1 1 On Line Diagnostics for Condition Based and Reliability Centered Maintenance Carl Öhlen* STRI Abstract-- Maintenance is required for almost all equipment in order to guarantee its performance, prevent failures and to extend the life expectancy. Modern high voltage equipment as well as protection & control equipment requires less maintenance compared to older technology. Unnecessary maintenance can also be a cause of failures by itself. Both failures and traditional maintenance will normally result in a disconnection of a part of the power system and by this reduce the availability. This paper describes on-line monitoring and on-site measurement for interruption free diagnostics of the power system. It also describes possible web-based On Line Analyser with database and trends. This creates information for Condition Based Maintenance (CBM) and Reliability Centred Maintenance (RCM). The goal is to achieve the perfect balance between maintenance and operation to optimize both availability and cost using on-line monitoring and web based diagnostics together with state-of-the art protection & supervisory control. I. INTRODUCTION The unavailability of the power system can be simplified as MTTR/MTBF + MTTM/MTBM: - MTBF = Mean Time Between Failure - MTTR = Mean Time To Repair - MTBM = Mean Time Between Maintenance - MTTM = Mean Time To Maintain The ideal situation with zero unavailability and 100% availability can theoretically be obtained if MTBF and MTBM is extremely high (infinity) which means that there are no faults and no need for maintenance. This is naturally impossible to obtain. The other alternative is that MTTR and MTTM is zero. This is however possible to obtain with a combination of redundancy and on-line diagnostics. Redundancy according to the n-1 criteria means for example that one component can be lost with maintained availability of power between two points. Still full redundancy for all components in a power system (lines, transformers, generators) is costly and un-realistic. If however the interruption can be limited to spontaneous faults (normally lightning) followed by a rapid auto re-closing the unavailability can still me minimised. By using on-line monitoring to discover stresses and ageing before a failure occurs and plan suitable maintenance (or replacement) the interruption of that particular part of the system can be done when other redundant part can maintain the operation. This is called CBM, Condition Based Maintenance and replaces the earlier TBM, Time Based Maintenance or in worst case NMA = No Maintenance at All. CBM can be further refined to RCM, Reliability Centered Maintenance which is using RBA, Risk Based Analysis to give the priority to maintenance and replacement activities. * carl.ohlen@stri.se
2 2 II. AN HOLISTIC APPROACH TO ASSET MONITORING A. Closing the Information Gap This vision of interruption free diagnostics of a complete network with substations, lines and cables requires a holistic approach identifying the critical components and possible supervision methods including both existing and new ways of monitoring. Today the data about the condition of different equipment is spread among different persons, organisations and measurement equipment. This includes everything from paper reports from manual inspection to digitally stored disturbance recordings. The main challenge is to convert raw data islands to useful information for Asset Management and Operation. This includes an efficient communication infrastructure and data management where for example high speed LAN/WAN according to IEC can be utilized. The major task is however still to analyse the data and present useful information for different users. This can be done manually or automatically. Since different organisations or even companies owns the assets, operate the assets and maintenance the assets another challenge is to improve the information exchange between these organisations. Some utilities has therefore created a special Asset monitoring function to handle both short term, mid term and long term analysis and planning. [1] In order to efficiently managing the data and then analyze the data to give directly applicable information to different users this paper will present a web based On Line Analyzer. This can directly communicate with on-line monitoring devices but also be the portal to enter inspection data. This means that all information about a certain asset is integrated in one portal = Asset Monitoring Site. For manual on site inspection of for example insulators and conductor joints it is however essential to have a common guide and template how to inspect and rate each object. These guides are available today together with the On Line Analyzer. How to get from raw data to information!asset Monitoring/Management!Systems integration!automatic data analysis!manual data analysis!data management!communication infrastructure!data capture Fig. 1. Data to information framework [1].
3 3 B. The right action in the right time The power system and each equipment part is designed for a certain voltage level and a certain current level. If these levels are exceeded the equipment will either fail or degenerate faster towards the technical and economical life length. There are certain defined limits, which should be verified in order to guarantee the performance of the system. You may in a very simplified manner divide this in three main areas. TABLE I EVENT/CAUSE/TIME/FUNCTION Event Cause Time to action Function Electrical short-circuit fault Lightening etc. ms Relay protection Abnormal operation Emergency load etc. seconds -hours Supervisory control Stress and ageing Insulation/contact wear days months -years On-line monitoring Lightning and other weather effects are most often the cause of an electrical short circuit and the location is most often on a transmission line. (75% - 95% of all faults) This means that it is not possible to completely eliminate. Instead a reliable and fast protection is required together with an auto re-closing scheme. Differential protection is the most accurate, rapid and selective method and can today with better communication also be used for lines even though distance protection is still in majority. The auto reclosing can be done three pole, multi pole or single pole. More advanced schemes can provide multi pole auto re-closing of two or several parallel lines in order to guarantee that a minimum of three different phases between two points are in operation. This type of logic is now relatively simple to introduce with the IEC high speed inter bay communication in a substation. Both stress, ageing and abnormal operation may lead to an electrical fault if not taken care of. But by right dimensioning of the towers, insulators, distances in combination with surge arresters and point-on-wave switching can reduce the probability for electrical failures due to lightning and switching. The software Line Performance Estimator available from STRI is such a design tool. Line Performance Estimator Fig. 2. Fault frequency and successful auto re-closing rate as a function of insulation and environment
4 C. Monitoring all links in the chain The overall availability of the chain depends on each individual link. It is therefore important to identify those critical links and assure that the condition is monitored either with continuous monitoring or manual inspection. Transformers and other equipment are monitored for temperature, breakers and GIS for SF6 density etc. But there are still no overall diagnostics, which can accurately predict if and when a more detailed test and maintenance should be done. And although a lot of data exist today there are still major parts of a substation with connected lines and cables, which are not being monitored or diagnosed. This includes insulation, operating mechanism, conductor joints, disconnectors as well as influence of pollution and weather. In the following some possible methods are presented which can be used for on-line monitoring and on-line diagnostics. Condition Monitoring 4 Generation Transmission kv Distribution kv Industry To be monitored and/or tested: " Line ending and joints (Resistance/Temp/IR) " Conductors (Temperature) " Towers (Corrosion) " Cable ending and joints (PD, Temp/IR) " Arresters (Leakage current) " Earthing switch (Resistance to ground) " Voltage transformer (Oil analysis) " Current transformer (Oil analysis) " Disconnector (Resistance/Temp) " Circuit Breaker (SF6, time, resistance, vibration) " Insulators (Temp/IR) " Power Transformer (Oil and gas analysis) " Generator (PD, temperature, vibration) Fig. 3. Different methods for condition monitoring Partial Discharge or PD monitoring is one of the methods, which now is available to monitor the insulation of generators, transformers, cables and GIS without taking the equipment out of service. The advantage is that a degeneration of the insulation can be detected well in advance and save the equipment from a complete and costly failure. The main challenge also here is to have an efficient on-line monitoring and diagnostics, which can establish when the measured PD is dangerous and requires an action. Circuit Breakers are essential for the system availability. The reliability of circuit breakers has improved during the years. International statistics shows that modern SF6 breakers with spring operating mechanisms have a low failure rate and a low maintenance requirement. It is also possible to monitor the breaker contacts by monitoring the number of operations and calculating I 2 t as a measure for contact wear. Besides for reactor breakers the wear is normally not a problem. According to statistics the operating mechanism is the major source of a failure. Traditionally time, travel or dynamic resistance has been used for breaker testing. It is however difficult to use these methods for on-line monitoring. Vibration testing is a new method, which can be used for monitoring (continuous or intervals) with a normal open-close operation.
5 Both PD monitoring and vibration monitoring gives high frequency data which has to be compared with an original signature to indicate any trends. This requires a database with old data as well as a user-friendly tool to analyse the result. Insulators are the most common part of the power system either as line insulators or as part of equipment and bushings. This means that the insulators have the highest risk for flashovers. Still there is normally no monitoring of insulators. Ageing or vandalism resulting in cracks in porcelain is an example of a mechanical defect. This can be detected by inspection. Snow and ice can also be detected visually. Pollution is more difficult. Pollution monitors available to utilities have been evaluated by CIGRÉ Taskforce first report, containing a review of monitors for characterizing pollution severity, as many as 33 different monitors were identified. The work was followed by a comparative field study where in total 11 monitors and site severity measurements were evaluated at 13 sites for a period of 24 months. [3,4] The protection and control system of modern design is to great extent self monitored. This includes both the electronics, communication but also connection to current and voltage transformers and trip circuits. These so called IEDs (Intelligent Electronic Devices) also includes disturbance, event and fault recorders, which can be used to analyse faults but also detect incorrect functions before they result in a fault. Modern IEDs designed for IEC can provide new flexibility, redundancy, functionality and communication. The standard separate hardware from functions and allows new architecture with duplication of all functions, interchange of data for more intelligent automation etc. More and more will also install high speed Internet or WAN in the station which allow rapid access of all data. 5 III. EXAMPLES OF ON-LINE MONITORING AND DIAGNOSTICS A. On-line monitoring of a generating station STRI has together with a LDIC, a German manufacturer of monitoring equipment and VB Kraft, a Swedish Utility installed a system for on-line monitoring and diagnostics of a generating station using SOLA, STRI On Line Analyser to monitor partial discharge, load and temperature. The data is collected in the station and then routed via the utility LAN and the Internet to the Asset Monitoring Site. All users can then access this site via Internet and get all historical and actual data as well as trend analysis. Fig. 4. STRI On Line Analyzer for a generating station
6 6 B. On-line monitoring of a substation STRI has together with Statnett, the Norwegian TSO installed an advance on-line monitoring and on-line diagnostics system for a 400 kv substation in Norway. Besides monitoring of electrical and environmental data, three cameras are monitoring pollution and swing angles on insulators. This is done by a picture analysing software. The data is collected in the station and then routed via the utility WAN and the Internet to the Asset Monitoring Site. All users can then access this site via Internet and get all historical and actual data as well as trend analysis. Fig. 5. STRI On Line Analyzer for a substation IV. REFERENCES [1] On-Line Condition Monitoring of High Voltage Equipment in Two Transmission Networks in Australia, CIGRE 2006 A3-201, S. Jones, A. Kingsmill, M. Blundell, J. Gabb, G. Slade. [2] Vibration Analysis for Diagnostic Testing of Circuit Breakers, IEEE Transactions, Vol 11, No. 4 Oct 1996, M Runde, G.E. Ottesen, B. Skyberg, M. Öhlén. [3] CIGRÉ Taskforce , Round Robin Pollution Monitor Study, 11 August 2000 [4] CIGRÉ Taskforce , Insulator pollution monitoring, Electra, No. 152, pp , Feb [5] IEEE DEIS Laboratory Tests and Web Based Surveillance to determine the Ice- and Snow Performance of Insulators. To be published S.M. Berlijn, I. Gutman, K.Å. Halsan, M. Eilertsten, I.Y.H. Gu. V. BIOGRAPHIES Carl Öhlen was born in Sundsvall, Sweden, on July 4, He graduated as M Sc in Electric Power Engineering at the Royal Institute of Technology in Stockholm and he has worked within the international power industry located in Brazil, Switzerland, Sweden and USA for more than 30 years especially with protection, automation and diagnostics. He is now employed by STRI, an independent technology consulting company and accredited high voltage laboratory, located in Ludvika, Sweden.
Equipment Strategy For High Voltage Circuit Breakers
Current version: 23/05/2018 EXTERNAL USE Page 1 of 7 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References... 3 1.4 Defined terms... 3 1.5 Monitoring and compliance... 3
More informationRegional Group Nordic GRID DISTURBANCE AND FAULT STATISTICS
Regional Group Nordic GRID DISTURBANCE AND FAULT STATISTICS Table contents Table contents Page 1 INTRODUCTION... 4 1.1 Contact persons... 5 1.2 Guidelines the statistics... 5 1.3 Voltage levels in the
More informationStudy Committee SC A3
Prepared by Dagmar Kopejtkova in August 2010 Study Committee SC A3 Study Committee A3 HV Equipment Theory, design, construction and application of HV equipment components, equipment and equipment systems
More informationCircuit Breaker Asset Management using Intelligent Electronic Device (IED) Based Health Monitoring
Circuit Breaker Asset Management using Intelligent Electronic Device (IED) Based Health Monitoring Carey Schneider Mike Skidmore Zak Campbell Jason Byerly Kyle Phillips American Electric Power October
More informationABB Surge Arresters Contribution to Power Quality Line Side Protection
James Taylor, Technology Support Manager / Principal Specialist May 2013 ABB Surge Arresters Contribution to Power Quality Line Side Protection May 6, 2013 Slide 1 Availability of electric power supply
More informationMotor Surge Suppressors and Cable Considerations
Motor Surge Suppressors and Cable Considerations Understanding the growing need for motor surge protection in SA Arveen Gobind Pragma Condition Monitoring (Martec) Agenda Introduction Network Motor Surge
More informationCall for Papers GCC POWER 2011 GCC Cigre s Leading Electric Power Conference & Exhibition In the Gulf Region
Call for Papers GCC POWER 2011 GCC Cigre s Leading Electric Power Conference & Exhibition In the Gulf Region Kuwait - November 2011 GCC Cigre, is pleased to announce its 7 th International Conference GCC
More informationMONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017
MONITORING The difference between safe and reliable on-line bushing monitoring and false alarms often lays in the quality of the sensor design and the installation procedure ABSTRACT On-line monitoring
More informationToday, utilities are focusing on improving or maintaining
TRANSFORMER MONITORING Trends in continuous on-line condition monitoring ABSTRACT The article describes new trends in the field of continuous on-line condition monitoring of transformers. These trends
More informationSP Energy Networks Business Plan
SP Energy Networks 2015 2023 Business Plan Updated March 2014 Annex 132kV Substation Plant Strategy SP Energy Networks 29 March 2014 March 2014 Issue Date Issue No. Document Owner Amendment Details 17th
More informationp. 1 p. 9 p. 26 p. 56 p. 62 p. 68
The Challenges and Opportunities Faced by Utilities using Modern Protection and Control Systems - Paper Unavailable Trends in Protection and Substation Automation Systems and Feed-backs from CIGRE Activities
More informationGrid Automation packaged solutions Optimal automation of medium voltage grids
Grid Automation packaged solutions Optimal automation of medium voltage grids Application principles of the Zone concept Grid Automation (GA) packaged solutions The zone concept offers a method to analyze
More informationCentral Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date
Last Amended on 31.07.2015 Page 1 of 11 I. SWITCHGEAR EQUIPMENT 1. High Voltage switchgear & control gear and AB switches Ratings upto 1200 kv system Switching Impulse Voltage (Dry & Wet) Power Frequency
More informationQuality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru
Quality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru Abstract: Surge arrester is one of the important power system network components which is neglected
More informationGUIDELINES FOR THE CLASSIFICATION OF GRID DISTURBANCES ABOVE 100 kv
GUIDELINES FOR THE CLASSIFICATION OF GRID DISTURBANCES ABOVE 100 kv 13.04.2017 1 INTRODUCTION... 4 2 PURPOSE OF THE GUIDELINES... 4 3 SCOPE AND LIMITATIONS OF THE STATISTICS... 5 4 DEFINITIONS... 6 4.1
More informationExternally Gapped Line Arresters Smart Solution for Stable Power Supply
Smart Solution for Stable Power Supply Metal-oxide surge arresters with external series gaps improve the reliability of transmission systems, and help eliminate not only lightning damages of transmission
More informationExternally Gapped Line Arresters Smart Solution for Stable Power Supply
Smart Solution for Stable Power Supply Metal-oxide surge arresters with external series gaps improve the reliability of transmission systems, and help eliminate not only lightning damages of transmission
More informationThis annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation
Location(s) where activities are performed under accreditation Head Office Utrechtseweg 310, Building no. R11 6812 AR Arnhem The Netherlands Location Abbreviation/ location code Utrechtseweg 310, Building
More informationSurvey on new electrical devices with different technology compared to existing electrical devices
ENERGY Survey on new electrical devices with different technology compared to existing electrical devices Project KK51525 Henrik Hemark 23 August 2017 1 DNV GL 23 August 2017 SAFER, SMARTER, GREENER Agenda
More informationAdvanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets
Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets www.intellisaw.com The Case for Critical Asset* Monitoring The vast majority of critical assets in the field
More informationELECTRICITY SUPPLY SYSTEMS OF THE FUTURE
ELECTRICITY SUPPLY SYSTEMS OF THE FUTURE Rob Stephen President Cigre AFSEC conference March 2017 CIGRE Founded in 1921, CIGRE, the Council on Large Electric Systems, Our Mission:To be the world s foremost
More informationWe put the now in knowledge Today s solutions built on a century of innovation and expertise
PRODUCT OVERVIEW We put the now in knowledge Today s solutions built on a century of innovation and expertise Knowledge. It s what helps you make the next right decision about your critical assets. And
More informationCONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 3
CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 3 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational faults and interruptions
More informationHigh-Voltage Transmission Line and SF6 Gas-Insulated Substations Inspection Using Computed Radiography
BB&E ENGENHEIROS & CONSULTORES ASSOCIADOS SENDCONTROL INSPEÇÕES INDUSTRIAIS High-Voltage Transmission Line and SF6 Gas-Insulated Substations Inspection Using Computed Radiography 11th European Conference
More informationSubstation SCADA Monitoring
Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component
More informationProducts Portfolio. Pole mounted Vacuum Recloser
Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,
More informationDigital Substation Overview of Technology, Industry
Digital Substation Overview of Technology, Industry Trends and Standardization Efforts 4th International Scientific & Technical Conference Actual Trends in Development of Power System Protection and Automation
More informationfor the protection of gas-insulated metal-enclosed switchgear against lightning and switching overvoltages
GAS-INSULATED METAL-ENCLOSED SURGE ARRESTERS (GIS-ARRESTERS) for the protection of gas-insulated metal-enclosed switchgear against lightning and switching overvoltages GIS-Arresters from Siemens GIS arresters
More informationResearch on Technologies in Smart Substation
Available online at www.sciencedirect.com Energy Procedia 12 (2011) 113 119 ICSGCE 2011: 27 30 September 2011, Chengdu, China Research on Technologies in Smart Substation Hongwei Li *, Lixin Wang Technology
More informationIMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS
IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage
More informationPurpose of High Voltage Circuit Switchers
Purpose of High Voltage Circuit Switchers Vertical interrupter circuit switcher without integral disconnect switch (Figure 2) Three-phase Interruption and Protection Circuit switchers have been developed
More informationApplied Research on AC/DC Integrated Power Supply of Substation Lu Zhigang1, a, Lei Bo1, b, Zheng Yongqiang2, c
4th International Conference on Electrical & Electronics Engineering and Computer Science (ICEEECS 2016) Applied Research on AC/DC Integrated Power Supply of Substation Lu Zhigang1, a, Lei Bo1, b, Zheng
More informationIMP/ 001 / 014 Policy for the Protection of Distribution Networks
Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy
More informationASSET RISK MANAGEMENT Criticality Framework
ASSET RISK MANAGEMENT Criticality Framework 15 C O P Y R I G H T 2013 T R A N S P O W E R N E W Z E A L A N D L I M I T E D. A L L R I G H T S R E S E R V E D Preface This document has been prepared to
More informationDevelopment trends in Substation Design
Development trends in Substation Design on behalf of SC B3 Hans-Erik Olovsson Convenor Activity Area 1 (AA1) «Substation concepts and development» hans-erik.olovsson@se.abb.com 1 Agenda Evolution of primary
More informationELG4125: System Protection
ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.
More informationIt is the job of the protection system equipment to recognize and remove the fault.
Protection 1 (read section 13.0 of text) 1.0 Introduction Faults do not occur that frequently 1/year/100 miles of transmission is typical. Distribution systems may see more than this. However, when they
More informationB5-111 APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION
21, rue d'artois, F-75008 Paris http://www.cigre.org B5-111 Session 2004 CIGRÉ APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION A. TAKEUCHI F. KUMURA M. NAKAHARA Chubu Electric Power Co.
More informationCircuit Breaker Sentinel (CBS) for SF 6. power circuit breakers
Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers It is widely recognized that the concept of periodic equipment maintenance
More informationSpark gap surge arrester for direct current OLE line
Spark gap surge arrester for direct current OLE line System suitable to ensure surge protection to equipment and devices connected to (Overhead Line Electrification) OLE lines operating under direct current.
More informationUSE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION
H USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION Use Case Title Adaptive Transmission Line Protection Use Case Summary The requirements for improvement in the performance of protection relays under
More informationChapter 2 State Estimation and Visualization
Chapter 2 State Estimation and Visualization One obvious application of GPS-synchronized measurements is the dynamic monitoring of the operating conditions of the system or the dynamic state estimation
More informationPower Transmission Division Link between power generation and distribution
Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution
More informationUSE CASE 14 CONTROLLED ISLANDING
I USE CASE 14 CONTROLLED ISLANDING Use Case Title Centralized application separates grid into islands to prevent blackout Use Case Summary Controlled islanding is a method that can significantly improve
More informationEnergy Transmission and Distribution Services
Energy Transmission and Distribution Services Business segment presentation Asset Services Energy is an essential part of our daily lives Industry Education Mobility Workplace Entertainment Homes Healthcare
More informationPOWER GRIDS. We are bridging the gap. Enabling Digital Substations.
POWER GRIDS We are bridging the gap. Enabling Digital s. 2 A B B D i g i ta l S u b s tat i o n s ABB s Digital provides customers in the utility sector with unmatched control and efficiency. The digital
More informationENERGY AND POWER SYSTEM PLANNING DEPARTMENT
ENERGY AND POWER SYSTEM PLANNING DEPARTMENT Gredos - distribution network analysis software: Power Flows (AC/DC) Optimal Re-switching (optimal losses, reliability) Optimal Back-up Supply Reliability Analyses
More informationMV Network Switchgear, Protection and Control
MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control
More informationSystem Studies for American Transmission Co. s Benson Lake SVC Project
Helping to keep the lights on, businesses running and communities strong System Studies for American Transmission Co. s Benson Lake SVC Project Adam Manty, Transmission Planning Engineer, ATC Outline Introduction
More informationSmart Asset Management using Online Monitoring
Smart Asset Management using Online Monitoring Courtney, D., Littler, T., & Livie, J. (2017). Smart Asset Management using Online Monitoring. In Proceedings of Centre International de Recherche sur l'environnement
More informationOvervoltage Protection Devices
Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12
More informationFIELDS OF ACTIVITY OF STUDY COMMITTEES
FIELDS OF ACTIVITY OF STUDY COMMITTEES A 1 A 2 A 3 BB1 BB2 BB3 BB4 BB5 C 1 C 2 C 3 C 4 C 5 C 6 D 1 D 2 Rotating Electrical Machines Economics, design, construction, test, behaviour and materials for turbine
More informationSmall Power Station Surge Protection Analysis and Plan
[Type the document title] Small Power Station Surge Protection Analysis and Plan By ArresterWorks Jonathan Woodworth ArresterWorks Page 1 Contents 1.0 Executive Summary... 3 1.1 Project Overview... 3 1.2
More informationRobust Topology Determination Based on Additional Substation Data from IEDs
Robust Topology Determination Based on Additional Substation Data from IEDs M. Kezunovic 1, Fellow IEEE, T. Djokic, T. Kostic 2, Member IEEE Abstract This paper describes an approach for more robust power
More informationIEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems
Alexandre Oudalov, ABB Switzerland Ltd., Corporate Research, 2014-04-30 Microgrid Protection IEEE PES Swiss Chapter Workshop: Microgrids Evolution and Integration in Modern Power Systems Microgrid Protection
More informationPlug and Operate Transformer Technology
Plug and Operate Transformer Technology Deepal Shah PFISTERER deepal.shah@pfisterer.com by and Andre Goessler PFISTERER andre.goessler@pfisterer.com 1 THE POWER CONNECTION We have always worked closely
More informationElectrical Integration with Smart Communication
Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as
More informationNETS SQSS Review of Requirement of Onshore Connection Facilities for Offshore Wind Farm Connections (GSR014) Working Group Report
NETS SQSS Review of Requirement of Onshore Connection Facilities for Offshore Wind Farm Connections (GSR014) Working Group Report January 2014 Executive Summary This document summarises the results of
More informationRisk Assessment of Damages due to Lightning Discharges: A Case Study to a Telecommunication System in Singburi Province of Thailand.
Proceedings of the 2007 WSEAS Int. Conference on Circuits, Systems, Signal and s, Gold Coast, Australia, January 17-19, 2007 216 Risk Assessment of Damages due to Lightning Discharges: A Case Study to
More informationDesign, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter
1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560
More informationAIR INTELLIGENT GRID AUTOMATION
AIR INTELLIGENT GRID AUTOMATION Felipe ROVER Tiago MORAIS Jorge AITH Elektro Brazil Elektro Brazil Elektro Brazil felipe.rover@elektro.com.br tiago.morais@elektro.com.br jorge.aith@elektro.com.br ABSTRACT
More informationM ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS
M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS G1 Outdoor Surge Protector for AC/Traction network VP range Dimensions (in mm) 19 M8 44 73 diam. 47 6 mm² Electrical
More informationALP UPS FEATURES & ADVANTAGES
ALP UPS FEATURES & ADVANTAGES 1. True Galvanic Isolation Usually, Y-caps are installed in UPS s input & output to eliminate the electro-magnetic interference, but Y-caps will increase the ground leakage
More information2 Check that Public Safety has been considered (e.g. cabinet secured and locked, trip hazards removed where applicable).
NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify
More informationBenefits, offering and references
DOC ID: 9AKK107045A9180 DISTRIBUTION SOLUTIONS Digital medium-voltage switchgear Benefits, offering and references Contents Digital switchgear for medium-voltage applications Digital switchgear definition
More information2 Principle of lightning protection
2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical
More informationSubstation automation products. MicroSCADA Pro for substation automation
Substation automation products for substation automation Perfect control anywhere, anytime is an investment for today and tomorrow. Start, for instance, with monitoring or gateway functionality and integrate
More informationTransforming the Electric Grid
Transforming the Electric Grid - ORNL s role in supporting DOE s mission January 6 th, 2005 Tom King Program Manager, Power Technologies Oak Ridge National Laboratory kingtjjr@ornl.gov 865-675-4390 Office
More informationLandsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.
Landsnet-Icegrid Requirements for protection and control systems. Principles for the Icelandic power transmission network. Introduction.... 4 System requirements... 6 Validity:... 6 Requirements for protection:...
More informationEquipment Strategy for Voltage Transformers Strategy
Equipment Strategy for Voltage Transformers Strategy Current version: 19/06/2018 EXTERNAL USE Page 1 of 6 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References... 3 1.4
More informationApplication of the Lightning Location System for the selection of Lightning Protection of Overhead Medium Voltage Lines using Long Flashover Arresters
Application of the Lightning Location System for the selection of Lightning Protection of Overhead Medium Voltage Lines using Long Flashover Arresters D. Bago Abstract--This paper will describe the implementation
More informationAsset Management through Integrated Monitoring & Diagnostics in. Protection Relays
Asset Management through Integrated Monitoring & Diagnostics in IEEE Seminar, Houston, Feb 23 2016 Protection Relays Page 1 Presenter Vijay Muthukrishnan, M.S R&D Leader Industrial / Distribution Protection
More informationOur Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium
Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with
More informationIntegrated monitoring system for power transformers and hydro generators as an asset management and "smart grid" component. Miroslav Poljak, Ph.
Integrated monitoring system for power transformers and hydro generators as an asset management and "smart grid" component Miroslav Poljak, Ph.D Monitoring - Definition On-line monitoring system (MS) is
More informationTechnology Live Workshop
Technology Live Workshop David Pitt Product Manager Eaton Electric Ltd. Technology Live Workshop Subjects to be covered in this Technology Live Workshop: Increased need for installation of transient voltage
More informationICX-CMOS-E-2006 Electrical / I&C Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
102904-ICX-CMOS-E-2006 Electrical / I&C Engineer Holds a B. Sc. in Electronics & Electrical Communications Engineering and has over 9 years hands-on experience working in I&C field. Has extensive experience
More informationABB Data Center Forum 2017
ABB DATA CENTER FORUM 2017, 11 TH JULY 2017 ABB Data Center Forum 2017 Perfecting Data Center availability with Ultra-Fast Protection Devices Barbara Schlegel ABB DATA CENTER FORUM 2017, 11 TH JULY 2017
More informationPower Systems Communications Implementation of IEC61850 in a Substation Environment
Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details
More informationCircuit Breakers,Reclosers, Switches, and Fuses
Section 17 Circuit Breakers,Reclosers, Switches, and Fuses 170. ARRANGEMENT This rule requires circuit breakers, reclosers, switches, and fuses be accessible only to qualified persons. Section 17 is part
More informationNetwork Configuration Document Selection for New Substations Framework
Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...
More informationNew generation of circuit-breaker monitoring
New generation of circuit-breaker monitoring 02/26/2015-5.27 pm Asset management Digital substation Maintenance Smart Grids Life management of substation equipment is a key economic factor for utilities.
More informationFortum SGEM Program Presentation of ongoing research activities
Fortum SGEM Program Presentation of ongoing research activities MV and LV Network Automation Solutions in EU Benchmarking Research 1 Existing Distribution Grid Little change in the past few decades Mostly
More informationCost and performance implications of infrastructure investment options in the Eskom Distribution network
Cost and performance implications of infrastructure investment options in the Eskom Distribution network Dr Clinton Carter-Brown Industry Association Resource Centre Eskom Holdings Limited Martin Cameron
More informationCONNEX. The Plug-in Connection System for Power Transformers and Gas-Insulated Switchgear. the power connection THE PFISTERER GROUP
CONNEX The Plug-in Connection System for Power Transformers and Gas-Insulated Switchgear THE PFISTERER GROUP the power connection CONNEX Safety and Versatility in Substations Power grids are changing dynamically
More informationSCADA and Central Applications An introduction
SCADA and Central Applications An introduction Course map Outline of the lecture Power System Operation - Centralised Control Applications SCADA - SCADA architecture & Components - SCADA system functions
More informationComplete Installation Guide
Complete Installation Guide Ethernet Extender Model Number: SJ-L-DSL Product Description Product Features SJ-L-DSL is network signal extension device, which Long distance transmission as far as 5,000m.
More informationMEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety
MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator
More informationLightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany
Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning
More informationSIMEAS SAFIR The network quality system: Know your network quality avoid faults minimize downtime
SIMEAS SAFIR The network quality system: Know your network quality avoid faults minimize downtime Power Transmission and Distribution The intelligent way to monitor your power system network: Know in advance
More informationAutomated Analysis of Digital Relay Data Based on Expert System
Automated Analysis of Digital Relay Data Based on Expert System X. Luo, Student Member, IEEE, and M. Kezunovic, Fellow, IEEE Abstract Modern digital protective relays generate various files and reports
More informationA Novel Digital Relay Model Based on SIMULINK and Its Validation Based on Expert System
A Novel Digital Relay Model Based on SIMULINK and Its Validation Based on Expert System X. Luo, Student Member, IEEE, and M. Kezunovic, Fellow, IEEE Abstract This paper presents the development of a novel
More informationSCADA Training - T&D Automation
SCADA Training - T&D Automation Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This course covers all the
More informationAnalysis of End-to-End Delay Characteristics among Various Packet Sizes in Modern Substation Communication Systems based on IEC 61850
Analysis of End-to-End Delay Characteristics among Various Packet Sizes in Modern Substation Communication Systems based on IEC 6185 Narottam Das, Senior Member, IEEE, Tze Jia Wong, and Syed Islam, Senior
More informationYour partner in energy solutions. Systems Division. Automation & services. (Formerly Pauwels Canada Inc)
Systems Division Automation & services The CG Systems Division has developed into an important division within the CG group. The Systems Division specializes in electrical turnkey projects and has an impressive
More informationSapphire Wind Farm 330/33kV Substation
Signature projects: Projects: Project Edison AusNet Sapphire Wind Farm 330/33kV Substation TransGrid Zinfra constructed 330/33kV substation and transmission line as part of the cut in works for the Sapphire
More informationLightning and Surge Arresters
Lightning and Surge Arresters 5/4 Product overview 5/5 Lightning arresters, requirement category I (B) 5/6 Combined arresters, requirement category I (B) and II (C) 5/7 Single-pole surge arrester, requirement
More informationHigh and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel.
Training Course : High and Medium Voltage Substation Design, Testing and Maintenance Training Course For One Week In KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel Which Be Held As Under Details : Tel.
More informationAmsterdam 27 September 2017 David MacDonald
Operations & Maintenance facilitating condition based and predictive maintenance to support cost-efficient operation and maximum life-cycle of next generation IEC 61850 systems Amsterdam 27 September 2017
More informationLessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc.
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Lessons Learned Implementing an IEC 61850-based Microgrid Power- Management System K.A.
More informationGrid Solutions. SERVICES Optimizing Asset Reliability, Up-Time and Performance
Grid Solutions SERVICES Optimizing Asset Reliability, Up-Time and Performance Electrical asset reliability and performance are key requirements for attaining customer business objectives and return-on-investment.
More information