User Guide. Westermo Teleindustri AB MCW-211. Industrial Ethernet Media Converter.

Size: px
Start display at page:

Download "User Guide. Westermo Teleindustri AB MCW-211. Industrial Ethernet Media Converter."

Transcription

1 User Guide MCW-211 S E R I E S Westermo Teleindustri AB Industrial Ethernet Media Converter

2 Legal information The contents of this document are provided as is. Except as required by applicable law, no warranties of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose, are made in relation to the accuracy and reliability or contents of this document. Westermo reserves the right to revise this document or withdraw it at any time without prior notice. Under no circumstances shall Westermo be responsible for any loss of data or income or any special, incidental, and consequential or indirect damages howsoever caused. More information about Westermo can be found at the following Internet address:

3 Safety!!! Before installation: Read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check that your application does not exceed the safe operating specifications for this unit. This unit should only be installed by qualified personnel. This unit should be built-in to an apparatus cabinet, or similar, where access is restricted to service personnel only. The power supply wiring must be sufficiently fused, and if necessary it must be possible to disconnect manually from the power supply. Ensure compliance to national installation regulations. This unit uses convection cooling.to avoid obstructing the air flow around the unit, follow the spacing recommendations (see Installation section). Before mounting, using or removing this unit: Prevent access to hazardous voltage by disconnecting the unit from power supply. Warning! Do not open connected unit. Hazardous voltage may occur within this unit when connected to power supply. Class 1 Laser Product Do not look directly into fibre optical fibre port or any connected fibre although this unit is designed to meet the Class 1 Laser regulations. Care recommendations Follow the care recommendations below to maintain full operation of unit and to fulfil the warranty obligations. This unit must not be operating with removed covers or lids. Do not attempt to disassemble the unit. There are no user serviceable parts inside. Do not drop, knock or shake the unit, rough handling above the specification may cause damage to internal circuit boards. Do not use harsh chemicals, cleaning solvents or strong detergents to clean the unit. Do not paint the unit. Paint can clog the unit and prevent proper operation. Do not expose the unit to any kind of liquids (rain, beverages, etc). The unit is not waterproof. Keep the unit within the specified humidity levels. Do not use or store the unit in dusty, dirty areas, connectors as well as other mechanical part may be damaged. If the unit is not working properly, contact the place of purchase, nearest Westermo distributor office or Westermo Tech support. Fibre connectors are supplied with plugs to avoid contamination inside the optical port. As long as no optical fibre is mounted on the connector, e.g. for storage, service or transportation, should the plug be applied

4 General This unit is intended for use in Zone 2 hazardous location only. Marking ATEX Information (Applicable for MCW-211 Ex only) II 3 G Ex na IIC T4 Gc SPECIAL CDITI WARNING DO NOT SEPARATE WHEN ENERGIZED Indicate that this unit complies with relevant European standards that are harmonised with the 94/9/EC Directive (ATEX). II 3 G Ex na IIC T4 Gc SPECIAL CDITI Equipment group II. This unit can be installed in all places with an explosive gas atmosphere other than mines susceptible to firedamp Equipment category 3. A category is the classification according to the required level of protection. This unit ensures the requisite level of protection during normal operation and is intended for use in areas in which explosive atmosphere caused by gases, vapours, mists, or dust mixtures are unlikely to occure or, if they do occure, are likely to do so only infrequently and for a short periode only. Indicates protection concerning explosive atmospheres caused by gases, vapours or mists (G). Indicates that this unit is in conformity with relevant European Ex standard(s). Type of protection used. This unit is a non-sparking device "na" which is constructed to minimize the risk of occurence of arcs or sparks capable of creating an ignition hazard during conditions of normal operation. Gas group, a typical gas i hydrogen. Temperature class T4 (T4 = 135 C). This unit is classified in accordance with its maximum surface temperature (external and internal). Equipment protection level Gc (EPL Gc). Equipment for explosive gas atmospheres, having a "enhanced" level of protection, which is not a source of ignition in normal operation and which may have some additional protection to ensure that it remains inactive as an ignition source in the case of regular expected occurences. EPL Gc are analogous to the ATEX Categories (Category 3 G = EPL Gc). This unit has a special condition of use. The special conditon for safe use contains safety related information that is necesarry for the correct installation and safe use

5 Ratings and safety control drawing Power (12 48) VDC; 200 ma Ambient temperature 25ºC Ta +70ºC Maximum surface temperature Temperatur class T4 (max 135 ºC ) Degree of protection IP21 Installation spacing Minimum 25 mm above / below and minimum 10 mm left / right Ethernet TX RJ-45 Position Direction*/ descripton 1 In/Out / TD+ 2 In/Out / TD 3 In/Out / RD+ 4 Not connected 5 Not connected 6 In/Out / RD 7 Not connected 8 Not connected Input/Output values U = ±1 V (4 µv/s) l = ±20 ma Data rate: 10/100 Mbit/s * Galvanically isolated via signal transformers and capacitively isolated to signal ground through 3 kv 470 pf capacitor. Ethernet FX SC, ST or LC Position Direction/ descripton Input/Output values Rx In / Receive port Max optical power = dbm Tx Out / Transmit port Data rate: 100 Mbit/s Power Position Direction/ descripton Input/Output values 1 In / COM U in = (10 60) VDC 2 In / +VA Max l in = VDC 3 In / +VB MaxP In = 3.6 W The FX port is selectable between SC, -ST or -LC connection depending on variant of the model

6 SPECIAL CDITI FOR SAFE USE Ambient temperature: This unit is designed for use in extreme ambient temperature conditions according to the following: 25ºC Ta +70ºC Installation in an apparatus cabinet: This unit requires installation in an Ex certified apparatus cabinet suitable for the area of use and providing a degree of protection of at least IP54. Resistance to impact: This unit requires installation in an apparatus cabinet where adequate resistance to impact is provided by the apparatus cabinet. See "Installation in an apparatus cabinet" above for requirements on the external apparatus cabinet. Resistance to light: This unit requires installation in an apparatus cabinet where it is protected from light (for example daylight or light from luminaires). See "Installation in an apparatus cabinet" above for requirements on the external apparatus cabinet. Secureness of plugs: When this unit is installed in an explosive atmospheres, all connectors must be mechanically secured to prevent loosening. Conductor temperature: When this unit is installed in locations with high ambient temperature, special precautions shall be taken upon the choice of external conductors and the temperature rating of the conductor(s). Directive 94/9/EC alongside with other directives: Directive 2004/108/EC (EMC) applies and to assure a safe performance of this unit under the scope of Directive 94/9/EC, refer to the electromagnetic immunity level specified under "Type tests and environmental conditions" in this manual. Standards and date of compliance EN and EN

7 Note. Fibre Optic Handling Fibre optic equipment needs special treatment. It is very sensitive to dust and dirt. If the fibre will be disconnected from the modem the protective hood on the transmitter/ receiver must be connected. The protective hood must be kept on during transportation. The fibre optic cable must also be handle the same way. If this recommendation not will be followed it can jeopardise the warranty. Cleaning of the optical connectors In the event of contamination, the optical connectors should be cleaned by the use of forced nitrogen and some kind of cleaning stick. Recommended cleaning fluids: Methyl-, ethyl-, isopropyl- or isobutyl-alcohol Hexane Naphtha Maintenance No maintenance is required, as long as the unit is used as intended within the specified conditions. Agency approvals and standards compliance Type EMC Approval / Compliance EN , Immunity industrial environments EN , Emission industrial environments Marine DNV Standard for Certification no. 2.4¹ Ex EN and EN ² Note ¹ Applicable only for , , (MCW-211-SM-LC15, MCW-211-SM-LC40, MCW-211-MM-LC2) ² Applicable only for MCW-211Ex series

8 Declaration of Conformity Westermo Teleindustri AB Declaration of conformity The manufacturer Westermo Teleindustri AB SE Stora Sundby, Sweden Herewith declares that the product(s) Type of product Model Art no Industrial Ethernet Media Converter MCW-211 series , -0010, -0020, -0030, -0040, MCW-211 EX series ,-5010, -5020, -5030, -5040, is in conformity with the following EC directive(s). No Short name 2004/108/EC Electromagnetic Compatibility (EMC) 94/9/EC 1 Equipment Explosive Atmospheres (ATEX) References of standards applied for this EC declaration of conformity. No Title Issue EN Electromagnetic compatibility Immunity for industrial 2005 environments EN Electromagnetic compatibility Emission for industrial 2007 environments EN Explosive atmospheres 2009 Equipment General requirements EN Electrical apparatus for explosive gas atmospheres Construction, test and marking of type of protection n electrical apparatus 2005 The last two digits of the year in which the CE marking was affixed: 11 Pierre Öberg Technical Manager 27 April Applicable for MCW-211 EX series only. Org.nr/ Postadress/Postal address Tel. Telefax Postgiro Bankgiro Corp. identity number Registered office S Stora Sundby Eskilstuna Sweden Int Int

9 Type tests and environmental conditions Electromagnetic Compatibility Phenomena Test Description Level ESD EN Enclosure contact ± 4 kv Enclosure air ± 8 kv RF field AM modulated IEC Enclosure 10 V/m 80% AM (1 khz), MHz Fast transient EN Signal ports ± 1 kv Power ports ± 2 kv Surge EN Signal ports balanced ± 2 kv line to earth, ± 1 kv line to line Power ports ± 2 kv line to earth, ± 2 kv line to line RF conducted EN Signal ports 10 V 80% AM (1 khz), MHz Voltage dips and interruption Power ports 10 V 80% AM (1 khz), MHz EN DC power ports 10 & 100 ms, interruption 10 ms, 30% reduction 10 ms, 60% reduction +20% above & 20% below rated voltage Radiated emission EN Enclosure Class A Conducted emission EN DC power ports Class A Dielectric strength EN Signal port to other isolated ports Environmental Power port to other isolated ports 1.5 kvrms 50 Hz 1 min 2 kvrms 50 Hz 1 min Temperature Operating 25 to +70ºC Maximum surface temperature Storage & Transport 135 C (temperature class T4) 40 to +70ºC Humidity Operating 5 to 95% relative humidity Storage & Transport 5 to 95% relative humidity Altitude Operating m / 70 kpa Service life Operating 10 year Vibration IEC Operating 7.5 mm, 5 8 Hz 2 g, Hz Shock IEC Operating 15 g, 11 ms Packaging Enclosure, MCW-211 UL 94 PC / ABS Flammability class V-1 Enclosure, MCW-211 Ex Cabelec 6141 Dimension W x H x D Weight 35 x 121 x 119 mm 0.25 kg Degree of protection IEC 529 Enclosure IP 21 Cooling Mounting Convection Horizontal on 35 mm DIN-rail

10 Interface specifications Power Rated voltage Operating voltage Rated current Rated frequency Inrush current I2t Startup current* Polarity Redundant power input Isolation to Connection 12 to 48 VDC 10 to 60 VDC VDC VDC VDC DC VDC 0.75 A peak Reverse polarity protected Yes Ethernet TX Ethernet FX Detachable screw terminal Connector size mm² (AWG 24 12) Shielded cable * Direction relative this unit Not required Ethernet TX Electrical specification Data rate Duplex Transmission range Isolation to Connection Ethernet FX Optical specification Data rate Duplex Connection IEEE std Edition 10 Mbit/s or 100 Mbit/s, manual or auto Full or half, manual or auto 100 m Power RJ-45 IEEE std Edition 100 Mbit/s Full or half SC, ST or LC

11 Location of interface ports and LED s LED Indicators (for details see page 13) DIP switches are accessible under the lid Ethernet TX RJ-45 Position Direction* Description 1 In/Out TD+ 2 In/Out TD 3 In/Out RD In/Out RD 7 8 * Direction relative this unit Ethernet FX SC, ST or LC Position Direction* Description Product marking Rx In Receive port Rx Tx Out Transmit port * Direction relative this unit Power Position Direction* Description Tx Product marking 1 Common COM 2 In + Voltage A +VA 3 In + Voltage B +VB * Direction relative this unit

12 Fibre optic power budget Model Transmitted wavelength Min. output power, transmitter Max. output power, transmitter Input sensitivity, receiver Min. power budget Max. power budget Recommended fibre cable and core / cladding diameter MCW-211-MM xx2 MCW-211-SM SC15 MCW-211-SM LC15 MCW-211-SM LC nm 1310 nm 1310 nm 1310 nm 19 dbm 15 dbm 15 dbm 5 dbm 12 dbm 8 dbm 8 dbm 0 dbm 31 dbm 34 dbm 31 dbm 34 dbm 12 dbm 19 dbm 16 dbm 29 dbm 19 dbm 26 dbm 23 dbm 34 dbm Multimode 50/125, 62.5/125 Singlemode 9/125, 10/125 Singlemode 9/125, 10/125 Singlemode 9/125, 10/125 Fibre type Normal 1310 nm multimode Normal 1310 nm singlemode 50/ dbm/km 62,5/ dbm/km 9/ dbm/km 10/ dbm/km Attenuation in connectors / splices Type Connector Fusion splice Mechanical splice Normal attenuation dbm 0.1 dbm 0.2 dbm

13 LED indicators LED indicators are available on the front panel and on the RJ-45 TX connector. LED Status Description PWR Internal power, initialising OK Slow flash Fast flash Initialisation progressing Initialisation error LINK TX OFF No Ethernet link TX Flash Good Ethernet link TX Ethernet data is transmitted or received on TX interface LINK FX OFF No Ethernet link FX Flash Good Ethernet link FX Ethernet data is transmitted or received on FX interface FX DPX OFF Half dupex FX interface Full duplex FX interface LFF OFF Link fault forward is not active Link fault forward is active and has shutdown an interface LED Status Description SPD OFF 10 Mbit/s TX interface 100 Mbit/s TX interface DPX OFF Half duplex TX interface Full duplex TX interface SPD TX DPX

14 ! Installation Mounting / Removal Before mounting or removing the unit: Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap). Prevent access to hazardous voltages by disconnecting the unit from AC/DC mains supply and all other electrical connections. Mounting This unit should be mounted on 35 mm DIN-rail which is horizontally mounted on a wall or cabinet backplate. This unit uses convection cooling. To avoid obstructing the airflow around the unit, use the following spacing rules. Recommended spacing 25 mm (1.0 inch) above/below and 10 mm (0.4 inches) left/right the unit. Snap on mounting, see figure 10 mm * (0.4 inches) 25 mm CLICK! * Spacing (left/right) recommended for full operating temperature range 25 mm Removal Press down the black support at the back of the unit, see figure

15 Configuration DIP switches are accessible under the lid on top of the unit. DIP switches are used to configure the unit.! DIP-switch settings Before DIP-switch settings: Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap). NOTE DIP-switch alterations are only effective after a power on. To be observe when the DIP-switches will be configured Speed and duplex setting only valid when auto-negotiation is disabled. If auto-negotiation and auto MDI/MDI-X disabled the TX ports supports MDI-X configuration

16 TX Port settings Flow control setting Auto-negotiation and auto MDI / MDI-X disabled TX port Flow control disabled Auto-negotiation and auto MDI / MDI-X enabled TX port Flow control enabled 10 Mbit/s speed selected TX port Link fault forward settings 100 Mbit/s speed selected TX port TX FX Link fault forward disabled Half duplex selected TX port TX FX Link fault forward enabled Full duplex selected TX port FX TX Link fault forward disabled FX Port settings FX TX Link fault forward enabled Half duplex selected FX port Factory settings Full duplex selected FX port

17

18

19

20 Westermo Teleindustri AB SE Stora Sundby, Sweden Phone Fax Westermo Web site: Sales Units Sweden Westermo Data Communications AB Svalgången 1 SE Västerås Phone: +46 (0) Fax: +46 (0) info.sverige@westermo.se United Kingdom Westermo Data Communications Ltd Talisman Business Centre Duncan Road Park Gate, Southampton SO31 7GA Phone: +44(0) Fax.:+44(0) sales@westermo.co.uk Germany Westermo Data Communications GmbH Goethestraße 67, Waghäusel Tel.: +49(0) Fax.:+49(0) info@westermo.de France Westermo Data Communications S.A.R.L. 9 Chemin de Chilly CHAMPLAN Tél : Fax : infos@westermo.fr Singapore Westermo Data Communications Pte Ltd 2 Soon Wing Road #08-05 Soon Wing Industrial Building Singapore Phone Fax sales@westermo.com.sg North America Westermo Data Communications 939 N. Plum Grove Road, Suite F Schaumburg Chicago Phone: Fax: info@westermo.com Taiwan Westermo Data Communications Co F2, No. 188, Pao-Chiao Rd. Shing-Tien City Taipei Phone: info@westermo.com Westermo Teleindustri AB have distributors in several countries, contact us for further information. REV.A Westermo Teleindustri AB, Sweden A Beijer Electronics Group Company

User Guide. Westermo Teleindustri AB 2004 REV.A SDW Industrial Ethernet 5-port Switch.

User Guide. Westermo Teleindustri AB 2004 REV.A SDW Industrial Ethernet 5-port Switch. User Guide SDW-500 S E R I E S 6644-2211 Westermo Teleindustri AB 2004 REV.A Industrial Ethernet 5-port Switch www.westermo.com Contents 1. Description... 3 2. Safety... 4 3. Approvals... 4 3.1 Declaration

More information

User Guide Westermo Teleindustri AB SDW-500. Industrial Ethernet 5-port Switch.

User Guide Westermo Teleindustri AB SDW-500. Industrial Ethernet 5-port Switch. User Guide 6644-2214 SDW-500 S E R I E S Westermo Teleindustri AB Industrial Ethernet 5-port Switch www.westermo.com Software tools Related software tools are available in the folder software tools under

More information

800xA Networks. NE801 User Manual. Power and productivity for a better worldtm

800xA Networks. NE801 User Manual. Power and productivity for a better worldtm 800xA Networks NE801 User Manual Power and productivity for a better worldtm 800xA Networks NE801 User Manual NOTICE This document contains information about one or more ABB products and may include a

More information

INSTALLATIONSANVISNING INSTALLATION MANUAL INSTALLATIONS ANLEITUNG MANUEL D INSTALLATION RD-48 LV/HV. RS-422/485 Repeater Répéteur RS-422/485

INSTALLATIONSANVISNING INSTALLATION MANUAL INSTALLATIONS ANLEITUNG MANUEL D INSTALLATION RD-48 LV/HV. RS-422/485 Repeater Répéteur RS-422/485 LV/HV INSTALLATISANVISNING INSTALLATI MANUAL INSTALLATIS ANLEITUNG MANUEL D INSTALLATI Westermo Teleindustri AB 2004 REV. C Galvanic Isolation Transient Protection Balanced Transmission CE Approved RS-422/485

More information

User Guide. Westermo Teleindustri AB TD-29 DC. FSK-modem Multidrop 2-wire.

User Guide. Westermo Teleindustri AB TD-29 DC. FSK-modem Multidrop 2-wire. User Guide 6611-2002 TD-29 DC Westermo Teleindustri AB FSK-modem Multidrop 2-wire www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable law,

More information

User Guide. Westermo Teleindustri AB RV-07B. 19 rack system PS-20 Power card.

User Guide. Westermo Teleindustri AB RV-07B. 19 rack system PS-20 Power card. User Guide 6130-2200 RV-07B Westermo Teleindustri AB 19 rack system PS-20 Power card www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable

More information

ODW-641. Industrial Converter PROFIBUS DP to Fibre Optic Link. Point to Point applications. Fibre Optic Modem. User Guide

ODW-641. Industrial Converter PROFIBUS DP to Fibre Optic Link. Point to Point applications. Fibre Optic Modem. User Guide User Guide 6650-2291 ODW-641 Fibre Optic Modem Westermo Teleindustri AB Industrial Converter PROFIBUS DP to Fibre Optic Link. Point to Point applications www.westermo.com Legal information The contents

More information

MCW-211-F1G-T1G. Industrial Ethernet Media Converter.

MCW-211-F1G-T1G. Industrial Ethernet Media Converter. MCW-211-F1G-T1G Industrial Ethernet Media Converter www.westermo.com 2 6645-2211 General information Legal information The contents of this document are provided as is. Except as required by applicable

More information

User Guide. Westermo Teleindustri AB DDW-100. Industrial Ethernet SHDSL Extender.

User Guide. Westermo Teleindustri AB DDW-100. Industrial Ethernet SHDSL Extender. User Guide 6621-2202 DDW-100 Westermo Teleindustri AB Industrial Ethernet SHDSL Extender www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable

More information

ODW-621 Fibre Optic Modem

ODW-621 Fibre Optic Modem User Guide 6650-2222 ODW-621 Fibre Optic Modem Westermo Teleindustri AB Industrial Converter Serial RS-232 to fibre optic link Point-to-point applications www.westermo.com Legal information The contents

More information

User Guide. Westermo Teleindustri AB DDW-220. Wolverine series DDW-220. Industrial Ethernet SHDSL extender.

User Guide. Westermo Teleindustri AB DDW-220. Wolverine series DDW-220. Industrial Ethernet SHDSL extender. User Guide 6642-22005 DDW-220 Wolverine series Westermo Teleindustri AB DDW-220 Industrial Ethernet SHDSL extender www.westermo.com Legal information The contents of this document are provided as is. Except

More information

ODW-622 Fibre Optic Modem

ODW-622 Fibre Optic Modem User Guide 6650-2233 ODW-622 Fibre Optic Modem Westermo Teleindustri AB Industrial Converter RS-232 to Fibre Optic Link. Repeater, line and redundant ring www.westermo.com Legal information The contents

More information

Lynx. Industrial Ethernet 10-port Switch L110 / L210. User Guide

Lynx. Industrial Ethernet 10-port Switch L110 / L210. User Guide User Guide 6643-2213 WeOS Lynx L110 / L210 Westermo Teleindustri AB Industrial Ethernet 10-port Switch www.westermo.com License Information This device contains public available software which is under

More information

AD-01 M-BUS Adapter. Industrial adapter, M-bus, Repeater, Converter and zone controller.

AD-01 M-BUS Adapter. Industrial adapter, M-bus, Repeater, Converter and zone controller. AD-01 M-BUS Adapter Industrial adapter, M-bus, Repeater, Converter and zone controller www.westermo.com 2 6612-2202 General information Legal information The contents of this document are provided as is.

More information

User Guide. Westermo Teleindustri AB DDW-120. Industrial Ethernet SHDSL Extender.

User Guide. Westermo Teleindustri AB DDW-120. Industrial Ethernet SHDSL Extender. User Guide 6621-2214 DDW-120 Westermo Teleindustri AB Industrial Ethernet SHDSL Extender www.westermo.com Software tools Related software tools are available in the folder software tools under technical

More information

Viper port Ethernet M12 switch. User Guide Westermo Teleindustri AB. X1 X5 X9 X6 X10 X7 X11 SRV 1 X2 X8 X12 DC X4

Viper port Ethernet M12 switch. User Guide Westermo Teleindustri AB.   X1 X5 X9 X6 X10 X7 X11 SRV 1 X2 X8 X12 DC X4 User Guide 6641-2241 Viper-12 s e r i e s Westermo Teleindustri AB X1 X5 X9 SRV 1 X2 SRV 2 X3 X6 X10 X7 X11 DC X4 X8 X12 X1 X5 X9 ON USB RSTP FRNT X2 X3 X6 X10 X7 X11 CON DC X4 X8 X12 12-port Ethernet

More information

User Guide Westermo Teleindustri AB DDW-100. Industrial Ethernet SHDSL Extender.

User Guide Westermo Teleindustri AB DDW-100. Industrial Ethernet SHDSL Extender. User Guide 6621-2202 DDW-100 Westermo Teleindustri AB Industrial Ethernet SHDSL Extender www.westermosales.com Legal information The contents of this document are provided as is. Except as required by

More information

User Guide. Westermo Teleindustri AB DDW-220 WOLVERINE SERIES DDW-220. Industrial Ethernet SHDSL extender.

User Guide. Westermo Teleindustri AB DDW-220 WOLVERINE SERIES DDW-220. Industrial Ethernet SHDSL extender. User Guide 6642-22005 DDW-220 WOLVERINE SERIES Westermo Teleindustri AB DDW-220 Industrial Ethernet SHDSL extender www.westermo.com Software tools Related software tools are available in the folder software

More information

User Guide Westermo Teleindustri AB. Lynx SERIES. Industrial Ethernet 8-port Switch.

User Guide Westermo Teleindustri AB. Lynx SERIES. Industrial Ethernet 8-port Switch. User Guide 6640-2001 Lynx SERIES Westermo Teleindustri AB Industrial Ethernet 8-port Switch www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable

More information

User Guide. Westermo Teleindustri AB Lynx DSS. WeOS. Industrial Ethernet Device Server Switch.

User Guide. Westermo Teleindustri AB Lynx DSS. WeOS. Industrial Ethernet Device Server Switch. User Guide 6643-2220 WeOS Lynx DSS Westermo Teleindustri AB Industrial Ethernet Device Server Switch www.westermo.com License Information This device contains public available software which is under the

More information

User Guide Westermo Teleindustri AB. Lynx SERIES. Industrial Ethernet 8-port Switch.

User Guide Westermo Teleindustri AB. Lynx SERIES. Industrial Ethernet 8-port Switch. User Guide 0-0 SERIES Westermo Teleindustri AB Industrial Ethernet -port Switch www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable law,

More information

User Guide. Westermo Teleindustri AB Lynx L110 / L210. WeOS. Industrial Ethernet 10-port Switch.

User Guide. Westermo Teleindustri AB Lynx L110 / L210. WeOS. Industrial Ethernet 10-port Switch. User Guide 6643-2213 WeOS Lynx L110 / L210 Westermo Teleindustri AB Industrial Ethernet 10-port Switch www.westermo.com Safety! Warning Do not open connected unit. Hazardous voltage may occur within this

More information

DDW-002-B1. EN Ethernet Broadband Bridge. User Guide Westermo Teleindustri AB. 10/100 BASE-TX LINK DC1 X1 X1 DC2

DDW-002-B1. EN Ethernet Broadband Bridge. User Guide Westermo Teleindustri AB.   10/100 BASE-TX LINK DC1 X1 X1 DC2 User Guide 6641-2280 DDW-002-B1 Westermo Teleindustri AB 10/100 BASE-TX LINK DC1 X1 X1 DC2 LINK STATUS ACTIVITY LINK MASTER ON POWER M12 Torque 0,6±0,1Nm / 0,45±0,1 lbft EN 50155 Ethernet Broadband Bridge

More information

User Guide. Westermo Teleindustri AB RedFox. Ethernet switch and router approved for railway usage.

User Guide. Westermo Teleindustri AB RedFox. Ethernet switch and router approved for railway usage. User Guide 6641-2223 RedFox R A I L Westermo Teleindustri AB Ethernet switch and router approved for railway usage www.westermo.com Software tools Related software tools are available in the folder software

More information

User Guide. Westermo Teleindustri AB Lynx L110 / L210. WeOS. Industrial Ethernet 10-port Switch.

User Guide. Westermo Teleindustri AB Lynx L110 / L210. WeOS. Industrial Ethernet 10-port Switch. User Guide 6643-2213 WeOS Lynx L110 / L210 Westermo Teleindustri AB Industrial Ethernet 10-port Switch www.westermo.com Safety! Warning Do not open connected unit. Hazardous voltage may occur within this

More information

User Guide. Westermo Teleindustri AB DDW-226 WOLVERINE SERIES. WeOS. Industrial Ethernet SHDSL extender.

User Guide. Westermo Teleindustri AB DDW-226 WOLVERINE SERIES. WeOS. Industrial Ethernet SHDSL extender. User Guide 6642-22402 WeOS DDW-226 WOLVERINE SERIES Westermo Teleindustri AB Industrial Ethernet SHDSL extender www.westermo.com Software tools Related software tools are available in the folder software

More information

Legacy Serial. Legacy Serial Redundant Ring Ethernet Extender DDW-222. High Speed Ethernet extension over copper. Configuration and diagnostics

Legacy Serial. Legacy Serial Redundant Ring Ethernet Extender DDW-222. High Speed Ethernet extension over copper. Configuration and diagnostics Redundant Ring Ethernet Extender High Speed Ethernet extension over copper The is an Industrial Ethernet SH extender with support for redundant rings. The redundant protocol can be used either on the SH

More information

User Guide. Westermo Teleindustri AB RedFox Industrial. WeOS. Industrial Routing Switch.

User Guide. Westermo Teleindustri AB RedFox Industrial. WeOS. Industrial Routing Switch. User Guide 664-0 WeOS RedFox Industrial s e r i e s Westermo Teleindustri AB Industrial Routing Switch www.westermo.com License Information This device contains public available software which is under

More information

User Guide. Westermo Teleindustri AB Lynx DSS L105-S1/L205-S1. WeOS. Industrial Ethernet 5-port Device Server Switch.

User Guide. Westermo Teleindustri AB Lynx DSS L105-S1/L205-S1. WeOS. Industrial Ethernet 5-port Device Server Switch. User Guide 6643-2230 WeOS Lynx DSS L105-S1/L205-S1 Westermo Teleindustri AB Industrial Ethernet 5-port Device Server Switch www.westermo.com Software tools Related software tools are available in the folder

More information

User Guide. Westermo Teleindustri AB Lynx DSS L106-S2/L206-S2. WeOS. Industrial Ethernet 6-port Device Server Switch.

User Guide. Westermo Teleindustri AB Lynx DSS L106-S2/L206-S2. WeOS. Industrial Ethernet 6-port Device Server Switch. User Guide 6643-2240 WeOS Lynx DSS L106-S2/L206-S2 Westermo Teleindustri AB Industrial Ethernet 6-port Device Server Switch www.westermo.com Software tools Related software tools are available in the folder

More information

User Guide. Westermo Teleindustri AB RedFox Industrial. WeOS. Industrial Routing Switch.

User Guide. Westermo Teleindustri AB RedFox Industrial. WeOS. Industrial Routing Switch. User Guide 66-0 WeOS RedFox Industrial S E R I E S Westermo Teleindustri AB Industrial Routing Switch www.westermo.com Software tools Related software tools are available in the folder software tools under

More information

User Guide. Westermo Teleindustri AB 2006 EDW Serial Adapter.

User Guide. Westermo Teleindustri AB 2006 EDW Serial Adapter. User Guide EDW-100 6616-2202 Westermo Teleindustri AB 2006 Serial Adapter www.westermo.com Safety!! Before installation: Read this manual completely and gather all information on the unit. Make sure that

More information

RedFox Industrial Series

RedFox Industrial Series www.westermo.com RedFox Industrial Series Industrial Routing Switch WeOS 66-0 General information Legal information The contents of this document are provided as is. Except as required by applicable law,

More information

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4

More information

User Guide Westermo Teleindustri AB EDW-100. Serial Adapter.

User Guide Westermo Teleindustri AB EDW-100. Serial Adapter. User Guide 6616-2203 EDW-100 Westermo Teleindustri AB Serial Adapter www.westermo.com Software tools Related software tools are available in the folder software tools under technical support on the Westermo

More information

User Guide Westermo Teleindustri AB TDW-33. DIN-rail Tele V.90 modem.

User Guide Westermo Teleindustri AB TDW-33. DIN-rail Tele V.90 modem. User Guide 6619-2202 TDW-33 Westermo Teleindustri AB DIN-rail Tele V.90 modem www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable law,

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features

More information

RedFox Industrial Rack Series

RedFox Industrial Rack Series www.westermo.com RedFox Industrial Rack Series Industrial Routing Switch Digital In- Digital In+ Status- Status+ WeOS 2 6641-22810 General information Legal information The contents of this document are

More information

User Guide. Westermo Teleindustri AB Lynx DSS L108 / L208-F2G-S2. WeOS. Industrial Ethernet 8-port Device Server Switch.

User Guide. Westermo Teleindustri AB Lynx DSS L108 / L208-F2G-S2. WeOS. Industrial Ethernet 8-port Device Server Switch. User Guide 6643-2220 WeOS Lynx DSS L108 / L208-F2G-S2 Westermo Teleindustri AB Industrial Ethernet 8-port Device Server Switch www.westermo.com Safety! Warning Do not open connected unit. Hazardous voltage

More information

RuggedMC RMC RUGGEDCOM ISO 9001 REGISTERED. Features and Benefits. Ethernet Media Converter (Copper to Fiber) Universal Power Supply Options

RuggedMC RMC RUGGEDCOM ISO 9001 REGISTERED. Features and Benefits. Ethernet Media Converter (Copper to Fiber) Universal Power Supply Options Features and Benefits The RuggedMC is an industrially hardened fiber optical media converter specifically designed to operate in harsh environments such as those found in electric utility substations and

More information

Industry Line. Ethernet Solutions for Building Automation Systems and CCTV Surveillance Applications

Industry Line. Ethernet Solutions for Building Automation Systems and CCTV Surveillance Applications Industry Line Ethernet Solutions for Building Automation Systems and CCTV Surveillance Applications Westermo Worldwide... Produced by: Westermo Teleindustri AB Specifications are subject to change without

More information

RuggedMC RMC40 RUGGEDCOM ISO 9001 REGISTERED. Features and Benefits. 4-Port Ethernet Media and Speed Converter

RuggedMC RMC40 RUGGEDCOM ISO 9001 REGISTERED. Features and Benefits. 4-Port Ethernet Media and Speed Converter Features and Benefits 4-Ethernet Ports with Optional Dual Fiber Optics Three configurations to choose from: z2 10/100TX ports + 1 100FX port (SC/ST) z2 10/100TX ports + 2 100FX port (MTRJ/LC) z4 10/100TX

More information

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015)

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015) SMM Series 3G and GSM Modems Quick Start Guide Document Number: 0013-001-000272 () Documentation Control Generation Date: October 20, 2015 Cybertec Pty Limited All rights Reserved. No part of this publication

More information

User Guide. Westermo Teleindustri AB BRD-355. Industrial ADSL/VDSL Router.

User Guide. Westermo Teleindustri AB BRD-355. Industrial ADSL/VDSL Router. User Guide 6623-2232 BRD-355 Westermo Teleindustri AB Industrial ADSL/VDSL Router www.westermo.com Legal information The contents of this document are provided as is. Except as required by applicable law,

More information

Viper 20A Series. 20 port Ethernet M12 switches. User Guide REV. C. Westermo Teleindustri AB. X9 X15 X16 X17 X10 X11

Viper 20A Series. 20 port Ethernet M12 switches. User Guide REV. C. Westermo Teleindustri AB.  X9 X15 X16 X17 X10 X11 User Guide 6641-22531 REV. C Viper 20A Series Westermo Teleindustri AB X3 X9 X15 X3 X9 X15 X1 X2 X4 X5 X1 X2 X10 X11 X4 X5 X16 X17 X10 X11 X16 X17 ON RSTP FRNT DC USB CON 24-110 V DC X6 X7 X8 ON USB RSTP

More information

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

Wolverine DDW DDW Industrial Ethernet Extender WeOS

Wolverine DDW DDW Industrial Ethernet Extender WeOS www.westermo.com Wolverine DDW-142-485 DDW-242-485 Industrial Ethernet Extender WeOS 2 6642-22511 General information Legal information The contents of this document are provided as is. Except as required

More information

TU531, TU532 Terminal Unit

TU531, TU532 Terminal Unit Ordering Data DATA SHEET TU531, TU532 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 217 200 R0001 1SAP 217 000 R0001 1SAP 417 000 R0001 TU531, terminal unit, 230 VAC,

More information

AO523 Analog Input Module

AO523 Analog Input Module Ordering Data DATA SHEET AO523 Analog Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 200 R0001 1SAP 450 200 R0001 AO523, analog output module, 16 AO, U/I, 12 bits

More information

IMC-101 Series Quick Installation Guide

IMC-101 Series Quick Installation Guide IMC-101 Series Quick Installation Guide Moxa Industrial Media Converter Edition 9.1, June 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777

More information

Series AME25-JZ 25 Watt AC-DC / DC-DC Converter

Series AME25-JZ 25 Watt AC-DC / DC-DC Converter FEATURES: Click on Series name for product info on aimtec.com Series AME-JZ I/O Isolation 000VAC Low Ripple and Noise Operating Temp: -0 C to +70 C Over Voltage Protection Over current Protection Up to

More information

CompactBlock Guard I/O EtherNet/IP Safety Modules

CompactBlock Guard I/O EtherNet/IP Safety Modules Installation Instructions CompactBlock Guard I/O EtherNet/IP Safety Modules Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16 Topic Page Important User Information 2 North American Hazardous Location Approval

More information

Quick Start Guide Elinx ESW100 Series. 5 and 8 port Unmanaged Ethernet Switch

Quick Start Guide Elinx ESW100 Series. 5 and 8 port Unmanaged Ethernet Switch Quick Start Guide Elinx ESW100 Series 5 and 8 port Unmanaged Ethernet Switch ESW100 Series Documentation Number: ESW100series-1112qsg International Headquarters: 707 Dayton Road Ottawa, IL 61350 USA Phone

More information

Chrome DIN Rail Power Supply 5V 7.5W 1 Phase (Class II & NEC Class 2) / DRC-5V10W1AZ

Chrome DIN Rail Power Supply 5V 7.5W 1 Phase (Class II & NEC Class 2) / DRC-5V10W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description I/O extension module, eight digital transistor outputs Data sheet 105364_en_00 PHOENIX CONTACT 2013-03-26 1 Description The I/O extension module can be used in conjunction with Radioline wireless modules

More information

INDUSTRIAL 1000BASE-T TO 1000BASE-X MEDIA CONVERTERS. KCD-400 Series. Installation Guide

INDUSTRIAL 1000BASE-T TO 1000BASE-X MEDIA CONVERTERS. KCD-400 Series. Installation Guide INDUSTRIAL 1000BASE-T TO 1000BASE-X MEDIA CONVERTERS KCD-400 Series Installation Guide DOC.060227-KCD-400-1- (C) 2005 KTI Networks Inc. All rights reserved. No part of this documentation may be reproduced

More information

Viper-12A. 12 port Ethernet M12 switch. User Guide Westermo Teleindustri AB. ON USB X2 X3 RSTP FRNT CON V ON USB

Viper-12A. 12 port Ethernet M12 switch. User Guide Westermo Teleindustri AB.   ON USB X2 X3 RSTP FRNT CON V ON USB User Guide 6641-22511 Viper-12A S E R I E S Westermo Teleindustri AB X1 X5 X9 ON USB RSTP FRNT CON ON USB RSTP FRNT CON X4 X1 X2 X3 24-110V X2 X3 X4 24-110V 1000BASE-T 1000BASE-T X5 X9 X6 X10 X7 X11 X8

More information

ICF-1150 Series Quick Installation Guide

ICF-1150 Series Quick Installation Guide ICF-1150 Series Quick Installation Guide Fifth Edition, July 2015 2015 Moxa Inc. All rights reserved. P/N: 1802011500014 1802011500014 Overview Introduction ICF-1150 series fiber converters have a multi-interface

More information

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description Repeater power supply, active Data sheet 09_en_0 PHOENIX CONTACT 0--0 Description The. mm wide... repeater power supply supplies transmitters in the field and electrically isolates the input signal from

More information

AI561 Analog Input Module

AI561 Analog Input Module Ordering Data DATA SHEET AI561 Analog Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R1101 AI561, analog input module, 4 AI, U/I 1TNE 968 901 R3101 1TNE 968

More information

Industrial Routing Switch

Industrial Routing Switch Industrial Routing Switch RFI-14-F4G The RedFox is a high performance industrial Ethernet switch with enhanced routing functionality, in a single robust box. A single RedFox allows you to build cost effective,

More information

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069 D09S09 D09D09 INSTRUCTION MANUAL SIL Relay Output Module DINRail Models D09S09, D09D09 D0909 SIL Relay Output Module ISM00 SIL Applications For Safety Related System and SIL, SIL Applications according

More information

D1093S INSTRUCTION MANUAL. D SIL 3 Relay Output Module with Line and Load diagnostics. DIN-Rail Model D1093S

D1093S INSTRUCTION MANUAL. D SIL 3 Relay Output Module with Line and Load diagnostics. DIN-Rail Model D1093S D109S INSTRUCTION MANUAL SIL Relay Output Module with Line and diagnostics DINRail Model D109S D109 SIL Relay Output Module with Line and diagnostics ISM0096 SIL Applications For Safety Related System

More information

AO561 Analog Output Module

AO561 Analog Output Module Ordering Data DATA SHEET AO561 Analog Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R1201 AO561, analog output module, 2 AO, U/I 1TNE 968 901 R3102 Terminal

More information

Series AMEPR60C-AZ up to 5A AC-DC / DC-DC LED Driver / Converter

Series AMEPR60C-AZ up to 5A AC-DC / DC-DC LED Driver / Converter Click on Series name for product info on aimtec.com Series AMEPRC-AZ Models Single output Model Max Output Power (W) 1 FEATURES: Output Voltage Range (V) 3 Output Current 3 AMEPRC-120AZ 36-0 - 1.20 AMEPRC-361AZ

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

AX521 Analog Input/Output Module

AX521 Analog Input/Output Module Ordering Data DATA SHEET AX521 Analog Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 100 R0001 1SAP 450 100 R0001 AX521, analog input/output module, 4 AI,

More information

Series AME5-CJZ 5 Watt AC-DC / DC-DC Converter

Series AME5-CJZ 5 Watt AC-DC / DC-DC Converter Click on Series name for product info on aimtec.com FEATURES: I/O Isolation 000V Continuous Short circuit protection Operating Temp: -2 C to 0 C Energy Star compliant Input: -26V, -6Hz, or 20-0VDC pact

More information

MRD-350. Industrial Mobile Broadband Router GSM / GPRS / EDGE / 3G / HSDPA / HSUPA / HSPA. User Guide

MRD-350. Industrial Mobile Broadband Router GSM / GPRS / EDGE / 3G / HSDPA / HSUPA / HSPA. User Guide User Guide 6623-2221 MRD-350 Westermo Teleindustri AB Industrial Mobile Broadband Router GSM / GPRS / EDGE / 3G / HSDPA / HSUPA / HSPA www.westermo.com Legal information The contents of this document are

More information

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

CM597 Ethernet Communication Module

CM597 Ethernet Communication Module Ordering Data DATA SHEET CM597 Ethernet Communication Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 173 700 R0001 1SAP 373 700 R0001 CM597-ETH, communication module Ethernet

More information

TF501, TF521 Terminal Bases

TF501, TF521 Terminal Bases Ordering Data DATA SHEET TF501, TF521 Terminal Bases 1 Ordering Data Part No. Scope of delivery Product life cycle status 1SAP 117 000 R0271 1SAP 317 000 R0271 1SAP 117 200 R0271 1SAP 317 200 R0271 TF501-CMS,

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

Series AMEL10-MJZ 10 Watt AC-DC / DC-DC Converter

Series AMEL10-MJZ 10 Watt AC-DC / DC-DC Converter Click on Series name for product info on aimtec.com Models Single output Model Input Voltage (VAC/Hz) FEATURES: Input Voltage (VDC) Max Output wattage (W) Output Voltage (V) Output Current max (A) Maximum

More information

AX522 Analog Input/Output Module

AX522 Analog Input/Output Module Ordering Data DATA SHEET AX522 Analog Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 000 R0001 1SAP 450 000 R0001 AX522, analog input/output module, 8 AI

More information

Quick Start Guide Elinx ESW200 Series. 5 and 8 port Unmanaged Ethernet Switch

Quick Start Guide Elinx ESW200 Series. 5 and 8 port Unmanaged Ethernet Switch Quick Start Guide Elinx ESW200 Series 5 and 8 port Unmanaged Ethernet Switch ESW200 Series Documentation Number: ESW200series-1112qsg International Headquarters: 707 Dayton Road Ottawa, IL 61350 USA Phone

More information

Stride SE2 Series Unmanaged Industrial Ethernet Switches and Media Converters

Stride SE2 Series Unmanaged Industrial Ethernet Switches and Media Converters Ethernet Switches and Media Converters SE2 Series DIN Rail mounted switches Features Broadcast storm protection Wide temp range option Optional panel mounting accessory 12, 24, 48 VDC & 18-30 VAC redundant

More information

Rugged MediaConverter

Rugged MediaConverter Rugged MediaConverter Installation Guide RuggedCom Inc. 30 Whitmore Road, Woodbridge, Ontario Canada L4L 7Z4 Web: http://www.ruggedcom.com/ Tel: (905) 856-5288 Fax: (905) 856-1995 Toll Free: (888) 264-0006

More information

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN Highlights & Features Full corrosion resistant Aluminium chassis Suitable for 24V system up to 40A Built-in diagnostic monitoring for DC OK, Discharge and Battery Fail by relay contacts LED indicator for

More information

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1A

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1A Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections Data sheet 3379_en_B 1 Description PHOENIX CONTACT 2015-07-14 2 Features Media converters provide

More information

ICF-1150 Series Quick Installation Guide

ICF-1150 Series Quick Installation Guide ICF-1150 Series Quick Installation Guide Second Edition, March 2012 2012 Moxa Inc. All rights reserved. P/N: 1802011500011 Overview Introduction The ICF-1150 series fiber converters are equipped with a

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1 Power Supply, Primary Switch Mode, arrow Design -PS-100-240AC/24/1 POWER provides: Extra narrow widths of 22.5, 45, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide range input A high

More information

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S D5090S INSTRUCTI MANUAL 4 A Relay Output Module for NE, DIN-Rail and Termination Board, Model D5090S D5090-4 A Relay Output Module for NE G.M. International ISM09-3 Characteristics General Description:

More information

Industrial Serial RS-232 to Fiber Converter. KSC-200 Series. Installation Guide

Industrial Serial RS-232 to Fiber Converter. KSC-200 Series. Installation Guide Industrial Serial RS-232 to Fiber Converter KSC-200 Series Installation Guide DOC.100803-KSC-200-1- (C) 2006 KTI Networks Inc. All rights reserved. No part of this documentation may be reproduced in any

More information

RTU500 series Data Sheet Power Supply CP-E 24/2.5

RTU500 series Data Sheet Power Supply CP-E 24/2.5 Data Sheet Power Supply CP-E 24/2.5 Power Supply CP-E 24/2.5 Application The primary switch mode power supply offers two voltage input ranges. This enables the supply with AC or DC. Furthermore it is equipped

More information

Series AME10-VZ 10 Watt AC-DC / DC-DC Converter

Series AME10-VZ 10 Watt AC-DC / DC-DC Converter Click on Series name for product info on aimtec.com FEATURES: Picture Coming Soon I/O Isolation 000VAC Continuous Short circuit protection Operating Temp: -0 C to + C Energy Star compliant Input: -VAC,

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

FLEX Ex Spring Clamp Terminal Base

FLEX Ex Spring Clamp Terminal Base Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification

More information

Perle IDS-108F(XT) Unmanaged 10/100 Ethernet Switches. Installation Guide. P/N (Rev G)

Perle IDS-108F(XT) Unmanaged 10/100 Ethernet Switches. Installation Guide. P/N (Rev G) Perle IDS-108F(XT) Unmanaged 10/100 Ethernet Switches Installation Guide P/N 5500339-10 (Rev G) Overview This document contains instructions necessary for the installation and operation of the Perle IDS-108F

More information

Chrome Class II DIN Rail Power Supply 24V 10W 1 Phase (NEC Class 2 & Household) / DRC-24V10W1HZ

Chrome Class II DIN Rail Power Supply 24V 10W 1 Phase (NEC Class 2 & Household) / DRC-24V10W1HZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Household appliance approvals IEC/EN 60335-1 4kV Electrical Fast Transient / Burst Universal AC input voltage

More information

1756 ControlLogix Chassis Specifications

1756 ControlLogix Chassis Specifications Technical Data 1756 ControlLogix Chassis Specifications Catalog Numbers 1756-A4/B, 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B, 1756-A4LXT, 1756-A5XT, 1756-A7LXT, 1756-A7XT Topic Page Standard ControlLogix

More information

Series AMER120-AZ up to 5A AC-DC / DC-DC LED Driver / Converter

Series AMER120-AZ up to 5A AC-DC / DC-DC LED Driver / Converter Click on Series name for product info on aimtec.com Series AMER120-AZ FEATURES: AC-DC Constant Current or Constant Over Current Protection Voltage LED Driver Short Circuit Protection Input range 90-305VAC/47-440Hz

More information

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 80.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

General. 5 and 8 port Fast Ethernet switches. 6 and 8 Port Gigabit Ethernet switches. Switches with fiber uplink

General. 5 and 8 port Fast Ethernet switches. 6 and 8 Port Gigabit Ethernet switches. Switches with fiber uplink Entry Line Industrial Gigabit Ethernet Switch 4x 10/100/1000Base-T with PoE+, 1x 10/100/1000Base-T or 100/1000Base-X Combo Port, 1x 100/1000Base X SFP Slot General The IP protocol has already left the

More information

CliQ II Buffer Module 24V 20A / DRB-24V020AB

CliQ II Buffer Module 24V 20A / DRB-24V020AB Highlights & Features Full corrosion resistant aluminium chassis Minimum buffering time of 250ms @ 24V/20A Flexible operating buffering voltage modes: o Fixed mode at 22Vdc o Dynamic mode for V in -1V

More information

CliQ II Buffer Module 24V 20A / DRB-24V020AB

CliQ II Buffer Module 24V 20A / DRB-24V020AB Highlights & Features Full corrosion resistant Aluminium chassis Long minimum buffering time of 250ms @ 24V/20A Can connect in parallel to increase buffering time Charging time of < 30 seconds Conformal

More information

PI-EX-ME-2NAM/COC-24VDC

PI-EX-ME-2NAM/COC-24VDC Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 4 V DC Supply INTERFACE Data Sheet 0033_0_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/COC-4VDC

More information