ABB STOTZ-KONTAKT GmbH Webinar ABB i-bus KNX

Size: px
Start display at page:

Download "ABB STOTZ-KONTAKT GmbH Webinar ABB i-bus KNX"

Transcription

1 place picture here Jürgen Schilder and Thorsten Reibel ABB STOTZ KONTAKT GmbH July 2015 ABB STOTZ-KONTAKT GmbH Webinar ABB i-bus KNX Monitoring and Data Logging SMB/S 1.1 EUB/S 1.1 BDB/S 1.1

2 Monitoring Unit EUB/S 1.1 Monitoring of KNX devices Fault Monitoring Unit SMB/S 1.1 Detection and processing of fault signals Data Logging Unit BDB/S 1.1 Detection of operating hours and switching cycles DESTO Jürgen Schilder 2

3 Monitoring Unit EUB/S 1.1 Monitoring of KNX devices Fault Monitoring Unit SMB/S 1.1 Detection and processing of fault signals Data Logging Unit BDB/S 1.1 Detection of operating hours and switching cycles DESTO Jürgen Schilder 3

4 Monitoring Unit EUB/S 1.1 The Monitoring Unit EUB/S 1.1 enables monitoring of up to 100 KNX devices The KNX bus devices (members) are monitored to ensure their presence and minimum functionality (send and receive) The monitoring occurs by four different monitoring modes Furthermore, devices can be combined in up to 5 groups for monitoring purposes DESTO Jürgen Schilder 5

5 Monitoring Unit EUB/S 1.1 Devices can be monitored via the individual address or via a group address telegram Overall there are four monitoring modes available: (individually per device) Monitoring Techniques Monitoring via physical address (PA) Monitoring via group address (GA) Poll PA cyclically Poll PA by object Poll GA cyclically Receive GA cyclically DESTO Jürgen Schilder 6

6 Monitoring Unit EUB/S Monitoring mode: Poll physical address cyclically With this mode of monitoring the unit cyclically polls the physical address of the devices to be monitored to ensure that they are still present The EUB/S sends a polling request to the device to be monitored If the device is present and in operation it will respond and the EUB/S detects the device If a connection cannot be established to the monitoring device, it will be evaluated as a failure (after three repetition) DESTO Jürgen Schilder 7

7 Monitoring Unit EUB/S Monitoring mode: Poll individual address cyclically DESTO Jürgen Schilder 8

8 Monitoring Unit EUB/S Monitoring mode: Poll individual address cyclically This object is used to indicate the failure of a monitored device A failure has occurred if it is not possible to poll a physical address 3 times Object values will only be updated by alteration 0 : Operational 1 : Failured DESTO Jürgen Schilder 9

9 Monitoring Unit EUB/S Monitoring mode: Poll individual address cyclically With this object the cyclical polling of physical addresses (PA) is blocked 0 : Enable polling 1 : Block polling DESTO Jürgen Schilder 10

10 Monitoring Unit EUB/S Monitoring mode: Poll physical address cyclically Phys. addressed telegram to T_Connect Sensor Response from T_Disconnect Rocker 1 switching Rocker 2 switching 4/1/98 x/y/z Monitoring unit Device 1 4/1/98 Block connection to.. Device 1 Failure Device 2 xxx Device x xxx 0/3/47 5/1/33 0/3/47 0 on alteration Switch actuator Output A 3/1/11 Switch 7/3/112 / / Outtput A 0/5/73 Status Switching DESTO Jürgen Schilder 11 Device no. 1: cycle time 10min. Device no. 2: Device no. 3:

11 DESTO Jürgen Schilder 13

12 Monitoring Unit EUB/S Monitoring mode: Poll physical address cyclically Phys. addressed telegram to T_Connect Sensor X No response from X Rocker 1 switching Rocker 2 switching 4/1/98 x/y/z Monitoring unit Device 1 4/1/98 Block connection to.. Device 1 Failure Device 2 xxx Device x xxx 0/3/47 5/1/33 0/3/47 1 Failure! Switch actuator Output A 3/1/11 Switch 7/3/112 / / Outtput A 0/5/73 Status Switching DESTO Jürgen Schilder 14 Device no. 1: cycle time 10min. Device no. 2: Device no. 3:

13 3 repetition of the request Device 1 failure 0/3/ DESTO Jürgen Schilder 16

14 Monitoring Unit EUB/S Monitoring mode: Poll physical address by object With this mode of monitoring the devices to be monitored can be polled by other bus members in the KNX system For example, devices can be polled via a pushbutton or a time switch at a certain time If a connection cannot be established to the monitoring device, it will be evaluated as a failure (after three repetition) DESTO Jürgen Schilder 17

15 Monitoring Unit EUB/S Monitoring mode: Poll physical address by object DESTO Jürgen Schilder 18

16 Monitoring Unit EUB/S Monitoring mode: Poll physical address by object This object initiates polling of the physical address of a device to be monitored Mode of monitoring Poll physical address by object 0 : No reaction 1 : Start polling DESTO Jürgen Schilder 19

17 Monitoring Unit EUB/S Monitoring mode: Poll physical address by object This object is used to indicate the failure of a monitored device A failure has occurred if it is not possible to poll a physical address 3 times Object values will only be updated by alteration 0 : Operational 1 : Failured DESTO Jürgen Schilder 20

18 Monitoring Unit EUB/S Monitoring mode: Poll physical address by object Phys. addressed telegram to T_Connect 2/5/23 1 Start polling Response from T_Disconnect Sensor Rocker 1 switching 2/5/23 Monitoring unit Device 2 Polling 2/5/23 2/4/69 0 on alteration Switch actuator Rocker 2 switching x/y/z Device 2 Failure Device3 xxx Device x xxx 2/4/69 2/4/22 Output A 3/1/11 Switch 7/3/112 / / Output A 0/5/73 Status Switching DESTO Jürgen Schilder 21 Device no. 1: Device no. 2: Device no. 3:

19 Monitoring Unit EUB/S Monitoring mode: Poll physical address by object Phys. addressed telegram to T_Connect 2/5/23 1 Start polling No response from X X Sensor Rocker 1 switching 2/5/23 Monitoring unit Device 2 Polling 2/5/23 2/4/69 1 Failure! Switch actuator Rocker 2 switching x/y/z Device 2 Failure Device3 xxx Device x xxx 2/4/69 2/4/22 Output A 3/1/11 Switch 7/3/112 / / Output A 0/5/73 Status Switching DESTO Jürgen Schilder 24 Device no. 1: Device no. 2: Device no. 3:

20 Start polling 2/5/ repetition of the request Device 2 failure 2/4/ DESTO Jürgen Schilder 26

21 Monitoring Unit EUB/S Monitoring mode: Poll group address cyclically This mode of monitoring is also referred to as active monitoring With active monitoring the Monitoring Unit cyclically sends telegrams via group address to the device to be monitored and evaluates the telegrams received It is recommended to use a communication object (1 Bit) in the device to be monitored which has no other assignments. Read flag must be active! If the Monitoring Unit does not receive a response telegram within an adjusted time, it will be evaluated as a failure DESTO Jürgen Schilder 27

22 Monitoring Unit EUB/S Monitoring mode: Poll group address cyclically DESTO Jürgen Schilder 28

23 Monitoring Unit EUB/S Monitoring mode: Poll group address cyclically This object cyclically polls an object assigned via the group address and evaluates the response telegram If no telegrams are received after a programmed time, this is evaluated as a failure The failure is signaled by the group object Failure DESTO Jürgen Schilder 29

24 Monitoring Unit EUB/S Monitoring mode: Poll group address cyclically This object is used to indicate the failure of a monitored device A failure has occurred an expected group address telegram has not been received three times in a row 0 : Operational 1 : Failured DESTO Jürgen Schilder 30

25 Monitoring Unit EUB/S Monitoring mode: Poll group address cyclically 8/1/95 Value read 8/1/95 Value response Monitoring unit Device 3 8/1/95 Send/receive telegram Device 3 Failure 8/1/96 8/1/96 0 on alteration Switch actuator Co-object 8/1/95 Read Flag set! Device 4 xxx Device 4 xxx 2/4/22 2/4/23 Output A 3/1/11 Switch 7/3/112 / / DESTO Jürgen Schilder 31 Device no. 2:. Device no. 3: cycle time 10min max response time 5sec. Device no. 4:.

26 Cycl. polling 8/1/95 value read 8/1/95 value response DESTO Jürgen Schilder 33

27 Monitoring Unit EUB/S Monitoring mode: Poll group address cyclically 8/1/95 Value read X 8/1/95 No value response X Monitoring unit Device 3 8/1/95 Send/receive telegram Device 3 Failure 8/1/96 8/1/96 1 Failure! Switch actuator Gr.-object8/1/95 Read Flag set! Device 4 xxx Device 4 xxx 2/4/22 2/4/23 Output A 3/1/11 Switch 7/3/112 / / DESTO Jürgen Schilder 34 Device no. 2:. Device no. 3: cycle time 10min max response time 5sec. Device no. 4:.

28 Cycl. polling 8/1/95 value read 3 repetition of the request Device 3 failure 8/1/ DESTO Jürgen Schilder 36

29 Monitoring Unit EUB/S Monitoring mode: Receive group address cyclically This mode of monitoring is also referred to as passive monitoring Telegrams which are cyclically sent by the device being monitored are evaluated If the telegrams are not received for a definable time (e.g. 60 sec.), it will be evaluated as a failure For this monitoring mode it is necessary that the devices being monitored can send telegrams cyclically Object In Operation or other cyclical sender In order to keep the bus load as low as possible with this mode, the monitoring cycles of cyclically sending devices should be adjusted longer than 10 minutes DESTO Jürgen Schilder 37

30 Monitoring Unit EUB/S Monitoring mode: Receive group address cyclically DESTO Jürgen Schilder 38

31 Monitoring Unit EUB/S Monitoring mode: Receive group address cyclically This object receives cyclical telegrams from a device to be monitored If no telegrams are received after a programmed time, this is evaluated as a failure The failure is signaled by the group object Failure DESTO Jürgen Schilder 39

32 Monitoring Unit EUB/S Monitoring mode: Receive group address cyclically This object is used to indicate the failure of a monitored device A failure has occurred an expected group address telegram has not been received three times in a row 0 : Operational 1 : Failured DESTO Jürgen Schilder 40

33 Monitoring Unit EUB/S Monitoring mode: Receive group address cyclically 6/0/ In Operation Monitoring unit Device 4 Receive telegram Device 4 Failure 6/0/179 6/0/180 6/0/180 0 on alteration Switch actuator General In Operation 6/0/179 Device 5 xxx Device 6 xxx 2/4/22 2/4/23 Output A 3/1/11 Switch 7/3/112 / / DESTO Jürgen Schilder 41 Device no. 3:. Device no. 4: cycle time 10min. Device no. 5:. Send cyclical In Operation telegram 4 min

34 DESTO Jürgen Schilder 43 Cycl. telegram 6/0/179

35 Monitoring Unit EUB/S Monitoring mode: Receive group address cyclically No cyclical telegram (6/0/179 0 ) X X Monitoring unit Device 4 Receive telegram Device 4 Failure 6/0/179 6/0/180 6/0/180 1 Failure! Switch actuator General In Operation 6/0/179 Device 5 xxx Device 6 xxx 2/4/22 2/4/23 Output A 3/1/11 Switch 7/3/112 / / DESTO Jürgen Schilder 44 Device no. 3:. Device no. 4: cycle time 10min. Device no. 5:. Send cyclical In Operation telegram 4 min

36 No more telegrams received Device 4 failure 6/0/ DESTO Jürgen Schilder 46

37 Monitoring Unit EUB/S 1.1 Collective Messages Groups Each monitored KNX device can be assigned to one of five groups Collective message Group 1..5 Group 2 Group 1 EUB/S OG DESTO Jürgen Schilder 47

38 Monitoring Unit EUB/S 1.1 Collective Messages Groups Each monitored KNX device can be assigned to one of five groups Collective message Group DESTO Jürgen Schilder 48

39 Monitoring Unit EUB/S 1.1 Collective Messages Groups Each monitored KNX device can be assigned to one of five groups Collective message Group DESTO Jürgen Schilder 49 Sends a status message of devices assigned to a group to be monitored A failure occurs if one of the devices to be monitored in the group can not be detected 0 : No fault (all devices of a group will be detected) 1 : Fault (min. one device of a group will not be detected)

40 Monitoring Unit EUB/S 1.1 Collective Messages All All monitored KNX devices are assigned to this group All Collective message All All EUB/S OG DESTO Jürgen Schilder 50

41 Monitoring Unit EUB/S 1.1 Monitoring of KNX devices Fault Monitoring Unit SMB/S 1.1 Detection and processing of fault signals Data Logging Unit BDB/S 1.1 Detection of operating hours and switching cycles DESTO Jürgen Schilder 53

42 Fault Monitoring Unit SMB/S 1.1 Projects Hospitals Industrial facilities Office buildings Projects where a proven solution with a complete logic for a fault monitoring system is required DESTO Jürgen Schilder 54

43 Fault Monitoring Unit SMB/S 1.1 Detection and processing of fault messages (1 Bit signals, e.g. from binary inputs) Examples for fault signals: Heating, Cooling, Ventilation, electrical circuit, KNX device (via EUB/S 1.1), status message of switch actuator, Generation of control signals for optical and acoustical signalization Examples for signaling devices: Siren, flash light, tableau, Voice message via phone, Fault Monitoring Unit SMB/S 1.1 supports the following types, specified in DIN (one type per SMB/S): Fault signal with permanent light New value signal with simple flashing light Initial value signal with simple acknowledgement Motor signal DESTO Jürgen Schilder 55

44 Fault Monitoring Unit SMB/S 1.1 Fault 1 Fault 2.. Fault 99 Fault 100 Acknowledgement Opt. Indication 1 Fault 1 Opt. Indication 2 Fault 2.. Opt. Indication 99 Fault 100 Opt.Indicat. 100 Fault 100 Acoustical centr. Indication Optical centr. Indication DESTO Jürgen Schilder 56

45 Fault Monitoring Unit SMB/S 1.1 Inputs (1 Bit) Binary Input BE/S Status message, e.g. switch actuator with current detection and motor with monitored load current Universal concentrator UK/S 32.1 to connect many fault contacts at the same location Monitoring Unit EUB/S 1.1 with information KNX Device out of function Fault Confirmation SMB/S DESTO Jürgen Schilder 57

46 Fault Monitoring Unit SMB/S 1.1 Outputs (1 Bit) Switch actuator with flash light or siren Universal concentrator UK/S 32.1 to connect signal lamps Telephone gateway TG/S 3.2 with quiet alarm (Voice message, sms, ) SMB/S DESTO Jürgen Schilder 58

47 Fault Monitoring Unit SMB/S 1.1 Fault signal with permanent light (DIN ) An operating state to be signalled is indicated by permanent lighting of a visual indicator which is assigned to this signal. At the same time, a central acoustic and visual indicator is switched on. An acknowledgement signal switches off all indicators at the same time DESTO Jürgen Schilder 59

48 Fault Monitoring Unit SMB/S 1.1 New value signal with simple flashing light (DIN ) With the new value signal every new operating state to be signalled is indicated by a flashing signal, and remains on until the visual indicator is acknowledged. At the same time one or more signals of the assigned central acoustic and visual indicator are switched on DESTO Jürgen Schilder 60

49 Fault Monitoring Unit SMB/S 1.1 Initial value signal with simple acknowledgement (DIN ) The initial value signal represents a function expansion of the new value signal. Only the first operating state to signal will flash, all subsequent signals will be assigned to the permanent light DESTO Jürgen Schilder 61

50 Fault Monitoring Unit SMB/S 1.1 Initial value signal with simple acknowledgement (DIN ) The initial value signal represents a function expansion of the new value signal. Only the first operating state to signal will flash, all subsequent signals will be assigned to the permanent light DESTO Jürgen Schilder 62

51 Fault Monitoring Unit SMB/S 1.1 Motor Message (DIN ) The motor signal indicates with a flashing light and acoustic signal, if a setpoint state e.g. actuation of a switch actuator does not correspond with the actual state, e.g. feedback contact of equipment. This means that a direct comparison of the input and output states is undertaken DESTO Jürgen Schilder 63

52 Fault Monitoring Unit SMB/S 1.1 Features Depending on the type of fault management up to 100 fault signals can be processed In addition fault signals can be split into independent groups, e.g. 5 groups with each 20 fault messages Typically binary inputs are used to collect the fault signals. BE/S x.x.2.1 have special parameters to evaluate fault signals correctly, e.g. Minimum signaling time Debounce time Scan input after download, ETS reset, bus voltage recovery Parameters to be adjusted as recommended in the manual of BE/S x.x DESTO Jürgen Schilder 64

53 Fault Monitoring Unit SMB/S 1.1 ETS Group Objects Communication objects for flash and permanent light (except for fault signal with permanent light) Flashing function to be implemented in the actuator (e.g. switch actuator SA/S) DESTO Jürgen Schilder 65

54 Fault Monitoring Unit SMB/S 1.1 ETS Group Objects DESTO Jürgen Schilder 66

55 Fault Monitoring Unit SMB/S 1.1 ETS Group Objects Data loss: Indicates, that after bus voltage recovery either at least one fault message input object has not yet received a telegram or that a response telegram has not been received after polling. Update: Activates the polling of all fault signal objects, which are assigned to a group DESTO Jürgen Schilder 67

56 Fault Monitoring Unit SMB/S 1.1 ETS Parameters DESTO Jürgen Schilder 68

57 Monitoring Unit EUB/S 1.1 Monitoring of KNX devices Fault Monitoring Unit SMB/S 1.1 Detection and processing of fault signals Data Logging Unit BDB/S 1.1 Detection of operating hours and switching cycles DESTO Jürgen Schilder 69

58 Data Logging Unit BDB/S 1.1 Application fields (1) The module can be used for example, in an office complex in order to record the operating life of fluorescent lamps For example when a reference office in the office complex is taken and from this data the switch on duration and switching operations are recorded Based on these values it is possible to determine what the service life of the fluorescent lamps will be This will allow you to make assumption with regard to the maintenance expenditure and effort in the office complex DESTO Jürgen Schilder 71

59 Data Logging Unit BDB/S 1.1 Application fields (2) The module can be used for example in a functional building to record the switch on times of pumps in the heating system The service life of the pumps can be derived from the switch on time This enables co-ordination of prompt pump maintenance DESTO Jürgen Schilder 72

60 Data Logging Unit BDB/S 1.1 Application fields (3) This module can be used for example in a department store to record the operating duration of the motors in the escalators or elevators A maintenance plan can be created based on the recorded use The plan can be co-ordinated so that the operations in the department store are not affected DESTO Jürgen Schilder 73

61 Data Logging Unit BDB/S 1.1 Application fields (4) The module can be used for example in a hotel to record the operating life of filters in the air conditioning A maintenance plan can be created using this data DESTO Jürgen Schilder 74

62 Data Logging Unit BDB/S 1.1 Detection of Operating hours Switching operations per channel 35 channels available Counting method from zero upwards or from a set value downward Setting and monitoring of thresholds Automatic alarm message if value exceeds the threshold Thresholds and initial values can be changed via KNX DESTO Jürgen Schilder 75

63 Data Logging Unit BDB/S 1.1 Programming of channels All channels together or Each channel individually Operating hour telegrams can be sent cyclically or after change Switching operation telegrams can be sent cyclically Bus voltage failure All values (operating hours, switching operations, initial values and thresholds) will be stored continuously For a better overview each channel can be described with a text Cyclical scanning of assigned objects (READ flag must be set in the group objects to be recalled actuators) DESTO Jürgen Schilder 76

64 Data Logging Unit BDB/S DESTO Jürgen Schilder 77

65 Data Logging Unit BDB/S DESTO Jürgen Schilder 78

66 Data Logging Unit BDB/S DESTO Jürgen Schilder 79

67 Data Logging Unit BDB/S 1.1 ETS Group Object: Per Channel (1-35) DESTO Jürgen Schilder 80

68 Data Logging Unit BDB/S 1.1 ETS Group Object: Recall all switch positions A recall of all switch positions of the monitored channels is started Telegram value: 1 = recall 0 = do not recall Note: Channels are only recalled if: The input object of the channel is assigned to a group address The channel parameter Cyclic switch position recall in the parameter window Channel parameters is set to yes DESTO Jürgen Schilder 81

69 Data Logging Unit BDB/S 1.1 ETS Group Object: Send all operating data Send the current operating data via the group objects: Channel X switching operations Number Channel X operating hours Number Channel X switching operations - Alarm Channel X operating hours - Alarm Telegram value: 1 = send 0 = do not send DESTO Jürgen Schilder 82

70 Data Logging Unit BDB/S 1.1 ETS Group Object: Enable delete/overwrite DESTO Jürgen Schilder 83 If a 1 is received the enable to delete/overwrite of the operating data is issued and a time window of ten seconds is activated Via the group object Delete all operating data System, all operating data can be deleted in the Data Logging Unit When counting upwards the counter value is set to zero When counting downwards the counter value is set to start value The operating hours counter, start and limit values, the switching operations counter, start and limit values can be modified via the respective communication objects via the bus Telegram value: 1 = time window active 0 = time window not active

71 Data Logging Unit BDB/S 1.1 ETS Group Object: Delete all operating data DESTO Jürgen Schilder 84 Deleting of the operating data switching operations and operating hours Deleting applies for all channels If a 1 is received the values of the communication objects Channel X switching operations Number Channel X operating hours Number are set to zero counting up and set to the start value when counting down Before the operating data is deleted a 1 must be received on the communications object Enable delete/overwrite System Telegram value: 1 = delete 0 = do not delete

72 Data Logging Unit BDB/S 1.1 ETS Group Object: In operation This group object is only active if yes has been selected for the parameter Send cyclic In operation telegram As long as the group object is activated it sends an In operation telegram Send interval between 10min. and 24 hours Telegram value: 1 = system in operation DESTO Jürgen Schilder 85

73 Data Logging Unit BDB/S 1.1 Operating time Detection per channel in seconds Output telegram in hours (4-byte) Each action ON OFF ON and OFF (always) Counting method from zero upwards or from a set value downwards Counted and initial values, thresholds can be changed via KNX Stored values, remaining- and initial values can be overwritten by download DESTO Jürgen Schilder 86

74 Data Logging Unit BDB/S Alarm message Max. value Threshold: - Adjustable ETS - Change value via KNX bus telegram Operating time Way of counting Total runtime Starting from zero (count up) Limit value max hours Threshold adjustable: Alarm message if limit has been reached 0 Start DESTO Jürgen Schilder 87

75 Data Logging Unit BDB/S Max. value Start value: - Adjustable ETS - Change value via KNX bus telegram Operating time Way of counting Remaining runtime Count down from an start value (adjustable) Start value max hours Alarm message if zero has been reached Alarm message DESTO Jürgen Schilder 88

76 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X switch position - received Receives the current 1-bit switching telegram of the channel to be recorded, e.g. from a switching actuator DESTO Jürgen Schilder 89

77 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X operating hours - Number Contains the current number (= counter value) of operating hours The counter value can also be modified via the bus DESTO Jürgen Schilder 90

78 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X operating hours start/limit value The operating hours start or limit value can be changed via the bus DESTO Jürgen Schilder 91

79 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel 1 operating hours - Alarm Sends a 1, as soon as the set operating hours limit value is reached when counting upwards When counting downwards a 1 is sent as soon as zero is reached As soon as the group object 248 Send all operating data System receives a 1, this group object also is sent Telegram value: 1 = limit value reached 0 = limit value not reached DESTO Jürgen Schilder 92

80 Data Logging Unit BDB/S 1.1 Operating hours 0/5/73 switch sensor Radio time switch Switch actuator Data logging unit Rocker 1 switching Rocker 2 switching 3/1/11 x/y/z Channel 1 Switching Channel 2 Switching 7/3/8 x/y/z Output A 3/1/11 Switch 7/3/8 / / Outtput A 0/5/73 Status Switching Channel 1 Switch position 0/5/73 Channel 1 2/4/11 Operating hours number Channel 1 2/4/12 Oper. hours start/limit value change/read 1-bit 4-byte 4-byte Channel 1 2/4/13 Operating hours alarm 1-bit DESTO Jürgen Schilder 93

81 Data Logging Unit BDB/S 1.1 Switching operations Detection per channel Each action increases the counter Count operation with change of switch position from OFF ON ON OFF Counting method from zero upwards or from a set value downward Counted and initial values, thresholds can be changed via KNX Stored values, remaining- and initial values can be overwritten by download DESTO Jürgen Schilder 94

82 Data Logging Unit BDB/S Alarm message Max. value Threshold: - Adjustable ETS - Change value via KNX bus telegram Switching operations Way of counting Total value Starting from zero (count up) Limit value max Threshold adjustable: Alarm message if limit has been reached 0 Start DESTO Jürgen Schilder 95

83 Data Logging Unit BDB/S Max. value Start value: - Adjustable ETS - Change value via KNX bus telegram Switching operations Way of counting Remaining value Count down from an start value (adjustable) Start value max Alarm message if zero has been reached Alarm message DESTO Jürgen Schilder 96

84 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X switch position - received Receives the current 1-bit switching telegram of the channel to be recorded, e.g. from a switching actuator DESTO Jürgen Schilder 97

85 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X switching operations - Number Contains the current number (= counter value) of switching operations The counter value can also be modified via the bus DESTO Jürgen Schilder 98

86 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X switching operations start/limit value The switching operation start or limit value can be changed via the bus DESTO Jürgen Schilder 99

87 Data Logging Unit BDB/S 1.1 ETS Group Object: Channel X switching operations - Alarm Sends a 1, as soon as the set switching operations limit value is reached when counting upwards When counting downwards a 1 is sent as soon as zero is reached As soon as the group object 248 Send all operating data System receives a 1, this group object also is sent Telegram value: 1 = limit value reached 0 = limit value not reached DESTO Jürgen Schilder 100

88 Data Logging Unit BDB/S 1.1 Switching operations 0/5/73 switch sensor Radio time switch Switch actuator Data logging unit Rocker 1 switching Rocker 2 switching 3/1/11 x/y/z Channel 1 Switching Channel 2 Switching 7/3/8 x/y/z Output A 3/1/11 Switch 7/3/8 / / Outtput A 0/5/73 Status Switching Channel 1 Switch position 0/5/73 Channel 1 2/4/21 Switching operations Number Channel 1 2/4/22 Switch. oper. start/limit value change/read 1-bit 4-byte 4-byte Channel 1 2/4/23 Switching operations alarm 1-bit DESTO Jürgen Schilder 101

89 KNX Association DESTO Jürgen Schilder 102

90 Next Webinar Wednesday 23 th of September 2015 Morning 09:00 am Europe Time (Berlin, UTC + 2h) Afternoon 03:00 pm Europe Time (Berlin, UTC + 2h) New IP Devices IP Router IPR/S IP Interface IPS/S Summer Break!!! DESTO Jürgen Schilder 103

91 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document. Copyright [2015] ABB. All rights reserved DESTO Jürgen Schilder 104

92

Application Controller AC/S

Application Controller AC/S October 2018 Application Controller AC/S Webinar Competence Center Europe Building Automation Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Stefan Grosse, Thorsten Reibel Agenda ClimaECO new Devices

More information

Webinar KNX Sensors commercial Buildings

Webinar KNX Sensors commercial Buildings JUNE 2017 Webinar KNX Sensors commercial Buildings BU EPBP GPG Building Automation Carolina Bachenheimer-Schaefer, Thorsten Reibel, Jürgen Schilder & Ilija Zivadinovic Global Application and Solution Team

More information

BU EPBP GPG Building Automation

BU EPBP GPG Building Automation JULY 2017 Webinar KNX Visualisation Updates and Solutions BU EPBP GPG Building Automation Carolina Bachenheimer-Schaefer, Thorsten Reibel, Jürgen Schilder & Ilija Zivadinovic Global Application and Solution

More information

Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Thorsten Reibel, Stefan Grosse

Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Thorsten Reibel, Stefan Grosse NOVEMBER 2018 ClimaECO BA-Controller KNX BAC/S Webinar Competence Center Europe Building Automation Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Thorsten Reibel, Stefan Grosse Agenda Building Automation

More information

Thorsten Reibel, Jürgen Schilder, Martin Wichary & Ilija Zivadinovic

Thorsten Reibel, Jürgen Schilder, Martin Wichary & Ilija Zivadinovic DECEMBER 2017 New ABB-free@home features Webinar Competence Center Europe Building Automation Thorsten Reibel, Jürgen Schilder, Martin Wichary & Ilija Zivadinovic Webinar ABB-free@home Update 2.1.4 New

More information

Webinar Energy Analyzer QA/S 3.x.1

Webinar Energy Analyzer QA/S 3.x.1 HEIDELBERG, OCTOBER 2017 Webinar Energy Analyzer QA/S 3.x.1 ABB EQmatic Global Application and Solution Team Agenda Introduction Commissioning Connecting to the device and commissioning wizard Management

More information

HEIDELBERG, SEPTEMBER 2018 Webinar EQmatic Energy Analyzer QA/S

HEIDELBERG, SEPTEMBER 2018 Webinar EQmatic Energy Analyzer QA/S HEIDELBERG, SEPTEMBER Webinar EQmatic Energy Analyzer QA/S M-Bus and Modbus Thorsten Reibel, Jürgen Schilder, Stefan Grosse, Martin Wichary & Ilija Zivadinovic Competence Center Europe Building Automation

More information

ABB i-bus KNX SUG/U 1.1 Split Unit Gateway Product Manual

ABB i-bus KNX SUG/U 1.1 Split Unit Gateway Product Manual SUG/U 1.1 Split Unit Gateway Product Manual Contents Contents Page 1 General... 3 1.1 Using the product manual...3 1.1.1 Notes...4 1.2 Overview of product and functions...5 1.2.1 Integration in the i-bus

More information

EAE KNX Switch Actuator

EAE KNX Switch Actuator EAE KNX Switch Actuator Order Number: 48002 Content 1 General... 2 2 Device Technology... 3 2.1 Connection Diagram... 3 2.2 Technical Data... 4 3 Communication Object Table... 5 4 Parameters... 6 4.1 Main

More information

SWISS GARDE 360 HOKUSPOKUS KNX/KLR APPLICATION DESCRIPTION

SWISS GARDE 360 HOKUSPOKUS KNX/KLR APPLICATION DESCRIPTION SWISS GARDE 360 HOKUSPOKUS KNX/KLR APPLICATION DESCRIPTION MODEL TYPE NO. SG HOKUSPOKUS KNX/KLR 25010 Program version 2.7 2012 M. Züblin AG Neue Winterthurerstrasse 30, 8304 Wallisellen, Switzerland The

More information

Product documentation

Product documentation Product documentation Rotary sensor ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle Telefon: +49.23 55.8 06-0 Telefax: +49.23 55.8 06-2 04 kundencenter@jung.de www.jung.de Service Center Kupferstr.

More information

Competence Center Europe Smart Buildings

Competence Center Europe Smart Buildings FEBRUARY 2019 Competence Center Europe Smart Buildings Thorsten Reibel, Jürgen Schilder, Stefan Grosse, Martin Wichary & Ilija Zivadinovic Copyright 2019 ABB. All rights reserved. Agenda Firmware update

More information

Competence Center Europe Smart Buildings

Competence Center Europe Smart Buildings MARCH 2019 Competence Center Europe Smart Buildings Thorsten Reibel, Jürgen Schilder, Stefan Grosse, Martin Wichary & Ilija Zivadinovic Copyright 2019 ABB. All rights reserved. Document ID.: Rev.: Agenda

More information

PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX. Product Handbook

PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX. Product Handbook PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX Product Handbook Product: PD00D01KNX Description: PRESENCE DETECTOR, CONSTANT CONTROLLER Document Version: 1.3 Date: 03/10/2017 Tribunale di Mila

More information

Product documentation

Product documentation Product documentation Universal push-button module with integrated BCU, 1-gang Universal push-button module with integrated BCU, 2-gang Universal push-button module with integrated BCU, 3-gang Universal

More information

Application program: description and examples

Application program: description and examples F a n C o i l U n i t C o n t r o l l e r F a n C o i l 4 9 5 5 1 Application program: description and examples Woertz AG Electrotechnical accessories, installation systems Hofackerstrasse 47, P.O. Box

More information

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook FANCOIL CONTROLLER UNIT TC17B01KNX Product Handbook Product: TC17B01KNX Description: FANCOIL CONTROLLER UNIT Document Version: 1.2 Date: 09/09/2016 1/37 INDEX 1. General Introduction... 4 2. Product and

More information

EAE KNX Room Control Unit Product Manual RCUXXYY

EAE KNX Room Control Unit Product Manual RCUXXYY EAE KNX Room Control Unit Product Manual RCUXXYY RCU2018 RCU2016 RCU1212 RCU0808 RCU2000 RCU2000 RCU1200 RCU0800 Note: RCUXXYY where XX denotes the number of outputs and YY number of inputs. Index 1 General...

More information

Tebis application software

Tebis application software 5 Tebis application software SXB322AU V 1.x 2 inputs / 2-output module LED SXB344AU V 1.x 4 inputs / 4-output module LED Product reference Product designation TXB322AU TXB344AU Embedded module: 2 inputs

More information

Product Manual V ABB i-bus EIB / KNX DALI-Gateway DG/S 1.1. Intelligent Installation Systems ABB

Product Manual V ABB i-bus EIB / KNX DALI-Gateway DG/S 1.1. Intelligent Installation Systems ABB Product Manual V1-0 31.07.2006 ABB i-bus EIB / KNX DALI-Gateway DG/S 1.1 Intelligent Installation Systems ABB This manual describes the function of the 1-fold DALI-Gateway with its application programs

More information

ABB i-bus KNX Binary Inputs BE/S Product Manual

ABB i-bus KNX Binary Inputs BE/S Product Manual kg ABB i-bus KNX Binary Inputs BE/S Product Manual Contents Contents Page 1 General 5 1.1 Using the product manual...5 1.1.1 Structure of the product manual...5 1.1.2 s...6 1.2 Product and functional

More information

MA /2015. User manual CU-DIN DRY 4-Z KNX EC

MA /2015. User manual CU-DIN DRY 4-Z KNX EC MA00652800 06/2015 User manual CU-DIN DRY 4-Z KNX EC10430381 TABLE OF CONTENTS 1 Description...3 2 Safety instructions...4 3 Product function...4 4 Hardware...5 4.1 Technical data... 5 4.2 Dimensional

More information

Din Rail Universal Module 8 inputs / 8 outputs IO88E01KNX

Din Rail Universal Module 8 inputs / 8 outputs IO88E01KNX Din Rail Universal Module 8 inputs / 8 outputs IO88E01KNX Product Handbook Product Description: Din Rail Universal 8 in / 8 out Module Order Code: IO88E01KNX Document Version: 1.1 Date: 22/07/2011 1/64

More information

ABB i-bus EIB. Shutter Actuator, 2-fold, 6 A, 230 VAC, MDRC JA/S 2.6.1, GH Q R0111

ABB i-bus EIB. Shutter Actuator, 2-fold, 6 A, 230 VAC, MDRC JA/S 2.6.1, GH Q R0111 , GH Q31 0022 R0111 The 2-fold shutter actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus connecting terminal. It is used to control two

More information

Use of the application program. Contents overview. Gamma instabus Application program description. November 2016

Use of the application program. Contents overview. Gamma instabus Application program description. November 2016 Use of the application program Product family: Product type: Manufacturer: Application: Name: Description: Order no: Application: Name: Description: Order no: Lighting Dimmer Siemens Switch-/Dimming Actuator

More information

ABB i-bus EIB / KNX Shutter Actuator with Manual Operation, 4-fold, SMI, MDRC JA/S 4.SMI.1M. Product Manual. Intelligent Installation Systems ABB

ABB i-bus EIB / KNX Shutter Actuator with Manual Operation, 4-fold, SMI, MDRC JA/S 4.SMI.1M. Product Manual. Intelligent Installation Systems ABB Product Manual ABB i-bus EIB / KNX Shutter Actuator with Manual Operation, 4-fold, SMI, MDRC JA/S 4.SMI.1M Intelligent Installation Systems ABB JA/S 4.SMI.1M Shutter Actuator with Manual Operation, 4-fold,

More information

ABB i-bus KNX Fan Coil Actuator, PWM, MDRC FCA/S , 2CDG110195R0011

ABB i-bus KNX Fan Coil Actuator, PWM, MDRC FCA/S , 2CDG110195R0011 Technical data 2CDC508136D0202 ABB i-bus KNX Product description The device is a modular installation device (MDRC) in Pro M design. It is intended for installation in distribution boards on 35 mm mounting

More information

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Output Binary Siemens Name: Switching Actuator N 53/ Order no.: 5WG 53-AB Name: Switching Actuator N 52/ Order no.: 5WG 52-AB

More information

Application description for the KNX Roombox. (Art. no. ORBK8L0S4HW/ORBK8D0S4HW/ORBK4L4S4HW/ORBK4D4S4HW)

Application description for the KNX Roombox. (Art. no. ORBK8L0S4HW/ORBK8D0S4HW/ORBK4L4S4HW/ORBK4D4S4HW) Application description for the KNX Roombox (Art. no. ORBK8L0S4HW/ORBK8D0S4HW/ORBK4L4S4HW/ORBK4D4S4HW) Introduction to the ORB plug-in... 1 Zone Global... 9 Zone Energy metering... 11 Push-button interface...

More information

ABB STOTZ-KONTAKT GmbH. ABB i-bus KNX Room Master, Basic, RM/S 1.1

ABB STOTZ-KONTAKT GmbH. ABB i-bus KNX Room Master, Basic, RM/S 1.1 ABB STOTZ-KONTAKT GmbH ABB i-bus KNX Room Master, Basic, RM/S 1.1 2CDC 514 052 N0201 Slide 1 New Innovation Room Master Innovation features Room Scenarios Recall with one group-address All function in

More information

Rev KNX Technical Reference Manual ABB i-bus KNX. KNX Sensors

Rev KNX Technical Reference Manual ABB i-bus KNX. KNX Sensors 0073-1-7704 Rev. 01 04.2011 KNX Technical Reference Manual ABB i-bus KNX KNX Sensors KNX Technical Reference Manual ABB i-bus KNX 1 Quick-Start-Guide Additional key Set value minus (1) Set value plus (2)

More information

Use of the application program. Contents overview. GAMMA instabus Application program description. August 2012

Use of the application program. Contents overview. GAMMA instabus Application program description. August 2012 Use of the application program Product family: Heating, Air conditioning, Ventilation Product type: Controller Manufacturer: Siemens Name Room Temperature Controller UP 237K Design: DELTA i-system Color

More information

Use of the application program. Functional description. GAMMA instabus Application program description. March S1 rocker (BCU2)

Use of the application program. Functional description. GAMMA instabus Application program description. March S1 rocker (BCU2) Use of the application program Product family: Product type: Manufacturer: Push button Push button, 1-fold Siemens Name: Pushbutton UP 241, single, neutral DELTA profil Order-no.: 5WG1 241-2AB_1 Name:

More information

½ Caution! Introduction. Blind.switch 5701/1.0

½ Caution! Introduction. Blind.switch 5701/1.0 Blind.switch 5701/1.0 Introduction General information This software application enables you to program blind/switch actuators using manual mode (referred to below as actuator), control blind and roller

More information

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001 SK 0012 B 98 The control unit is a DIN rail mounted device for insertion in the distribution board. It is used to control digitally dimmable electronic ballast devices or transformers via the EIB. In a

More information

Software-Information. Binary 8f 23021/1.3b, Binary 8f 2021/1.3b. Software-Information to: Binary 4f 23021/1.3b, Binary 4f 2021/1.

Software-Information. Binary 8f 23021/1.3b, Binary 8f 2021/1.3b. Software-Information to: Binary 4f 23021/1.3b, Binary 4f 2021/1. Product: Binary Input Type: BE/S x.x.1 urrent application program: Binary 4f 23021/1.3b, Binary 4f 2021/1.3b, Binary 8f 23021/1.3b, Binary 8f 2421/1.3b =======================================================================================

More information

Operation and installation manual KNX IO 511 (1O2I) Application. 1. Installation and Connection

Operation and installation manual KNX IO 511 (1O2I) Application. 1. Installation and Connection EN Operation and installation manual KNX IO 511 (1O2I) (Art. # 5232) Switching actuator with 1 output and 2 binary inputs A. KNX Programming mode The KNX programming mode is activated/deactivated either

More information

ABB i-bus KNX Room Master Basic RM/S 1.1 Product Manual

ABB i-bus KNX Room Master Basic RM/S 1.1 Product Manual ABB i-bus KNX Room Master Basic RM/S 1.1 Product Manual ABB i-bus KNX Contents Contents Page Contents i 1 General 5 1.1 Use of the product manual...6 1.1.1 Structure of the product manual...6 1.1.2 Notes...7

More information

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011 Technical data 2CDC507101D0202 ABB i-bus KNX Product description The ABB i-bus KNX DALI Light Controller DLR/S 8.16.1M is a KNX modular installation device (MDRC) in ProM design for installation in the

More information

RMG 8 Switch Actuator. RME 8 / RMX 4 Switch Actuator Modules. JMG 4 Blinds Actuator (for JMG 4 refer to Chapter 1.3)

RMG 8 Switch Actuator. RME 8 / RMX 4 Switch Actuator Modules. JMG 4 Blinds Actuator (for JMG 4 refer to Chapter 1.3) RMG 8 Switch Actuator RME 8 / RMX 4 Switch Actuator Modules JMG 4 Blinds Actuator (for JMG 4 refer to Chapter 1.3) JMG 4 490 0 250 RMG 8 490 0 251 RME 8 490 0 252 RMX 4 490 0 256 Key for JMG 4 / RMG 8

More information

EAE KNX IP Router Product Manual IPR100 (sayfa düzeni ve foto düzenlemesi gerekli)

EAE KNX IP Router Product Manual IPR100 (sayfa düzeni ve foto düzenlemesi gerekli) Product Manual IPR100 (sayfa düzeni ve foto düzenlemesi gerekli) EAE Technology www.eaetechnology.com CONTENTS 1 General...3 1.1 Communication objects...4 1.2 IPR100 as programming interface...4 1.3 Tunnelling...4

More information

Din Rail 8 Input / 8 Output Module

Din Rail 8 Input / 8 Output Module Din Rail 8 Input / 8 Output Module IO88B02KNX Product Handbook Product: Din Rail 8 Input / 8 Output Module Order Code: IO88B02KNX 1/32 INDEX 1. General Introduction... 3 2. Product and functional overview...

More information

ABB i-bus KNX Fan Coil Actuator FCA/S 1.1M Product Manual

ABB i-bus KNX Fan Coil Actuator FCA/S 1.1M Product Manual ABB i-bus KNX Fan Coil Actuator FCA/S 1.1M Product Manual ABB i-bus KNX Contents Contents Page Contents i 1 General 5 1.1 Use of the product manual...5 1.1.1 Note...6 1.2 Product and functional overview...7

More information

Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Thorsten Reibel

Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Thorsten Reibel APRIL 2018 News Light + Building 2018 Webinar Competence Center Europe Building Automation Ilija Zivadinovic, Martin Wichary, Juergen Schilder, Thorsten Reibel Agenda ClimaECO - complete HVAC solution

More information

Product documentation

Product documentation Product documentation KNX Room controller display compact module ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 D-58579 Schalksmühle Telefon: +49.23 55.8 06-0 Telefax: +49.23 55.8 06-1 89 E-mail: mail.info@jung.de

More information

Din Rail 4 Output Module BO04A01KNX

Din Rail 4 Output Module BO04A01KNX Din Rail 4 Output Module BO04A01KNX Product Handbook Product Description: Din Rail 4 Output Module Order Code: BO04A01KNX Document Version: 1.1 Date: 28/01/2014 1/45 INDEX 1. General Introduction... 4

More information

Water-protected surface-mounted push-button bus coupler Order No , , ,

Water-protected surface-mounted push-button bus coupler Order No , , , KNX Product documentation Issue: 14.10.2014 629x2y2z Water-protected surface-mounted push-button bus coupler Contents KNX Product documentation 1 Product definition... 3 1.1 Product catalogue... 3 1.2...

More information

Connections, displays and operating elements. Hand 1 / / 4

Connections, displays and operating elements. Hand 1 / / 4 GB Blind actuator REG-K/4x24/6 with manual mode Operating instructions Hand Connections, displays and operating elements I H 1 2 1 2 1 2 1 2 Hand 3 4 3 4 3 4 3 4 B A C D E ½ CAUTION The blind actuator

More information

Functional description. Use of the application program. GAMMA instabus Application program description. June C0 Sensor Switch

Functional description. Use of the application program. GAMMA instabus Application program description. June C0 Sensor Switch Use of the application program Functional description Product family: Product type: Manufacturer: Push button Push button, 1 4 fold Siemens The touch sensors have one, two or four vertically arranged pairs

More information

Contents. GAMMA instabus Application program - Descriptions. June B0 KNX / DALI Gateway Twin N 141/

Contents. GAMMA instabus Application program - Descriptions. June B0 KNX / DALI Gateway Twin N 141/ Contents 1. Product description...2 1.1 DALI fundamentals...2 1.2 Gateway fundamentals...2 2. Functional overview...2 2.1 Modes... 3 2.1.1 Normal mode... 3 2.1.2 Standalone mode... 3 2.1.3 Direct mode...

More information

EDIFICIOS INTELIGENTES Y MULTIMEDIA: DOMOTICA Y CABLEADO ESTRUCTURADO

EDIFICIOS INTELIGENTES Y MULTIMEDIA: DOMOTICA Y CABLEADO ESTRUCTURADO EDIFICIOS INTELIGENTES Y MULTIMEDIA: DOMOTICA Y CABLEADO ESTRUCTURADO Hojas de Aplicaciones para los módulos domóticos de Siemens de las Prácticas 5 y 6 Producto Número Pedido Programa Aplicación Base

More information

Product documentation

Product documentation Product documentation Signal panel ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 D-58579 Schalksmühle Telefon: +49.23 55.8 06-0 Telefax: +49.23 55.8 06-1 89 E-mail: mail.info@jung.de Internet: www.jung.de

More information

/ 2CKA001473B KNX Technical Reference Manual ABB i-bus KNX. Room temperature controller with display 6108/18-500

/ 2CKA001473B KNX Technical Reference Manual ABB i-bus KNX. Room temperature controller with display 6108/18-500 1473-1-8913 / 2CKA001473B8913 23.03.2016 KNX Technical Reference Manual ABB i-bus KNX Room temperature controller with display 6108/18-500 Table of contents Table of contents 1 s on the instruction manual...

More information

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm 2 2.1 Air Quality Sensor LGS/A 1.1 The ABB i-bus KNX Air Quality Sensor 1.1 is a combined sensor for CO 2, temperature and humidity measurement (relative humidity). Three independent thresholds can be

More information

IQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel :

IQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : IQ-MP Gateway Version 4.009 28. apr. 2011 Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : +45 8880 7580 www.electrocom.dk p. 2 Description The IQ-MP Gateway is a communications module, which

More information

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011 Technical Data 2CDC505082D0203 ABB i-bus KNX Product description Switch Actuators SA/S x.16.6.1, 16/20 A are modular installation devices in ProM design for installation in the distribution board. They

More information

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011 Technical Data 2CDC504084D0201 ABB i-bus KNX Product description The device is used to record analogue data. Four conventional sensors can be connected to the device. The connection to the bus is established

More information

LUXORliving System manual Version 1

LUXORliving System manual Version 1 LUXORliving System manual Version 1 2018-04-18 Contents 1 General 3 2 System 4 3 Installation 5 4 Start-up 7 4.1 Establish a connection 7 4.2 Configuration with LUXORplug 10 4.3 Programming with LUXORplug

More information

Philips LightMaster. KNX Commissioning Guide

Philips LightMaster. KNX Commissioning Guide Philips LightMaster KNX Commissioning Guide Philips LightMaster Commissioning Guide version 1.0 Specifications subject to change without notice. Copyright 2012 Controls, Systems & Services, Philips Lighting,

More information

Use of the application program. Table of Contents. GAMMA instabus Application program description. April B0 CO Room Control Unit

Use of the application program. Table of Contents. GAMMA instabus Application program description. April B0 CO Room Control Unit Use of the application program Product family: Product type: Manufacturer: Displays Display and operating units Siemens AG Name Room control unit UP 227 DELTA i-system Order no.: Table of Contents 5WG1

More information

Application description. KNX Push-button module 1gang. KNX Push-button module 2gang

Application description. KNX Push-button module 1gang. KNX Push-button module 2gang Application description KNX Push-button module 1/2gang Electrical/mechanical data: see the operating instructions for the product Order number Product designation Application programme TP product Radio

More information

ABB i-bus KNX HCC/S Heating/cooling circuit controller

ABB i-bus KNX HCC/S Heating/cooling circuit controller ABB i-bus KNX HCC/S 2.2.1.1 Heating/cooling circuit controller Description of product The device is a modular DIN rail component (MDRC) in pro M design. It is intended for installation in distribution

More information

Application description

Application description Hersteller Berker Taster ETS Multifunktions-Tastsensor 1-4fach Application description 1-fold KNX multifunctional push-button 2-fold KNX multifunctional push-button 3-fold KNX multifunctional push-button

More information

Application description. KNX push-button 1gang. KNX push-button 2gang. KNX push-button 3gang. KNX push-button 4gang. Page 1/51

Application description. KNX push-button 1gang. KNX push-button 2gang. KNX push-button 3gang. KNX push-button 4gang. Page 1/51 Application description KNX push-button 1, 2, 3 and 4gang Electrical/mechanical data: see the operating instructions for the product Order number Product designation Application programme TP product Radio

More information

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order

More information

KNX S4-B10 230V. Multifunctional Actuator. Installation and Adjustment

KNX S4-B10 230V. Multifunctional Actuator. Installation and Adjustment EN KNX S4-B10 230V Multifunctional Actuator Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical data... 4 2. Installation and start-up... 5 2.1. Notes on installation... 5 2.2. Device

More information

B.IQ push button comfort 1-4gang, Flush-mounted (Up) x, x, x, x

B.IQ push button comfort 1-4gang, Flush-mounted (Up) x, x, x, x The B.IQ push-button comfort is plugged onto a flushmounted bus coupling unit (flush-mounted BCU). The push-buttons of the device can be programmed for the following functions: switching, dimming, blind/shutter

More information

Operation and installation manual KNX IP Multi IO 580 (48I/O) Application. 2. Factory default settings. 1. Installation and connection ❹ ❼ ❻ ❷

Operation and installation manual KNX IP Multi IO 580 (48I/O) Application. 2. Factory default settings. 1. Installation and connection ❹ ❼ ❻ ❷ EN ❶ Operation and installation manual KNX IP Multi IO 580 (48I/O) (Art. # 5238) KNX IP Multi IO with 48 configurable In- and Outputs ❸ ❹ ❼ ❺ ❽ ❻ ❷ ❶ ❶ ❶ Inputs and Outputs 1-48 ❷ LAN Connector ❸ OLED

More information

ABB i-bus KNX DALI Gateway Emergency Lighting DGN/S Product Manual

ABB i-bus KNX DALI Gateway Emergency Lighting DGN/S Product Manual DALI Gateway Emergency Lighting DGN/S 1.16.1 Product Manual Contents Contents Page 1 General... 3 1.1 Product and functional overview...4 1.2 DALI general...6 1.3 ABB i-bus DALI-Gateway in comparison...7

More information

Application description

Application description Manufacturer Berker Motion detector Application description KNX motion detector module comfort 1.10m KNX motion detector module comfort 2.20m ETS KNX motion detector module comfort 1.10m ETS KNX motion

More information

Application description for the KNXnet/IP Interface Web

Application description for the KNXnet/IP Interface Web Contents 1. General 1. General... 1 1.1 Basic information about the KNX/EIB BUS... 1 1.2 Application versions......1 1.3 Symbols...1 1.4 Function description... 2 1.5 Short description of the function

More information

KNX 2-channel Dimmer module EK-GA1-TP

KNX 2-channel Dimmer module EK-GA1-TP KNX 2-channel Dimmer module EK-GA1-TP Contents 1 Scope of the document... 4 2 Product description... 5 3 Switching, display and connection elements... 6 4 Configuration... 7 5 Commissioning... 7 6 Function

More information

EMO valve drive. 1. Function 1. Table of Contents. 2. Installation

EMO valve drive. 1. Function 1. Table of Contents. 2. Installation Chapter 13: Devices for single room heating 13.2 Valve drives EMO valve drive Art. no. 639119 EMO valve drive EMO valve drivechapter 13:Devices for single room heatingart. no.639119as at 08/0213.2Valve

More information

GVS K-BUS R KNX/EIB Push Button Sensor Contents 1. Summary

GVS K-BUS R KNX/EIB Push Button Sensor Contents 1. Summary Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R Push Button Sensor User manual-ver. 1.1 CHKP-01/01.1.xx CHKP-02/01.1.xx CHKP-03/01.1.xx KNX/EIB Intelligent Installation Systems GVS K-BUS R

More information

KNX S-B2-UP. Actuator for 230 V or 24 V. Installation and Adjustment

KNX S-B2-UP. Actuator for 230 V or 24 V. Installation and Adjustment EN KNX S-B2-UP Actuator for 230 V or 24 V Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical data... 3 1.2. Structure... 4 1.2.1. Structure 230 V AC version... 4 1.2.2. Structure

More information

ABB i-bus. KNX JRA/S Blind/Roller Shutter Actuator with Binary Inputs Product Manual

ABB i-bus. KNX JRA/S Blind/Roller Shutter Actuator with Binary Inputs Product Manual ABB i-bus KNX JRA/S 6.230.3.1 Blind/Roller Shutter Actuator with Binary Inputs Product Manual Contents Contents Page 1 General... 3 1.1 Using the product manual...3 1.1.1 s...4 1.2 Overview of product

More information

KNX function and configuration

KNX function and configuration 2 KNX function and configuration Introduction A presence detector monitors the detection zone for occupancy, and causes one or more actions to be executed when a person enters the detection area. In their

More information

Product documentation. KNX Blind- a.heating-act.fm w.3 Inputs Art.-No. MEG

Product documentation. KNX Blind- a.heating-act.fm w.3 Inputs Art.-No. MEG Product documentation KNX Blind- a.heating-act.fm w.3 Inputs Issue: 22.12.2010 KNX Product documentation Contents 1 Product definition... 3 1.1 Product catalogue... 3 1.2 Function... 3 2 Installation,

More information

Blind actuator 4-gang 230 V AC Order-No

Blind actuator 4-gang 230 V AC Order-No KNX/EIB Product documentation Issue: 11.02.2011 Blind actuator 4-gang 230 V AC KNX/EIB Product documentation Contents 1 Product definition... 3 1.1 Product catalogue... 3 1.2 Function... 3 2 Installation,

More information

Use of the application program

Use of the application program 2 Use of the application program Product family: Product type: Product type: Product type: Manufacturer: Push button 1-fold 2-fold 4-fold Siemens Name: Pushbutton UP 233, single with IR receiver DELTA

More information

Bosch Smart Home. Plug Instruction Manual

Bosch Smart Home. Plug Instruction Manual Bosch Smart Home Plug Instruction Manual Start making your home smart! Please be sure to install the Bosch Smart Home Controller first. Please ensure that you have a Bosch Smart Home Controller and the

More information

KNX TP1 Topology. KNX Association

KNX TP1 Topology. KNX Association KNX TP1 Topology Table of Contents 1 Topology Overall view... 3 2 Topology... 4 3 Topology: Area... 5 4 Topology: Several Areas... 6 5 Physical address... 7 6 Coupling Unit: Gate Function... 8 7 Coupler:

More information

Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD

Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD KNX Product documentation Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD Issue: 19.12.2012 Page 1 of 153 KNX Product documentation Contents 1 Product

More information

KNX S-B4T-UP. Actuator for 230 V or 24 V. Installation and Adjustment

KNX S-B4T-UP. Actuator for 230 V or 24 V. Installation and Adjustment EN KNX S-B4T-UP Actuator for 230 V or 24 V Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical data... 3 1.2. Structure... 4 1.2.1. Structure 230 V AC version... 4 1.2.2. Strucure

More information

Use of the application program

Use of the application program Application program description Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Table of contents Physical sensors Presence detector Siemens OPTISENS ice 5WG1

More information

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Output Controller Siemens UP 255/11 brightness controller or AP 255/12 brightness controller 5WG1 255-4AB11 or

More information

DIN RAIL 12/8/4 OUTPUT MODULE. BOxxB01KNX. Product Handbook

DIN RAIL 12/8/4 OUTPUT MODULE. BOxxB01KNX. Product Handbook DIN RAIL 12/8/4 OUTPUT MODULE BOxxB01KNX Product Handbook Product: BOxxB01KNX -BO12B01KNX -BO08B01KNX -BO04B01KNX Description: DIN RAIL 12/8/4 OUTPUT MODULE Document Version: 1.2 Date: 07/07/2015 1/16

More information

ABB i-bus KNX Room Master RM/S 3.1 Product Manual

ABB i-bus KNX Room Master RM/S 3.1 Product Manual ABB i-bus KNX Room Master RM/S 3.1 Product Manual Contents Contents Page 1 General... 3 1.1 Using the product manual...3 1.1.1 s...4 1.2 Room Master: Areas of application...5 1.2.1 Residential care homes...5

More information

The output variables can be force-controlled from a coordinating control system.

The output variables can be force-controlled from a coordinating control system. Produktname: 4-channel analog actuator Bauform: rail-mounted device Artikel-Nr.: 1022 00 ETS-Suchpfad: Gira Giersiepen / Output / Analog output 4fach / Analog actuator 4fach Scope of application: The analog

More information

Line Coupler, MDRC LK/S 2.1, GH Q R0001

Line Coupler, MDRC LK/S 2.1, GH Q R0001 , GH Q605 0019 R0001 The coupler can be used as a line In the distribution board the coupler is coupler or as an area coupler. Used as installed on the secondary line of the a line coupler it joins up

More information

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies PRODUCT MANUAL ABB i-bus KNX SV/S KNX-Power Supplies Contents Contents side 1 General... 3 1.1 Using the product manual...3 1.1.1 Structure of the product manual...4 1.1.2 Notes...4 1.2 Product and functional

More information

Use of the application program. 1. Functional description. instabus EIB Application Program Description. August 2016.

Use of the application program. 1. Functional description. instabus EIB Application Program Description. August 2016. IP- 001031 Table of contents Use of the application program 1 1. Functional description 1 2. Communication objects 4 3. s 4 General 4 Routing (Bus > IP) 4 Routing (IP > Bus) 5 IP 5 Setting the additional

More information

Product documentation. KNX Blind Act.FM w.3 Inputs Art.-No. MTN

Product documentation. KNX Blind Act.FM w.3 Inputs Art.-No. MTN Product documentation KNX Blind Act.FM w.3 Inputs Issue: 22.12.2010 KNX Product documentation Contents 1 Product definition... 3 1.1 Product catalogue... 3 1.2 Function... 3 2 Installation, electrical

More information

ABB i-bus EIB / KNX Telephone Gateway TG/S 3.1

ABB i-bus EIB / KNX Telephone Gateway TG/S 3.1 Product Manual ABB i-bus EIB / KNX Telephone Gateway TG/S 3.1 Intelligent Installation Systems This manual describes the function and configuration of the Telephone Gateway TG/S 3.1 Subject to changes

More information

Application program usage. Functional description

Application program usage. Functional description Application program usage Product family: Product type: Manufacturer: Name: Order-No.: Controller Controller Siemens Functional description IP Controller N350E 5WG1 350-1EB01 The IP Controller N350E is

More information

Binary Inputs, 4 fold K-BUS R. User manual-ver. 1 CTBI-04/00.1. KNX/EIB Intelligent Installation Systems

Binary Inputs, 4 fold K-BUS R. User manual-ver. 1 CTBI-04/00.1. KNX/EIB Intelligent Installation Systems Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R Binary Inputs, 4 fold User manual-ver. 1 CTBI-04/00.1 KNX/EIB Intelligent Installation Systems Contents 1. General-----------------------------------------------------------------------------------------------------------------

More information

Technical Documentation Intensity

Technical Documentation Intensity Intensity Status: Draft Firmware Version : v1.4 Hardware Version : Intensity Snr. 140505 / 140203 Order Number: INTXXX Technical Details: Power Supply Maximum Power Consumption Bus Power Consumption Fan-In

More information

Building Automation Training Center

Building Automation Training Center Building Automation Training Center Training Course: KNX Advanced Course General Information Course Description The KNX Advanced Course is an extension 100% practical course, to the KNX Basic Course. The

More information

ABB i-bus KNX IP Router, MDRC IPR/S 3.1.1, 2CDG110175R0011

ABB i-bus KNX IP Router, MDRC IPR/S 3.1.1, 2CDG110175R0011 Technical Data 2CDC502086D0201 Product description IP Router 3.1.1 is the interface between KNX installations and IP networks. It can be used as a line coupler or area coupler and can utilize the local

More information

Colour Touch Panel 3.5

Colour Touch Panel 3.5 Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R Colour Touch Panel 3.5 User manual-ver. 1.2 CHTF-35/01.1 CHTF-35/01.2.21 CHTF-35/01.2.22 CHTF-35/01.2.24 KNX/EIB Intelligent Installation Systems

More information