Instruction Sheet Board Style Low Water Cutoff

Size: px
Start display at page:

Download "Instruction Sheet Board Style Low Water Cutoff"

Transcription

1 Instruction Sheet Board Style Low Water Cutoff SUPERSEDES: REVISION E DATED December 12, 2007 # REV F PLANT ID US Patents 6,904,800, 7,243,540, and 7,317,993 Other Patents Pending Contact Ratings* Voltage Motor Switch Rating Pilot Rating Full Load Locked Rotor 24 VAC VA 120 VAC 7.5 A 43.2 A 125 VA 240 VAC 3.75 A 21.6 A 50 or 60 Hz * 1A resistive at 120 F to 150 F (49 C to 66 C) EFFECTIVE: January 6, 2009 Listings/Approvals: UL GUIDE (MBPR2) for Limit Controls per UL Standard 353 Limit Controls - Component UL GUIDE (MBPR8) Controls, Limit Certified for Canada - Component per CSA Standard C22.2 Delays: Probes: 3 Second Delay on Break, (DOB) 1/2 Second Delay on Make, (DOM) Sold Separately. All Taco probe styles are compatible with LTB Ambient Temperature: -40 F to 150 F (-40 C to 66 C) Probe Sensitivity: Extended operation to 40K Ohms Open Collector Outputs: Maximum current 50 5 VDC - 24 VDC Enclosure: None, PCB assembly only. For indoor use only. Mounting holes to permit stand-off mounting on customer supplied plate and housing. Reset: Testing: Configurable as automatic or manual reset style. When a normally closed switch is connected, device will be a manual reset device that looks for opening of reset switch. The LTB is fully compliant with CSD-1 requirements. Externally supplied test switch can be wired in series with probe connection to open probe circuit simulating a low water condition. ** 24VAC to be supplied by an EXTERNAL Class 2 power source. Input Voltage Power Consumption 24 VAC** 3 VA GENERAL The Board Style Low Water Cutoff (LTB) is an advanced, microprocessor based low water cutoff for detecting the presence of water in a boiler. The LTB uses advanced signal processing to identify when the probe signal levels have decreased due to possible fouling. These advanced technologies permit extended operation for probe impedance up to 40K Ohms. The LTB functions longer without requiring probe cleaning, and it functions normally under nonideal installation conditions. The LTB is designed for use with hot water boilers and hot water heating boilers. (See each boiler manufacturers' specifications for recommended minimum safe water levels). During a low water condition, the "Status" LED will illuminate RED. Under normal conditions, it will illuminate GREEN. See "Status LED States" table for details. Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. Read all instructions carefully and understand them before starting installation. Save instructions for future use. Instruct user how to test and operate this cutoff device as described in these instructions. Shock Hazard. Disconnect power source before servicing. Serious injury or death could result. Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. The LWCO device must be installed in series ahead of other limit and operating controls installed on the boiler. When installations are complete, check for correct operation of ALL limit and operating controls. Wire insulation must be rated at 167º F (75º C) or greater, over copper conductors only. Use of other wire or insulation types could result in fire causing property damage, serious injury, and death. Foam in boiler or piping can cause improper operation. If the boiler is foaming, shutdown the boiler and clean it per the manufacturers recommendations to eliminate foaming. Failure to do so could result in damage to the equipment and property or could cause an explosion resulting in serious injury or death. For use with hot water boilers and hot water heating boilers only. Use on steam boilers could cause improper operation resulting in property damage, serious injury, and death. Hot or pressurized boiler systems can discharge steam and hot water. Cool boiler system to 80º F (27º C) and to 0 psi (0 bar) before servicing. Failure to do so could result in serious burns. Do not use manual reset low water cutoffs with automatic water feeders. Flooding, equipment damage, and property damage can result. Only use automatic water feeders with automatic reset low water cutoffs.

2 PROBE SPACING REQUIREMENTS Fig. 1 FEATURES & CONNECTOR LOCATIONS Fig. 2 Open Collector Outputs, (Model LTB024A Only) O.C. 24VAC / CONTROL Connector, J3 PIN 1 PIN 2 PIN 3 Status LED 6 J3 3 Header, J4 RESET Connector, J2 J2 24VAC/ CONTROL PIN 2 - Do not mount device with probe angled upward or deposits can accumulate in the probe. - Mount only with probe facing horizontally or vertically downward and maintain 1/4" minimum clearance from electrode and pipe wall. - Failure to install probe as directed can cause improper operation and damage to equipment and property. P Alternate Probe Connector RESET GND J4 Alternate Chassis Ground Connector Relay J4 PIN 1 Item Status LED 24VAC/CONTROL Connector RESET Connector Open Collector Outputs Bi-color LED status indicator. See "Status LED States" table for details. 24VAC power connections. Probe connection. Connections to Form C relay. Connections to a manual reset switch, if present in system. Open collector outputs are available on LTB024A models for driving remote LED's, relays, buzzers, or other equipment that is powered by DC power sources from 5-24VDC. Status LED States: Mode Color/State Contacts Meaning Steady Green COM-NC Normal Steady Red COM-NO Low Water Condition or weak probe signal Blinking Red COM-NO Control Failure. Lockout in Low Water Condition Steady Off COM-NO No power to LWCO LTB Connectors: Connector Designator LTB Connector Open Collector Connector AMP, MTA-100 Friction Lock Header, Reset Connector J2 AMP, Mini-Universal Mate-N-Lok, VAC/Control Connector J3 AMP, Mini-Universal Mate-N-Lok,

3 RESET Connector - J2 and Alternate Connectors: Position 1 Reset switch 2 Reset switch 3 Chassis GND Connection (alternate) P Alternate probe connection - 3/16" male quick disconnect GND Alternate chassis ground connection - 1/4" male quick disconnect 24VAC/CONTROL Connector - J3: P J RESET GND Position 1 Alarm Output, NO relay contact - normally open to COM with normal water level and control operation 2 24VAC Common / Chassis GND Connection 3 Probe connection, electrode 4 Low Water Output, NC relay contact - normally closed to COM with normal water level and control operation. 5 Safety Circuit, COM relay contact 6 24VAC Power 24VAC/ CONTROL J Open Collector Outputs (Model LTB024A only) The LTB024A is offered with open collector outputs for signaling purposes. These outputs can drive relays, LED indicators, or other equipment. When turned on, each output can sync up to 50mA at a voltage from 5 VDC to 24 VDC. The DC supply return must connect to Pin 2 of connector. PIN 1 PIN 2 PIN 3 Pin Number 1 Low Water Open Collector Output 2 DC Supply Return 3 Status Open Collector Output Low Water Status Output Mode State Meaning Status Steady On LTB has power Status Steady Off No power to LTB Low Water Steady Off Normal Low Water Steady On Low Water Condition Low Water Pulsed On/Off Control Failure. Lockout in Low Water Condition Example Wiring of External Indicators Using Open Collector Outputs: Low Water DC Return Status O.C VDC Power Source Current Limit Resistors LED Indicators DC supply return must be connected to open collector connector as shown. Failure to do so could result in damage to equipment or property. Open collector outputs must be externally current limited. Failure to do so could result in damage to equipment or property.

4 Configuring Reset Style: The LTB defaults to an automatic reset control. Upon power up, if the LTB does not detect a manual reset switch between pins 1 and 2 of the RESET connector, J2, the LTB is configured for automatic reset. When water covers the LTB probe, LTB enters normal operation. Upon power up, if the LTB detects a normally closed, manual reset switch between pins 1 and 2 of the RESET connector, J2, the LTB is configured for manual reset. After a low water condition, pressing the manual reset button while water covers the LTB probe resets the LTB for normal operation. Once the LTB is configured for manual reset, it remains as manual reset until it is re-configured. Refer to Fig. 2 for the location of the "RESET" connector, J2, and pins 1 and 2. Re-configuring Reset Style: If the reset style needs to be changed to automatic reset, re-configure the LTB. 1. Unplug the "24VAC/CONTROL" connector to remove power from the LTB. (See Fig. 2 for location of the "24VAC/ CONTROL" connector.) 2. Be sure no manual reset switch is connected to the LTB. 3. Use a small wire to short pins 1 and 2 together on header J4. (See Fig. 2 for J4 location.) 4. Plug-in the "24VAC/CONTROL" connector to apply power to the LTB. The LTB blinks the "STATUS LED" red to indicate that the reset style is erased. 5. Unplug the "24VAC/CONTROL" connector to remove power from the LTB. Remove the wire shorting pins 1 and 2 of header J4. 6. Plug the "24VAC/CONTROL" connector to apply power to the LTB. The LTB powers up and configures the reset style as noted in the "Configuring Reset Style" section. All LTB devices have the reset style configured to automatic reset prior to leaving the factory. Installation: 1. Install the probe above the minimum safe water level, as determined from the boiler manufacturer's literature. NOTE: This may be in a tapping on the boiler or in the boiler supply or return piping. 2. Install the probe to extend into the boiler cavity or piping to make contact with the water. 3. Install the probe so that the exposed portion of the stainless steel is a minimum of 1/4" from any grounding surface inside the boiler (to prevent the probe from shorting). (See Fig. 1) 4. Tighten probe securely with a wrench, using bushing flats provided. Use pipe thread sealant to seal the probe threads. Wiring: 1. Connect OEM provided plugs to the 24 VAC/Control connector J3 and to Reset connector J2. NOTE: In automatic reset applications, no connections to the Reset connector J2 are required. 2. If connections are provided for the alternate probe, install the connection in the spade terminal marked P. 3. If connections are provided for the chassis ground connections, install the connection in the spade terminal marked GND. NOTE: In systems where the AC Common is not connected to the chassis, use one of the alternate chassis ground connections. Refer to wiring diagrams in Fig. 3 and On model LTB024A, connect OEM provided plug to the O.C. connector to provide connections for open collector outputs. 3. Remove outer locknut on the probe. Install the ring terminal connection from the probe connection on pin 3 of 24 VAC/Control connector J3 and secure the locknut over the ring terminal. NOTE: Do not install bare wire under locknut. 4. The LTB design permits relay outputs to be either 24VAC or 120VAC. 120VAC circuits may only be connected to relay terminals on the 24 VAC/Control connector J3. Refer to wiring diagram in Fig. 4. Install probe wiring with ring terminal. Do not install bare wire between probe locknuts. LTB power source is 24 VAC. Do not connect line voltage to pins 2 or 6 on the "24 VAC/Control" connector J3. Use only copper conductors at lease 18 AWG or as required by code. Insulation must be rated at 167 F (75 C) or greater. Failure to wire as shown in these instructions can cause improper operation, damage to equipment and property, or serious injury.

5 TYPICAL WIRING FOR 24VAC BURNER SYSTEM Fig. 3 TYPICAL WIRING FOR 120VAC BURNER SYSTEM Fig. 4

6 Dimensions: A 0.78" 0.22" 0.56" B Probe Model Dimension "A" Dimension "B" P8S-1 Standard 1.95" 1.17" P8N-1 Extended Electrode 2.95" 2.17" 3/8" NPT 11/16" Hex Low Water Cutoff Test Button LWCO Ordering L T B 024 S 1 B S A Style Standard Open Collector Annunciators Input Power VAC LWCO Type Board Style Probe Probe Only Ordering P 8 S 1 8 Probe Style S Standard Probe Electrode N Extended Length Probe Electrode Process Connection 3/8 NPT Controls Made Easy TACO, INC., 1160 Cranston Street, Cranston, RI Telephone: (401) FAX: (401) TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/ FAX: 905/ Manufactured by POTTER ELECTRIC SIGNAL CO., St. Louis, MO Visit our web site at: Printed in USA Copyright 2008 TACO, Inc.

Manual. Water Vend Controller Model ESDI WARNING! ELECTRICAL SHOCK HAZARD! AUTHORIZED PERSONNEL ONLY. EXPOSED 120 VAC ON CIRCUIT BOARD

Manual. Water Vend Controller Model ESDI WARNING! ELECTRICAL SHOCK HAZARD! AUTHORIZED PERSONNEL ONLY. EXPOSED 120 VAC ON CIRCUIT BOARD Manual Water Vend Controller Model ESDI 030400 WARNING! ELECTRICAL SHOCK HAZARD! AUTHORIZED PERSONNEL ONLY. EXPOSED 120 VAC ON CIRCUIT BOARD THE CIRCUIT BOARD HAS MANY EXPOSED AREAS THAT ARE AT 120 VAC.

More information

PV Rapid Shutdown device

PV Rapid Shutdown device PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.

More information

MAXIMA+ Series Rotary Level Indicator

MAXIMA+ Series Rotary Level Indicator MAXIMA+ Series Rotary Level Indicator BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE

More information

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit

More information

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual Your Global Flow Control Partner Series 50 Valve Status Monitor Table of Contents 1. Definition of Terms... 2 2. Safety... 2 3. Storage... 3 4. Commissioning... 3 4.1. Mounting your VSM... 3 4.2. Wiring

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 Rev. A

More information

KOBOLD TDA Series Digital Temperature Transmitter

KOBOLD TDA Series Digital Temperature Transmitter KOBOLD TDA Series Digital Temperature Transmitter TDA-15 Series User Instructions KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com

More information

Replacing the Power Supply

Replacing the Power Supply APPENDIX B This appendix includes information on how to replace the power supply for the Cisco AS550XM universal gateway and contains the following sections: Safety Recommendations, page B-1 Required Tools

More information

S66 Series Electronic Fan Speed Control

S66 Series Electronic Fan Speed Control FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,

More information

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual.  Page 1 of 13 Battery Controller Module TSP-BCM24, TSP-BCM24A TSP-BCM48, TSP-BCM48A Operating Instruction Manual http://www.tracopower.com Page 1 of 13 Dimensions drawings: TSP-BCM24 & TSP-BCM48 Weight: 0.816lb Gewicht:

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Rotork Fairchild PAX1 Linear Actuator User s Manual

Rotork Fairchild PAX1 Linear Actuator User s Manual Rotork Fairchild PAX1 Linear Actuator User s Manual Product Overview The PAX1 is a flexible low voltage DC powered linear actuator featuring a 5 mm maximum thrust rod stroke moving at speeds up to 0 mm/min

More information

RUC industrial relays of small dimensions

RUC industrial relays of small dimensions Contact data Number and type of contacts Contact material Rated / max. switching voltage Min. switching voltage Rated load Min. switching current Max. inrush current Rated current Max. breaking capacity

More information

C-POWER AC AUTOMATIC CONTROL

C-POWER AC AUTOMATIC CONTROL Issue 1 Print 1 C-POWER AC AUTOMATIC CONTROL INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model: 93 ACMC100I A Charles Industries, Ltd. All rights reserved. Printed in the United States of America. Issue

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 TABLE OF

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

high RESISTANCE STOPLIGHT Instruction Manual C-101EM

high RESISTANCE STOPLIGHT Instruction Manual C-101EM stoplight high RESISTANCE GROUNDING SYSTEM STOPLIGHT Instruction Manual C-101EM high resistance grounding protection The StopLight system uses a unique indicator light system to provide visual detection

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

ZC Series Zone Monitoring Controllers

ZC Series Zone Monitoring Controllers ZC Series Zone Monitoring Controllers Installation Instructions MANUAL Reset Controllers Model Description Part Number ZC-1 1 Zone Controller 0421 ZC-2 2 Zone Controller 0422 ZC-3 3 Zone Controller 0423

More information

Sidewinder Pumps Inc. AC C1D2 Timer/Controller

Sidewinder Pumps Inc. AC C1D2 Timer/Controller Sidewinder Pumps Inc. AC C1D2 Timer/Controller Page 1 of 14 Rev 4/26/17 Table of Contents 1. Warnings --------------------------------------------------------------------------------------------------

More information

S7999D SOLA Operator Interface Display

S7999D SOLA Operator Interface Display S7999D Operator Interface Display INSTALLATION INSTRUCTIONS APPLICATION The S7999D is microprocessor-based color touch-screen Operator Interface (OI) display that provides an operator interface for monitoring

More information

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application WWW.PHIHONG.COM 60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3bt Standard Non-Vented Case with Mounting Bracket

More information

KOBOLD PDA Series Digital Pressure Transmitter

KOBOLD PDA Series Digital Pressure Transmitter KOBOLD PDA Series Digital Pressure Transmitter PDA-153 Series User Instructions KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com

More information

INSTRUCTION MANUAL DIGI-LOCK. Keyless Entry System. Installation. Programming. Troubleshooting. BASE Industries

INSTRUCTION MANUAL DIGI-LOCK. Keyless Entry System. Installation. Programming. Troubleshooting. BASE Industries INSTRUCTION MANUAL DIGI-LOCK Keyless Entry System Installation Programming Troubleshooting BASE Industries 45 Pomona Rd. Corona, CA. 9880 Revision F TABLE OF CONTENTS OWNER REGISTRATION CARD INTRODUCTION

More information

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-STC Kelvin Standard Triaxial Connector Card Description The Model 8020-STC Kelvin Standard

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

RUC industrial relays of small dimensions

RUC industrial relays of small dimensions with adaptor (V) with adaptor (H) Power relays of general application AC and DC coils Mounting: in sockets; 35 mm rail mount acc. to PN-EN 60715; on panel; PCB Versions: faston 187 (4,8 x 0,5 mm); faston

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

ASI Systems ML5720A Series

ASI Systems ML5720A Series ML5720A Series Electric Linear Valve Actuators Non-Spring Return APPLICATION The ML5720A series actuators operate standard ASI Systems valves in heating, ventilating and air conditioning (HVAC) applications.

More information

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW) Characteristics soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW)/500V(45kW) Price* : 683.00 GBP Main Range of product Altistart 22 Product or component type Product destination Product

More information

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data: Instruction Manual M Pump Motor Controller For file reference, please record the following data: Model No: Serial No: Installation Date: Installation Location: When ordering replacement parts for your

More information

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies ADC7520 SERIES 1600W Battery Chargers and Power Supplies Wide output adjustment range 0 72VDC Analog control by external 0-5VDC voltage Temp.comp charging, sense as on option Power fail relay alarm Master-Slave

More information

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0 BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

1 Description. 2 Specifications. Product Installation Document. Honeywell 12 Clintonville Road Northford, CT

1 Description. 2 Specifications. Product Installation Document. Honeywell 12 Clintonville Road Northford, CT Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULACM4CB HP600ULACM8CB Access Control Power Supply/Charger with Power Distribution Controller PN 52395:A 1/05/06 ECN

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

Sidewinder Pumps Inc. AC Timer/Controller

Sidewinder Pumps Inc. AC Timer/Controller Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.

More information

FDS / FDS-R / FDS-PS

FDS / FDS-R / FDS-PS FDS / FDS-R / FDS-PS USER MANUAL For use with 120V 60Hz input. Output is 120V 60Hz at 5amps 600W MAX. switched. ETL LISTED Conforms to UL STD 1241 3091594 79-15167-00 REV. A www.fiberstars.com Page 1 of

More information

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Rhino Redundancy Module PSM24-REM360S. Operating Instructions Rhino Redundancy Module PSM4-REM360S Operating Instructions RHINO REDUNDANCY MODULE PSM4-REM360S Description With this module and two power supplies of the PSM series (78, 90, 56, 80 and 360 watt models),

More information

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-KHV Kelvin Keithley Triaxial Connector Card Description The Model 8020-KHV Keithley HV Connector

More information

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW) Product data sheet Characteristics ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW) Complementary Assembly style Function available Power supply voltage limits Main Range of

More information

RUC-M industrial relays for DC loads

RUC-M industrial relays for DC loads Contact data Number and type of contacts Contact material Rated / max. switching voltage Min. switching voltage Rated load Min. switching current Max. inrush current Rated current Min. breaking capacity

More information

P522 Signal Processor

P522 Signal Processor P522 Signal Processor INSTALLATI INSTRUCTIS Self-Check Contact Ratings: Max switching power - 60 W 125Vac Max switching voltage - 220VDC, 250Vac Max switching current - 2A DC, AC Analog Flame Signal: User

More information

Conveyor Belt Alignment Switches from IDEM

Conveyor Belt Alignment Switches from IDEM Conveyor Belt Alignment Switches from IDEM Data Sheet Die-Cast Models Python Line Series Stainless Steel Models Using Conveyor Belt Alignment Switches Application: Conveyor Belt Alignment switches are

More information

RM699B miniature relays

RM699B miniature relays Version (V) Contact data Number and type of contacts Contact material Max. switching voltage Min. switching voltage Rated load Min. switching current Max. inrush current Rated current Max. breaking capacity

More information

Mechanically Activated Device for Dry Run Protection in Applications with LORENTZ Solar Pump Systems

Mechanically Activated Device for Dry Run Protection in Applications with LORENTZ Solar Pump Systems Well Probe Mechanically Activated Device for Dry Run Protection in Applications with LORENTZ Solar Pump Systems The switch can be used to detect the water level within a well. When the water level in the

More information

Installation Job Aid for VSP 4850GTS

Installation Job Aid for VSP 4850GTS Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe

More information

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW) Characteristics soft starter-ats22-control 220V-power 230V(15kW)/400...440V(30kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

ASI Systems ML5740A Series

ASI Systems ML5740A Series ML5740A Series Electric Linear Valve Actuators Non-Spring Return APPLICATION The ML5740A series actuators operate standard ASI Systems valves in heating, ventilating and air conditioning (HVAC) applications.

More information

CS2 DMX Distribution Splitter

CS2 DMX Distribution Splitter CS2 DMX Distribution Splitter User Manual Order code: BOTE72 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up,

More information

EAP 300 REMOTE ANNUNCIATOR INSTALLATION MANUAL. r.0454a

EAP 300 REMOTE ANNUNCIATOR INSTALLATION MANUAL. r.0454a EAP 300 REMOTE ANNUNCIATOR INSTALLATION MANUAL r.0454a PM084 Rev 0 08/06/20 9087A 198 th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110 Telefax (604) 888-3381 E-Mail: info@thomsontechnology.com

More information

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW) Characteristics soft starter-ats22-control 220V-power 230V(110kW)/400...440V(220kW) Complementary Assembly style Function available Power supply voltage limits Main Range of product Altistart 22 Product

More information

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual Omnitron Systems Technology, Inc. 1 iconverter 19-Module Managed Power Chassis User s Manual 27 Mauchly, #201, Irvine, CA 92618 Phone: (949) 250-6510; Fax: (949) 250-6514 2 Omnitron Systems Technology,

More information

Input Frequency: 650 range 50/60Hz 675 range Hz Input Ranges in Amps: Measurement Maximum Inrush

Input Frequency: 650 range 50/60Hz 675 range Hz Input Ranges in Amps: Measurement Maximum Inrush Features Mini Housing Size Housing Product overview The AX-CSG-xxx range of s are a range of solid state transducers that convert the primary Ac circuit current to a proportional analogue signal. The sensors

More information

Instruction Bulletin. Fiber Optic Switch Packs. SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION CONTENTS OF THE BOX

Instruction Bulletin. Fiber Optic Switch Packs. SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION CONTENTS OF THE BOX Instruction Bulletin 63249-500-04A3 07/2010 Fiber Optic Switch Packs SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION SLSPSP101 Single Input Switch Pack SLSPSP102 Dual Input Switch Pack The

More information

Posi-Lok Plugs and Panels

Posi-Lok Plugs and Panels THE SAFEST ELECTRICAL SYSTEM FOR HIGH AMPERAGE CONNECTIONS, POSI-LOK IS PART OF THE CAM-LOK FAMILY OF CONNECTORS. THE GROUND ALWAYS MAKES FIRST AND BREAKS LAST ALL POSI-LOK SYSTEMS ARE UL LISTED AND CSA

More information

GCI-5K INSTALLATION AND OPERATOR S MANUAL

GCI-5K INSTALLATION AND OPERATOR S MANUAL GCI-5K INSTALLATION AND OPERATOR S MANUAL Grid-tied inverter for wind Ningbo Ginlong Technologies 1 INTRODUCTION 2 SAFETY GUIDELINES AND WARNINGS 3 INSTALLATION 3.1 Selecting a location for the inverter

More information

INSTALLATION MANUAL SLI 50 INVERTER

INSTALLATION MANUAL SLI 50 INVERTER INSTALLATION MANUAL SLI 50 INVERTER www.unipowerco.com Manual No. SLI-50-48-3 2016 UNIPOWER LLC All Rights Reserved UNIPOWER LLC 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA sales@unipowerco.com

More information

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp)

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp) Characteristics softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp) Main Range of product Altistart 22 Product or component type Product destination Product specific application

More information

SMI-100 Stack Monitoring Interface Installation & Operation Manual

SMI-100 Stack Monitoring Interface Installation & Operation Manual SMI-100 Stack Monitoring Interface Installation & Operation Manual Aquion Energy, Inc. 32 39th Street Pittsburgh, PA 15201 +1 412.904.6400 aquionenergy.com AQ-OP-00015_C 12.23.16 2016 Aquion Energy, Inc.

More information

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22D75S6U Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

Digital Keypad Introduction

Digital Keypad  Introduction K2 Digital Keypad Introduction The K02 uses the latest microprocessor technology to operate door strikes and security systems that require a momentary (timed) or latching dry contact closure. All programming

More information

CMSA-100 Manual. Cinema Media Server Automation

CMSA-100 Manual. Cinema Media Server Automation CMSA-100 Manual Cinema Media Server Automation 181 Bonetti Drive San Luis Obispo, CA 93401-7397 USA Phone: +1 805 549 0161 Fax: +1 805 549 0163 www.uslinc.com Table of Contents 1. Safety Notice... 3 2.

More information

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module) SDM120 SERIES Single phase two wire DIN rail energy meter (One module) User manual ------------ 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Dimension

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) SUITABLE FOR EXTERNAL DISTRIBUTION

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) SUITABLE FOR EXTERNAL DISTRIBUTION ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 ES-Key 12- Relay Board P/N 103190 and 103338 PAGE 1 of 13 1. REVISI LOG... 2 2. OVERVIEW... 3 2.1. PART NUMBERS... 3 2.2. MODULE

More information

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h Characteristics soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h Complementary Assembly style Function available Power supply voltage limits Main Range of product Altistart

More information

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter Install Guide Revision C (12/18) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Revision C (12/18) Turn off all power supplying equipment

More information

Scanner 2000 Steam Mass Flow Transmitter

Scanner 2000 Steam Mass Flow Transmitter 3352051/2 IM-P335-24 MI Issue 2 Scanner 2000 Steam Mass Flow Transmitter Installation and Maintenance Instructions 1. Safety information 2. Mechanical installation 3. Configuring software 4. Wiring procedures

More information

PGR-3200 MANUAL INSULATION MONITOR

PGR-3200 MANUAL INSULATION MONITOR Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-3200 MANUAL INSULATION MONITOR REVISION 3-E-040918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document Number: PM-1025-EN

More information

Installation Job Aid for VSP 4450GTX-HT- PWR+

Installation Job Aid for VSP 4450GTX-HT- PWR+ Installation Job Aid for VSP 4450GTX-HT- PWR+ Notices Release 6.1.0.0 NN46251-305 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

A-dec 570L Dental Light on a DCS System INSTALLATION GUIDE

A-dec 570L Dental Light on a DCS System INSTALLATION GUIDE A-dec 570L Dental Light on a DCS System INSTALLATION GUIDE C ONTENTS Choose an Installation Guide...... Before You Begin.............. 3 Disconnect the Light Cable........ 3 Cut the Light Cable............

More information

ILUMEN PID SOLUTION INDOOR OUTDOOR ILUMEN PIDBOX MINI INSTALLATION MANUAL. Ilumen PIDbox mini Version 1.5

ILUMEN PID SOLUTION INDOOR OUTDOOR ILUMEN PIDBOX MINI INSTALLATION MANUAL. Ilumen PIDbox mini Version 1.5 ILUMEN PID SOLUTION ILUMEN PIDBOX MINI INSTALLATION MANUAL INDOOR OUTDOOR Ilumen PIDbox mini Version 1.5 1 TABLE OF CONTENT 1 Information on this manual... 3 1.1 Validity... 3 1.2 Target group... 3 1.3

More information

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112 SELECTRONIX, INC. WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL Models: SLC2102-SLC2112 SLC2102X-SLC2112X SLC2152-SLC2162 SLC2170-xx Relay

More information

Honeywell Model 700/800 Signal Processor and Viewing Head

Honeywell Model 700/800 Signal Processor and Viewing Head Honeywell Model 700/800 Signal Processor and Viewing Head USER MANUAL Model 700ACSP Universal 85-265 VAC powered, plus 24VDC backup. Model 700DCSP 22-26VDC powered, plus 24VDC backup. The two Model 700

More information

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1 200 HP)

More information

Connecting Power and Ground

Connecting Power and Ground This chapter explains how to connect the power and ground for NCS 2006 shelf. The sections are: Power and Ground Description, page 1 NTP-L12 Installing Power and Ground to the NCS 2006 Shelf, page 2 Power

More information

Expandable Power Systems

Expandable Power Systems Expandable Power Systems Installation Guide Models Include: Maximal11EV 12VDC @ 4A or 24VDC @ 3A. 12VDC @ 4A or 24VDC @ 3A. Maximal33EV 12VDC or 24VDC @ 6A. 12VDC or 24VDC @ 6A. Maximal37EV 24VDC @ 10A.

More information

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D D600S - D600D INSTRUCTI MANUAL SIL Switch/Proximity Detector Repeater Relay, DIN Rail, Models D600S, D600D D600 - SIL Switch/Proximity Detector Repeater Relay G.M. International ISM0- Characteristics General

More information

Model 2657A-LIM-3 LO Interconnect Module

Model 2657A-LIM-3 LO Interconnect Module Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 2657A-LIM-3 LO Interconnect Module User's Guide Description The Model 2657A-LIM-3 LO Interconnect

More information

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001 SLATE Digital I/O Module R8001D4001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform

More information

Ground Fault Protection. Instruction Manual

Ground Fault Protection. Instruction Manual Ground Fault Protection DSP OHMNI Accessory: DSP-CA(S) Cable Adapter Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR

More information

RS3000 SERIES BILL ACCEPTORS

RS3000 SERIES BILL ACCEPTORS Flash Diagnostic Codes RS3000 SERIES BILL ACCEPTORS INSTALLATION GUIDE s of the bill acceptor. Below is a chart that lists all the flash codes of the RS3000 Bill Acceptor and a description of each code.

More information

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Section Page Introduction 1 Materials Provided 1 I) Safety Instructions 1 A) Inverter Safety Instructions 1 B) Battery Safety

More information

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics. Characteristics soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Main Range of product Altistart 22 Product or component type Product destination Product specific application

More information

Installing and Configuring Rialto Analytic Appliances

Installing and Configuring Rialto Analytic Appliances Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation

More information

Installing the Cisco AS5400XM Universal Gateway

Installing the Cisco AS5400XM Universal Gateway CHAPTER 3 Installing the Cisco AS5400XM Universal Gateway This chapter guides you through the installation of the Cisco AS5400XM universal gateway and includes the following sections: Setting Up the Chassis,

More information

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22D47S6U Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

Switched Mode Power Supply Operating manual PAP800

Switched Mode Power Supply Operating manual PAP800 Features: Switched mode power supply Wide output 0 144Vdc Analog control by an external 0 5Vdc Power failure alarm output Master-slave connection Powerfinn PAP series is a high power, lightweight, advanced

More information

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B Safety Relay as a Contact Extension Block INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- 24DC/URM4/4X1/2X2/B safety relay can be used as a contact extension block in safety circuits

More information

Rack Mount Power Supplies

Rack Mount Power Supplies Rack Mount Power Supplies Installation Guide Models Include: VertiLine33D - 12VDC @ 8A - Sixteen (16) PTC protected outputs VertiLine33TD - 12VDC @ 16A - Sixteen (16) PTC protected outputs VertiLine63D

More information

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION Document 476092 User and Service Manual Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

Butterfly Laser Diode Mount

Butterfly Laser Diode Mount LM14S2 Butterfly Laser Diode Mount Operating Manual LM14S2 Laser On TEC Driver LD Driver THORLABS, Inc. Ph: (973) 579-7227 435 Route 206N Fax: (973) 383-8406 Newton, NJ 07860 USA www.thorlabs.com 10614-D02

More information

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS Installation Manual 1180 METRIX Experience Value 8824 Fallbrook Dr. Houston, TX 77064, USA Tel: 1-281-940-1802 After Hours Technical Assistance: 1-713-702-8805

More information

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English Configurable Output Distribution 120V / 208V / 240V 60Hz User Manual English TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................... 1 GLOSSARY OF SYMBOLS....................................

More information

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm Long Distance Cylindrical. Extra long for increased protection and sensing performance triple proximity sensors for flush mounting requirements. designed and tested for extra long life. Ordering Information

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW) Characteristics soft starter-ats22-control 220V-power 230V(4kW)/400...440V(7.5kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

Installation Job Aid for Ethernet Routing Switch 5900 Series

Installation Job Aid for Ethernet Routing Switch 5900 Series Installation Job Aid for Ethernet Routing Switch 5900 Series Notices NN47211-301 Issue 05.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

OV1000 Part No OV1000 HEIGHT ADJUSTABLE TABLE USER GUIDE

OV1000 Part No OV1000 HEIGHT ADJUSTABLE TABLE USER GUIDE OV1000 Part No. 23624 OV1000 HEIGHT ADJUSTABLE TABLE USER GUIDE PRODUCT OVERVIEW User Guide: OV1000 OV1000 HEIGHT ADJUSTABLE TABLE A healthier work environment starts with the option to sit or stand throughout

More information