CDW7. Standard: IEC Application. Standard and certification. International standard: IEC Approved certification: CB, CE, KEMA
|
|
- Walter Craig
- 6 years ago
- Views:
Transcription
1 Application Applied to power distribution of AC Hz/60Hz, rated operational voltage 400/ 690V, rated current 200A~6300A and lower For power distribution and protecting circuit and power supply equipment aganist harm from overload, undervoltage, short circuit, earthing, and other faults Circuit breaker which ampere frame size is under 630A can protect motor aganist overload,undervoltage and shortcircuit Core parts use intelligent control unit which has accurate discrimination protection, it can avoid unnecessary power failure and enhance the reliability of power supply system Standard and certification International standard: IEC Approved certification: CB, CE, KEMA Operating condition and installation recommendation Ambient temperature shall be controlled between +40 and -5, the average temperature in 24 hours shall not exceed +35 Note:contacting manufacturer about circuit breaker used in place where ambient temperature is higher than +40 or lower than -5 42
2 Parameter and characteristics Certification approved: IEC IEC In Icu Ics Icm AC 400V AC 690V AC 400V AC 690V AC 400V AC 690V AC 400V AC 690V CDW , 4 B /400/630 /800/ CDW , 4 B 0 400/ /800/1000 /12/1600/ CDW , 4 B 0 400/ /20 / CDW , 4 B /00 /
3 Protection characteristics Fault and alarm reset button Fault/Alarm LED In normal state, this LED is off. In case of fault release, the red LED will flash quickly; in case of alarm, the red LED will be on constantly Normal LED As long as the controller is on and operates normally, the green LED always flashes Communication indicator The communication state indication is as follows: Profibus: OFF if no communication; ON if communication exists Modbus: OFF if no communication; flash if communication exists Device Net: Flash if no communication; ON if communication exists Curve LEDs Red LEDs exist behind the curve. In case of fault release, the corresponding LED will flash indicating the fault type; During the parameter setting process, the LED is always on and indicates the current item. Keypad Measure key l, used to switch to the default measurement menu. Set key 2, used to switch to the parameter setting menu. Protection Key 3, used to switch to the protection parameter setting menu. Info key 4, used to switch to the historical record and maintenance menu. Up, Move up the cursor through the menu items on the current level, or increment the value of the selected parameter. Down, Move down the cursor through the menu items on the current level, or decrement the value of the selected parameter. Exit, exit from the current level and return to the upper level, or cancel the current parameter selection. Select, Select to enter into the next level from the current item, or select the current parameter, or store the change. 44
4 45
5 46
6 ECWS- H Different curves available for long time delay protection Different curves available for inverse short time delay protection Definite short time delay protection Instantaneous protection Current unbalance (open phase) protection Earth protection Earth fault alarm Neutral phase protection Load monitor Four phase current (I1, I2, I 3, IN) and earth current Thermal capacity Up to 8 fault logs Up to 8 alarm logs Up to 8 position logs Historical current peak Contact equivalence Number of operating cycles Clock function Self-diagnosis function LCD display of Chinese GUI LED indication Key operation MCR and out-of-limit tripping protection DO Signal alarm function Communication function ECW - M ECW - H Long time delay protection Definite time delay + inverse time delay for short time delay protection Instantaneous protection Earthing protection Load monitor Different curves available for long time delay protection Different curves available for inverse short time delay protection Definite short time delay protection Instantaneous protection MCR and out-of-limit tripping protection Current unbalance (open phase) protection Earth protection Earth fault alarm Max. phase current Four phase current (I1, I2, I 3, IN) and earth current Four phase current (I1, I2, I 3, I N ) and earth current Thermal capacity Fault log Self-diagnosis function Feature test function Up to 8 fault logs Up to 8 alarm logs Up to 8 position logs Historical current peak Contact equivalence Number of operating cycles Fault clock function Self-diagnosis fault log Self-diagnosis function Feature test function Digital display LED indication Key operation Digital setting of protection parameters LCD display of Chinese GUI LED indication Key operation DO Signal alarm function MCR and out-of-limit tripping protection Earth fault or leakage protection (either) Over-voltage protection Under-voltage protection Voltage unbalance protection Over-currency protection Under-frequency protection Phase protection Inverse power protection Demand protection Zonal system interlock protection Communication function Neutral phase protection Load monitor 47
7 CDW ECWS-H intelligent controllers Ir1=(0.4~1)ln CDW7-2000~6300 ECW-M intelligent controllers Ir1=(0.4~1)ln ECW-H intelligent controllers Ir1=(0.4~1)ln 1.05 Ir1 h 1.3 Ir1 h 1.5Ir1 2.0Ir1 3.0Ir1 2h 2h 8,12.8,19.2,32,48,64,80, 108,144,224,320,480,640, 800,960, ,5.32,8.00,13.32,20.00, 26.66,33.30,45.00,60.00, 93.32,133,200,266,333, 400, ,2.00,3.00,5.00,7., 10.0,12.5,16.8,22.5,35.0,.0,75.0,100,125,1,162 2h 1h 15,30,60,120,240, ,16.9,33.8,67.5,135,270 2h 1h 15,30,60,120,240,360,480, 600,720,840, ,16.9,33.8,67.5,135,202. 5,270,337.5,405,472.5,540 Ir2=(1.5~15)In 15% Ts=K/10(N 2-1),(Ts 20ms) 0.1,0.2,0.3, ,0.13,0.2,0.27 Ir2=(0.4~15)In 10% I 2 Ts= 8Ir1) 2 ts 0.1,0.2,0.3, ,0.16,0.25,0.34 Ir2=(1.5~15)In 10% Ts=K/10(N 2-1),(Ts 0.1,0.2,0.3, ,0.13,0.2, ms) ECWS-H ECW-H CDW7-1000~6300A (1.0~20)ln 15% ECW-M CDW Ir3=1In~KA+OFF 15% CDW Ir3=1In~75KA+OFF 15% CDW IIr3=1In~100KA+OFF 15% Ir4=(0.2~1.0)In 10% Ir4=(0.2~1.0)In 10% Ir4=(0.2~1.0)In 10% 0.1s~1s (Rank difference 0.1s) 0.1~0.4s (Rank difference 0.1s) 0.1s~1s(Rank difference 0.1s) 48
8 Auxiliary functions AC 380V (0.35~0.7)Ue (0.85~1.1)Ue 0.35Ue 36VA 5VA AC220V (0.35~0.7)Ue (0.85~1.1)Ue 0.35Ue 24VA 5VA AC380 AC220 DC220 DC110 36VA 24VA 24W 24W 5VA 5VA 5W 5W (0.7~1.1)Us less than 30ms ~6300 AC380 AC220 DC220 DC110 36VA 24VA 24W 24W 10VA 10VA 10W 10W (0.85~1.1)Us less than 70ms 49
9 CDW7-2000~6300 In 2000A 2000A In 3200A 3200A In 6300A CDW AC380 AC220 DC220 DC110 85VA 85VA 85VA 85VA 110VA 110VA 110VA 110VA 1VA 1VA 1VA 1VA 80VA 80VA 80VA 80VA (0.85~1.1)Us less than 5s AC-15 DC-13 U/Ue cos 0.95 I/Ie U/Ue cos T Pe Pe 10 Pe W T0.95e s upper limit 300ms
10 Overall and mounting dimension CDW7-1000A fixed circuit breaker outline and horizonal/vertical connected dimension 200, , , , 1000 L L L N
11 CDW7-1000A drawout type circuit breaker outline and horizonal/vertical wiring Unit:mm 200, , , , P 4P L L L L L n H
12 CDW7-2000A~3200A CDW7-2000A fixed circuit breaker vertical connection diagram CDW7-2000A~3200A fixed circuit breaker overall and horizonal/vertical wiring L1 L2 L3 CDW P 4P CDW P P L In A 400~ ~ ~ Unit:mm a CDW mounting dimension is same regardless of different current used in"horizonal-wiring" or"vertical-wiring" 53
13 CDW7-2000A~6300A CDW7-2000A drawout circuit breaker vertical connection diagram CDW7-2000A~6300A drawout type circuit breaker outline and horizonal/vertical connection Unit:mm CDW CDW CDW (4000/00A) CDW P 4P 3P 4P 3P 4P 3P L L L L L W W b In A 400~ ~ ~ ~ ~ ~6300 a note: 1) CDW the mounting dimension is same regardless of different current used in"horizonal-connected" or "vertical-connected" 54
14 CDW CDW7-1000A CDW7-1000A CDW7-2000~6300 CDW7-2000~6300A CDW7-2000~6300A CDW7-2000~6300 panel cut-out dimension and mounting dimension a b CDW CDW CDW c 3P (4000/00A) 246.5(6300A) 4P (4000/00A) -- Unit:mm 55
15 Auxiliary connection diagramn F X with different current ratings shall connect with different sources when controller power choose DC,the output is DC24V,user can select DC power module circuit breaker status detection terminal(used when MCR function included) 45 overload pre-alarm signal output 46 automatic diagnosis alarm signal output 47 fault trip alarm signal output 48 earthing but non-tripping,only alarm signal output 49 four groups of contacts output common terminal 51 externally sensor input terminal 58 able to directly connect to power supply(automatic pre-energization),also able to join up with normal open pushbutton to connect to power supply(manual preenergization) 56
16 Pin functions: Pin 1# and 2#: Auxiliary power input,pin 1# is positive for DC input Pin 3#, 4#, 5#: Fault trip contact output (4# is common terminal); contact capacity: AC380V, 16A Pin 6# and 7#, 8# and 9#: Two groups of auxiliary contacts for breaker status; contact capacity: AC380V, 16A 12#,13#(Contact1)and 14#,15#(Contact2)and 16#, 17#(Contact3)and 18#,19#(Contact4):Output of four groups of signal for controllers,contact capacity:4a/240v 7A/24VDC 20#: Earth protection 21#~24#:input of voltage signal (Note:the order cant be wrong) Components: Q - Under-voltage release F - Shunt release X Closing electromagnet DF - Auxiliary switch M - Motor SB1 Button for closing SB2 Button for shunt Note: 1. If the control voltage values of Q, F, X, and M are different to each other, these components can be connected to different power supply units; in the application, the shunt release and closing electromagnet shall be connected serially with normally open and normally closed auxiliary contacts (the part enclosed by dotted lines shall be connected by the user; the part represented by a two-dot chain line is the wiring of circuit 51); Note 2: The pin 35# can be connected to the power supply directly (automatic pre-energy storage) or connected serially to a normally open button and then to the power supply (manual pre-energy storage); Note 3: If the user requests, pin #6~#7 can be connected to normally closed contacts; Note 4: The ECW power supply module I is a DC power supply module, and it can be omitted if the power supply is AC power supply; the polarity and lead-ins/ lead-outs shall not be reversed (for draw-out type circuit breakers, the lead-outs of the power supply module has been connected before the circuit break is shipped from the factory); Note 5: In case of circuit 47, the auxiliary contacts are four closed and four open contacts; pin #25 and #26 are input terminals of an external current transformer, used for earth fault protection as (3P+N)T type ; Note 6: In case of circuit 51, the auxiliary contacts are six closed and six open contacts (or five closed and five open contacts); pin #25, #26, and #51 form normally open and normally closed contacts; Note 7: If Profibus or any other protocol is used, ECW-H + DP conversion module and other conversion modules must be ordered; ECW power supply module lv and ECW201 relay module must be ordered separately; Note 8:Pin #12~#19 input/output contacts can be user-defined programmable signal contacts. 57
17 1 2: terminal 35# can directly connect to power supply (automatic pre-energy storage),or join up with normal open pushbutton to connect power supply(manual pre-energy storage) 3: terminal 6#~7# can lead out normal close contact if user suggested 4: ECW power supply module is DC power supply module, the module doesn't exist when power supply current is AC, polarity,incoming line and leading-out line shall not connected reversely(leading-out terminal of power supply module in drawout type had been connected before sale) 5: in 47 circuit,auxiliary contact is 4 open 4 close;25# 26# is input terminal of external sensor 6: in 51 circuit,auxiliary contact is 6open6close(5open 5close);25# 26# 51# form normal open normal close contact(earth-leakage protection excluded) 7: if using profibus or other protocols, user shall order ECW-H+HP transformation module and others;ecw power supply modulev,ecw201 relay module and others shall order seperately 8: #12~#19 output input contacts are programmableselfdefined signal contaccts 1# 2#: 1# is the front terminal when DC is supplied by auxiliary power 3# 4# 5 AC380V 16A 6# 7# 8# 9#: two groups of circuit breaker status auxiliary terminal: AC380V 16A 10# 11#: respectively as the communication leading-out of RS485A,RS485B 12#: overload pre-alarm signal output 13#: communication remote control shunt release output 14#: communication remote control closing output or instantaneous short time-delay trip signal output 15#: communication remote control energy storage or long time-delay trip signal output 16#: S-earth(RS-485 transmissionn common ground wire 17#: load monitor output1 19#: signal output common earth wire 21#: neutral voltage signal N phase 23#: voltage signal B phase 18#: load monitor signal 2 20#: PE line,shield earth wire 22#: voltage signal A phase 24#: voltage signal C phase 58
18 Other additional parameter 59
19 Series Air Circuit Breakers Order Instructions Customer Sets purchased Date Mode CDW7 Fixed Draw-out 3 Poles 4Poles Rated voltage AC400 AC690 Rated current In= A H Type Intelligent electronic trip Accessaries Mechanical interlock Basic function Overload long delay time protection Short-circuit short delay time protection Earthing protection Load monitoring function (Not available for L type) Short-circuit instantaneous protection Metering function Power supply AC 230V AC 400V DC 220V DC 110V Under-voltage instantaneous trip AC 230V AC 400V Under-voltage trip Under-voltage time-delay trip 1s 3s 5s Shunt trip AC 230V AC 400V DC 220V DC 110V Energy releasing electromagnet AC 230V AC 400V DC 220V DC 110V Motor Driven AC 230V AC 400V DC 220V DC 110V Interphase barrier Escutcheon N phase external connection Earth-leakage CT(Only for cable) Auxiliary switch standard(4a4b) special(6a6b) Auxiliary Connection Terminal 1-lock,1-key 2-lock,1-key 3-lock,1-key Steel-cable interlock Interlocking rod with 3 switches Interlocking rod with 2 switches Door interlock(available for Draw-out type) Note:for any special requirement,please contact with the manufacturer. 60
SACE Emax 2 Specification guide
SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or
More informationNW08 to NW63 fixed circuit breakers Circuit breakers
fixed circuit breakers Circuit breakers DB404362.eps DB404363.eps A Masterpact fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b
More informationSentron 3VT circuit breakers Simply Smart: First choice for power distribution
s Sentron 3VT circuit breakers Simply Smart: First choice for power distribution www.siemens.com/industry Sentron 3VT Molded Case Circuit-Breakers - 10-1600Amperes With the standard line of 3VT molded-case
More information.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical
Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of
More informationQuantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III
Compact DC Drive Package The delivers a DC drive package that integrates the intelligence of the Mentor II with a space saving design that incorporates many accessories typically required in the North
More informationMetering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs
.3 Features and Benefits Saves installation time and cost One part number to order; no need to worry that any part has been left out Pick the meter or meters you need as it is designed to fit various Eaton
More informationMULTI 9 System Catalog UL Recognized C60N Supplementary Protectors
UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5
More informationCommon Departures Interconnecting Facilities Requirements
Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low
More informationMULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors
B Curve NC100H Supplementary Protectors Rating 1P 2P 3P 4P 80 MG27164 MG27175 MG27186 MG27197 MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors C Curve NC100H Supplementary Protectors
More informationWiring diagrams. Content. Information for reading and graphic symbols... 5/2. Wiring diagrams of the circuit-breakers... 5/3
Wiring diagrams Content Information for reading and graphic symbols... 5/2 Wiring diagrams of the circuit-breakers... 5/3 Electrical accessories... 5/4 5/1 Information for reading and graphic symbols State
More informationAir Circuit Breaker (ACB)
MPACT Air Circuit Breaker (ACB) Rated from 0 to 000A the MPACT circuit breaker has been designed to meet the most stringent demands in fault detection and safe interruption thereof. Available in frame
More informationSECTION SWITCHBOARDS
SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS
More information9926 Series Branch Rated Circuit Breakers AC Version
Branch Rated AC Version Hydraulic Magnetic Single pole and double pole versions 20/240 VAC, 50/60 Hz Up to 25A Just 3 mm wide Mounts on 35mm DIN-rail UL 489 listed, CSA C22.2 No. 5-02, CE VDE Ordering
More informationOCR alarm (AL) (standard) When it happen to trip by over current, ground fault ( GFR ) and Earth leakage ( ER ), it issue a warning alarm.
A Power supply module This module provides control source for DISPLAY module,trip indicator and several indicators (LEDs). (Even when the control power source is off, the function of over current protection
More informationMicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers
MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers Easily replace electro-mechanical trip units with the latest electronic, digital trip unit technology Ensure
More informationInstructions Order No. 3ZX1812-0WN60-0AC0 /
as copy and fax form Instructions Order. 3ZX1812-0WN60-0AC0 / 9239 9916 176 SIEMENS 3W... ID.:... OK! Caution! Dangerous high voltage! Dangerous storage spring! De-energize the equipment and secure against
More informationPHASE MONITOR RELAYS Product Summary
Product Summary Phase Monitor Relays provide protection against premature equipment failure caused by voltage faults on 3 Phase systems. All Macromatic Phase Monitor Relays are designed to be compatible
More informationNPW800R RETROFITTING. Power and Volatge Protection Relay
RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)
More informationSENTRON 3VL Molded Case Circuit Breakers
Siemens AG SENTRON VL Molded Case Circuit Breakers Switching, Protection, Measuring and Monitoring Devices For the operating range from A to 00 A, the molded case circuit breaker ensures the optimum overload
More informationHAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL
HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD CONTENT 1 OVERVIEW... 5 2 PERFORMANCE AND CHARACTERISTICS... 6 3 SPECIFICATION... 8 4 OPERATING...
More informationPGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document
More informationSYMAP R Plug in Variants FI, MI, 87M, TI Technical data
SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection
More informationTmax molded case circuit breakers Specification guide
Tmax molded case circuit breakers Specification guide Tmax Specification Guide 1 Specification Number: 26 28 16.14 Product Name: MOLDED CASE CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings
More informationDIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers
DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS Introducing the DIN Series High-quality, high-performance circuit breakers Features (1) All models fully comply with IEC regulations
More informationMicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Westinghouse Power Circuit Breakers
MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Westinghouse Power Circuit Breakers Easily replace electro-mechanical trip units with the latest electronic, digital trip unit technology Ensure
More informationIntroduction Circuit Protection
Introduction Circuit Protection Weidmuller s DIN-rail mounted circuit breakers are available for use in applications where circuit protection must be able to distinguish between circuit overloads and short
More information24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD
United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated
More informationC C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description
CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated
More informationAir Circuit Breakers. 1/2 Introduction
/2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers /5 Introduction Up to 6300 A (AC), IEC /6 Introduction /9 General data /6 3-pole, fixed-mounted versions /23 3-pole, withdrawable
More informationLV power circuit breaker and switch-disconnectors. Masterpact NW Direct current 1000 to 4000 A. Catalogue
LV power circuit breaker and switch-disconnectors Masterpact NW Direct current 1000 to 4000 A Catalogue 2002 Get more with the world s Power & Control specialist Masterpact NW General contents Presentation
More informationPowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)
PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 0CT00R/0 0 CONTENTS Description..............................................Page Description.............................................
More informationSECTION SOLID-STATE REDUCED VOLTAGE STARTERS
SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.
More informationNM1 Moulded Case Circuit Breaker. 1. General. 2. Type Designation. 3. Classification. Moulded Case Circuit Breakers. Russia.
Moulded Case Netherland Czech Ukrain ussia outh Africa NM Moulded Case Circuit Breaker. General. Certificates: KEMA, CC, PCT, EC, UKTET;. Electric ratings: AC V,/Z, ~A;. Mounting mode: Vertical and horizontal;.
More informationBulletin 1489 Circuit Breakers. Selection Guide
Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options
More informationATS CONTROLLER OPERATING MANUAL
HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER OPERATING MANUAL Smartgen Electronic CONTENT 1 SUMMARY... 4 2 PERFORMANCE AND CHARACTERISTICS... 4 3 SPECIFICATION... 5 4 OPERATING... 6 4.1
More information4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection...
.3 Product Description Drawout molded case circuit breaker switchboard Front accessible Front connected Through-the-door design drawout mechanism through 600A Insulated case UL 89 breakers up to 200A Visual
More informationATP1006-4 TIME SWITCH Instruction Manual 1 Purpose and Scope ATP1006-4 TIME SWITCH of Belling apparatus, control circuit with AC 50Hz/60Hz, rated control power voltage of 220V at most and rated working
More information2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...
TPR-6 Temperature Protection Relay Instruction Manual Ver. June 1 st 2010 2 Table of Contents 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Introduction... 3 3. Wiring Diagram... 5 4. Terminals Review...
More informationCircuit Breakers, Type CTI 25M, CTI 45MB, CTI 100
MAKING MODERN LIVING POSSIBLE Data sheet Circuit Breakers, Type CTI 25M, CTI 45MB, CTI 100 Circuit breakers for short circuit and overload protection of motor applications cover together with the circuit
More informationFLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.
CENTRIFLOW PUR 3D (A, PLUG B, C, D) FAN GMPM FC101 AND SLIDE IN FREQUENCY ROTOR CASSETTE CONVERTER QUICK GUIDE FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS
More information60103 Circuit Breaker
6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard
More informationVIP 40/45 VIP 400/410
40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered
More informationSiemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE AMBERG, GERMANY
Issued to: Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE 48 92220 AMBERG, GERMANY This is to certify that Auxiliary Devices representative samples of 3UF70 followed by 0 or 1 followed by 0
More informationNewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators
NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator
More informationSection 4 Ground-Fault Protection Devices
Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that
More informationSiemens AG Air Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.
Siemens AG Air Circuit Breakers Totally Integrated Power SENTRON Configuration Manual Edition / siemens.com/lowvoltage Siemens AG Siemens AG WL Air Circuit Breakers Introduction WL air circuit breakers/
More informationCommunication COM option in Masterpact
CT CCM modbus CD CE Functions and characteristics Communication COM option in 056431 056401 The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system.
More informationGE Multilin 350 Feeder Protection Relay Specifications
GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following
More information4. CIRCUIT BREAKERS. Functional Emergency Switching
4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit
More informationwww. ElectricalPartManuals. com l Basler Electric MPS100 MOTOR PROTECTION SYSTEM ADVANTAGES WINDOWS SOFTWARE ADDITIONAL INFORMATION
The Motor Protection System is a microprocessor based digital relay which provides comprehensive motor protection including metering, communications, data recording and diagnostics. ADVANTAGES Extensive
More informationCircuit Breakers Type CTI 25M, CTI 45MB
Data sheet Circuit Breakers Type CTI 25M, CTI 45MB Circuit breakers for short circuit and overload protection of motor applications cover the current range 0.1 45 A (AC-3 rating). The product range is
More information1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control
. Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Overload Relays.................... C440/XT
More informationPowerFlex 400 AC Drive Guide Specification
PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5
More informationJtec 10kA Miniature Circuit Breaker
Jtec 0kA Miniature Circuit Breaker EN 60898 The Jtec range has been enthusiastically adopted by a diverse range of customers seeking a cost effective 0kA performance. Jtec MCBs are available in a wide
More information160 AA02SF1 AF DS-D17
Ordering Instructions The Standard Packaged Drive Program allows users to create drive packages based on their specific needs. A complete drive package may be specified by assembling a single catalog number
More informationIPS INTELLIGENT PUMP STARTER
IPS INTELLIGENT PUMP STARTER The IPS Intelligent Pump Starter features SMARTSTART motor protection, integrated electronic pump protection overload, and power metering and data logging options. Ø & Ø, 0/60
More informationMotors Automation Energy Transmission & Distribution Coatings. DWB Molded Case Circuit Breakers DWB
Motors Automation Energy Transmission & Distribution Coatings DWB Molded Case Circuit Breakers DWB Molded Case Circuit Breakers Molded Case Circuit Breakers DWB Summary Presentation 0 General Characteristics
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationDescription. Installation. Power supply
Air circuit breakers Special versions Series MEGT07 0V/500V/DC 50 up to 5000 A The air circuit breakers MEGT07 are suitable for use as disconnecting switch in DC distributions up to a rated voltage of
More informationIssued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog
Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic
More informationLV power circuit breakers and switch-disconnectors. Masterpact NT and NW Merlin Gerin. << Back. Catalogue. Building a New Electric World
More information
Electrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationOverload Relays. 3RB2 Solid-State Overload Relays. 3RB20, 3RB21 for standard applications. 5/48 Siemens LV Overview
Overload Relays Siemens AG 2009 Overview 1 2 2 (1)Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors and soft starters, these connecting
More informationResidual current circuit breakers
circuit breakers (RCCB) The residual current circuit breakers are most up-to-date devices mainly used for protection against indirect contact, but in some cases also against direct contact. The residual
More informationOEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers
OEM CLIMATIX TM Room unit QAA822 with2- wire interface For use with Climatix controllers Remote control of air conditioning unit Mandík Measurement of the room temperature Buttons for starting, setting
More informationDGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application
DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and
More informationSR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.
SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering
More informationSED2 Variable Frequency Drives with Electronic (E) Bypass Options
SED2 Variable Frequency Drives with Electronic (E) Options Description The E- Options are companion packages for the family of SED2 Variable Frequency Drives (s). For information on the family of SED2
More informationMG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD
United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL
More informationSOCOMEC SIRCOVER MANUALLY OPERATED CHANGEOVER SWITCHES
MANALL OPERATED CHANGEOER SWITCHES are manually operated multipolar changeover switches. They changeover between two low voltage power circuits under load and provide safety disconnection. Application:
More informationThe City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2
The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results
More informationIZMX Series Air Circuit Breakers. Small, flexible, efficient
IZMX Series Air Circuit Breakers Small, flexible, efficient Versatile circuit breakers up to 4000 A for cost-effective, optimized solutions. The IZMX16 of the NRX series is the smallest air circuitbreaker
More informationMiniature Circuit-Breaker IEC Series 8562
> 1 to 3 pole versions > Rated current from 0.5... 40 A > 6 or 10 ka breaking capacity to DI VDE 0641, respectively E 60898 > Isolating Function to E 60947-2 > Permanently set thermal and magnetic trips
More informationSpectra RMS Circuit Breakers with microentelliguard Trip Units
GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications
More informationPLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet
Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical
More informationTeSys protection components
Description, characteristics -pole electronic thermal overload, TeSys LR9D0, 0, 08, and LR9D0S DB8880.eps 7 / & 8 Description LR9D0, 0, 08 and self-powered electronic thermal overload are designed for
More informationBulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications
Power Circuit Control Circuit (External Source) Control Circuit (Internal Source) Short Circuit Current Rating (SCCR) Application Electrical Ratings Three-phase Number of Poles 3 Input Power Terminals
More informationIZMX series Air Circuit Breakers with Power Xpert Releases PXR
IZMX series Air Circuit Breakers with Power Xpert Releases PXR Australia and New Zealand The new series IZMX16/IZMX40 Small, flexible & fully loaded Versatile circuit breakers up to 4000A for cost-effective,
More informationLM10 to MM200 Retrofit
Grid Solutions LM10 to MM200 Retrofit Replace old LM10 Motor Controller relays with the Multilin TM MM200 Motor Management System The LM10 Motor Controller (discontinued in 2013) has been replaced by new
More informationAir & Moulded Case Circuit Breaker Service & Maintenance
Charnchanok T., Low Voltage Products Division Air & Moulded Case Circuit Breaker Service & Maintenance November 12, 2013 Slide 1 Air Circuit Breaker : New Emax Series Reliability and sturdiness - Materials
More informationJ7MN. Ordering Information. Motor Protection Circuit Breaker. Model Number Legend. MPCB system. Options. Motor Protection Circuit Breaker J7MN I-1
Motor Protection Circuit Breaker J7MN ) MPCB system Rotary and switch types Rated operational current 32 A, 63 A and 00 A Switching capacity up to 00 ka/400 V Fixed short-circuit release = 3 x I u Overload
More informationQUICK REFERENCE PRICE GUIDE JUNE 2016
QUICK REFERENCE PRICE GUIDE JUNE 2016 OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this Quick Price Guide carry a guarantee against defects in materials and workmanship
More informationSECTION ( ) LIGHTING CONTROL PANELBOARD
(26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting
More informationTeSys contactors 5. Selection 5. For utilisation category AC-3. Operational current and power conforming to IEC (θ y 60 C) Contactor size
Selection TeSys contactors For utilisation category AC- Operational current and power conforming to IEC (θ y 0 C) Contactor size Maximum operational current in AC- Rated operational power P (standard motor
More informationTeSys IEC Contactors and Overload Relays
TeSys IEC Contactors and Overload Relays Making High-Fault Short-Circuit Current Ratings Simple Schneider Electric is an industry leader in IEC contactors and overload relays, and is recognized as the
More informationlow voltage GLOBAL CATALOGUE RANGE Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters
CTLOGUE GLOBL RNGE 2. Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters 2. 2. Product Overview. 2.2 Overload Relay Setting Range 2. - 2.8 Product Specifications 2.9-2. Contactor
More informationCurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.
CurrentWatch Current Sensors Ground Fault Sensors with Solid-State or Mechanical Relay s 1 Contents Overview.................... 1 Model Selection, Switches...... 2 Model Selection, Accessories... 3 Wiring
More informationOriginal operating instructions Safety relay with relay outputs G1501S / / 2016
Original operating instructions Safety relay with relay outputs G50S UK 8023637 / 00 02 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...5 3 Items supplied...6 4 Functions
More informationRemote communication options include IEC Ethernet communications or Modbus (RS485).
2019 The MELPRO D series relay is suitable for feeder protection, motor protection and transformer protection applications. The relay offers multiple step time grading for over-current protection co-ordination.
More informationFTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE
FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP750-51(B) FTA750 Full Voltage Starting Limited Service Electric Fire Pump Controllers Product Description Description Firetrol
More informationMV Network Switchgear, Protection and Control
MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control
More informationAIR COOLED MODULAR RECTIFIER
CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:
More informationMPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution
MPSC-2000 Microprocessor-based protection and metering devices for low voltage power circuit breakers ABB Power Distribution Introduction For circuit breaker protection, metering and communications, the
More informationCompact NSX communication
Functions and characteristics Compact NSX communication Communications modules All Compact NSX devices can be equipped with the communication function via a prewired connection system and a Modbus network
More informationZelio Control-modular measurement and control relays 1
Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and
More informationHAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL
HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co.,
More informationC E R T I F I C A T E O F C O M P L I A N C E
Issued to: This is to certify that representative samples of SIEMENS AG DF CP R&D VC 2 WERNER-VON-SIEMENS-STRASSE 48 92224 AMBERG, GERMANY MOTOR CONTROLLERS, MANUAL (See following page for additional information.)
More informationINTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box
INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families
More informationF-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide
MODBUS FLOW AND ENERGY MEASUREMENT F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0725-2
More informationBE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY
BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES
More information