FRICK QUANTUM HD UNITY SYSTEM CONTROLLER

Size: px
Start display at page:

Download "FRICK QUANTUM HD UNITY SYSTEM CONTROLLER"

Transcription

1 Form O (AUG 2015) OPERATION File: SERVICE MANUAL - Section 90 Replaces: NOTHING Dist: 3, 3a, 3b, 3c OPERATION FRICK QUANTUM HD UNITY SYSTEM CONTROLLER ENGINE ROOM CONDENSER VESSEL EVAPORATOR Version CURRENT DESIGN AUGUST 2015 Please check for the latest version of this publication.

2 O (AUG 2015) Page 2 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION SECTION 1 - QUANTUM HD UNITY SYSTEM CONTROLLER SETUP DESCRIPTION... 4 WIRING... 4 CONFIGURATION... 4 OPERATION... 4 TYPICAL SYSTEM... 4 QUANTUM HD UNITY SYSTEM CONTROLLER... 4 EVAPORATOR REMOTE I/O PANEL... 4 TYPICAL SYSTEM CONFIGURATION... 4 SYSTEM INSTALLATION... 5 WIRING FOR AC POWER... 5 QUANTUM HD UNITY SYSTEM CONTROLLER... 5 REMOTE EVAPORATOR I/O PANELS... 5 CHECKING THE AC POWER... 5 QUANTUM HD UNITY SYSTEM CONTROLLER... 5 REMOTE EVAPORATOR I/O PANELS... 5 WIRING FOR COMMUNICATIONS... 6 QUANTUM HD UNITY SYSTEM CONTROLLER... 6 REMOTE EVAPORATOR I/O PANELS... 6 SECTION 2 - STARTUP AND CONFIGURATION INITIAL STARTUP AND LOGIN... 8 SYSTEM CONFIGURATION... 8 SECURITY SYS CONFIG. > SECURITY... 9 PANEL SYSTEM CONFIG. > PANEL SECTION 3 - ENGINE ROOM CONTROL INTRODUCTION...12 MAIN MENU & NAVIGATION...12 EVENTS:...13 TRENDING:...13 Trending Sub-menus...13 ABOUT: STATUS: ALARMS: CALIBRATION:...15 Calibration Sub-menus...15 CONFIGURATION: Configuration Sub-menus Analog Refrigerant Detection Digital Refrigerant Detection SERVICE: CLEAN SCREEN: ENGINE ROOM ALARMS TABLE OF CONTENTS SECTION 4 - CONDENSER CONTROL INTRODUCTION...22 MAIN MENU & NAVIGATION...22 EVENTS: TRENDING: Trending Sub-menus ABOUT: STATUS: ALARMS: CALIBRATION: Calibration Sub-menus CONFIGURATION: Configuration Sub-menus Condenser Controller Setpoints SERVICE: CLEAN SCREEN: CONDENSER ALARMS...29 SECTION 5 - VESSEL CONTROL INTRODUCTION...32 MAIN MENU & NAVIGATION...32 EVENTS: TRENDING: Trending Sub-menus ABOUT: STATUS: ALARMS: CALIBRATION: Calibration Sub-menus CONFIGURATION: Configuration Sub-menus SERVICE: CLEAN SCREEN: VESSEL ALARMS...39 SECTION 6 - EVAPORATOR CONTROL INTRODUCTION...42 MAIN MENU & NAVIGATION...42 EVENTS: TRENDING: Trending Sub-menus ABOUT: STATUS: ALARMS: CALIBRATION: Calibration Sub-menus CONFIGURATION: Configuration Sub-menus Digital Auxiliaries Analog Auxiliaries Communications Proportional Integral Control SERVICE: CLEAN SCREEN:...51 EVAPORATOR ALARMS...51

3 SECTION 1 - Quantum HD Unity System Controller ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION O (AUG 2015) Page 3 SECTION 1 INTRODUCTION TO THE QUANTUM HD UNITY SYSTEM CONTROLLER

4 O (AUG 2015) Page 4 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION Setup Description The following Setup Guide is meant to assist the installation technician in making all necessary electrical power, control and communications connections to a Quantum HD Unity system. This guide also provides the basic information necessary to login and configure the system, and will aid in troubleshooting the system should problems arise. This Guide will help to ensure: Wiring Location of incoming AC source power to all panels, main controller and Remote I/O Panels Basic installation guidelines are followed. Location, polarity & grounding of communications wiring. Location of all control (I/O) wiring. Proper powering up of all panels. Configuration Logging into the system Verifying communications. Configuring Zones Calibrating sensors. Setting up operating Setpoints. Operation Setting the operating Mode. Verifying the data being returned to the Interface panel from all remote panels. (Zones) Checking and clearing of alarms. Ammonia Configuration Typical System A system will typically include one Quantum HD Unity System Controller to control the engine room, condensers, vessels and evaporators along with remote I/O panels for the evaporators. The I/O for the engine room, condensers and vessels is contained in the Quantum HD Unity System Controller enclosure. Evaporator Remote I/O Panel One remote Evaporator I/O panel can control up to 3 zones or valve stations. Each system may have one or more Engine Room, Vessel, Evaporator or Condenser remote I/O panels. The Evaporator Remote I/O panel (below) does not have a display. Typical System Configuration The typical Quantum HD Unity System Controller consists of one centrally located control and I/O panel that contains the controllers for condenser, vessel, engine room and evaporator control. This panel also contains the digital and analog I/O for condenser, vessel and engine room control. The evaporator I/O is located in smaller remote I/O panels that can be mounted wherever it is convenient for installation and maintenance. Up to 10 remote evaporator I/O panels (30 zones) are controlled by one evaporator controller. Quantum HD Unity System Controller

5 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION O (AUG 2015) Page 5 System Installation Follow these basic installation rules: Maximum total serial communications cable distance between the main unit controller and the very last Remote Evaporator I/O Panel on any one communications cable run is 2000 feet. It is possible to have two separate communications cable runs depending upon the total number of Remote I/O Panels. Keep in mind, however, that neither of these cable runs can exceed 2000 feet in length. Keep all communications wiring in a separate conduit from control or power wiring. When wiring for serial communications, it is important to ground only one end of the communications cable. This ground will be located in the very last Remote Panel of each communications cable run. Ground loops could develop if the communications were to be grounded at both ends, impairing communications between panels. The Main Unity controller panel is rated NEMA Type-12. This needs to be considered when selecting a location to install the main Quantum HD Unity System Controller enclosure. Remote I/O Panels are rated for both indoor and outdoor use. Although the need to access Remote Panels will be rare after installation and setup, it is still advantageous to keep them accessible for potential maintenance situations (reasonable lighting, sufficient door swing, etc.). Install all panels within a convenient distance of a power source. Wiring For AC Power Quantum HD Unity System Controller The incoming AC power will consist of 3 #10 AWG wires (Hot Neutral and Ground that are fed from a 20 Amp service minimum. Connect the three incoming AC wires to the terminal screws as shown on the drawings for the Main Quantum HD Unity System Controller enclosure. Proceed to the section entitled Checking the AC Power. Remote Evaporator I/O Panels The incoming AC power will consist of three 12 AWG wires (hot neutral and ground) from a 15 amp service (minimum). Unlatch the two ¼ turn cover latches to the Interface panel, and open the door. Inside the enclosure, there is a long DIN rail at the right side of the panel. At the top of the DIN rail is a terminal strip. Connect the three incoming AC wires to the terminal screws per the remote evaporator I/O panel drawing. Notice that there are multiple number 2 terminals, connection may be made to any of them. Checking The AC Power Quantum HD Unity System Controller Ensure the Control Power switch is in the OFF position. Energize the 120 Volt circuit at its source. Using a DVM, measure the voltage at the AC power terminal strip. Ensure that you read approximately 120 VAC between Hot and Neutral, and Hot and Ground. There must not be voltage between Neutral and Ground. Once the incoming voltage has been verified, turn the Control Power switch to ON. Watch the Quantum HD Unity controller circuitry on the backside of the door. You should notice various LEDs blinking or flashing. Watch the display on the front of the door. After a short period of time, you should notice the display showing a boot sequence. Various text messages will be shown as it proceeds with the boot-up process. When finished, a screen similar to the following image should be visible: If the panel has reached the point of showing the previous screen, the boot process was successful. Turn OFF the Control Power switch, and de-energize the 120 Volt circuit at its source. If the panel does not reach to the point of showing the above screen, then troubleshooting will be required. Refer to end of this guide entitled Troubleshooting. Remote Evaporator I/O Panels The remote evaporator I/O panel can come with optional HOA switches that can be used to manually energize evaporator zone components. These are easily added in the field after startup if determined to be necessary.

6 O (AUG 2015) Page 6 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION Wiring For Communications Red, power OFF tab Black, power ON plunger Notice in the above pictorial, there is a Red power OFF tab, and a black power ON plunger. These items are located on a circuit breaker for each of the two HOA modules. Push each of the Red power OFF tabs down. The Black power ON plunger should pop up. If the plunger does not pop up, then the power was already off. Do this to both HOA modules. Energize the 120 Volt circuit by switching on the control power switch on the right side of the enclosure. Using a DVM, measure the voltage at the AC power terminals (1, 2 and PE). Ensure that you read approximately 120 VAC between Hot and Neutral, and Hot and Ground. There must not be voltage between Neutral and Ground. Above the optional HOA modules are the I/O boards. There will be at least one Digital board (recognizable by the plug-in I/O modules), and one Analog board. Inspect all boards for the presence of flashing, blinking or steadily lit LED s. If LED s are lit on all boards, then power has been properly applied. If LED s are not lit on all boards, then refer to the section entitled Troubleshooting. Quantum HD Unity System Controller All serial communications between the condenser, vessel and engine room control are factory wired and tested. Verify that the Rx/TX lights for all analog and digital boards for condenser, vessel and engine room control are flashing. Remote Evaporator I/O Panels Use the following wiring procedure: Open the Quantum HD Unity controller door. At the bottom left there is a DIN rail with several terminals for the Condenser, Vessel, Engine Room and Evaporator serial communications. The Condenser, Vessel and engine Room comms are already are factory wired. The terminals are marked by product. The Evaporator terminals are marked as E -R/T 3 and E +R/T 3 for the first 5 remote I/O panels, and E -R/T 4 and E +R/T 4 for the second set of 5 remote I/O panels. Follow the wiring diagrams for both the Evaporator I/O panels and the Quantum HD Unity System Controller/ Evaporator Control to properly wire the serial communications observing the grounding points, wire sizes and general serial communications daisy chaining practices Refer to the CONDENSER/VESSEL SYSTEM COMMUNICA- TIONS WIRING DIAGRAM to verify dipswitch settings.

7 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION O (AUG 2015) Page 7 SECTION 2 - STARTUP AND CONFIGURATION

8 O (AUG 2015) Page 8 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION Initial Startup And Login The touch-screen was calibrated at the factory but this calibration may be compromised during shipment. During the booting process the touch-screen calibration page will occur with a 5 second timer as shown here. Touch anywhere on the screen before the timer times out to initiate the touch-screen calibration process. System Configuration System configuration requires the user to be logged in at the service user level. Once logged in the system configuration must be completed before moving to the individual control configuration for Engine Room, Condenser, Vessel and Evaporator. Once calibration has been initiated this animated symbol below will appear in the top left corner of the screen. System Networking - If all segments of the control (dependent on which segments were ordered) are listed and shown on the System Overview page (shown above) no action needs taken on the System Networking page. If a segment of control does not appear on the System Overview page, or a segment is being added after delivery, select Sys Config. > System Networking (shown below). Touch this symbol and follow it through all 16 points of the screen calibration. Once the touch-screen calibration is complete, the boot process will continue to the System Overview Screen shown below. This screen will list the areas of control provided by this system that may include Engine Room, Condenser, Vessel and Evaporator control. System Networking has several pages. The landing page for System Networking is the List page (below) which will list each control section that is currently networked and communicating. Controls sections can be edited on this page with regard to product category, IP address, port and URL. Control sections can also be deleted from the network on this page. As indicated on the previous image a login is required to interact with the controller. The factory default logins are as follows; Basic User 1 Operator User 2 Service User 3

9 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION O (AUG 2015) Page 9 Security Sys Config. > Security There must always be at least one user for each user level - Basic, Operator and Service. To add, edit or delete a user touch the corresponding button for that action. To Add or Edit User, select that action and fill in or edit the appropriate fields. To delete a user select the Delete User button that corresponds with the user being deleted. Respond to the question Are you sure you want to delete this user accordingly. A Scan Network button is available on this page as a quick means to adding control sections that may be added after initial startup. Other pages within System Networking are Network and Add. The Network page is where a network s Gateway Address and Subnet Mask settings can be entered. There is also an Auto Detect button that can be used to identify these values if connected to a network. Be sure to press the Save button to save any changes made on this page before exiting. The Add page is where control sections such as Condenser, Vessel, Engine Room and Evaporator can be manually added. Once on the Add page 1. Fill in the information for the user being added. Address, Mobile Phone Number and Mobile Carrier are not required. 2. Select a level of access for that user 3. Enter a PIN number for that user (typically 1-6 characters) 4. Save changes before leaving this page To add a control section on the Add page: 1. Select the control section from the drop down box. 2. If Condenser/Vessel select Condenser, Vessel or Both 3. Enter the IP Address 4. Enter the Port number (a common port configuration is 80). 5. Enter a website URL if a website will be used to connect to the Quantum HD Unity controller 6. Be sure to save any changes that were made before leaving this page.

10 O (AUG 2015) Page 10 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION Panel System Config. > Panel The Panel configuration page is where the basic panel configuration with regard to date, time, language, temperature and pressure units are configured. There are 4 drop down selection boxes on this page and are described below. Other parameters are setpoints that are defined by ranges. When changing any of the date and time configuration the Submit Changes button must be selected for the changes to be in effect. Date Format mm/dd/yyyy, dd/mm/yyyy Language English Pressure Units KPaA, Bar, BarA, PSIA, PSIG Clean Screen Mode Timeout Establishes the amount of time that the touch-screen is locked out when Clean Screen is selected from any menu page. At the end of any session be sure to Logout from any Menu page before leaving. An Auto-Logout will occur after 5 minutes of inactivity.

11 ENGINE ROOM OPERATION O (AUG 2015) Page 11 SECTION 3 - ENGINE ROOM CONTROL

12 O (AUG 2015) Page 12 ENGINE ROOM OPERATION Introduction Engine Room Control provides monitoring and control for the following: Refrigerant Detection Monitors up to 4 refrigerant sensors and provides the appropriate level of notification and response based on the level reading. Engine Room Ventilation Up to four output to control ventilation based on temperature or refrigerant level in the space. Floor Warming Pumped glycol or electric heat control for floor warming. Additional digital and analog auxiliaries along with proportional and integral control loops can be configured to control other ancillary items as necessary. Select Engine Room control by touching anywhere in the Engine Room control block on the System Overview page or selecting from the drop down if on another control page such as Evaporator. The Engine Room home page illustrates all the pertinent operating data on the left side of the page and operational status and interactive control buttons on the right. A System Operating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the system. The System Operating Values data is configured by touching the Select Data button shown in the next graphic. From the user defined page select the additional items to be displayed on the Engine Room home page and select Save Changes. Main Menu & Navigation Home Returns the user to the Engine Room home page Alarms Displays current and historical alarms as well as freeze data for each alarm Calibration Calibration for all enabled analog inputs Configuration Configuration for all operational feature such as refrigerant detection, ventilation and floor warming About Displays all software information for the processor, interface, analog and digital boards Status Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ethernet I/P Service Diagnostics, software maintenance, security, download system data Logout Logs out user when session is complete

13 ENGINE ROOM OPERATION O (AUG 2015) Page 13 EVENTS: The Events page displays recorded events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen. TRENDING: The Trending page displays historical data and provides a means to Select Data To Trend, the read Interval and Download Trending Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data. Trending Sub-menus Select Data To Trend - Select Data to be trended from the list shown when the Select Data To Trend button is pushed. Interval - Change the read interval by touching the Interval setpoint box, select the desired value using the on-page keypad and press Enter. is detected touch the Download Trending Data button on the trending page. Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

14 O (AUG 2015) Page 14 ENGINE ROOM OPERATION ABOUT: The About page lists the software and firmware version for the processor, interface, analog and digital boards. It also lists the Sales Order and Item numbers. STATUS: The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P. ALARMS: The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button.

15 ENGINE ROOM OPERATION O (AUG 2015) Page 15 CALIBRATION: The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog outputs. Calibration Sub-menus Calibration Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accordingly. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (ma) signal. To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page. Select the Analog Board and Channel for the output to be calibrated. Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be calibrated. Set the calibrated meter to read DC ma Select Calibrate Low End and use the + and value buttons of various change values to calibrate to the desired value of 0 or 4 ma. Select Calibrate High End and use the + and buttons of various change values to calibrate the high end to 20 ma.

16 O (AUG 2015) Page 16 ENGINE ROOM OPERATION CONFIGURATION: The Configuration page/menu is used to access main areas of configuration such as Refrigerant Detection, Ventilation, Floor Warming Digital and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O. Configuration Sub-menus Configuration for Refrigerant Detection, Ventilation, Floor Warming, Digital I/O and Analog I/O are covered on the following pages. Common configuration items such Digital Auxiliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections. Digital Refrigerant Detection Refrigerant Warning 1 When This warning can be set so that the warning occurs when the input module is de-energized or energized (based on configuration) for the delay. Refrigerant Warning 2 When This warning can be set so that the warning occurs when the input module is de-energized or energized (based on configuration) for the delay. NOTICE In digital mode the Refrigerant Warning 1 and Refrigerant Warning 2 are independent and can occur out of sequence and can be cleared independently if the digital status is corrected per the configuration. Ventilation Up to 4 digital outputs can be enabled, named and configured to manage the ventilation of the engine room relative to minimum air flow and emergency air flow requirements. All four can be configured for independent VFD operation. Refrigerant Detection Up to 4 analog inputs and 2 digital inputs can be configured for Refrigerant Detection. Start by enabling Analog Refrigerant Detection/Warning, Digital Refrigerant Detection/Warning or both. Analog Refrigerant Detection Number of Detectors Select up to 4 sensors to be monitored with two levels of warning Detector Custom tag the detectors listed or leave at default tags Refrigerant Warning 1 Sets the value at which a Refrigerant Warning 1 alarm is issued after the delay. A Refrigerant Warning 1 will energize the audible/visual alarm. It self-clears once the level drops below 20PPM. Refrigerant Warning 1 Sets the value at which a Refrigerant Warning 2 alarm is issued after the delay. A Refrigerant Warning 2 energizes the audible/visual alarm and initiates Emergency Ventilation (all ventilation steps are on at full capacity). It cannot be cleared until the PPM level is below the Refrigerant Warning 1 level. Number of Fan Outputs Selectable from 0 4. The number selected sets the number of fan outputs to be configured. Each output can be custom named based on the users preference or building drawing designations.

17 ENGINE ROOM OPERATION O (AUG 2015) Page 17 Type Select between Fixed and VSD for the type of fan control that will be used. Step On Establishes the order which each step will come on-line. More than one output can be configured with the same Step On number. Control Setpoint Set the desired Temperature to be maintained in the engine room. Upper Dead Band Sets the degrees of temperature above the control setpoint where steps are brought on-line. Upper Dead Band Sets the degrees of temperature below the control setpoint where steps are taken off-line. Step Delay The delay to bring step on-line or take steps off-line. All Outputs On Sets the temperature at which all ventilation outputs will energize. Steps configured as VSD will go to the Maximum Output configured in VSSD Ventilation Control. VSD Ventilation Control If any of the ventilation steps are configured as VSD, the following setpoints are used to control the output to the VSD. Proportional Band The value over the Control Setpoint at which time the VSD output will be at it s maximum proportionally. Integration Time The time in which additional VSD output is integrated into the total VSD output, enabling the control to maintain the Control Setpoint. Maximum Output Sets the maximum drive output that can be emitted from the assigned analog output. If the output is configured as 4-20 ma and the Maximum Output is 80% the output would be limited to 16.8 ma. Minimum Output As with the Maximum Output, the Minimum Output set the low limit for the VSD output signal. Floor Warming Floor Warming is used to prevent freezing and heaving of the freezer space floors. It can be done by circulating glycol through tubes that run within the floor or resistive heating also integrated into the floor. Glycol Heating Floor temperature readings are used to control the On/Off of glycol Circulation Pump while returning glycol temperature is used to control the Glycol Heating. Electric Heating Floor Temperature Readings are used to control the On/Off of the Electric Heating. Underfloor Temperatures Select and name up to 4 underfloor temperature probes used to monitor floor temperature and control the Glycol Circulation Pump or the Electric Heating. Glycol Temperatures Enable to monitor the supply and return temperatures as well as control glycol heating On/Off from the glycol return temperature. Digital I/O Configuration Used to configure standard Engine Room Control digital I/O by board and channel as well as display current status. Non-standard items can be configured for monitoring, alarms and control in Digital Auxiliaries configuration.

18 O (AUG 2015) Page 18 ENGINE ROOM OPERATION Analog I/O Configuration (inputs) Used to configure standard Engine Room Control analog inputs by sensor range (low/high), sensor type, board and channel. Non-standard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration. Analog I/O Configuration (outputs) Used to configure standard Engine Room Control analog outputs for VSD fan control by board and channel.

19 ENGINE ROOM OPERATION O (AUG 2015) Page 19 SERVICE: The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity. CLEAN SCREEN: Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

20 O (AUG 2015) Page 20 ENGINE ROOM OPERATION Engine Room Alarms Following is the listing of all possible Engine Room alarms: Analog Aux Low Warning (1) Occurs if the warning is enabled on Analog Aux Input A J and the respective analog input reading is less than or equal to the low setpoint for the time delay. Analog Aux High Warning (1) Occurs if the warning is enabled on Analog Aux Input A J and the respective analog input reading is greater than or equal to the high setpoint for the time delay. Digital Aux Input Warning (digital aux input a-j) (2) Occurs if the warning is enabled on Digital Aux Input A J and the respective input is de-energized for the time delay. Analog Board 1 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 1 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 1 Reset Occurs if the watchdog circuit on the respective digital board does not see active communications with the processor board for 5 seconds or if the 5vdc power to the board drops below 4.85vdc. Engine Room Temperature Sensor Fault (5) Occurs if the digital count for the respective sensor is outside of the low or high end of the count range. Refrigerant Warning 1 - Refrigerant Detector A, B, C or D (3) Occurs if Analog Refrigerant Detection Warnings are enabled, the Refrigerant Warning 2 Digital Output is safe, and the respective Refrigerant Detector reading is above this warning s setpoint for its time delay. Refrigerant Warning 2 - Refrigerant Detector A, B, C or D (3) Occurs if Analog Refrigerant Detection Warnings are enabled and the respective Refrigerant Detector reading is above this warning s setpoint for its time delay. Refrigerant Warning 1 - Digital Input Occurs if Digital Refrigerant Detection Warnings are enabled, the Refrigerant Warning 2 Digital Output is safe, and the Refrigerant Warning 1 Digital Input is in the user-selected state for this warning for its time delay. Refrigerant Warning 2 - Digital Input Occurs if Digital Refrigerant Detection Warnings are enabled, and the Refrigerant Warning 2 Digital Input is in the userselected state for this warning for its time delay. (3) (5) Refrigerant Detector A Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (3) (5) Refrigerant Detector B Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (3) (5) Refrigerant Detector C Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (3) (5) Refrigerant Detector D Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. Underfloor Glycol Return Temp. Sensor Fault (5) Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. Underfloor Glycol Supply Temp. Sensor Fault (5) Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (4) (5) Underfloor Temperature A Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (4) (5) Underfloor Temperature B Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (4) (5) Underfloor Temperature C Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. The count range can be viewed on the Analog Board status page. (4) (5) Underfloor Temperature D Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. SENSOR FAULT COUNT RANGE Sensor Type Low End Count High End Count ICTD (temperature) RTD (temperature v or 2-10v or 4-20mA <614 No Upper Limit Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA. 1. Analog Aux Inputs A-J may be custom named by user. 2. Digital Aux Inputs A-J may be custom named by user. 3. Refrigerant Detector A-D may be custom named by user. 4. Underfloor Temp Sensor A-D may be custom named by user. 5. See the count range table for various sensor types.

21 CONDENSER OPERATION O (AUG 2015) Page 21 SECTION 4 - CONDENSER CONTROL

22 O (AUG 2015) Page 22 CONDENSER OPERATION Introduction Condenser Control provides monitoring and control for the following: Condenser Steps 16 steps of condenser control that can be configured as a fixed speed fan, 2 Sp Fan Lo, 2 Sp Fan Hi, Var. Sp Fan or Water Pump. Eight analog outputs are available for Var. Sp Fan control. Dynamic Setpoint Control Monitors humidity and outdoor temperature to calculate wet-bulb temperature. The condenser approach is added to the wet-bulb temperature to establish a dynamic condenser control setpoint that will change with the ambient conditions. Non-Condensable Gas Notification Alerts the operator if a high level of non-condensable gas is detected in the system. Alternate Pressure Control Can be configured to adjust the condensing control setpoint to a value which will ensure adequate defrost. Bleed Control Turns on a bleed output for a used defined period of time at a user defined interval. Additional digital and analog auxiliaries along with proportional and integral control loops can be configured to control other ancillary items as necessary. The System Operating Values data is configured by touching the Select Data button shown above. From the user defined page select the additional items to be displayed on the Condenser home page and select Save Changes. Select Condenser control by touching anywhere in the Condenser control block on the System Overview page or selecting from the drop down if on another control page such as Evaporator. Main Menu & Navigation Home Returns the user to the Condenser home page Alarms Displays current and historical alarms as well as freeze data for each alarm Calibration Calibration for all enabled analog inputs Configuration Configuration for all operational feature such as refrigerant detection, ventilation and floor warming About Displays all software information for the processor, interface, analog and digital boards Status Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ethernet I/P Service Diagnostics, software maintenance, security, download system data Logout Logs out user when session is complete The Condenser home page illustrates all the pertinent operating data on the left side of the page and operational status and interactive control buttons on the right. A System Operating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the system.

23 CONDENSER OPERATION O (AUG 2015) Page 23 EVENTS: The Events page displays recorded events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen. TRENDING: The Trending page displays historical data and provides a means to Select Data To Trend, the read Interval and Download Trending Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data. Trending Sub-menus Select Data To Trend - Select Data to be trended from the list shown when the Select Data To Trend button is pushed. Interval - Change the read interval by touching the Interval setpoint box, select the desired value using the on-page keypad and press Enter. Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive is detected touch the Download Trending Data button on the trending page. Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

24 O (AUG 2015) Page 24 CONDENSER OPERATION ABOUT: The About page lists the software and firmware version for the processor, interface, analog and digital boards. It also lists the Sales Order and Item numbers. STATUS: The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P.

25 CONDENSER OPERATION O (AUG 2015) Page 25 ALARMS: The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button. CALIBRATION: The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog outputs. Calibration Sub-menus Calibration Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accordingly. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (ma) signal. To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page. Select the Analog Board and Channel for the output to be calibrated. Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be calibrated. Set the calibrated meter to read DC ma Select Calibrate Low End and use the + and value buttons of various change values to calibrate to the desired value of 0 or 4 ma. Select Calibrate High End and use the + and buttons of various change values to calibrate the high end to 20 ma.

26 O (AUG 2015) Page 26 CONDENSER OPERATION CONFIGURATION: The Configuration page/menu is used to access main areas of configuration such as Pumps and Fans, Summer/Winter Sequence, Condenser Control Setpoints and overrides and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O. Configuration Sub-menus Configuration for Pumps and Fans, Summer/Winter Sequence, Condenser VSD, Condenser Control Setpoints and Overrides, Digital I/O and Analog I/O are covered on the following pages. Common configuration items such Digital Auxiliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections. Condenser Information Select the number of individual condenser/s and enter model number and serial number information for each. Summer/Winter Sequence Set the step sequence for the summer sequence on this page. There is also a winter sequence page. The Step On / Off Sequence can be selected as standard or custom. Standard sequence sets the Off sequence relative to the On sequence in a first On, last Off order. Custom sequence allows the user to set both the On and Off sequence to best fit the application. Pumps and Fans Pumps and Fans A-H (8) and I-P (8) are configured on this page. Select each condenser step as a Water Pump, Single Spd Fan, Var Speed Fan or 2-Spd Fan Lo. Selecting a step as 2-Spd Fan Lo automatically sets the next step as 2-Spd Fan Hi. Each step can have an Aux. Failure enabled. Water pumps will have an Outside Air Stop enabled. If selected as a VFD the analog output used for that step is selectable. If set as a 2-Spd Fan Lo/Hi a delay between high speed and low speed is available. The name for each step is has a default tag relative to the selection and can be changed by the user to match plant designations. Condenser VSD Control If any of the condenser steps are configured as VSD Fan, the VSD control setpoints are on this page. These setpoints are the same as used in other areas for P/I control. The fan control strategy can be selected as one of the following; Ramp After All Steps On After all VSD Fan steps are on at minimum speed (30%), the fans will ramp up and down together. Ramp After Each Step Each VSD Fan is allowed to ramp after it is turned on. When other VSD Fan steps come on they will sink to the speed of the others on line.

27 CONDENSER OPERATION O (AUG 2015) Page 27 Condenser Controller Setpoints Summer / Winter Controls setpoints for both Summer and Winter nodes are set on this page. The control setpoint is a calculated value when the Control Strategy is selected as Dynamic. Also selecte between Automatic and manual with regard to transitioning from Summer to Winter modes. Digital I/O Used to configure standard Condenser Control digital I/O by board and channel as well as display current status. Non-standard items can be configured for monitoring, alarms and control in Digital Auxiliaries configuration. There 4 pages to cover all of the standard I/O for condenser control. Control / Safety The following condenser control features are configured on this page. Control Strategy Fixed Setpoint or Dynamic: Dynamic control calculates the wet-bulb temperature along with the condenser approach setpoint and the refrigerant selection to establish a saturated condensing temperature/pressure to control to. Condenser Bleed Control Will control the energizing of a bleed solenoid for a user defined period of time at a user defined interval. Alternate Pressure Control Can be set as Defrost, Standby or Disabled: Often set as defrost, the controller will communicate to the evaporator controller to determine if units are going into defrost. When units go into defrost the Condenser Control Setpoint will change to the Defrost Setpoint on the Summer / Winter setpoints page if the current setpoint is less than that value. Analog I/O Configuration Used to configure standard Condenser Control analog inputs by board and channel. Nonstandard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration. Condenser Control Overrides Override setpoints are designed to take control over the configured control strategies if the operation is outside of the bounds listed below for the associated delay. Analog I/O Configuration (outputs) Used to configure standard Condenser Control analog outputs for VSD fan control by board and channel. The Analog Outputs page is used to configure the VSD Fan outputs by board and channel if used.

28 O (AUG 2015) Page 28 CONDENSER OPERATION SERVICE: The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity. CLEAN SCREEN: Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

29 CONDENSER OPERATION O (AUG 2015) Page 29 Condenser Alarms Following is the listing of all possible Condenser alarms: Analog Aux Low Warning (1) Occurs if the warning is enabled on Analog Aux Input A J and the respective analog input reading is less than or equal to the low setpoint for the time delay. Analog Aux High Warning (1) Occurs if the warning is enabled on Analog Aux Input A J and the respective analog input reading is greater than or equal to the high setpoint for the time delay. Digital Aux Input Warning (digital aux input a-j) (2) Occurs if the warning is enabled on Digital Aux Input A J and the respective input is de-energized for the time delay. Analog Board 1 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 1 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 2 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 1 Reset Occurs if the watchdog circuit on the respective digital board does not see active communications with the processor board for 5 seconds or if the 5vdc power to the board drops below 4.85vdc. Digital Board 2 Reset Occurs if the watchdog circuit on the respective digital board does not see active communications with the processor board for 5 seconds or if the 5vdc power to the board drops below 4.85vdc. Ammonia 1, 2 or 3 Warning (analog) (3) Occurs if the respective warning is enabled and the respective Ammonia Input reading is greater than the warning setpoint for the time delay. Condenser Step Aux. (4) Up to 16 condenser steps can be enabled. They are listed as Steps A-P. The Condenser Step Aux. alarm occurs if the Aux Failure feature is enabled for the respective condenser step and the aux. input is de-energized when the output for that step is energized Condenser False Run Input (4) Up to 16 condenser steps can be enabled. They are listed as Steps A-P. The Condenser False Run Input alarm occurs if the Aux Failure feature is enabled for the respective condenser step and the aux. input is energized when the output for that step is de-energized. High Pressure Warning Occurs if the active condensing pressure A or B is above the high pressure warning setpoint for the time delay. Non-Condensable Gas Warning Occurs if the warning is enabled and the condensing pressure is greater than the saturated condensing pressure plus the Non-Condensable Gas Dead Band for the delay. Note: The saturated condensing pressure is derived by converting the Condenser Liquid Temperature to a saturated pressure relative to the selected refrigerant. (5) (6) Ammonia 1, 2 or 3 Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (5) (6) Condensing Pressure A Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (5) (6) Condensing Pressure B Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (5) (6) Liquid Temperature Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (5) (6) Outside Air Temperature Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. (5) (6) Outside Air Humidity Sensor Fault Occurs if the if the digital count for the respective sensor is at the low or high end of the count range. SENSOR FAULT COUNT RANGE Sensor Type Low End Count High End Count ICTD (temperature) RTD (temperature v or 2-10v or 4-20mA <614 No Upper Limit Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA. 1. Analog Aux Inputs A-J may be custom named by user. 2. Digital Aux Inputs A-J may be custom named by user. 3. Ammonia Inputs 1-3 may be custom named by user. 4. Condenser Steps A-P may be custom named by user. 5. Underfloor Temp Sensor A-D may be custom named by user. 6. See the count range table for various sensor types.

30 O (AUG 2015) Page 30 CONDENSER OPERATION

31 VESSEL OPERATION O (AUG 2015) Page 31 SECTION 5 - VESSEL CONTROL

32 O (AUG 2015) Page 32 VESSEL OPERATION Introduction Vessel Control provides monitoring and control for the following: Recirculator Vessel Control Level and pump control for up to 3 vessels with up to 4 pumps each. Digital or analog liquid makeup Choose between digital or analog controlled liquid makeup on up to 2 makeup circuits on each vessel. Pump Order Rotation Rotate the pump order manually or automatically based on run hours. The Vessel home page illustrates all the pertinent operating data on the left side of the page and operational status and interactive control buttons on the right. A System Operating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the systems. Main Menu & Navigation Select Vessel control by touching anywhere in the Vessel control block on the System Overview page or selecting from the drop down if on another control page such as Evaporator. Home Returns the user to the Vessel home page Alarms Displays current and historical alarms as well as freeze data for each alarm Calibration Calibration for all enabled analog inputs Configuration Configuration for all operational features such as refrigerant detection, ventilation and floor warming About Displays all software information for the processor, interface, analog and digital boards Status Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ethernet I/P Service Diagnostics, software maintenance, security, download system data Logout Logs out user when session is complete Vessel Overview Page shows all enable vessels with basic operational status. Select a particular vessel by touching anywhere in the vessel field to go to the home page for that vessel.

33 VESSEL OPERATION O (AUG 2015) Page 33 EVENTS: The Events page displays recorded events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen. TRENDING: The Trending page displays historical data and provides a means to Select Data To Trend, the read Interval and Download Trending Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data. Trending Sub-menus Select Data To Trend - Select Data to be trended from the list shown when the Select Data To Trend button is pushed. Interval - Change the read interval by touching the Interval setpoint box, select the desired value using the on-page keypad and press Enter. Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive is detected touch the Download Trending Data button on the trending page. Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

34 O (AUG 2015) Page 34 VESSEL OPERATION ABOUT: The About page lists the software and firmware version for the processor, interface, analog and digital boards. It also lists the Sales Order and Item numbers. STATUS: The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P. ALARMS: The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button.

35 VESSEL OPERATION O (AUG 2015) Page 35 CALIBRATION: The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog outputs. Calibration Sub-menus Calibration Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accordingly. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled. From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (ma) signal. To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page. Select the Analog Board and Channel for the output to be calibrated. Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be calibrated. Set the calibrated meter to read DC ma Select Calibrate Low End and use the + and value buttons of various change values to calibrate to the desired value of 0 or 4 ma. Select Calibrate High End and use the + and buttons of various change values to calibrate the high end to 20 ma.

36 O (AUG 2015) Page 36 VESSEL OPERATION CONFIGURATION: The Configuration page/menu is used to access main areas of configuration such as Vessel Enable, Level and Pump Control, Safeties, Digital and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O. Configuration Sub-menus Configuration to enable vessels, pumps, level control, pump control, safeties, refrigerant detection, digital and analog I/O are covered on the following pages. Common configuration items such Digital Auxiliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections. Vessel/Receiver Enable Enable Vessels 1-3 for full vessel control including pumps liquid make-up and safeties. Also enable receivers for level monitoring only. All vessels and receivers can custom named to match the plant designations. Key pump control configuration items are: Auto Pump Operation Runs With Compressors, Runs Continuously, Off on High Level. Low level safeties are active for all auto pump operation selections Auto Pump Rotate Rotates pump operating order based on pump run hours. Pump Diff. Control Monitors the pressure differential across each pump to protect the pump against cavitation. Pump Bypass Control If the pressure differential rises above the Bypass Pressure Diff. setpoint for the delay the bypass output is turned on.setpoint Level Control Select between modulating level control or solenoid level control or a combination as shown here. The setpoints for the modulating control work the same as all other Quantum HD P/I Control loops. Select up to 2 modulating valves, up to 2 solenoid valves and whether the solenoid control is analog from a level sensor or digital from float switches. To configure other enabled vessels touch the next vessel to be configured. Safeties Level safeties are configured on this page for both analog (probe) and digital (float/s) along with associated delays. Configure the safeties for other vessels by selecting the vessel from this page. Pump Control Configure up to 4 pumps (Pumps A & B), (Pumps C & D) per vessel. To configure another vessel, select that vessel from this page.

37 VESSEL OPERATION O (AUG 2015) Page 37 Refrigerant Detection Configure up to three analog refrigerant detection channels. Three corresponding digital outputs can be configured to be Normally On or Normally Off. These are triggered to the opposing position when triggered. Board and channel configuration is in Analog and/or Digital I/O configuration. Names can be user defined to match the plant designations for these devices. Analog I/O Configuration (inputs) - Used to configure standard Vessel Control analog inputs by board and channel. Nonstandard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration. Digital I/O Configuration - Used to configure standard Vessel Control digital I/O by board and channel as well as display current status. Non-standard items can be configured for monitoring, alarms and control in Digital Auxiliaries configuration. There 6 pages to cover all of the standard I/O for condenser control. Analog I/O Configuration (Outputs) Used to configure modulating makeup valves A & B for vessel 1, 2 and 3 by board and channel.

38 O (AUG 2015) Page 38 VESSEL OPERATION SERVICE: The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity. CLEAN SCREEN: Clean Screen disables the screen for cleaning purposes. Timeout is displayed on the page.

39 VESSEL OPERATION O (AUG 2015) Page 39 Vessel Alarms Most vessel alarms are duplicated from an original or template alarm, and the particular vessel name defines the corresponding alarm. In the alarms definitions below the letter X represents any respective vessel. Vessels can be custom named by the user. That custom name will be the prefix for all alarms associated with that vessel. Analog Aux Low Warning (1) Occurs if the warning is enabled on Analog Aux Input A J and the respective analog input reading is less than or equal to the low setpoint for the time delay. Analog Aux High Warning (1) Occurs if the warning is enabled on Analog Aux Input A J and the respective analog input reading is greater than or equal to the high setpoint for the time delay. Digital Aux Input Warning (digital aux input a-j) (2) Occurs if the warning is enabled on Digital Aux Input A J and the respective input is de-energized for the time delay. Analog Board 2 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Analog Board 3 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 4 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 4 Reset Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 5 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 5 Reset Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 6 Communications Shutdown Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Digital Board 6 Reset Occurs if the processor does not communicate with the respective analog board for a period of 5 seconds. Vessel X - High Level Warning Digital Input Occurs if the High Level Warning Digital Input is enabled and the digital input is de-energized for the time delay. Vessel X - High Level Shutdown Digital Input Occurs if the High Level Shutdown Digital Input is enabled and the digital input is de-energized for the time delay. Vessel X - Low Level Warning Digital Input Occurs if the Low Level Warning Digital Input is enabled and the digital input is de-energized for the time delay. Vessel X - Low Level Shutdown Digital Input Occurs if the Low Level Shutdown Digital Input is enabled and the digital input is de-energized for the time delay. Vessel X - High Level Warning Occurs if Analog Input Safeties are enabled and the refrigerant level reading is above the high level warning setpoint for the time delay. Vessel X - Low Level Warning Occurs if Analog Input Safeties are enabled and the refrigerant level reading is below the low level warning setpoint for the time delay. Vessel X - Low Level Shutdown Occurs if Analog Input Safeties are enabled and the refrigerant level reading is below the low level shutdown setpoint for the time delay. Vessel X - Pump A, B, C or D Pressure Differential Shutdown Occurs if the Pressure Diff. Control alarm is enabled, the pump is running, and the differential between the high side pump pressure and low side pump pressure is less than the Min. Pressure Diff. setpoint for the time delay. Vessel X - Refrigerant Pump A, B, C or D Auxiliary Shutdown Occurs if the Pump Auxiliary Input is enabled, the pump is running, and the Pump Auxiliary Input is de-energized for the time delay. Vessel X - Pump A, B, C or D Hi Side Press. Sensor Fault (3) Occurs if the Pressure Diff. Control alarm is enabled, and the respective sensor is at the low end of the count range. Vessel X - Pump A, B, C or D Lo Side Press. Sensor Fault (3) Occurs if the Pressure Diff. Control alarm is enabled, and the respective sensor is at the low end of the count range. Vessel X - Pump A, B, C or D High Pressure Shutdown Occurs if the High Pressure Shutdown feature is enabled, the pump is running, and the high side pump pressure is greater than the High Pressure Shutdown setpoint for the time delay. Vessel X - Refrigerant Level Sensor Fault (3) Occurs if the digital count for the respective sensor is at the low end of the count range. SENSOR FAULT COUNT RANGE Sensor Type Low End Count High End Count ICTD (temperature) RTD (temperature v or 2-10v or 4-20mA <614 No Upper Limit Note: Sensor faults are not provided for these sensor types: 0-5v, 0-10v or 0-20mA. 1. Analog Aux Inputs A-J may be custom named by user. 2. Digital Aux Inputs A-J may be custom named by user. 3. See the count range table for various sensor types.

40 O (AUG 2015) Page 40 ENGINE ROOM/ CONDENSER/ VESSEL/EVAPORATOR OPERATION

41 EVAPORATOR OPERATION O (AUG 2015) Page 41 SECTION 6 - EVAPORATOR CONTROL

42 O (AUG 2015) Page 42 EVAPORATOR OPERATION Introduction Evaporator Control provides monitoring and control for the following: Cooling & Defrost Control Control cooling and defrost for up to 30 zones across 10 remote I/O panels. Dehumidification Control Run additional cooling to draw excess moisture out of the space. Heating and Re-heating Control Used for more complex space conditioning requirements. Load Shedding Take evaporators off-line or set to a higher control setpoint/mode during periods of higher energy costs. The Evaporator home page illustrates all the pertinent operating data on the left side of the page and operational status and interactive control buttons on the right. A System Operating Values area is in the lower left of the page. This is used to display non-standard analog values that may be configured and read by the system. Main Menu & Navigation Select Evaporator control by touching anywhere in the Evaporator control block on the System Overview page or selecting from the drop down if on another control page such as Condenser. Home Returns the user to the Evaporator home page Alarms Displays current and historical alarms as well as freeze data for each alarm Calibration Calibration for all enabled analog inputs Configuration Configuration for all operational features such as refrigerant detection, ventilation and floor warming About Displays all software information for the processor, interface, analog and digital boards Status Displays current status of the analog and digital I/O, serial comm. Ports 1-3, I/O comms., Modbus TCP and Ethernet I/P Service Diagnostics, software maintenance, security, download system data Logout Logs out user when session is complete Evaporator Overview Page shows all enable Evaporators with basic operational status. Select a particular Evaporator by touching the Select Zone and selecting the appropriate zone. Up to 15 zones will be displayed in 2 columns on this page for a total of 30.

43 EVAPORATOR OPERATION O (AUG 2015) Page 43 EVENTS: The Events page displays recorded events such as power down and power up times. Touch the Next button in the lower right to view earlier events that do not appear on this screen. TRENDING: The Trending page displays historical data and provides a means to Select Data To Trend, the read Interval and Download Trending Data. A USB Thumb Drive must be inserted into the respective controller USB port to Download System Data. Trending Sub-menus Select Data To Trend - Select Data to be trended from the list shown when the Select Data To Trend button is pushed. Each Evaporator will have it s own trending page. Interval - Change the read interval by touching the Interval setpoint box, select the desired value using the on-page keypad and press Enter. Download Trending Data - Download Trending Data, plug in a flash drive/thumb drive (configured for FAT32). Once the drive is detected touch the Download Trending Data button on the trending page. Download Trending Data can also be done by a networked computer, tablet or smartphone that has the ability to save and open Excel spreadsheets.

44 O (AUG 2015) Page 44 EVAPORATOR OPERATION ABOUT: The About page lists the software and firmware version for the processor, interface, analog and digital boards. It also lists the Sales Order and Item numbers. STATUS: The Status page displays the real time status of the analog and digital I/O, serial comm. ports 1-3, I/O comms., Modbus TCP and Ethernet I/P.

45 EVAPORATOR OPERATION O (AUG 2015) Page 45 ALARMS: The Alarms page displays current and historical alarms as well as freeze data for each alarm. Alarm Silence or Clear All alarms from this page. Freeze Data Selection is also initiated from this page. View earlier alarms by pressing the Next button. CALIBRATION: The Calibration page is used to calibrate all enabled analog inputs, analog auxiliaries and analog outputs. Calibration Sub-menus Calibration Enter the value for the device being calibrated into the Current Value box for that device. The Offset value will automatically calculate and populate that cell. Offsets can also be zeroed which will change the Current Value accordingly. Each Evaporator has a calibration page. Other pages include ammonia, kw, auxiliaries and outputs (analog). From this page select Auxiliaries to calibrate any analog auxiliary channels that may be enabled in the same manner. To Calibrate an analog output requires a calibrated meter that can read a milliamp (ma) signal. To calibrate an analog output for a 4-20mA or 0-20mA do the following from the Output calibration page. Select the Analog Board and Channel for the output to be calibrated. Attach the black lead to the negative terminal and the red probe to the positive terminal for the channel to be calibrated. Set the calibrated meter to read DC ma Select Calibrate Low End and use the + and value buttons of various change values to calibrate to the desired value of 0 or 4 ma. Select Calibrate High End and use the + and buttons of various change values to calibrate the high end to 20 ma.

46 O (AUG 2015) Page 46 EVAPORATOR OPERATION CONFIGURATION: The Configuration page/menu is used to access main areas of configuration such as Zone Enable, Refrigerant Detection, Zone Functions, Zone Cooling, Defrost, Dehumidification, Heating and Reheating control, Digital and Analog Auxiliaries, Communications, P/I Control, Digital and Analog I/O. Configuration Sub-menus Configuration to enable evaporator zones, refrigerant detection, zone function, zone cooling & defrost, zone heating, load shedding, digital and analog I/O are covered on the following pages. Common configuration items such Digital Auxiliaries, Analog Auxiliaries, Communications and Proportional Integral Control are covered in their respective sections. Global Zone Configuration Enable and name up to 30 zones along with defrost grouping, control input selection (entering temp, room temp or user defined temp). User defined naming of the of the user defined temp is done on this page. Global Refrigerant Detection Name up to 30 refrigerant detection points with alarm and shutdown values with delays. Up to three refrigerant detection sensor/inputs can be enabled per zone or multiple zones can use the same sensor/ input. This is selectable in Zone Function Configuration. Defrost Groups Up to 10 defrost groups can be configured to better manage the number of units in any one area that are in defrost at the same time. Zone Function Configuration Enable all zone functions on this page to include cooling, soft hot gas, dehumidification, defrost, heating and reheat. Enable up to 4 modes (capacity control setpoints). Configure all valve functions/actions and select refrigerant sensors associated with this zone. If enabled the Dehumidification and reheat setpoints are on the Zone Cooling Modes page and Heating setpoints are on the Zone Heating Modes page.

47 EVAPORATOR OPERATION O (AUG 2015) Page 47 Dehumidification Requires an RH% humidity input. If the humidity level is above the on setpoint, cooling (liquid and fan) are turned on even if below their respective off setpoints to remove the non-wanted moisture from the space. A low temp. override setpoint will turn the liquid and fan off to prevent the space from getting too cold. Reheat This feature is used in conjunction with de-humidification where there is a dedicated reheat coil within the complete coil bundle. This is used to add heat to the space to prevent the space temperature from dropping to low while the cooling coil removes the non-wanted moisture from the space. Heating This feature is used to heat a space using hot gas in the main coil. The process of shifting from cooling to heating and back to cooling is essentially the same as when going into and coming out of defrost. Zone Cooling Modes Configure each enable mode for each zone for Liquid. Hot Gas Warning monitors the evaporator pressure when the hot gas is on to be ensure adequate pressure for defrost. There is also a warning for high pressure. Either a low or high Hot Gas Warning could indicate a problem with the back pressure regulator during defrost. Requires a pressure transducer to read the evaporator pressure. Manual Defrost Control is initiated on the zone s home screen. Once initiated, a service level operator can advance the stages in a manual defrost from the Zone Defrost page. Defrost Schedule Up to 8 defrosts can be scheduled per zone per day. The schedule of one day can be easily copied to other days by selecting the day to be copied from and the days to be copied to and touch the copy button. Liquid - Liquid can be by solenoid control or modulating valve control if enable in zone function configuration. I configured for modulation valve additional setpoints for the P/I control of that valve are listed in the liquid section. If not enable only the liquid On and Off setpoints are present. Fan The fan can be configured a fixed speed or VSD fan. If fixed only a fan On and fan Off setpoint will be listed in the fan section. If fan cycling is enable in zone function setpoints to cycle the fan On for a period of time and a user defined interval will also appear. If selected as VSD fan as shown hereadditional setpoints for the P/I control will appear. Alarm Low and high temperature warning values with delays and mode switch delay. Dehumidification/Reheat These two features work together to remove unwanted moisture from the space while not allowing the space to get too cold. Requires a special coil within a coil or a secondary coil for the reheat process. Zone Defrost Standard defrost timer settings for pump out, soft hot gas, hotgas, bleed, fan delay are provided. If fan is VSD a pump out fan sped setpoint is provided. Initiate defrost from schedule, liquid timer, schedule w/liquid override. Defrost can also be iniated on demand by enabling the feature and energizing the demand defrost digital input. Power Outage During Defrost If a power outage occurs during defrost the controller will move straight to the bleed stage on power up to avoid any vapor propelled liquid slugging from occurring. Zone Heating Modes Setpoints on this are used to transition to heating mode, control in heating mode and transition back to cooling mode. Heating is an operation of using hot gas to heat a space as needed. Other than the initiation process, the transition to heating and back to cooling are similar to that of defrost. Fan setpoints are similar to that of cooling.

48 O (AUG 2015) Page 48 EVAPORATOR OPERATION Load Shedding Provides a means of reducing system load during certain periods where it is advantageous to do so. This could be during higher rate periods or anytime when the flywheel effect will sustain the requirements for the space and product. Units can either be turned off by setting the mode to 0 (zero) or to a higher temperature setting by selecting the mode associated with that setting. An override temp will prevent the space from getting too warm. If the unit has a VSD fan, it s speed during load shed is set on this page. Zone Digital I/O Configuration Used to configure standard Condenser Control digital I/O by board and channel as well as display current status. Non-standard items can be configured for monitoring, alarms and control in Digital Auxiliaries configuration. There 2 pages to cover each zone of evaporator control. In and Out of Load Shed Sequence Is set by the % Differential value that proportionally compares the actual temperature to the difference between the liquid On setpoint and the Override temperature for each zone. Colder units with the lower % differential values go into load shedding first while warmer units with higher % Differential values come out of load shedding first. Any unit that exceeds the Override Temp. comes out of load shedding at that point. Load Shedding can be initiated manually, by schedule, kw reading or a combination of schedule and kw reading as shown here. Three timed schedules can be set per day. If the kw reading is above the start kw value and within the set start and stop period, load shedding will commence and stay in load shedding until the scheduled stop or the kw value drops below the stop value. The Source of kw Reading is the controller from which a plant wide value can be read, Engine Room Controller or Evaporator Controller. kw control will require a kw meter to be wired into the analog board of the engine room or one of the evaporator zones. The input from this meter should represent the entire plant load or at least the entire refrigeration system load. Global Digital I/O Configuration Global Digital I/O are for the configuration of global evaporator system control outputs. Two commonly used outputs are Main Hot Gas and Main Liquid which can be turned off in the event of a Refrigerant Detection shutdown. Zone Analog I/O Configuration (inputs and Outputs) Used to configure standard Evaporator Control analog inputs by sensor range (low/high), sensor type, board and channel. Non-standard items can be configured for monitoring, alarms and control in Analog Auxiliaries configuration. Also configure analog outputs for each zone for VSD Fan and Modulating Liquid Valve.

49 EVAPORATOR OPERATION O (AUG 2015) Page 49 Global Analog I/O Configuration Used to configure non-zone specific analog input channels that can be used anywhere in the evaporator system. As an example one NH3 sensor can be linked to all zones for refrigerant detection warning and shutdown. This is where a kw meter input would be configured to read to kw load. Analog Auxiliaries Analog Auxiliary Inputs Can be configured to expand the control and operation of the Evaporator control. Digital Auxiliaries Digital Auxiliary Inputs Digital Auxiliary inputs can be configured to expand the operation and control of the Quantum HD Unity System Controller beyond that which is standard. They allow the operator to configure additional safeties based on the status of other system components. These can be configured as warning when running, warning always, shutdown when running or shutdown always. The text can be user defined. Channel Configuration Set the Name, I/O Board, Channel and Sensor Output Sensor Configuration Displays current value, select Sensor Type and set the low range and high range limits of the sensor Safety Configuration Configure the safety for when active along with low and high end safeties and their delays. Communications Ethernet Enable one or both of the Ethernet Protocols dependent on the integration Digital Auxiliary Outputs Digital Auxiliary outputs can be configured to expand the operation and control of the system by configuring digital outputs to energize and de-energize based on an analog value (control Input) relative to the On When and Off When values. Serial Configure the serial comm port relative to the master device protocol, baud rate etc Evaporator control has just comm 1 and comm 2 available for external comms. Coms 3 & 4 are used for the I/O comms between the controller and the remote units.

50 O (AUG 2015) Page 50 EVAPORATOR OPERATION Map File Provides a means to download the Quantum HD Map File of addresses for the purpose of grouping items and uploading these groups. This allows an integrator to grab chunks of data with one query rather than many single item queries. Name: User Defined Control Input: Select the analog value to be used for the control. Control: Select between the following option relative to the control. Engine Room: Disabled, Enabled Condenser: Disabled, Enabled Vessel: Disabled, Enabled Evaporator: Disabled, Running, Always, Heating, Cooling, Defrost (running = anytime unit is Active or not Off as shown) You must have a USB thumb drive plugged into the appropriate controller prior to touching the Download Map File button. Proportional Integral Control P/I Control P/I controls expands the operation and control of the Quantum HD Unity System Controller by controlling ancillary modulating devices based on the value of analog input signal P/I Configuration Set Action for Forward for the input to increase if the actual value is above the setpoint and Reverse for the output to increase when the actual value is below the setpoint. Set all control setpoints, along with board and channel for the output. NOTICE May require calibrating of the analog output channel, covered in the calibration section for each control. SERVICE: The Service page is for Diagnostics, Communications Testing, Software Maintenance, Ethernet Integrity, System Data Downloads and I/O Integrity.

FRICK QUANTUM LX CONDENSER/VESSEL CONTROL PANEL

FRICK QUANTUM LX CONDENSER/VESSEL CONTROL PANEL Form File: SERVICE MANUAL - Section 90 Replaces: 090.560-O (APR 2015) Dist: 3, 3a, 3b, 3c FRICK QUANTUM LX CONDENSER/VESSEL CONTROL PANEL Version 3.0x Please check www.johnsoncontrols.com/frick for the

More information

FRICK QUANTUM LX AcuAir CONTROL PANEL

FRICK QUANTUM LX AcuAir CONTROL PANEL Form 090.510-O (SEPTEMBER 2013) File: SERVICE MANUAL - Section 90 Replaces: 090.512-O (DECEMBER 2012) Dist: 3, 3a, 3b, 3c FRICK QUANTUM LX AcuAir CONTROL PANEL Version 3.2x 090.510-O (SEPTEMBER 13) Page

More information

Quantum HD Release Notes

Quantum HD Release Notes Quantum HD Release Notes OS Version 10.17 Released 7-14-2014 To upgrade to OS version 10.17 directly the current OS version must be 10.13 through 10.16. To check the current OS version on the Quantum HD

More information

High Motor Current Shutdown High Motor Current Warning Low Motor Current Shutdown Compressor Auxiliary Shutdown

High Motor Current Shutdown High Motor Current Warning Low Motor Current Shutdown Compressor Auxiliary Shutdown Important: To upgrade from Quantum HD version 10.21 or earlier to Quantum HD Unity version 10.30 or later requires the flashcard to be changed. These are available through the Baltimore Parts Center, part

More information

CONTROLS. Quantum HD. Heavy Duty Performance In High Definition

CONTROLS. Quantum HD. Heavy Duty Performance In High Definition CONTROLS Quantum HD Heavy Duty Performance In High Definition CONTROLS Quantum HD Industrial Refrigeration Controller Quantum HD with Unity Architecture Quantum HD control panels make equipment management

More information

INDEX. Analog Board Boot and Voltage Test 2 Testing Input Channels 3 Testing Output Channels 4

INDEX. Analog Board Boot and Voltage Test 2 Testing Input Channels 3 Testing Output Channels 4 INDEX Analog Board Boot and Voltage Test 2 Testing Input Channels 3 Testing Output Channels 4 Digital Board Boot and Voltage Test 5 Testing Input Channels 6 Testing Output Channels 7 Display Testing 8

More information

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

Instruction Manual CTC-1

Instruction Manual CTC-1 Troubleshooting & Specs CTC-1 Amps / Volts requirements Min / Max operating temperature Min / Max operating Humidity Temperature Measurement range Temperature Accuracy CO2 sensor type CO2 Measurement range

More information

Multi-Point Gas Detection and Control System

Multi-Point Gas Detection and Control System Multi-Point Gas Detection and Control System DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control system for various gas, temperature and humidity detection, control and

More information

INSTRUCTION MANUAL FOR GUARDIAN INFINITY SIM PROGRAM

INSTRUCTION MANUAL FOR GUARDIAN INFINITY SIM PROGRAM INSTRUCTION MANUAL FOR GUARDIAN INFINITY SIM PROGRAM Model: INF Firmware 60.xxx Date: July 16, 2008 Page 0 of 29 INDEX 1- INFSIM OVERVIEW:...3 1.1- STARTING THE SOFTWARE:...3 1.2- ESTABLISHING COMMUNICATIONS:...3

More information

Baltimore Aircoil Company

Baltimore Aircoil Company Baltimore Aircoil Company VFD Startup Guide TABLE OF CONTENTS: A. Verifying Power and Control Wiring...1 B. Setting the VFD Parameters...2 C. Reentering Startup Wizard After Initial Setup...5 D. Starting

More information

Carbon Monoxide (CO) Gas Detection and Control System

Carbon Monoxide (CO) Gas Detection and Control System Carbon Monoxide (CO) Gas Detection and Control System DESCRIPTION Gas monitor with built-in carbon monoxide (CO) sensor, wall-mounted, accepts inputs from remote devices such as other gas sensors, temperature

More information

Multi-Point Gas Detection and Control System

Multi-Point Gas Detection and Control System Multi-Point Gas Detection and Control System Specifications subject to change without notice. USA 40804 Page of 7 DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control

More information

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP. DIVERSIFIED HEAT TRANSFER SERIES 700 STEAM GENERATOR CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE AT SIGMACONTROLS.COM SERIES 700 DHT STEAM GENERATOR MANUAL 042514 2 TABLE OF CONTENTS INTRODUCTION.

More information

FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x

FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x S90-500 O/JUL 2002 File: SERVICE MANUAL - SECTION 90 Replaces: S90-500 O/APR-2001 Dist: 3, 3a, 3b, 3c OPERATION FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x S90-500 O FRICK QUANTUM ACUair CONTROL PANEL

More information

FRICK QUANTUM CONDENSER/VESSEL CONTROL PANEL VERSION 2.1x

FRICK QUANTUM CONDENSER/VESSEL CONTROL PANEL VERSION 2.1x S90-555 M/OCT 2001 File: SERVICE MANUAL - SECTION 90 Replaces: NOTHING (New Manual) Dist: 3, 3a, 3b, 3c FRICK QUANTUM CONDENSER/VESSEL CONTROL PANEL VERSION 2.1x S90-555 M Page 2 FRICK QUANTUM CONDENSER/VESSEL

More information

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING Installation and Operation Manual ETV Platinum Plus Electronic Tempering Valve with Safeguard WARNING This Heat-Timer control is strictly an operating control; it should never be used as a primary limit

More information

CDD Carbon Dioxide Transmitter

CDD Carbon Dioxide Transmitter Introduction The OSA CO2 transmitter uses Infrared Technology to monitor CO2 levels within a range of 0 2000 ppm and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. The enclosure is designed to operate

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

FX 2 Instruction Manual

FX 2 Instruction Manual FX 2 Instruction Manual Climma Compact Version Annapolis MD USA 301 352 6962 info@veco-na.com Introduction: The FX2-DX digital controller operates onboard air conditioning equipment to provide room temperature

More information

Multi-Point Gas Detection and Control System

Multi-Point Gas Detection and Control System Multi-Point Gas Detection and Control System Specifications subject to change without notice. USA 50729 Page of 9 DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control

More information

Smart heating system. with wireless thermostats & smartphone control for every room. Get the most out of any water based underfloor heating

Smart heating system. with wireless thermostats & smartphone control for every room. Get the most out of any water based underfloor heating Smart heating system with wireless thermostats & smartphone control for every room Get the most out of any water based underfloor heating DETAILED OVERVIEW Control the heating in your home from anywhere.

More information

MAXDTC-BT Family User Manual

MAXDTC-BT Family User Manual MAXDTC-BT Family User Manual Description The MAXDTC-BT is a fully programmable industrial temperature controller. The controller is configurable and monitorable thru a Bluetooth connection from your Android

More information

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller WSHP-IOP-2 May 1998 Installation, Operation, and Programming Tracer ZN510 Controller Literature History The Trane Company has a policy of continuous product improvement and it reserves the right to change

More information

FRICK QUANTUM ACUair CONTROL PANEL VERSION 2.1x

FRICK QUANTUM ACUair CONTROL PANEL VERSION 2.1x S90-500 M/JULY 2002 File: SERVICE MANUAL - SECTION 90 Replaces: NOTHING (New Information) Dist: 3, 3a, 3b, 3c FRICK QUANTUM ACUair CONTROL PANEL VERSION 2.1x S90-500 M FRICK QUANTUM ACUair CONTROL PANEL

More information

SCC Inc. TS Series Application Guide. Technical Instructions. Document No. TS 8000 January 9, Description

SCC Inc. TS Series Application Guide. Technical Instructions. Document No. TS 8000 January 9, Description SCC Inc. Application Guide Technical Instructions January 9, 2018 Description The Application Guide includes programming, wiring, and operation examples of the control system for the most common applications.

More information

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL 1 700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700 DPC MANUAL 072114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC.   RATING IS 1 AMP COND. B ENABLE COOL B ENABLE. Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER

More information

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL 1 700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700SERIESTPCMANUAL071414 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features

More information

Dual Digital Module Technical Guide

Dual Digital Module Technical Guide Factory Packaged Controls Coil Products Dual Digital Module Table of Contents OVERVIEW... 3 INSTALLATION AND WIRING... 4 Environmental Requirements...4 Mounting...4 Power Supply and Communications...4

More information

AirTest Model CN9000 Series Sensor Controller

AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller THEORY OF OPERATION A basic CN9000 configuration consists of Input/Process/Display combination modules, a 3 relay

More information

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters DESCRIPTION Pump-Down Controller Input Scalable Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters The Model 4052 Pump-Down Controller provides total control for duplex pumping

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

Rev Single-Channel Pulse Modulating Anti-Sweat Control (SC-PMAC) Installation and Operation Manual

Rev Single-Channel Pulse Modulating Anti-Sweat Control (SC-PMAC) Installation and Operation Manual 026-1502 Rev 2 11-20-07 Single-Channel Pulse Modulating Anti-Sweat Control (SC-PMAC) Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 30144 Phone: (770) 425-2724 Fax: (770)

More information

FRICK QUANTUM EVAPORATOR CONTROL PANEL

FRICK QUANTUM EVAPORATOR CONTROL PANEL Form 090.60-M (MAY 06) File: SERVICE MANUAL - Section 90 Replaces: 090.60 - M (DEC 0) Dist:, a, b, c FRICK QUANTUM EVAPORATOR CONTROL PANEL Version.x Please check www.johnsoncontrols.com/frick for the

More information

TOXALERT MODEL AIR 2000

TOXALERT MODEL AIR 2000 TOXALERT MODEL AIR 2000 NOTE: Toxalert s Model GVU-CO 2 Sensor is the same as the Air2000R. Microprocessor-based, Infrared Environmental CO 2 Sensor OPERATOR S MANUAL TOXALERT TM INTERNATIONAL INC. P.O.

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

BA/BS4S Temperature Sensor Installation & Operating Instructions

BA/BS4S Temperature Sensor Installation & Operating Instructions Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service. PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA

More information

Tachometer Panel, PE3

Tachometer Panel, PE3 Features Plug-n-play units with factory programmed parameters 4-20 ma feedback signal Isolated relay alarm outputs Frequency input Diagnostic indicators NEMA 4 Enclosure Model PE3, Tachometer Panel Benefits

More information

Submittal Data Sheet intelligent Touch Manager DCM601A71

Submittal Data Sheet intelligent Touch Manager DCM601A71 For use with the following VRV Models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXTQ, FXUQ, FXZQ, VAM For use with the following Daikin SkyAir Models: FAQ, FBQ, FCQ, FHQ, FTQ Capacity:

More information

RGX COMMUNICATIONS GATEWAY

RGX COMMUNICATIONS GATEWAY RGX COMMUNICATIONS GATEWAY BTU Ventilation Corporation 47418 US Highway 10 Perham, Mn 56573 USA Phone (218) 346-7482 Fax (218) 346-7485 http:/// Manual ver 2.1 Copyright BTU Ventilation Corp 2008 RGX Communications

More information

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...

More information

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL 1 700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP MANUAL 042814 TABLE OF CONTENTS 2 INTRODUCTION

More information

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display HTC 5 Features Australian Made and designed Power can be either 24V or 240V AC 10 Amp (Resistive) Potential free relay contacts

More information

4-step Chiller and Heat Pump Controller

4-step Chiller and Heat Pump Controller 4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide. MXM-50 Modbus Interface for Mitsubishi Air-Conditioning Installation and User Guide www.innon.co.uk 1. Product Overview The Black Pear MXM-50 unit allows a Modbus building management system (BMS) to monitor

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS-2000 March 15, 2016

SCC Inc. TS Series. Technical Instructions. Document No. TS-2000 March 15, 2016 SCC Inc. TS-MS Master Lead/Lag Panels for Boiler Management, and Building Management System Interface Technical Instructions March 15, 2016 Description A TS-MS Series Master Lead/Lag Panel sequences and

More information

Operating Instructions. For. Level Control Module. Model SSR 1000

Operating Instructions. For. Level Control Module. Model SSR 1000 Operating Instructions For Level Control Module Model SSR 1000 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions before unpacking and commissioning.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS www.altroniccontrols.com INSTALLATION INSTRUCTIONS EXACTA 21 MONITORING AND CONTROL SYSTEM CAUTION: The EXACTA 21 CONTROL SYSTEM is CSA CERTIFIED FOR use in Class I, GROUPS C & D, Division 2 hazardous

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting G2522en Heating controller Installation Instructions RVL470 1 Installation 1.1 Place of installation In a dry room, e.g. the boiler room Mounting choices: In a control panel (on the inner wall or on a

More information

LC-5 Level Controller & Flow Monitor

LC-5 Level Controller & Flow Monitor The Level Controller and Flow Monitor provides a fully integrated Duplex Controller supporting both analog and discrete (float switch) level detection. The unit allows collecting 'rate of flow' information

More information

Model OI x82 ProSafe

Model OI x82 ProSafe Model OI-7480 4x82 ProSafe Operation Manual Revision 2.2.1w Product Overview The Otis Instruments, Inc. GenII ProSafe 4x82 Model OI-7480 is a eight (or twelve) channel gas monitor that functions as a transmission

More information

Technical Manual Nova: Cabinet Security Management System (CSMS)

Technical Manual Nova: Cabinet Security Management System (CSMS) Technical Manual Nova: Cabinet Security Management System (CSMS) KP_nova_TM_160501_EN 1 Publication May, 2016, Keyprocessor BV Paasheuvelweg 20 1105BJ Amsterdam, The Netherlands www.keyprocessor.com/nova

More information

Instruction Manual HID-2

Instruction Manual HID-2 Specifications HID-2 Amps / Volts requirements 15 amps @ 120 volts Min / Max operating temperature 32 to 120 F Min / Max operating humidity 0-99% RH Time setting Hours, Minutes, Seconds Hi-temp setting

More information

Model OI x42 ProSafe

Model OI x42 ProSafe Model OI-7440 4x42 ProSafe Operation Manual Revision 2.2w Product Overview The Otis Instruments, Inc. GenII ProSafe 4x42 Model OI-7440 is a four channel gas monitor that functions as a transmission controller.

More information

LC-110/H. Reference Manual

LC-110/H. Reference Manual LC-110/H Reference Manual 1. Introduction...1 1.1 Customer Service...1 1.2 Standard Equipment...2 1.3 Safety information...2 2. Calibrator Interface and Operation...5 2.1 Milliamp Source...6 2.2 Milliamp

More information

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER! QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Service Bulletin SB685 Date: 8/18/2017 Subject: TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Units: All TriPac EVOLUTION Summary: This bulletin updates and

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

PM Series Power Meter

PM Series Power Meter PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See

More information

Product Manual SZ2141

Product Manual SZ2141 Product Manual SZ11 Refrigeration Controller Communicating Controls Description The SZ11 is a microprocessor-based refrigeration controller and alarm interface designed to control three coolers or freezers

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information

Product Catalog. senseware.co Tysons Boulevard Floor 5 Tysons VA, 22102

Product Catalog. senseware.co Tysons Boulevard Floor 5 Tysons VA, 22102 Product Catalog 2018 senseware.co 571.766.6443 1775 Tysons Boulevard Floor 5 Tysons VA, 22102 TABLE OF CONTENTS Senseware Base Hardware..................................... 2 Environmental Sensors......................................

More information

USER S MANUAL. DAS-G01 The Power of Tomorrow

USER S MANUAL. DAS-G01 The Power of Tomorrow USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 0 USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 Page 1 USER'S MANUAL TABLE OF CONTENTS Page # 1.0 GENERAL INFORMATION...

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

BCM2 Series Branch Circuit Monitors Quick Setup Guide

BCM2 Series Branch Circuit Monitors Quick Setup Guide BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

TT /12b INSTALLATION INSTRUCTIONS. Introduction

TT /12b INSTALLATION INSTRUCTIONS. Introduction TT-1545 11/12b INSTALLATION INSTRUCTIONS Original Issue Date: 6/10 Model: 20-300 kw Generator Sets Market: Industrial Subject: Decision-Maker 3000 Controller Service Replacement Kit GM75376 Introduction

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

AccuTank ULTRASONIC LEVEL MONITORING SYSTEM

AccuTank ULTRASONIC LEVEL MONITORING SYSTEM AccuTank ULTRASONIC LEVEL MONITORING SYSTEM FLO-CORP s AccuTank Ultrasonic Level Monitoring System is the most economical, reliable and accurate remote monitoring system on the market. This affordable

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

V0STAT51P-2 Programmable Wired Controller

V0STAT51P-2 Programmable Wired Controller PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF V0STAT51P-2 Programmable Wired Controller Bulletin No. 210766 March 2016 Grouping - Controller can control up to 16 indoor units on the same

More information

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication. HTC-DIGITAL-LCD Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication. Features Use Australian Made and designed LCD 2 X 16 Character Backlit Display Five Programmable

More information

LC-1 Level Controller & Flow Monitor

LC-1 Level Controller & Flow Monitor The Level Controller and Flow Monitor provides a fully integrated Duplex Controller. The unit allows collecting 'rate of flow' information and the verification of the run time characteristics of the external

More information

PRO VPR100 Series ViPR Multi Channel Monitoring System

PRO VPR100 Series ViPR Multi Channel Monitoring System PRO VPR100 Series ViPR Multi Channel Monitoring System Operation & Maintenance Manual 590 Fisher Station Drive Victor, NY 14564 (800) 999-5290 (585) 924-4650 Internet: www.ctconline.com E-mail: sales@ctconline.com

More information

Multi Units Humidity/Temperature Transmitter. HygroViewer Model JW300 User Manual

Multi Units Humidity/Temperature Transmitter. HygroViewer Model JW300 User Manual Multi Units Humidity/Temperature Transmitter HygroViewer Model JW300 User Manual 1. Electrical Wired & Installation The power cord is a one-meter length, 22 AWG, 7 different colors for recognition. Please

More information

ACTpro Single Door IP Controller. Operating & Installation Instructions

ACTpro Single Door IP Controller. Operating & Installation Instructions ACTpro 1500 Single Door IP Controller Operating & Installation Instructions 18-00079 Issue 1 This manual refers to the ACTpro 1500 a TCP/IP based control unit supporting up to 32 doors. Access Control

More information

HLS34 Modbus FCU/VAV Controllers installation instructions

HLS34 Modbus FCU/VAV Controllers installation instructions HLS34 Modbus FCU/VAV Controllers installation instructions The HLS34 is specifically designed for individual room temperature and zone control applications. The controllers have built-in RS-485 channel

More information

Quantum HD Unity Software Update Procedure

Quantum HD Unity Software Update Procedure Quantum HD Unity Software Update Procedure Read Thoroughly Updating the Operating Software on a Quantum HD Unity is easy and free. Use the following steps to download the update and upload it to your Quantum

More information

Junos WebApp Secure 5.0 Hardware Guide

Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a

More information

BMS Steam Station Solutions

BMS Steam Station Solutions BMS Steam Station Solutions rtk@circor.com www.circorenergy.com Compact Programmable Controller Touch Screen Operator Panel MP-02 CPU Modem / Router Remote management using a SMARTphone Remote management

More information

VLT 2800 DRIVE SPECIFICATIONS

VLT 2800 DRIVE SPECIFICATIONS VLT 2800 DRIVE SPECIFICATIONS Drive Input Power Input voltage 3 phase... 200 through 240, or 380 through 460; 3-phase all ratings 200 through 240, 1-phase through 2 HP Input voltage range for full output...

More information

STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625

STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 September 2011 STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 MATERIAL SPECIFICATIONS FOR WEIGH-IN-MOTION SYSTEM The

More information

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions Product Identification BAPI s Touch Low Range Pressure Sensor with Attached Static Pressure Probe is an accurate, rugged and economical solution for measuring and reporting duct/building static pressure,

More information

How to Improve Energy Efficiency & Reduce Maintenance

How to Improve Energy Efficiency & Reduce Maintenance How to Improve Energy Efficiency & Reduce Maintenance Getting the most from your energy management system John Wallace Emerson Climate Technologies Retail Solutions Discussion Topics Introduction to an

More information

Multi-Point Digital Gas Detection and Control System

Multi-Point Digital Gas Detection and Control System Multi-Point Digital Gas Detection and Control System Specifications subject to change without notice. USA 80308 Page of 0 DESCRIPTION Wall mounted, microprocessor-based, multi-point, RS-85 digital communicating

More information

RTD-NET Installation Instructions

RTD-NET Installation Instructions LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND

More information

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018 Installation Instructions February 12, 2018 OCI415.30 for use with LMV5... Linkageless Burner Management Systems OCI415.30 Description The OCI415.30 provides the LMV5... family of flame controllers with

More information

INTELLI-HOOD TROUBLESHOOTING GUIDE

INTELLI-HOOD TROUBLESHOOTING GUIDE INTELLI-HOOD TROUBLESHOOTING GUIDE Melink Corporation (513) 965-7300 www.melinkcorp.com Last Updated 7/22/2015 Table of Contents Page I. About this Document 2 II. Related Documents 2 III. Glossary of Abbreviations

More information

Installation Manual. DZK BACnet

Installation Manual. DZK BACnet Installation Manual DZK BACnet InterfacepbilCodarPageNumber TABLE OF CONTENTS Page Overview... 5 Outline and Features... 5 System outline... 5 Specifications and device elements... 6 Functional specifications...

More information

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...

More information

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak Control

More information