SCADAPack E 5505 RTD Input Hardware Manual

Size: px
Start display at page:

Download "SCADAPack E 5505 RTD Input Hardware Manual"

Transcription

1 SCADAPack E 5505 RTD Input Hardware Manual

2 2 SCADAPack E 5505 RTD Input Hardware Manual Table of Contents Part I 5505 RTD Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview Installation DIP Switch... Settings 10 6 Operation... and Maintenance Troubleshooting Calibration Specifications Approvals... and Certifications 18

3 5505 RTD Input Module 3 I 5505 RTD Input Module 2013 Control Microsystems Inc. All rights reserved. Printed in Canada. Version: The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us. No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric. All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components. When devices are used for applications with technical safety requirements, the relevant instructions must be followed. Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results. Failure to observe this information can result in injury or equipment damage. 1 Technical Support Support related to any part of this documentation can be directed to one of the following support centers.

4 4 SCADAPack E 5505 RTD Input Hardware Manual Technical Support: The Americas Available Monday to Friday 8:00am 6:30pm Eastern Time Toll free within North America Direct Worldwide TechnicalSupport@controlmicrosystems.com Technical Support: Europe Available Monday to Friday 8:30am 5:30pm Central European Time Direct Worldwide +31 (71) euro-support@controlmicrosystems.com Technical Support: Asia Available Monday to Friday 8:00am 6:30pm Eastern Time (North America) Direct Worldwide TechnicalSupport@controlmicrosystems.com Technical Support: Australia Inside Australia au.help@schneider-electric.com 2 Safety Information Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

5 5505 RTD Input Module 5 DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury. CAUTION CAUTION used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in equipment damage. PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. BEFORE YOU BEGIN Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine. EQUIPMENT OPERATION HAZARD CAUTION Verify that all installation and set up procedures have been completed. Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.

6 6 SCADAPack E 5505 RTD Input Hardware Manual Remove tools, meters, and debris from equipment. Failure to follow these instructions can result in injury or equipment damage. Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references. Software testing must be done in both simulated and real environments. Verify that the completed system is free from all short circuits and grounds, except those grounds installed according to local regulations (according to the National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage. Before energizing equipment: Remove tools, meters, and debris from equipment. Close the equipment enclosure door. Remove ground from incoming power lines. Perform all start-up tests recommended by the manufacturer. OPERATION AND ADJUSTMENTS The following precautions are from the NEMA Standards Publication ICS (English version prevails): Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is improperly operated. It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer s instructions as a guide for functional adjustments. Personnel who have access to these adjustments should be familiar with the equipment manufacturer s instructions and the machinery used with the electrical equipment. Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics. 3 Overview The model 5505 RTD input module adds four RTD inputs to the 5000 input/output system. Up to sixteen Model 5505 modules may be connected to the I/O bus, for a total of 64 RTD inputs per bus. These RTD inputs are used with 3 or 4 wire 100 ohm platinum RTDs that conform to the ohms/ohm/ C calibration standard based on ASTM E 1137/E 1137M-04. Resistance from 0 to 500 ohms and RTDs from 200ºC to 800ºC can be measured.

7 5505 RTD Input Module 7 The 5505 module scales and linearizes each RTD input and returns the individual data in ohms, C, F or K as a 32 bit floating point number. The 5505 module provides 4mA excitation current with a low duty cycle. The high excitation current along with the low duty cycle results in high accuracy while minimizing self-heating. The 5505 module can detect whether a 3 or 4 wire RTD has been wired and will excite and monitor the RTD accordingly. The 5505 module uses a 24-bit delta sigma analog to digital (A/D) converter. A single chip microcontroller with integral watchdog timer operates the A/D, linearizes and scales the output data and communicates over the I/O bus. Inputs have transient protection and are optically isolated from the main logic power. F igu re 1 : RTD In pu t M odu le

8 8 SCADAPack E 5505 RTD Input Hardware Manual 4 Installation The installation of the 5505 module requires mounting the module on the 7.5mm by 35mm DIN rail and connecting the module to the system I/O Bus. Refer to the System Configuration Guide, at the beginning of this manual, for complete information on system layout, I/O Bus cable routing and module installation. Field Wiring Controller, modem and I/O modules use screw termination style connectors for termination of field wiring. They accommodate solid or stranded wires from 22 to 12 AWG. The connectors are removable. This allows module replacement without disturbing the field wiring. Leave enough slack in the wiring for the connector to be removed. Remove power before servicing unit. To remove the connector: Pull the connector upward from the board. Apply even pressure to both ends of the connector. To install the connector: Line up the pins on the module with the holes in the connector. Push the connector onto the pins. Apply even pressure to both ends on the connector. The 5505 module provides four RTD inputs for use with 3 or 4-wire RTDs. Figure 2: Typical 5505 RTD Field Wiring shows how to wire these RTDs. When using 4 wire RTDs, the four wires are connected to the Sense + (S+), Sense (S ), Excitation Current + (I+) and Excitation Current (I ) terminals. The I+ and I terminals supply the excitation current to the RTD. The S+ and S terminals return the sensed voltage to the 5505 module. 4 wire measurement techniques are the more accurate and consume the least amount of power. Although the circuitry and measurement technique can compensate for wiring resistance, the user should minimize the lead resistance as much as possible. When using 3 wire RTDs, three wires are connected to the Excitation/Sense + (I/S+), Sense (S ) and Excitation Current (I ) terminals. The I/S+ and I terminals supply the excitation current to the RTD. The S+ and S terminals return the sensed voltage to the 5505 module. The Excitation Current + (I+) terminal is not used. The wiring resistance is monitored and compensated. In 3 wire installations the 3 wires are of the same length and type for this compensation to be accurately performed. A DC supply powers the isolated RTD input circuits. A 5000 power supply or SCADAPack controller normally sources this voltage. A range of voltages can be tolerated. Refer to the specifications for details. In systems where multiple 5000 modules and other devices are connected to the DC power supply, it is possible for noise to be coupled into the DC power supply. For these reasons it is recommended that the negative side of the DC supply be connected to the panel or chassis ground. This connection can be made on the 5000 power supply, SCADAPack terminal blocks or as part of the panel wiring.

9 5505 RTD Input Module 9 F igu re 2 : Ty pical RTD F ield W irin g ATEX and IECEx applications only This equipment is to be installed in an enclosure certified for use, providing a degree of protection of IP54 or better. The free internal volume of the enclosure must be dimensioned in order to keep the temperature rating. A T4 rating is acceptable.

10 10 SCADAPack E 5505 RTD Input Hardware Manual 5 DIP Switch Settings Address Selection 5000 Series I/O module types may be combined in any manner to the maximum supported by the controller used. Each type of I/O module, connected to the I/O bus, has a unique I/O module address. Different types of I/O modules may have the same module address. The address range supported by the SCADAPack controller module may restrict the I/O module address range. Refer to the controller manual for the maximum address supported. Each analog input module has a unique set of channels. The four address switches labeled 1, 2, 4 and 8 set the module address. To set the address: Open the four switches by sliding the actuator to the left side of the switch. Slide actuators to the right such that they total the desired address. Figure 3: 5505 Analog Input Module Address Switches shows the switch setting for each of the 16 module addresses. Figure 3: 5505 Analog Input Module Address Switches 5503 Emulation Mode Switch 5503 Emulation mode is not supported for SCADAPack E controllers. The Emulation switch is set to the left position.

11 5505 RTD Input Module 11 6 Operation and Maintenance F igu re 4 : Em u lation Sw itch. The 5505 RTD module is configured for use using the SCADAPack E Configurator SCADAPack I/O property page. Each input is individually configurable for resistance measurement or RTD temperature measurement Each RTD input is configurable to return the measured temperature in degrees Celsius, Kelvin, or Fahrenheit. Inputs have a common configurable filter rate that can be used to dampen process variations or noise. Data is returned as an IEEE 32 bit, single precision floating point number that requires no additional scaling. Data Format The 5505 module returns RTD resistance and temperature data. The returned data is in floating point format. You will need to use the g30v1 32bit Analog In object type for the data. The RTD data is returned via one of the following methods: The following table shows the data output for o C, o F, o K, and Ohms for the 5505 RTD module. Temperature Condition Output <-200ºC out of range ºC operating ºC operating 800 >800ºC out of range 800 <-328ºF out of range -328

12 12 SCADAPack E 5505 RTD Input Hardware Manual Temperature Condition Output -328ºF operating ºF operating 1472 >1472ºF out of range 1472 <73.15K out of range K operating K operating > K out of range ohms under-range ohms operating 500 >500 ohms out of range 500 RTD Status The 5505 RTD module returns the status of the RTD analog input point for each channel. The Analog Input Point Attributes dialog, selected from the SCADAPack E Configurator SCADAPack I/O property page, displays the point quality flags for the RTD status of the analog input points. The following status conditions are reported: When the 5505 RTD module detects an Open condition on the RTD channel or Power Input Off condition, the point Over-range quality flag is set. The point value reported in SCADA protocols is set to e+038. When the 5505 RTD module detects a low Out-of-Range condition on the RTD channel, the point Under-range quality flag is set. The point value reported in SCADA protocols is set to e+038. When the 5505 RTD module indicates a high Out-of-range condition on the RTD channel, the point Over-range point quality flag is set. The point value reported in SCADA protocols is set to e+038. When the RTD channel returns to a valid reading, the analog point quality flags are cleared. Condition Analog Input Point SCADA Protocol reports Quality Flags RTD signal good all cleared Status: Online Value: 32-bit floating point value RTD signal under-range Under-Range Point is Failed Status: Offline, Out-of-range Value: e+038 RTD signal over-range Over-Range Status: Offline, Out-of-range

13 5505 RTD Input Module 13 Point is Failed Module Power Input OFF * Over-Range Point is Failed No 5505 module communication * I/O Not Responding Point is Failed Value: e+038 Status: Offline, Out-of-range Value: e+038 Status: Offline, Comms Lost Value: previous value Module Binary Status Point ON (if configured) * All RTD ch an n el an alog poin ts affected Maintenance This module requires no routine maintenance. If the module is not functioning correctly, contact Schneider Electric Technical Support for more information and instructions for returning the module for repair.

14 14 SCADAPack E 5505 RTD Input Hardware Manual 6.1 Troubleshooting Troubleshooting Condition Inputs read 0. Inputs read Reading is constant. Appears to be on wrong range. Action Check power. Check range. Check for open RTD. Check range. Check that the analog input is not forced. Reset is required from the bus controller to read the RTD range switches. Refer to the Status Registers for additional information when diagnosing the module.

15 5505 RTD Input Module 15 7 Calibration The 5505 module is calibrated at the factory. It does not require periodic calibration. Calibration may be necessary if the module has been repaired as a result of damage. Calibration is done electronically at the factory. There are no user calibration procedures. 8 Specifications Disclaimer: Schneider Electric reserves the right to change product specifications without notice. For more information visit General I/O Terminations Dimensions Packaging Environment 12 to 22 AWG 15A contacts Screw termination - 6 lb.-in. (0.68 Nm) torque 2.9 inch (74 mm) wide 4.9 inch (124 mm) high 1.8 inch (45 mm) deep corrosion resistant zinc plated steel with black enamel paint 5% RH to 95% RH, non-condensing 40 o C to 70 o C ( 40 o F to 158 o F) operation 40 o C to 85 o C ( 40 o F to 185 o F) storage Addressing 16 modules. DIP switch selectable. RTD Inputs Quantity 4 Type 100 ohm platinum ohms/ C ASTM E 1137/E 1137M-04 ITS-90 3 and 4 wire. Auto detection and compensation Ranges Can be configured to return data in ohms, C, F or K. 200 to 800 o C 0 to 500 ohms 5503 Emulation Ranges DIP switch selectable. 0 to 200 o C

16 16 SCADAPack E 5505 RTD Input Hardware Manual 100 to +100 o C 200 to 0 o C 0 to 800 o C 0 to 400 o C 0 to 400 ohms Data format Resolution RTD Status Accuracy on RTD ranges Accuracy on 0 to 500 ohms 5505: 32 bit floating point and 12 status bits 5503 Emulation: 16 bit signed number 5505: >17 bits effective 5503 Emulation: 15 bits RTD is good (not open) RTD in range RTD 3/4 wire RTD status not available in 5503 Emulation percent of full scale over operational temperature range including linearization tolerances: +0.10%/ 0.05% Percent of full scale over operational temperature range: ±0.03% Excitation Current 4mA, 7.2% duty cycle in 4-wire mode, 14.4% in 3-wire mode, 250ms scan interval. Line resistance Converter type Response Time Transient Protection Connectors Isolation 100 ohms max., in each line 24 bit delta-sigma 380 ms typical for 10% to 90% signal change at minimum filter setting 2.5kV surge withstand capability as per ANSI/ IEEE C Two removable. 10 positions (Power, RTD0, RTD1), 8 positions (RTD2, RTD3) Isolation from logic supply and chassis. Voltage 500Vrms Power Supply 5V power requirements 11-30Vdc power requirements 6mA UL508 rated Vdc. Class 2. 12V operation: 4mA

17 5505 RTD Input Module 17 plus 0.6mA per 4 wire RTD plus 1.2mA per 3 wire RTD 24V operation: 2.2mA plus 0.3mA per 4 wire RTD plus 0.6mA per 3 wire RTD 11-30Vdc - Connector Removable. Shared with the RTD Inputs Vdc - Isolation Isolation from logic supply and chassis

18 18 SCADAPack E 5505 RTD Input Hardware Manual 9 Approvals and Certifications Hazardous Locations - North America Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T5 CSA certified to the requirements of: CSA Std. C22.2 No. 213-M Hazardous Locations. UL Std. No Hazardous (Classified) Locations. Hazardous Locations - Europe Hazardous Locations ATEX and IECEx Applications only ATEX II 3G, Ex na IIC T4 per EN , protection type n (Zone 2) IECEx, Ex na IIC T4 per IEC , protection type n (Zone 2) This equipment is to be installed in an enclosure certified for use, providing a degree of protection of IP54 or better. The free internal volume of the enclosure must be dimensioned in order to keep the temperature rating. A T4 rating is acceptable. For products using Solid State Relays (5415, 5606 and 5607 modules and SCADAPack using 5606 and 5607 modules) A T4 rating is acceptable for maximum loads of 2A. When 3A loads are connected to the Solid State Relays, the maximum ambient rating is lowered to 50 C in order to maintain the T4 rating. Safety CSA (ccsaus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL916. (Process Control Equipment, Industrial Control Equipment) in Canada and USA. UL (culus) listed: UL508 (Industrial Control Equipment) Digital Emissions FCC Part 15, Subpart B, Class A Verification EN : Electromagnetic Compatibility Generic Emission Standard Part2: Industrial Environment C-Tick compliance. Registration number N Immunity Declaration EN : Electromagnetic Compatibility Generic Standards Immunity for Industrial Environments This product conforms to the above Emissions and Immunity Standards and therefore conforms with the requirements of Council Directive 2004/108/EEC (as amended) relating to electromagnetic compatibility and is eligible to bear the CE mark. The Low Voltage Directive is not applicable to this product.

19 5505 RTD Input Module 19

SCADAPack E 5405 Digital Input Hardware Manual

SCADAPack E 5405 Digital Input Hardware Manual SCADAPack E 5405 Digital Input Hardware Manual 2 SCADAPack E 5405 Digital Input Hardware Manual Table of Contents Part I 5405 Digital Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3

More information

5504 Thermocouple Analog Input Module

5504 Thermocouple Analog Input Module 550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

5521 Potentiometer Analog Input Module

5521 Potentiometer Analog Input Module 55 Potentiometer Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

5401 and 5402 Digital I/O Modules

5401 and 5402 Digital I/O Modules 50 and 50 Digital I/O Modules Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

5403 and 5404 Digital Input Modules

5403 and 5404 Digital Input Modules 503 and 50 Digital Input Modules Installation, Operation and Maintenance Setup Manual //07 Copyright 0-07 Schneider Electric Canada Inc. All rights reserved. 503 and 50 Digital Input Modules The information

More information

5502 Differential Analog Input Module

5502 Differential Analog Input Module 550 Differential Analog Input Installation, Operation and Maintenance Setup Manual //07 Copyright 0-07 Schneider Electric Canada Inc. All rights reserved. 550 Differential Analog Input The information

More information

SCADAPack E Idec PLC Interface Manual

SCADAPack E Idec PLC Interface Manual SCADAPack E Idec PLC Interface Manual 2 SCADAPack E Idec PLC Interface Manual Table of Contents Part I Idec PLC Interface 3 1 Technical... Support 3 2 Safety... Information 4 3 Preface... 6 4 Overview...

More information

SCADAPack E Target 5 DF1 PLC Interface

SCADAPack E Target 5 DF1 PLC Interface SCADAPack E Target 5 DF1 PLC Interface 2 Table of Contents Part I 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview... 7 4 I/O Device... Interface 7 4.1 Input Devices... 9 4.2 Output Devices...

More information

5607 Input/Output (I/O) Module

5607 Input/Output (I/O) Module 5607 Input/Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

SCADAPack E 5607 I/O Hardware Manual

SCADAPack E 5607 I/O Hardware Manual SCADAPack E 5607 I/O Hardware Manual 2 SCADAPack E 5607 I/O Hardware Manual Table of Contents Part I 5607 Input/Output Module 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview... 6 4 Installation...

More information

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual 5304 Analog Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:

More information

CONTROL MICROSYSTEMS and 5404 Digital Input Module. Hardware Manual

CONTROL MICROSYSTEMS and 5404 Digital Input Module. Hardware Manual 503 and 50 Digital Input Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual 506 and 507 Relay Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

SCADAPack E ISaGRAF Quick Start Guide

SCADAPack E ISaGRAF Quick Start Guide SCADAPack E ISaGRAF Quick Start Guide 2 SCADAPack E ISaGRAF Quick Start Guide Table of Contents Part I ISaGRAF 3 Quick Start Guide 3 1 Technical... Support 3 2 Safety... Information 4 3 Preface... 6 4

More information

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual 5915 SDI-12 Interface Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:

More information

CONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual

CONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual 50 and 50 Digital I/O Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

SCADAPack E I/O Module Hardware Manual (337E Only) Version: Date: August 2017

SCADAPack E I/O Module Hardware Manual (337E Only) Version: Date: August 2017 SCADAPack E 5606 I/O Module Hardware Manual (337E Only) Version: Date: August 2017 Table of Contents 1 Legal...5 Information 2 Technical...6 Support 3 Safety...7 Information 4 Overview...10 5 Installation...11

More information

5910 Ethernet Gateway Module

5910 Ethernet Gateway Module Hardware Manual 2/24/2017 Copyright 2014-2017 Schneider Electric Canada Inc. All rights reserved. 5910 Ethernet Gateway Module The information provided in this documentation contains general descriptions

More information

CONTROL MICROSYSTEMS Analog Input Module. Hardware Manual

CONTROL MICROSYSTEMS Analog Input Module. Hardware Manual 550 Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676 Canada -CONTROL

More information

SCADAPack Input/Output Module Hardware Manual. Version: February 2016

SCADAPack Input/Output Module Hardware Manual. Version: February 2016 SCADAPack Version: Date: February 2016 Table of Contents 1 Legal Information...6 2 Technical Support...7 3 Safety Information...8 4 Documentation...11 Check 5 About this Manual...13 6 About the 5607 I/O

More information

CONTROL MICROSYSTEMS Differential Analog Input Module. Hardware Manual

CONTROL MICROSYSTEMS Differential Analog Input Module. Hardware Manual 550 Differential Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

CONTROL MICROSYSTEMS High Speed Counter Input Module. Hardware Manual

CONTROL MICROSYSTEMS High Speed Counter Input Module. Hardware Manual 50 High Speed Counter Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

CONTROL MICROSYSTEMS Thermocouple Analog Input Module. Hardware Manual

CONTROL MICROSYSTEMS Thermocouple Analog Input Module. Hardware Manual 550 Thermocouple Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

Packaging User Guide for Temperature Control M221 Project Template

Packaging User Guide for Temperature Control M221 Project Template Packaging EIO0000001762 04/2014 Packaging User Guide for Temperature Control M221 Project Template 04/2014 EIO0000001762.00 www.schneider-electric.com The information provided in this documentation contains

More information

SCADAPack E Input/Output Module Hardware Manual. Version: Date: August 2017

SCADAPack E Input/Output Module Hardware Manual. Version: Date: August 2017 SCADAPack E Version: Date: August 2017 Table of Contents 1 Legal Information...5 2 Technical Support...6 3 Safety Information...7 4 Documentation Check...10 5 About this Manual...11 6 About the 5610 I/O

More information

SCADAPack E ISaGRAF 3 I/O Connection Reference

SCADAPack E ISaGRAF 3 I/O Connection Reference SCADAPack E ISaGRAF 3 I/O Connection Reference 2 SCADAPack E ISaGRAF 3 I/O Connection Reference Table of Contents Part I ISaGRAF 3 I/O Connection 4 1 Technical... Support 4 2 Safety... Information 5 3

More information

SCADAPack E Koyo DirectNET PLC Interface Manual

SCADAPack E Koyo DirectNET PLC Interface Manual SCADAPack E Koyo DirectNET PLC Interface Manual 2 SCADAPack E Koyo DirectNET PLC Interface Manual Table of Contents Part I Koyo DirectNET PLC Interface 3 1 Technical... Support 3 2 Safety... Information

More information

SCADAPack E Input/Output Module Hardware Manual. Version: March 2016

SCADAPack E Input/Output Module Hardware Manual. Version: March 2016 SCADAPack E Version: Date: March 2016 Table of Contents 1 Legal Information...6 2 Technical Support...7 3 Safety Information...8 4 Documentation...11 Check 5 About this Manual...13 6 About the 5606 I/O

More information

Security Quick Start Guide

Security Quick Start Guide 2 Table of Contents Part I 4 1 Technical... Support 4 2 Safety... Information 5 3 Introduction... 7 4 Security... Overview 8 5 How to... Configure DNP3 Secure Authentication 11 5.1 Check RTU Firm... w

More information

SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide

SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide SoMachine EIO0000001868 11/2016 SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide 11/2016 EIO0000001868.04 www.schneider-electric.com The information provided in this documentation

More information

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution LXM32 Explanation for detected error E 733F Expert Support Machine Solution The information provided in this documentation contains general descriptions and/or technical characteristics of the performance

More information

SCADAPack 350E Hardware Manual

SCADAPack 350E Hardware Manual SCADAPack 350E Hardware Manual 2 Table of Contents Part I 4 1 Technical... Support 4 2 Safety... Information 5 3 Introduction... 8 4 Installation... 9 4.1 Field Wiring... 11 5 Power... Supply Overview

More information

5601/5601A Input / Output (I/O) Module

5601/5601A Input / Output (I/O) Module 5601/5601A Input / Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or

More information

SCADAPack E Data Processing Technical Reference

SCADAPack E Data Processing Technical Reference SCADAPack E Data Processing Technical Reference 2 SCADAPack E Data Processing Technical Reference Table of Contents Part I Data Processing Technical 4 1 Technical... Support 4 2 Safety... Information 5

More information

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction

More information

SCADAPack 32. Smart RTU

SCADAPack 32. Smart RTU SCADAPack 32 Smart RTU 1 Compared to the SCADAPack 300 platform, the SCADAPack 32 is a higher performance Smart RTU built to meet the demands of larger applications including support for up to 10 gas flow

More information

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated

More information

GETTING STARTED GUIDE NI Channel, 60 V, High-Speed, Sourcing Digital Output Module

GETTING STARTED GUIDE NI Channel, 60 V, High-Speed, Sourcing Digital Output Module GETTING STARTED GUIDE NI 9475 8-Channel, 60 V, High-Speed, Sourcing Digital Output Module This document explains how to connect to the NI 9475. Note Before you begin, complete the software and hardware

More information

SCADAPack Smart RTU

SCADAPack Smart RTU SCADAPack 330 334 Smart RTU 1 Built on the proven SCADAPack 300 platform, the SCADAPack 330 and 334 feature high-performance 32-bit processing, highspeed LAN, serial and USB communications, integrated

More information

CONTROL MICROSYSTEMS Potentiometer Analog Input Module. Hardware Manual

CONTROL MICROSYSTEMS Potentiometer Analog Input Module. Hardware Manual 55 Potentiometer Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

GETTING STARTED GUIDE NI V, 32-Channel (Sinking Input), 7 µs C Series Digital Module

GETTING STARTED GUIDE NI V, 32-Channel (Sinking Input), 7 µs C Series Digital Module GETTING STARTED GUIDE NI 9425 24 V, 32-Channel (Sinking Input), 7 µs C Series Digital Module This document explains how to connect to the NI 9425. In this document, the NI 9425 with spring terminal and

More information

TM3DI16G module TM3-16 inputs spring

TM3DI16G module TM3-16 inputs spring Characteristics module TM3-16 inputs spring Main Range of product Product or component type Range compatibility Modicon TM3 Discrete input module Modicon M221 Modicon M241 Modicon M251 Discrete input number

More information

5604 Input/Output (I/O) Module

5604 Input/Output (I/O) Module 5604 Input/Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

GETTING STARTED GUIDE NI Channel Solid-State Relay (SSR) Digital Output Module

GETTING STARTED GUIDE NI Channel Solid-State Relay (SSR) Digital Output Module GETTING STARTED GUIDE NI 9485 8-Channel Solid-State Relay (SSR) Digital Output Module This document explains how to connect to the NI 9485. Note Before you begin, complete the software and hardware installation

More information

RM35LM33MW liquid level control relay RM35-L V AC/DC

RM35LM33MW liquid level control relay RM35-L V AC/DC Characteristics liquid level control relay RM35-L - 24..240 V AC/DC Complementary reset time maximum switching voltage Main range of product product or component type relay type relay name relay monitored

More information

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA Characteristics phase control relay RM17-T - range 183..484 V AC Main Range of product Product or component type Relay type Product specific application Relay name Relay monitored parameters Switching

More information

RMCN22BD Analog Converter ma - for Zelio Analog

RMCN22BD Analog Converter ma - for Zelio Analog Characteristics Analog Converter - 4..20 ma - for Zelio Analog Main Commercial Status Range of product Product or component type Analogue input type Analogue output type Commercialised Zelio Analog Voltage/Current

More information

GETTING STARTED GUIDE NI AO, 0 ma to 20 ma, 16 Bit Simultaneous

GETTING STARTED GUIDE NI AO, 0 ma to 20 ma, 16 Bit Simultaneous GETTING STARTED GUIDE NI 9266 8 AO, 0 ma to 20 ma, 16 Bit Simultaneous This document explains how to connect to the NI 9266. In this document, the NI 9266 with screw terminal and the NI 9266 with DSUB

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

ICF-1150 Series Quick Installation Guide

ICF-1150 Series Quick Installation Guide ICF-1150 Series Quick Installation Guide Fifth Edition, July 2015 2015 Moxa Inc. All rights reserved. P/N: 1802011500014 1802011500014 Overview Introduction ICF-1150 series fiber converters have a multi-interface

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language)

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) XPSMCMx Fieldbus Expansion Modules EAV8283001 12/2014 XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) 12/2014 EAV8283001.00 www.schneider-electric.com The information provided

More information

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC Characteristics on-delay timing relay - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical

More information

XMLK006B2C21 pressure sensor XMLK bar - G 1/4A mA - DIN - set of 1

XMLK006B2C21 pressure sensor XMLK bar - G 1/4A mA - DIN - set of 1 Characteristics pressure sensor XMLK - 0..6bar - G 1/4A - 4..20mA - DIN - set of 1 Complementary Pressure setting range Maximum permissible accidental pressure Destruction pressure Materials in contact

More information

SCADAPack 32 Controller

SCADAPack 32 Controller SCADAPack 32 Controller Installation, Operation and Maintenance Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical characteristics

More information

SCADAPack E Input/Output Module Hardware Manual. Version: March 2016

SCADAPack E Input/Output Module Hardware Manual. Version: March 2016 SCADAPack E Version: Date: March 2016 Table of Contents 1 Legal Information...5 2 Technical Support...6 3 Safety Information...7 4 About this Manual...11 5 About the 6601 I/O Expansion Module...12 6 Hardware

More information

FLEX Ex Spring Clamp Terminal Base

FLEX Ex Spring Clamp Terminal Base Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification

More information

CONTROL MICROSYSTEMS and 5601A Input/Output (I/O) Module. Hardware Manual

CONTROL MICROSYSTEMS and 5601A Input/Output (I/O) Module. Hardware Manual 5601 and 5601A Input/Output (I/O) Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9

More information

ABL4RSM24050 regulated SMPS - 1 or 2 phase V AC - 24 V - 5A

ABL4RSM24050 regulated SMPS - 1 or 2 phase V AC - 24 V - 5A Characteristics regulated SMPS - 1 or 2 phase - 120..230 V AC - 24 V - 5A Complementary Input voltage limits Network frequency Inrush current Main Range of product Product or component type Power supply

More information

Momentum 170ENT11001/170ENT11002 Ethernet Communications Adapter User Guide

Momentum 170ENT11001/170ENT11002 Ethernet Communications Adapter User Guide Momentum 31004109 09/2017 Momentum 170ENT11001/170ENT11002 Ethernet Communications Adapter User Guide 09/2017 31004109.07 www.schneider-electric.com The information provided in this documentation contains

More information

ABL8REM24050 regulated SMPS - 1 or 2-phase V AC - 24 V - 5 A

ABL8REM24050 regulated SMPS - 1 or 2-phase V AC - 24 V - 5 A Characteristics regulated SMPS - 1 or 2-phase - 100..240 V AC - 24 V - 5 A Complementary Input voltage limits Network frequency Inrush current Main Range of product Product or component type Power supply

More information

TM7BDM8B. Main. Enclosure material. Input/output number 8 Input/output number of splitter box

TM7BDM8B. Main. Enclosure material. Input/output number 8 Input/output number of splitter box Product datasheet Characteristics TM7BDM8B Main Range of product Product or component type Range compatibility Enclosure material Bus type System Voltage Input/output number 8 Input/output number of splitter

More information

TM7BDI16B. Main. Enclosure material. Input/output number 16 Input/output number of splitter box

TM7BDI16B. Main. Enclosure material. Input/output number 16 Input/output number of splitter box Product datasheet Characteristics TM7BDI16B Main Range of product Product or component type Range compatibility Enclosure material Bus type System Voltage Input/output number 16 Input/output number of

More information

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0 170 ADM 850 10 10 to 60 VDC Module Base / 170 ADO 830 30 6 Pt. Relay Out Module Base Version 1.0 31005197 00 Safety Information NOTICE Read these instructions carefully, and look at the equipment to become

More information

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW) Product data sheet Characteristics ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW) Complementary Assembly style Function available Power supply voltage limits Main Range of

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW) Characteristics soft starter-ats22-control 220V-power 230V(110kW)/400...440V(220kW) Complementary Assembly style Function available Power supply voltage limits Main Range of product Altistart 22 Product

More information

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC Characteristics multifunction phase control relay RM35-T - range 194..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22C17Q Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22D75S6U Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

CONTROL MICROSYSTEMS Toggle Switch Digital Input Module. Hardware Manual

CONTROL MICROSYSTEMS Toggle Switch Digital Input Module. Hardware Manual 5 Toggle Switch Digital Input Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 8 Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support:

More information

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS Characteristics battery control module - 24..28.8 V DC - 24 V - 20 A - for regulated SMPS Main Range of product Product or component type Input voltage Output voltage Maximum output current Phaseo Battery

More information

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC Characteristics phase control relay RM17-T - range 183..484 V AC Complementary Maximum switching voltage Minimum switching current [Us] rated supply voltage Supply voltage limits Control circuit voltage

More information

Analog Monitor Installation Manual

Analog Monitor Installation Manual Analog Monitor Installation Manual Part Number: 144-23919 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems and equipment.

More information

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22D47S6U Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O Product datasheet Characteristics RM22LA32MR Level control relay RM22-L - 24..240 V AC/DC - 2 C/O Main Range of product Product or component type Relay type Relay name Relay monitored parameters Time delay

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

TM3TI4 module TM3-4 inputs temperature

TM3TI4 module TM3-4 inputs temperature Characteristics module TM3-4 inputs temperature Complementary Analogue input resolution Permissible continuous overload Input impedance LSB value Conversion time Sampling duration Main Range of product

More information

SCADAPack 100 Controller

SCADAPack 100 Controller Installation, Operation and Maintenance Setup Manual 2/24/2017 Copyright 2014-2017 Schneider Electric Canada Inc. All rights reserved. The information provided in this documentation contains general descriptions

More information

ICF-1150 Series Quick Installation Guide

ICF-1150 Series Quick Installation Guide ICF-1150 Series Quick Installation Guide Second Edition, March 2012 2012 Moxa Inc. All rights reserved. P/N: 1802011500011 Overview Introduction The ICF-1150 series fiber converters are equipped with a

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

SCADAPack 350E 357E. Smart Remote Terminal Unit

SCADAPack 350E 357E. Smart Remote Terminal Unit SCADAPack 350E 357E Smart Remote Terminal Unit 1 The SCADAPack 300E Smart RTU is a platform built on a 32-bit processor and fitted with a 12-30 Vdc supply, various communication links and a wide range

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output Complementary Control type Voltage range Main Range of product Product or component type Discrete output type Width

More information

ArmorPoint I/O Field Potential Distributor, Series A

ArmorPoint I/O Field Potential Distributor, Series A Installation Instructions ArmorPoint I/O Field Potential Distributor, Series A (Cat. No. 1738-FPD) The field potential distributor (Cat. no. 1738-FPD) lets you change the field power distribution source

More information

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h Characteristics soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h Complementary Assembly style Function available Power supply voltage limits Main Range of product Altistart

More information

TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module

TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module 1639093 03/2009 TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module User Manual 03/2009 1639093 www.schneider-electric.com Schneider Electric assumes no responsibility for any errors that may appear

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/ O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - on base plate Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific

More information

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC Characteristics time delay relay for star-delta starter - 0.05..1 s - 24 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW) Product datasheet Characteristics ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/400...440V(7.5kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Instruction Bulletin 30072-452-48 Retain for future use. 30072-452-48 Altivar 61/71 Heatsink Fan Kits VZ3V1212 and VZ3V1216

More information

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A Product datasheet Characteristics ABL8RPS24100 regulated SMPS - 1 or 2-phase - 100..500 V - 24 V - 10 A Complementary Input voltage limits Network frequency Inrush current Cos phi Main Range of product

More information

Schneider Electric Floating License Manager

Schneider Electric Floating License Manager Schneider Electric Floating License Manager EIO0000001078 11/2012 Schneider Electric Floating License Manager User Manual 12/2012 EIO0000001078.01 www.schneider-electric.com The information provided in

More information

ABL1RPM24100 regulated SMPS - single phase V input - 24 V output W

ABL1RPM24100 regulated SMPS - single phase V input - 24 V output W Characteristics regulated SMPS - single phase - 100..240 V input - 24 V output - 240 W Complementary Input voltage limits Network frequency limits Inrush current Main Range of product Product or component

More information

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink Product datasheet Characteristics ATV12H075M3 variable speed drive ATV12-0.75kW - 1hp - 200..240V - 3ph - with heat sink Complementary Main Range of product Altivar 12 Product or component type Product

More information

EH-RIO IP67 Profibus-DP I/O modules

EH-RIO IP67 Profibus-DP I/O modules Installation Instructions EH-RIO IP67 Profibus-DP I/O modules (RIO-PBXDP8M12, -PBXDP8M8, -PBYTP8M12, -PBYTP8M8, -PBXYP8M12, -PBXYP8M8) M12 Style Connectors M8 Style Connectors 43819 The EH-RIO IP67 Profibus-DP

More information

Ethernet Modbus X80 Gateway Device Type Manager

Ethernet Modbus X80 Gateway Device Type Manager Ethernet Modbus X80 Gateway Device Type Manager EIO0000001315 10/2012 Ethernet Modbus X80 Gateway Device Type Manager User Manual 10/2012 EIO0000001315.00 www.schneider-electric.com The information provided

More information