Automation stations modular series

Size: px
Start display at page:

Download "Automation stations modular series"

Transcription

1 s P01 DESIGO PX Automation stations modular series PXC...D PXC...-E.D PXA40- Freely programmable modular automation stations for HVAC and building services plants. Native BACnet automation station with communications BACnet via LonTalk, PTP or Ethernet / IP BTL label (BACnet communications is BTL tested) High performance and reliable operation Comprehensive management and system functions (alarm management, time schedules, trends, remote management, access protection, etc.) The integrated web server allows for generic or graphical web operation as well as sending alarms via SMS or Island bus to connect external TX-I/O modules with any data point mix For stand-alone applications, or for use within a device or system network Supports the following operating elements: local / network capable operator units PXM... PX-WEB (operation via web browser, touch panel or PDA) System controller for integration of DESIGO RXC and LONMARK compatible 3rd party devices CM1N9222en_02 30 Jun 2009 Building Technologies

2 Type summary Automation stations for connection of TX-I/O-modules via island bus Up to 200 data points Over 200 data points Automation station BACnet / LonTalk PXC100.D PXC200.D Automation station BACnet / IP PXC100-E.D PXC200-E.D Compatibility Operating units Type Data sheet Local operating unit PXM10 CM1N9230 Operating unit PXM20 CA1N9231 Operating unit for Ethernet PXM20-E CM1N9234 Connection cable (to connect to operator units PXM10 or PXM20 and to download firmware) PXA-C1 -- TX-I/O device Type Data sheet Digital input module 8 or 16 I/O points TXM1.8D, TXM1.16D CM2N8172 Universal module without / with local operation and LCD TXM1.8U, TXM1.8U-ML CM2N8173 Super universal mod. without / with local operation and LCD TXM1.8X, TXM1.8X-ML CM2N8174 Relay module without / with local operation TXM1.6R, TXM1.6R-M CM2N8175 Resistance measuring module (for Pt100 4-wire) TXM1.8P CM2N8176 Power supply module 1.2 A, Fused 10A TXS1.12F10 CM2N8183 Bus interface module, Fused 10A TXS1.EF10 CM2N8183 Island bus expansion module TXA1.IBE CM2N8184 TX OPEN module TXI1.OPEN CM1N8185 System controllers for integration via extension modules PXX... System controller BACnet / LonTalk System controller BACnet / IP PXC00.D PXC00-E.D Extension module LONWORKS for integration of DESIGO RXC and LonMark compatible 3rd party devices (together with PXC00.D) Type Data sheet Integration of max. 60 devices Integration of max. 120 devices PXX-L11 PXX-L12 CM1N / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

3 Option module for Automation stations and system controllers PXC00 / 100 / 200.D (BACnet/LonTalk) The option module can be mounted in place of the front cover. Module PXA Interfaces USB Host (for modem via PXA-C3) Network functions PTP Dial-in XWP (modem) 1) T X X Option module for Automation stations and system controllers PXC00 / 100 / 200-E.D (BACnet/IP) The option module can be mounted in place of the front cover. Module PXA W0 W1 W2 T Interfaces Ethernet RJ45 X X X USB Host (für Modem via PXA-C3) X X X X Remote management PTP Dial-in DESIGO INSIGHT X X X X (Modem) 1) PPP via Ethernet RJ45 1) X X X Web functions Generic Web functions X 2) X X Graphic Web functions X 2) X Send alarms via SMS (Modem) X X X Send alarms via (RJ45) X X X 1) 2) The modem connection can be configured as follows: either for Remote Management (XWP) or for Remote Management PX WEB generic / graphical and alarming with SMS. Web functions for one automation station only Option modules are "hot-pluggable" PXA40- option modules can be plugged and unplugged when the automation station is operating. The functionality is available immediately after inserting. The functionality disappears approx.1 minute after unplugging. Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun / 14

4 Automation station functions These freely programmable automation stations provide the infrastructure for the provision and processing of system-specific and application-specific functions. In addition to the control functions, the automation station also incorporates convenient integrated management functions such as: Alarm management with alarm routing throughout the network. Management of simple, basic and extended alarms, with safe transfer tracking and automatic monitoring of alarm transmission Time schedules Trend Remote management function Access protection throughout the network, with individually definable user profiles and categories Programming language Communication BACnet/IP (PXC...-E.D only) BACnet/LonTalk (PXC...D only) BACnet/PTP (with option module PXA40...) The automation stations are freely programmable in D-MAP programming language. This involves the creation of plant operating programs through graphicsbased interconnection of function blocks and compounds held in libraries. Communication is via Ethernet with the internationally standardized BACnet protocol. Both peer-to-peer communications with other automation stations and connection to the PXM20-E operator units are supported. The devices communicate via an open LonTalk system in accordance with the international standard BACnet protocol. Both peer-to-peer communications with other automation stations and connections to the PXM20 operator units are supported. The devices communicate via the public telephone network in accordance with the international standard BACnet protocol. Automation station operation There are various options for the operation of the PXC U automation stations: Local PXM10 operator unit, either plugged into the automation station or connected via a PXA-C1 cable Network-compatible PXM20 operator unit (BACnet/LonTalk) for operation of the local automation station or an automation station in a network; either plugged into the automation station, or connected via PXA-C1 cable Network capable operator unit PXM20-E (BACnet / IP) to operate an automation station in the network, connected to an Ethernet hub or switch PX-WEB: Optional web server via PXA40-W... option module. Allows operation with a web browser, a touch panel or a PDA. The transfer of alarms via SMS or can be configured in the automation station. 4 / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

5 Mechanical design The compact construction enables the automation stations to be mounted on a standard mounting rail. PXC...D z01 PXA b 9222z16 1 Plastic housing 2 Cover to interface for extension module 3a Front cover 3b PXM option module 4 Plug-in terminal block with screw terminals (operating voltage) 5 Interface for network, operator units, tool, etc. 6 LED display for devices and system status 7 Island bus connector (not on PXC00 ) 8 Slider for mounting on DIN rail Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun / 14

6 LED indicators RUN FLT BAT COM INF SRV 9222z14 Service pin (DESIGO) LED Color Activity Function RUN Green Continuously ON Continuously OFF Power OK No power FLT Red Continuously OFF Continuously ON Rapid flashing OK Fault Firmware missing / corrupt BAT Red Continuously OFF Continuously ON Battery OK Battery empty replace! COM Yello w Continuously ON Continuously OFF Flashing Connection to hub OK No connection to hub Communication INF Red Freely programmable SRV (Ethernet) SRV (LONWORKS Bus) Red Red Continuously OFF Continuously ON Flashing Flashing per wink command *) Continuously OFF Continuously ON Flashing Flashing per wink command *) *) Wink command pattern: OK No connection to hub No IP address configured Physical identification of automation station after receipt of wink command LONWORKS node is configured Faulty LONWORKS chip, or service pin currently depressed LONWORKS node is not configured Physical identification of automation station after receipt of wink command 21s 9222z02 5 Hz 5 Hz 2s 1s 2s 1s Mounting instructions The automation stations can be snapped onto standardized rails. The power supply connection and the room devices have plug-in screw terminal blocks. The other interfaces are quick plug-in connections. Instead of the front cover a PXA40... option module can be fitted on the modular automation station. 6 / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

7 Commissioning In order to prevent equipment damage and/or personal injuries always follow local safety regulations and the required safety standards. Load plant operating program Setting parameters and configurations Wiring test Network connection Force Firmware Download Restart The plant operating program is downloaded using the tool PX Design from XWP locally via the automation station's RJ45 interface or via the network (BACnet/IP or BACnet/LonTalk). Use the PX Design tool in XWP for setting the control parameters and the configuration data. Data visible on the network may also be edited with an operator unit PXM20 / PXM20-E (BACnet / LonTalk or BACnet / IP). Part of the data can also be edited locally using the operator unit PXM10. It is possible to test field devices and the wiring as soon as the power supply is connected, without first downloading the plant operating program. BACnet / LonTalk for PXC...D and PXC..-T.D: using operator unit PXM20 BACnet / IP for PXC..-E.D: using operator unit PXM20-E. Requirement: PX and PXM20-E are on the default IP and alone on the IP segment. The network addresses are configured with XWP. For unique identification in the network (BACnet/IP or BACnet/LonTalk), press the Service button with a long, pointed object or send a wink command to the appropriate automation station (service LED blinks). Variant via V24: If the Force Firmware Download Key is pressed during a restart (reset), the current D-MAP program is deleted from the FLASH. The automation station waits briefly for the signal to activate the FWLoader and then starts the automation station. IP variant: (for PXC..-E.D, significantly faster) Press the Force Firmware Download Button for 5 seconds (within hitting the reset button). Requirement: The automation station has conducted a node setup and no application is loaded or was deleted in the CFC by clear/reset (communication settings remain which would not be the case when erasing by pressing the reset key). Press the Reset button to force a restart Assignment of buttons and batteries FW Reset RUN FLT BAT COM INF SRV Alkaline AA Lithium Service Pin 9222z04 Power supply The power supply of the automation station must be switched on and off simultaneously with the power supply of the TX-I/O modules. Otherwise, unwanted alarms will be generated. Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun / 14

8 Maintenance Battery life Database information is stored in SDRAM which is supported by a battery (Alkaline AA). This saves time for reloading the program and database after longer power outages (up to approx. 1 month). Alkaline batteries usually have a life span of at least four years. After the Battery low event, the battery still has a residual life of a few more days. The Real-Time Clock is supported by a lithium battery with a life span of at least 10 years. The Low BAT LED lights up when one of the batteries charges is low and the automation station automatically sends a system event. It can also be set as an alarm to select recipients. Replacing the battery STOP Caution To change the battery remove the front cover. The battery can be removed indefinitely as long as the unit has power. A wrist-strap and grounding cable must be used to avoid hardware damage through electrostatic discharge (ESD). Firmware upgrades Firmware and operating system stored in non-volatile Flash ROM. Flash ROM memory can be easily updated on the plant, when a new firmware version is available. Disposal The devices are classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 8 / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

9 Technical data General device data Operating voltage AC 24 V ± 20% Safety extra-low voltage SELV or HD 384 Extra-low voltage PELV Operating frequency 50/60 Hz Energy consumption Max. 24 VA (same for all types) Internal fuse 5 A Operating data Processor Motorola Power PC MPC885 Storage 64MB SDRAM / 32MB FLASH (96MB total) Accuracy class 0.5 Data backup in event of power failure Battery backup for SDRAM 1 x AA alkaline (replaced on plant) Typically one month (unused: 4 years) Battery backup for real-time clock Lithium (replaced on plant) 10 years Communication interfaces PXC...D PXC...-E.D Building Level Network LONWORKS FTT Transceiver (screw terminals (B)) 10 Base-T / 100 Base-TX IEEE802.3, Auto-sensing (RJ45 (D)) Local communication PXM20 (BACnet/LonTalk) *) (HMI) (RJ45 (C)) Local communication (HMI, Tool) (RJ45 (E)) PXM10 (serial) PXM20 (BACnet/LonTalk) *) Tool Connection cable max. 3 meters PXM10 (serial) Local communication PXM10 (serial) (HMI) (RJ45 (G)) USB host interface RS232 modem (via USB-RS232 (Modem) adapter cable PXA-C3) USB device interface (for future applications) (for future applications) RS232 modem (via USB-RS232 adapter cable PXA-C3) Ethernet interface Interface type 100BaseTX, IEEE compatible Bit rate 10 / 100 MBit/s, autosensing Protocol BACnet auf UDP/IP Pin RJ45 Buchse geschirmt LONWORKS bus interface Network TP/FT-10 Baud rate 78 kbit/s Protocol BACnet Interface chip Echelon Processor TMPN3150B1AF Island bus interface (CD, CS ) Short-circuit proof Short-circuit proof *) only ONE PXM20 per automation station Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun / 14

10 Plug-in screw terminal Power supply Solid or stranded conductors mm2 or 2 x 1.5 mm2 Plug-in screw terminal LonWorks bus Solid or stranded conductors mm2 or 2 x 1.5 mm2 Simple cable lengths, cable Connection cable Ethernet and PXM20-E types (see Installation Guide Cable type PX, CA110396) Connection cable LONWORKS bus Cable type Connection cable PXM10 Connection cables for island bus Housing protection standard Protection standard to EN IP 20 Protection class Insulation protection class II Max. 100 m Standard at least CAT5 UTP (Unshielded Twisted Pair) or STP (Shielded Twisted Pair) See Installation Guide CA ConCab or CAT5 Max. 3 m See CM Ambient conditions Normal operation To IEC Environmental conditions Class 3K5 Temperature C Humidity 5 95 % r.h. (non-condensing) Mechanical conditions Class 3M2 Transport To IEC Environmental conditions Class 2K3 Temperature C Humidity 5 95 % r.h. (non-condensing) Mechanical conditions Class 2M2 Standards, guidelines And approvals Product safety Automatic electronic controls for household and similar use Electromagnetic compatibility Interference immunity Emitted interference CE compliance: Electromagnetic compatibility EN EN (industry) EN (residential) 2004/108/EC UL approval (UL 916) PAZX7 Federal Communications Commission (US) FCC CFR 47 Part 15 Class B C-Tick compliance per Australian EMC Radio Communications Act 1992 Framework Radio Emission Standard AS/NZS 2064 Environmental compatibility The product environmental declaration CM1E9222 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) ISO (Environment) ISO 9001 (Quality) SN (Environmentally compatible products) 2002/95/EC (RoHS) Dimensions See Dimensions Weight Excluding packaging With packaging All types 0,489 kg 0,531 kg 10 / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

11 Connection terminals and interfaces PXC...D 24 V~ T (A) CLA CLB (B) HMI (C) (E) HMI / TOOL (F) (G) HMI 9222Z10 PXC...-E.D V~ T (A) (D) (F) (G) HMI 9222Z11 1, 2 24 V ~, Operating voltage AC 24 V 3 Functional ground Plug-in screw terminal block (A) USB host interface (for modem via PXA-C3 adapter cable) 4,5 (B) CLA, CLB LONWORKS bus Plug-in screw terminal blocks (C) HMI RJ45 interface (LONWORKS) for operator unit PXM20 (tool as well) (D) RJ45 interface for Ethernet (Operator unit PXM20-E can be connected to hub/switch) (E) HMI / Tool RJ45 interface (LONWORKS and serial) for PXM10, PXM20 and tool (F) USB device interface (for future applications) (G) HMI RJ45 interface (serial) for operator unit PXM10 11 / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

12 Pin assignment for RJ45 plug Plug (C) "HMI" (LONWORKS) z12 Pin description 1. LONWORKS Data A (CLA) 2. LONWORKS Data B (CLB) 3. G0 / GND 4. G / Plus Pin description 5. Unused 6. Unused 7. Unused 8. Unused Plug (D) Ethernet RJ45 socket screened, standard connection in accordance with AT&T z12 1. Tx+ 2. Tx 3. Rx + 4. Unused 5. Unused 6. Rx 7. Unused 8. Unused Plug (E) "HMI / Tool" (LONWORKS and serial) z12 1. LONWORKS Data A (CLA) 2. LONWORKS Data B (CLB) 3. GND V max. 300 ma (PXM20) 5. Unused 6. Unused 7. COM1 / TxD 8. COM1 / RxD Plug (G) "HMI" (serial) z12 1. unused 2. unused 3. G0 / GND 4. G / Plus 5. Unused 6. *) 7. COM1/TxD 8. COM1/RxD *) 6 Unused (PXC.D) Connected to pin 8 (PXC -E.D) Connection diagrams Connecting TX-I/O modules and field devices See Planning and Installation Guide TX-I/O, CM / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

13 Dimensions All dimensions in mm Automation stations, system controllers PXC.D (PXA40-...) (PXA40-...) 9222m14 Option modules PXA m15 13 / 14 Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

14 14 / Siemens Switzerland Ltd Subject to change Siemens PXC...D PXC...-E.D + PXA40- Automation stations modular series CM1N9222en_02 Building Technologies 30 Jun 2009

15 s P01 TX-I/O ; DESIGO OPEN TX OPEN RS232/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the DESIGO building automation and control system (Version 4 or higher) Suitable for operation using pre-defined applications from Siemens or using in-house developed applications USB interface for connecting the TX OPEN Tool Compact design per DIN Easy installation and setup Plug-in screw terminals Power from Island bus (DC 24 V) Simple, fast diagnostics CM2N8185en_01 31 Jan 2009 Building Technologies

16 Function The TX OPEN RS232/485 module integrates third-party systems via RS232 or RS485 interface to the DESIGO building automation and control system. The required applications are loaded onto the module via the USB interface. Siemens offers finished applications for the following systems: Modbus (Engineering guide CM110571) M-bus (Engineering guide CM110572) SED2 (Engineering guide CM110573) Additional applications are currently being prepared You may also develop your own applications using Microsoft embedded Visual C++ 4.0, see Developer's guideline for the TXI1.OPEN, CM The TX OPEN RS232/485 module is powered directly with DC 24 V from the island bus. A webpage that may be viewed in the web browser via the USB interface, displays the interface configuration and values from the third-party system / device. The TX OPEN Tool supports the download of firmware and applications as well as the configuration data. Type summary Product No. Stock number Designation TXI1.OPEN S55661-J100 TX OPEN RS232/485 module Accessories Configuration software TX OPEN Tool (Please contact your regional company for orders) Ordering When ordering, please specify the quantity, designation, product number and stock number. Example: 10 TX OPEN RS232/485 Module TXI1.OPEN, S55661-J100 Equipment combinations Note: Version 2.37 The TX OPEN RS232/485 module is suitable for using an island-bus capable automation station, i.e. in plants with version 4 or higher. For plants with versions up to 2.37, only I/O OPEN modules from the PT-I/O range are suitable.. 2 / 8 Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan 2009

17 Design and technology Overview F B A TX RX REF _ + RUN G RS232 RS485 D E x10 x1 Address C 2 3 G COM F Key U Plug-in screw terminal for RS232 and RS485 (Changeover via software) Terminal RS232 RS485 1 TX + 2 RX 3 REF (Potential equalization) B LED "RUN" Power OK C LED COM Communication (RS) D USB connection for TX OPEN Tool E Rotary switches to set module address G 8185Z01 F G Bus connector Attachment slider for standard rails Mechanical properties Housing The housing complies with DIN and is 96 mm wide. During mounting, ensure sufficient convection (max. ambient temperature 50 C). Electrical properties Power Interfaces Island bus System ground Protection against incorrect wiring The TX OPEN RS232/485 module is powered directly with DC 24 V from the island bus. No separate power required. Plug-in screw terminal for serial interfaces RS232 and RS485 USB plug type B for connecting the TX OPEN Tool The TX OPEN RS232/485 module has contacts on the left and right side of the housing for the island bus. The module is plugged in between existing modules or attached at the end of a I/O row. The serial interfaces RS232 / RS485 are electrically isolated from the island bus side. The connected third-party system may be earthed. All terminals are protected against short circuit and incorrect wiring using AC/DC 24 V. Side bus connector: No protection Voltage higher than AC / DC 24 V: No protection Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan / 8

18 Interfaces General RS232 RS485 Bus terminator Serial interfaces are electrically isolated The serial interfaces use the same connection terminals. You can use either RS232 or RS485 (Changeover via software). The interface supports baud rates from 300 to Baud. The signals RXD and TXD are available, but without handshake signals. The interface supports baud rates of 9600 and Baud. You can switch up a bus termination via software in the I/O OPEN module (1nF, 120 Ohm in series). Signaling RUN (green) COM (green) LED displays power is available and sufficient. This LED displays communications on the RS side. Address switch The module address is switched using the two rotary switches. The factory setting is 00 (the TX OPEN RS232/485 module is inactive). Corresponds to a open address key in an I/O module. Related documents Document Number [1] TX OPEN developer's guideline CM [2] TX-OPEN Modbus engineering CM [3] TX OPEN M-bus engineering CM [4] TX OPEN SED2 engineering CM [5] TX OPEN Tool online help -- [6] TX-I/O module, data sheets CM1N [7] TX-I/O Planning and installation manual CM Disposal The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 4 / 8 Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan 2009

19 Mounting Fixings Order Exchange Permissible mounting positions The device is mounted on a standard rail 35 x 7.5 mm (tophat rails TH per EN60715) The device can be plugged into any position on the I/O row. One TX OPEN RS232/485 module may be removed from the row of modules. Please note, however, that the island bus and power is interrupted for all subsequent modules. TX-I/O devices can be mounted in any position: You must ensure, however, that sufficient ventilation is available to maintain the permissible ambient temperature (max. 50 C). Technical data Operating voltage Power consumption Power from the island bus. No separate power required. DC 24 V 55 ma / 1.32 W Protection against shortcircuit Side bus connector No protection! and incorrect wiring Serial interfaces Protection against surges to AC/DC 24 V and short circuits Electronic isolation from island bus GND RS242/485 interface You can switch up a bus termination via software in the I/O OPEN module (1nF, 120 Ohm in series) USB interface Plug Type B (USB device) Data rate (USB 1.0 full speed) 12 MBit/s Electronic isolation from island bus GND No Protective switch against surges and over Yes current Connection terminals, plug-in Mechanical design Copper wire or copper stranded wires with ferrules Copper stranded wires without ferrules Screwdriver Maximum stud torque Plug-in screw terminal 1 x 0.6 mm to 2.5mm 2 or 2 x 0.6 mm to 1,0 mm 2 1 x 0.6 mm to 2.5 mm 2 or 2 x 0.6 mm to 1,5 mm 2 Flat screwdriver size 1 with shaft ø 4.5 mm 0.6 Nm Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan / 8

20 Classification per EN Function of automatic control devices Degree of pollution Mechanical design Housing type IP class per EN Front parts in DIN excerpt terminal part Type 1 2 Protection class III IP30 IP20 Environmental conditions Standards, directives and approvals Operation Climatic conditions Temperature Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Product safety Automatic electrical controls devices for household and similar use Electromagnetic compatibility Immunity Industrial sector Emissions Residential, Light industry CE conformity Electromagnetic compatibility Low-voltage directive c-tick conformity as per Australian EMC Framework Radio Emission Standard UL approval (UL 916) As per IEC Class 3K C 5 95 % r.f Class 3M2 As per IEC Class 2K C 5 95 % r.f Class 2M2 EN EN EN /108/EC 2006/95/EC Radio Communication Act 1992 AS/NZS M5 Color Housing Light gray, RAL 7035 Dimensions Housing as per DIN , see dimensions Weight With / without packaging 130g / 168g 6 / 8 Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan 2009

21 Dimensions Dimensions in mm M01 Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan / 8

22 8 / Siemens Switzerland Ltd Subject to change Siemens TXI1.OPEN TX OPEN RS232/485 module CM2N8185en_01 Building Technologies 31 Jan 2009

23 . SIEMENS p01 TX-I/O Module system Modules and accessories Assortment overview DESIGO / UNIGYR / VISONIK / SIMATIC TXM1... TX TX-I/O modules can be connected to all automation stations equipped with P-Bus by means of a TXB1.PBUSP-Bus interface module, if the automation station supports the I/O functions used in the modules. Related information can be found in the function descriptions and the tools of the building automation and control systems. Contants 1 Modules and functions Type summary TX-I/O modules and accessories Compatibility Documentation... 4 CM2N8170en_ Building Technologies

24 1 Modules and functions Draft The following functions are available in the TX-IO modules: Function / signal type Description Number of I/O points per function Max. number of functions per module TXM1.8D TXM1.16D TXM1.8U TXM1.8U-ML TXM1.8X TXM1.8X-ML TXM1.6R TXM1.6R-M Digital inputs D20 / D20R Status indication, volt-free maintained contact, normally-open / normally-closed D20S Status indication, volt-free pulsed contact, normally-open or normally-closed C Count, volt-free pulse contact 1), normally-open, 25 Hz, with debouncing Analog inputs R1K Temperature LG-Ni P1K Resistance 2500 Ω and temp. Pt T1 Temperature T1 (PTC) U10 Voltage, DC 0 10V I420 Current DC 4 20 ma Digital outputs Q250 Maintained contact, normally open and normally closed Q250A-P Pulse, N/O contact Q250A-P / Q250-P On/off pulse (N/O and N/C contact) Y250-T Pulse, control signal, three-position output, internally adjustable stroke Q-M3 Maintained contact, three-stage Q250-P3 Pulse, three-stage Analog outputs Y10S Proportional control signal DC V Y420 Proportional control signal DC ma Indication and local override Local override X X X LCD display X X 3-colored I/O status LEDs X X Example of a Read operation The Q250-T function (control signal, three-position output) uses 3 I/O points. One TXM1.6R relay module can accommodate 2 actuators. 2/4 Building Technologies Modules and accessories Assortment overview CM2N8170en_

25 Draft Type summary TX-I/O modules and accessories Description Type (ASN No.) Data sheet I/O modules Digital input module, 8 I/O points TXM1.8D CM2N8172 Digital input module, 16 I/O points TXM1.16D CM2N8172 Universal module TXM1.8U CM2N8173 Universal module with local override facility and LCD TXM1.8U-ML CM2N8173 Super universal module TXM1.8X CM2N8174 Super universal module with local override facility and LCD TXM1.8x-ML CM2N8174 Relay module TXM1.6R CM2N8175 Relay module with local override facility TXM1.6R-M CM2N8175 Power supply Power supply module 1.2 A, fuse 10A TXS1.12F10 CM2N8183 Bus connection module, fuse 10A TXS1.EF10 CM2N8183 Bus interface P-Bus Interface module with power supply 1.2A, fuse 10A TXB1.P-BUS CM2N8180 Address keys Address key reset key TXA1.K12 CM2N8170 Address key reset key TXA1.K24 CM2N8170 Address key reset key Address key reset key TXA1.K48 CM2N8170 Address key reset key Address key reset key TXA1.K72 CM2N8170 Address key reset key Address key 5, 10, reset key TXA1.5K120 CM2N8170 Address key 65, 70, reset key Address labels Address label sheets A4 (100 pcs. per box) TXA1.LA4 CM2N8170 Address label sheets Letter (100 pcs. per box) TXA1.LLT Spare transparent label holders (10 pcs. per box) TXA1.LH CM2N Compatibility The TX-I/O module system is compatible with the following systems: DESIGO from V2.1 UNIGYR from V3.3 VISONIK from V2.x SIMATIC from S7 Building Technologies Modules and accessories Assortment overview CM2N8170en_ /4

26 Draft Dokumentation Description Type (ASN No.) Data sheet I/O-Module Digital input module, 8 I/O points TXM1.8D CM2N8172 Digital input module, 16 I/O points TXM1.16D CM2N8172 Universal module TXM1.8U CM2N8173 Universal module with local override facility and LCD TXM1.8U-ML CM2N8173 Super universal module TXM1.8X CM2N8174 Super universal module with local override facility and LCD TXM1.8x-ML CM2N8174 Relay module TXM1.6R CM2N8175 Relay module with local override facility TXM1.6R-M CM2N8175 Speisung Power supply module 1.2 A, fuse 10A TXS1.12F10 CM2N8183 Bus connection module, fuse 10A TXS1.EF10 CM2N8183 Bus-Interface P-Bus Interface module with power supply 1.2A, fuse 10A TXB1.P-BUS CM2N8180 Zubehör Address keys TXA1.K... CM2N8170 Address label sheets TXA1.LA4 CM2N8170 Spare transparent label holders TXA1.LH CM2N8170 Projektierung TX-I/O Functions and operation CM TX-I/O Planning and installation manual CM Integration DESIGO Point Test CM TX-I/O Tool User's guide CM TX-I/O Tool Short guide CM TX-I/O Power and cabinet dimensioning CM TX-I/O IO MD Tool User's guide CM TX-I/O Module-report User's guide CM Workflow TX-I/O DTS / XWORKS CM Workflow TX-I/O VISONIK CM Workflow TX-I/O UNIGYR CM / Siemens Switzerland Ltd. Subject to change Building Technologies Modules and accessories Assortment overview CM2N8170en_

27 8 173 TX-I/O Module system Universal modules TXM1.8U TXM1.8U-ML Two fully compatible versions: TXM1.8U: 8 inputs/outputs with LED signal / fault indication TXM1.8U-ML: As TXM1.8U, but with additional local override facility with LCD display (LO/ID to ISO ) 8 universal I/O points, individually configurable as Digital input: maintained contact, pulse or counter Analog input: sensor, 0..10V Analog output: 0..10V Compact DIN format, small footprint Separate terminal base and plug-in I/O module for convenient handling Bus created automatically for maximum ease of installation Terminal isolation function for fast commissioning I/O module replaceable in seconds, without rewiring and without affecting the full functioning of the remaining I/O modules All terminals are directly on the I/O modules, allowing direct connection of field devices without additional terminal strips. Simple strategy for operation and display I/O status LED for each I/O point; mode of operation (N/C or N/O) and brightness depend on I/O function LEDs and LCD for fast diagnostics Double-sided labels for identification of all I/O points CM2N8173en_ Building Technologies

28 Functions The modules support the following I/O functions: Function Signal type Description Status signal D20 Volt-free, N/O or N/C contact, interrogation (maintained contact) D20R Status pulses D20S Volt-free, N/O or N/C, interrogation (pulse) Counter pulses C Volt-free, N/O contact, interrogation (pulse) Counting frequency max. 25 Hz Voltage, resistance and temperatures Proportional output signals U10 R1K P1K T1 Y10S Voltage DC V Temperature sensor LG-Ni 1000 ohms Resistance Pt 1000 ohms and resistance transmitter Temperature sensor PTC Proportional control output, DC V, with storage of control value For a detailed description of these functions, please refer to document CA110561, "TX-I/O functions and operation". Type summary ASN Universal module TXM1.8U Universal module TXM1.8U-ML with LCD display and local override Delivery The terminal base and the electronic plug-in unit are interconnected and delivered in the same box. Accessories The available accessories include address keys, label sheets, and spare transparent label holders. Refer to data sheet CM2N /10 Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation

29 Technical and mechanical design For a description of the features common to all TX-I/O modules, please refer to the TX-I/O Engineering and installation manual, document CM Indicators and operator controls V V 33 Connection terminals (No. 1 screwdriver) with test pickup (for mm pins) and terminal number Signal designation 12 (5) (6) (7) (8) Override status LEDs (yellow) Address key and module status LED LCD panel (TXM1.8U-ML only) (1) (2) (3) (4) (5) (6) (7) (8) I/O point numbers Override switch (TXM18U-ML only) (1) (2) (3) (4) I/O status LEDs (green) z10 V 5 V 13 I/O status LEDs The I/O status LEDs (green) indicate the status of the inputs and outputs (peripheral devices) They are also used for diagnostics Module status LED Address key The module status LED illuminates the transparent address key The LED (green) shows the module status as a whole (as opposed to the status of the I/O points) It is also used for diagnostics The module operates only with the address key inserted The module address is mechanically encoded in the address key When replacing the I/O module, the address key must be swiveled outward. It remains plugged into in the terminal base. Local override and LCD display (TXM1.8U-ML only) For a detailed description, please refer to document CM110561, "TX-I/O Functions and operation". Override switch Pressing an override switch in the middle enables or disables the local override Pressing "+" or " " respectively increases or reduces the output value. Only outputs can be overwritten. Any attempt to overwrite an input results in an error indication. Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation /10

30 Override status LED LCD display Warning The yellow "Override" LED indicates that local override is active The following information is displayed for each I/O point: Configured signal type Symbolic display of process value Information for diagnostics. All safety-relevant functions must be implemented with external solutions The local override must not be used for safety shutdown operations In compliance with the standard (ISO , Section 3.110), the module executes all local override operations directly, without safety precautions or interlocks. Full responsibility lies with the operator. Module labeling The plug-in I/O module has a removable transparent cover (the label holder) for insertion of a label z11 Disposal The device includes electrical and electronic components and must not be disposed of as domestic waste. Current local legislation must be observed. Engineering, mounting, installation and commissioning Please refer to the following documents Document TX-I/O Functions and operation TX-I/O Engineering and installation manual TX-I/O Integration documentation Number CM CM CM ff 4/10 Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation

31 Mounting Permitted orientation The TX-I/O devices can be installed in any orientation: It is important to provide adequate ventilation so that the admissible ambient temperature (max. 50 C) is not exceeded. Technical data Supply (bus connector on side) Operating voltage DC V Extra low voltage SELV or PELV in accordance with HD384 Max. power consumption TXM1.8U 1.5 W TXM1.8U-ML 1.8 W Protection All terminals of the modules Against shortcut and incorrect wiring with AC / DC 24 V Bus connector on side No protection! Field devices Insulation resistance The of the connected field devices against mains voltage must comply with the requirements for safety extra-low voltage (SELV) or protection by extra-low voltage (PELV) as per HD 384. Measuring cables Cable material Solid or stranded copper wire Cable cross section See manual CM Permitted cable length max. 300 m AC/DC output Voltage AC / DC V (field supply) Admissible current per module Max. 4 A (total for all 4 terminals) (, Terminals 7, 15, 24, 32) Fuse T 10A, in power supply module/bus connection module Digital inputs / counter inputs Digital inputs are not galvanically separated from the system's electronics. Mechanical contacts must be potential-free or connected to system neutral. Electronic switches must be connected to system neutral. Contact sensing voltage Contact sensing current Contact resistance with contacts closed Contact resistance with contacts open DC V 1.0 ma (initial current 6 ma) Max. 200Ω Min. 50kΩ Min. closing / opening time [ms] including bouncing Max. bounce time [ms] Counting frequency (symmetric) Maintained contact Pulse contact Counter Hz Counter inputs Counter memory x 10 9 (32-bit counter) Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation /10

32 Analog inputs Converter: 16 Bit Correction of line resistance 1 Ω (calibrated In module) Resistance Pt 1000 and resistance transmitter Signal type Range Resolution (25 C) P1K Ω 0.05 Ω Temp. measurement R1K (LG-Ni 1000) C 0.02 K T (150) C 1) 0.02 K 1) (extended range) only with reduced hum injection Voltage measurement U V 1 mv Admissible input voltage max. DC ± 20 V Analog outputs Converter: 10 Bit Signal type Range Resolution Output voltage Y10S 0 10 V 11 mv Connection terminals Mechanical design Solid conductors Stranded conductors without connector sleeves Stranded conductors with connector sleeves (DIN 46228/1) Screwdriver Rising cage terminals 1 x 0.5 mm 2 to 4mm 2 or 2 x 1.5 mm 2 1 x 0.5 mm 2 to 2.5 mm 2 or 2 x 1.5 mm 2 1 x 0.25 mm 2 to 2.5 mm 2 or 2 x 1.5 mm 2 Slot-headed screws Screwdriver No. 1 with shaft diameter 4.5 mm 0.6 Nm Max. tightening torque Test pickups (test terminals) For pin diameter mm Local override (TXM1.8U-ML only) Local override / indication device ISO , Section 3.11 Classification to EN Housing protection standard Ambient conditions Mode of operation of automatic electrical controls Contamination level Mechanical design Protection standard to EN Front-plate components in DIN cut-out Terminal base Operation Climatic conditions Temperature Humidity Mechanical conditions Operation Climatic conditions Temperature Humidity Mechanical conditions Type 1 2 Protection class III IP30 IP20 To IEC Class 3K C 5 95 % rh Class 3M2 To IEC Class 2K C 5 95 % rh Class 2M2 6/10 Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation

33 Industry standards Product safety Automatic electronic controls for household and similar use Electromagnetic compatibility Interference immunity Industrial environments Emitted interference Residential, commercial and light industrial environments Meets the requirements for CE marking in EMC Directive Low Voltage Directive C-tick conformity in accordance with Australian EMC framework Radio Emission Standard UL approval (UL 916, UL 864) EN EN EN /336/EEC 73/23/EEC Radio Communications Act 1992 AS/NZS 3548 UUKL Color Terminal base and plug-in I/O module RAL 7035 (light gray) Dimensions Housing to DIN , see "Dimensions" Weight With / without packaging TXM1.8U 194 / 219 g TXM1.8U-ML 211 / 236 g Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation /10

34 Connection diagrams (examples) Digital inputs U (1) (2) (3) (4) (5) K1 K2 K3 K4 S5 8174z13 U K1 K2 K3 K4 S5 Universal module Status contact (N/O) Status contact (N/C) Pulse contact (N/O) Pulse contact (N/C) Electronic switch Terminal layout TXM1.8U, TXM1.8U-ML I/O point (1) (2) (3) (4) (5) (6) (7) (8) System neutral ( ) 1) Input (+) Analog inputs U (1) (2) M B (3) U B1 B2 R3 B4 B5 Universal module LG-Ni 1000 temperature sensor Pt 1000 temperature sensor Resistance-type sensor Active sensor with external supply Active sensor with AC / DC supply B1 B2 R3 U (1) (2) V 5 8 V V B4 B5 8173z14 Terminal layout TXM1.8U, TXM1.8U-ML I/O point (1) (2) (3) (4) (5) (6) (7) (8) Measuring neutral ( ) 1) Input (+) AC / DC sensor supply voltage 2 Selected from: 5, 13, 22, 32 2) 8/10 Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation

35 Analog outputs U (1) (2) V 5 8 (3) U Y1 Y2 Y3 Universal module Actuator with input DC V General device with input DC V, supplied by module General device with input DC V, supplied externally V Y1 Y2 V Y3 8173z15 Terminal layout TXM1.8U, TXM1.8U-ML I/O point (1) (2) (3) (4) (5) (6) (7) (8) System neutral ( ) 1) Output (+) AC / DC operating voltage 2) Selected from: 5, 13, 22, 32 2) 1) All measuring / system neutral terminals are interconnected, not in the terminal base but in the plug-in I/O module. When this unit is pulled outward (into the "parking" position) there is no connection. The system neutral of a digital input can be connected to any system neutral terminal It is also permissible to combine the system neutral conductors of several digital inputs in order to save wire. However, the inputs concerned must be on the same module. With analog inputs and outputs, the measuring / system neutral must always be connected to the terminal associated with that I/O point. 2) All AC/DC 24V supply terminals are interconnected (in the I/O module, not in the terminal base). They are protected in the power supply module / bus connection module. Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation /10

36 Dimensions Dimensions in mm M01 10/ Siemens Building Technologies Ltd Subject to change Building Technologies TXM1.8U, TXM1.8U-ML Universal modules CM2N8173en_00 Building Automation

Automation stations modular series

Automation stations modular series s 9 222 9222P01 DESIGO PX Automation stations modular series PXC...D PXC...-E.D PXA40- Freely programmable modular automation stations for HVAC and building services plants. Native BACnet automation station

More information

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O 8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility

More information

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O s 8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility

More information

Super universal modules

Super universal modules s 8 174 TX-I/O Super universal modules TXM1.8X TXM1.8X-ML Two fully compatible versions: TXM1.8X: 8 inputs/outputs with LED signal / fault indication TXM1.8X-ML: As TXM1.8X, but with additional local override

More information

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O s 8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility

More information

Power supply module, bus connection module

Power supply module, bus connection module s 8 183 8183p01, p02 TX-I/O Power supply module, bus connection module TXS1.12F10 TXS1.EF10 Each I/O row begins with one of these devices TXS1.12F10 power supply module Up to 4 power supply modules can

More information

Resistance measuring module

Resistance measuring module s 8 176 8176P01 TX-I/O Resistance measuring module TXM1.8P 8 inputs with LED signal / fault display. 8 resistance measuring inputs with individual configuration of resistance or temperature measurement.

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

Automation stations modular series

Automation stations modular series s 9 222 9222P01 Desigo PX Automation stations modular series PXC...D PXC...-E.D PXA40- Freely programmable modular automation stations for HVAC and building services plants. Communications BACnet/IP BACnet/LonTalk

More information

Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D s 9 283 9283P01 Desigo PX Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXX-PBUS The PXX-PBUS extension module allows for integrating existing PTM

More information

Web interface BACnet/IP

Web interface BACnet/IP s 9 294 DESIGO PX Web interface BACnet/IP PXG3.W100 Local or remote operation of one or multiple PX automation station(s) via Desigo Touch Panels (TP) and standard web browser Connection via Ethernet Central

More information

PXR11 PXR12. System controllers DESIGO PX

PXR11 PXR12. System controllers DESIGO PX 9 235 DESIGO PX System controllers PXR11 PXR12 For integration of the room controllers in the DESIGO RXC range into the DESIGO building automation and control system (operates as an interface) For the

More information

Island bus expansion module

Island bus expansion module s 8 184 8184P01 TX-I/O Island bus expansion TXA1.IBE Expand island bus to a distance of up to 2 x 200 meters Compact design per DIN 43 880, requires little space Easy installation and setup Mounted on

More information

Extension module for Web functions generic

Extension module for Web functions generic s 9 264 9263p01 DESIGO PX Extension module for Web functions generic Plugs into the modular automation stations, type PXC...-U PXA30-W1 Extension module for PXC -U automation stations in the DESIGO building

More information

9283P01. Extension module. Integration of existing PT-I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

9283P01. Extension module. Integration of existing PT-I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D s 9 283 9283P01 Desigo PX Extension module Integration of existing PT-I/O modules in Desigo Used with PXC50...D, PXC100...D or PXX-PBUS The PXX-PBUS extension module allows for integrating existing PT-I/O

More information

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O s 8 179 8179p01 TX-I/O Triac module sed for Thermic and motor-driven actuators (AC 24 V) AC 24 V-controlled devices TXM1.8T 8 triac outputs (AC 24 V), configured individually for: Permanent contact Three-point

More information

Extension module for graphic Web functions for one automation station

Extension module for graphic Web functions for one automation station s 9 266 9263p01 DESIGO PX Extension module for graphic Web functions for one automation station Plugs into the modular automation stations, type PXC...-U For operation of the PXC -U automation stations

More information

Room automation station

Room automation station s 9 203 9203mmP01 Desigo TRA Room automation station PXC3.E7... Modular, programmable room automation stations for HVAC, lighting, and shading. BACnet / IP communications; BACnet profile ASC (BTL label).

More information

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station s 3 836 3836P01 Desigo TRA PL-Link IO Block Use with PXC3 series room automation station RXM39.1 The PL-Link IO Block contains the inputs and outputs controlled by a room automation station via PL-Link.

More information

BACnet/IP Web Interface

BACnet/IP Web Interface Desigo Control Point BACnet/IP Web Interface PXG3.W100-1, PXG3.W200-1 Web-based, graphical operation of BACnet automation stations using Desigo touch panels and devices with an HTML 5.0 web browser. Simultaneous

More information

Automation stations, compact model

Automation stations, compact model s 9 215 9215P01_01 Desigo PX Automation stations, compact model PXC...D PXC12.D PXC22.D PXC22.1.D PXC36.1.D PXC12-E.D PXC22-E.D PXC22.1-E.D PXC36.1-E.D Freely programmable compact automation stations for

More information

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP s 9 270 Desigo PX BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP PXG3.L PXG3.M Routing between BACnet/IP, BACnet/LonTalk (PXG3.L only), and BACnet MS/TP Supports BACnet/IPv4 and BACnet/IPv6 ANSI/ASHRAE

More information

Extension module for BACnet over Ethernet / IP and graphic Web functions

Extension module for BACnet over Ethernet / IP and graphic Web functions s 9 265 9263p01 DESIGO PX Extension module for BACnet over Ethernet / IP and graphic Web functions Plugs into the modular automation stations, type PXC...-U PXA30-W2 For operation of the PXC -U automation

More information

Automation station, compact series

Automation station, compact series s 9 70 970p0 DESIO INTERAL Migration Automation station, compact series PXC-NRUF In existing INTERAL plants, you can replace compact automation units NRUE/A, NRUF/A and NRUT/A with the PXC NRUF automation

More information

Automation stations compact model

Automation stations compact model 9 PXC36-S DESIO PX Automation stations compact model PXC5 PXC36-S PXC5 Freely programmable compact automation stations for HVAC and building services systems The fixed data point mix ensures optimum efficiency

More information

TXM1.8RB. TX-I/O Blinds module

TXM1.8RB. TX-I/O Blinds module s 8 178 8178p01 TX-I/O Blinds module TXM1.8RB 8 non-floating relay outputs for... 4 blinds motors with 2 end switches, or 2 blinds motors with 3 end switches, or 2 blinds motors with 2 end switches + 1

More information

Automation stations, compact model

Automation stations, compact model s 9 215 9215P01_01 Desigo PX Automation stations, compact model PXC...D PXC12.D PXC22.D PXC22.1.D PXC36.1.D PXC12-E.D PXC22-E.D PXC22.1-E.D PXC36.1-E.D Freely programmable compact automation stations for

More information

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13 s 3 875 RXB Room controller Communicating room controller for fan-coil applications FC-13 RXB39.1 The RXB39.1 room controller is used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil

More information

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications s 3 856 Desigo RXC Room controller RXC39.5 Communicating room controller for fan-coil applications The RXC39.5 room controller is used for temperature control in individual rooms. For fan-coil systems

More information

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018 Technical Specification Sheet Document No. 149-476 February 20, 2018 TX-I/O Product Range TX-I/O is a range of I/O modules, with associated power and communication modules, for use within the APOGEE Automation

More information

Automation station, compact series

Automation station, compact series s 9 70 970p0 Desigo Integral Migration Automation station, compact series PXC-NRUF In existing Integral plants, you can replace compact automation units NRUE/A, NRUF/A and NRUT/A with the PXC NRUF automation

More information

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013 Technical Specification Sheet Document No. 149-476 July 18, 2013 TX-I/O Product Range TX-I/O is a range of I/O modules, with associated power and communication modules, for use within the APOGEE Automation

More information

TX-I/O Product Range. Features. Description. Document No January 24, 2007

TX-I/O Product Range. Features. Description. Document No January 24, 2007 Document No. 149-476 January 24, 2007 TX-I/O Product Range Description TX-I/O is a line of I/O modules with associated power and communication modules for use within the APOGEE system. TX-I/O products

More information

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02 s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled

More information

TX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007

TX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007 Technical Specification Sheet Document No. 149-476 January 24, 2007 TX-I/O Product Range Description TX-I/O is a line of I/O modules with associated power and communication modules for use within the APOGEE

More information

Extension module for lighting control

Extension module for lighting control s 3 842 DESIGO RXC Extension module for lighting control Extension to the RXC30 / RXC31 / RXC38 room controller RXC40.1 RXC40.5 The RXC40 extension module is used in conjunction with an RXC30, RXC31 or

More information

Room unit with PPS2 interface

Room unit with PPS2 interface 1 642 Desigo RX Room unit with PPS2 interface for use with: QAX33.1 devices of the ranges Desigo RXC, RXB, RXL, and RXA (PPS2) Desigo PX Automation stations 1) devices with a PPS2 interface Room temperature

More information

Room automation stations

Room automation stations s 9 203 9203mmP01 Desigo TRA Room automation stations PXC3.E... Modular, programmable room automation stations for HVAC, lighting, and shading. BACnet / IP communications; BACnet profile ASC (BTL label).

More information

CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. POWER SUPPLY RELAY OUTPUTS. Power supply. 4.

CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. POWER SUPPLY RELAY OUTPUTS. Power supply. 4. CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. 4. Relays Power supply 2. Relays 8. Universal Inputs/ Process Bus (KNX) RS485 (Modbus) Tool (USB) Ethernet Tool (USB)/

More information

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC 1 648 Desigo RXC Flexible room unit for integrated operation of HVAC, lighting and blinds in individual rooms; with LONMARK -compatible bus communication QAX50.1 QAX50.5 QAX51.1 QAX51.5 Room temperature

More information

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B 3 136 Synco 700 Extension odules for heating controller RH760B RZ782B RZ783B Extension modules for use with the RH760B heating controller to provide additional auxiliary functions Use Heating plants controlled

More information

PXM20-E. Operator unit BACnet auf Ethernet/IP DESIGO PX

PXM20-E. Operator unit BACnet auf Ethernet/IP DESIGO PX 9 234 DESIGO PX Operator unit BACnet auf Ethernet/IP PXM20-E Network-compatible operator unit for viewing and operating one or more DESIGO PX automation stations. High-grade display with adjustable contrast

More information

Room unit with PPS2 interface

Room unit with PPS2 interface s 1 640 1640P01 Desigo RX Room unit with PPS2 interface For use with: QAX34.3 Equipment from the RXC, RXB, RXL and RXA (PPS2) ranges Desigo PX automation stations 1) Devices with a PPS2 interface Measurement

More information

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02 s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled

More information

Room unit with PPS2 interface

Room unit with PPS2 interface 1 641 DESIGO RX Room unit with PPS2 interface for use with: QAX321 devices of the ranges DESIGO RXC, RXB, and RXA (PPS2) DESIGO PX Automation stations 1) devices with a PPS2 interface Room temperature

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

Airflow Pressure Sensor

Airflow Pressure Sensor Desigo TRA Airflow Pressure Sensor DXA.S04P1... Airflow Pressure Sensor (APS) is used to measure airflow for room pressurization and fume hood control applications. Differential Pressure (velocity) is

More information

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication 3 870 DESIO RXB Room controller for chilled ceilings and radiators with EIB bus communication RXB10.1 The RXB10.1 controller is used for temperature control in individual rooms: For chilled ceilings and

More information

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000 1 542 1542P03 1542P01 1542P02 QXA2001 QXA2000 AQX2000 Condensation Monitor QXA2000 QXA2001 The QXA2000 condensation monitor is used to avoid damage due to condensation on chilled ceilings and in HVAC plant.

More information

POL635.XX/XXX POL636.XX/XXX POL638.XX/XXX POL638.70/XXX

POL635.XX/XXX POL636.XX/XXX POL638.XX/XXX POL638.70/XXX s 3 230 Climatix TM Climatix Controllers For controlling, switching and monitoring functions POL635.XX/XXX POL636.XX/XXX POL638.XX/XXX POL638.70/XXX The controllers are products of the Climatix range.

More information

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035 Meters and Energy Cost Allocation M-bus web server WTV676-HB6035 The web server reads out wireless or wired M-bus devices over Ethernet or the Internet using a browser. Power and connection for up to 20

More information

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B 3 136 Synco 700 Extension odules for heating controller RH760B RZ782B RZ783B Extension modules for use with the RH760B heating controller to provide additional auxiliary functions Use Heating plants controlled

More information

Non-communicating room controllers

Non-communicating room controllers 3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,

More information

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02 1/8 NRK16/A, NRK16-B/A, (NRK16-T /A, NRK14-T /A, NRK16-WEB/A) Control and interlock devices with pre-programmed system-specific application modules The controllers may be used as stand-alone control and

More information

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use s 3 146 Synco 700 Universal Modules RMZ78 Extension modules for use with controls of the Synco 700 family. Use For heating, ventilation, air conditioning and chilled water plant equipped with controls

More information

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700 3 113 Synco 700 Bus Operator Unit RMZ792 Communicating operator unit for operating up to 150 controllers, room units and central units from the Synco 700 range via Konnex bus. Favorite pages can be freely

More information

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates 1 883 1883P01 1883P02 QFM4160 AQF4150 Symaro Duct Sensors for relative humidity and temperature with calibration certificates QFM41 Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 420 ma for

More information

Rotary version, three-position control

Rotary version, three-position control 4 622 Residential Air damper actuators GXD..31.1 Rotary version, three-position control Electric motor-driven actuators for three-position control 1.5 Nm nominal torque AC 24 V or AC 230 V rated voltage

More information

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix s 3 262 Climatix Climatix AHU ext. module 14 I/O POL955.XX/XXX POL955.XX/XXX is a versatile Climatix extension module that can be connected to any type of Climatix POL6xx controller. Its high level of

More information

Heating Circuit Controller

Heating Circuit Controller 2 706 Synco living Heating Circuit Controller RRV918 RF-controlled heating circuit controller for up to 8 heating circuits RF communication based on KNX standard (868 MHz, bidirectional) Connection facility

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 6 A Compact design, only 50 mm wide Simple DIN rail mounting Absolutely interruption-free buffering of mains failures through immediately

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke s 4 501 ACVATIX Electromotive actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal SAX61.. Operating voltage AC/DC 24 V, control signal DC 0 10 V,

More information

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12 3 877 3877P0 RXL Room controllers Communicating controllers for fan-coil applications FC-0, FC-, FC2 RXL2. RXL22. The RXL2. and RXL22. room controllers are used for temperature control in individual rooms.

More information

Room controller. For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode)

Room controller. For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode) s 3 874 RXB Room controller For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and TE mode) RXB24.1 The RXB24.1 room controller is used for temperature control in

More information

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Uninterruptible power supply with integrated power supply unit INTERFACE Data sheet 104211_en_00 1 Description PHOENIX CONTACT - 01/2010 Features The MINI-DC-UPS provide an uninterruptible DC voltage both

More information

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates 1 859 1859P01 1859P02 1859P04 QFA4160 QFA41 D AQF4150 AQF3153 Symaro Room sensors for relative humidity and temperature with calibration certificates QFA41 Operating voltage AC 24 V / DC 13.5...3 Signal

More information

Room unit with PPS2 interface

Room unit with PPS2 interface 1 626 Room unit with PPS2 interface for use with: controllers with a PPS2 interface QAA88.3 Room temperature measurement Key buttons for adjustment of the room temperature setpoint Key buttons for operating

More information

Use. Functions. OpenAir TM. Linear version, modulating, AC 24 V

Use. Functions. OpenAir TM. Linear version, modulating, AC 24 V 4 666 OpenAir TM Air damper actuators Linear version, modulating, AC 24 V GBB16...2 Electromotive linear actuators, DC 0...10 V modulating control signal, nominal force 440 N, operating voltage AC 24 V,

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

VAV compact controller KNX / PL-Link

VAV compact controller KNX / PL-Link s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air

More information

Touch Panels 10.1" and 15.6"

Touch Panels 10.1 and 15.6 Desigo Control Point Touch Panels 10.1" and 15.6" PXM40.E, PXM50.E, PXM40-1, PXM50-1, PXA.V40, PXA.V50 High-quality touch panels for technical on-site operation of plants as well as room operation. Optimized

More information

EXOcompact. Third generation freely programmable controllers

EXOcompact. Third generation freely programmable controllers revision 1 013 EXOcompact Third generation freely programmable controllers Small, compact controller with different types of communication, with or without built-in display. EXOcompact can be used either

More information

Room Temperature Controller

Room Temperature Controller 3 023 Room Temperature Controller for four-pipe fan coil units RCC30 Outputs for on / off valve actuators Outputs for three-speed fan Control depending on room or return air temperature Operating modes:

More information

Heating Circuit Controller

Heating Circuit Controller 2 705 Synco 900 Heating Circuit Controller RRV912 RF-controlled heating circuit controller for up to 2 heating circuits RF communication based on KNX standard (868 MHz, bidirectional) Connection facility

More information

Transponder card holder

Transponder card holder 6 336 HOTEL SOLUTION Transponder card holder HTH3.1/B Transponder card holder for identification of room occupancy status Touch-free recognition of access code on transponder card Transfer of access code

More information

TC Modular Series for BACnet Networks

TC Modular Series for BACnet Networks Technical Specification Sheet Document No. 588-783 July 28, 2017 TC Modular Series for BACnet Networks Features Figure 1. TC Modular. The TC Modular Series for BACnet networks is a high-performance modular

More information

LON Module for Variable Speed Drive

LON Module for Variable Speed Drive 5 193. LON Module for Variable Speed Drive SED2 Conforms to and is certified to the LONMARK Interoperability Guidelines enabling information sharing with other LONMARK products. LONMARK-compliant with

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-MOD Communicative rotary actuator for ball valves orque motor 5 Nm Nominal voltage AC/DC 24 V Control modulating,, hybrid mode Conversion of sensor signals Communication via BACnet

More information

Sauter Systems

Sauter Systems 96.692/1 EYZ 292:, interface The is a interface for connecting the CASE Suite/ programming tools and the various novapro software on the management level to the EY3600 system with in a local area network

More information

Compact actuating room automation stations, BACnet/IP, AC24 V (Actuating DXR)

Compact actuating room automation stations, BACnet/IP, AC24 V (Actuating DXR) Desigo Room Automation Compact actuating room automation stations, BACnet/IP, AC24 V (Actuating DXR) DXR2.E10PL-102B, DXR2.E10PLX-102B Combination room automation station and actuator for buildings with

More information

Electromotoric actuators

Electromotoric actuators 4 861 ACVATIX Electromotoric actuators for Combi-valve types VPI45.., DN15 32 SSD31.. SSD81.. SSD61.. SSD31.. operating voltage AC 230 V 3-position control signal SSD81.. operating voltage AC 24 V 3-position

More information

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO Order Number: 8160.UISO Status: V3; 17.09.2010c G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 UMB ISO CONVERTER ISOCON... 6 CONFIGURATION...

More information

Touch Panels 10.1" and 15.6"

Touch Panels 10.1 and 15.6 Desigo Control Point Touch Panels 10.1" and 15.6" PXM40.E, PXM50.E, PXM40-1, PXM50-1, PXA.V40, PXA.V50 High-quality touch panels for technical on-site operation of plants as well as room operation. Optimized

More information

Air Damper Actuators Modbus RTU

Air Damper Actuators Modbus RTU s OpenAir Air Damper Actuators Modbus RTU GMA.., GCA.. Spring return types Air Damper actuators 7 Nm / 18 Nm (spring return) with Modbus communication GMA.. 7 Nm nominal torque GCA.. 18 Nm nominal torque

More information

Communication module to connect M-bus devices to POL6xx.xxx controllers.

Communication module to connect M-bus devices to POL6xx.xxx controllers. s 3 936 Climatix TM Climatix communication M-Bus module POL907.00/xxx Communication module to connect M-bus devices to POL6xx.xxx controllers. The POL907.00/xxx communication module offers the following

More information

Non-communicating room controllers

Non-communicating room controllers 3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For

More information

Air Damper Actuators Modbus RTU

Air Damper Actuators Modbus RTU s OpenAir Air Damper Actuators Modbus RTU GEB.., GIB.. Non-spring return types Damper actuators 15 Nm / 35 Nm (non-spring return) with Modbus communication GEB.. 15 Nm nominal torque GIB.. 35 Nm nominal

More information

Compact universal controllers

Compact universal controllers 7 867 Compact universal controllers RWF55... The RWF55 is used mainly for controlling the temperature or pressure in oil- or gas-fired heating plants. If the relevant parameters are set, the RWF55 can

More information

Communication over Modbus protocol Connection with multiple controllers Application upgrade by using an SD 1) card or a USB stick

Communication over Modbus protocol Connection with multiple controllers Application upgrade by using an SD 1) card or a USB stick Climatix Climatix touch panel POL8T.4X/STD POL8T.7X/STD POL8T.8X/STD The Climatix touch panel offers the following features: Power supply over DC 24V Ethernet port and serial port connection SD ) card

More information

DS December Omni BEMS Controller

DS December Omni BEMS Controller DS 30.01 Models: OMC40: 40 OMC40D: OMC40 with Display OMC0: 0 OMC0D: OMC0 with Display OMC14: 14 OMC14D: OMC14 with Display Omni BEMS Controller Overview The Innotech Omni generation of Native BACnet BEMS

More information

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING Product and Applications Description Note If the application program is not loaded completely by the ETS, you had better interrupt the 24 V voltage supply of the I/O-module during the loading interval.

More information

Air damper actuators

Air damper actuators 4 604 OpenAir Air damper actuators Rotary version, AC/DC 24 V and AC 230 V GQD...1 GQD 1 Electric motor-driven actuators for two-position and three-position control as well as DC 0 10 V control 2 Nm nominal

More information

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes Datasheet SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/DC, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO 24V DC 0.5A 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY:

More information

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current Data sheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information Engineering

More information

Immersion Temperature Sensors

Immersion Temperature Sensors 1 782 1782P01 Symaro Immersion Temperature Sensors QAE2164 QAE2174 Active sensors for acquiring the water temperature in pipes and tanks Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V or

More information

TRIO-DIODE/12-24DC/2X10/1X20

TRIO-DIODE/12-24DC/2X10/1X20 Redundancy module INTERFACE Data sheet 104278_en_00 1 Description PHOENIX CONTACT 20100423 Features TRIO DIODE is the DINrail mountable redundancy module from the TRIO POWER product range. Using the redundancy

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current Data sheet SIMATIC S7-1200, CPU 1211C, COMPACT CPU, DC/DC/RELAY, ONBOARD I/O: 6 DI 24V DC; 4 DO RELAY 2A; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 50 KB General information

More information

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current Datasheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information Engineering

More information