UL508Afor Panel Builders Getting Started

Size: px
Start display at page:

Download "UL508Afor Panel Builders Getting Started"

Transcription

1 UL508Afor Panel Builders Getting Started Restricted Siemens AG 2016 siemens.tld/keyword

2 Exclusion of Liability The typical circuit diagrams and interpretations of the standard are not binding and do not claim to be complete regarding configuration, equipment or any other eventuality. They do not represent any client-specific solutions and are only intended to offer assistance for typical tasks. Each person viewing this presentation is responsible for the correct operation of the products described. This presentation does not relieve you of your responsibility regarding safe handling when using, installing, operating, and maintaining the equipment. By viewing this presentation you agree that Siemens cannot be made liable for possible damage beyond the above mentioned liability clause. We reserve the right to make changes and revisions to this informational documentation without prior announcement. When writing these guidelines, a lot of tables and texts were lifted straight from the relevant standards. All users of this documentation must always check whether the items quoted are still up to date or not. The final decision about the appropriateness of applying the applicable standards must be made by the user of this documentation. The reproduction of this presentation and its distribution, utilization or the dissemination of its contents to third parties is not permitted. Page 2

3 Speaker Jeff Woolfolk Bachelor of Science, Electrical Engineering Technology System Consultant Digital Factory Control Products Application consulting: - North American Standards and Codes - European Directives and international IEC/ISO standards Page 3

4 Differences between USA and everywhere else = Page 4

5 Excerpts of the OSHA standards and NEC Ed OSHA (b)(2) Subpart S Electrical / General requirements: Installation and use: Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. Definitions acc. NEC Art. 100: Equipment: A general term, including fittings, devices, appliances, luminaires, apparatus, machinery, and the like used as a part of, or in connection with, an electrical installation. Listed: Equipment, materials, or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets appropriate designated standards or has been tested and found suitable for a specified purpose. Labeled: Equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicates compliance with appropriate standards etc. Page 5

6 Relevant standards for panels for the US market Page 6

7 Comparison between USA and IEC standards IEC IEC IEC Page 7

8 UL508A Industrial Control Panels 1893 World Exhibition in Chicago Outbreak of a fire 1894 Start of UL William H. Merrill opens the Underwriters Electrical Bureau Page 8

9 National Fire Protection Association Foundation: 1896, due to increasing sprinkler system installations Headquarters: Quincy, Massachusetts Publication of over 300 standards to date National Electrical Code or NFPA70 NFPA79 Electrical Standard for Industrial Machinery Standardization organization in the field of fire protection, electrical safety and building safety Page 9

10 NFPA (nec) and UL508A work together Page 10

11 NFPA (nec) and UL508A work together When it comes to Industrial control panels the NEC 2014 refers still to UL 508A! Recommendation: Industrial control Panels should fulfill furthermore the UL 508A Maximum voltage 600V! UL 508A is still limited to 600V or less! Page 11

12 Most Important Network Types in Detail Grounded wye / solidly grounded wye Slash rating: e.g.: 480Y/277V, solidly grounded wye 3 phase; 4 wire 3 phase; 3 wire Possible devices 480Y/277V; 600/347V 480V; 600V Transformer 3p, 4w / grounded phase-ground U = 277 V across one contact worst case! I k 480Y/277V AC L1 L2 L3 Note: All devices having a slash rating with the indicated voltage or higher All devices having a delta rating with at least the higher of both voltages M Page 12

13 Most Important Network Types in Detail Corner grounded delta Straight (Delta) rating: e.g.: 480V / 3 phase - 3 wire Transformer 480V AC L1 L2 L3 Possible devices in this example: 480V; 600V I k Phase - Ground Do not use: 480Y/277V; 600Y/347V U = 480 V across one contact worst case!! Note: The devices switch full (=high) voltage at the first single pole short-circuit (phase to ground) M The following applies to this network in principle: Only devices with delta rating must be used! Page 13

14 Most Important Network Types in Detail Ungrounded delta - Ungrounded wye Straight rating: e.g.: 480V / 3 phase - 3 wire Transformer Δ/Y 480V AC L1 L2 L3 Possible devices in this example: 480V; 600V Do not use: 480Y/277V; 600Y/347V Note: Phase - Phase U = 480 V across one contact worst case!! The devices switch the full (=high) voltage at the second single-pole short-circuit (phase to ground) I k! Operation Betrieb requires Insulation monitoring! Insulation measuring M The following applies to this network in principle: Only devices with delta rating must be used! Page 14

15 UL Category Code Numbers The CCN represents a clear description of the respective product The respective CCN Guide Information clearly describes how and under which conditions the respective product can or may be applied ( Every AHJ or UL inspector can thus verify whether the respective product was correctly configured and applied The CCN should be additionally integrated in the parts list Examples: DIVQ // DIVQ7 // NMTR2 // NMTR8 Page 15

16 UL508A Table SA1.1 Page 16

17 ( Page 17

18 UL508A Short Circuit Current Rating (SCCR) Requirement of NEC 2005 Art. 409 (mandatory since April 26, 2006) Re-enforcement of the standards for industrial control panels Failures in determining the short-circuit current rating (= SCCR) of an industrial control panel. For the short-circuit current rating not only the short-circuit breaking capacity of, e.g. the circuit breaker is needed, also the short-circuit current rating of every individual device is as relevant. SCCR-relevant components in the power circuit, such as: Circuit-breakers, contactors, soft starters, overload relays, but also Terminals, busbars, Supply to an control transformers, Frequency converters, Further current limiting effects are not allowed to be considered e.g.: that of wires, cables, busbars, Page 18

19 UL508A Short Circuit Current Rating (SCCR) NEC Article Marking An industrial control panel shall be marked with the following information that is plainly visible after installation:. (4) Short-circuit current rating of the industrial control panel based on one of the following: a. Short-circuit current rating of a listed and labeled assembly b. Short-circuit current rating established utilizing an approved method Informational Note: ANSI/UL 508(A), Standard for Industrial Control Panels, Supplement SB, is an example of an approved method. Exception to (4): Short-circuit current rating markings are not required for industrial control panels containing only control circuit components Page 19

20 UL508A Short Circuit Current Rating (SCCR) Determination of the short-circuit current rating (SCCR) acc. to NEC (4): Step 1: necessary! SCCR of the installed and UL-listed components Step 2: necessary! Establishment of the SCCR on the basis of standard values (UL508A suppl. SB or UL-guide; chapter 5.8.4). Step 3: Optional, very helpfull! SCCR of tested industrial control equipment assemblies (series rating = 2 circuit breakers in series or combination tests = motor branch circuits) Step 4: Optional, not very helpfull! Use of current limiting devices (transformers, fuses, circuit breakers) Page 20

21 UL508A Short Circuit Current Rating (SCCR) Page 21

22 UL508A Short Circuit Current Rating (SCCR) List the short circuit current ratings of components, from UL 508A, Table SB 4.1, if no values on the nameplate or on instructions provided with the components (see step 1) Establishment of the SCCR value using the table in UL508A. These standard values must be used if the technical documents do not provide SCCR values for the applied devices. Page 22

23 UL508A Short Circuit Current Rating (SCCR) SCCR of tested industrial control equipment assemblies Series rating tests Series connection of 2 or more devices, which are able to automatically respond in short circuit cases without delay. SB4.3.2 in UL508A! Current limiting cannot be used here! Combination tests Series connection of any type of devices, e.g.: Motor protection circuit breaker and contactor (=fuseless load feeders as type F acc. to UL508) MCCB and terminal block Page 23

24 UL508A Short Circuit Current Rating (SCCR) Series rating for Siemens Breakers Series rating Tested combinations Fuse MCCB 3VL MCCB 3VL MCB 5SJ4..HG4 MCB 5SJ4..HG4 M 3RT contactor 3RB motor protection relay Page 24

25 UL508A Short Circuit Current Rating (SCCR) Transformer peak-let-through currents can be used to protect Branch circuits! Feeder circuit Main Disconnect Current limiting device Every Transformer is current limiting Branch circuit Short circuit protection Short circuit protection Short circuit protection contactor contactor contactor Overloadrelay Overloadrelay motor motor heater Page 25

26 UL508A Short Circuit Current Rating (SCCR) Page 26

27 UL508A Short Circuit Current Rating (SCCR) Page 27

28 UL508A Short Circuit Current Rating (SCCR) 1.) Single Phase Transformers: Transformer Full-Load Current (IFL) = (Transformer kva x 1000) / Voltage* Short Circuit Current (ISC line-to-line) = ((Transformer Full Load Current (IFL )) / Transformer Impedance (Z) 2.) Three Phase Transformers: Transformer Full-Load Current (IFL) = (Transformer kva x 1000) / (Voltage** x 1.732) Short Circuit Current (ISC line-to-line-to-line) = ((Transformer Full Load Current (IFL )) / Transformer Impedance (Z) Page 28

29 UL508A Short Circuit Current Rating (SCCR) Result: 3 Ph. 480Y/277V AC Class J Fuse, 100 Amps A.I.C: 100 ka Overall SCCR = 100kA = A.I.C of the Class J Fuse on the primary side of the Transformer since the available secondary fault current of the transformer (4.6kA) is less than the SCCR and A.I.C s of the components on the load side of the transformer Transformer: S = 150 kva, Z = 4%, 3 Phase, 480/277V Available secondary Fault Current = Power Distribution Block SCCR: 10 Infeed system SCCR: 65 MCB A.I.C: 10 MSP A.I.C: 65 Compact MSP A.I.C: 30 MSP s A.I.C: 65 Solid state relay SCCR: 5 Contactors SCCR: 5 Terminal Block SCCR: 10 Terminal Block SCCR: 10 Terminal Block SCCR: 10 Terminal Blocks SCCR: 10 Page 29

30 UL508A Short Circuit Current Rating (SCCR) Use of current limiting fuses, when used as feeder elements SB Only fuses listed in UL508A table SB 4.2 are applicable. Use let-through values from the UL508A table SB 4.2 ONLY (manufacturer s values are NOT permissible) Fuses are also standardized in the geometrical dimensions manufacturer-independent replacement The fuse is replaced by the service staff, which shall not compare the corresponding let-through values (old fuse versus new fuse) Note: For practical application only partially useable, as, e.g.: Standard contactor up to 37kW: max. 5kA Standard busbar: max. 10kA Standard terminal block: max. 10kA Page 30

31 UL508A Short Circuit Current Rating (SCCR) Use of current limiting fuses, when used as feeder elements SB Use let-through values from the UL508A table SB 4.2 ONLY (manufacturer s values are NOT permissible) Fuses are also standardized in the geometrical dimensions manufacturer-independent replacement The fuse is replaced by the service staff, which shall not compare the corresponding let-through values (old fuse versus new fuse) Example: There are 7 different 30A Class R Fuses, each. with different characteristics Page 31

32 UL508A Short Circuit Current Rating (SCCR) Use of current limiting circuit breakers, listed as current limiting, when applied as feeder element SB The circuit breaker must be listed as current limiting The circuit breaker must be marked as current limiting (UL508A SB 4.3.2) The manufacturer has to publish the current limiting characteristics or data and provide them to the user When replacing the circuit breaker by a different type or manufacturer, the SCCR value must be checked again engineering is required Note: For practical applications hardly usable, as, e.g.: Standard contactor up to 37kW: max. 5kA Standard busbar: max. 10kA Standard terminal block: max. 10kA Siemens current limiting breakers Page 32

33 UL508A Short Circuit Current Rating (SCCR) Siemens SIRIUS Contactor 3RT1035 Short Circuit Current 5kA, 600V Page 33

34 UL508A Short Circuit Current Rating (SCCR) See report in the annex Magnetic Motor Control Type F Page 34

35 UL508A Short Circuit Current Rating (SCCR) Page 35

36 Thank Questions? you for your attention! Siemens Industry Inc All Rights Reserved.

UL 508 A standard-compliant design of industrial control panel

UL 508 A standard-compliant design of industrial control panel UL 508 A standard-compliant design of industrial control panel Axel Jöhnke System Architecture Expert 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net Origin and Comprehension Organizations Certificates

More information

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

UL 508A Industrial Control Panels Eaton. All Rights Reserved. UL 508A Industrial Control Panels Objectives Who is UL? UL508A Origin Current emphasis on UL508A What is the UL 508A Standard? Implementation of the Standard Component Selection Short Circuit Current Ratings

More information

Requirements for machine approval in North America under the new NEC 2017

Requirements for machine approval in North America under the new NEC 2017 Requirements for machine approval in North America under the new NEC 2017 2 Rittal NEC 2017 The NEC 2017 introduces increased requirements for SCCR Rittal has long been prepared Rittal always responds

More information

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime

More information

Equipment Short-Circuit Current Rating and Available Fault Current

Equipment Short-Circuit Current Rating and Available Fault Current Equipment Short-Circuit Current Rating and Available Fault Current Dan Neeser Field Application Engineer Eaton s Bussmann Business Dan.Neeser@CooperIndustries.com Agenda Interrupting Rating & Series Rating

More information

Industrial control panels for the North American market. UL guidelines 11/2010. Industrial Controls. Answers for industry.

Industrial control panels for the North American market. UL guidelines 11/2010. Industrial Controls. Answers for industry. Industrial control panels for the North American market UL guidelines 11/2010 Industrial Controls Answers for industry. Preface Working with this documentation 1 Industrial Control Panels for North America

More information

Industrial controls SIRIUS Innovations Star-Delta (Wye-Delta) Combination Assembly and Wiring Application description June 2010

Industrial controls SIRIUS Innovations Star-Delta (Wye-Delta) Combination Assembly and Wiring Application description June 2010 Cover Sheet Industrial controls SIRIUS Innovations Star-Delta (Wye-Delta) Combination Assembly and Wiring Application description June 2010 Applications & Tools Answers for industry. Industry Automation

More information

Industrial Control Panels Tested product combinations to meet NEC Article 409 and UL 508A Standard

Industrial Control Panels Tested product combinations to meet NEC Article 409 and UL 508A Standard Industrial Control Panels Tested product combinations to meet NEC Article 409 and UL 508A Standard Short circuit current ratings and the new NEC Article 409 The 2005 Edition of the National Electrical

More information

Short Circuit Current Ratings and AC Drives

Short Circuit Current Ratings and AC Drives Short Circuit Current Ratings and AC Drives Ivan Spronk, Product Marketing AC Drives Schneider Electric Industry NOW Express Goal of this session Understand Importance of proper SCCRs Hot button points

More information

Industrial Control Panels for North America

Industrial Control Panels for North America Industrial Control Panels for North America Interactive animation on the subject Industrial Control Panels for North America Interactive animation on the subject The animation is based on 2 Control Panels

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

Overload Relays. 3RB2 Solid-State Overload Relays. 3RB20, 3RB21 for standard applications. 5/48 Siemens LV Overview

Overload Relays. 3RB2 Solid-State Overload Relays. 3RB20, 3RB21 for standard applications. 5/48 Siemens LV Overview Overload Relays Siemens AG 2009 Overview 1 2 2 (1)Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors and soft starters, these connecting

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

SIRIUS Overload Relays. SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link

SIRIUS Overload Relays. SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link Integrated Motor Protection for High-Feature Applications SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link SIRIUS Overload Relays www.siemens.com/sirius SIRIUS 3RB24

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

Easy, efficient and always up to date the SIRIUS modular system

Easy, efficient and always up to date the SIRIUS modular system Easy, efficient and always up to date the SIRIUS modular system siemens.com/sirius Easy, efficient and always up to date, that s how industrial controls can be! Switching Protecting Starting Monitoring

More information

Spacing Requirements for Power Distribution and Terminal Blocks

Spacing Requirements for Power Distribution and Terminal Blocks Spacing Requirements for Power Distribution and Terminal Blocks New requirements in the 2005 NEC for a marked short-circuit current rating on industrial control panels, industrial machinery, and commercial/industrial

More information

Solid-State Switching Devices

Solid-State Switching Devices Overview 3RF21 3RF20 3RF22 3RF23 SIRIUS 3RF2 solid-state switching devices Solid-state switching devices for resistive loads Solid-state relays Solid-state contactors Function modules Solid-state switching

More information

Electrical Service Change-Tn Neenah

Electrical Service Change-Tn Neenah Electrical Service Change-Tn Neenah Permit # Owners name Project address Contractors name Contractors address Fax #: Type of occupancy Job description New construction Main panel Single phase Additional

More information

Problem solver for the North American market: PKZM4-...-CB

Problem solver for the North American market: PKZM4-...-CB Molded Case Circuit Breaker for USA and Canada www.eaton.eu Problem solver for the North American market: PKZM4-...-CB Technical paper Dipl.-Ing. Wolfgang Esser Problem solver for the North American market:

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North

More information

Circuit Protection Methods

Circuit Protection Methods Circuit Protection Methods Differentiating between Supplementary Protection, Branch Circuit Protection, and Self-Protected Devices Introduction Modern electrical equipment continues to increase in complexity

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link

SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link Integrated Motor Protection for High-Feature Applications siemens.com/sirius Answers for industry. SIRIUS 3RB24

More information

Safety-related controls SIRIUS Safety Integrated

Safety-related controls SIRIUS Safety Integrated Functional Example CD-FE-I-018-V30-EN Safety-related controls SIRIUS Safety Integrated with monitored start up to SIL 1 acc. to IEC 62061 and PL c acc. to ISO 13849-1 with a SIRIUS safety relay 3TK28 with

More information

Solid-State Contactors

Solid-State Contactors Solid-state contactors for switching motors The solid-state contactors for switching motors are intended for frequently switching on and off three-phase current operating mechanisms up to 7.5 kw and reversing

More information

White Paper October 2009

White Paper October 2009 ANSI /UL1449 Third Edition Safety Standard (New UL and NEC standards means new performance levels, test procedures and markings to products and manufacturers) White Paper October 2009 The past two years

More information

TeSys IEC Contactors and Overload Relays

TeSys IEC Contactors and Overload Relays TeSys IEC Contactors and Overload Relays Making High-Fault Short-Circuit Current Ratings Simple Schneider Electric is an industry leader in IEC contactors and overload relays, and is recognized as the

More information

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series POWER & ACTUATION OVERLOAD RELAYS series Need reliable, accurate overload and phase-loss protection for your motors? c3controls Series Bimetallic Overload Relays provide unmatched protection and can be

More information

Electrical Plan Review

Electrical Plan Review Electrical Plan Review Overcurrent Protection and Devices, Short-Circuit Calculations, Component Protection, Selective Coordination, and Other Considerations Table of Contents Part I: Overcurrent Protection

More information

Standards and approvals

Standards and approvals 2 SIRIUS controls contactors and contactor assemblies 4 SIRIUS controls solid-state switching devices 4 SIRIUS protective devices 8 SIRIUS load feeders and compact starter 12 SIRIUS Circuit Breaker 12

More information

Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE AMBERG, GERMANY

Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE AMBERG, GERMANY Issued to: Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE 48 92220 AMBERG, GERMANY This is to certify that Auxiliary Devices representative samples of 3UF70 followed by 0 or 1 followed by 0

More information

Miniature Circuit Breakers for Railway Applications

Miniature Circuit Breakers for Railway Applications Siemens AG 00 for Railway Applications BETA Low-Voltage Circuit Protection The miniature circuit breakers are used in fixed railway systems and rolling stock for protecting system components against overcurrent

More information

Industrial Controls. Protection Devices. Gerätehandbuch. Answers for industry. Edition 09/2014

Industrial Controls. Protection Devices. Gerätehandbuch. Answers for industry. Edition 09/2014 Industrial Controls Protection Devices SIRIUS Innovations - Thermal Overload Relays SIRIUS 3RU2 / Solid-State Overload Relays SIRIUS 3RB3 Gerätehandbuch Manual Edition 09/2014 Answers for industry. SIRIUS

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: SIEMENS AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE 48 92220 AMBERG GERMANY This is to certify that representative samples of Motor Controllers, Magnetic (See following pages for additional

More information

Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 Effective May 27, 2010 Effective December 3, 2011

Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 Effective May 27, 2010 Effective December 3, 2011 Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 INTERCONNECTION APPLICATION FOR ALL BUT UL1741 CERTIFIED INVERTER BASED SYSTEMS LESS THAN 10 KW In addition to the information provided below, a complete

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Figure.1 Altech s three new series deliver multiple capabilities. In all three series, ground fault sensitivity levels range

More information

SIRIUS Safety Integrated. Modular safety system 3RK3

SIRIUS Safety Integrated. Modular safety system 3RK3 Functional Example CD-FE-I-048-V10-EN SIRIUS Safety Integrated Modular safety system 3RK3 Emergency Stop with monitored Start and Protective Door with automatic start according to category 4 in EN 954-1.

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers NEMA Standards Publication AB 5-2011 Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite

More information

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2 Supersedes 6/2015 Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2 XXCFXXX10-DIN Contents Description Page 1.0 Setup...2 1.1 Before Installation...2 1.2 Installation...3 For AC Applications...3

More information

Load Feeders and Motor Starters for Use in the Control Cabinet

Load Feeders and Motor Starters for Use in the Control Cabinet Load Feeders and Motor Starters for Use in the Control Cabinet Price groups 12W, 14O, 230, 241, 250, 260, 41B, 41D, 41E, 41L, 42C, 42D, 42F, 471, 4N1, 5K1, 5K2, 5N2, 764, 15, 16 /2 Introduction SIRIUS

More information

3RT, 3TB, 3TF Contactors for Switching Motors

3RT, 3TB, 3TF Contactors for Switching Motors RT, TB, TF Contactors for Switching Motors Overview RT contactors and coupling relays Size S00 with mountable accessories The SIRIUS generation of controls is a complete, modular system family, logically

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 11 FROM:

More information

E A54-UL 2012-AUGUST-29 XP POWER L L C SUITE E DYER RD SANTA ANA CA 92705

E A54-UL 2012-AUGUST-29 XP POWER L L C SUITE E DYER RD SANTA ANA CA 92705 CERTIFICATE OF COMPLIANCE Certificate Number 20120829-E139109 Report Reference Issue Date E139109-A54-UL 2012-AUGUST-29 Issued to: XP POWER L L C SUITE 150 1241 E DYER RD SANTA ANA CA 92705 This is to

More information

Solid-State Switching Devices

Solid-State Switching Devices Controls Solid-State Switching Devices /2 Introduction Solid-State Switching Devices /3 General data Solid-State Switching Devices for Resistive Loads /5 General data Solid-State Relays /7 General data

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Overload Relays 3RU Thermal Overload Relays 3RB Solid State Overload Relays 3UF SIMOCODE pro Intelligent Motor Protection

Overload Relays 3RU Thermal Overload Relays 3RB Solid State Overload Relays 3UF SIMOCODE pro Intelligent Motor Protection IEC Power Control Product Overview Alphabetical Product and Catalog Number Index MSPs 3RV20 Motor Starter Protectors 3RV27 & 3RV28 Circuit Breakers 3RA19/29 & 3RV19/29 Accessories 1 Contactors 3RT, 3TF,

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 277/480 Y V DC 60

Application Switchgear for industrial and advanced commercial applications. U e V AC 277/480 Y V DC 60 DATASHEET - FAZ-C5/2-RT Miniature circuit breaker (MCB), 5A, 2p, C-Char, AC Part no. FAZ-C5/2-RT Catalog No. 102203 Eaton Catalog No. FAZ-C5/2-RT EL-Nummer 1691799 (Norway) Similar to illustration Delivery

More information

More Questions from Inspectors Numerous PV Systems Pose Issues

More Questions from Inspectors Numerous PV Systems Pose Issues Perspectives on PV More Questions from Inspectors Numerous PV Systems Pose Issues by John Wiles 76 IAEI NEWS March. April 2012 www.iaei.org Photovoltaic (PV) systems prices continue to drop and inspectors

More information

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020 Selection Guide Control Circuit and Load Protection Circuit Protection Portfolio 1489-M Circuit Breakers Approved for branch circuit protection in the United States and Canada, and certified as Miniature

More information

Fast Bus Busbar System

Fast Bus Busbar System Busbar System Industrial Controls Product Catalog 2017 Section c o n t e n t s Fast Bus busbar adapter system mm system Page Selection and ordering data Busbar holders /9 Fast Bus adapter shoes /11 Incoming

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

Fast Bus Fast Bus Busbar System

Fast Bus Fast Bus Busbar System Fast Bus Busbar System Contents Fast Bus busbar adapter system mm system Page Selection and ordering data Busbar holders /9 Fast Bus adapter shoes /11 Incoming supply terminals /6 Copper busbar /6 Busbar

More information

Overcurrent and Overvoltage Protection Changes in the 2008 NEC Code. www. ElectricalPartManuals. com

Overcurrent and Overvoltage Protection Changes in the 2008 NEC Code. www. ElectricalPartManuals. com Overcurrent and Overvoltage Protection Changes in the 2008 NEC Code National Electrical Code and N.E.C. are registered trademarks of the National Fire Protection Association (NFPA), Quincy, MA 02269. This

More information

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors Close Protection from Moeller miniature branch circuit breakers miniature supplementary protectors FAZ branch circuit breakers General Information... Selection Tables Trip Characteristic C - Box terminals...

More information

Cat. No. 140M-F M-D8E-B

Cat. No. 140M-F M-D8E-B Motor Protection Circuit Breakers Product Selection Motor Protection Circuit Breakers Short Circuit Protection Standard Magnetic Trip ( x I e ) Motor Overload Protection Trip Class 0 0 Rated Operational

More information

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example Introduction 1 Application example 2 Industrial Controls Motor management and control devices SIMOCODE pro - Application examples Application Manual Example circuits control functions 3 Further application

More information

Max. Short Circuit Current [ka] Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 600V C-Frame

Max. Short Circuit Current [ka] Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 600V C-Frame ! Bulletin 0M Motor Circuit Protectors Type Coordination 00V Current Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 00V For Use With Contactors Below (or larger) 0M-CE-A

More information

Protection Equipment

Protection Equipment Protection Equipment Price groups 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J, 143, 401 /2 Introduction Motor starter protectors/ circuit breakers SIRIUS 3RV2 motor starter protectors up to 40 A / General data

More information

SIGUARD Safety Combinations and Safe Load Feeders. safety INTEGRATED

SIGUARD Safety Combinations and Safe Load Feeders. safety INTEGRATED SIGUARD Safety Combinations and Safe Load Feeders safety INTEGRATED EMERGENCY Topmost priority protection of man, machine and the environment The topmost priority is to protect man, machine and the environment

More information

Load Feeders and Motor Starters for Use in the Control Cabinet

Load Feeders and Motor Starters for Use in the Control Cabinet Load Feeders and Starters for Use in the Control Cabinet rice groups G W, 4O, 30, 4, 50, 60, 4B, 4D, 4E, 4L, 4C, 4D, 4F, 47, 4N, 5K, 5K, 5N, 764, 5, 6 / Introduction SIRIUS 3RA load feeders /4 General

More information

Click 'n' Go: SIRIUS Modular System SIRIUS. Highly flexible system-based switching, protecting and starting. Answers for industry.

Click 'n' Go: SIRIUS Modular System SIRIUS. Highly flexible system-based switching, protecting and starting. Answers for industry. Click 'n' Go: SIRIUS Modular System SIRIUS Highly flexible system-based switching, protecting and starting. Answers for industry. s Everything for the electrical cabinet: SIRIUS Modular System. Contents

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control . Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Overload Relays.................... C440/XT

More information

Innovations in the Sirius Modular System for greater efficiency in Industrial Controls and in control cabinet construction

Innovations in the Sirius Modular System for greater efficiency in Industrial Controls and in control cabinet construction Eckard Eberle, Head of the Control Components Business Segment Siemens AG, Nuremberg International Trade Press Conference held on 24 November 2009 in Nuremberg Innovations in the Sirius Modular System

More information

The purpose of this document is to specify the power requirements for Core Health and Fitness LLC equipment.

The purpose of this document is to specify the power requirements for Core Health and Fitness LLC equipment. Power Requirements Applies to: All Machines The purpose of this document is to specify the power requirements for Core Health and Fitness LLC equipment. Latest Rev. Attention: Obtain the assistance of

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16289 to 26 35 00, removed references to other section numbers 10/14/14 Amend text in section B

More information

STANDARD SUBMITTAL PACKAGE

STANDARD SUBMITTAL PACKAGE STANDARD SUBMITTAL PACKAGE SBP1000-51( ) FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for

More information

Siemens AG Highly flexible system-based switching, protecting and starting. SIRIUS Modular System. Answers for industry.

Siemens AG Highly flexible system-based switching, protecting and starting. SIRIUS Modular System. Answers for industry. Siemens AG 00 Highly flexible system-based switching, protecting and starting. SIRIUS Modular System SIRIUS Answers for industry. Everything for the electrical cabinet: SIRIUS Modular System. Press Shop

More information

Cutler-Hammer. January 2001

Cutler-Hammer. January 2001 Cutler-Hammer January 0 Vol.,Ref. 2-2 Product Line Overview January 0 Vol., Ref. No. [068] 2 Product Line Description Cutler-Hammer Molded Case Circuit s are designed to provide circuit protection for

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Page 1 of 149 First Revision No. 50-NFPA 79-2012 [ Global Input ] Delete the parenthetical terms used to describe IEC terms that follow terms used in NFPA 79 such as "protective bonding". Add information

More information

Contactors and Contactor Assemblies

Contactors and Contactor Assemblies RT contactors, size S00 The product range at a glance The new generation is a complete, modular system family, logically designed right down to the last detail, from the basic units to the accessories.

More information

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-25 Delivery program Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection Part no. PKZM4-25 Catalog No. 222352 Eaton Catalog No. XTPR025DC1NL EL-Nummer 0004355158 (Norway)

More information

UL TEST REPORT AND PROCEDURE

UL TEST REPORT AND PROCEDURE Issue Date: 2011-02-09 Page 1 of 16 Report Reference # E116994-A60-UL UL TEST REPORT AND PROCEDURE Standard: Certification Type: CCN: Product: Model: Rating: UL 60601-1, 1st Edition, 2006-04-26 (Medical

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: This is to certify that representative samples of SIEMENS AG DF CP R&D VC 2 WERNER-VON-SIEMENS-STRASSE 48 92224 AMBERG, GERMANY MOTOR CONTROLLERS, MANUAL (See following page for additional information.)

More information

SCCR Overall Panel Short Circuit Current Rating. per NEC and UL standards. Technical Paper Dipl-Ing. Wolfgang Esser.

SCCR Overall Panel Short Circuit Current Rating. per NEC and UL standards. Technical Paper Dipl-Ing. Wolfgang Esser. VER0211-959_D_GB 27.02.2007 13:15 Uhr Seite U4 www.moeller.net SCCR Overall Panel Short Circuit Current Rating Moeller addresses worldwide: www.moeller.net/address E-Mail: info@moeller.net per NEC and

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

Standards Update Notice (SUN) Issued: August 11, 2017

Standards Update Notice (SUN) Issued: August 11, 2017 Standard Information Standard Number: UL 621 Standard Name: Ice Cream Makers Standard Edition and Issue Date: 7 th Edition Dated May 7, 2010 Date of Revision: February 15, 2017 Date of Previous Revision

More information

SIRIUS Safety Integrated. Modular safety system 3RK3

SIRIUS Safety Integrated. Modular safety system 3RK3 Functional Example CD-FE-I-045-V10-EN SIRIUS Safety Integrated Modular safety system 3RK3 EMERGENCY STOP with Protective Door Monitoring according to category 2 in EN 954-1, with MSS Basic Comments "Safety

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC B Functional Safety Edition 05/2009 16811216 / EN SEW-EURODRIVE Driving the world Content Content

More information

Medium Voltage Metal-Enclosed Power Capacitor Banks

Medium Voltage Metal-Enclosed Power Capacitor Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium

More information

Safe Isolation of Main Circuits with Switch-Disconnectors N or with Molded Case Switches NS

Safe Isolation of Main Circuits with Switch-Disconnectors N or with Molded Case Switches NS www.moeller.net Safe Isolation of Main Circuits with Switch-Disconnectors N or with Molded Case Switches NS Reliably and safely controlling, switching and managing power. In industry, in buildings and

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) I cs 7,5 ka

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) I cs 7,5 ka DATASHEET - FAZ-C16/1 Miniature circuit breaker (MCB), 16A, 1p, C-Char, AC Part no. FAZ-C16/1 Catalog No. 278561 Eaton Catalog No. FAZ-C16/1 EL-Nummer 0001695154 (Norway) Similar to illustration Delivery

More information

Switching, protecting, starting and monitoring with the highly flexible modular system usa.siemens.com/controls

Switching, protecting, starting and monitoring with the highly flexible modular system usa.siemens.com/controls SIRIUS Modular System. The perfect combination Switching, protecting, starting and monitoring with the highly flexible modular system usa.siemens.com/controls Everything for the control cabinet: the SIRIUS

More information

SIRIUS modular system

SIRIUS modular system SIRIUS modular system Switching, protecting, starting and monitoring with the highly flexible modular system siemens.com/sirius Everything for the control cabinet: the SIRIUS modular system. Press shop

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

Entry Level Assessment Blueprint Electrical Occupations

Entry Level Assessment Blueprint Electrical Occupations Entry Level Assessment Blueprint Electrical Occupations Test Code: 3029 / Version: 01 Specific Competencies and Skills Tested in this Assessment: Safety Apply shop safety rules and ergonomics Explain fire

More information

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Medium Voltage Metal-Enclosed Harmonic Filter Systems 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Harmonic Filter Systems General NEPSI s armorvar, medium voltage metal-enclosed

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

MNS Platform, low voltage systems Rear Access Power Motor Control Center. Alberto Carini, Global Product Manager

MNS Platform, low voltage systems Rear Access Power Motor Control Center. Alberto Carini, Global Product Manager MNS Platform, low voltage systems Rear Access Power Motor Control Center Alberto Carini, Global Product Manager MNS Platform, low voltage systems Add Value to our customers Sales After sales Maximum safety;

More information

UL TEST REPORT AND PROCEDURE

UL TEST REPORT AND PROCEDURE Issue Date: 2012-02-09 Page 1 of 13 Report Reference # E116994-A76-UL UL TEST REPORT AND PROCEDURE Standard: ANSI/AAMI ES60601-1:2005, 3rd ed. (Medical Electrical Equipment - Part 1: General Requirements

More information

SIRIUS modular system

SIRIUS modular system SIRIUS modular system Switching, protecting, starting and monitoring with the highly flexible modular system siemens.com/sirius Everything for the control cabinet: the SIRIUS modular system. Press shop

More information

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2 BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC ET 200SP BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) Manual Preface Guide to the documentation 1 Product overview 2 BaseUnits for I/O modules 3 BaseUnits

More information

Siemens AG RA6 Fuseless Compact Starters. Catalog News LV 1 N April 2008 SIRIUS.

Siemens AG RA6 Fuseless Compact Starters. Catalog News LV 1 N April 2008 SIRIUS. 3RA Fuseless Compact Starters Catalog News LV 1 N April 2008 SIRIUS www.siemens.com/lowvoltage 3RA Fuseless Compact Starters General data Overview 3RA fuseless compact starters and infeed system for 3RA

More information

sirius Switching. Protecting. Starting. SIRIUS Product Overview

sirius Switching. Protecting. Starting. SIRIUS Product Overview sirius Switching. Protecting. Starting. SIRIUS Product Overview S00 Design Direct-on-line starting Reversing duty Assembly kit for busbar mounting 0 mm: RA9 -C 0 mm: RA9 -D Consisting of: wiring kit busbar

More information

Supplement to Instruction Manual

Supplement to Instruction Manual Supplement to Instruction Manual Compact Inverter 0 V series: FRN0001 to 00C2S-2 400 V series: FRN0002 to 0011C2S-4 Single-phase 0 V series: FRN0001 to 0012C2S-7 Thank you for purchasing our FRENIC-Mini

More information