Circuit Breakers,Reclosers, Switches, and Fuses

Size: px
Start display at page:

Download "Circuit Breakers,Reclosers, Switches, and Fuses"

Transcription

1 Section 17 Circuit Breakers,Reclosers, Switches, and Fuses 170. ARRANGEMENT This rule requires circuit breakers, reclosers, switches, and fuses be accessible only to qualified persons. Section 17 is part of Part 1, Electric Supply Stations ; therefore, the rules of this section apply only to circuit breakers, reclosers, switches, and fuses located in the electric supply substation. Circuit breakers, reclosers, switches, and fuses in the electric supply station are accessible only to qualified persons when Rule 110A is met. To protect persons from energized parts or arcing, this rule requires the following: Walls Barriers Latched doors Location Isolation Other means The requirements of Rule 124, guarding of live parts, also applies. Conspicuous and unique markings must be provided at the switching device or at any remote operating points to identify the equipment (e.g., circuit breaker, recloser, switch) that is being controlled. When the switch contacts are not normally visible (e.g., under oil, contained in a vacuum bottle, etc.), the switching device must be equipped with an operating 101

2 102 ELECTRIC SUPPLY STATIONS Rule 171 position indicator. The work rules in Part 4 provide switching control procedures and rules for de-energizing equipment or lines to protect employees. An example of a switch position indicator is shown in Fig APPLICATION The following ratings must be considered when applying a circuit breaker, circuit switcher, recloser, switch, or fuse: Voltage Continuous current See Photo Fig Example of a switch position indicator (Rule 170-1).

3 Rule 172 CIRCUIT BREAKERS, RECLOSERS, SWITCHES, AND FUSES 103 Momentary current Short-circuit current interrupt rating If the device is used to interrupt fault current, the maximum short-circuit current interrupt rating must be considered. When to apply ratings for momentary currents and interrupt currents is dependent on how the switch is used. If a switch is used as a disconnect only (i.e., it does not open under a fault condition), then it must be able to withstand a fault current flowing through it but it does not need to be rated to interrupt the fault current. The fault current it must withstand is termed the momentary fault current rating. If a switch is used to interrupt a fault, it must be rated to withstand the momentary fault current and interrupt the fault current without damage to the switch itself. A device that interrupts fault current must have a fault current interrupt rating. The interrupting capacity should be reviewed prior to each significant system change. For example, if a substation recloser is rated to interrupt 1250 A of short-circuit current and the substation transformer is replaced, the available fault current may increase to a value larger than 1250 A, which could cause damage to the recloser and personnel when the recloser operates to interrupt a fault. An example is given in Fig CIRCUIT BREAKERS, RECLOSERS, AND SWITCHES CONTAINING OIL Circuit breakers, reclosers, and switches containing oil receive special attention due to the flammability of the oil. Similar requirements are outlined in Rule 152 for oil-filled power transformers and regulators. Fig Example of checking interrupting capacity prior to a significant system change (Rule 171).

4 104 ELECTRIC SUPPLY STATIONS Rule 173 Segregation of oil-filled circuit-interrupting devices is required in the electric supply station. Segregation of oil-filled equipment minimizes fire damage to adjacent equipment or buildings. Segregation can be provided by the following methods: Spacing Fire-resistant barrier walls Metal cubicles Gas release vents are required, and means to control oil discharges from vents or tank rupture are required. Methods to contain oil are outlined below: Absorption beds Pits Drains Combination of the above This list is slightly different from the requirements for oil-filled transformers and regulators in Rule 152 but the general intent is the same. IEEE Standard 979, IEEE Guide for Substation Fire Protection, is an excellent reference for fire protection requirements. Buildings or rooms housing circuit breakers, reclosers, and switches containing flammable oil must be of fire-resistant construction. Not all circuit breakers, reclosers, and switches contain oil. Some are air break, some are vacuum break, and some are SF 6 gas insulated. This rule applies only to circuit breakers, reclosers, and switches that contain oil and are located inside the substation fence SWITCHES AND DISCONNECTING DEVICES Switches and disconnecting devices must have capacity for the following system ratings: Voltage Current Load break current (if required) Switches can be used to break load currents or open under no-load conditions. If required to break load current, the load current they are rated to interrupt must be marked on the switch. This value should not be confused with the short-circuit (fault) current-interrupt rating discussed in Rule 171. Switches and disconnectors must be able to be locked open and locked closed, or plainly tagged where locks are not practical. Part 4 of the NESC specifies the work rules applicable to operating, locking, and tagging switches. Switches that are operated remotely and automatically must have a disconnecting means for the control circuit near the disconnecting apparatus to limit the likelihood of accidental operation of the switch. Rule 173C has been deleted by the Tentative Interim Amendment (TIA) located at the end of the NESC.

5 Rule 174 CIRCUIT BREAKERS, RECLOSERS, SWITCHES, AND FUSES DISCONNECTION OF FUSES Disconnecting an energized fuse can be dangerous at any voltage. This rule requires fuses in circuits of more than 150 V to ground or more than 60 A (at any voltage) to be classified as disconnecting, or arranged to be disconnected from the source of power, or removed with insulating handles. In most cases, fused cutout-type switches are configured such that the switchblade or fuse is dead when the switch is in the open position. Loop feeds can create energized blades when the switch is in the open position. The NESC does not have a requirement for how the switch blades or fuses are energized but does require the proper handling of the fuse. Proper consideration must be given to clearance requirements when fuse and switch blades are in the open position.

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08 DNB Power and Control System Information and Interim Safety Procedures Version draft 5/06/08 DNB Power and Control System Information There are four sources of power for the DNB in the power supply and

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Air-insulated medium-voltage secondary distribution switchgear

Air-insulated medium-voltage secondary distribution switchgear DISTRIBUTION SOLUTIONS Air-insulated medium-voltage secondary distribution switchgear Compact size Complete solution Factory tested Air-insulated medium-voltage secondary distribution switchgear The ABB

More information

Purpose of High Voltage Circuit Switchers

Purpose of High Voltage Circuit Switchers Purpose of High Voltage Circuit Switchers Vertical interrupter circuit switcher without integral disconnect switch (Figure 2) Three-phase Interruption and Protection Circuit switchers have been developed

More information

TRENDS IN SWITCHGEAR SPECIFICATIONS

TRENDS IN SWITCHGEAR SPECIFICATIONS TRENDS IN SWITCHGEAR SPECIFICATIONS What changes are we seeing in equipment specifications? What s being discussed in client meetings? What s happening in the market to support these requests? EQUIPMENT

More information

ELECTRICAL CONTROL SYSTEM COMPONENTS

ELECTRICAL CONTROL SYSTEM COMPONENTS Module - 2 ELECTRICAL CONTROL SYSTEM COMPONENTS Lecture - 1 MECHANICAL SWITCHES Shameer A Koya EEET 221 : Electrical Control Systems. Module 2 - Objectives State the functions of control system components

More information

SWITCHYARD SYSTEM BC1-SS-11-SD TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1

SWITCHYARD SYSTEM BC1-SS-11-SD TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1 SWITCHYARD SYSTEM TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1 November 2011 PREFACE This Training System Description has been designed to assist you in meeting the requirements of Module BC1-SS-11

More information

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator

More information

LV MCC with Arc Flash Mitigation (AFM) Units

LV MCC with Arc Flash Mitigation (AFM) Units LV MCC with Arc Flash Mitigation (AFM) Units Technical Tuesday June 30, 2015 Imagination at work. Markets Oil and Gas Petro-Chemical Mining and metals Pulp and paper Mass-production manufacturing Water

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

It is the job of the protection system equipment to recognize and remove the fault.

It is the job of the protection system equipment to recognize and remove the fault. Protection 1 (read section 13.0 of text) 1.0 Introduction Faults do not occur that frequently 1/year/100 miles of transmission is typical. Distribution systems may see more than this. However, when they

More information

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel.

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel. Training Course : High and Medium Voltage Substation Design, Testing and Maintenance Training Course For One Week In KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel Which Be Held As Under Details : Tel.

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN Padmounted switchgear MN285011EN Effective May 2017 Supersedes November 2004 (S285-10-4) Visible-Break switch accessory operation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

White Paper. UL Standards for Power Control System Equipment

White Paper. UL Standards for Power Control System Equipment White Paper UL Standards for Power Control System Equipment UL Standards for Power Control System Equipment An Introduction to UL 891 and UL 1558 Commercially available Power Controls Systems (PCS) can

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

Benefits, offering and references

Benefits, offering and references DOC ID: 9AKK107045A9180 DISTRIBUTION SOLUTIONS Digital medium-voltage switchgear Benefits, offering and references Contents Digital switchgear for medium-voltage applications Digital switchgear definition

More information

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123 Product: High Voltage AC Test Set Type: P123 Bicotest High Voltage Products Ltd Hellesdon Park Road, Drayton High Road, Norwich NR6 5DR United Kingdom Phone

More information

Best practices for making switchgear safer.

Best practices for making switchgear safer. Best practices for making switchgear safer. www.sea.siemens.com www.usa.siemens.com/switchgear Prepared by: Ken Newsome - Consulting Business Developer Kevin Mullins - Consulting Business Developer Joe

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

High Power Electronic Gear Installation and operation Guide

High Power Electronic Gear Installation and operation Guide High Power Electronic Gear Installation and operation Guide 96268731 GT 1 KW 230-240 V HQITS-S DGE CLI WI SC 96267936 GT 2 KW 230-240 V HO/HF DGE CLI WI SC IP21 IP21 electronical gear for 1 and 2 kw HIT-DE

More information

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and IEC 60309 H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and amperage to prevent interchangeability of voltages Watertight

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

Electrical Equipment and Comprehensive Power Grid Solutions

Electrical Equipment and Comprehensive Power Grid Solutions Integration into the future Electrical Equipment and Comprehensive Power Grid Solutions About us Joint-Stock Company Rusatom Automated Control Systems (JSC RASU) is a subsidiary of State Atomic Energy

More information

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv) Outdo Distribution (15.5 kv and 27 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault interrupting system shall confm to the following specification. 1.02 The

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

Checking the compatibility with IT (ungrounded) and corner-grounded delta systems. EMC filter +E200 (690 V drives and drive modules)

Checking the compatibility with IT (ungrounded) and corner-grounded delta systems. EMC filter +E200 (690 V drives and drive modules) Update notice Update notice 1 The notice concerns the ACS880-04XT hardware manuals listed below. Contents of the notice: Checking the compatibility of the drive with IT (ungrounded) and cornergrounded

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

UniSec, MV AIS for Secondary Distribution Smart Grid applications

UniSec, MV AIS for Secondary Distribution Smart Grid applications Ing. Natalia Moizzes- Switchgear Product Specialist Chile Abril 14 th 2015 UniSec, MV AIS for Secondary Distribution Smart Grid applications Slide 1 Concept - Needs and Solutions Requests are: Manage faults

More information

Best practices for making switchgear safer

Best practices for making switchgear safer Best practices for making switchgear safer White Paper Introduction What could be more important than protecting the safety of our most valuable assets, our people? Today s workers hold the keys to an

More information

SmartClose 3-phase, Synchronous Close Vacuum Capacitor Switch

SmartClose 3-phase, Synchronous Close Vacuum Capacitor Switch installation instructions SmartClose 3-phase, Synchronous Close Vacuum Capacitor Switch 2013 Hubbell Incorporated hpsliterature@hubbbell.com hubbbellpowersystems.com The equipment covered by these installation

More information

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Authors: Dr. Brett Watson, Siemens Ltd., PO Box 4833, Loganholme, QLD 4129, Australia

More information

Honeywell Safety Products. Lockout / Tagout. I Keep equipment from being set in motion & endangering workers.

Honeywell Safety Products. Lockout / Tagout. I Keep equipment from being set in motion & endangering workers. Honeywell Safety Products Lockout / Tagout I Keep equipment from being set in motion & endangering workers 480 Honeywell Safety Products Lockout / Tagout Most industrial accidents are caused by the unexpected

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

ENhanced TEChnology.  Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver. ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser

More information

Fundamentals of Circuit Breaker Maintenance. AVO Training Institute, Inc. 2018

Fundamentals of Circuit Breaker Maintenance. AVO Training Institute, Inc. 2018 Fundamentals of Circuit Breaker Maintenance 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation

More information

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS SUMMARY OF MODELS OF HRC FUSE-LINKS PNA000 PHNA000 PNA00 PHNA00 Rated current I n up to A up to 0 A up to A up to 0 A Rated voltage U n AC 00 V, 00 V 90 V 00 V 90 V DC 0 V 0 V 0 V 0 V Fuse-link size 000

More information

SERIES SD3800 / SD3810 SPECIFICATION

SERIES SD3800 / SD3810 SPECIFICATION SERIES SD3800 / SD3810 SPECIFICATION SOLID DIELECTRIC SINGLE SIDED 15 KV & 25 KV PADMOUNTED VACUUM LOAD INTERRUPTERS AND VACUUM FAULT INTERRUPTERS WITH VISIBLE DISCONNECTS MANUALLY OPERATED / REMOTELY

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIA-0402N Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808R, UID-0808T, UID-1600,UID-0016R, UID-0016T Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides

More information

Conext CL-60 Inverter Firmware Upgrade Process

Conext CL-60 Inverter Firmware Upgrade Process Conext CL-60 Inverter Firmware Upgrade Process http://solar.schneider-electric.com 976-0380-01-01/B August 2017 Application Note EXCLUSION FOR DOCUMENTATION UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER

More information

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold Tru-Break switchgear module Tru-Break switchgear module agenda Design platform and value Product specifications Operation Configuration examples

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UID-W1616R, UID-W1616T Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide

More information

Standards Update Notice (SUN) Issued: August 11, 2017

Standards Update Notice (SUN) Issued: August 11, 2017 Standard Information Standard Number: UL 621 Standard Name: Ice Cream Makers Standard Edition and Issue Date: 7 th Edition Dated May 7, 2010 Date of Revision: February 15, 2017 Date of Previous Revision

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

Why is my AFCI tripping?

Why is my AFCI tripping? www.garyklinka.com Page 1 of 21 Instructions: Fee $25 1. Print these pages. 2. Use the included information located on pages 12-20 to answer the 61 questions below. 3. Circle the correct answers and transfer

More information

Agilent 34401A 6½ 桁マルチメータ ユーザーガイド

Agilent 34401A 6½ 桁マルチメータ ユーザーガイド Agilent 34401A 6½ 桁マルチメータ ユーザーガイド Safety Information General Do not use this product in any manner not specified by the manufacturer. The protective features of this product may be impaired if it is used

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

AMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network

AMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network AMEU 2012 FuseSaver Highest availability and cost savings for your medium voltage distribution network October Page 2012 1 Siemens IC AG LMV 2012 MV C PPM Challenges for rural networks Characteristics

More information

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0 BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY

More information

Siemens AG SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A

Siemens AG SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A Switch Disconnectors Introduction Overview All key product features at a glance Compliant with IEC/EN 60439-1, IEC/EN 6094-3 Voltage levels up to 690 V AC Rated operational current from 160 A to 2000 A

More information

Small Power Station Surge Protection Analysis and Plan

Small Power Station Surge Protection Analysis and Plan [Type the document title] Small Power Station Surge Protection Analysis and Plan By ArresterWorks Jonathan Woodworth ArresterWorks Page 1 Contents 1.0 Executive Summary... 3 1.1 Project Overview... 3 1.2

More information

Installation and safety instructions for devices for conveying air/gas mixtures

Installation and safety instructions for devices for conveying air/gas mixtures The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission.

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission. Switchgear Interlock Applications Data Sheet Industries Power Distribution Power Generation Power Transmission Type DM Access Interlock with Spring Bolt Type PPS Interlock Quick-Trip ARC Flash Reduction

More information

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with

More information

Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak

Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak SIEREK switchgear Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak SIEREK Metal-Enclosed Interrupter Switchgear Selection and pplication Guide SIEREK medium-voltage metal-enclosed interrupter

More information

MNS ACS880 Switchgear mounted industrial drives

MNS ACS880 Switchgear mounted industrial drives MNS ACS880 Switchgear mounted industrial drives Switchgear mounted industrial drives AC Drives are designed for installation in a normal industrial environment. However, various auxiliary equipment for

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

ENhanced TEChnology.   Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

Grid Automation packaged solutions Optimal automation of medium voltage grids

Grid Automation packaged solutions Optimal automation of medium voltage grids Grid Automation packaged solutions Optimal automation of medium voltage grids Application principles of the Zone concept Grid Automation (GA) packaged solutions The zone concept offers a method to analyze

More information

Energy Isolation: Module II: EI for the Authorized Employee Answer Key NSTC-16

Energy Isolation: Module II: EI for the Authorized Employee Answer Key NSTC-16 North Slope Training Cooperative Energy Isolation Module II Answer Key (revision 6/2014) Energy Isolation: Module II: EI for the Authorized Employee Answer Key NSTC-16 (Authorized employees are required

More information

IntelliTeam II Automatic Restoration System

IntelliTeam II Automatic Restoration System No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation Location(s) where activities are performed under accreditation Head Office Utrechtseweg 310, Building no. R11 6812 AR Arnhem The Netherlands Location Abbreviation/ location code Utrechtseweg 310, Building

More information

Ground Fault Protection. Instruction Manual

Ground Fault Protection. Instruction Manual Ground Fault Protection DSP OHMNI Accessory: DSP-CA(S) Cable Adapter Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Bulletin Installation of solar photovoltaic systems Rules , , , , and Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR AUGUST 14, 2001 REVISION 1 Publication: SE-135-M Document: S95-C135-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

Network Configuration Document Selection for New Substations Framework

Network Configuration Document Selection for New Substations Framework Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...

More information

17 th Edition (BS 7671:2008) incorporating Amendment No 1

17 th Edition (BS 7671:2008) incorporating Amendment No 1 20 17th Edition 17 th Edition (BS 7671:2008) incorporating Amendment No 1 Installations designed from the 1 st January 2012 are to comply with Amendment number 1. Geoff Cronshaw The first amendment to

More information

INTRINSICALLY SAFE Ex ia PSU TYPE AC36W

INTRINSICALLY SAFE Ex ia PSU TYPE AC36W Title INTRINSICALLY SAFE Ex ia PSU TYPE AC36W USER MANUAL Document Number 66-184-12 Issue 10 10 Update new logo and address 2017.10.18 CW CW PC 09 Added Um as 265V, Io up to 3.3A & IIB data 2017.08.21

More information

Gas / Electric Arcing Interactions

Gas / Electric Arcing Interactions Gas / Electric Arcing Interactions Michelle Gallardo Senior Engineer Alan Mulkey Consulting Engineer Gas System Integrity May 20, 2015 Puget Sound Energy (PSE) PSE is Washington state s oldest local energy

More information

Power Transmission Division Link between power generation and distribution

Power Transmission Division Link between power generation and distribution Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Microprocessor protection and automation devices

Microprocessor protection and automation devices Microprocessor protection and automation devices THE ТЭМП 2501 MICROPROCESSOR PROTECTION TERMINALS It is well known that microprocessor protection devices have indisputable advantages over electromechanical

More information

LOCK OUT/TAG OUT. Energy Isolation. LOTO Application and Uses WHAT S INSIDE STEPS TO SAFELY PERFORM MACHINE MAINTENANCE:

LOCK OUT/TAG OUT. Energy Isolation. LOTO Application and Uses WHAT S INSIDE STEPS TO SAFELY PERFORM MACHINE MAINTENANCE: WHAT S INSIDE LOCK OUT/TAG OUT Energy Isolation Most industrial accidents are caused by the unexpected energization or start-up of machines or equipment or by the uncontrolled release of energy. Many of

More information

Circuit Breaker Analyzer & Timer CAT-P

Circuit Breaker Analyzer & Timer CAT-P Circuit Breaker Analyzer & Timer CAT-P Portable (1,4 kg / 3.1 lbs) Internal battery power supply Online measurement (First trip test) Offline measurement DC voltage and DC current measurement Touch screen

More information

Benefits of Limiting MV Short-Circuit Current in Large Data Centers

Benefits of Limiting MV Short-Circuit Current in Large Data Centers Benefits of Limiting MV Short-Circuit Current in Large Data Centers White Paper 253 Revision 0 by Antony Parsons Executive summary Once IT load levels exceed just a few megawatts (MW) of power, moving

More information

Improvements in Transmission Switching Reliability using SF 6 Interrupter Technology

Improvements in Transmission Switching Reliability using SF 6 Interrupter Technology 1 Improvements in Transmission Switching Reliability using SF 6 Interrupter Technology Brian J. Berner, Member, IEEE and Joseph R. Rostron, Member, IEEE Abstract The use of load break switches and sectionalizers

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

VisoVac padmount fault interrupter

VisoVac padmount fault interrupter Network Protector Catalog Data CA024003EN New Issue VisoVac padmount fault interrupter General The medium voltage padmount vacuum fault interrupter from Eaton delivers economical, reliable and flexible

More information

Medium Voltage Metal-Enclosed Power Capacitor Banks

Medium Voltage Metal-Enclosed Power Capacitor Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium

More information

Standards Update Notice (SUN) Issued: July 28, 2017

Standards Update Notice (SUN) Issued: July 28, 2017 Standard Information Standard Number: CSA C22.2 No. 107.1 Standard Name: Power conversion equipment Standard Edition and Issue Date: 4 th Edition Dated June 2016 Date of Issue: June 2016 Date of Previous

More information