( Chap. 8.5). 2. Establish switching function in the EDIT mode ( Chap. 8.6). 3. Apply signal value. 4. Press the A key and button. The current signal value will then be adopted as the first Teach point (TP). [t-in] flashes. 5. Apply signal value Press the A-key and button. The current signal value will then be adopted as the first Teach point (TP2). Switch to the RUN mode.

7 There is no timeout in the TEACH mode. The sensor changes to the RUN mode only after the entire teach process is ended. 8.4 Zero point synchronisation (zero adjust) Reuirement: The sensor is ready for operation (RUN mode). [Z.AdJ] is set to on [ON] ( Chap. 8.7). The measured value lies in the range bar ± 3 % FS. Press the A- and B-key and button simultaneously. [OK] appears. The zero point synchronisation was successful. [FAIL] appears. The zero point synchronisation was not successful. Check reuirements. If [Z.AdJ] [OFF] is set for a later time, the device takes over the factory setting calibration values. 9 Operation After the supply voltage is switched on, the SFAH needs a warm-up time of minutes until it achieves the specified accuracy. The flow rate displayed by the SFAH refers to the standard conditions that were set under Options in the special menu. 9. Restoring factory settings (restore) By resetting to factory settings, the current settings are lost. If reuired, make a note of these settings before resetting.. Switch off the operating voltage. 2. Keep the A- and B-keys pressed down simultaneously. 3. Switch on the operating voltage. 4. Additionally press the button. [RSto PArM] appears. All parameters are reset to the factory settings. Maintenance and care. Turn off energy source and compressed air. 2. Clean sensor with non-abrasive cleaning agents. Disassembly. Turn off energy source and compressed air. 2. Separate connections from the sensor. 3. Loosen the mountings. 2 Fault clearance Malfunction Possible cause Remedy No display No operating voltage or impermissible operating voltage Apply permissible operating voltage Electrical connections swapped Connect the device in accordance with the circuit diagram Device defective Replace device Eco mode on Press key or switch off Eco mode Indicator or switching does not react as expected Short circuit or overload at the Eliminate short circuit or overload Incorrect switching point taught Repeat Teach procedure (e.g. at l/min) Incorrect standard condition set for Correct standard condition volumetric flow rate Device defective Replace device Parameter incorrect Reset to factory settings [Er] / [FAIL] ) Device defective Replace device [Er2] / [ASIC] ) Device defective Replace device [Er3] / [SEnS] ) Device defective Replace device [Er9] / [UndR] Below sensing range Stay in sensing range [Er] / [OVER] Sensing range exceeded Stay in sensing range [Er7] / [SUPL] 2) Undervoltage Maintain permissible operating voltage [Er2] / [t.hi] 2) Temperature error Check operating conditions Check ambient temperature Check wiring Replace device [Er2] / [SHRt] 2) Short circuit at A/Puls Eliminate short circuit [Er22] / [SHRt] 2) Short circuit at B Eliminate short circuit Malfunction Possible cause Remedy [Err] / [busy] A/Puls is switched active in the Check device settings device sensor [Err] / [Id] Device ID error, devices do not have the same design When replicating, use sensor with the same type flow rate measurement range (same device ID) [Err] / [COM] IO-Link communication error Check settings of the device sensor Check line ) Display flashes red 2) Display illuminates red Fig Accessories 4 Technical data General information Certification RCM mark CE marking ( Declaration of conformity) in accordance with EU EMC Directive on materials RoHS-compliant Input signal / Measurement element Measured variable Volumetric flow rate, mass flow rate Flow direction Unidirectional, bidirectional Measuring principle Thermal Warm-up time [min] Method of measurement Heat transfer Operating pressure [bar] -.9 Nominal pressure [bar] ; in calibration, the sensors are exhausted to the atmosphere Operating medium Compressed air to ISO 8573-:2 [6:4:4], nitrogen Temperature of medium [ C] 5 Ambient temperature [ C] 5 Nominal conditions for determination of the accuracy specification Operating pressure : bar relative (During calibration, the sensors are vented against the atmosphere) Medium and ambient temperature: 23 C Analogue : voltage with 2k Ohm load Switching : load current in the switched status 5 ma Mounting position: horizontal, display upwards Inflow: Chap. 7.3 Flow measuring range unidirectional and bidirectional -.U- -.5U- -U- -5U- -U- -5U- -U- -2U- Start value [l/min.] End value [l/min.] Flow measuring range bidirectional, additional -.B- -.5B- -B- -5B- -B- -5B- -B- -2B- Start value [l/min.] End value [l/min.] put, general Accuracy of zero point [±%FS] ± Accuracy of span [±%FS] ±2 (±3 with use of the current ) Repetition accuracy [±%FS].2 zero point Repetition accuracy range [±%FS].8 Temperature coefficient of [±%FS/K] Typ..5 (max..3) margin Temperature co-efficient [±%FS/K] Max..5 (typ. ) zero point Pressure influence span [±%FS] Typ. (in the pressure range -.7 bar) ) Position dependency of zero point with vertical installation [±%FS/bar].5 ) In the pressure range -.9 -,7 bar, an additional pressure influence span of typ. ±-4 %FS can be expected.

8 Switching Display/operation Variant Switching 2x PNP or 2x NPN, switchable Switching function Threshold value comparator, window comparator, auto difference monitoring Switching element function N/C contact or N/O contact, switchable Switch-on time [ms] Max. 6 (with FILT=OFF) Switch-off time [ms] Max. 5 (with FILT=OFF) Max. current [ma] Voltage drop [V] Max. Pull-down resistor [ms] PNP: integrated Pull-up resistor [ms] NPN: not integrated (load current of at least 2 ma reuired) Inductive protective circuit Present Analogue Variant -..U- -..B- Flow characteristic curve [l/min.] put characteristic curve [V] All or 5 for voltage put characteristic curve for current [ma] All 4 2 Rise time [ms] All Max. 3 with FILT = OFF Max. load resistance of current [Ohm] All 5 Min. load resistance Voltage [kohm] All 2 put, additional data Short circuit protection Overload protection Electronics Yes Present Operating voltage range DC [V] Idle current [ma] Max. 25 Reverse polarity protection For all electrical connections Setting range, threshold value volume l; sft³; g l; sft³; g l; sft³; g l; sft³; g l; sft³; 9999 g NL; sft³; 9999 g -2 Zero range hiding [%FS] All <.5 (Z.Adj = OFF) 2) The following volumes / load units are permanently assigned to the flow rate units: l/min, l/h - l scft/min, scft/h - scft g/min - g Immissions/emissions Storage temperature [ C] -2 8 Degree of protection IP4 Pressure drop with 6 bar at [mbar] < input and max. Pressure drop with bar at and max. [mbar] < Standard nominal flow rate (6 -> 5 bar) [l/min.] IO-Link Protocol version Device V. Profiles Smart sensor profile Function classes Binary data channel (BDC) Process data variable (PDV) Identification Diagnostics Teach channel Communication mode COM2 (38.4 kbaud) Port class A Process data width IN 3 byte Process data content IN 2 bit BDC (flow rate monitoring) bit BDC (volume monitoring) 4 bit PDV (flow measured value) IODD, IO-Link device description Fig. 27 Electromechanical -M8- -L- Connection type Plug connector Connection technology M8x, A-coded, to LJ EN Number of pins/wires 4 Max. connecting cable length [m] 3 (2 for IO-Link operation) Mechanical Mounting position Any Pneumatic connection Fig. 2, Fig. 7 Product weight [g] Approx. 9 Information on housing materials Reinforced polyamide Materials in contact with medium NBR PA reinforced High-alloy stainless steel Wrought aluminium alloy, anodised Silicon Silicon nitride Epoxide Display/operation Variant Displayable units 2) l/min, l/h, scft/h, g/min, l, scft, g l/min, l/h, scft/min, scft/h, g/min, l, scft, g l/min, scft/min, scft/h, g/min, l, scft, g

Flow sensors SFAB Key features

Flow sensors SFAB Key features Key features At a glance Quick and secure installation thanks to QS fitting Display can be rotated 270 Manifold assembly of the sensor via H-rail or individual assembly via adapter plate for wall mounting

More information

Pressure sensors SPAN

Pressure sensors SPAN Features At a glance Communication interface Convenient design Compact design 30x30 mm Degree of protection IP40 Reduced weight with QS4 Universal pressure measurement Pressure and vacuum 13 pressure measuring

More information

Flow sensors SFAM Key features

Flow sensors SFAM Key features Key features At a glance Threaded mounting of individual device with stabilising zone Can be combined with MS6 or MS9 series service units Illuminated LCD display with blue background and white 9-segment

More information

Pressure sensors SDE1, with display

Pressure sensors SDE1, with display Product range overview Method of measurement Piezoresistive pressure sensor with display Operating voltage Measured variable Pressure measuring range Pneumatic connection Type of mounting Electrical output

More information

Pressure sensors SDE3, with display

Pressure sensors SDE3, with display Pressure sensors SDE3 Key features At a glance SDE3- -M plug version, plug M8x1 and M12x1 SDE3- -FQ, cable with plug Fast H-rail, wall or surface mounting Fast front panel mounting High-contrast, two-colour

More information

Pressure sensors SPAE

Pressure sensors SPAE Key features Function The SPAE is an electronic pressure sensor with piezoresistive pressure measuring cell, integrated signal processing, numerical percentage pressure indicator, control keys and a switching

More information

Pressure sensors SPAW with display

Pressure sensors SPAW with display Key features At a glance 9 pressure ranges from 1 +1 bar up to 0 +100 bar 4-digit LED display, easy to read, robust Protection class IP67 320 rotatable display 1% accuracy, 0.15% repetition accuracy Temperature

More information

Pressure sensors SPAE

Pressure sensors SPAE Key features At a glance Single-button operation 7-segment display Various pneumatic connection options Switching status indication Choice of pressure ranges Function The SPAE is an electronic pressure

More information

Pressure sensors SDE5

Pressure sensors SDE5 q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity qready for dispatch

More information

Pressure sensors SDE5

Pressure sensors SDE5 Key features At a glance SDE5- -M8 Plug version, plug M8x1, 3-pin SDE5- -K Cable version, 2.5 m long, 3-wire Linkable wall bracket with clip-in facility for sensors (included in the scope of delivery)

More information

Pressure sensors SDE1, with display

Pressure sensors SDE1, with display Product range overview Method of measurement Piezoresistive pressure sensor with display Operating voltage Measured variable Pressure measuring range Pneumatic connection Type of mounting Electrical output

More information

Air gap sensors SOPA

Air gap sensors SOPA Product range overview Key features General Lightweight, compact and highly precise, this pneumatic solution offers impressive scope for integration: SOPA features a control module, compressed air regulation,

More information

Pressure transmitters SPTE

Pressure transmitters SPTE Key features At a glance Compact design Very lightweight Various pneumatic connection options Output signal: 0 10 V or 1 5 V Choice of pressure ranges Pneumatic connections Push-in sleeve Push-in connector

More information

Pressure sensors SPAB, with display

Pressure sensors SPAB, with display Key features, product range overview At a glance Variants: Plug M8x1 with electric adapter SASC Plug, square design L1 Cable version with connecting cable NEBS Compact design 30 x 30 mm Multi-coloured,

More information

Positioner CMSX-...-C-U-F1-...

Positioner CMSX-...-C-U-F1-... Positioner CMSX-...-C-U-F-.... CMSX-SE-... (linear) 5 Festo AG & Co. KG Postfach Esslingen Germany +9-0 www.festo.com (en) Operating instructions 80595 0a [80595] aj 9 8 Housing cover Inspection window

More information

IO-Link parameter description

IO-Link parameter description Application Note IO-Link parameter description A brief explanation of the contents - identification - parameter and commands - block parameterization - teach-in - process data - using different pressure

More information

Service unit combinations MSE6, MSE series

Service unit combinations MSE6, MSE series Key features Overview Product description The MSE6-E2M is an intelligent pneumatic service unit for optimising the use of compressed air as an energy medium in industrial automation technology. Equipped

More information

Position transmitter SDAT-MHS e [ ]

Position transmitter SDAT-MHS e [ ] Position transmitter SDAT-MHS en Manual 8068247 1612e [8068249] Translation of the original instructions SDAT-MHS This documentation refers to the following version: From Revision R04. Identification of

More information

Proximity sensors, round design

Proximity sensors, round design Proximity sensors, round design Proximity sensors, round design Product range overview Measuring principle Magnetoinductive Version Type Assembly Switching element function Switch output Electrical connection

More information

Proximity sensors, block design

Proximity sensors, block design Proximity sensors, block design Proximity sensors, block design Product range overview Measuring principle Version Type Mounting Switching element function Switching Electrical connection N/O contact N/C

More information

Pressure sensors SPAN

Pressure sensors SPAN q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity qready for dispatch

More information

IO-Link parameter description

IO-Link parameter description Application Note IO-Link parameter description A brief explanation of the contents - identification - parameter and commands - block parameterization - teach-in - process data - using different pressure

More information

Pressure sensors SPAE

Pressure sensors SPAE Key features At a glance Single-button operation 7-segment display Various pneumatic connection options Switching status indication Choice of pressure ranges Function The SPAE is an electronic pressure

More information

Positioner CMSX-...-C-U-F1-...

Positioner CMSX-...-C-U-F1-... Positioner CMSX-...-C-U-F-.... CMSX-SE-... (linear) Festo AG & Co. KG Postfach Esslingen Germany +9-0 www.festo.com aj 9 8 (en) Operating instructions 8088 09NH [8080] Original: de Positioner CMSX... English

More information

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Standstill monitor A / / 2011 Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II

More information

Air gap sensors SOPA

Air gap sensors SOPA Product range overview Key features General Lightweight, compact and highly precise, this pneumatic solution offers impressive scope for integration: SOPA features a control module, compressed air regulation,

More information

Proximity sensors SME-8, for T-slot Technical data Magnetic reed

Proximity sensors SME-8, for T-slot Technical data Magnetic reed Function e.g. N/O contact, with cable, 3-wire Magnetic reed measuring principle Insertable in the slot lengthwise e.g. N/O contact, with plug, 3-pin SME-8-SL Sturdy thanks to long guides Plug directly

More information

Positioner CMSX-...-C-U-F1-...

Positioner CMSX-...-C-U-F1-... Positioner CMSX-...-C-U-F-... Festo AG & Co. KG Ruiter Straße 8 Esslingen Germany +9-0 www.festo.com Product overview. Function The CMSX digital electropneumatic positioner enables simple and efficient

More information

Proximity sensors SME-8M, for T-slot Technical data Magnetic reed

Proximity sensors SME-8M, for T-slot Technical data Magnetic reed Function e.g., 3-wire, with cable e.g., 3-wire, with plug Magnetic reed measuring principle Insertable in the slot from above, does not protrude over the cylinder profile Cable clip and inscription labels

More information

Sensor boxes SRBC. Festo core product range Covers 80% of your automation tasks

Sensor boxes SRBC. Festo core product range Covers 80% of your automation tasks Sensor boxes SRBC q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity

More information

Position transmitters SDAT-MHS for T-slot

Position transmitters SDAT-MHS for T-slot Key features General Position transmitters are used to provide feedback on piston movement in pneumatic drives. They are situated between simple cylinder switches and expensive displacement encoders, both

More information

Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx SB0524

Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx SB0524 Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx SB0524 UK 80256992 / 00 11 / 2016 Contents 1 Preliminary note...4 1.1 Symbols used...4 2 Safety instructions...4 3 Functions and features...5

More information

Vacuum generator. Operating instructions b [ ]

Vacuum generator. Operating instructions b [ ] Vacuum generator OVEM- -LK en Operating instructions 8079732 2017-10b [8079734] Original instructions OVEM- -LK-DE Identification of hazards and instructions on how to prevent them: Warning Hazards that

More information

Sensor boxes SRBG Key features

Sensor boxes SRBG Key features Key features Function SRBG sensor boxes are the compact solution when it comes to electrical feedback signals and monitoring the position of process valves which are actuated with pneumatic quarter turn

More information

Fork light barriers SOOF

Fork light barriers SOOF Product range overview Method of measurement Size Min. object diameter Max. switching frequency Switching output Type of light Page/ Internet [mm] [mm] [Hz] Metal light barrier SOOF-M- -C30 30x35 0.5 4,000

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

SM9000. Magnetic-inductive flow meter. Made in Germany

SM9000. Magnetic-inductive flow meter. Made in Germany Made in Germany Application Application totaliser function; empty pipe detection; for industrial applications Installation connection to pipe by means of an adapter Media conductive liquids; water; hydrous

More information

TSE. Functional Description. Order Code TSE HA /2010. Electrical Pressure Switch N D. p max up to 400 bar (5801 PSI)

TSE. Functional Description. Order Code TSE HA /2010. Electrical Pressure Switch N D. p max up to 400 bar (5801 PSI) Electrical Pressure Switch TSE HA 90 /010 p max up to 400 bar (5801 PSI) Electronic pressure switch TSE To monitor the pressure in the circuit and the signalisation switching after reaching pre-set pressure

More information

Electronic pressure switch with display Model PSD-4

Electronic pressure switch with display Model PSD-4 Electronic pressure measurement Electronic pressure switch with display Model PSD-4 WIKA data sheet PE 81.86 Applications Machine tools Hydraulics and pneumatics Pumps and compressors Special-purpose machine

More information

Flow sensors SFAW Key features

Flow sensors SFAW Key features Key features General The SFAW is intended for use in measuring and monitoring the flow, volume and temperature of liquid media in piping or in terminals in industry. The flow velocity is recorded in accordance

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Technical data. General specifications. factory setting: 125 ms Memory Non-volatile memory Write cycles Indicators/operating means

Technical data. General specifications. factory setting: 125 ms Memory Non-volatile memory Write cycles Indicators/operating means Model Number Single head system Features IO-link interface for service and process data Programmable via DTM with PACTWARE Switch output and analog output Selectable sound lobe width Synchronization options

More information

Pressure transmitters SPTE

Pressure transmitters SPTE Key features At a glance Compact design Very lightweight Various pneumatic connection options Output signal: 0 10 V or 1 5 V Choice of pressure ranges Pneumatic connections Push-in sleeve Push-in connector

More information

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ]

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ] Compact performance Brief description CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8 English 8080251 2017-11e [8080244] Translation of the original instructions Documentation on the

More information

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ]

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ] System CPX-E IO-Link master module CPX-E-4IOL- Description Protocol IO-Link Function Parameterisation 877 27-7 [879] IO-Link master module CPX-E-4IOL- Original instructions CPX-E-4IOL- -E N IO-Link is

More information

Datasheet DE DB_EN_DE44_LCD Rev. ST4-C 07/17. Digital 2-channel differential pressure switch/transmitter with colour-change LCD * *

Datasheet DE DB_EN_DE44_LCD Rev. ST4-C 07/17. Digital 2-channel differential pressure switch/transmitter with colour-change LCD * * 09005318 DB_EN_DE44_LCD Rev. ST4-C 07/17 *09005318* Datasheet DE44 Digital 2-channel differential pressure switch/transmitter with colour-change LCD 1 Product and functional description FISCHER Mess- und

More information

Pressure sensor SPAN. Festo AG & Co. KG. Ruiter Straße Esslingen Germany

Pressure sensor SPAN. Festo AG & Co. KG. Ruiter Straße Esslingen Germany Pressure sensor SPAN Festo AG & Co. KG Ruiter Straße 8 73734 Esslingen Germany +49 7 347- www.festo.com Oerating instructions 8366 7-a [8368] Translation of the original instructions Pressure sensor SPAN...

More information

Operating instructions Memory plug E /02 11/2011

Operating instructions Memory plug E /02 11/2011 Operating instructions Memory plug E30398 UK 704930/02 11/2011 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Terms used...3 2 Safety instructions...4 3 Factory setting...4 4 Functions and features...5

More information

Dimensions. Model Number. Electrical connection emitter. Features. Electrical connection receiver. Product information. Pinout OBE12M-R100-S2EP-IO-V31

Dimensions. Model Number. Electrical connection emitter. Features. Electrical connection receiver. Product information. Pinout OBE12M-R100-S2EP-IO-V31 OBEM-R00-SEP-IO-V Dimensions. 8.7. 7..9. M (x).. ø... 0 9.9 7. 7. Release date: 08-06-08 :0 Date of issue: 08-06-08 80998_eng.xml Model Number OBEM-R00-SEP-IO-V Thru-beam sensor with -pin, M8 x connector

More information

Digital electropneumatic positioner

Digital electropneumatic positioner Digital electropneumatic positioner Type 879 can be combined with Compact metal housing Graphic display with backlight Easy start-up Comprehensive range of additional software functions Profibus DPV1 (optional)

More information

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ]

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ] CPX-Terminal Brief description CPX analogue I/O modules CPX-2AE CPX-4AE CPX-2AA English 8080173 2017-11e [8080175] Translation of the original instructions Documentation on the product For all available

More information

Proximity sensors, block-shaped Product range overview

Proximity sensors, block-shaped Product range overview Proximity sensors, block-shaped Product range overview Measuring Version Type Assembly Switching element function Switch output Electricalconnection principle N/C contact Cable Plug Magneto- Operating

More information

Operating instructions Electronic pressure sensor. PN72xx PN73xx PN76xx / / 2016

Operating instructions Electronic pressure sensor. PN72xx PN73xx PN76xx / / 2016 Operating instructions Electronic pressure sensor PN72xx PN73xx PN76xx 8002464 / 00 07 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...4 3 Functions and features...5 3. Applications...5

More information

Motor controllers CMMO-ST

Motor controllers CMMO-ST q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity qready for dispatch

More information

Operating instructions Pressure sensor. PN78xx / / 2010

Operating instructions Pressure sensor. PN78xx / / 2010 Operating instructions Pressure sensor PN78xx UK 704788 / 00 05 / 2010 Contents 1 Preliminary note3 1.1 Symbols used 3 2 Safety instructions 3 3 Functions and features 4 4 Function 5 4.1 Processing of

More information

Controller CMXH-ST2 Key features

Controller CMXH-ST2 Key features Key features At a glance The controller controls two servo motors which drive an H-shaped rotating toothed belt. The toothed belt moves a slide, whose position is calculated by the controller from the

More information

Operating instructions Electronic pressure sensor. PM205x /01 09/2011

Operating instructions Electronic pressure sensor. PM205x /01 09/2011 Operating instructions Electronic pressure sensor PM205x 706071/01 09/2011 Contents 1 Preliminary note...3 1.1 Symbols used...3 2 Safety instructions...3 3 Functions and features...4 3.1 Applications...4

More information

Operating instructions Electronic temperature sensor TN /00 04/2011

Operating instructions Electronic temperature sensor TN /00 04/2011 Operating instructions Electronic temperature sensor TN7531 UK 704772/00 04/2011 Contents 1 Preliminary note3 1.1 ymbols used 3 2 afety instructions 3 3 Functions and features 4 4 Function 4 4.1 Communication,

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

3-step setting 2. 2-Color Display High-Precision Digital Pressure Switch. ZSE30A(F)/ISE30A Series. Added vacuum range.

3-step setting 2. 2-Color Display High-Precision Digital Pressure Switch. ZSE30A(F)/ISE30A Series. Added vacuum range. 2-Color Display High-Precision Digital Pressure Switch ZSE3A(F)/E3A Series RoHS Can copy to up to 1 switches simultaneously. setting labor Minimizing ZSE3 E3 ZSE4 E4 The settings of the master sensor can

More information

Level sensor Stainless steel version Model RLT-1000, for industrial applications

Level sensor Stainless steel version Model RLT-1000, for industrial applications Level measurement Level sensor Stainless steel version Model RLT-1000, for industrial applications WIKA data sheet LM 50.02 Applications Level measurement of liquids in machine building Control and monitoring

More information

IO-Link parameter description

IO-Link parameter description Application Note IO-Link parameter description A brief explanation of the contents - identification - parameter and commands - block parameterization - teach-in - process data - using different pressure

More information

Operating instructions Electronic temperature sensor TN7511

Operating instructions Electronic temperature sensor TN7511 Operating instructions Electronic temperature sensor TN7511 80231575 / 00 11 / 2016 Contents 1 Safety instructions...3 2 Functions and features...3 3 Function...3 3.1 Switching function...4 3.2 Display

More information

Operating instructions Electronic pressure sensor PN7xxx

Operating instructions Electronic pressure sensor PN7xxx Operating instructions Electronic pressure sensor PN7xxx 8000579 / 00 08 / 208 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...4 3 Functions and features...5 3. Applications...5

More information

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2 Electronic pressure measurement Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2 WIKA data sheet PE 81.53 Applications Test bench construction Water jet

More information

THERMASGARD TM 65. Immersion screw-in duct temperature measuring transducer, calibratable, with multi-range switching and active output TECHNICAL DATA

THERMASGARD TM 65. Immersion screw-in duct temperature measuring transducer, calibratable, with multi-range switching and active output TECHNICAL DATA Patented quality product (Immersion sensor patent no. DE 10 2012 017 500.0) Calibratable temperature measuring transducer THERMASGARD with eight switchable measuring ranges, continuous linear output, enclosure

More information

Operating Instructions for Low Volume Rotating Vane Flow Meter. Model: DPL-1P... DPL-1V... DPL-1E...

Operating Instructions for Low Volume Rotating Vane Flow Meter. Model: DPL-1P... DPL-1V... DPL-1E... Operating Instructions for Low Volume Rotating Vane Flow Meter Model: DPL-1P... DPL-1V... DPL-1E... 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 5. Operating

More information

Dimensions. Model Number. Electrical connection. Features. Pinout. Product information. Indicators/operating means OMT300-R201-IEP-IO-V1

Dimensions. Model Number. Electrical connection. Features. Pinout. Product information. Indicators/operating means OMT300-R201-IEP-IO-V1 Dimensions. 9.9 6 Model Number 6.7 Ref. 6. 5. 5.8 7 7.7.6 ø. 9 50 78.5 Receiver Emitter M x..7 sensor with -pin, M x connector Electrical connection Features Medium design with versatile mounting options

More information

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ]

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ] Terminal CPX Electrical interface CPX CTEL 4 M12 5POL Description CTEL master module I-Port 574601 1411a [8041791] Electrical interface CPX CTEL 4 M12 5POL Translation of the original instructions P.BE-CPX-CTEL-EN

More information

Proximity sensors SMT/SME-10, for C-slot

Proximity sensors SMT/SME-10, for C-slot Proximity sensors SMT/SME-10, for C-slot q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement

More information

Digital electropneumatic positioner

Digital electropneumatic positioner Digital electropneumatic positioner Type 879 can be combined with Compact metal housing Graphic display with backlight Easy start-up Comprehensive range of additional software functions Profibus DPV1 (optional)

More information

Electronic pressure switch with display For sanitary applications Model PSA-31

Electronic pressure switch with display For sanitary applications Model PSA-31 Electronic pressure measurement Electronic pressure switch with display For sanitary applications Model PSA-31 WIKA data sheet PE 81.85 Applications Food and beverage industry Pharmaceutical industry Filling

More information

Operating Instructions VEGAMET 381

Operating Instructions VEGAMET 381 Operating Instructions VEGAMET 381 in out Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6 2.1 Authorised personnel...

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS Electronic Rotational Speed Monitoring Device Type EDO Device Identification No.: 93.045 508.001 /.005 /.007 /.012 OPERATING INSTRUCTIONS 2 CE-Sign an Conformity The device meets the requirements of the

More information

Operating Instructions for Low Volume Rotating Vane Flow Meter. Model: DPL-1P... DPL-1V... DPL-1E...

Operating Instructions for Low Volume Rotating Vane Flow Meter. Model: DPL-1P... DPL-1V... DPL-1E... Operating Instructions for Low Volume Rotating Vane Flow Meter Model: DPL-1P... DPL-1V... DPL-1E... 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 5. Operating

More information

Operating instructions Control monitor for temperature sensors TR /00 04/2011

Operating instructions Control monitor for temperature sensors TR /00 04/2011 Operating instructions Control monitor for temperature sensors TR7432 704773/00 04/20 Contents Preliminary note3. ymbols used 3 2 afety instructions 3 3 Functions and features 4 4 Function 4 4. Communication,

More information

Pressure sensor For highest pressure applications to 15,000 bar Model HP-2

Pressure sensor For highest pressure applications to 15,000 bar Model HP-2 Pressure Pressure sensor For highest pressure applications to 15,000 bar Model HP-2 WIKA data sheet PE 81.53 for further approvals see page 6 Applications Test bench construction Water jet cutting High-pressure

More information

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet sales@jumo.co.uk info.us@jumo.net Page 1/9 JUMO PINOS L01 Calorimetric flow sensor Brief description The JUMO PINOS L01 flow sensor serves the measuring and monitoring of flow velocities of water and aqueous

More information

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm Pressure Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm WIKA data sheet PE 81.67 Applications Machine tools Hydraulics and pneumatics Pumps and

More information

Electronic pressure switch with display For sanitary applications Model PSA-31

Electronic pressure switch with display For sanitary applications Model PSA-31 Electronic pressure measurement Electronic pressure switch with display For sanitary applications Model PSA-31 WIKA data sheet PE 81.85 Applications Food and beverage industry Pharmaceutical industry Filling

More information

Connecting cables for valves, plug pattern ZC, metric screw Type codes

Connecting cables for valves, plug pattern ZC, metric screw Type codes Type codes NEBV Z4 WA 2 L R E 5 N M8 G 3 S1 Function NEBV Connecting cables for valves Connection technology on left, field device side Z4 Socket, plug pattern ZC, metric screw Cable outlet left WA Angled

More information

Operating Instructions Differential Pressure Transducer PS27

Operating Instructions Differential Pressure Transducer PS27 Operating Instructions Differential Pressure Transducer PS27 halstrup-walcher GmbH Stegener Straße 10 79199 Kirchzarten/Germany Phone: +49 (0) 76 61/39 63 0 Fax: +49 (0) 76 61/39 63 99 E-mail: info@halstrup-walcher.com

More information

OPT2011. High-performance distance sensor. Operating Instructions

OPT2011. High-performance distance sensor. Operating Instructions OPT2011 High-performance distance sensor Operating Instructions Status: 15/07/2013 2 Table of Contents 1. Use for Intended Purpose 4 2. Safety Precautions 4 2.1. Safety Precautions 4 2.2. Laser/LED warning

More information

DCT 531. Industrial Pressure Transmitter with RS485 Modbus RTU. Stainless Steel Sensor

DCT 531. Industrial Pressure Transmitter with RS485 Modbus RTU. Stainless Steel Sensor DCT 5 Industrial Pressure Transmitter with RS85 Modbus RTU Stainless Steel Sensor accuracy according to IEC 60770: : 0.5 % FSO option: 0.5 % FSO Nominal pressure from 0... 00 mbar up to 0... 00 bar output

More information

Rotary Measuring Technology Absolute encoders, Multiturn, optional with incremental track

Rotary Measuring Technology Absolute encoders, Multiturn, optional with incremental track Electronic multiturn gear with intelligent sensing technology (IST) Integrative Technology Max. 4 programmable outputs* for the SSI version Programmable parameters include*: code type, resolution per revolution,

More information

Fork light barriers SOOF

Fork light barriers SOOF Product range overview Method of measurement Size Min. object diameter Max. switching frequency Switching output Type of light Page/ Internet [mm] [mm] [Hz] Metal light barrier SOOF-M- -C30 30x35 0.5 4,000

More information

Installation instructions Diagnostic electronics for vibration sensors VSE / / 2007

Installation instructions Diagnostic electronics for vibration sensors VSE / / 2007 Installation instructions Diagnostic electronics for vibration sensors UK VSE00 70406 / 00 07 / 2007 Contents Safety instructions 3 Function and features 4 Mounting 4 Mounting of the sensors 5 Electrical

More information

LMP 308. Separable Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO / 0.

LMP 308. Separable Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO / 0. LMP 08 Separable Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.25 % FSO / 0. % FSO Nominal pressure from 0... mh 2 O up to 0... 250 mh 2 O Output signals 2-wire:

More information

Pressure switch RE B/ Type HEDE10.../1/ Operating instructions

Pressure switch RE B/ Type HEDE10.../1/ Operating instructions Pressure switch Type HEDE10.../1/ RE 30276-B/10.10 Replaces: 06.10 Operating instructions 2/20 Bosch Rexroth AG HEDE10.../1/ RE 30276-B/10.10 Contents 1 Overview of menu...3 2 Safety note... 4 3 Operating

More information

Pressure sensors SPAU

Pressure sensors SPAU Key features At a glance Product description The pressure sensor SPAU is suitable for monitoring compressed air and noncorrosive gases. The variant with display offers the option of reading the pressure

More information

Flow measurement FlexFlow PF20S Flow sensor for industrial applications

Flow measurement FlexFlow PF20S Flow sensor for industrial applications Product highlights Parallel measurement of flow and temperature Flow measurement independent of the mounting position Large measuring range up to 400 cm/s Measurement at high media temperatures up to 125

More information

Semi-rotary drives DRVS

Semi-rotary drives DRVS q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity qready for dispatch

More information

Operating instructions Flow sensors SAxx04 SAxx14

Operating instructions Flow sensors SAxx04 SAxx14 Operating instructions Flow sensors SAxx04 SAxx14 UK 80261065 / 00 05 / 2018 Contents 1 Preliminary note...3 2 Safety instructions...4 3 Functions and features...4 4 Function...5 4.1 Operating modes (ModE)...5

More information

Operating instructions Pressure sensor. PN70xx / / 2012

Operating instructions Pressure sensor. PN70xx / / 2012 Operating instructions Pressure sensor PN70xx 706136 / 00 01 / 2012 Contents 1 Preliminary note...3 1.1 ymbols used...3 2 afety instructions...3 3 Functions and features...4 4 Function...5 4.1 Communication,

More information

Electronic Level Switch ENS 3000

Electronic Level Switch ENS 3000 Electronic Level Switch ENS 3000 Description: The ENS 3000 is an electronic level switch with integrated display. The instrument has 1, 2 or 4 switching outputs and an analogue output signal is available

More information

Products no longer available

Products no longer available echnical data sheet NVF4-MF(-E)-R Modulating linear actuator with emergency function for -way and 3-way globe valves Actuating force 800 N Nominal voltage AC/DC 4 V Modulating control DC 0... 10 V Position

More information

SBS, vision sensor Key features

SBS, vision sensor Key features Key features Vision sensor SBS The vision sensors SBS are an easy introduction into vision systems and can be used to read 1D/2D codes or for quality inspection of parts, depending on the model. Their

More information

Product Catalog. Represented by Norstat Inc. in North America

Product Catalog. Represented by Norstat Inc. in North America Product Catalog Represented by Norstat Inc. in North America About MP-Sensor MP-SENSOR a Technology Company located in Neuhausen in the south of Germany near Stuttgart is a company specializing in the

More information

OPT2041. Fiber Optic Cable Sensor. Operating Instructions. Available as PDF only Status:

OPT2041. Fiber Optic Cable Sensor. Operating Instructions. Available as PDF only Status: OPT2041 Fiber Optic Cable Sensor Operating Instructions Available as PDF only Status: 18.06.2018 www.wenglor.com Index 1. Proper Use 3 2. Safety Precautions 3 3. General Information Regarding the Device

More information