Lighting & HVAC Control System
|
|
- Barrie Nash
- 6 years ago
- Views:
Transcription
1 ighting & HVAC Control System DOC# Controllers: AluxM1 AluxM4 AluxM5 Slave relays: AluxS1 AluxS2 AluxS3 AluxS4 Function: Switching off of lighting and HVAC units in un-occupied rooms or areas. Configuration: An AUX control system consists of a controller unit and up to 8 slave relays controlled or switched by the controller. The switching or control signal is low voltage and is done via a "daisy-chain" configuration connecting the slave relays to the controller. The controller receives input from one or more occupancy sensors and switches the slave relays according to its internal logic and customer specified settings. Movement or occupancy detection can be done utilizing occupancy sensors supplied by Deman or any other 3rd party 12 or 24V sensors. Slave relays available: inline unit plug-socket unit voltage free output unit high current unit. The inline and plug-socket slave relays switches power from overhead power ducts to light fittings while the voltage free output slave and high current slave relays are usually used for HVAC or other environmental control purposes. 01
2 Index Wiring example AluxM1 master AluxM4 mini master AluxM5 micro master AluxS1 inline slave AluxS2 high current slave AluxS3 HVAC slave AluxS4 plug/socket slave Product selection guide AluxM1 system example AluxM4 system example AluxM5 system example Related dokuments AUXQ20 Wiring examples 02
3 Wiring example E N M4 E N E N E N S1 S1 S1 E N E N E N (5) E N E N E N M4 Controller or master installed above ceiling. S1 Inline slave relay installed on or near light fitting. S3 HVAC slave relay installed on or near airconditioner, fan-coil unit or other HVAC unit. S3 c m o Occupancy sensor. ight fitting. Occupancy input on HVAC unit. Output from S3 is a change over voltage free contact. Signal cable from master to slave units. Telephone cable with RJ9 plugs on both ends. 12V switching signal. (5) 3core cable to occupancy sensor. 12V or 24V sensors can be utilized. N E air-con 03
4 AluxM1 master Design: delay time setting status indecation EDs output to slave relays (RJ9 sockets) plug in screw terminals Screw terminals: 12V out gnd sens in sens in light switch 12V / 24V DC supply GND Input 1 from sensor (voltage in) Input 2 from sensor (GND in) See wiring of Occupancy sensors Voltage free input from light switch. (closed = on) Bridge when not used. comms gnd ocal network connection HVAC out Voltage free NO output to HVAC controller. Maximum switching capacity: 48V 1Amp. Functioning: Input from occupancy sensor restarts internal timer. Slave relays are switched on when timer is running. Output to slave relays on side of unit. ight switch open causes slave relays to be switched off. Each M1 controller on a local net transmits its sensor input onto the net. All the M1 controllers on the net reacts to these inputs. At least one controller must have a sensor plugged in. Contact is closed when timer is running. Even with light switch open. Status indecation: power sensor lights 230V power to the unit is on. (green) Occupancy sensor input on. (yellow) 12V output to slave relays is on. Flashes if wiring to slave units shorted. (red) Delay time setting: By turning the timer "POT" with a screw driver the minimum on time period can be set from 0 to 32 minutes. Internal logic can lengthen this time if the need arises
5 AluxM1 master (continues) Output to slave relays: Two RJ9 sockets are available for wiring to the slave relays. (A maximum of 9 slave relays) Signal cable from master to slave units is a 4way telephone cable with RJ9 plugs on both ends. slave out slave out Switching signal to the slave relays is 12V. NOTE: The "daisy chain" wiring to the slave units must not loop back. Power in: 230V +- 15% 5VA Sensor supply: 12V or 24V 700mW max. Signal to slave relays: 9 relays max. HVAC out: Voltage free contact. Cotact rating 48V 1A. AluxM4 mini master Design: output to slave relays (RJ9 sockets) occupancy sensor plug status indecation EDs Functioning: Input from occupancy sensor restarts internal timer. Slave relays are switched on when timer is running. A self learning program adapts the timer setting to the environment. Power input:230v (+ 15% -15%) Switching capacity: 8 slave units. 5VA Sensor supply: 12 or 24V DC 700mW max. 05
6 AluxM4 mini master (continues) Occupancy sensor socket (See wiring of occupancy sensors.) Indication EDs power sensor 230V power to the unit is on. (green) Occupancy sensor input on. (yellow) lights 12V output to slave relays is on. Flashes if wiring to slave units shorted. (red) Output to slave relays. RJ9 sockets. Power cord with 5A plug. AluxM5 micro master Design: Power in N E Output to slave relays Power to light fitting N E Occupancy sensor plug Functioning: Input from occupancy sensor restarts internal timer. Slave relays are switched on when timer is running. Internal relay switches with slave relays. A self learning program adapts the timer setting to the occupancy environment. Power input:230v (+ 15% -15%) Switching capacity: 3 slave units. 3,5VA Sensor supply: 12V DC 700mW max. 06
7 AluxS1 inline slave relay screw terminals META BASE Design: RJ9 socket PASTIC CIP-ON COVER Wiring: N E slave in/out Power to light fitting. Non directional RJ9 socket for wiring to master and/or other slave units. Polarity insensitive. Switching : 230V AC 1A free hanging (2 off ECG each with 2x 85W lamps) 2A if fixed to a metal surface. AluxS2 high current slave relay Wiring: Power in Power to load N E N E RJ9 sockets for wiring to master and/or other slave units. Switching : 230V AC 15A 07
8 AluxS3 voltage free output slave relay META BASE RJ9 SOCKETS PASTIC CIP-ON COVER Slave wiring: Relay out NC COMM NO slave in/out RJ9 socket for wiring to master and/or other slave units. Polarity insensitive. Switching : 48V 1A max. AluxS4 plug socket slave relay Slave wiring: Socket side for 5A plug from light fitting Plug pins (5A configuration) to plug into lighting power duct RJ9 sockets for wiring to master and/or other slave units. Switching : 230V AC 3A 08
9 Product isting M1 AuxM1A21 Controller. 24V DC out to occupancy sensor M4 AuxM1A31 AuxM4A11 AuxM4A41 Controller. 12V DC out to occupancy sensor Mini Controller. 12V DC out to occupancy sensor Mini Controller. 24V DC out to occupancy sensor M5 AuxM5A10 Micro Controller 12V DC out to occupancy sensor S1 S2 S3 S4 AuxS1A11 AuxS2A10 AuxS3A10 AuxS4A20 Inline slave relay High current slave relay Voltage free output slave relay Plug-socket slave relay Cl-1806A10 Ceiling mount occupancy sensor 7m diameter sensing area H AuxH10 M1/M4 to slave relay & slave relay to slave relay 3m cable AuxH20 M1/M4 to slave relay & slave relay to slave relay 5m cable AuxH30 M1/M4 to slave relay & slave relay to slave relay 8m cable Aux2KH10 AuxS3 to HVAC controller 2m cable Aux3KH20 M1 to Suren sensor 2m cable Aux3KH30 M1 to Hubbel sensor 2m cable Aux3KH51 Aux3KH70 Aux3KH90 M4 to Suren sensor M4 to Hubbel sensor M4 to eviton sensor 2m cable 2m cable 2m cable 09
10 AluxM1 system example Controller with various slave relays 230V 5A plug duct M1 controller (6) SAVE UNITS (7) (8) S4A20 (9) (6) S1A11 S3A10 M1A12 OCA NET HVAC (5) HVAC I1 A10 IGHT FITTINGS IGHT SWITCH OCCUPANCY Voltage free output to air conditioning system (48V max.) Multi masters area network. External on/off switch (voltage free input). Power and signal connection to occupancy sensor. (12V or 24V sensors) (5) 230V power lead. (6) "Daisy chain" master to slave relays connecting cables (4 core telephone cables with RJ9 plugs) (12V system) (7) Inline slave relays. Switches 230V from power duct to light fittings. (8) Voltage free output slave relay. General purpose change over contact out. (48V max.) (9) Plug-socket slave relays. Switches 230V from power duct to light fittings. 10
11 AluxM4 system example Mini controller with plug-socket slave relays SAVE UNITS 230V 5A power duct 5A plug S4A20 M4 mini controller M4A10 I1 A10 OCCUPANCY SENSOR IGHT FITTINGS S2A10 (5) Power and signal connection to occupancy sensor (12V or 24V sensor) 230V power lead with 5A plug. Plugs into AluxS4A20 slave unit. "Daisy chain" master to slave relays connecting cables (4 core telephone cables with RJ9 plugs) (12V system) Plug-socket slave relays. Switches 220V to light fitting. (5) High current slave relay. AIR-CON. 11
12 AluxM5 system example Micro controller with plug-socket slave relays SAVE UNITS 230V 5A power duct S4A20 5A plug M5 micro controller M5A10 I1 A10 IGHT FITTINGS OCCUPANCY SENSOR S2A10 (5) Power and signal connection to occupancy sensor (12V or 24V sensor) 230V power lead with 5A plug. Plugs into AluxS4A20 slave unit. "Daisy chain" master to slave relays connecting cables (4 core telephone cables with RJ9 plugs) (12V system) Plug-socket slave relays. Switches 220V to light fitting. (5) High current slave relay. AIR-CON. 12
13 Deman Manufacturing (Pty)td 10 Steenbok street Koedoespoort 0186 Pretoria South Africa PO BOX Gezina 0031 Pretoria South Africa tel fax
Global Plasma Solutions. 10 Mall Terrace, Bldg C Savannah, GA (912) ph (877) fax
10 Mall Terrace, Bldg C Savannah, GA 31406 (912) 356-0115 ph (877) 270-5353 fax GPS-RN IOM MANUAL 10 Mall Terrace, Bldg C Savannah, GA 31406 (912) 356-0115 ph (912) 356-0114 fax GPS-RN RTU/AHU INSTALLATION
More informationTemperature Controller
2 728 Temperature Controller ultizone Floor Heating Systems RRV817 ultizone model with up to 7 zone outputs by combining 2 RRV817 controllers. Used for central control of underfloor heating systems in
More informationInstallation & Operation Guide
Installation & Operation Guide Direct Digital VAV Controllers KMD-7001/7051 - VAV Terminal Units KMD-7002/7052 - Dual Duct VAV Units KMD-7003/7053 - Fan Induction Units 907-019-01C 1 Introduction This
More informationDESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications
3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for
More informationEcoSystem to 0 10 V- Interface
to Interface to Interface 369537i 1 03.22.19 The to Interface provides a control gateway from an link to a compatible lighting device, typically an ED driver. It allows for individual addressing of the
More informationAbstractAVR. Ledbuddy controller. Ledbuddy Panel User Manual 2009 Abstract AVR and Sabre Technology Tel:
Ledbuddy Panel User Manual 2009 Abstract AVR and Sabre Technology Tel: 0116 278 8078 http://www.abstractavr.com AbstractAVR Ledbuddy controller Page 12 Introduction The LedBuddy is a simple yet powerful
More informationETM-2050/ETM-2051 Service Manual
Introduction Novar s Electronic Thermostat Modules (ETMs) are intelligent control modules that provide local, direct digital control of unitary, packaged, staged HVAC systems. This document: Describes
More informationOT EASY 60 II. LED control unit Operating instructions
II LED control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Intended use 4 Description... 5 Function and application 5 Function 5 Important definitions
More informationInstallation & Operation Guide
Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief
More informationTemperature controller Ducted systems
2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master
More informationTECHNICAL PRODUCT DATASHEET
FORM-ENG-0018 REV A 06-02-03 ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 SUITABLE FOR EXTERNAL DISTRIBUTION TECHNICAL PRODUCT DATASHEET ES-Key Climate Control Module P/N
More informationFieldbus System. New. New. Series EX260 IP67. Drives up to 32 solenoids. Daisy-chain wiring communication. Compact 28mm
Fieldbus System (Output device for driving port solenoid valves) Compact 8mm (Actual size) Space-saving Installation Daisy-chain wiring communication New IP67 For units with D-sub connector, and when connected
More informationINTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx
INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box
More informationM1000 INTELLIGENT ZONE CONTROL SYSTEM
HARDWARE GUIDE DIMENSIONS & SPECIFICATIONS REV. 5.2 M1000 INTELLIGENT ZONE CONTROL SYSTEM ROOFTOP CONTROLLER 2 Table of Contents GENERAL INFORMATION... 3 PL-M1000 Rooftop Controller...3 Description...3
More informationModel BB9 RS-232 Multi-Drop Box. Operating Bulletin. Innovative Flow and Pressure Solutions. Standard 8 pin Mini-DIN Connector
Operating Bulletin Standard 8 pin Mini-DIN Connector Model BB9 RS-232 Multi-Drop Box Innovative Flow and Pressure Solutions 6 pin Locking Industrial Connector 1 12/15/2011 Rev.1 DOC-BB9MAN-RS232 2 Alicat
More informationSensacell Troubleshooting Guide
A ONLY SOME MODULES LIGHT UP B PANEL DOES NOT LIGHT UP Only some modules light up Panel does not light up Check jumpers and power wiring AC Power present at Power Supply input terminals? Check AC Line
More informationInstallation & Operation and Maintenance
Gas Safety Products Dual Current Monitor Installation & Operation and Maintenance Read these instructions carefully before operating or servicing Rev: 01 Date: 12-02-18 1 CONTENTS Chapter Content Page
More informationStarzone 4000 Master Control Panel Figure 2.1 Master Control Panel
Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel The heart of the Starzone 4000 system is the Starzone Master controller (SZM-4000). Each AHU that is to be zoned will have its own SZM-4000
More informationRoom unit with PPS2 interface
1 642 Desigo RX Room unit with PPS2 interface for use with: QAX33.1 devices of the ranges Desigo RXC, RXB, RXL, and RXA (PPS2) Desigo PX Automation stations 1) devices with a PPS2 interface Room temperature
More informationPOWERHOUSE. -- the finest in Digital Command Control -- PRODUCT MANUAL FOR PB-110A TEN AMP POWER STATION
POWERHOUSE TM -- the finest in Digital Command Control -- PRODUCT MANUAL FOR PB-110A TEN AMP POWER STATION NCE Corporation 1260 CREEK STREET Suite 105 WEBSTER NEW YORK 14580 FAX : (716) 671-9337 E-mail:
More informationAS-Interface I/O Module
AS-Interface I/O Module Construction The AS-Interface I/O module is designed as a compact, robust field module. It is composed of an electronic module (top) and a coupler module (base). Connectors (standard
More informationADVANCED TECHNICAL MANUAL AAC1 SMALL SYSTEM CONTROL CONSOLE. Redefine your comfort zone.
ADVANCED TECHNICAL MANUAL AAC1 SMALL SYSTEM CONTROL CONSOLE ATM ACC1 Table of Contents Safety Precautions... 3 Overview... 4 Specifications... 4 Installation... 5 Control Console Operation... 9 2 Advanced
More information4 Channel DMX Driver Instruction Manual
LEDstuff.co.nz 4 Channel DMX Driver Instruction Manual Quality LED Lighting Products The LEDstuff 4 Channel DMX Driver is a flexible module that is an ideal addition to an existing home automation or lighting
More informationBA/BS4S Temperature Sensor Installation & Operating Instructions
Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.
More informationProduct Information Fan Powered Terminal Unit For under floor ventilation system Type FAT PI/FAT/M/1
TROX Malaysia Sdn. Bhd. (278360-V) 20, Persiaran Bunga Tanjong 1, Senawang Land Industrial Park, 70400 Seremban, Negeri Sembilan Darul Khusus, Malaysia Telephone : (+6) 06-6788188 Telefax : (+6) 06-6788
More informationAndover ContinuumTM Infinet II
Andover ContinuumTM Infinet II The i80 Series controllers are designed for control of Air Handling Units, Roof Top Units, and other mechanical plant equipment. Features 0 Choose the i80 model with the
More informationContent. Product Description
EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product
More informationAdvantys ETB. DATA SHEET Advantys ETB IP 67 Ethernet Digital I/O Modules. Description. Features
Advantys ETB DATA SHEET Advantys ETB IP 67 Ethernet Digital I/O Modules The Advantys ETB family of IP 67 digital I/O modules with direct connection to the Ethernet ( Modbus TCP/IP ) Communication Network.
More informationRTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM
RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V
More informationRXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13
s 3 875 RXB Room controller Communicating room controller for fan-coil applications FC-13 RXB39.1 The RXB39.1 room controller is used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil
More informationTAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta
TAC Xenta TAC Xenta 101-VF 3-Speed Fan Coil Controller TAC Xenta 101-VF is a zone controller intended primarily for fan coil applications with the ability to control fans with multiple speeds, with one
More informationapplication sheet RAKO CONTROLS WIRED RAK OVERVIEW
WDA-600 application sheet Introduction When installing a wired system dimmers are typically housed in RAK boxes with either 8 modular cards (RAK8) or 4 fixed type controls (RAK4). These are typically mounted
More informationActive Distributors ASi Safety, IP67
x connectors for profile cable Periphery connection via M8 cable sockets M cable sockets (Figure similar) Figure Type Inputs, SIL 3, Cat. 4 9 mm 9 mm 9 mm 9 mm channels channels channels channels Inputs
More informationLRA1750, LRM1763, LCC172x Datasheet OccuSwitch Wireless System
1/8 RM1763 Occuswitch Wireless sensor 8.1 mm 25 mm 56.4 mm General description The OccuSwitch Wireless family exists of a wireless sensor and an actuator (relay-box). Savings of up to 30% can be achieved
More informationNon-communicating room controllers
3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,
More informationFiber optic converter audio and CAN TA OPERATION MANUAL
Fiber optic converter audio and CAN TA-110.1 IOA110-1 March 2009 LANEX S.A., Technical support: tel. ul.ceramiczna 8, 20-150 Lublin tel. +48 81 443 96 36 Contents 1. General Characteristics.... 5 1.1.
More informationOperating instructions ClassicLine module AC5204 / AC5209 / AC5212 AC5235 / AC5236 / AC5237 AC /00 07/2017
Operating instructions ClassicLine module AC5204 / AC5209 / AC5212 AC5235 / AC5236 / AC5237 AC5274 7390889/00 07/2017 Contents 1 Functions and features...3 2 Operating and display elements...3 3 Installation...4
More informationSK Installation Instructions
Guestroom HVAC Energy Management System SK200-001 Installation Instructions GENERAL SYSTEM COMPONENTS INTRODUCTION The S200 series hospitality HVAC Energy Management (HEM) System is specially designed
More informationTracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005
Tracer Controls Tracer MP501 Controller January 2005 BAS-PRC008-EN Introduction The Tracer MP501 controller is a configurable, multi-purpose controller used to provide direct-digital control for heating,
More informationADC7520 SERIES. 1600W Battery Chargers and Power Supplies
ADC7520 SERIES 1600W Battery Chargers and Power Supplies Wide output adjustment range 0 72VDC Analog control by external 0-5VDC voltage Temp.comp charging, sense as on option Power fail relay alarm Master-Slave
More informationBasic principles PL. Sending units
asic principles P P technology P (Plusink) is a system for controlling light. The system is based on a conventional electrical installation. ommands are sent via P, and there is no need for either software
More informationInstallation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T
Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION LOCATION The I/CO 2 transmitter is designed to mount over a standard single
More information2M Outdoor Motorized Bullet Camera
2M Outdoor Motorized Bullet Camera 8608586000010 Quick Installation Guide Please follow the installation steps below to set up your 2MP Bullet IP Camera. Check the package contents against the list below.
More informationFitting Ah-ha to a machine using Gecko Stepper drives
Fitting Ah-ha to a machine using Gecko Stepper drives Please note these instructions are for guidance. If you have any doubt on any particular point please check with us. If you have any difficulties in
More informationCTI CALL INFORMATION INTERFACE
CTI CALL INFORMATION INTERFACE MODEL CN-4750 SERIAL/ITEM 533/nnn OPERATOR MANUAL Issue 3, FEB, 2002 AUTHOR: PETER ZEUG PATENTS PENDING DESIGNED AND MANUFACTURED IN AUSTRALIA DESIGN TWO THOUSAND PTY LTD
More informationIQ-MP Gateway. Version apr Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel :
IQ-MP Gateway Version 4.009 28. apr. 2011 Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel : +45 8880 7580 www.electrocom.dk p. 2 Description The IQ-MP Gateway is a communications module, which
More informationSS-22 USER MANUAL. Revision 01 Original document 04 May 2006 Revision 02 Cosmetic changes 23 January 2008 CONTENTS
SS-22 User Manual Revision History Revision 01 Original document 04 May 2006 Revision 02 Cosmetic changes 23 January 2008 CONTENTS 1. INTRODUCTION... 3 2. FEATURES... 3 3. DESCRIPTION... 3 4. CONNECTIONS...
More informationConductive Sensors 2 to 4-point level controller Type CL with teach-in
Conductive Sensors to 4-point level controller Type CL with teach-in Conductive level controller Teach-in of sensitivity operating resistance from 0Ω to 0KΩ Multiple combinations of filling and emptying
More informationSmall distributed I/O module
MLIO Summary Application Function Small distributed I/O module Small I/O module MLIO is a microprocessor-controlled, communiccative module for installation outside the control panel. It is used for topologies
More informationTime Counters mini "h", DC Version
Type 633-DC Time Counters mini "h", DC Version Type 633.0 Type 633.7 Type 633.8 High shock resistance Miniature dimensions Electrical connections in standard grid Suitable for PCB mounting Machine-solderable
More informationthe Interactive Catalog
Interactive Catalog Supplements Catalog PDFs If you need detailed product information, or help choosing the right product for your application, see our Interactive Catalog Use the Interactive Catalog to
More informationCS-1 Active Full Range Integrated Commercial Audiovisual System
Active Full Range Integrated Commercial Audiovisual System User Manual SAFETY INSTRUCTIONS PLEASE READ THROUGH THIS MANUAL FIRST BEFORE OPERATING THE CS-1 SYSTEM. Thank you for purchasing this Beta3 product
More informationIP7-MZC Multi Zone Controller ZX4L Zone Expansion. Hardware Installation Manual
IP7-MZC Multi Zone Controller ZX4L Zone Expansion Hardware Installation Manual IP7-MZC ZX4L This page left blank Table of Contents IP7-MZC Zone Controller System... 1 Overview... 1 Technical Specifications...
More informationRoom Temperature Controller
3 023 Room Temperature Controller for four-pipe fan coil units RCC30 Outputs for on / off valve actuators Outputs for three-speed fan Control depending on room or return air temperature Operating modes:
More informationCoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide
CoolPlug CooLinkHub HVAC Bridge Quick Installation Guide Warning Read and understand the following Safety Guidelines and Warnings to ensure a safe installation Failure to follow WARNING may result in
More informationManual Control Unit GFC 32
Manual Control Unit 1400004_EN/05.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 6 7. Remote control
More informationCounting ramp SP User s manual.
Counting ramp SP2-143 User s manual www.schick-sa.com Table of content 1 Introduction 3 2 LED colours definitions 3 2.1 Normal operating mode 3 3 Installation 3 3.1 Fitting 3 3.2 Connections 3 3.3 Limit
More informationJNIOR Series 4. A Network I/O Resource Utilizing the JAVA Platform. JNIOR Series 4 with 4 Relay Output Expansion Module. Version 5.
JNIOR Series 4 A Network I/O Resource Utilizing the JAVA Platform JNIOR Series 4 with 4 Relay Output Expansion Module Version 5.0 NOTE: JNIOR JANOS 1.7 or greater required INTEG Process Group, Inc. 2919
More informationDLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.
DLA DMX512 Analyzer DLA DLA-HH 1 Table Of Contents IMPORTANT SAFEGUARDS... 2 DLA OVERVIEW... 3 CONNECTION... 3 OPERATION... 3 HARDWARE SETUP... 4 DLA-HH (PORTABLE) LAYOUT... 4 CHASSIS LAYOUT... 4 DLA MENU
More informationQuick Installation Guide MAC1000/MAC1000SR STANDALONE BIOMETRIC CONTROLLER
MAC1000/MAC1000SR STANDALONE BIOMETRIC CONTROLLER Table of contents 1 PRODUCT INTRODUCTION... 2 1.1 NAME AND FUNCTION OF EACH PART... 2 1.2 CABLE COLOR TABLE... 4 1.3 CABLE SELECTION... 6 2 IDENTIFYING
More informationVARAN-INTERFACE VAC 012
VARAN-INTERFACE VAC 012 This VARAN interface module is used for communication between a DIAS drive and a control over the VARAN bus. The VAC 012 is built into the DIAS-Drive and is also equipped with interface
More informationDUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS
LD220 DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS USER MANUAL P.O.Box 24 STANFIELD 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com 18/08/2005
More informationUSR-TCP Hard version: V2.0 File version: V
Serial Device Server - RS232/RS485 to Ethernet converter USR-TCP232-300 Hard version: V2.0 File version: V1.1 2011-8-17 Serial Device Server - RS232/RS485 to Ethernet converter is an Equipment for convert
More informationService Section. December 2003
Service Section December 2003 Network Interface Module (NIM) Family Transceiver Boards NIM NIM PC Ver 2 S-NIM G-WAY NIM TELE Transceiver Boards (TX Boards) Extend the communication distance between the
More informationPA2000 SERIES. USER MANUAL Rev. P CELL PHONE ENTRY SYSTEM. Platinum Access Systems Inc.
PA2000 SERIES CELL PHONE ENTRY SYSTEM USER MANUAL Rev. P Platinum Access Systems Inc. PRODUCT LINE PA2020 --- Cell Phone Entry System PA2022 --- Cell Phone Entry System (Flush Mount) PA2120 --- Cell Phone
More informationNon-communicating room controllers
3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For
More informationEncoder signal/ Sensor signal. Number of monitored axes. sine/cosine, SSI, TTL (1) up to 2 independent axes. sine/cosine. up to 2 independent axes
w AS-i Speed Monitor for sine/cosine encoder for HTL encoder for SSI encoder for TTL encoder for sensors for 2 fast electronic safe outputs 128 devices Supplied out of AS-i and external 24 V (figure similar)
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationRTD-NET Installation Instructions
LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND
More informationAS-i / IO-Link Module, IO-Link Master with 4 IO-Link Ports
/ IO-Link Module, /IO-Link Module, IO-Link Master with 4 s fourfold IO-Link Master in one housing Power supply of s (or ) (Figure similar) Figure Type Inputs digital 4 x + 4 x + 4 x Outputs digital M12
More information16-Way Input 48-Way Output Card
16-Way Input 48-Way Output Card Features 16 Configurable Inputs Push Button, Switch Input Fast Input Response 48 Configurable Outputs OFF, ON, 0.5S ON / 0.5S OFF, 1S ON / 1S OFF Configurable Buzzer OFF,
More informationQuick Draw Electronics. Shooting Sports Timer User Manual. Model AIO-1
Quick Draw Electronics Shooting Sports Timer User Manual Model AIO-1 Rev. C October 2017 QUICKDRAW ELECTRONICS SHOOTING SPORT TIMER SYSTEM THE SYSTEM CONSISTS OF; 1 IMPACT SENSOR 1 LIGHT ASSEMBLY 1 ALL
More informationDC3IOB Revision User Guide Updated 3/29/10. Overview
Revision 080910 User Guide Updated 3/29/10 Overview The is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The integrated PLC
More informationMegaPoints Controllers Feedback Module.
MegaPoints Controllers Feedback Module. 24 channel feedback module for version 2 MultiPanel Processors. User guide Features include No soldering truly plug and play Various sensor types o DCC and analogue
More informationInstallation & Operation Guide
& Operation Guide KMD-7301/7301C Direct Digital Controller For Air Handling Applications 880-019-02C KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Introduction This section provides
More informationConductive Sensors 2 to 4-point level controller Type CL with teach-in
Conductive Sensors to -point level controller Type CL with teach-in Conductive level controller Teach-in of sensitivity operating resistance from 0Ω to 0KΩ Multiple combinations of filling and emptying
More informationPC170 Control Box USER MANUAL 24V DC GEAR MOTOR FOR RESIDENTIAL
PC170 Control Box 24V DC GEAR MOTOR FOR RESIDENTIAL USER MANUAL INDEX 1. CONTROL BOX 2. SETTING 2.1 SW1 DIP SWITCH SETTING 2.1.1 SLOWDOWN ADJUSTMENT (DIP 1. SLOW) 2.1.2 OVER-CURRENT ADJUSTMENT (DIP 2.OVER
More informationT7560A1036 Digital Wall Module
T7560A1036 Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. T7560A1036
More information75F Smart VAV with Reheat
A unique system-wide approach to maximizing performance PRODUCT OVERVIEW The wireless control solution reduces install cost, improves energy efficiency, and introduces remote control and diagnostic capabilities
More informationProduct Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012
Product Catalog Tracer Controller MP501 May 2012 BAS-PRC008-EN Copyright 2012 Trane. All rights reserved. This document and the information in it are the property of Trane and may not be used or reproduced
More informationTEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company
TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display HTC 5 Features Australian Made and designed Power can be either 24V or 240V AC 10 Amp (Resistive) Potential free relay contacts
More informationTelephone Line Monitor USER GUIDE
Telephone Line Monitor USER GUIDE For Technical Assistance call the Manufacturers direct Ph 800 530 8645 8AM - 5PM West Coast Pacific Time NATCOMM USA LLC Responsible Supplier Code NC OPERATION Our Telephone
More informationST Series - Part Numbering
- Part Numbering Features Super-miniature size with multiple contact Safe insert system preventing pin damage Applications Professional A/V Measuring equipment Sensors Wireless radio Medical Part Numbering
More informationRoom unit with PPS2 interface
1 641 DESIGO RX Room unit with PPS2 interface for use with: QAX321 devices of the ranges DESIGO RXC, RXB, and RXA (PPS2) DESIGO PX Automation stations 1) devices with a PPS2 interface Room temperature
More informationclarity 3 Programmable Controller
clarity 3 Programmable Controller BACnet General Purpose Controllers (B-AAC) DESCRIPTION Taco Clarity 3 FPC series controllers are designed to control building systems and HVAC equipment. The integrated
More informationQAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC
1 648 Desigo RXC Flexible room unit for integrated operation of HVAC, lighting and blinds in individual rooms; with LONMARK -compatible bus communication QAX50.1 QAX50.5 QAX51.1 QAX51.5 Room temperature
More informationPOWERHOUSE. -- the finest in Digital Command Control -- PRODUCT MANUAL FOR PB-205a DUAL 5AMP POWER STATION
POWERHOUSE TM -- the finest in Digital Command Control -- PRODUCT MANUAL FOR PB-205a DUAL 5AMP POWER STATION NCE Corporation 1260 CREEK STREET SUITE 100 WEBSTER NEW YORK 14580 FAX : (716) 671-9337 E-mail:
More informationCONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE
Catalogue 207 CONTENTS CONTROLLERS... 4 room controllers... 5 room units... 29 control units... 24 PRODUAL 3 CATALOGUE T U R KU I C T C ON T R OL L E R S Multifunctional controllers for optimal performance
More informationFCU-4 FAN COIL CONTROLLER
FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced
More informationManual Simatek Control Unit GFC 32
Manual Simatek Control Unit GFC 32 Original instructions 1400004_GB Ver. 2014.01.09 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections
More informationGUARD CENTURION OPERATING INSTRUCTIONS THE AUTOMATIC CHOICE
GUARD CENTURION THE AUTOMATIC CHOICE OPERATING INSTRUCTIONS 0 In a In hurry? a hurry? The following KwikLearn procedure and connection diagram will enable you to start using your SmartGUARD system right
More informationSirius Light Source Range
Light Source User Guide Sirius Light Source Range Models covered by this manual: UFOSIRCW UFOSIRCW-C UFOSIRCW-T UFOSIRCW-Cs UFOSIRCW-Ts UFOSIRSW UFOSIRSW-C UFOSIRSW-T UFOSIRSW-Cs UFOSIRSW-Cs UFOSIRNW UFOSIRNW-C
More informationC5S120 Installation and Connection Guide
C5S120 Installation and Connection Guide Version: V1.1 1. Cautions Please note the following cautions. Mis-operation may lead to personal injury or equipment failure: 1) Do not energize the system before
More informationDFM44E Series. Installation Instructions. System Requirements: Win 95b/98/Me/2000/XP Resolution: 1024 x MB RAM
DFM44E Series Installation Instructions Copyright 2003. Maxitrol Company. All Rights Reserved. System Requirements: Win 95b/98/Me/2000/XP Resolution: 1024 x 768 32MB RAM Read Before Installation DFME Amplifier
More informationDefining the Future in Motion Control
Defining the Future in Motion Control USER S MANUAL 1 DINIO7 user s manual Overview The DINIO7 is a DIN-rail mounted peripheral for the SmartMotor versions 3 and 4 product lines Hereafter, the SmartMotor
More informationRangerBOSS Network Ready Constant Monitor Model CM2800
RangerBOSS Network Ready Constant Monitor Model CM2800 Instruction Manual Contents 1 Description CM2800 1 Features 1 2 Installation Installation Instructions 2 Installation Diagram 3 3 Operation Wrist
More informationCT1 Series 2. General Purpose Timer. Installation Manual 1 st Edition
CT1 Series 2 General Purpose Timer Installation Manual 1 st Edition FEATURES 4 Timing Ranges: - 1 to 127 seconds in 1 second increments. - 10 seconds to 21 minutes in 10 second increments. - 1 to 127 minutes
More informationPTC Model III. Programmable Turntable Controller. Automatic Power Router. Installation Instructions
PTC Model III Programmable Turntable Controller A Automatic Power Router Installation Instructions New York Railway Supply 13225 Thornton Dr Westlake, TX 76262 (817) 233-5068 http://www.nyrs.com NYRS Inc2010,
More informationDigital Keypad Introduction
K2 Digital Keypad Introduction The K02 uses the latest microprocessor technology to operate door strikes and security systems that require a momentary (timed) or latching dry contact closure. All programming
More informationPI84 with socket GZM80 interface relays
RM84 + GZM80 Contact data Number and type of contacts Contact material Rated / max. switching voltage Min. switching voltage Rated load (capacity) Min. switching current Max. inrush current Rated current
More information