PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

Size: px
Start display at page:

Download "PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP"

Transcription

1 PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP UPDATED: OCTOBER 2017

2 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak Control System (CPCS) can be directly connected to a BACnet/IP based Building Automation System (BAS). Based on Carel s pcoweb serial card, the interface allows connection to an Ethernet network. 80 control points, including all basic information and set points for the PoolPak dehumidification system, are available through the interface. COMMANDPAK CONTROL SYSTEM CONFIGURATION FOR BACNET PoolPak dehumidifiers equipped with CPCS can be directly connected to a BACnet/IP based Building Automation System (BAS). Based on Carel s pcoweb serial card, the interface allows connection to an Ethernet network. 80 control points, including all basic information and set points for the PoolPak dehumidification system, are available through the interface. The BACnet configuration parameters for the controller are accessed in the configuration menu. To access this menu: 1. Press the program key ( ) on the RIU or CM1 module 2. Scroll down to Service then press Enter ( ). 3. Scroll up for the service password 0005, then press Enter ( ). 4. Scroll down to Unit Config then press Enter ( ). 5. Scroll down for the advanced password of 9995, then press Enter ( ). 6. Use the arrow keys to scroll down to BAS Interface, then press Enter ( ). 7. Press the Enter key to move the cursor to different fields. Use the arrow keys to change the following parameters as needed: TYPE BACnet This is the type of BAS system connecting. BAUD RATE Sets the baud rate for the onboard serial port. It must be set to for use with the BACnet interface is the factory default setting for this parameter. Note that this is the baud rate of the internal serial interface between the BACnet board and the PoolComPak controller. The baud rate of the BACnet MS/TP connection is set with a utility program from Carel. See the Interface Card Field Setup and Configuration section of this document for more information. BAS Addr 001 Sets the address of the BACnet interface card in the serial slot of the controller. It must be set to 1 for proper operation of the BACnet interface. The factory default setting is 1. Note that this is the internal serial address of the BACnet board. The station address for the BACnet MS/TP network is set with a utility program from Carel. See the Interface Card Field Setup and Configuration section of this document for more information. 8. After changing any of the above parameters, reboot the controller by cycling power with the unit control power switch. This switch is located within or adjacent to the main control panel of the dehumidifier PoolPak LLC. All rights reserved. Page 2

3 INTERFACE CARD FIELD SETUP AND CONFIGURATION The BACnet interface card is shipped from the factory with the following default settings: DHCP: ON IP Address:... Netmask:... Gateway:... DNS1:... DNS2:... BACnet ID (Device Instance): BACnet Type: IP Change the above card settings on the controller or keypad as follows: 1. Press and hold the Alarm ( ) and Enter ( ) keys. 2. Arrow down to Other Information then press Enter ( ) 3. Arrow down to PCOWEB/NET CONFIG then press Enter ( ) 4. Arrow down to PCOWEB, then press Enter ( ). (PCONET is for MS/TP) 5. Use the Enter ( ) key to move the cursor to the value you need to change. Use the arrow keys to change the value. 6. The last screen will say pconet CONFIG ENABLE, then Update pconet? Select YES then press Enter ( ). 7. After changing any of the above parameters, reboot the controller by cycling power with the unit control power switch. The above parameters along with UDP Port, Description, and Location can be changed through the web interface available through the Ethernet connection on the BACnet card. To access this page, enter the following address in a web browser: IP Address /config where IP Address is the address assigned to the card manually or through a DHCP server. The computer used must be on the same subnet as the BACnet card. Contact PoolPak Service at for login information. For any difficulty changing these parameters, contact PoolPak Service at for assistance. PHYSICAL NETWORK CONNECTION The 8P8C ( RJ-45 ) Ethernet socket is located on the pcoweb interface card. The pcoweb card occupies the serial card slot directly below the keypad built into the CM1 control module. This control module is located in the main control panel of the PoolPak dehumidifier. The Ethernet connection to the interface card should comply with standard installation practices. Use care to route the cable away from sources of interference and keep the maximum cable length less than 300 feet. CONTROL POINTS MAPPING 80 objects are accessible through the BACnet interface. Set points, sensor values, and enumerated variables are shared as analog-value objects. Status information points are shared as binary-value objects. The interface card is pre-configured at the factory with a device instance number of To change this value, follow the instructions shown in the Interface Card Field Setup and Configuration section of this document PoolPak LLC. All rights reserved. Page 3

4 The following table lists the available points along with their object types and instance numbers. TYPE READ/ WRITE INSTANCE NAME DESCRIPTION UNITS AV R 1 CPR1_xwfCprCur System 1 Cmpr Current Amps AV R 2 CPR2_xwfCprCur System 2 Cmpr Current Amps AV R 3 CPR3_xwfCprCur System 3 Cmpr Current Amps AV R 4 xwfairoffevprelhum Air Leaving Evap Rel Humidity (RH) % AV R 5 xwfairoffevptmp Air Leaving Evap Temperature C AV R 6 xwfauxaircoolpercent Aux Air Cooling Percent Output % AV R 7 xwfauxairheatpercent Actual Aux Air Heating % Output % AV R 8 xwfauxairheatpercent_1 Calc Aux Air Heating % Output % AV R 9 xwfexhairvol Exhaust Air Volume CFM AV R 10 xwfexhfancur Exhaust Fan Current Amps AV R 11 xwfmixboxpctopen Mixing Box Position % AV R 12 xwfoutairdewpoint Outside Air Dewpoint C AV R 13 xwfoutairrelhum Outside Air RH % AV R 14 xwfoutairtmp Outside Air Temperature C AV R 15 xwfoutairvol Outside Air Volume CFM AV R 16 xwfoutdprfbk Outside Air Damper Position % AV R 17 xwfpool1wtrtmp Pool1 Water Temperature C AV R 18 xwfpool2wtrtmp Pool2 Water Temperature C AV R 19 xwfpurairvol Purge Air Volume CFM AV R 20 xwfpurfancur Purge Fan Current Amps AV R 21 xwfrtnairdewpoint Return Air Dewpoint C AV R 22 xwfrtnairrelhum Return Air RH % AV R 23 xwfrtnairtmp Return Air Temperature C AV R 24 xwfsetevtminmixboxpos Event Min Mix Box Position % AV R 25 xwfsetmaxmixboxpos Max Mix Box Position % AV R 26 xwfsetminmixboxpos Min Mix Box Position % AV R 27 xwfsetpool1wtrtmp Pool1 Water Temp Setpoint F AV R 28 xwfsetpool2wtrtmp Pool2 Water Temp Setpoint F AV R 29 xwfsetrtnairrelhum Return Air RH Setpoint % AV R 30 xwfsetrtnairtmp Return Air Temp Setpoint F AV R 31 xwfsupairtmp Supply Air Temperature C AV R 32 xwfsupairvol Supply Air Volume CFM AV R 33 xwfsupfancur Supply Fan Current Amps AV R 34 xwfsurtmp Surface Temperature C AV R 1001 CPR1_xwiActiveFaultCode Cmpr1 Fault Code See below AV R 1002 CPR1_xwiMode Cmpr1 Actual Mode See below 2017 PoolPak LLC. All rights reserved. Page 4

5 BACnet Points List continued TYPE READ/ WRITE INSTANCE NAME DESCRIPTION UNITS AV R 1003 CPR2_xwiActiveFaultCode Cmpr2 Fault Code See below AV R 1004 CPR2_xwiMode Cmpr2 Actual Mode See below AV R 1005 CPR3_xwiActiveFaultCode Cmpr3 Fault Code See below AV R 1006 CPR3_xwiMode Cmpr3 Actual Mode See below AV W 1007 twisetinpevtminmixboxpos Event Min Mix Box Pos Setpoint % AV W 1008 twisetinpmaxmixboxpos Max Mix Box Pos Setpoint % AV W 1009 twisetinpminmixboxpos Min Mix Box Pos Setpoint % AV W 1010 twisetinppool1wtrtmp Pool1 Water Temp Setpoint F AV W 1011 twisetinppool2wtrtmp Pool2 Water Temp Setpoint F AV W 1012 twisetinppurmixboxpos Purge Mode Mix Box Setpoint % AV W 1013 twisetinprtnairrelhum Return Air RH Setpoint % AV W 1014 twisetinprtnairtmp Return Air Temp Setpoint F AV R 1015 xwiauxaircoolstgrqd Aux Air Cool Requested (Rqd) Stages AV R 1016 xwiauxairheatstgrqd Aux Air Heat Stages Rqd Stages AV R 1017 xwicpr1modereq Cmpr1 Mode Requested Stages AV R 1018 xwicpr2modereq Cmpr2 Mode Requested Stages AV R 1019 xwicpr3modereq Cmpr3 Mode Requested Stages AV R 1020 xwidehstgrqd Dehumidification Stages Rqd Stages AV R 1021 xwiheatcoolstgrqd Heat/Cool Stages Rqd Stages AV R 1022 xwilastunitgnlfltcode Last Unit Fault Code See below AV R 1023 xwisengnlfltcode Sensor Fault Code See below AV R 1024 xwiunitgnlfltcode Unit Fault Code See below BV R 1 xbalarm_do Alarm Output on/off BV R 2 xbauxaircool1_do Aux Cool 1 Output on/off BV R 3 xbauxaircool2_do Aux Cool 2 Output on/off BV R 4 xbauxaircool3_do Aux Cool 3 Output on/off BV R 5 xbauxairheat1_do Aux Air Heat 1 Output on/off BV R 6 xbauxairheat2_do Aux Air Heat 2 Output on/off BV R 7 xbauxairheat3_do Aux Air Heat 3 Output on/off BV W 8 xbbasforcenopurmod Force NoPurge Mode on/off BV W 9 xbbasforceoccupied Force Occupied on/off BV W 10 xbbasforcepurmod Force Purge Mode on/off BV W 11 xbbasforceunoccupied Force Unoccupied on/off BV R 12 xbexhfan_do Exhaust Fan Output on/off BV R 13 xboccupied Occupied Mode on/off BV R 14 xbpool1auxwtrheat_do Pool1 Aux Heat Output on/off BV R 15 xbpool2auxwtrheat_do Pool2 Aux Heat Output on/off 2017 PoolPak LLC. All rights reserved. Page 5

6 TYPE COMPRESSOR ACTIVE FAULT CODE AV1001, AV1003 and AV1005 are enumerated values indicating the most significant active fault in each compressor system of the dehumidifier. The present value for these objects can be decoded as follows: 0 Normal READ/ WRITE INSTANCE 1 Run/Pumpdown switch in pumpdown position 2 System warmup in progress. Normal for 5 minutes after power-on. 3 Liquid temperature sensor failed 4 Suction temperature sensor failed 5 Compressor current sensor failed 6 Suction pressure transducer failed 7 Discharge pressure transducer failed 13 Low refrigerant pressure detected 14 High compressor motor temperature detected 15 High refrigerant pressure detected 50 Compressor locked out due to 10 faults since last power cycle NAME DESCRIPTION UNITS BV R 16 xbpoolwtrcndflowa Pool Water Flow Circuit A on/off BV R 17 xbpoolwtrcndflowb Pool Water Flow Circuit B on/off BV R 18 xbpurfan_do Purge Fan Output on/off BV R 19 xbpurmod Purge Mode Active on/off BV R 20 xbremexhfan_do Remote Exhaust Fan Output on/off BV R 21 xbsmartpump1_do Pool Pump Output on/off BV R 22 xbsupfan_do Supply Fan Output on/off COMPRESSOR SYSTEM MODE AND MODE REQUESTED AV1002, AV1004, AV1006 (Modes) and AV1017, AV1018, AV1019 (Modes Requested) are enumerated values indicating the operation mode of the corresponding compressor system. The present value for these objects can be decoded as follows: 0 Compressor Off 1 Air Heating Mode. Recovered heat is being used to heat the air. 3 Pool Water Heating Mode. Recovered heat is being used to heat the water. 4 Air Cooling Mode. Recovered heat is being rejected to an external air or water-cooled condenser. SENSOR FAULT CODE (XWISENGNLFLTCODE) AV1023 is an enumerated value indicating a failed sensor. The value for this object is decoded as follows: 0 Normal. No sensors in failure. 1 Return air temperature 2 Return air humidity 3 Supply air temperature 4 Outside air temperature 2017 PoolPak LLC. All rights reserved. Page 6

7 5 Supply air CFM 6 Exhaust air CFM 7 Purge air CFM 8 Outside air CFM 9 Supply fan current signal 10 Exhaust fan current signal 11 Purge fan current signal 13 Pool 1 temperature 14 Pool water circuit A pressure drop 15 Pool 2 temperature 16 Pool water circuit B pressure drop 19 Air off evaporator temperature 20 Air off evaporator humidity 22 Evaporator bypass damper position feedback 24 Outside air damper position feedback 25 Recirc air damper position feedback 26 Space pressure 27 Return air CO2 level 28 Surface temperature 29 Outside air filter pressure drop 30 Return air filter pressure drop UNIT FAULT CODE AND LAST UNIT FAULT CODE (XWIUNITGNLFLTCODE) AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit. The last fault (AV1022) indicates the most recent previous fault condition for the unit. The value for these objects is decoded as follows: 0 Normal 1 Coil freeze warning active 2 Fire trip mode active 3 Smoke purge mode active 4 Supply fan not running 5 Exhaust fan not running 6 Purge fan not running 7 Exhaust fan VFD fault active 8 Supply fan VFD fault active 9 Purge fan VFD fault active 10 System startup active Normal for 5 minutes after power on. 11 Supply fan deadheaded. Supply fan requested on with both outside air and recirc air dampers less than 25% open. 12 Aux heating system failure 13 Aux cooling system failure 14 Compressor Module 1 fault active 15 Compressor Module 2 fault active 16 Compressor Module 3 fault active 2017 PoolPak LLC. All rights reserved. Page 7

8 CHANGING A SET POINT Two analog value objects are allocated for each set point, a readable value and a writeable value. To change a set point, set the present value of the writeable object to the new set point value. Verify that the controller accepted the change by reading the value of the corresponding readable object. The controller applies limits to the set point values. If the BAS tries to set an inappropriate value, the readable object will show the min or max allowed value instead of the requested value. The BAS can detect this event by verifying the change in the readable object s present value. The following limits are applied by the controller: Return Air Temperature: 75 F 95 F Return Air Humidity: 40% 65% Pool Water Temperature: 75 F 95 F Damper Position: 0% 100% Mixing Box Position: 0% 100% Set points for temperature are represented by integer values in degrees Fahrenheit. CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s Purge mode directly. This control overrides all internal schedules and controls except for the freeze protection algorithm. To force purge mode, set the xbbasforcepurmod object value to the ON state and the xbbasforcenopurmod object value to the OFF state. To force non-purge mode, set the value of the xbbasforcepurmod object to OFF and the xbbasforcenopurmod object to ON. ACTIVE ALARM FLAG CONTROL The xbalarm_do binary value object indicates the status of the system alarm flag. This status corresponds to the red light inside the alarm button of the control module, CM1. When the present value of this object is ON, there is an uncleared alarm present in the controller. If there are no active alarms present, the value of xbalarm_do will change to OFF. If there are still active alarms present, the value of xbalarm_do will remain ON. To determine the actual alarm condition, the BAS can examine the present value of the active fault objects. See the Fault Code sections earlier in this document for a list of possible states PoolPak LLC. All rights reserved. Page 8

9 SYMPTOM POSSIBLE CAUSE SOLUTION The interface card is not properly connected to the network. Correct network wiring. The dehumidifier cannot be seen on the BACnet network. The variable values sent by the controller are different than those shown on the RIU. Power to the controller is off. The BAS is trying to access the interface with the wrong device instance number. Incorrect setting of the BAS configuration parameters in the service menu. If safe to do so, turn on the main disconnect and the control power switch(cps) in the control compartment of the dehumidifier. Follow the instructions in this document to set the instance number to a value appropriate for the BAS. Correct the parameter values to match the settings shown in this document. Set point changes are different than requested by the BAS. Requested set point change is outside of the acceptable range. Select set points based on the acceptable range. For questions about the interface that are not answered in this document, please contact the PoolPak Service department at BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). This trademark is used in the text, but for the sake of readability, it is not individually marked. With more than 45 years of experience in indoor pool dehumidification equipment manufacturing, PoolPak LLC is the most well-known brand in the industry. Our people and products work daily to improve the quality and comfort of indoor pool environments. PoolPak dehumidification solutions include a variety of heating, ventilation, and air conditioning systems, in addition to an industry-leading PoolPak support network. For more information, please visit Industrial Drive York, Pennsylvania USA Fax PoolPak LLC. All rights reserved. SVW07-MPKBACNIP

BACnet MS/TP Interface User s Guide

BACnet MS/TP Interface User s Guide PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak

More information

PoolPak SWHP Series ECCIII Modbus RTU BAS Interface DOCUMENT #: SVW05-ECCIIIMODBUS

PoolPak SWHP Series ECCIII Modbus RTU BAS Interface DOCUMENT #: SVW05-ECCIIIMODBUS PoolPak SWHP Series ECCIII Modbus RTU BAS Interface DOCUMENT #: SVW05-ECCIIIMODBUS-20180530 UPDATED: MAY 2018 INTRODUCTION PoolPaks equipped with the ECCIII controller can be directly connected to a Modbus

More information

CommandCenter Operator Panel

CommandCenter Operator Panel CommandCenter Operator Panel Introduction This document describes the different features of the Operator Panel (local or remote) that is used with the Seresco units. Startup Screens When the unit start

More information

Millennium Simplicity Elite Parameter Points and Quirks

Millennium Simplicity Elite Parameter Points and Quirks Millennium Simplicity Elite Parameter Points and Quirks How to access, view and change parameter settings Program Button Test Reset UP Alarms Change Data Address Down 1. Push the Program button once. The

More information

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers Wireless Sensor CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-583-01 6/2/2017 Verify that you have the most current version of this

More information

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS 1 25 95 00 Integrated Automation Control Sequences for HVAC GENERAL The HVAC operational sequences in this guideline are commonly used by Duke University. They are being provided as a preferred design

More information

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide Quick Start Guide 560/583 DDC 8733914716(2014/02) Please refer to the included Hardware User s Guide and BACview Installation and Operation Manual for more detailed information on setting up and using

More information

SE7600E Series Application Guide

SE7600E Series Application Guide SE7600E Series Application Guide Schneider Electric SE7600E Series RTU Controller with IAQ Control Application Guide CONTENTS Solution Overview 2 Product Overview 3 Features & Benefits 3 System Overview

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001 Tracer Controls Tracer MP.501 Controller June 2001 BAS-PRC008-EN Introduction The Tracer MP.501 controller is a configurable, multi-purpose controller used to provide direct-digital control for heating,

More information

Communication Register Map - Uniflair Cooling

Communication Register Map - Uniflair Cooling DIGITAL 0 1 1 - - - - DIGITAL 1 2 2 System On (Fan) 0 or 1 boolean R DIGITAL 2 3 3 Compressor 1 0 or 1 boolean R DIGITAL 3 4 4 Compressor 2 0 or 1 boolean R DIGITAL 4 5 5 Compressor 3 0 or 1 boolean R

More information

BACVIEW DEVICE INTERFACE For DDC Software Version Software Configuration Guide (11/2015)

BACVIEW DEVICE INTERFACE For DDC Software Version Software Configuration Guide (11/2015) DEVICE INTERFACE For DDC Software Version 7.05.03 Software Configuration Guide 8733940857 (11/2015) 2 Table of contents TABLE OF CONTENTS Key to Symbols... 3 Warnings... 3 BACview Interfaces... 3 BACview

More information

RGX COMMUNICATIONS GATEWAY

RGX COMMUNICATIONS GATEWAY RGX COMMUNICATIONS GATEWAY BTU Ventilation Corporation 47418 US Highway 10 Perham, Mn 56573 USA Phone (218) 346-7482 Fax (218) 346-7485 http:/// Manual ver 2.1 Copyright BTU Ventilation Corp 2008 RGX Communications

More information

SE7600E Series Application Guide

SE7600E Series Application Guide Schneider Electric SE7600E Series RTU Controller with IAQ Control Application Guide CONTENTS Solution Overview 2 Product Overview 3 Features & Benefits 3 System Overview & Architecture 4 Models Available

More information

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification General The VT76xxW series is designed for single-stage and multi-stage control of water source heat pumps with dedicated

More information

MicroTech II ServiceTools for Applied Air Handling Unit Controllers

MicroTech II ServiceTools for Applied Air Handling Unit Controllers Users Manual UM 734-6 Group: Controls Part Number: UM 734 Date: June 2007 Supersedes: UM 734-5 MicroTech II ServiceTools for Applied Air Handling Unit Controllers Rooftop Models RPS, RAH, RDT, RFS/RCS,

More information

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005 Tracer Controls Tracer MP501 Controller January 2005 BAS-PRC008-EN Introduction The Tracer MP501 controller is a configurable, multi-purpose controller used to provide direct-digital control for heating,

More information

Installation and Operation Instructions

Installation and Operation Instructions 33ZC ComfortID Test and Balance Tool Software Installation and Operation Instructions Part Number 33ZCBAL-SA INSTALLATION The ComfortID Test and Balance Tool software requires no special installation.

More information

FX 2 Instruction Manual

FX 2 Instruction Manual FX 2 Instruction Manual Climma Compact Version Annapolis MD USA 301 352 6962 info@veco-na.com Introduction: The FX2-DX digital controller operates onboard air conditioning equipment to provide room temperature

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet DataSheet ev 1.12.302/4.3 October 27, 2014 Operating Sequence Standard Occupied During normal occupied operation the display will

More information

Installation Manual. DZK BACnet

Installation Manual. DZK BACnet Installation Manual DZK BACnet InterfacepbilCodarPageNumber TABLE OF CONTENTS Page Overview... 5 Outline and Features... 5 System outline... 5 Specifications and device elements... 6 Functional specifications...

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL INTEGRATED PROGRAMMABLE CONTROLS

INSTALLATION, OPERATION & MAINTENANCE MANUAL INTEGRATED PROGRAMMABLE CONTROLS INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR EV450, ALL HE, LE AND RD UNITS Carel c.pco Mini Carel c.pcoe Expansion Board WWW.RENEWAIRE.COM IMPORTANT SAFETY INFORMATION WARNING Arc flash and electric

More information

System Controls Suggested Specification

System Controls Suggested Specification 1. Description A. Rooftop Unit Controller The Rooftop Unit Controller shall come equipped with a proportional-integral (PI) controller for accurate temperature control. The rooftop unit controller shall

More information

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL 641-K31 1 BACVIEW INSTALLATION AND OPERATION IMPORTANT: This manual is for use with controller ZONE I/O 560 FHP part number 641-224

More information

MicroTech II Vertical Self-contained Systems Unit Controller

MicroTech II Vertical Self-contained Systems Unit Controller Installation and Maintenance IM-710 Group: Applied Systems Part Number: IM710 Date: February 2002 MicroTech II Vertical Self-contained Systems Unit Controller Used with McQuay models: SWP and SWT BACK

More information

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions Controls Guide for XeteX Units Beyond meeting the typical specification and performance requirements, controlling the equipment is usually the most important success factor for HVAC projects. XeteX provides

More information

INTELLI-HOOD TROUBLESHOOTING GUIDE

INTELLI-HOOD TROUBLESHOOTING GUIDE INTELLI-HOOD TROUBLESHOOTING GUIDE Melink Corporation (513) 965-7300 www.melinkcorp.com Last Updated 7/22/2015 Table of Contents Page I. About this Document 2 II. Related Documents 2 III. Glossary of Abbreviations

More information

Economizer Controller Installation Guide

Economizer Controller Installation Guide Economizer Controller Installation Guide PD 9/20/2013 - v 1.2 2 Table of Contents INPUTS... 3 OUTPUTS... 3 WHILE INSTALLING THIS CONTROLLER... 3 ACCESSORIES... 3 OPTIONAL ACCESSORIES... 3 INSTALLATION

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? RTU Open v5 CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-697-01 6/11/2018 Verify that you have the most current version of this document

More information

VT8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

VT8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller 1 User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller CONTENTS Home Screen Display 2 How to Enter Setup Screen 3 Setup Screen Display 4 ClockSettings 5 Schedule Settings 6 Occupancy

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net Digi-RTU WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve

More information

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN ECON-ZIP-BASE ZIP Economizer Base Unit 24 VAC ± 20%, 50/60 Hz; Class 2 power source 4 VA Base Control (ECON-ZIP-BASE) 5.5 VA Base Control with Energy Module (ECON-ZIP-BASE + ECON-ZIP-EM) Power Consumption

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x

FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x S90-500 O/JUL 2002 File: SERVICE MANUAL - SECTION 90 Replaces: S90-500 O/APR-2001 Dist: 3, 3a, 3b, 3c OPERATION FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x S90-500 O FRICK QUANTUM ACUair CONTROL PANEL

More information

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN Tracer Controls Tracer Unitary Controller 7 April 2003 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports the following

More information

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN Installation and Operation Tracer MP501 Controller CNT-SVX08B-EN Installation and Operation Tracer MP501 Controller CNT-SVX08B-EN April 2005 CNT-SVX08B-EN Tracer MP501 Controller Installation and Operation

More information

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet DataSheet ev 1.12.307/4.0 June 14, 2018 Operating Sequence Standard Occupied During normal occupied

More information

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC.   RATING IS 1 AMP COND. B ENABLE COOL B ENABLE. Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER

More information

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet DataSheet ev 1.12.307/4.0 Jun 20, 2018 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012 Product Catalog Tracer Controller MP501 May 2012 BAS-PRC008-EN Copyright 2012 Trane. All rights reserved. This document and the information in it are the property of Trane and may not be used or reproduced

More information

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Engineering Data ED15080-1 Group: Controls Date: June 2002 MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Alerton BACtalk Building

More information

Andover ContinuumTM. b3850 Series Terminal Controllers

Andover ContinuumTM. b3850 Series Terminal Controllers TM b3850 Series Terminal Controllers The TM b3850 series controllers are native BACnet controllers that communicate on an RS-485 field bus as Master devices using the MS/TP BACnet protocol. 02 Features

More information

BACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies

BACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies BACnet PTEC Controller Constant Volume - Cooling Only, Application 6660 Application Note 140-1107 Building Technologies Table of Contents Overview... 4 BACnet... 5 Hardware Inputs... 5 Room Unit Identification...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS EIFM CONTROL REPLACEMENT KIT 8620-239 For Use with 3-1/2 Through 6 Ton Wall Mount Air Conditioners and Heat Pumps with EIFM-5* Economizers or "E" Vent Option Bard Manufacturing

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP Installation and Maintenance Manual IM 853 Group: Controls Part Number: IM 853 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet

More information

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...

More information

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions Before Starting Installation Warning Shut power to unit prior to any work being done. Personal injury or death could result. Only qualified HVAC service personnel should install, troubleshoot, repair or

More information

BACnet Protocol Implementation Conformance Statement (PICS) Integrity, Innovation. Service Excellence. Version 8.0 Melink Document #IH-ENG-DTS-BAC-006

BACnet Protocol Implementation Conformance Statement (PICS) Integrity, Innovation. Service Excellence. Version 8.0 Melink Document #IH-ENG-DTS-BAC-006 Integrity, Innovation. Service Excellence. BACnet Protocol Implementation Conformance Statement (PICS) Version 8.0 Melink Document #IH-ENG-DTS-BAC-006 Melink Corporation 5140 River Valley Rd Cincinnati,

More information

The Bard BrightStat Room Controllers

The Bard BrightStat Room Controllers The Bard BrightStat Room Controllers Introduction Smart energy management has never been easier than with the BrightStat Room Controllers for Bard Air Conditioning and Heat Pump applications. Designed

More information

MANUAL INSTALLATION + SERVICE. Price Intelligent Controller. PIC Series. v400 Issue Date: 12/18/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION + SERVICE. Price Intelligent Controller. PIC Series. v400 Issue Date: 12/18/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION + SERVICE Price Intelligent Controller PIC Series v400 Issue Date: 12/18/18 2018 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General...1 Installing

More information

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Engineering Data ED 15080-2 Group: Controls Part Number: ED 15080 Date: April 2006 Supercedes: ED 15080-1 MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained

More information

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN IntesisBox HS-RC-MBS-1 v.0.1 Modbus RTU (EIA-485) Interface for Hisense air conditioners. Compatible with commercial line of air conditioners commercialized by Hisense. User Manual Issue Date: 12/2017

More information

Fast Route to Reliable Energy Savings ZIP Economizer

Fast Route to Reliable Energy Savings ZIP Economizer Fast Route to Reliable Energy Savings ZIP Economizer LCD Display Automotive quality, easy-to-read display allows easy verifi cation of set values and real time operating information Alarm Notification

More information

Dual Digital Module Technical Guide

Dual Digital Module Technical Guide Factory Packaged Controls Coil Products Dual Digital Module Table of Contents OVERVIEW... 3 INSTALLATION AND WIRING... 4 Environmental Requirements...4 Mounting...4 Power Supply and Communications...4

More information

BCM. MicroTech II Chiller Unit Controller BACnet Communication Module. Installation and Maintenance Manual IM ASHRAE 135, MCQ Rev.

BCM. MicroTech II Chiller Unit Controller BACnet Communication Module. Installation and Maintenance Manual IM ASHRAE 135, MCQ Rev. Installation and Maintenance Manual IM 736-0 Part No: 736015423 Group: McQuay Controls Date: January 2003 MicroTech II Chiller Unit Controller BACnet Communication Module ASHRAE 135, 2001 WSC Water-Cooled

More information

Submittal Data Sheet intelligent Touch Manager DCM601A71

Submittal Data Sheet intelligent Touch Manager DCM601A71 For use with the following VRV Models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXTQ, FXUQ, FXZQ, VAM For use with the following Daikin SkyAir Models: FAQ, FBQ, FCQ, FHQ, FTQ Capacity:

More information

VTR8300 User Interface Guide VTR8300 Room Controller Series

VTR8300 User Interface Guide VTR8300 Room Controller Series VTR8300 User Interface Guide VTR8300 Room Controller Series CONTENTS Home Screen Display 2 How to Enter Setup Screen 3 Setup Screen Display 3 Network Settings 4 ZigBee Network Settings 4 BACnet Network

More information

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB User Guide Multipipe Units CMAA / RTMA CNT-SVU004B-GB USER GUIDE WARNING Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of low water temperature,

More information

Table of Contents. RTU Open Controller

Table of Contents. RTU Open Controller RTU Open Controller Integration Guide CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-428-01 11/19/2010 Table of Contents Introduction...

More information

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE

More information

BACnet Integration Manual ITG-VZ7xxx-BAC-E04.doc ( _R4 Issue Date: May 31 st, 2012)

BACnet Integration Manual ITG-VZ7xxx-BAC-E04.doc ( _R4 Issue Date: May 31 st, 2012) Zoning Product Series VZ7260 & VZ7656 Series For Commercial Zoning Systems BACnet Integration Manual ITG-VZ7xxx-BAC-E04.doc (028-6011_R4 Issue Date: May 31 st, 2012) 1 VZ7260 Product Overview The Viconics

More information

IntesisBox PA-AC-MBS-1

IntesisBox PA-AC-MBS-1 IntesisBox PA-AC-MBS-1 v.2.3 Modbus RTU (EIA-485) Interface for Panasonic air conditioners. Compatible with Etherea line air conditioners commercialized by Panasonic. User s Manual Issue Date: 11/2017

More information

BACnet. b3867 Terminal Controllers

BACnet. b3867 Terminal Controllers BACnet b3867 Terminal Controllers The Andover Continuum TM b3867 is a native BACnet controller that communicates on an RS-485 field bus as a Master device using the MS/TP BACnet protocol. 02 Features Product

More information

FOCUS GUIDE VAV ZONE CONTROLLER. Configuration Guide for ProLon Focus Software

FOCUS GUIDE VAV ZONE CONTROLLER. Configuration Guide for ProLon Focus Software FOCUS GUIDE VAV ZONE CONTROLLER Configuration Guide for ProLon Focus Software www.proloncontrols.com info@proloncontrols.com 17 510, rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV. 6.2.0 PL-FOC-VAV-C/F-EN

More information

The PanasonicVRF Driver

The PanasonicVRF Driver The PanasonicVRF Driver The PanasonicVRF driver interfaces to a Panasonic or Sanyo variable refrigerant flow (VRF) air conditioning system. Compatible VRF systems include Panasonic ECOi, ECO G, and Sanyo

More information

Commercial Controls. Advanced control for saving time and money

Commercial Controls. Advanced control for saving time and money L Connection NetWork Commercial Controls Advanced control for saving time and money The efficient way to control hvac and building operations L Connection Network at a glance: Controls a wide range of

More information

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010 Product Catalog Tracer Controls Tracer Unitary Control August 2010 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports

More information

IntesisBox PA-AW-MBS-1 v.2.0

IntesisBox PA-AW-MBS-1 v.2.0 IntesisBox PA-AW-MBS-1 v.2.0 Modbus RTU (EIA485) Interface for Panasonic Aquarea series. User Manual Issue Date: 08/2014 r2.0 Order Code: PA-AW-MBS-1: Modbus RTU Interface for Panasonic Aquarea series

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 September 24, 2014 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides

More information

VT8600 Series Installation Guide. Rooftop Unit, Heat Pump and Indoor Air Quality Controller

VT8600 Series Installation Guide. Rooftop Unit, Heat Pump and Indoor Air Quality Controller VT8600 Series Installation Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller 2 Installation Guide VT8600 Series If replacing an existing Room Controller, label wires before removal of Controller.

More information

Sir Walter Scott may not have been thinking of building automation systems. How BACnet. Is Connecting At ASHRAE s Headquarters

Sir Walter Scott may not have been thinking of building automation systems. How BACnet. Is Connecting At ASHRAE s Headquarters This article was published in ASHRAE Journal, November 2009. Copyright 2009 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

Modbus Integration Integration for Modbus Functionality for VTR8300 Series

Modbus Integration Integration for Modbus Functionality for VTR8300 Series Modbus Integration Integration for Modbus Functionality for VTR8300 Series Building Management System *For data visualization and analysis Modbus Controller VT8000 Series room controllers 2 TABLE OF CONTENTS

More information

Owner's Manual. BACnet Gateway. Original Instructions. Commercial Air Conditioners. Models: ME30-24/D4(B)

Owner's Manual. BACnet Gateway. Original Instructions. Commercial Air Conditioners. Models: ME30-24/D4(B) Owner's Manual Original Instructions Commercial Air Conditioners BACnet Gateway Models: ME30-24/D4(B) User Notice Dear customer: Please read this manual carefully prior to installation and operation and

More information

Prodigy Control System Premium Rooftop Unit Control

Prodigy Control System Premium Rooftop Unit Control CONTROLS Prodigy Control System Premium Rooftop Unit Control Bulletin No. 210537 February 2010 Supersedes January 2010 L E N N O X L E N N O X L E N N O X OVERVIEW The Prodigy Control System intelligently

More information

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL USER'S GUIDE BARD-LINK TM LC1000-100/LC1500-100 SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead,

More information

BACnet Integration Manual ITG-VWG-50-BAC-E01.doc ( R1 Issue Date: January 10 th, 2012)

BACnet Integration Manual ITG-VWG-50-BAC-E01.doc ( R1 Issue Date: January 10 th, 2012) 6/ VWG-50 BACnet Integration Manual Viconics Wireless Gateway BACnet Integration Manual ITG-VWG-50-BAC-E01.doc (028-6039 R1 Issue Date: January 10 th, 2012) 1 Product Overview The VWG-50 and related wireless

More information

CONFIGURATION GUIDE. Model DVD. For Smart Stat with BACnet Systems

CONFIGURATION GUIDE. Model DVD. For Smart Stat with BACnet Systems Model DVD CONFIGURATION GUIDE For Smart Stat with BACnet Systems Page: 2 of 6 PRELOADED APPLICATIONS BUTTON NAVIGATION GUIDE Enters advanced menu when held for 5 seconds. Navigates between parameters.

More information

BACnet FF Configuration Wizard Guide

BACnet FF Configuration Wizard Guide BACnet FF Configuration Wizard Guide TABLE OF CONTENTS SYSTEM ENGINEERING GUIDE INTRODUCTION... 3 WEBStation-AX... 3 Features... 3 BACnet FF Configuration Wizard... 3 BACnet FF Configuration Requirement...

More information

OPERATION MANUAL.

OPERATION MANUAL. OPERATION MANUAL 1 2 The Prodigy control system is the latest example of Lennox commitment to advanced HVAC technology. Standard on every Strategos rooftop unit, the Prodigy control system makes setup,

More information

Economizer Control 2-1

Economizer Control 2-1 HVAC Economizers 101 Section #2 Economizer Control Methods 2-1 Section #2 Economizer Control Methods Most Commonly Used Control Strategy Dry-bulb changeover Enthalpy changeover Differential dry bulb Differential

More information

Building Management System Application Datasheet

Building Management System Application Datasheet Building Management System Optergy Enterprise + Proton IP (Internet) 1 2 3 4 BACnetO MSTP R MODBUS RTU Description Optergy Building Management System (BMS), is software that allows users to monitor and

More information

Belimo Energy Valve Communication Document

Belimo Energy Valve Communication Document Version 4_11_14 Belimo Energy Valve Communication Document > Learn more www.energyvalve.com Measures Energy Controls Power Manages Delta T Actuator Communication Actuator Communication The Energy Valve

More information

MicroTech III Chiller Unit Controller BACnet IP Communication Module

MicroTech III Chiller Unit Controller BACnet IP Communication Module Installation and Maintenance Manual IM 966 Group: Controls Part Number: IM 966 Date: October 2009 Supercedes: New MicroTech III Chiller Unit Controller BACnet IP Communication Module Pathfinder Chiller,

More information

Heatronic Introduction. BAS Integration Manual. Table of Contents

Heatronic Introduction. BAS Integration Manual. Table of Contents Heatronic 4000 BAS Integration Manual Introduction The Heatronic 4000 can communicate with a Building Automation System (BAS) using either BACnet IP or Modbus. This manual provides information about boiler

More information

Zio LCD Wall Modules TR70 AND TR70-H with Sylk bus

Zio LCD Wall Modules TR70 AND TR70-H with Sylk bus Zio LCD Wall Modules TR70 AND TR70-H with Sylk bus OPERATING GUIDE PREFACE This Operating Guide is intended to provide configuration information (using the Niagara Workbench tool) and a general overview

More information

Packaged Rooftop Air Conditioning Units

Packaged Rooftop Air Conditioning Units PACKAGED ROOFTOP AIR CONDITIONING UNITS QUICK START-UP GUIDE New Release Form 100.50-SU3 (1207) 035-21972-200 TM Packaged Rooftop Air Conditioning Units YPAL 050 YPAL 051 YPAL 060 YPAL 061 DESIGN LEVEL

More information

TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications

TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications Product Bulletin TEC2647Z-3, TEC2647Z-3+PIR, TEC2664Z-3 The technologically advanced TEC Zoning Control System provides

More information

FRICK QUANTUM HD UNITY SYSTEM CONTROLLER

FRICK QUANTUM HD UNITY SYSTEM CONTROLLER Form 090.670-O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c OPERATION FRICK QUANTUM HD UNITY SYSTEM CONTROLLER ENGINE ROOM CONDENSER VESSEL EVAPORATOR Version

More information

THERMOSTATS & CONTROLLERS

THERMOSTATS & CONTROLLERS DESCRIPTION The Belimo ZIP Economizer Series saves energy in buildings by using cool outside air as a means of cooling the indoor space. This application can drastically reduce HVAC energy costs while

More information

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M INSTALLATION INSTRUCTIONS PECCSUN672 Series Power Exhaust for York - 6 Ton Units Before Starting Installation Warning Severe injury can result from incorrect servicing. Only qualified HVAC service personnel

More information

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928- Group: Controls Part Number: 66920770 Date: July 2009 Supersedes: IM 928 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module NOTICE Use this

More information

MLM Integration with BMS Network Protocols

MLM Integration with BMS Network Protocols MLM Integration with BMS Network Protocols The Master Comms Unit 2 (MCU) serves as a gateway to other BMS protocols such as Lontalk or BACnet. The MCU features four diffuser data channels with a capacity

More information

CONTROLLER INSTALLATION OPERATION & QUICK START

CONTROLLER INSTALLATION OPERATION & QUICK START CONTROLLER INSTALLATION OPERATION & QUICK START Controller: 8403-066 ECU Series Controller Manual: 2100-559 Supersedes: NEW File: Tab 19 Date: 05-02-11 Page 1 of 6 TABLE OF CONTENTS Installation Note...

More information

STRA-17 Room controller. Installation and maintenance manual. Content

STRA-17 Room controller. Installation and maintenance manual. Content Content Installation preparations... Wiring diagram...3 Display handling...5 Technical data...6 Configuration...7 Operating modes...7 Controller modes...7 Activation operating modes...7 Control states...8

More information

Modbus Register Map: InRow ACRD60x / ACRC60x

Modbus Register Map: InRow ACRD60x / ACRC60x Modbus Map: InRow ACRD60x / ACRC60x Notes: 1. 16-bit registers (INT16, UINT16, ENUM) are transmitted MSB first (i.e., big-endian). 2. INT32 and UINT32 are most-significant word in n+0, least significant

More information

QUICK START GUIDE M2000 SERIES rue Charles, Suite 100, Mirabel, QC, J7J 1X9

QUICK START GUIDE M2000 SERIES rue Charles, Suite 100, Mirabel, QC, J7J 1X9 QUICK START GUIDE M2000 SERIES www.proloncontrols.com info@proloncontrols.com 17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV.2.0 PL-QCK-M2000-EN Copyright 2018 Prolon. All rights reserved. No

More information

IntesisBox TO-RC-MBS-1

IntesisBox TO-RC-MBS-1 IntesisBox TO-RC-MBS-1 v.1.5 MODBUS RTU (EIA485) Interface for Toshiba air conditioners from the Digital Inverter & VRF lines. User Manual Issue Date: 01/2014 Order Codes: TO-RC-MBS-1 Intesis Software

More information

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller Pocket Quick Reference Guide On the TOSHIBA RBC-AMS51E Remote Controller Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of data

More information