Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades

Size: px
Start display at page:

Download "Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades"

Transcription

1 Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades May 2012 / 1910DB1202 by Hal Theobald, Product Manager, Schneider Electric Services and Reza Tajali, P.E., Schneider Electric Engineering Services Make the most of your energy SM

2 Summary 1.0 Introduction Circuit Breaker Performance Upgrade Solutions Now Available Choosing the Right Solution Why Upgrade? Application Considerations Conclusion White paper for circuit breaker modernization

3 1.0 Introduction With increasing dependence on computers and automated processes, most modern facilities cannot afford downtime. In order to maximize the useful life of the electrical equipment and to mitigate the risk of unscheduled power outages, it is critical to properly maintain the switchgear and switchboards that distribute electricity throughout the power distribution system. Electrical switchgear is composed of passive and active components. The passive components include the horizontal and vertical bus structures while the active components are the power circuit breakers and fusible switching devices. The main function of the active components is to protect the electrical assets downstream and to disconnect the circuit and protect personnel in case of an arc flash event. Both the passive and active components require regular maintenance to ensure equipment integrity, proper mechanical and electrical functionality, and to extend the equipment s useful life. 2.0 Circuit Breaker Performance Unless maintenance testing has been utilized to track the performance of circuit breakers, degradation of insulation and the moving parts will not be noticed. Industry groups such as IEEE have analyzed the factors that affect the condition and performance of circuit breakers and published average failure rates for this equipment. However, these average failure rates do not account for the varying degrees of maintenance between different installations. Further, even the best maintained equipment is subject to two key phenomena: 1. Equipment ultimately degrades and reaches the end of its useful life, no matter how much maintenance is performed. 2. Advances in technology both in material sciences and microprocessor based controls facilitate the production of more modern circuit breakers with better performance, reduced maintenance requirements and on-board diagnostics, to name a few features. With the advancements in the design of the new circuit breakers, circuit breakers with older technology are no longer considered sustainable solutions. White paper for circuit breaker modernization 03

4 2.0 Circuit Breaker Performance (con t.) The oldest design power circuit breakers manufactured prior to 1980s employed dash-pot actuated trip units. In addition, their bearings, arc chutes, and contacts required regular maintenance. The introduction of solid state trip units and improved lubrication material produced significant advancement over these older circuit breakers. Modern composites, which combined the circuit breaker frame with the insulating material, provided further enhancement. Masterpact M frame circuit breakers are the product of this era of technological advancement. These circuit breakers quickly became the workhorse of the industry and appeared in large numbers in data centers, generating stations, industrial facilities and practically every other installation in the 1990s and 2000s. 3.0 Upgrade Solutions Now Available Masterpact MP is a UL 489 listed circuit breaker, Masterpact MC is an ANSI rated circuit breaker (UL1066), while Masterpact M is an IEC rated circuit breaker. Throughout the remainder of this document, we will refer to these three circuit breakers as the Masterpact M. Masterpact M circuit breakers have been discontinued since 2004 and are scheduled to become fully obsolete in At that time, it is anticipated that parts will no longer be available as inventories will quickly be depleted. A viable solution to consider is upgrading the existing equipment with the latest state of the art circuit breakers. Schneider Electric has developed methods for adapting the latest technology circuit breakers into a switchgear or switchboard cell that was originally designed for Masterpact M circuit breakers. ANSI standard C37.59 addresses this kind of upgrade and includes design and testing requirements for the adaptation. By following this standard, Schneider Electric provides a comfort level that the user will receive a reliable product. 04 White paper for circuit breaker modernization

5 4.0 Choosing the Right Solution There are two options available to replace the Masterpact M with today s current production Masterpact NW circuit breaker. Both options allow the Masterpact NW to fit into the existing cell and are engineered, fully tested and validated to ANSI C Choosing the right solution is dependent upon the existing circuit breaker ratings. Option 1: The Plug & Play approach is a fully-designed solution that is applicable only to 3-pole M-series circuit breakers that have a continuous current rating of 3000 amperes or less and an interrupting rating up to 85kA at 600V. With this option, only one electrical outage must be coordinated, with a total duration of approximately 4 hours. During this outage, the M-series circuit breaker is removed and modifications to the existing cradle rails and secondary contacts are made by an experienced field service representative to facilitate the installation of the new Masterpact NW circuit breaker. Option 2: A Retrofill solution, applicable to M-series circuit breakers of all ratings, is specifically designed for those with a continuous current rating greater than 3000 amperes or a short circuit rating greater than 85kA. This option requires two electrical outages. The first outage is brief and is utilized by a Schneider Electric engineer to measure bus connection locations. After this outage, Schneider Electric engineers will design a kit of components to facilitate the retrofill process. A second, and more extensive, outage is then coordinated to remove the old circuit breaker and the old cradle along with the bus run backs. Field service representatives will then install the new Masterpact NW cell adapters, cradle and circuit breaker. With either option, a system coordination study should be performed. After the upgrade, the end-user has a modern circuit breaker with enhanced features to help improve the reliability of their system. The original Masterpact M chassis is retained. (no intervention on the switchboard structure) Masterpact NW adapted for the "Plug and Play" solution Masterpact M White paper for circuit breaker modernization 05

6 5.0 Why Upgrade? With either of the two options referred to in section 4.0, Masterpact NW circuit breakers are provided. These circuit breakers feature enhancements that were not available with the Masterpact M circuit breakers. These consist of positive stops in the connected, test, and disconnected positions plus a visual position indicator. Also, the Masterpact NW circuit breaker maintains ground contact between its body and the draw-out cell when the cover is removed while the circuit breaker is in the connected, test, or disconnected positions. There is also a push-open crank interlock. Additional improved functionalities, some of which are optional, include: Power metering, monitoring and communication to building management systems Extended AIC rating when fault currents increase Finger clusters are on the circuit breaker instead of the cradle for the ANSI and UL versions, making them easier to maintain (Retrofill option only) Ring terminals are available for secondary connections (improved reliability) Electronic contact wear indicator provision (optimized maintenance) Additional keylock and padlock provisions Large LCD dot matrix display Field-replaceable trip unit and/or rating plugs Protective relaying functions built into the trip unit with up to six programmable contacts Internal shutter mechanism to isolate energized line side bus (Retrofill option only) 06 White paper for circuit breaker modernization

7 6.0 Application Considerations Taking on a project to upgrade the existing switchgear should involve an engineering evaluation of the system. Following are a few items that should be considered with either the Plug & Play or the Retrofill upgrade options. Schneider Electric Engineering Services is prepared to develop custom designs for any demanding application: Trip units The Masterpact NW circuit breaker uses a more sophisticated and function-rich trip unit as compared to the previous design (Masterpact M STR trip units). The new trip unit means different instantaneous and delay trip curves, therefore, a coordination study is recommended to appropriately set the new circuit breaker trip points. 4-wire system - Upgrading to the Masterpact NW will require a new neutral sensor and wiring. Zone Selective Interlocking (ZSI) - If a ZSI system is being utilized, upgrading from the Masterpact M to Masterpact NW will require a new ZSI module and interlocking scheme. Key Interlocking Scheme - The current key interlocking schemes on the existing Masterpact M circuit breakers will have to be incorporated into the new Masterpact NW upgrade solution. Modified Differential Ground Fault System - MDGF system is an arrangement of sensors (current transformers or CTs) to assure ground fault protection on systems that comprise multiple grounded power sources. As the old technology neutral current sensors are replaced to the new NW style external current sensors, some bussing modifications may be required in the switchgear. MDGF system complexity is facility-specific. The Schneider Electric Engineering Services team is available to address specific application requirements. 7.0 Conclusion The application of the circuit breaker and the operating environment come into consideration in choosing the upgrade method. Plug & Play or retrofill solutions upgrade the critical components that protect assets and personnel. They also provide enhanced system capabilities, such as communications, without the extended downtime of a full switchgear replacement. The existing structure remains intact, reducing the downtime required for the upgrade, and the active component is replaced to extend the useful life of the equipment. Upgrading existing equipment is a cost effective approach that does not compromise the reliability of the switchgear. Masterpact NW circuit breakers were designed and developed with an eye on retrofill applications. The new workhorse of the industry, Masterpact NW circuit breakers will provide many years of successful operation when properly installed by the original manufacturer s trained personnel. White paper for circuit breaker modernization 07

8 Schneider Electric USA 1415 S. Roselle Road Palatine, IL Tel: Fax: Document Number 1910DB1202 May 2012 jw 2012 Schneider Electric. All rights reserved.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability 1910DB1207 By Hal Theobald, Product Marketing Manager, Schneider Electric Services Summary 1.0 Abstract...3 2.0 Introduction...3

More information

Mitigating Arc Flash Hazards

Mitigating Arc Flash Hazards 1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash

More information

NW08 to NW63 fixed circuit breakers Circuit breakers

NW08 to NW63 fixed circuit breakers Circuit breakers fixed circuit breakers Circuit breakers DB404362.eps DB404363.eps A Masterpact fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that

More information

Switchgear Design Impacts the Reliability of Backup Power Systems

Switchgear Design Impacts the Reliability of Backup Power Systems Switchgear Design Impacts the Reliability of Backup Power Systems December 2010/AT307 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision #1 12/10 When a cascaded

More information

GE Industrial Solutions. Aftermarket Solutions. Product Portfolio

GE Industrial Solutions. Aftermarket Solutions. Product Portfolio GE Industrial Solutions Aftermarket Solutions Product Portfolio Aftermarket Solutions Product Portfolio At GE we service the electrical distribution equipment that keeps industrial operations powered and

More information

Spectra RMS Circuit Breakers with microentelliguard Trip Units

Spectra RMS Circuit Breakers with microentelliguard Trip Units GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

Best practices for making switchgear safer.

Best practices for making switchgear safer. Best practices for making switchgear safer. www.sea.siemens.com www.usa.siemens.com/switchgear Prepared by: Ken Newsome - Consulting Business Developer Kevin Mullins - Consulting Business Developer Joe

More information

I-Line Panelboards. Innovative design, smart bus technology, and simple installation

I-Line Panelboards. Innovative design, smart bus technology, and simple installation I-Line Panelboards Innovative design, smart bus technology, and simple installation TM Smart: designed for efficient installation Simple: Efficient Installation Process I-Line Breakers Main Lugs: Fixed-mounted

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution MPSC-2000 Microprocessor-based protection and metering devices for low voltage power circuit breakers ABB Power Distribution Introduction For circuit breaker protection, metering and communications, the

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Common Departures Interconnecting Facilities Requirements

Common Departures Interconnecting Facilities Requirements Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low

More information

Having communication issues? Model 6 intelligent Motor Control Centers communicate on all platforms. Make the most of your energy SM

Having communication issues? Model 6 intelligent Motor Control Centers communicate on all platforms. Make the most of your energy SM Having communication issues? Model 6 intelligent Motor Control Centers communicate on all platforms. Make the most of your energy SM Model 6 intelligent Motor Control Centers An intelligent solution. Intelligence.

More information

Best practices for making switchgear safer

Best practices for making switchgear safer Best practices for making switchgear safer White Paper Introduction What could be more important than protecting the safety of our most valuable assets, our people? Today s workers hold the keys to an

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Low Voltage and Medium Voltage Direct Replacement and Retrofill Circuit Breakers Selector Guide

Low Voltage and Medium Voltage Direct Replacement and Retrofill Circuit Breakers Selector Guide Low and Medium Direct Replacement and Retrofill Circuit Breakers Selector Guide Make the most of your energy SM As switchgear reaches the end of its intended useful life, a viable, cost-effective strategy

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

EntelliGuard* G Circuit Breakers Don t compromise arc flash protection for system reliability.

EntelliGuard* G Circuit Breakers Don t compromise arc flash protection for system reliability. GE Energy Management EntelliGuard* G Circuit Breakers Don t compromise arc flash protection for system reliability. The next chapter in the history of low-voltage circuit breakers EntelliGuard* G circuit

More information

Integrating Monitoring and Diagnostic Equipment on Aging Transformers

Integrating Monitoring and Diagnostic Equipment on Aging Transformers May 13-14, 2008 International Centre, Mississauga, Ontario April 2008 Volume 20, No. 3 Integrating Monitoring and Diagnostic Equipment on Aging Transformers Valuable information on maintaining critical

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence

More information

Benefits, offering and references

Benefits, offering and references DOC ID: 9AKK107045A9180 DISTRIBUTION SOLUTIONS Digital medium-voltage switchgear Benefits, offering and references Contents Digital switchgear for medium-voltage applications Digital switchgear definition

More information

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins Today's Moderator Ed Sulivan Editor Today's Presenter Steve Maling Director, US Field Services Marketing, Schneider

More information

4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection...

4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection... .3 Product Description Drawout molded case circuit breaker switchboard Front accessible Front connected Through-the-door design drawout mechanism through 600A Insulated case UL 89 breakers up to 200A Visual

More information

RELT Reduced Energy Let Thru 2018

RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, There is an increasing concern in the electrical industry about arc flash energy levels

More information

ASCO 7000 SERIES Power Control Systems

ASCO 7000 SERIES Power Control Systems ASCO 7000 SERIES Power Control Systems 1 7000 SERIES PCS LINEUP ASCO 7000 SERIES Power Control Systems (PCS) offer the most advanced power management features for mission-critical facilities. Every 7000

More information

Switchgear FEATURE. Basler Electric Company

Switchgear FEATURE. Basler Electric Company Switchgear LIFe ExtenSIon: Replacement of electromechanical Overcurrent Relaying By Todd Martin, Basler Electric Company Chemical Facility U p d at i n g S w i t c h g e a r R e l ay s Electromechanical

More information

30-Cycle Rated Switchboards - Selectivity Tradeoffs

30-Cycle Rated Switchboards - Selectivity Tradeoffs 30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted

More information

Innovation for MV distribution

Innovation for MV distribution Innovation for MV distribution Introducing Premset switchgear, a new way to design, install, and operate MV networks. schneider-electric.us/premset 2 schneider-electric.us/premset schneider-electric.us/premset

More information

Zone-Selective Interlocking Field Testing and Commissioning

Zone-Selective Interlocking Field Testing and Commissioning GE Energy Connections DEH-583 Instruction Guide Zone-Selective Interlocking Field Testing and Commissioning For EntelliGuard* and microentelliguard* Trip Units 2 Table of Contents 1. Overview... 4 2. ZSI

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers It is widely recognized that the concept of periodic equipment maintenance

More information

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

PanelFAST. Setting a new standard for immediate product availability with Square D Ready to Install (RTI) Panelboards

PanelFAST. Setting a new standard for immediate product availability with Square D Ready to Install (RTI) Panelboards PanelFAST Setting a new standard for immediate product availability with Square D Ready to Install (RTI) Panelboards Whether you planned ahead or have an unexpected project, why wait? You should expect

More information

Square D Homeline Load Centers and Circuit Breakers. Engineered for value

Square D Homeline Load Centers and Circuit Breakers. Engineered for value Square D Homeline Load Centers and Circuit Breakers Engineered for value TM From the Square D brand you know and trust, Homeline Load Centers are engineered for value, reliability, and innovation. The

More information

Risk Mitigation of Aging Electrical Infrastructure

Risk Mitigation of Aging Electrical Infrastructure Risk Mitigation of Aging Electrical Infrastructure 2014 66 th Annual Conference 2pm Tuesday May 8 th, 2014 Presented by Dick McDonnell Authored by Jeff M. Miller, PE, ENV SP About the Presenter Dick McDonnell

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

Type VR Electrically Operated Ground and Test Device

Type VR Electrically Operated Ground and Test Device Type VR Electrically Operated Ground and Test Device For Use with Masterclad Switchgear 4.76 kv 15 kv, 1200, 2000, 3000, 4000 A Up to 63 ka Short Circuit Rating Class 6055 Instruction Bulletin 6055-37

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

Process and Power Control

Process and Power Control Process and Power Control Insert Photo Here Sergio Gama Rockwell Automation Rockwell Automation Process Solutions User Group (PSUG) November 14-15, 2011 Chicago, IL McCormick Place West Copyright 2011

More information

Compact NSX communication

Compact NSX communication Functions and characteristics Compact NSX communication Communications modules All Compact NSX devices can be equipped with the communication function via a prewired connection system and a Modbus network

More information

LV MCC with Arc Flash Mitigation (AFM) Units

LV MCC with Arc Flash Mitigation (AFM) Units LV MCC with Arc Flash Mitigation (AFM) Units Technical Tuesday June 30, 2015 Imagination at work. Markets Oil and Gas Petro-Chemical Mining and metals Pulp and paper Mass-production manufacturing Water

More information

The Center of Automation with IEC Products. CENTERLINE Motor Control Center. Allen-Bradley Replacements

The Center of Automation with IEC Products. CENTERLINE Motor Control Center. Allen-Bradley Replacements The Center of Automation with IEC Products CENTERLINE Motor Control Center Allen-Bradley Replacements 2 Continually enhanced since its introduction in 1971, CENTERLINE is the leading MCC in the North American

More information

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER C. Petit Schneider Electric, France Innovation in the field of medium voltage protection devices is accelerating to meet the ever growing demands

More information

Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ).

Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ). S W I T C H G E A R Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ). Prime Engineering is a full service electrical engineering firm that specializes in medium and high voltage equipment

More information

Power-Style QED-2, Series 2 Low Voltage Switchboards

Power-Style QED-2, Series 2 Low Voltage Switchboards Power-Style QED-2, Series 2 Low Voltage Switchboards Catalog 2742CT1001 (Addendum to 2742CT9501R12/09) 2010 Class 2742 CONTENTS Description............................................. Page Features...................................................

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

Insulated-Case Circuit Breakers

Insulated-Case Circuit Breakers 001Power Circuit Breakers & Sheet.0-1 Insulated-Case Circuit Breakers Contents Breaker Type Comparison.......................................0-2 Magnum Product Family..........................................1-1

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,

More information

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent

More information

MOUNTING BASE AQB-A402 PLAN VIEW OF MOUNTING BLOCK & CIRCUIT BREAKER AQB-A802 CIRCUIT BREAKER MOUNTING BLOCK 2.50 MOTOR OPERATOR 25.

MOUNTING BASE AQB-A402 PLAN VIEW OF MOUNTING BLOCK & CIRCUIT BREAKER AQB-A802 CIRCUIT BREAKER MOUNTING BLOCK 2.50 MOTOR OPERATOR 25. Weights & Dimensions 4 1/8 4 5/16 4 1/8 4 5/16 Weights & Dimensions 5 1/16 6 1/2 15 1/2 17 15/16 A C A C 6 3/16 MOUNTING ASE MOUNTING ASE 5 1/16 6 3/16 MOUNTING ASE DIMENSIONS DESCRIPTION A C SINGLE ASE,

More information

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SXP200002B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of

More information

Powering innovation. Powering efficiency. Powering home

Powering innovation. Powering efficiency. Powering home Powering efficiency Powering home DISCONNECTS The best prices & selection in Siemens general, industrial & heavy duty safety switches for every application. Powering innovation Illustrating the diverse

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District 5 WHAT IS A BUS? All connections are at the same voltage. WHAT IS A BUS? All

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

CENTERLINE 2500 Motor Control Centers

CENTERLINE 2500 Motor Control Centers CENTERLINE 2500 Motor Control Centers High Performance Motor Control Centers and Switch Gear Meeting IEC 61439-2 Product Description Allen-Bradley CENTERLINE 2500 motor control centers (MCCs) are designed

More information

Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets

Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets www.intellisaw.com The Case for Critical Asset* Monitoring The vast majority of critical assets in the field

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Masterpact MTZ Micrologic X Control Unit

Masterpact MTZ Micrologic X Control Unit Masterpact MTZ Micrologic X Control Unit Firmware Version 002.000.003 Release Note 05/2018 DOCA0144EN-01 The information provided in this documentation contains general descriptions and/or technical characteristics

More information

Masterpact NW Restricted Earth Fault Protection

Masterpact NW Restricted Earth Fault Protection Masterpact NW Restricted Earth Fault Protection Date: November 2011 Page 1 of 12 Contents Introduction 3 Principle of Operation 4 Equipment Required 5 Installation of the Neutral CT 5 Connection of the

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

LV power circuit breaker and switch-disconnectors. Masterpact NW Direct current 1000 to 4000 A. Catalogue

LV power circuit breaker and switch-disconnectors. Masterpact NW Direct current 1000 to 4000 A. Catalogue LV power circuit breaker and switch-disconnectors Masterpact NW Direct current 1000 to 4000 A Catalogue 2002 Get more with the world s Power & Control specialist Masterpact NW General contents Presentation

More information

White Paper. UL Standards for Power Control System Equipment

White Paper. UL Standards for Power Control System Equipment White Paper UL Standards for Power Control System Equipment UL Standards for Power Control System Equipment An Introduction to UL 891 and UL 1558 Commercially available Power Controls Systems (PCS) can

More information

MiCOM P111. Three phase and earth fault overcurrent relays

MiCOM P111. Three phase and earth fault overcurrent relays Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features

More information

GE Energy Industrial Solutions. GE Overcurrent Device Instantaneous Selectivity Tables

GE Energy Industrial Solutions. GE Overcurrent Device Instantaneous Selectivity Tables GE Energy Industrial Solutions GE Overcurrent Device Instantaneous Selectivity Tables Contents Introduction...3 Selectivity with EntelliGuard TU and microentelliguard EntelliGuard TU Trip Units in ANSI

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Safe, seamless, smart

Safe, seamless, smart Series NRX NF and RF Frame low-voltage circuit breakers with Power Xpert Release Technical product guide Safe, seamless, smart Series NRX with Power Xpert Release trip units low-voltage power circuit breakers

More information

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission.

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission. Switchgear Interlock Applications Data Sheet Industries Power Distribution Power Generation Power Transmission Type DM Access Interlock with Spring Bolt Type PPS Interlock Quick-Trip ARC Flash Reduction

More information

60103 Circuit Breaker

60103 Circuit Breaker 6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard

More information

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document

More information

Why is my AFCI tripping?

Why is my AFCI tripping? www.garyklinka.com Page 1 of 21 Instructions: Fee $25 1. Print these pages. 2. Use the included information located on pages 12-20 to answer the 61 questions below. 3. Circle the correct answers and transfer

More information

PRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system

PRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system PRODUCT BROCHURE Cyberex Remote Power Panel (RPP) Power distribution system 2 CYBEREX RPP POWER DISTRIBUTION REMOTE POWER PANEL Cyberex power distribution Remote Power Panel (RPP) With constantly evolving

More information

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold Tru-Break switchgear module Tru-Break switchgear module agenda Design platform and value Product specifications Operation Configuration examples

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

Symmetra PX 48kW. Scalable from 16 to 48kW. Make the most of your energy TM. Modular, Scalable, High-Efficiency Power Protection for Data Centers

Symmetra PX 48kW. Scalable from 16 to 48kW. Make the most of your energy TM. Modular, Scalable, High-Efficiency Power Protection for Data Centers Symmetra PX 48kW Scalable from 16 to 48kW Modular, Scalable, High-Efficiency Power Protection for Data Centers High performance, right-sized, modular, scalable, 3-phase power protection with high efficiency

More information

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT ESTABLISHED SINCE 1985 Circuit Breaker Solid State Controls with RMS-2007AF LOGIC (All logics come with ARC FLASH as a standard) The SURE TRIP SOLID STATE

More information

The complete application guide to specifying a Smart-Gear power distribution solution (PDS) E50001-F710-A123-V1-4A00. Answers for energy.

The complete application guide to specifying a Smart-Gear power distribution solution (PDS) E50001-F710-A123-V1-4A00. Answers for energy. The complete application guide to specifying a Smart-Gear power distribution solution (PDS) E50001-F710-A123-V1-4A00 Answers for energy. Smart-Gear power distribution solution (PDS) Siemens, a world leader

More information

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision

More information

Product brochure. Cyberex. Remote Power Panel (RPP) Power distribution system

Product brochure. Cyberex. Remote Power Panel (RPP) Power distribution system Product brochure Cyberex Remote Power Panel (RPP) Power distribution system Cyberex power distribution Remote power panel (RPP) With constantly evolving demands and the increasing need to store critical

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

3- and 4-pole switching in UPS installation

3- and 4-pole switching in UPS installation Smart tricks to improve power supply reliability White paper series Power Distribution & UPS 3- and 4-pole switching in UPS installation Janne Paananen Technology Manager, Critical Power Solutions, Eaton

More information

FT Flexitest Family. Switches, Covers and Test Plugs

FT Flexitest Family. Switches, Covers and Test Plugs FT Flexitest Family Switches, Covers and Test Plugs FT Flexitest Switches Description The flexibility provided by the FT case design evolved into a separate family of molded base test switches for testing

More information

The Leviton Load Center THE FUTURE MADE CURRENT

The Leviton Load Center THE FUTURE MADE CURRENT The Leviton Load Center THE FUTURE MADE CURRENT Raising the Bar Again For over 110 years, Leviton has cultivated a rich tradition of safety and innovation, developing electrical products that set the

More information

A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering

A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy Patrick Robinson Altelec Engineering Captured Arcing Fault Event Arc begins as phase A-C, 8ka peak, dies out then

More information

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/pgr-4700 PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY REVISION 2-B-032218 Copyright 2018 by Littelfuse, Inc. All rights reserved.

More information

Ground Fault Protection on Solidly Grounded Low Voltage Electrical Systems APPLICATION GUIDE. application GUIDE

Ground Fault Protection on Solidly Grounded Low Voltage Electrical Systems APPLICATION GUIDE. application GUIDE Ground Fault Protection on Solidly Grounded Low Voltage Electrical Systems APPLICATION GUIDE application GUIDE Application Guide, October 2014 ABOUT I-GARD I-Gard s commitment to electrical safety provides

More information