Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual"

Transcription

1 Relion 611 series Feeder Protection and Control REF611 Modbus

2

3 Document ID: 1MRS Issued: Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved

4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative.

5 Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network. It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

6 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN for the EMC directive, and with the product standards EN and EN for the low voltage directive. The product is designed in accordance with the international standards of the IEC series.

7 Table of contents Table of contents Section 1 Section 2 Introduction...5 This manual... 5 Intended audience... 5 Product documentation...6 Product documentation set...6 Document revision history... 6 Related documentation...7 Symbols and conventions...7 Symbols...7 Document conventions...7 Functions, codes and symbols Overview...11 Supported functions in REF Indications Premapped indications...13 Common data CTRL.CBCILO1 Circuit breaker enable signals (1)...13 CTRL.CBCSWI1 Circuit breaker (1) mom. position CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position...14 CTRL.CBXCBR1 Circuit-breaker control (1) LD0.CCBRBRF1 Circuit breaker failure protection (1) LD0.CMMXU1 Three-phase current measurement (1) LD0.DARREC1 Autoreclosing (1) LD0.DARREC1 Autoreclosing state (1)...17 LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1) LD0.DEFLPDEF1 Directional earth-fault protection, low stage (1) LD0.DEFLPDEF2 Directional earth-fault protection, low stage (2) LD0.DPHHPDOC1 Three-phase directional overcurrent protection, high stage (1)...18 LD0.DPHLPDOC1 Three-phase directional overcurrent protection, low stage (1) LD0.DPHLPDOC2 Three-phase directional overcurrent protection, low stage (2) LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1) REF611 1

8 Table of contents LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1)...19 LD0.EFLPTOC1 Non-directional earth-fault protection, low stage (1)...20 LD0.EFLPTOC2 Non-directional earth-fault protection, low stage (2)...20 LD0.INRPHAR1 Three-phase inrush detector (1) LD0.INTRPTEF1 Transient/intermittent earth-fault protection (1) LD0.LEDGGIO1 Indication LED states Color1/Color LD0.LEDGGIO1 Indication LED states OFF/ColorX LD0.LEDPTRC1 Global conditioning (1) LD0.MVGAPC1 Move (8 pcs) (1) LD0.NSPTOC1 Negative-sequence overcurrent protection (1) LD0.NSPTOC2 Negative-sequence overcurrent protection (2) LD0.PDNSPTOC1 Phase discontinuity protection (1)...25 LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1) LD0.PHHPTOC2 Three-phase non-directional overcurrent protection, high stage (2) LD0.PHIPTOC1 Three-phase non-directional overcurrent protection, instantaneous stage (1) LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1)...27 LD0.RESCMMXU1 Residual current measurement (1) LD0.RESVMMXU1 Residual voltage measurement (1) LD0.ROVPTOV1 Residual overvoltage protection (1) LD0.ROVPTOV2 Residual overvoltage protection (2) LD0.ROVPTOV3 Residual overvoltage protection (3) LD0.T1PTTR1 Three-phase thermal protection for feeders, cables and distribution transformers (1) LD0.TCSSCBR1 Trip circuit supervision (1) LD0.TCSSCBR2 Trip circuit supervision (2) LD0.TRPPTRC1 Master trip (1) LD0.TRPPTRC2 Master trip (2) LD0.VMMXU1 Three-phase voltage measurement (1) LD0.XAGGIO130 Physical I/O states (AIM card XA130) LD0.XGGIO100 Physical I/O states (PSM card X100)...30 LD0.XGGIO120 Physical I/O states (AIM card X120) LD0.XGGIO130 Physical I/O states (BIO card X130) Unmapped indications...32 All premapped three-phase protection function stages, start and operate/phase-dependent objects added REF611

9 Table of contents Common data DR.RDRE1 Disturbance recorder signals LD0.CBPSOF1 Switch onto fault (1) LD0.IL1TCTR1 Three-phase CT supervision (1) LD0.RCHLCCH1 Ethernet supervision (1) LD0.RESTCTR1 Io CT supervision (1) LD0.RESTVTR1 Uo VT supervision (1) LD0.UL1TVTR1 Three-phase VT supervision (1) Registers Premapped registers Active parameter setting group read and write...36 Control structure Control structure Control structure Control structure Control structure Control structure Control structure Control structure Device ID string Event record structure Fault record structure header Fault record data IED real-time clock (in local time mode), read and write (synchronize)...47 IED real-time clock (in UTC time mode), read and write (synchronize)...48 Indication bits mirrored in registers SSR1 System status register (1) device health...48 SSR2 System status register (2) IED mode and state SSR3 System status register (3) data available 1 (clientdependent) SSR4 System status register (4) data available 2 (clientdependent, user-definable) SSR5 System status register (5) device alive register SSR6 System status register (6) control command status (client-dependent) System register values Time and reason for latest IED reset...52 User-definable bits [Alt.2], visible on 0x,1x,3x and 4x User-definable registers [Alt.1], visible on 3x and 4x CTRL.CBCSWI1 Circuit breaker operation counter (1) LD0.CMMXU1 Phase current demand values (1) LD0.CMMXU1 Three-phase current measurement (1) REF611 3

10 Table of contents LD0.CSMSQI1 Sequence current measurement (1)...55 LD0.DARREC1 Autoreclosing counters (1)...55 LD0.DARREC1 Autoreclosing values (1) LD0.FMMXU1 Frequency measurement (1) LD0.PEMMTR1 Three-phase energy measurements (1)...56 LD0.PEMMXU1 Power measurement demand values (1) LD0.PEMMXU1 Three-phase power and energy measurement (1) LD0.RESCMMXU1 Residual current demand value (1)...58 LD0.RESCMMXU1 Residual current measurement (1) LD0.RESVMMXU1 Residual voltage demand value (1) LD0.RESVMMXU1 Residual voltage measurement (1) LD0.T1PTTR1 Three-phase thermal protection for feeders, cables and distribution transformers (1) LD0.VMMXU1 Three-phase voltage measurement (1) LD0.VMMXU1 Voltage demand values (1) LD0.VSMSQI1 Sequence voltage measurement (1)...61 Unmapped registers CTRL.LLN0 Local, Remote, Station, Off and Combinations.. 61 Controls Reset, acknowledge and trigger points CTRL.CBCSWI1 Circuit breaker control (1) LD0.LDEV1 IED warm reset (1) Unmapped control points...63 Section 3 Glossary REF611

11 1MRS B Section 1 Introduction Section 1 Introduction 1.1 This manual The point list manual describes the outlook and properties of the data points specific to the protection relay. The manual should be used in conjunction with the corresponding communication protocol manual. 1.2 Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation from an protection relay perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. REF611 5

12 Section 1 Introduction 1MRS B 1.3 Product documentation Product documentation set Planning & purchase Engineering Installation Commissioning Operation Maintenance Decommissioning, deinstallation & disposal Quick start guide Quick installation guide Brochure Product guide Operation manual Installation manual Connection diagram Engineering manual Technical manual Application manual Communication protocol manual IEC engineering guide Point list manual Cyber security deployment guideline GUID-0777AFDA-CADF-4AA9-946E-F6A856BDF75E V1 EN Figure 1: The intended use of manuals in different lifecycles Product series- and product-specific manuals can be downloaded from the ABB Web site Document revision history Document revision/date Product version History A/ First release B/ Content updated to correspond to the product version Download the latest documents from the ABB Web site 6 REF611

13 1MRS B Section 1 Introduction Related documentation Name of the document Modbus Communication Protocol Manual Document ID 1MRS Symbols and conventions Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property. The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices Document conventions A particular convention may not be used in this manual. Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the push button icons. To navigate between the options, use and. Menu paths are presented in bold. Select Main menu/settings. LHMI messages are shown in Courier font. To save the changes in nonvolatile memory, select Yes and press. Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks. REF611 7

14 Section 1 Introduction 1MRS B The corresponding parameter values are "On" and "Off". Input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. This document assumes that the parameter setting visibility is "Advanced" Functions, codes and symbols Table 1: Functions included in the relay Function IEC IEC IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage Three-phase directional overcurrent protection, low stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 2 Three-phase directional overcurrent protection, high stage, instance 1 Directional earth-fault protection, low stage, instance 1 Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Transient/intermittent earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Table continues on next page PHLPTOC1 3I> (1) 51P-1 (1) PHHPTOC1 3I>> (1) 51P-2 (1) PHHPTOC2 3I>> (2) 51P-2 (2) PHIPTOC1 3I>>> (1) 50P/51P (1) EFLPTOC1 Io> (1) 51N-1 (1) EFLPTOC2 Io> (2) 51N-1 (2) EFHPTOC1 Io>> (1) 51N-2 (1) EFIPTOC1 Io>>> 50N/51N DPHLPDOC1 3I> -> (1) 67-1(1) DPHLPDOC2 3I> -> (2) 67-1(2) DPHHPDOC1 3I>> -> (1) 67-2(1) DEFLPDEF1 Io> -> (1) 67N-1 (1) DEFLPDEF2 Io> -> (2) 67N-1 (2) DEFHPDEF1 Io>> -> 67N-2 INTRPTEF1 Io> -> IEF 67NIEF EFHPTOC1 Io>> (1) 51N-2 (1) NSPTOC1 I2> (1) 46 (1) 8 REF611

15 1MRS B Section 1 Introduction Function IEC IEC IEC-ANSI Negative-sequence overcurrent protection, instance 2 NSPTOC2 I2> (2) 46 (2) Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers ROVPTOV1 Uo> (1) 59G (1) ROVPTOV2 Uo> (2) 59G (2) ROVPTOV3 Uo> (3) 59G (3) T1PTTR1 3Ith>F 49F Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF Three-phase inrush detector INRPHAR1 3I2f> 68 Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1) Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2) Switch onto fault CBPSOF1 SOTF SOTF Other Input switch group 1) ISWGAPC ISWGAPC ISWGAPC Output switch group 2) OSWGAPC OSWGAPC OSWGAPC Selector 3) SELGAPC SELGAPC SELGAPC Minimum pulse timer (2 pcs) 4) TPGAPC TP TP Move (8 pcs), instance 1 MVGAPC MV (1) MV (1) Control Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB Autoreclosing DARREC1 O -> I 79 Condition monitoring and supervision Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1) Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2) Logging Disturbance recorder RDRE1 DR (1) DFR(1) Fault recorder FLTRFRC1 - FR Measurement Three-phase current measurement, instance 1 CMMXU1 3I 3I Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0 Residual current measurement, instance 1 Three-phase voltage measurement, instance 1 Sequence voltage measurement, instance 1 RESCMMXU1 Io In VMMXU1 3U 3U VSMSQI1 U1, U2, U0 U1, U2, U0 Table continues on next page REF611 9

16 Section 1 Introduction 1MRS B Function IEC IEC IEC-ANSI Residual voltage measurement RESVMMXU1 Uo Vn Frequency measurement, instance 1 FMMXU1 f f Three-phase power and energy measurement, instance 1 1) 10 instances 2) 20 instances 3) 6 instances 4) 10 instances PEMMXU1 P, E P, E 10 REF611

17 1MRS B Section 2 Section Overview This document describes the Modbus data points and structures available in the IED. The point list describes a superset of all data available through the standard configuration/s including the optional functionalities. The majority of the Modbus data points are valid for all standard configurations. Some data points are standard configuration or optional application dependent and thus not available in each IED. The unavailable, that means unused, data points always return value 0 when they are read. The configuration dependent and optional data do not overlap. 2.2 Supported functions in REF611 Table 2: Supported functions Function IEC A B C FE/C101 FE/C102 FE/C103 Protection Three-phase non-directional overcurrent protection, low stage PHLPTOC 1 1 Three-phase non-directional overcurrent protection, high stage PHHPTOC 2 2 Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC Non-directional earth-fault protection, low stage EFLPTOC 2 1) Non-directional earth-fault protection, high stage EFHPTOC 1 1) Non-directional earth-fault protection, instantaneous stage EFIPTOC 1 1) Three-phase directional overcurrent protection, low stage DPHLPDOC 2 Three-phase directional overcurrent protection, high stage DPHHPDOC 1 Directional earth-fault protection, low stage DEFLPDEF 2 1)2) 2 1)2) Directional earth-fault protection, high stage DEFHPDEF 1 1)2) 1 1)2) Transient/intermittent earth-fault protection INTRPTEF 1 1 Non-directional (cross-country) earth fault protection, using calculated Io EFHPTOC 1 3) 1 3) Negative-sequence overcurrent protection NSPTOC Phase discontinuity protection PDNSPTOC Residual overvoltage protection ROVPTOV 3 2) 3 2) Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR Table continues on next page REF611 11

18 Section 2 1MRS B Function IEC A B C FE/C101 FE/C102 FE/C103 Circuit breaker failure protection CCBRBRF Three-phase inrush detector INRPHAR Master trip TRPPTRC Switch onto fault CBPSOF Control Circuit-breaker control CBXCBR Autoreclosing DARREC (1) (1) (1) Condition monitoring and supervision Trip circuit supervision TCSSCBR Logging Disturbance recorder RDRE Fault recorder FLTRFRC Measurement Three-phase current measurement CMMXU Sequence current measurement CSMSQI Residual current measurement RESCMMXU Three-phase voltage measurement VMMXU 1 Sequence voltage measurement VSMSQI 1 Residual voltage measurement RESVMMXU 1 1 Frequency measurement FMMXU 1 Three-phase power and energy measurement PEMMXU 1 Other Input switch group ISWGAPC Output switch group OSWGAPC Selector SELGAPC Minimum pulse timer (2 pcs) TPGAPC Move (8 pcs) MVGAPC , 2,... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the standardized configuration. () = optional 1) Io selectable by parameter and default value is "Io measured" 2) "Uo measured" is always used 3) Io selectable by parameter and default value is "Io calculated" 12 REF611

19 1MRS B Section Indications Table 3: Column name BitA RegA IEC name SA name Description Value Explanations of the indications table columns Description Default 0X and 1X bit address for the data. Default 3X and 4X register.bit (00-15) address for the data. Original IED data object identification. Described in the IEC format as Logical Device.Logical Node and thereafter.data Object.Data Attribute. Logical Node is the same as the application function block name. The signal may have a defined label that is visible, for example, in the Application Configuration tool in PCM600. Short description of the signal. See the technical manual for more information. Meaning of the value states Premapped indications Common data 1 Table 4: Common data 1 CTRL.LLN Loc.stVal - Remote/Local state 0/1=Rem/Loc LocKeyHMI.stVal.Statio n DR.RDRE1 - Station state 1=Station RcdMade.stVal - DR recording made 1=Made CTRL.CBCILO1 Circuit breaker enable signals (1) Table 5: CTRL.CBCILO1 Circuit breaker enable signals (1) CTRL.CBCILO EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled REF611 13

20 Section 2 1MRS B CTRL.CBCSWI1 Circuit breaker (1) mom. position Table 6: CTRL.CBCSWI1 Circuit breaker (1) mom. position CTRL.CBCSWI1 POSITION Pos.stVal - Close bit 1=Close Pos.stVal - Open bit 1=Open Pos.stVal - Fault bit 1=Pos(00/11) CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position Table 7: CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position CTRL.CBCSWI1 POSITION Pos.stVal Close bit 1=Close Pos.stVal Open bit 1=Open < reserved > < reserved > Pos.stSeld SELECTED CB selected for control 1=Selected SynItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass CTRL.CBXCBR1 Circuit-breaker control (1) Table 8: CTRL.CBXCBR1 Circuit-breaker control (1) CTRL.CBXCBR BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked REF611

21 1MRS B Section LD0.CCBRBRF1 Circuit breaker failure protection (1) Table 9: LD0.CCBRBRF1 Circuit breaker failure protection (1) LD0.CCBRBRF Str.general CB_FAULT_AL Timer running 1=Running OpEx.general TRBU Fail, external trip 1=Ext.trip OpIn.general TRRET Internal re-trip 1=Re-trip LD0.CMMXU1 Three-phase current measurement (1) Table 10: LD0.CMMXU1 Three-phase current measurement (1) LD0.CMMXU HiAlm.stVal HIGH_ALARM High alarm 1=Alarm HiWrn.stVal HIGH_WARN High warning 1=Warning LoWrn.stVal LOW_WARN Low warning 1=Warning LoAlm.stVal LOW_ALARM Low alarm 1=Alarm LD0.DARREC1 Autoreclosing (1) Table 11: LD0.DARREC1 Autoreclosing (1) LD0.DARREC PrgRec.stVal INPRO AR in progess 1=In progress PrgRec1.stVal INPRO_1 1st shot in progess 1=In progress PrgRec2.stVal INPRO_2 2nd shot in progess 1=In progress PrgRec3.stVal INPRO_3 3rd shot in progess 1=In progress PrgRec4.stVal INPRO_4 4th shot in progess 1=In progress Table continues on next page REF611 15

22 Section 2 1MRS B PrgRec5.stVal INPRO_5 5th shot in progess 1=In progress SucRec.stVal SUC_RECL Successful AR 1=Success UnsRec.stVal UNSUC_RECL Unsuccessful AR 1=Unsuccess InInhRec.stVal INHIBIT_RECL Inhibit reclose 1=Inhibit InBlkThm.stVal BLK_THERM Thermal block 1=Block LO.stVal LOCKED Lockout status 1=Lockout RdyRec.stVal READY Reclose ready 1=Ready ActRec.stVal ACTIVE Reclose active 1=Active PrgDsr.stVal DISCR_INPRO Discr.time in progress 1=In progress PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress FrqOpAlm.stVal FRQ_OP_ALM Frequent op. Alarm 1=Alarm RclTmStr.stVal Reclaim time started ProCrd.stVal Protection coordination 1=In progress CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed OpCls.general CLOSE_CB Operate (close XCBR) 1=Close CB OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal REF611

23 1MRS B Section LD0.DARREC1 Autoreclosing state (1) Table 12: LD0.DARREC1 Autoreclosing state (1) LD0.DARREC AutoRecOn.stVal AR_ON AutoRecloser state 0/1=Off/On LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1) Table 13: LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1) LD0.DEFHPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.DEFLPDEF1 Directional earth-fault protection, low stage (1) Table 14: LD0.DEFLPDEF1 Directional earth-fault protection, low stage (1) LD0.DEFLPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.DEFLPDEF2 Directional earth-fault protection, low stage (2) Table 15: LD0.DEFLPDEF2 Directional earth-fault protection, low stage (2) LD0.DEFLPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate REF611 17

24 Section 2 1MRS B LD0.DPHHPDOC1 Three-phase directional overcurrent protection, high stage (1) Table 16: LD0.DPHHPDOC1 Three-phase directional overcurrent protection, high stage (1) LD0.DPHHPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate LD0.DPHLPDOC1 Three-phase directional overcurrent protection, low stage (1) Table 17: LD0.DPHLPDOC1 Three-phase directional overcurrent protection, low stage (1) LD0.DPHLPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate REF611

25 1MRS B Section LD0.DPHLPDOC2 Three-phase directional overcurrent protection, low stage (2) Table 18: LD0.DPHLPDOC2 Three-phase directional overcurrent protection, low stage (2) LD0.DPHLPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1) Table 19: LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1) LD0.EFHPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1) Table 20: LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1) LD0.EFIPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate REF611 19

26 Section 2 1MRS B LD0.EFLPTOC1 Non-directional earth-fault protection, low stage (1) Table 21: LD0.EFLPTOC1 Non-directional earth-fault protection, low stage (1) LD0.EFLPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.EFLPTOC2 Non-directional earth-fault protection, low stage (2) Table 22: LD0.EFLPTOC2 Non-directional earth-fault protection, low stage (2) LD0.EFLPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.INRPHAR1 Three-phase inrush detector (1) Table 23: LD0.INRPHAR1 Three-phase inrush detector (1) LD0.INRPHAR Str.general BLK2H General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start REF611

27 1MRS B Section LD0.INTRPTEF1 Transient/intermittent earth-fault protection (1) Table 24: LD0.INTRPTEF1 Transient/intermittent earth-fault protection (1) LD0.INTRPTEF Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.LEDGGIO1 Indication LED states Color1/Color2 These LED indication points interpret the case when a signal is wired to both the OK and ALARM inputs, but inverted to the other. This means that the LED toggles between red and green colors. The default color for ALARM is red and green for OK. Colors can, however, be reconfigured with a setting parameter. Signal NOT OK ALARM RESET LEDx GUID-2AE4D47A-2BBD-4422-A81C-CF2EB V1 EN Figure 2: Signal wired to both OK and ALARM inputs inverted to the other If the OK and ALARM inputs are wired to separate indication signals, the LED will have three legal states and cannot be expressed with one bit only. In this case, it is possible to combine this LED bit interpretation with the corresponding value from the other LED state interpretation. Signal 1 Signal 2 OK ALARM RESET LEDx GUID E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN Figure 3: Separate signals wired to OK and ALARM inputs REF611 21

28 Section 2 1MRS B Table 25: LD0.LEDGGIO1 Indication LED states Color1/Color2 LD0.LEDGGIO LEDSt1.stVal - LED 1 state 0/1=Color1/ LEDSt2.stVal - LED 2 state 0/1=Color1/ LEDSt3.stVal - LED 3 state 0/1=Color1/ LEDSt4.stVal - LED 4 state 0/1=Color1/ LEDSt5.stVal - LED 5 state 0/1=Color1/ LEDSt6.stVal - LED 6 state 0/1=Color1/ LEDSt7.stVal - LED 7 state 0/1=Color1/ LEDSt8.stVal - LED 8 state 0/1=Color1/ LEDSt9.stVal 1) - LED 9 state 0/1=Color1/ LEDSt10.stVal 1) - LED 10 state 0/1=Color1/ LEDSt11.stVal 1) - LED 11 state 0/1=Color1/ <reserved> 0 1) Check Communication Management tool in PCM600 or LHMI or WHMI to confirm the availability for a particular device configuration LD0.LEDGGIO1 Indication LED states OFF/ColorX These LED indication points interpret the case when an indication signal is wired to either the OK or ALARM input of the LED function block. The default color for ALARM is red and green for OK. Colors can, however, be reconfigured with a setting parameter. Signal OK ALARM RESET LEDx Signal OK ALARM RESET LEDx GUID F8-C2DE-4138-B2C0-6B7C2774D4D2 V1 EN Figure 4: Signal wired to either OK or Alarm input 22 REF611

29 1MRS B Section 2 Table 26: LD0.LEDGGIO1 Indication LED states OFF/ColorX LD0.LEDGGIO LEDSt1.stVal - LED 1 state 0/1=Off/Color LEDSt2.stVal - LED 2 state 0/1=Off/Color LEDSt3.stVal - LED 3 state 0/1=Off/Color LEDSt4.stVal - LED 4 state 0/1=Off/Color LEDSt5.stVal - LED 5 state 0/1=Off/Color LEDSt6.stVal - LED 6 state 0/1=Off/Color LEDSt7.stVal - LED 7 state 0/1=Off/Color LEDSt8.stVal - LED 8 state 0/1=Off/Color LEDSt9.stVal 1) - LED 9 state 0/1=Off/Color LEDSt10.stVal 1) - LED 10 state 0/1=Off/Color LEDSt11.stVal 1) - LED 11 state 0/1=Off/Color <reserved> 0 1) Check Communication Management tool in PCM600 or LHMI or WHMI to confirm the availability for a particular device configuration LD0.LEDPTRC1 Global conditioning (1) Table 27: LD0.LEDPTRC1 Global conditioning (1) LD0.LEDPTRC Str.general - Global start 1=Start Op.general - Global operate 1=Operate LD0.MVGAPC1 Move (8 pcs) (1) Table 28: LD0.MVGAPC1 Move (8 pcs) (1) LD0.MVGAPC SPCSO1.stVal Output 1 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On SPCSO2.stVal Output 2 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On Table continues on next page REF611 23

30 Section 2 1MRS B SPCSO3.stVal Output 3 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On SPCSO4.stVal Output 4 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On SPCSO5.stVal Output 5 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On SPCSO6.stVal Output 6 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On SPCSO7.stVal Output 7 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On SPCSO8.stVal Output 8 0/1=Off/On <Mom only> Alternative 2 0/1=Off/On <Latched> Alternative 3 0/1=Off/On LD0.NSPTOC1 Negative-sequence overcurrent protection (1) Table 29: LD0.NSPTOC1 Negative-sequence overcurrent protection (1) LD0.NSPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate REF611

31 1MRS B Section LD0.NSPTOC2 Negative-sequence overcurrent protection (2) Table 30: LD0.NSPTOC2 Negative-sequence overcurrent protection (2) LD0.NSPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.PDNSPTOC1 Phase discontinuity protection (1) Table 31: LD0.PDNSPTOC1 Phase discontinuity protection (1) LD0.PDNSPTOC Str.general START Stage start 1=Start Op.general OPERATE Stage operate 1=Operate LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1) Table 32: LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1) LD0.PHHPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate REF611 25

32 Section 2 1MRS B LD0.PHHPTOC2 Three-phase non-directional overcurrent protection, high stage (2) Table 33: LD0.PHHPTOC2 Three-phase non-directional overcurrent protection, high stage (2) LD0.PHHPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate LD0.PHIPTOC1 Three-phase non-directional overcurrent protection, instantaneous stage (1) Table 34: LD0.PHIPTOC1 Three-phase non-directional overcurrent protection, instantaneous stage (1) LD0.PHIPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate REF611

33 1MRS B Section LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1) Table 35: LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1) LD0.PHLPTOC Str.general START General start 1=Start Str.phsA Phs A start 1=Start Str.phsB Phs B start 1=Start Str.phsC Phs C start 1=Start Op.general OPERATE General operate 1=Operate LD0.RESCMMXU1 Residual current measurement (1) Table 36: LD0.RESCMMXU1 Residual current measurement (1) LD0.RESCMMXU HiAlm.stVal HIGH_ALARM High alarm 1=Alarm HiWrn.stVal HIGH_WARN High warning 1=Warning LD0.RESVMMXU1 Residual voltage measurement (1) Table 37: LD0.RESVMMXU1 Residual voltage measurement (1) LD0.RESVMMXU HiAlm.stVal HIGH_ALARM High alarm 1=Alarm HiWrn.stVal HIGH_WARN High warning 1=Warning REF611 27

34 Section 2 1MRS B LD0.ROVPTOV1 Residual overvoltage protection (1) Table 38: LD0.ROVPTOV1 Residual overvoltage protection (1) LD0.ROVPTOV Str.general START General start 1=Start Op.general OPERATE General operate 1=Operate LD0.ROVPTOV2 Residual overvoltage protection (2) Table 39: LD0.ROVPTOV2 Residual overvoltage protection (2) LD0.ROVPTOV Str.general START General start 1=Start Op.general OPERATE General operate 1=Operate LD0.ROVPTOV3 Residual overvoltage protection (3) Table 40: LD0.ROVPTOV3 Residual overvoltage protection (3) LD0.ROVPTOV Str.general START General start 1=Start Op.general OPERATE General operate 1=Operate LD0.T1PTTR1 Three-phase thermal protection for feeders, cables and distribution transformers (1) Table 41: LD0.T1PTTR1 Three-phase thermal protection for feeders, cables and distribution transformers (1) LD0.T1PTTR Str.general START General start 1=Start AlmThm.general ALARM Thermal alarm 1=Alarm Table continues on next page 28 REF611

35 1MRS B Section Op.general OPERATE General operate 1=Operate LD0.TCSSCBR1 Trip circuit supervision (1) Table 42: LD0.TCSSCBR1 Trip circuit supervision (1) LD0.TCSSCBR CircAlm.stVal ALARM Supervision alarm 1=Alarm LD0.TCSSCBR2 Trip circuit supervision (2) Table 43: LD0.TCSSCBR2 Trip circuit supervision (2) LD0.TCSSCBR CircAlm.stVal ALARM Supervision alarm 1=Alarm LD0.TRPPTRC1 Master trip (1) Table 44: LD0.TRPPTRC1 Master trip (1) LD0.TRPPTRC Op.general - Op. input signal 1=Operate Tr.general - Trip output signal 1=Trip LD0.TRPPTRC2 Master trip (2) Table 45: LD0.TRPPTRC2 Master trip (2) LD0.TRPPTRC Op.general - Op. input signal 1=Operate Tr.general - Trip output signal 1=Trip REF611 29

36 Section 2 1MRS B LD0.VMMXU1 Three-phase voltage measurement (1) Table 46: LD0.VMMXU1 Three-phase voltage measurement (1) LD0.VMMXU HiAlm.stVal HIGH_ALARM High alarm 1=Alarm HiWrn.stVal HIGH_WARN High warning 1=Warning LoWrn.stVal LOW_WARN Low warning 1=Warning LoAlm.stVal LOW_ALARM Low alarm 1=Alarm LD0.XAGGIO130 Physical I/O states (AIM card XA130) Table 47: LD0.XAGGIO130 Physical I/O states (AIM card XA130) LD0.XAGGIO Ind1.stVal XA130-Input 1 State 0/1=Off/On mom-only Mom only alternative Ind2.stVal XA130-Input 2 State 0/1=Off/On mom-only Mom only alternative Ind3.stVal XA130-Input 3 State 0/1=Off/On mom-only Mom only alternative Ind4.stVal XA130-Input 4 State 0/1=Off/On mom-only Mom only alternative LD0.XGGIO100 Physical I/O states (PSM card X100) Table 48: LD0.XGGIO100 Physical I/O states (PSM card X100) LD0.XGGIO SPCSO1.stVal X100-Output 1 State 0/1=Off/On mom-only Mom only alternative Table continues on next page 30 REF611

37 1MRS B Section SPCSO2.stVal X100-Output 2 State 0/1=Off/On mom-only Mom only alternative SPCSO3.stVal X100-Output 3 State 0/1=Off/On SPCSO4.stVal X100-Output 4 State 0/1=Off/On SPCSO5.stVal X100-Output 5 State 0/1=Off/On mom-only Mom only alternative SPCSO6.stVal X100-Output 6 State 0/1=Off/On mom-only Mom only alternative LD0.XGGIO120 Physical I/O states (AIM card X120) Table 49: LD0.XGGIO120 Physical I/O states (AIM card X120) LD0.XGGIO Ind1.stVal X120-Input 1 State 0/1=Off/On mom-only Mom only alternative Ind2.stVal X120-Input 2 State 0/1=Off/On mom-only Mom only alternative Ind3.stVal X120-Input 3 State 0/1=Off/On mom-only Mom only alternative Ind4.stVal X120-Input 4 State 0/1=Off/On mom-only Mom only alternative LD0.XGGIO130 Physical I/O states (BIO card X130) Table 50: LD0.XGGIO130 Physical I/O states (BIO card X130) LD0.XGGIO Ind1.stVal X130-Input 1 State 0/1=Off/On Table continues on next page REF611 31

38 Section 2 1MRS B.mom-only Mom only alternative Ind2.stVal X130-Input 2 State 0/1=Off/On.mom-only Mom only alternative Ind3.stVal X130-Input 3 State 0/1=Off/On mom-only Mom only alternative Ind4.stVal X130-Input 4 State 0/1=Off/On mom-only Mom only alternative Ind5.stVal X130-Input 5 State 0/1=Off/On mom-only Mom only alternative Ind6.stVal X130-Input 6 State 0/1=Off/On mom-only Mom only alternative SPCSO1.stVal X130-Output 1 State 0/1=Off/On mom-only Mom only alternative SPCSO2.stVal X130-Output 2 State 0/1=Off/On mom-only Mom only alternative SPCSO3.stVal X130-Output 3 State 0/1=Off/On mom-only Mom only alternative Unmapped indications Unmapped indications are indication data that have no initial Modbus mapping locations, but can be added to the user-definable Modbus area using the Communication Management tool in PCM600. If Modbus events are enabled for these indication signals, the event identification is the user-definable area address. 32 REF611

39 1MRS B Section All premapped three-phase protection function stages, start and operate/phase-dependent objects added Table 51: All premapped three-phase protection function stages, start and operate/phase-dependent objects added LD0.xxxxxxxx (various).op.phsa Operate Phase A 1 = Operate.Str.phsA Start Phase A 1 = Start.Op.phsB Operate Phase B 1 = Operate.Str.phsB Start Phase B 1 = Start.Op.phsC Operate Phase C 1 = Operate.Str.phsC Start Phase C 1 = Start Common data 2 Table 52: Common data 2 Table continues on next page LD0.LDEV1.DevFail.stVal Internal fault 1=Fault.StLstOv.stVal Internal ind. overflow 1=Overflow.MeasLstOv.stVal Internal meas. overflow 1=Overflow.ChgFlg.stVal Configuration changed 1=Changed.FacSet.stVal Factory settings in use 1=In use LD0.GNRLLTMS1.TmChSt1.stVal Time synch. status 0/1=Down/Up.TmSyn.stVal IEC sync TmSrcSt.stVal Time sync source REF611 33

40 Section 2 1MRS B LD0.SCHLCCH1.ChLiv.stVal CH1LIV Ethernet channel 1 live 1=Live LD0.SCHLCCH2.ChLiv.stVal CH2LIV Ethernet channel 2 live 1=Live LD0.SCHLCCH3.ChLiv.stVal CH3LIV Ethernet channel 3 live 1=Live LD0.GSELPRT1.Alm.stVal GOOSE alarm 1=Alarm DR.RDRE1 Disturbance recorder signals Table 53: DR.RDRE1 Disturbance recorder signals DR.RDRE1.RcdStr.stVal Recording started 1=Started.RcdDltInd.stVal Recording deleted 1=Deleted.OvWrRcdInd.stVal Overwrite of record 1=Overwrite.PerTrgInd.stVal Periodic triggering 1=Triggered.ManTrgInd.stVal Manual triggering 1=Triggered LD0.CBPSOF1 Switch onto fault (1) Table 54: LD0.CBPSOF1 Switch onto fault (1) LD0.CBPSOF1.Op.general OPERATE Stage operate 1=Operate 34 REF611

41 1MRS B Section LD0.IL1TCTR1 Three-phase CT supervision (1) Table 55: LD0.IL1TCTR1 Three-phase CT supervision (1) LD0.IL1TCTR1.Alm.stVal ALARM Alarm 1=Alarm.Wrn.stVal WARNING Warning 1=Warning LD0.RCHLCCH1 Ethernet supervision (1) Table 56: LD0.RCHLCCH1 Ethernet supervision (1) LD0.RCHLCCH1.ChLiv.stVal CHLIV Ethernet channel live 1=Live.RedChLiv.stVal REDCHLIV Red. Ethernet channel live 1=Live LD0.RESTCTR1 Io CT supervision (1) Table 57: LD0.RESTCTR1 Io CT supervision (1) LD0.RESTCTR1.Alm.stVal ALARM Alarm 1=Alarm.Wrn.stVal WARNING Warning 1=Warning LD0.RESTVTR1 Uo VT supervision (1) Table 58: LD0.RESTVTR1 Uo VT supervision (1) LD0.RESTVTR1.Alm.stVal ALARM Alarm 1=Alarm.Wrn.stVal WARNING Warning 1=Warning REF611 35

42 Section 2 1MRS B LD0.UL1TVTR1 Three-phase VT supervision (1) Table 59: LD0.UL1TVTR1 Three-phase VT supervision (1) LD0.UL1TVTR1.Alm.stVal ALARM Alarm 1=Alarm.Wrn.stVal WARNING Warning 1=Warning 2.4 Registers Table 60: Column name RegA Type Scale IEC name SA name Description Values Explanations of columns in register tables Description Default 3X and 4X register address for the data. Type of the register. The alternatives are u16, u32 (unsigned 16 and 32 bits integer) or i16, i32 (signed 16 and 32 bit integer). Scale factor as default. Also, an adjustable offset value exists that is set to 0 by default. Original IED data object identification. Described in the IEC format as Logical Device.Logical Node and thereafter.data Object.Data Attribute. Logical Node is the same as the application function block name. The signal may have a defined label that is visible, for example, in the Application Configuration tool in PCM600. Short description of the signal. See the technical manual for more information. Also, if a register is writable, it is stated here. The value range of the original IEC value, that is, before scaling Premapped registers Active parameter setting group read and write Table 61: Active parameter setting group - read and write LD0.LLN u16 1 ActSetGr.Oper.ctlVal Active setting group REF611

43 1MRS B Section Control structure 1 Table 62: Control structure Execute register Password reg 1 acc to setting 8003 Password reg 2 acc to setting 8004 Control register < single bit > 8005 Confirm register < single bit > Control structure 2 Table 63: Control structure Execute register Password reg 1 acc to setting 8008 Password reg 2 acc to setting 8009 Control register < single bit > 8010 Confirm register < single bit > Control structure 3 Table 64: Control structure Execute register Password reg 1 acc to setting 8013 Password reg 2 acc to setting 8014 Control register < single bit > 8015 Confirm register < single bit > Control structure 4 Table 65: Control structure Execute register Password reg 1 acc to setting 8018 Password reg 2 acc to setting 8019 Control register < single bit > 8020 Confirm register < single bit > REF611 37

44 Section 2 1MRS B Control structure 5 Table 66: Control structure Execute register Password reg 1 acc to setting 8023 Password reg 2 acc to setting 8024 Control register < single bit > 8025 Confirm register < single bit > Control structure 6 Table 67: Control structure Execute register Password reg 1 acc to setting 8028 Password reg 2 acc to setting 8029 Control register < single bit > 8030 Confirm register < single bit > Control structure 7 Table 68: Control structure Execute register Password reg 1 acc to setting 8033 Password reg 2 acc to setting 8034 Control register < single bit > 8035 Confirm register < single bit > Control structure 8 Table 69: Control structure Execute register Password reg 1 acc to setting 8038 Password reg 2 acc to setting 8039 Control register < single bit > 8040 Confirm register < single bit > 38 REF611

45 1MRS B Section Device ID string Table 70: Device ID string 9000 u16 ASCII coded string 1) u16 1) See the technical manual Event record structure Table 71: Event record structure Selection write: 9250 u Num of multiple records i Read selection Record 1 data to read: 9252 u Record sequence num u Unread records left Timestamp of record 9254 u Year, Month Year/Month 9255 u Day, Hour Day/Hour 9256 u Minute, Second Min/Sec 9257 u Millisecond Millisecond 9258 u16 1 Event identification 1) 9259 u16 1 Data object ID u16 1 Data object ID u16 1 Event data value u16 1 Event data value 2 Record 2 data to read: If selected 9263 u Record sequence num u Unread records left Timestamp of record 9265 u Year, Month Year/Month 9266 u Day, Hour Day/Hour 9267 u Minute, Second Min/Sec 9268 u Millisecond Millisecond 9269 u16 1 Event identification Table continues on next page REF611 39

46 Section 2 1MRS B 9270 u16 1 Data object ID u16 1 Data object ID u16 1 Event data value u16 1 Event data value 2 Record 3 data to read: If selected 9274 u Record sequence num u Unread records left Timestamp of record 9276 u Year, Month Year/Month 9277 u Day, Hour Day/Hour 9278 u Minute, Second Min/Sec 9279 u Millisecond Millisecond 9280 u16 1 Event identification 9281 u16 1 Data object ID u16 1 Data object ID u16 1 Event data value u16 1 Event data value 2 Record 4 data to read: If selected 9285 u Record sequence num u Unread records left Timestamp of record 9287 u Year, Month Year/Month 9288 u Day, Hour Day/Hour 9289 u Minute, Second Min/Sec 9290 u Millisecond Millisecond 9291 u16 1 Event identification 9292 u16 1 Data object ID u16 1 Data object ID u16 1 Event data value u16 1 Event data value 2 Record 5 data to read: If selected 9296 u Record sequence num u Unread records left Timestamp of record 9298 u Year, Month Year/Month 9299 u Day, Hour Day/Hour Table continues on next page 40 REF611

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual Relion 615 series Feeder Protection and Control REF615 Modbus Document ID: 1MRS756581 Issued: 2016-05-20 Revision: K Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved Copyright This document

More information

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual Relion 615 series Feeder Protection and Control REF615 Modbus Document ID: 1MRS756581 Issued: 03.07.2009 Revision: C Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

Operation Manual Feeder Protection Relay REF615

Operation Manual Feeder Protection Relay REF615 Feeder Protection Relay REF615 Document ID: 1MRS756376 Issued: 02.07.2008 Revision: C Product version: 1.1 Copyright 2008 - ABB. All rights reserved Copyright This document and parts thereof must not

More information

Relion 615 series. Feeder protection and control REF615

Relion 615 series. Feeder protection and control REF615 Relion 65 series Feeder protection and control REF65 Compact and versatile solution for utility and industrial power distribution systems REF65 is a dedicated feeder IED perfectly aligned for the protection,

More information

Relion Protection and Control. 615 series ANSI Modbus Communication Protocol Manual

Relion Protection and Control. 615 series ANSI Modbus Communication Protocol Manual Relion Protection and Control 615 series ANSI Modbus Document ID: 1MAC052634-MB Issued: 01/20/2010 Revision: C Product version: 2.0 Copyright 2010 ABB. All rights reserved Copyright This document and

More information

Feeder Protection REF615. Product Guide

Feeder Protection REF615. Product Guide Product Guide Contents 1 Description.............................. 3 2 Standard configurations................. 3-4 3 Protection functions.................... 4-5 4 Application...........................

More information

Relion Protection and Control. 615 series IEC Communication Protocol Manual

Relion Protection and Control. 615 series IEC Communication Protocol Manual Relion Protection and Control 615 series IEC 60870-5-103 Communication Protocol Manual Document ID: 1MRS756710 Issued: 2016-05-20 Revision: G Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved

More information

Relion 615 series. Line Differential Protection and Control RED615 Product Guide

Relion 615 series. Line Differential Protection and Control RED615 Product Guide Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...12 4. Application... 12 5. Supported ABB

More information

COM600 series, Version 5.0 Modbus Serial Slave (OPC) User's Manual

COM600 series, Version 5.0 Modbus Serial Slave (OPC) User's Manual CO600 series, Version 5.0 odbus Serial Slave (OPC) User's anual 1RS756913 Issued: 9.10.2009 Version: E/24.5.2017 CO600 series, Version 5.0 odbus Serial Slave (OPC) User's anual Contents: 1. About this

More information

Relion 615 Series. Motor Protection and Control REM615 ANSI DNP3 Point List Manual

Relion 615 Series. Motor Protection and Control REM615 ANSI DNP3 Point List Manual Relion 615 Series Motor Protection and Control REM615 ANSI 3 List Manual Document ID: 1MAC254287-MB Issued: 4/14/2011 Revision: B Product version: 4.0 Copyright 2011 ABB. All rights reserved. Copyright

More information

Relion product family. Remote monitoring and control REC615 Protection of cable feeders with superior fault detection and location

Relion product family. Remote monitoring and control REC615 Protection of cable feeders with superior fault detection and location elion product family emote monitoring and control EC615 Protection of cable feeders with superior fault detection and location U12 0. 0 kv P 0.00 kw Q 0.00 kvar I2 0 A ESC A 1 15 AN DC IN CONSOE/S1 S2

More information

Relion 615 series. Transformer Protection and Control RET615 Product Guide

Relion 615 series. Transformer Protection and Control RET615 Product Guide Relion 615 series Transformer Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...14 4. Application... 15 5. Supported ABB solutions...

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Relion 611 series. Busbar and Multipurpose Differential Protection and Control REB611 Product Guide

Relion 611 series. Busbar and Multipurpose Differential Protection and Control REB611 Product Guide Relion 611 series Busbar and Multipurpose Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configuration...3 3. Protection functions...5 4. Application...5 5. Supported

More information

Substation Automation Products. Distributed busbar protection REB500 Communication Protocol Manual, IEC 61850

Substation Automation Products. Distributed busbar protection REB500 Communication Protocol Manual, IEC 61850 Substation Automation Products Communication Protocol Manual, IEC 61850 Document ID: 1MRK 511 342-UEN Issued: May 2015 Revision: - Product version: 8.10 Copyright 2015 ABB. All rights reserved Copyright

More information

COM600 Station Automation Series MNS is Connectivity (OPC) 3.2. User's Guide

COM600 Station Automation Series MNS is Connectivity (OPC) 3.2. User's Guide MNS is Connectivity 3.2 User's Guide 1MRS756569 Issued: 17.06.2008 Version: A/17.06.2008 User's Guide MNS is Connectivity 3.2 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks...

More information

Relion 620 series. Feeder protection and control REF620 Flexibility for utility and industrial power distribution systems

Relion 620 series. Feeder protection and control REF620 Flexibility for utility and industrial power distribution systems Relion 60 series Feeder protection and control REF60 Flexibility for utility and industrial power distribution systems Compact protection and control for a wide variety of feeder applications REF60 is

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

COM600 series 5.0 Operator's Manual

COM600 series 5.0 Operator's Manual COM600 series 5.0 1MRS756705 Issued: 13.2.2009 Version: F/24.5.2017 COM600 series 5.0 Contents: 1. About this manual... 5 1.1. Copyright... 5 1.2. Disclaimer... 5 1.3. Conformity... 6 1.4. Trademarks...

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756170 Issued: 02.03.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...15 1. Introduction...17 1.1. This Manual...17 1.2. Use of symbols...17 1.3.

More information

System 800xA Public Address System User Manual

System 800xA Public Address System User Manual System 800xA Public Address System User Manual System Version 6.0 Power and productivity for a better world System 800xA Public Address System User Manual System Version 6.0 NOTICE This document contains

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

Document ID: 1VCD Product Name: MyRemoteCare Gateway Document Name: Operation Manual Issued: Revision: R0001 Product Version: 1.

Document ID: 1VCD Product Name: MyRemoteCare Gateway Document Name: Operation Manual Issued: Revision: R0001 Product Version: 1. Document ID: 1VCD601158 Product Name: Document Name: Operation Manual Issued: 2012-06-15 Revision: R0001 Product Version: 1.0 Copyright 2012 ABB. All rights reserved Copyright This document and parts thereof

More information

Protection System Simulator SIM600. Installation Manual

Protection System Simulator SIM600. Installation Manual Protection System Simulator SIM600 1MRS756102 Issued: 08.12.2008 Version: B Protection System Simulator SIM600 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. Guarantee...

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

DIN Rail RTU 540CMD01 Data sheet

DIN Rail RTU 540CMD01 Data sheet RTU540 product line DIN Rail RTU 540CMD01 Data sheet 4 3 RS232C RS232C RS232C or RS485 or RS485 or RS485 1 2 E1 E2 10/100 MB LAN Protocol Protocol Controller Controller MPU Cortex-A8 AM3352 Application

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

Device Management Basic HART DTM 6.0 Installation

Device Management Basic HART DTM 6.0 Installation Device Management Basic HART DTM 6.0 Installation System Version 6.0 Power and productivity for a better world TM Device Management Basic HART DTM 6.0 Installation System Version 6.0 NOTICE This document

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

MicroSCADA Pro SYS Operation Manual

MicroSCADA Pro SYS Operation Manual MicroSCADA Pro SYS 600 9.2 1MRS756118 Issued: 28.02.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...7 1. Introduction...9 1.1. This manual...9 1.2. Use of symbols...9 1.3.

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays PROTECTION MiCOM P12x/y Three phase and earth fault overcurrent relays The MiCOM P12x/y relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault

More information

MiCOM P12x/y. Three phase and earth fault overcurrent relays

MiCOM P12x/y. Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

System 800xA Engineering

System 800xA Engineering System 800xA Engineering Engineering and Production Environments System Versions 6.0 Power and productivity for a better world TM System 800xA Engineering Engineering and Production Environments System

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Protection and Control IED Manager PCM600 Product Guide

Protection and Control IED Manager PCM600 Product Guide Product Guide Contents 1. Description...3 2. Project explorer...4 3. Parameter setting...4 4. Graphical application configuration...4 5. Signal matrix...5 6. Graphical display editor...5 7. Hardware configuration...6

More information

Three phase and earth fault overcurrent relays

Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

Power Products. Protection and Control IED Manager PCM600 Product Guide

Power Products. Protection and Control IED Manager PCM600 Product Guide Power Products Protection and Control IED Manager Product Guide Contents 1. Description............................ 3 2. Tool variants........................... 3 3. Connectivity packages...................

More information

Preface. Contents SIPROTEC. Basics 1. Mapping 2. Multifuction Protection. Literature & Index. 7SJ66 IEC61850 Mapping C53000-L2640-C554-1

Preface. Contents SIPROTEC. Basics 1. Mapping 2. Multifuction Protection. Literature & Index. 7SJ66 IEC61850 Mapping C53000-L2640-C554-1 Preface SIPROTEC Multifuction Protection 7SJ66 IEC61850 Mapping Contents Basics 1 Mapping 2 Literature & Index C53000-L2640-C554-1 Disclaimer of Liability We have checked the text of this manual against

More information

Station Automation COM Logic Processor User's Manual

Station Automation COM Logic Processor User's Manual Station Automation COM600 3.4 1MRS756738 Issued: 13.2.2009 Version: B/06.11.2009 Station Automation COM600 3.4 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. General...

More information

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL Circuit Breaker Failure Relay Operating Principle Revision: 2 from 2005-02-25 Edition: 2005-02-25 _CBF-description_eng.doc Page 1 /14 Table of Contents: 1 GENERAL DESCRIPTION 4 2 FUNCTIONAL DESCRIPTION

More information

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4 Content FPC 400 USER MANUAL Apr 2017 Feeder F3 Motor M4 Busbar B3 Transformer T4 1 USER MANUAL FPC 400-4/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia 2016. All rights reserved.

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

MicroSCADA Pro DMS Operation Manual

MicroSCADA Pro DMS Operation Manual DMS 600 4.2 1MRS755274 Issued: 30.6.2004 Version: E/28.3.2008 DMS 600 4.2 Contents: 1. About this manual... 11 1.1. Copyrights... 11 1.2. Trademarks... 11 1.3. General... 11 1.4. Use of symbols... 12

More information

Using GOOSE with SPA-ZC 400 Ethernet Adapter and RE_541/3/5 Terminals

Using GOOSE with SPA-ZC 400 Ethernet Adapter and RE_541/3/5 Terminals Using GOOSE with SPA-ZC 400 Ethernet SPA-ZC 400, RE_541/3/5 Application Note 1MRS756310 Issued: 26.02.2007 Version: B/10.04.2009 Using GOOSE with SPA-ZC 400 Ethernet Application Note Contents 1. Introduction...5

More information

Relion Protection and Control. 670 series 2.1 IEC Operation manual

Relion Protection and Control. 670 series 2.1 IEC Operation manual Relion Protection and Control 670 series 2.1 IEC Document ID: 1MRK 500 123-UEN Issued: December 2015 Revision: - Product version: 2.1 Copyright 2015 ABB. All rights reserved Copyright This document and

More information

MRA4 Profibus DP HighPROTEC. Data point list. Manual DOK-TD-MRA4PDE

MRA4 Profibus DP HighPROTEC. Data point list. Manual DOK-TD-MRA4PDE MRA4 DP HighPROTEC Data point list Manual DOK-TD-MRA4PDE Table of Contents Table of Contents TABLE OF CONTENTS... 2 PROFIBUS... 3 Configuration... 3 DATA POINT LISTS... 4 Signals... 4 Measuring values...

More information

Motor Control and Protection Unit M10x AO Module User Guide

Motor Control and Protection Unit M10x AO Module User Guide Motor Control and Protection Unit M10x AO Module User Guide The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility

More information

MicroSCADA Pro DMS 600 *4.0. Operation Manual

MicroSCADA Pro DMS 600 *4.0. Operation Manual MicroSCADA Pro DMS 600 *4.0 1MRS755274 MicroSCADA Pro DMS 600 *4.0 Issued: 30.6.2004 Version: A/30.6.2004 Contents: 1. About this manual... 11 1.1. Copyrights...11 1.2. Trademarks...11 1.3. General...11

More information

System 800xA. Engineering and Production Environments. Power and productivity for a better world TM. System Version 5.1

System 800xA. Engineering and Production Environments. Power and productivity for a better world TM. System Version 5.1 System 800xA Engineering and Production Environments System Version 5.1 Power and productivity for a better world TM System 800xA System Version 5.1 NOTICE This document contains information about one

More information

Engineering Manual Security Lock

Engineering Manual Security Lock DigiVis 500 Engineering Manual Security Lock Version 1.0 SP1 DigiVis 500 Engineering Manual Security Lock Version 1.0 SP1 NOTICE The information in this document is subject to change without notice and

More information

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation MiCOM P123R Overcurrent Relays Upgrade Documentation MiCOM P123R Page 1/14 CONTENTS MiCOM P123R ADDENDUM: MiCOM P12X UPDATE DOCUMENTATION 3 P12X/EN IT/EB6: INTRODUCTION 4 P12x/EN TD/Eb6: TECHNICAL DATA

More information

VideONet Connect for 800xA User Manual

VideONet Connect for 800xA User Manual VideONet Connect for 800xA User Manual System Version 6.0 Power and productivity for a better world VideONet Connect for 800xA User Manual System Version 6.0 NOTICE This document contains information

More information

LIB 510 MV Process Operator s Manual

LIB 510 MV Process Operator s Manual 1MRS751388-MUM Issue date: 31.01.2000 Program revision: 4.0.3 Documentation version: A LIB 510 Copyright 2000 ABB Substation Automation Oy All rights reserved. Notice 1 The information in this document

More information

Relion 615 series. Feeder protection and control REF615 ANSI Product guide

Relion 615 series. Feeder protection and control REF615 ANSI Product guide Relion 615 series Feeder protection and control Product guide Contents 1 Description............................. 3 2 Standard configurations................ 4-5 3 Protection functions...................

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations 2008 Many Changes in IEEE C37.2 IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations Major revisions first since 1995 Substantial additions 1 - New ten more

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...8 4. Application...16 5. Supported ABB solutions...22

More information

Substation automation products. MicroSCADA Pro for substation automation

Substation automation products. MicroSCADA Pro for substation automation Substation automation products for substation automation Perfect control anywhere, anytime is an investment for today and tomorrow. Start, for instance, with monitoring or gateway functionality and integrate

More information

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment TR No. 176002 1.1.EDITION April 1st, 2015 Nippon Telegraph and Telephone Corporation Introduction This document describes

More information

PRODUCT GUIDE. RER620 Advanced recloser protection & control

PRODUCT GUIDE. RER620 Advanced recloser protection & control PRODUCT GUIDE RER620 Advanced recloser protection & control 2 RER620 ADVANCED RECLOSER PROTECTION & CONTROL Table of contents 003 004 1. Description 004 006 2. Standard configurations 006 007 3. Protection

More information

Protective Relays & SCADA Systems

Protective Relays & SCADA Systems 14 SWITCHGEAR Protective Relays & SCADA Systems SCADA Substation Automation SICAM PAS & PQ Analyzer SICAM PAS (Power Automation System) is a complete substation automation control and protection system

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

Installation and commissioning manual Waveguide Access Point WGA631

Installation and commissioning manual Waveguide Access Point WGA631 Waveguide Access Point WGA631 Document ID: 1MRS755551 Issued: 23.06.2009 Revision: B Product version: 1.1 Copyright 2009 ABB. All rights reserved Copyright This document and parts thereof must not be

More information

800xA History. Installation. Power and productivity for a better world TM. System Version 6.0

800xA History. Installation. Power and productivity for a better world TM. System Version 6.0 800xA History Installation System Version 6.0 Power and productivity for a better world TM 800xA History Installation System Version 6.0 NOTICE This document contains information about one or more ABB

More information

Relion Protection and Control. 630 series Engineering Manual

Relion Protection and Control. 630 series Engineering Manual Relion Protection and Control 630 series Document ID: 1MRS756800 Issued: 2014-11-28 Revision: E Product version: 1.3 Copyright 2014 ABB. All rights reserved Copyright This document and parts thereof must

More information

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied:

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied: 1) IED Protection and Control Manager PCM 600 Tool (SEP-601) PCM 600 Introduction and Overview Application Configuration Tool (CAP 531) Signal Matrix Tool, SMT Graphical Display Editor, GDE Parameter Setting

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

COM600 series 5.0 Cyber Security Deployment Guideline

COM600 series 5.0 Cyber Security Deployment Guideline COM600 series 5.0 1MRS758267 Issued: 13.3.2015 Version: A/24.5.2017 COM600 series 5.0 Contents: 1. About this manual... 5 1.1. Copyright... 5 1.2. Disclaimer... 5 1.3. Conformity... 6 1.4. Trademarks...

More information

Section 4 Ground-Fault Protection Devices

Section 4 Ground-Fault Protection Devices Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that

More information

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management Reyrolle Protection Devices 7SR11 & 7SR12 Argus Overcurrent Relay Energy Management 7SR11 & 7SR12 Argus Contents Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration

More information

Utilization of IEC GOOSE messaging in protection applications in distribution network

Utilization of IEC GOOSE messaging in protection applications in distribution network 9AKK106930A2259 Utilization of IEC 61850 GOOSE messaging in protection applications in distribution network Yogesh Bhamare Head-Product Management, Distribution Automation, ABB Limited, Vadodara, India

More information

System 800xA Maintenance

System 800xA Maintenance System 800xA Maintenance System Version 6.0 Power and productivity for a better world System 800xA Maintenance System Version 6.0 NOTICE This document contains information about one or more ABB products

More information

S800 I/O DTM 6.0. System Version 6.0. Power and productivity for a better world

S800 I/O DTM 6.0. System Version 6.0. Power and productivity for a better world S800 I/O DTM 6.0 System Version 6.0 Power and productivity for a better world S800 I/O DTM 6.0 NOTICE This document contains information about one or more ABB products and may include a description of

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

System 800xA Spanish Language Package Release Notes System Version 6.0

System 800xA Spanish Language Package Release Notes System Version 6.0 System 800xA Spanish Language Package Release Notes System Version 6.0 Power and productivity for a better world TM System 800xA Spanish Language Package Release Notes System Version 6.0 NOTICE This document

More information

FIBARO SINGLE SWITCH

FIBARO SINGLE SWITCH OPERATING MANUAL EN FIBARO SINGLE SWITCH FGBHS-213 CONTENTS #1: Description and features 3 #2: Supported loads 4 #3: Installation 5 #4: Pairing the accessory 7 #5: Reset 8 v1.1 #6: Functionality 9 #7:

More information

Grid Automation Products. MicroSCADA Pro Substation automation applications.

Grid Automation Products. MicroSCADA Pro Substation automation applications. Grid Automation Products Substation automation applications. 2 Substation automation applications Automate, control and optimize your operations. is an investment for today and tomorrow. Start, for instance,

More information

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity

More information

DRTS 66 can test all the following relays

DRTS 66 can test all the following relays Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual control with color display Simultaneously available: 6 Current and 6 Voltage plus 1 battery simulator outputs

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

V E2B Snap-in I/O Module

V E2B Snap-in I/O Module i4 Automation Ltd - 01480 395256 V200-18-E2B Snap-in I/O Module The V200-18-E2B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration.

More information

System 800xA Engineering Engineering Studio Function Designer Getting Started

System 800xA Engineering Engineering Studio Function Designer Getting Started System 800xA Engineering Engineering Studio Function Designer Getting Started System Version 6.0 Power and productivity for a better world System 800xA Engineering Engineering Studio Function Designer

More information

RER 123 Bus Connection Module. Technical Description

RER 123 Bus Connection Module. Technical Description Bus Connection 1MRS751143-MUM Issued: 06.11.1998 Version: E/08.07.2005 Bus Connection 1. About this manual...4 1.1. Copyrights...4 1.2. Trademarks...4 1.3. Guarantee...4 2. Safety information...5 3. General...6

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

2 ms arc-flash protection and feeder relay in one platform

2 ms arc-flash protection and feeder relay in one platform Feeder Protection Relay 2 ms arc-flash protection and feeder relay in one platform Combine light sensor inputs with high-speed overcurrent protection to achieve secure arc-flash protection in as fast as

More information

System 800xA Device Management FOUNDATION Fieldbus Configuration

System 800xA Device Management FOUNDATION Fieldbus Configuration System 800xA Device Management FOUNDATION Fieldbus Configuration System Version 6.0 Power and productivity for a better world System 800xA Device Management FOUNDATION Fieldbus Configuration System Version

More information

Manual Version: V1.00. Video Decoder User Manual

Manual Version: V1.00. Video Decoder User Manual Manual Version: V1.00 Video Decoder User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. Copyright Copyright 2016 Zhejiang

More information

MiCOM P50 Agile P15D. Technical Manual. Dual Powered overcurrent relay

MiCOM P50 Agile P15D. Technical Manual. Dual Powered overcurrent relay MiCOM P50 Agile P15D Technical Manual Dual Powered overcurrent relay Platform Hardware Version: A Platform Software Version: 01 Publication Reference: P15D/EN M/C - ALSTOM 2015. All rights reserved. Information

More information

Medium Voltage Service Course Description Training Course CZ045 Operation and maintenance of UniGear ZS1 with VD4 and REF 620

Medium Voltage Service Course Description Training Course CZ045 Operation and maintenance of UniGear ZS1 with VD4 and REF 620 Medium Voltage Service Course Description Training Course CZ045 Operation and maintenance of UniGear ZS1 with VD4 and REF 620 Course Modules Course ID Course Venue Brno,Czech Republic Course Duration CZ045

More information

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015 Configuration and Interoperability Guide for IEC 60870-5-103 for the SEL-751 Feeder Protection Relay July 10, 2015 Contents 1 Interoperability... 3 1.1 Physical Layer... 3 Electrical Interface... 3 Optical

More information

IEC INTEROPERABILITY BETWEEN RECORDERS AND RELAYS. R. Midence* Hugo Davila* Nan Zhan* * ERLPhase Power Technologies, Winnipeg, MB, Canada

IEC INTEROPERABILITY BETWEEN RECORDERS AND RELAYS. R. Midence* Hugo Davila* Nan Zhan* * ERLPhase Power Technologies, Winnipeg, MB, Canada IEC 61850 INTEROPERABILITY BETWEEN RECORDERS AND RELAYS R. Midence* Hugo Davila* Nan Zhan* * ERLPhase Power Technologies, Winnipeg, MB, Canada ABSTRACT Today the use of digital IEDs for fault recording,

More information

ABB Inc. Instructions REF 550 Advanced Feeder Protection System

ABB Inc. Instructions REF 550 Advanced Feeder Protection System ABB Inc Instructions REF 550 Advanced Feeder Protection System Instruction Booklet 71117-50 Issue A1 March 2005 Revision Note: 01/28/05: Issue A0 release 03/25/05: Issue A1 release Product description

More information

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL DRS-LIGHT Digital Unit Decoupling Relay Type DRS-LP824 Device Description Edition:09.05.2008 SLLR_LP824_e.doc Page 1 /10 CAUTION Installing, commissioning and operating of this product may be performed

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756117 Issued: 02.03.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...7 1. Introduction...9 1.1. This manual...9 1.2. Use of symbols...10 1.3.

More information

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Reyrolle Protection Devices 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Siemens Protection Devices Limited 2 7SR10 Argus Contents Contents Technical Manual Chapters 1. Description of Operation

More information

Manual 09/11 MN Z-EN. NZM-XATS-C Automatic Transfer Switch-Controller Modbus Communication Protocol

Manual 09/11 MN Z-EN. NZM-XATS-C Automatic Transfer Switch-Controller Modbus Communication Protocol Manual 09/11 MN01219007Z-EN NZM-XATS-C Automatic Transfer Switch-Controller Modbus Communication Protocol All brand and product names are trademarks or registered trademarks of the owner concerned. Emergency

More information

MicroSCADA Pro Substation automation applications.

MicroSCADA Pro Substation automation applications. G R I D AUTO M ATI O N PRO D U C T S Substation automation applications. ABB Oy Finland Power Grids Grid Automation P.O. Box 614 FI-65101 Vaasa, Finland Phone: +358 10 22 21999 (Customer Support Center)

More information

MiCOM P14x. Feeder Management Relays. Protection Relays

MiCOM P14x. Feeder Management Relays. Protection Relays 01 Feeder Management Relays feeder management relays provide an integrated solution for the complete protection, control and monitoring of overhead lines and underground cables from distribution to transmission

More information