AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter
|
|
- Damian Burke
- 5 years ago
- Views:
Transcription
1 AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter Install Guide Revision C (12/18)
2 DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Revision C (12/18) Turn off all power supplying equipment before working on or inside the equipment. Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel. Read, understand and follow the instructions before installing this product. Product may use multiple voltage/power sources. Be sure all sources of power have been disconnected before servicing. Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors. Failure to follow these instructions will result in death or serious injury. CAUTION This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. The installer is responsible for conformance to all applicable codes. Mount this product inside a suitable fire and electrical enclosure. A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment, and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2011 Article 100 No responsibility is assumed by Leviton for any consequences arising out of the use of this material. DO NOT EXCEED 346V Line to Neutral or 600 volts Line to Line. This meter is equipped to monitor loads up to 346V L-N. Exceeding this voltage will cause damage to the meter and danger to the user. Always use a Potential Transformer (PT) for voltages in excess of 346V L-N or 600 volts line to line. The VerifEye is a 600 Volt Over Voltage Category III device. For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with the environment. Installation category: CAT II or CAT III Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment, and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC and IEC and shall be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconnecting device for supply conductors with approved current limiting devices suitable for protecting the wiring. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired. For the complete safety information for this product, see the full user guide. 2
3 Technical Specifications Revision C (12/18) Specification Service Types Voltage Channels Current Channels Maximum Current Input Measurement Type Line Frequency Power AC Protection Power Out Waveform Sampling Parameter Update Rate Measurements Description Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two independent voltage reference inputs 48 channels, VAC max, 333 mv CTs, 0-4,000+Amps depending on current transducer 150% of current transducer rating (mv CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs. True RMS using high-speed digital signal processing (DSP) with continuous sampling Hz From L1 Phase to L2 Phase VAC RMS CAT III 50/60Hz, 500mA AC Max Use of 12 volt auxiliary output requires 100 VAC minimum input voltage. 0.5A Fuse 200kA interrupt capacity Unregulated 12VDC output, 200 ma, self-resetting fuse 1.8 khz 1 second Volts, Amps, kw, kvar, kva, apf, dpf, kw demand, kva demand, Import (Received) kwh, Export (Delivered) kwh, Net kwh, Import (Received) kvah, Export (Delivered) kvah, Net kvah, Import (Received) kvarh, Export (Delivered) kvarh, Net kvarh, THD, Theta, Frequency. All parameters for each phase and system total. Accuracy 0.2% ANSI C Class 0.2 Resolution Indicators Pulse Input Alarm Output Values reported in IEEE-754 single precision floating point format (32 bit). 4-line display, tri-color backlight (PhaseChek ) AMC12 4 inputs, AMC48 2 inputs Voltage Phase Loss Alarm (SPDT Relay - 30 VDC) ( only) Communication Hardware Supported Protocols Max Communication Length (RS485) RS-485 Loading RS-485, Ethernet, & USB (for configuration only) Modbus RTU or BACnet Master Slave Token Passing protocol (MS/TP) Modbus (using SunSpec IEEE-754 single precision floating point model) BACnet MS/TP Modbus TCP BACnet IP 1200 meters total cable length, with Data Range of 100K bits/second or less 1/8 unit 3
4 Communication Rate (baud) Data Bits 8 Parity Stop Bit 2, 1 Termination Mechanical Wire Connections Mounting High Voltage Cover Modbus: 9600 (Default), 19200, 38400, 57600, 76800, BACnet: 9600 (Default), 19200, 38400, None, Even, Odd None provided AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated Enclosure or Panel Mount IP40 (embedded version) Operating Temperature -20 to + 60⁰ C (-4 to 140⁰ F) Humidity Enclosure 5% to 95% non-condensing ABS Plastic, 94-V0 flammability rating, connections sized for 1 inch EMT conduit Dimensions (L) 33.7cm x (W) 25.2cm x (H) 8.0 cm (13.3 x 10 x 3.1 ) (no enclosure version) (L) 24.7cm x (W) 25.2cm x (H) 8.0 cm (9.8 x 10 x 3.1 ) (no enclosure version) PCBA Dimensions (L) 21.6cm x (W) cm x (H) 6.4 cm (8.5 x 8.5 x 2.5 ) Obvius Ally Configuration Console Minimum System Requirements Operating System Windows 7. Windows 8, Windows 10 Communications Port USB or Ethernet connectivity Safety FCC Compliance Serial/Ethernet Meters This device has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user s own expense. The following are UL Recognized: AMC12-B-y-z, -P-y-z, AMC48-B-y-z, -P-y-z The following are UL Listed: AMC12-C-y-z, AMC48-C-y-z Conforms to UL Std , 3rd Edition, UL :2010 Certified to CSA Std C22.2 No , 3rd Edition 4
5 Mechanical Specifications & Mounting Series AMC48 - Enclosure Series AMC12 - Enclosure 5
6 Series AMC48 Enclosure Drill Pattern Series AMC12 Enclosure Drill Pattern 6
7 Series AMC48 Mounting Plate Template 7
8 The following section illustrates the 12 channel model. The mounting components are slightly different, but follow the same procedure. STEP 1) Remove top cover screws (4x) and high voltage cover screws (2x) provided STEP 2) Locate, mark, and drill wall mounting points (2x 6x customer supplied) The plastic enclosure itself can be used as a template for marking the drill locations on the wall. #8 Fastener If the meter is not available for use as a drill template, a drawing indicating the spacing between mounting holes can be found in the appendix. The centerline holes are intended for fastening to wall studs. If hollow wall fasteners are used, the outer 4 mounting points are recommended. 8
9 STEP 3) Mount conduit fittings, conduits, and blanking plugs STEP 4) Connect voltage leads 9
10 STEP 5) Attach high voltage cover IP30 TOUCH SAFE (with internal cover installed) STEP 6) Connect CT and Communications Wiring Connecting Voltage Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter through a dedicated disconnect or circuit breaker. A voltage lead of 14 AWG THHN Minimum 600VAC rating (or equivalent) is required. IMPORTANT: Verify the circuit breaker is marked as the disconnect breaker for the meter. 10
11 Wiring the AcquiSuite Ally Meter in a 3-wire, Split ɸ Service Panel High voltage MAY BE PRESENT. Risk of electric shock. Life threatening voltages may be present. Qualified personnel only. 3-Wire, 1 Phase used On MAINS L1-N, L2-N (RōCoils Shown) Connect the Neutral wire to V INPUT 1 (N) on the meter Meter is powered from L1 to L2 on the V Input 1 terminal (Label as Disconnect)) Single Phase 110 VAC Plug Loads L1-N or L2-N Single Phase 220 VAC Plug Load L1-L2 3-Wire, 1 Phase Split Load L1-N, L2-N Illustrating the intended wiring configuration for each of the Service Types available in the Service drop-down list under Meter Setup EXAMPLE LOADS: Single Phase L1-N or L2-N 110 VAC: Lighting, Appliance, Living Zone Single Phase L1 L2 220 VAC: Water Heater, Clothes Dryer, Equipment with no neutral wire. Split Phase L1 L2 220 VAC: Service Entrance, Equipment with neutral wire. 11
12 Wiring the AcquiSuite Ally Meter in a 4-wire, 3 ɸ Service Panel 3 Wire, 3 ɸ used On MAINS L1-N, L2-N, L3-N (Rogowski Coils Shown) Connect the Neutral wire or Ground wire to V INPUT 1 (N) on the meter Single Phase Branch Loads L1-N Meter Power Connect all phases to the V INPUT 1 terminal (Label as Disconnect) 4 Wire, 3 ɸ WYE load (Neutral Current) L1-N, L2-N, L3-N 3-Wire, 3 ɸ DELTA load (No possibility of Neutral Current) L1-N, L2-N(est), L3-N Illustrating the intended wiring configuration for each of the Service Types available in the Service drop-down list under Meter Setup Note: The AcquiSuite Ally Meter Series uses the Neutral Terminal as a voltage reference. For systems without a neutral conductor, Leviton suggests connecting a ground wire to this terminal. If the neutral terminal is left open, L-L measurements will be accurate, but L-N measurements may not be symmetric. If a ground wire is connected to the Neutral terminal, <2mA will flow into the ground wire. 12
13 Wiring the CTs to the AcquiSuite Ally Meter The image below is the counterpart to the service panel illustration and indicates how to connect CTs to the input terminals on the AcquiSuite Ally, for each service type. For service types that are not specifically listed, it is recommended to choose single phase service and configure each channel individually. Three phase loads are illustrated on the left and split phase loads on the right as an example only. Elements are fully interchangeable on the meter. Current and voltage inputs must be installed in phase for accurate readings (e.g. CT1 on Line 1, CT2 on Line 2) Orientation is critical: Ensure that all CTs are properly oriented with the line and load, as marked. Failure to install CTs in the correct orientation and on the correct phase will lead to inaccurate meter readings. 13
14 14 Revision C (12/18)
15 Communication Verification Revision C (12/18) Verification includes confirmation of BOTH the physical interface settings (Serial or Ethernet) and the protocol (Modbus or BACnet) settings. The LCD User interface can be used to quickly confirm the settings required for each combination of interface and protocol. The interface is intuitive and groups together commonly associated registers. The complete interface is presented in Appendix A as a navigational map. Arrows indicate how to move from one menu display to the next. A Reverse Contrast entry in the documentation indicates the active menu item in a list which corresponds to a blinking character in the physical LCD. The ENTER button is used to select a property and up / down buttons are used to select among the values supported by the meter. Note that changes to the meter configuration are limited to the communication interface using the LCD. If additional changes (such as CT type) are required they must be made using a software interface. Example LCD Navigation AcquiSuite Ally Configuration Console / Web Application If your AcquiSuite Ally model does not include the LCD user interface or if you prefer to verify the installation using software, then verification is facilitated through the AcquiSuite Ally 15
16 Configuration Console PC application or the Web App which shares a common design. Refer to the section on Configuration Details in the full user manual, or the AcquiSuite Ally Web App. Pulse Inputs Ally ACM12 meters are equipped with 4 pulse inputs and Ally ACM48 meters (hardware version I) are equipped with 2 pulse inputs. Pulse counting supports accumulation of consumption data from any external meter using a dry contact (Form A Relay) or open collector outputs. The AcquiSuite Ally pulse inputs are compatible with low speed meters. The pulse duration must exceed 50mS in both the logic low and high state allowing for a maximum input frequency of 10 Hz. Pulse scaling, resetting and accumulated values are accessed through registers and are system in scope. Refer to the register list, Obvius Ally Configuration Console, or videos for more information. >50 mec Typical Pulse Sequence >50 mec 16
AcquiSuite Ally 48 Advanced Branch Circuit Monitor
AcquiSuite Ally 48 Advanced Branch Circuit Monitor AMC48-MD AMC48-ED Split Core CT Split Core CT Ally Rogowski Rope CT DESCRIPTION The AcquiSuite Ally 48 is the perfect companion to the data acquisition
More informationENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS
POWER MONITORING ENERCEPT Networked Power Transducer (Modbus RTU) DANGER US Patent No. 6,373,238 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in
More informationBCM2 Series Branch Circuit Monitors Quick Setup Guide
BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationQUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.
PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationPM Series Power Meter
PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See
More informationAcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter
User s Guide AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter And AcquiSuite Ally Configuration Console Software Revision C (11/18) User s Guide: AcquiSuite Ally Power Meters 2018 Obvius, Inc. All
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationModels beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)
Models beginning with 2M, 2L or 2X Series 2000 Multiple Meter Units (MMUs) Product Description Technical Specifications Installation Instructions February 28 th, 2013 List of Figures...2 List of Tables...2
More informationQUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter
QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices.
More informationPowerLogic High Density Metering System 1-Meter Enclosure
PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these
More informationDTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A
DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current
More informationTechnical Specifications. Multi Function Meter
Technical Specifications of Multi Function Meter (SPM300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com
More informationPower Squad 12 Power Battalion 48
Operator s Guide Power Squad 12 Power Battalion 48 Networked Metering Systems and Headstart Software October 2017 Operator s Guide: Power Squad 12 & Battalion 48 Power Meters 2017 Setra Systems, Inc. All
More informationSEM3 - Embedded Micro Metering Module
SEM - Embedded Micro Metering Module Quick Reference Guide and Installation Instructions Scan QR Code for more information usa.siemens.com/sem Installation! DANGER Hazardous Voltage. Will cause death or
More informationUSER MANUAL 2012 V1.1
SMART MINI POWER SDM630 USER MANUAL 2012 V1.1-1 - Installation and Operation Instructions Important Safety Information is contained in the Maintenance section. Familiarise yourself with this information
More informationGE Industrial Solutions. DET-756 Installation Instructions ASPMETER Panelboard Monitoring System
GE Industrial Solutions DET-756 Installation Instructions SPMETER Panelboard Monitoring System Safety If SPMETER products are used in installations with circuits higher than the product ratings, the circuits
More informationINSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:
DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated
More informationSECTION SWITCHBOARDS
SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS
More informationACCESS 9340/9360 Meter Input/Output Module
Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the
More informationH704-42(H)(E), H704-42/1(H)(E)
POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (
More informationPDI Modular Compact Remote Power Panel
Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications
More informationMID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID
PRELIMINARY DATA SHEET RI-D35-100 Series Single Phase Multifunction Energy Meter (MID Certified) MID direct connected Two pulse outputs LED pulse indication High definition LCD display with white backlight
More informationDKM-407 DIN RAIL TYPE NETWORK ANALYZER
DKM-407 User Manual DKM-407 DIN RAIL TYPE NETWORK ANALYZER DESCRIPTION The DKM-407 is a DIN rail mounted precision and low cost unit allowing measurement and remote monitoring of AC parameters of a distribution
More informationTechnical Specifications. Dual Source Energy Meter (EB / DG)
Technical Specifications of Dual Source Energy Meter (EB / DG) (SPMG300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com
More informationSECTION ( ) LIGHTING CONTROL PANELBOARD
(26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting
More informationMIC-2 MKII, Multi-instrument DATA SHEET
MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)
More informationLiebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System
Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe
More informationPower Meter PowerMonitor 500
ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific
More informationPanelView Plus/VersaView CE Terminals and Display Modules
Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3
More informationDKM-405 NETWORK ANALYSER WITH TOTAL HARMONIC DISTORTION DISPLAY
datakom@datakom.com.tr http://www.datakom.com.tr Tel: +9-216 466 84 6 Fax: +9-216 364 65 65 DKM-45 NETWORK ANALYSER WITH TOTAL HARMONIC DISTORTION DISPLAY INTRODUCTION The DKM-45 is a low cost precision
More informationTechnical Specificaions. kwh Energy Meter
Technical Specificaions of kwh Energy Meter (SPK301) Class 1.0S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Adaptor Model No. CZ-CFUNC1U For your safety Read the following instructions carefully, and carry out secure installation and electrical work. The precautions given in this manual
More informationEM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters
Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is
More informationE3xA, E3xB, E3xC, E3xE
ZL0140-0C Page 1 of 21 2017 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0717 Commissioning Guide Power Monitoring E34E E31 * E30E & E31E E34A E30 *The CE mark indicates RoHS2
More informationInstallation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE
IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL
More informationDANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.
Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,
More informationQuick Start Guide TS A
Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer
More informationB+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1.
SDM630 Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 203 V. Important Safety Information is contained in the Maintenance section. Familiarize yourself with this
More informationUMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM
20 Channel Branch Circuit Monitoring Device with RCM RCM Harmonics via analysis channel Alarm management GridVis Analysis software 20 current channels Interfaces / communication RS485 RTU Accuracy of measurement
More informationNEW ERA METER. Installation & Operation Guide NE METER
NEW ERA METER Installation & Operation Guide NE METER Autoranging Power Supply Installation Diagnostics Per Phase Voltage & Current kwh, Demand and TOU 0.2% Accuracy -40 C to +85 C Watertight Enclosure
More informationSatellite INSTALLATION GUIDE
N3 Satellite INSTALLATION GUIDE ! WARNING! Shock Hazard. May result in serious injury or death. Turn power OFF at circuit breaker or remove fuse. Damage to this product caused by wiring with power on voids
More information3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE
3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE -ST-01 Page 1 of 10 November 2016 2016 Copyright Lite-On Technology Corporation ALL RIGHTS RESERVED. Lite-On is a trademark of Lite-On Technology
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
More informationINSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F
PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4
More informationMultifunction Transducer MT440
Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up
More informationSymmetra PX 160. Maintenance Bypass Enclosure. Installation 05/
Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries
More information*Approved by CSA for non-hazardous locations (Group Safety Publication IEC Third Edition).
PowerCore Model MPC-20 Installation Manual *Approved by CSA for non-hazardous locations (Group Safety Publication IEC 61010-1 Third Edition). Products covered in this document comply with European Council
More informationModel 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit
More informationTraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE
TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions
More informationTechnical data sheet. PowerLogic power-monitoring units EM3500 series DIN Rail meter
Technical data sheet PowerLogic power-monitoring units series DIN Rail meter The Series DIN Rail Meter combines exceptional performance and easy installation to deliver a cost-effective solution for power
More informationPV Rapid Shutdown device
PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.
More informationINTEGRA DIGITAL METERING SYSTEMS
CROMPTON INSTRUMENTS INTEGRA DIGITAL METERING SYSTEMS INTEGRA DIGITAL METERING SYSTEMS The Integra digital metering product portfolio offers an extensive range of systems designed to suit any power monitoring
More informationMODULAR CIRCUIT MONITORING SYSTEM
MODULAR CIRCUIT MONITORING SYSTEM Contact Anord Mardix (USA) Inc. 3930 Technology Court Sandston, VA 23150 Email: us.sales@anordmardix.com Call: +1 800 228 4689 www.linkedin.com/company/anordmardix www.twitter.com/anordmardix
More informationTechnical Specifications. Dual Source kwh Energy Meter
Technical Specifications of Dual Source kwh Energy Meter (SPKG300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email
More informationWa r n i n g-wa r n i n g-wa r n i n g
Installation Instructions of the Power Analyzer Wa r n i n g-wa r n i n g-wa r n i n g Read and understand this manual before connecting device. Death, fire or serious injury can occur from using equipment
More informationMCS-POWERMETER. Getting Started Manual. MCS Total Solution for all your Control Needs
Rev. - 2017-02-13 MCS-POWERMETER 5580 Enterprise Pkwy. Fort Myers, FL 33905 e 39 9 0089 F 39 9 003 Getting Started Manual www. s ontro s. o Powermeter monitors the voltage, current, power, energy, and
More informationEM-15 / EM-20 Energy Management Switch
Installation & Operator s Manual EM-15 / EM-20 Energy Management Switch WF-9900 Series Distributed in the U.S.A. and Canada by ARTERRA DISTRIBUTION Phone (877) 294-8997 Warranty: warranty@wfcoelectronics.com
More informationPowerLogic EM4000 series
PowerLogic Multi-circuit energy meters Technical datasheet Functions and characteristics PB113714 The compact PowerLogic multi-circuit energy meter from Schneider Electric enables reliable monitoring building
More informationNature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual
Nature Power Inverters Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w Owner s Manual Modified Sinewave Series True Sinewave Series For safe and optimum performance, the Power Inverter must be
More informationHUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)
HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) Instruction Bulletin 8222-0513B Retain for future use. SPIKESHIELD Wired-In Branch Panels 8222-0513B 05/2012 Table of Contents Precautions...
More informationPRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5
PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5 1 Safety instructions...3 2 Foreword...4 3 CE certificates...5 4 MID certificate...7 5 Performance criteria...8 6 Specifications...8
More informationLXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual
LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp Single phase two wire DIN rail energy meter (One module) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic
More informationSDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)
SDM120 SERIES Single phase two wire DIN rail energy meter (One module) User manual ------------ 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Dimension
More informationBCPM Series Panelboard Monitoring Systems
BCPM Series Panelboard Monitoring Systems BCPME User Guide Panelboard Monitoring System with Ethernet Communication, Solid-Core Branch Current Sensors (other current sensor strip sizes available) www.schneider-electric.com
More informationPRO-1250D CT MID DIN rail three phase four wire energy meter.
PRO-1250D CT MID DIN rail three phase four wire energy meter. 1.1 Safety instructions 1.2 Foreword 1.3 MID certificate 1.4 Performance criteria 1.5 Specifications 1.6 Basic errors 1.7 Description 1.8 Dimensions
More informationMultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation
MultiCube Single Phase Multi-Function Electricity Meter Installation and Operation PREFACE MultiCube Single Phase Meter Operating Guide Revision 5.01 August 2002 This manual represents your meter as manufactured
More informationElectronic Submeter with Advanced WiFi Ethernet Capability
SH RK 100S Electronic Submeter with Advanced WiFi Ethernet Capability AGGRESSIVE TECHNOLOGY W NEIndustry Leading Technology High Performance Metering Technology 0.2% Accuracy Class Revenue Certifiable
More informationModified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.
Modified Sinewave Power Inverter 1000/1500 MW 1210, MW1215 True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220 Owner s Manual Modified Sinewave Series True Sinewave Series 1. INTRODUCTION Thank you
More informationInstallation Job Aid for VSP 4850GTS
Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe
More informationDEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S
Multi-instrument 4921210107G Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Intelligent Suitable for all 3-phase network topologies Replaces transducers Accuracy U,
More informationSLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001
SLATE Digital I/O Module R8001D4001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform
More informationAutoranging True RMS Multimeter User Manual
Autoranging True RMS Multimeter User Manual Please read this manual before switching the unit on. Important safety information inside. Contents Page 1. Safety Information... 4 2. Safety Symbols... 5 3.
More informationIDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:
IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-773 61-775 The Service Information provides the following information: Precautions and safety information Specifications Performance test procedure Calibration
More informationHT2000 Transverter Installation & Operation Manual
HT2000 Transverter Installation & Operation Manual 1 A message from the team at Heart Transverter S.A. Thanks for your recent purchase of the HT2000 Power inverter in combination with the HTREM Remote
More informationINSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING
NEED HEL? Call 1-866-660-8864 INSTALLATION INSTRUCTIONS rotocol Energy Meter and Current/Voltage Transducers The is a three channel meter, capable of monitoring single-phase, two-phase and three-phase
More informationCEM M-RS485 INSTRUCTION MANUAL (M014B A)
Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could
More informationExplosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter
Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2
More informationUser Guide True RMS Multimeter Extech EX205T
User Guide Extech EX205T True RMS Digital Multimeter Extech EX210T True RMS Digital Multimeter IR True RMS Multimeter Extech EX205T Introduction Thank you for selecting the Extech EX205T True RMS Auto-ranging
More informationU niversal Measuring Device UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs. Digital I/O
U niversal Measuring Device Little Fieldbus Giant Modbus / Profibus Harmonics Memory Analogue outputs Digital I/O Modem Recorder Profibus Modbus PC I/O Universal Measuring Device Application Application
More informationAPM Power Meter User Guide. CAUTION: Risk of Danger Read complete instructions prior to installation and operation of the unit
APM Power Meter User Guide! CAUTION: Risk of Danger Read complete instructions prior to installation and operation of the unit CAUTION: Risk of electric shock Before installation please read the safety
More informationMU110-6U. Analog output module 6 channel. User guide
MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)
More informationPrincipal LED Street Stik Fluorescent Bulb Replacements
Principal LED Street Stik Fluorescent Bulb Replacements LED Retrofit Guide (PL-RT1-001) WARNING Installation must only be performed by a licensed electrician. To prevent death, injury or damage to property
More informationCVM-B100 CVM-B150 INSTRUCTION MANUAL (M010B B)
Power analyzer CVM-B100 CVM-B150 INSTRUCTION MANUAL (M010B01-03-16B) 2 Safety precautions Follow the warnings described in this manual with the symbols shown below. DANgeR Warns of a risk, which could
More informationINSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)
Surge-Trap STZ-R series Surge Protective Device (SPD) Danger Hazard of Electrical Shock, Explosion or Arc Flash Only qualified licensed electricians should install or service SPDs Verify that all power
More informationDigital Multifunction Meters. Digital Multifunction Meters
Digital Multifunction Meters Digital Multifunction Meters DIGITAL MULTIFUNCTIOL METERS SECTION INDEX 1. MFM 3410 3420 3430 3440 6100 & 2000 - Multifunctional Instrument Series 2. EM 3490, 3490SS, 3490DS
More informationPrincipal LED Qwik Stik Fluorescent Bulb Replacements
Principal LED Qwik Stik Fluorescent Bulb Replacements LED Retrofit Guide (PL-RT1-001) WARNING Installation must only be performed by a licensed electrician. To prevent death, injury or damage to property
More informationData Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D
WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low
More informationMini Digital Multimeter
User Manual Mini Digital Multimeter Model MN15A Additional User Manual Translations available at www.extech.com Introduction Congratulations on your purchase of the Extech MN15A MultiMeter. The MN15A offers
More informationInstallation Job Aid for VSP 4450GTX-HT- PWR+
Installation Job Aid for VSP 4450GTX-HT- PWR+ Notices Release 6.1.0.0 NN46251-305 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs
More informationIPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017
163C Single-Phase Multifunction Meter User Manual Version: V1 August 20, 2017 This manual may not be reproduced in whole or in part by any means without the express written permission from IPD. The information
More informationCU port USB 2.0 hub. Version: 1.1 Date:
CU8004-0000 4 port USB 2.0 hub Version: 1.1 Date: 2006-08-11 Table of Contents Table of Contents 1 Foreword 1 1.1 Notes on the documentation 1 1.1.1 Liability Conditions 1 1.1.2 Conditions of delivery
More informationSurge Protective Devices. STV100K Series. Instruction Manual
Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage
More informationACUREV Three-Phased DIN-Rail Multifunction Meter FEATURES
ACUREV 1310 Three-Phased DIN-Rail Multifunction Meter FEATURES Revenue grade accuracy: ANSI C12.20 0.5 Class Measurement Canada approved Tamper-proof sealing design approved for revenue applications Wide
More informationSurge Protective Devices. STV100K Series. Instruction Manual
Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage
More informationBFM-II BFM-II BRANCH FEEDER MONITOR. Highlights
BRANCH FEEDER MONITOR SATEC s is the second generation of Branch Feeder Monitor, providing energy management for multi-point power solutions. Ideal for both new and retrofit projects, the automatically
More informationInstallation and Operation Manual
Installation and Operation Manual APC 2X Series Hardwire Products PMP2X-A PMF2X-A PMG2X-A PMH2X-A APC hardwired products are designed to provide specification-grade performance at the service entrance,
More informationINSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING WARRANTY DISCLAIMER
NEED HEL? Call 1-866-660-8864 INSTALLATION INSTRUCTIONS rotocol Energy Meter and Current/Voltage Transducers The is a three channel meter, capable of monitoring single-phase, two-phase and three-phase
More informationEnerSure Installation Guide
EnerSure Installation Guide Danger!!! The electrical components of this system may contain voltage and /or amperage sufficient to injure or kill. Installation is only to be performed by a licensed, bonded
More informationSync Control. Installation/Operation Manual Rev. E
9 315 Sync Control Installation/Operation Manual 164201140 Rev. E ------------------------------------------------------------------------ ------------------------------------------------------------------------
More information