Galaxy VM kva 480 V, kva 400 V. Operation 05/2014.

Size: px
Start display at page:

Download "Galaxy VM kva 480 V, kva 400 V. Operation 05/2014."

Transcription

1 Galaxy VM kva 480 V, kva 400 V Operation 05/2014

2 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the sole property of Schneider Electric SA and its subsidiaries. They may not be used for any purpose without the owner's permission, given in writing. This guide and its content are protected, within the meaning of the French intellectual property code (Code de la propriété intellectuelle français, referred to hereafter as "the Code"), under the laws of copyright covering texts, drawings and models, as well as by trademark law. You agree not to reproduce, other than for your own personal, noncommercial use as defined in the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in writing. You also agree not to establish any hypertext links to this guide or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the guide or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.

3 Table of Contents kva 480 V, kva 400 V Important Safety Information...1 Safety Precautions...2 Galaxy VM System Overview...3 UPS...3 Battery Options...4 Modular Battery Cabinets...4 Classic Battery Cabinets...4 Battery Breaker Box...5 System Bypass Cabinet...5 Overview of User Interface...5 Overview of Mimic Diagram...7 Overview of Status LEDs...7 Display Menu Tree...8 Display Symbols...9 Overview of Controller Interface...9 Configuration...10 Add a New User or Edit an Existing User...10 Delete a User...10 Configure the Display Preferences Configure the Display Settings Configure the UPS Output Voltage Compensation...12 Configure High Efficiency Mode...12 Configure the Redundancy Level of the Parallel System...13 Configure the Input Contacts...14 Configure the Output Relays...15 Configure Reminder Settings...15 Configure Battery Alarm Threshold...16 Configure Automatic Battery Test...17 Configure the Network...18 Configure the Modbus...19 Restore Default Configuration...20 Operation...21 Operation Modes...21 UPS Operation Modes...21 System Operation Modes...23 Operation Procedures...25 Access Password-Protected Screens A 001 i

4 kva 480 V, kva 400 V View the System Status Information...26 Start Up Single System from Maintenance Bypass Operation...29 Shut Down Single System from Normal to Maintenance Bypass Operation...31 Start Up Parallel System from Maintenance Bypass Operation...32 Shut Down Parallel System from Normal to Maintenance Bypass Operation...33 Start Up and Add UPS to a Running Parallel System...35 Isolate this Single UPS from the Parallel System...36 Transfer UPS from Normal to Requested Static Bypass Operation...37 Transfer UPS from Requested Static Bypass Operation to Normal Operation...37 Start a Boost Charge of the Batteries...37 Access a Configured Network Management Interface...38 Maintenance...39 Replace the Top Filter in the Power Section...39 Replace the Three Bottom Filters in the Power Section...40 Troubleshooting...41 Troubleshooting via the Mimic Diagram LEDs...41 Input LED...41 Inverter LED...41 Load LED...41 Battery LED...42 Bypass LED...42 Reboot the Display...42 Reset the Password...43 Logs...43 View the NMC Log...43 View the UPS Log...45 Export Data from Logs...45 View the Active Alarms...46 Alarm Levels...46 Alarm Messages...47 Tests...52 Perform a Battery Test...53 Perform a Runtime Calibration...53 Perform an Annunciators Test...53 Calibrate the Display...54 Determine if you need a Replacement Part...54 Find the UPS Serial Number...54 Return Parts to Schneider Electric...54 ii A 001

5 Important Safety Information Important Safety Information kva 480 V, kva 400 V Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death. DANGER DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury. WARNING WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage. NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage. Please Note Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material A 001 1

6 kva 480 V, kva 400 V Important Safety Information A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. Safety Precautions DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH After the UPS system has been electrically wired, do not start up the system. Startup must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury A 001

7 Galaxy VM System Overview Galaxy VM System Overview kva 480 V, kva 400 V UPS Front View of UPS The UPS is the core in each Galaxy VM System and consists of two cabinets: To the right an I/O cabinet placed for field wiring and containing disconnection devices. To the left a power cabinet containing power electronics and the user interface A 001 3

8 kva 480 V, kva 400 V Galaxy VM System Overview Battery Options Modular Battery Cabinets The modular battery cabinet is available in two sizes: Narrow Modular Battery Cabinet Wide Modular Battery Cabinet Classic Battery Cabinets The classic battery cabinet is available in two sizes: Narrow Classic Battery Cabinet Wide Classic Battery Cabinet A 001

9 Galaxy VM System Overview kva 480 V, kva 400 V Battery Breaker Box The battery breaker box provides protection in installations with customer-specific battery solutions. Battery Breaker Box System Bypass Cabinet The system bypass cabinet is used in parallel systems and contains the maintenance bypass breaker MBB and the system isolation breaker SIB. The 675 kva system bypass cabinet is also available in a version with a load bank breaker. Front View of the System Bypass Cabinet Overview of User Interface The user interface is placed on the front of the power cabinet and consists of: A. Display interface B. Status LEDs C. Mimic diagram A 001 5

10 kva 480 V, kva 400 V Galaxy VM System Overview D. Inverter ON button E. Inverter OFF button F. USB port for export of logs G. Display reset button H. Network connection LED: Solid green: The system has valid TCP/IP settings. Flashing green: The system does not have valid TCP/IP settings. Refer to Configure the Network, page 18. Solid orange: The display is inoperable. Contact Schneider Electric. Flashing orange: The system is making BOOTP requests. Refer to Configure the Network, page 18. Alternately flashing green and orange: If the LED is alternately flashing slowly, the system is making DHCP requests.refer to Configure the Network, page 18. If the LED is alternately flashing rapidly, the system is starting up. Off: The display is not receiving input power or the display is inoperable. I. LED for indication of network connection type: Solid green: The system is connected to a network operating at 10 Megabits per second (Mbps). Flashing green: The system is receiving or transmitting data packets at 10 Megabits per second (Mbps). Solid orange: The system is connected to a network operating at 100 Megabits per second (Mbps). Flashing orange: The system is receiving or transmitting data packets at 100 Megabits per second (Mbps). Off: One or more of the following exists: The display is not receiving input power, the cable that connects the system to the network is disconnected, the device that connects the system to the network is turned off, or the display is inoperable. Check the connections and if the LED remains off, Contact Schneider Electric. J. Slots reserved for service. Do not use A 001

11 Galaxy VM System Overview kva 480 V, kva 400 V Overview of Mimic Diagram The mimic diagram shows the power flow through the UPS system, and the status of the main functions. Each LED can be in one of the below three states: Green The corresponding function is active and OK Red The corresponding function is not working properly Off The corresponding function is not active For more information, see Troubleshooting via the Mimic Diagram LEDs, page 41. Overview of Status LEDs The status LEDs placed next to the display interface shows the current status of the UPS system: Green: The load is protected Green + Orange: The load is protected, but the system reports an alarm at warning level Orange + Red: The load is unprotected and the system reports an alarm at warning level and an alarm at critical level Red: The load is unprotected and the system reports an alarm at critical level A 001 7

12 kva 480 V, kva 400 V Galaxy VM System Overview Display Menu Tree 1 Only available in single systems 2 Only available in parallel systems NOTE: The control and configuration screens are password-protected A 001

13 Galaxy VM System Overview kva 480 V, kva 400 V Display Symbols Symbol Description The home button when the system is locked by a password protection. Tap this button to go to the home screen of the display. The home button when the system has been unlocked using the password. Press this button to go to the home screen of the display. Tap the OK button to confirm your selections and exit the current screen. Tap the ESC button to cancel your changes and exit the current screen. Tap the filter button to up the filters for your logs. Tap the recycle bin button to clear the log. Overview of Controller Interface Front View of Power Cabinet A. Two Smart Slots for optional Network Management Cards B. Modbus and modbus dip switch settings C. Ethernet A 001 9

14 kva 480 V, kva 400 V Configuration Configuration Add a New User or Edit an Existing User 1. From the home screen on the display select Configuration > Display > Security. 2. Select Add User to add a new user or select Edit User to edit an existing user of the system. 3. In the Name field, type in the name of the user. Complete with Enter. 4. In the Pin field, type in a pin code for the user. Complete with Enter. 5. In the Confirm Pin field, retype the pin code of the user. Complete with Enter. 6. Under Language, select the preferred language of the user using the up and down arrows. 7. Under Date Format, select the preferred date format of the user. 8. Under Temperature, select if the user should see temperature values in either metric ( Celsius) or US Customary ( Fahrenheit) format. 9. Tap OK to save your settings. Delete a User 1. From the home screen on the display select Configuration > Display > Security > Delete User. 2. Browse to the user that you wish to delete using the up and down arrows and tap OK. 3. Tap Yes to confirm deletion of an existing user of the system A 001

15 Configuration Configure the Display Preferences kva 480 V, kva 400 V 1. From the home screen on the display select Configuration > Display > Preferences. 2. Select the preferred language using the up and down arrows. 3. Select the preferred date format using the up and down arrows. 4. Select the preferred temperature units: US Customary ( Fahrenheit) or Metric ( Celsius). 5. Set the current date and time using one of the below two methods: Set the date and time manually on the display by selecting Manual and typing the actual date and time and completing with Enter. Set the date and time automatically by selecting Synchronize with the NTP server (Network Time Protocol server). NOTE: NTP server settings can be configured in the network management interface via the Web. 6. Tap OK to save your settings. Configure the Display Settings 1. From the home screen on the display select Configuration > Display > System Settings A

16 kva 480 V, kva 400 V Configuration 2. Set the Alarm Volume. Choose between: Off, Low, Medium, and High. 3. Set the Button Volume. Choose between: Off, Low, Medium, and High. 4. Set the Brightness of the display. Choose between: Low, Medium, and High. 5. Enable or disable Backlight Timeout. If you wish to enable backlight timeout, set the time limit in minutes for enabling backlight timeout. Choose between: 60, 30, 10, 5, and Set the intensity of the backlight. Choose between: Off, Very Low, Low, and Medium. 7. Set the time limit in minutes for automatic log off. Choose between: 60, 30, 10, 5, and Tap OK to save your settings. Configure the UPS Output Voltage Compensation 1. From the home screen on the display select Configuration > UPS > Output. 2. Under Voltage Compensation type in the preferred voltage compensation for your system. Choose between 0%, 1%, 2%, or 3% and complete with Enter. 3. Tap OK to confirm your setting. Configure High Efficiency Mode NOTE: ECO Mode must be enabled by Schneider Electric during service configuration to make this selection available A 001

17 Configuration kva 480 V, kva 400 V 1. From the home screen on the display select Configuration > UPS > High Efficiency Mode and configure the following settings: a. Mode: Choose between ECO Mode, ECOnversion, and Disable. b. ECOnversion Harmonics Compensator: Choose Enable to activate harmonics compensation when in ECOnversion mode. 2. Tap > and configure the schedule settings: a. Schedule: Select when the system should enter the selected ECOnversion or ECO mode. Choose between Always, Programmed and Never. b. Active Schedules List: If you chose Programmed above, select Enable and set the time and date for when the system should enter the selected ECOnversion or ECO mode. 3. Tap OK to confirm your settings. Configure the Redundancy Level of the Parallel System This procedure sets the redundancy level of your parallel system. The parallel system can contain up to five UPS units and the maximum configuration is a 4+1 system with four UPS units in capacity and one in redundancy A

18 kva 480 V, kva 400 V Configuration 1. From the home screen on the display select Configuration > UPS > Parallel System. 2. Under Parallel system redundancy select the redundancy for your UPS system. Choose between N+0, N+1, N+2, N+3, N Tap OK to confirm your setting. Configure the Input Contacts 1. On the display select Configuration > Input Contacts and select the input contact that you wish to configure. 2. Choose between the below six options: Custom Input 1 Custom Input 2 Ground fault External Battery Monitor Detected Fault Battery Room Ventilation Inoperable Supplied By Genset 3. Tap OK to save your settings A 001

19 Configuration Configure the Output Relays kva 480 V, kva 400 V 1. On the display select Configuration > Output Relays and select the output relay that you wish to configure. 2. Select the function that you wish to use the specific output relay for from the list below: Common Alarm Battery Operation Static Bypass Output Overload Battery is not Working Correctly Battery Voltage Low Bypass Out of Tolerance UPS Critical External Fault System Critical Normal Operation Maintenance Bypass ECO Mode Fan Inoperable Battery Disconnected Input Out of Tolerance UPS Warning Parallel Redundancy Lost UPS Maintenance Mode System Warning System Common Alarm 3. Set the delay in seconds for the specific output to activate. Select a value between 0 and 60 seconds. 4. Tap OK to save your settings. Configure Reminder Settings 1. From the home screen on the display select Configuration > Reminders A

20 kva 480 V, kva 400 V Configuration 2. Configure the following settings: a. Reminders Signalling: Select Enable to enable the display of all reminders. b. Reminder: Select Enable to enable the display of reminders for air filter replacement. c. Duration before 1st Reminder: Set the time in weeks before the first reminder is shown. d. Elapsed Time: Manually set the number of days that the air filters have been used. 3. Tap OK to confirm your settings. Configure Battery Alarm Threshold 1. From the home screen on the display select Configuration > Battery > Alarms. 2. Select your preferred battery alarm threshold in seconds. Select a value between 60 and 6000 seconds and complete with Enter. 3. Tap OK to confirm your setting A 001

21 Configuration Configure Automatic Battery Test kva 480 V, kva 400 V 1. From the home screen on the display select Configuration > Battery > Test. 2. Set your preferred settings for the automatic battery test: a. Battery Test Interval: Select your preferred interval for battery tests. Choose between: Never, Every 52 Weeks, Every 26 Weeks, Every 12 Weeks, Every 8 Weeks, Every 4 weeks, Every 2 Weeks, or Once a Week. NOTE: Running battery tests too frequently can reduce the lifetime of the batteries. b. Battery Test Start Time: Select the time of the day in 24 hour format that the test should take place and complete with Enter. c. Battery Test Day of the Week: Select the day of the week that the test should take place and complete with Enter. 3. When all settings have been completed, tap OK to confirm your settings A

22 kva 480 V, kva 400 V Configuration Configure the Network The network can be configured for the display and for the cards in Smart Slot 1 and Smart Slot From the home screen on the display select Configuration > Network and select either Display, Smart Slot 1, or Smart Slot 2 if present. 2. Configure the following settings: a. TCP/IPv4: Enable IPv4 (if applicable), and select the Address Mode (Manual, DCHP, or BOOTP). b. TCP/IPv6: Enable IPv6 (if applicable), select Auto Configuration or Manual Configuration, and select the DHCPv6 Mode (Router controlled, Non-Address Information Only, Never, or Address and Other Information). NOTE: Tap Addresses to see all valid IPv6 addresses A 001

23 Configuration kva 480 V, kva 400 V c. Web Access: Enable Web (if applicable) and select the Access Mode (HTTP or HTTPS). NOTE: Not available for Smart Slots. d. FTP server: Enable FTP (if applicable). NOTE: Not available for Smart Slots. Configure the Modbus The modbus can be configured for the display and for the cards in Smart Slot 1 and Smart Slot 2. NOTE: Only the display and optional Network Management Card AP9635 can be used for serial modbus. 1. From the home screen on the display select Configuration > Modbus and select either Display, Smart Slot 1, or Smart Slot A

24 kva 480 V, kva 400 V Configuration 2. Configure the modbus by enabling Serial or TCP access, adding the needed values, and completing with Enter. 3. Tap OK to confirm your settings. Restore Default Configuration 1. From the home screen on the display select Configuration > Restore Defaults. 2. Select one of the below options: Restart Network Interface: Select this option to restart network interface. Reset All: Select this option to reset all settings to default. You can select to leave out the TCP/IP settings from the reset procedure. Reset Only: Select this option if you only wish to reset parts of the settings to default values. You can select to reset the following settings: TCP/IP, Event Configuration, and Display Settings. 3. When you have made your selection, tap OK to reset the selected settings to default A 001

25 Operation Operation kva 480 V, kva 400 V Operation Modes The Galaxy VM has two different levels of operation mode: UPS Operation Mode: The operation mode of the operated UPS System Operation Mode: The operation mode of the complete UPS system UPS Operation Modes Normal During normal operation, the UPS supports the load with conditioned power. While the UPS is in normal operation, the input, inverter, and load LEDs are green, and the battery and bypass LEDs are off. Battery If the utility/mains supply fails, the UPS transfers to battery operation and supports the load with conditioned power from the DC source. While the UPS system is in battery operation, the battery, inverter, and load LEDs are green, the bypass LED is off and the input LED is red. Requested Static Bypass The UPS can be transferred to requested static bypass following a command from the display. During static bypass operation, the load is supplied from the bypass source. If a fault is detected, the UPS will transfer to normal operation or forced static bypass operation. If there is an interruption to the utility/mains power supply during requested static bypass operation, the system will transfer to battery operation. The load may experience a short duration interruption of power (4 to 8 ms) during this transfer. During requested static bypass, the input, bypass and output LEDs are green and the battery and inverter LEDs are off A

26 kva 480 V, kva 400 V Operation Forced Static Bypass The UPS is in forced static bypass following a command from the UPS system or because the user has pressed the inverter OFF button on the UPS. During forced static bypass operation, the load is supplied directly by the bypass source. The batteries are not available as an alternate power source while the UPS is in forced static bypass operation. During forced static bypass, the input, bypass and output LEDs are green and the battery and inverter LEDs are off or red if an alarm is present. Maintenance Bypass Operation When the Maintenance Bypass Breaker (MBB) is closed, the UPS system enters maintenance bypass operation. The load is supplied with unconditioned power from the bypass input. The batteries are not available as an alternate power source while the UPS is in maintenance bypass operation. Static Bypass Standby NOTE: Static bypass standby is only applicable to an individual UPS in a parallel system. The UPS enters static bypass standby if the UPS is prevented from entering forced static bypass and the other UPS units of the parallel system can support the load. In static bypass standby the output of the specific UPS is off. The UPS automatically changes to the preferred operation mode when possible. NOTE: If the other UPS units cannot support the load, the parallel system enters forced static bypass. The UPS in static bypass standby will then transfer to forced static bypass. Inverter Standby NOTE: Inverter standby is only applicable to an individual UPS in a parallel system. The UPS enters inverter standby if there is an interruption to the utility/mains supply of the UPS and the other UPS units of the parallel system can support the load with the configured redundancy level maintained. This is to avoid that the batteries are being drained in situations where it is not necessary. Battery Test The UPS is in battery test mode when the UPS is performing a battery self-test or a runtime calibration. NOTE: The battery test will be aborted if the utility/mains supply is interrupted or a critical alarm is present and will return to normal operation upon return of utility/ mains A 001

27 Operation kva 480 V, kva 400 V ECO Mode NOTE: ECO mode must be enabled by a Schneider Electric field service engineer. ECO mode allows the UPS to be configured to use requested static bypass, with the load supplied through the bypass, as the preferred operation mode under predefined circumstances. If a fault is detected (bypass voltage out of tolerance, output voltage out of tolerance, etc), the UPS will immediately change to normal operation or forced static bypass. The main advantage of ECO mode is a reduction in the consumption of electrical power. In case of interruption to the utility/mains supply, the UPS transfers to inverter operation for a continuous supply of the load. The load may experience a short duration interruption of power (4 to 8 ms) during this transfer. ECOnversion Mode ECOnversion allows the system to supply the active part of the load through the bypass. The inverter is kept running in parallel with the bypass source and supplies the reactive part of the load. The input power factor of the UPS is, regardless of the load power factor, maintained close to unity as the reactive part of the load is significantly reduced in the UPS input current. In case of an interruption to the utility/mains supply, the inverter immediately maintains the output voltage so that breaks or drops during this transfer are practically eliminated. Self-test After startup of the UPS system, the UPS will perform an automatic self-test. The status and progress of the self-test are indicated by the flashing LEDs on the mimic diagram. When the self-test has been passed, the LEDs will indicate the operation mode of the UPS system. NOTE: If an LED continues to flash after completion of the self-test, please call Schneider Electric. Off When the UPS is in off, the UPS does not supply the connected load with power. System Operation Modes The system operation mode indicates the current output status of the complete UPS system and which source that supplies the load A

28 kva 480 V, kva 400 V Operation Inverter In inverter operation the load is supplied by the inverters. The UPS mode can be in either normal or battery operation when the system operation mode is inverter operation. Requested Static Bypass When the system is in requested static bypass, the load is supplied from the bypass source. If a fault is detected, the system will transfer to inverter operation or forced static bypass operation. The load may experience a short duration interruption of power (4 to 8 ms) during this transfer. Forced Static Bypass The system is in forced static bypass following a command from the UPS system or because the user has pressed the inverter OFF button on the UPS units. During static bypass operation, the load is supplied directly by the bypass source. The batteries are not available as an alternate power source while the system is in forced static bypass operation. Maintenance Bypass In maintenance bypass operation, the load is supplied by unconditioned power from the bypass input via the maintenance bypass breaker. NOTE: The batteries are not available as an alternate power source in maintenance bypass operation. ECO Mode NOTE: ECO mode must be enabled by a Schneider Electric field service engineer. ECO Mode allows the system to be configured to use requested static bypass, with the load supplied through the bypass, as the preferred operation mode under predefined circumstances. The main advantage of ECO mode is a reduction in the consumption of electrical power. In case of interruption to the utility/mains supply, the UPS transfers to inverter operation for a continuous supply of the load. The load may experience a short duration interruption of power (4 to 8 ms) during this transfer. ECONversion Mode ECOnversion allows the system to supply the active part of the load through the bypass. The inverter is kept running in parallel with the bypass source and supplies the reactive part of the load. The input power factor of the UPS is, regardless of the load power factor, maintained close to unity as the reactive part of the load is significantly reduced in the UPS input current. In case if an interruption to the utility/mains supply, the inverter immediately maintains the output voltage so that breaks or drops during this transfer are practically eliminated. Off When the system operation mode is off, the UPS system does not supply the connected load with power A 001

29 Operation Operation Procedures kva 480 V, kva 400 V Access Password-Protected Screens 1. When prompted for the password, select your username. 2. Type in the pin code for your username. NOTE: The default pin code is A

30 kva 480 V, kva 400 V Operation View the System Status Information 1. From the home screen on the display select Status. 2. Select the area for which you wish to see the status. Choose between: Input Phase-to-Neutral 1 Voltage (phase-to-neutral) Current The present phase-to-neutral input voltage in volts (V). The present input current from the AC utility power source per phase in amperes (A). Maximum RMS Current Apparent Power Active Power Power Factor Phase-to-Phase Voltage (phase-to-phase) Total Apparent Power Total Active Power Frequency Energy 1 Only applicable in systems with neutral connection. The maximum current for the latest 30 days. The present apparent power input for each phase in kva. Apparent power is the product of RMS (root mean square) volts and RMS amperes. The present active power (or real power) input for each phase in kilowatts (kw). Active power is the portion of power flow that, averaged over a complete cycle of the AC waveform, results in net transfer of energy in one direction. The ratio of the active power to apparent power. The present phase-to-phase input voltage. The present total apparent power input (for all three phases) in kva. The present total active power input (for all three phases) in kw. The present input frequency in hertz (Hz). The total energy consumption since the time of installation or since the number was reset A 001

31 Operation kva 480 V, kva 400 V Output Phase-to-Neutral 1 Voltage (phase-to-neutral) Current Maximum RMS Current Apparent Power Active Power Power Factor Current Crest Factor Current THD Phase-to-Phase Voltage (phase-to-phase) Total Apparent Power Total Active Power Load Neutral Current 1 Frequency Inverter Status The phase-to-neutral output voltage at the inverter in volts (V). The present output current for each phase in amperes (A). The maximum current for the latest 30 days. The present apparent power output for each phase in thousands of Volt- Amps (kva). Apparent power is the product of RMS (root mean square) volts and RMS amperes. The present active power (or real power) output for each phase in kilowatts (kw). Active power is the portion of power flow that, averaged over a complete cycle of the AC waveform, results in net transfer of energy in one direction. The present output power factor for each phase. Power factor is the ratio of active power to apparent power. The present output crest factor for each phase. The output crest factor is the ratio of the peak value of the output current to the RMS (root mean square) value. The THD (total harmonic distortion) for each phase, as a percentage, for the present output current. The phase-to-phase output voltage at the inverter in volts (V). The present apparent power output for each phase in thousands of Volt- Amps (kva). Apparent power is the product of RMS (root mean square) volts and RMS amperes. The present total active output power (for all three phases) in kilowatts (kw). The percentage of the UPS capacity presently used across all phases. The load percentage for the highest phase load is displayed. The present output neutral current in amperes (A). The present output frequency in hertz (Hz). The general condition of the inverter. PFC Status Energy 1 Only applicable in systems with neutral connection. The general condition of the PFC. The total energy supplied since the time of installation or since the value was reset A

32 kva 480 V, kva 400 V Operation Bypass Phase-to-Neutral 1 Voltage (phase-to-neutral) Current Maximum RMS Current Apparent Power Active Power Power Factor Phase-to-Phase Voltage (phase-to-phase) Total Apparent Power Total Active Power Frequency The present phase-to-neutral bypass voltage (V). The present bypass current for each phase, in amperes (A). The maximum current for the latest 30 days. The present apparent bypass power for each phase in thousands of Volt- Amps (kva). Apparent power is the product of RMS (root mean square) volts and RMS amperes. The present active bypass power for each phase in kilowatts (kw). Active power is the time average of the instantaneous product of voltage and current. The present bypass power factor for each phase. Power factor is the ratio of active power to apparent power. The present phase-to-phase bypass voltage (V). The present total apparent bypass power (for all three phases) in thousands of Volt-Amps (kva). The present total active bypass power (for all three phases) in kilowatts (kw). The present bypass frequency in hertz (Hz). 1 Only applicable in systems with neutral connection. Battery Voltage Current Power Estimated Charge Level Estimated Charge Time Runtime Remaining Charger Mode Battery Status Charger Status Total Battery Capacity The present battery voltage. The present battery current in amperes (A). A positive current indicates that the battery is charging; a negative current indicates that the battery is discharging. The present DC power being drawn from the battery, in kilowatts (kw). The present battery charge, as a percentage of full charge capacity. The estimated time, in minutes, until the batteries reach 80% charge. The amount of time in hours and minutes before the batteries reach the low-voltage shutdown level. The operation mode of the charger (Off, Float, Boost, Equalization, Cyclic, Test). The general condition of the battery. The general condition of the charger. The total capacity available from the available batteries. Temperature Ambient Temperature Exhaust Air Temperature Ambient temperature in degrees Celsius or Fahrenheit at the air intake of the UPS. Exhaust air temperature in degrees Celsius or Fahrenheit at the air exhaust of the UPS A 001

33 Operation kva 480 V, kva 400 V System Output Voltage Output Current Output Frequency Runtime Remaining System Time UPS Operation Mode System Operation Mode Total Output Power Output Power The phase-to-phase output voltage at the inverter in volts (V). The present output current for each phase in amperes (A). The present output frequency in hertz (Hz). The amount of time in hours and minutes before the batteries reach the low-voltage shutdown level. The time of the UPS system. The operation mode of the operated UPS. The operation mode of the complete UPS system. The apparent and active power (or real power) output for each phase. The phase-to-phase apparent and active power (or real power) output for each phase. Parallel System Input Current Output Current Bypass Current Parallel UPS Number Parallel system redundancy Number of Parallel Units Parallel Units Output Total Apparent Power Output Total Load The present phase-to-phase input current in amperes (A). The present phase-to-phase output current in amperes (A). The present phase-to-phase bypass current in amperes (A). The parallel UPS number of the operated UPS. The redundancy for the parallel system. The total number of UPSs in the parallel system. The numbers of all UPSs in the parallel system. The present total apparent output power (for all three phases) in thousands of Volt-Amps (kva). The percentage of the UPS system capacity presently used across all phases. The load percentage for the highest phase load is displayed. Active Alarms Active Alarms For more information on active alarms, go to View the Active Alarms, page 46. Mimic Mimic The mimic diagram shows the current status of the main parts of the UPS system: power sources, converters, bypass static switch and breakers, and it shows the power flow through the system. 3. Tap the home button to exit the screens and return to the home screen. Start Up Single System from Maintenance Bypass Operation Use this procedure to start up a single system from maintenance bypass operation with the load supplied through the MBB and all other breakers open. NOTE: Only operate a breaker when the associated breaker LED is green A

34 kva 480 V, kva 400 V Operation Front View of Single UPS 1. Close the unit input breaker UIB on the front of the I/O cabinet. This will power up the display interface after approximately 30 seconds. 2. From the home screen on the display, select Control > Startup Wizard. Select Startup from Maintenance Bypass and follow the steps which appear on the screen. NOTE: The following is a generic startup procedure. Always follow the steps of the Startup Wizard which are specific to your system. 3. Close the static switch input breaker SSIB on the front of the I/O cabinet. 4. Close the battery breakers in your specific battery solution. 5. Initiate transfer to static bypass by tapping the Transfer Load to static bypass button on the display interface. In systems with kirk-keys, the key is released from the solenoid key release unit. If the UPS system does not transfer to requested static bypass, go to Status > Active Alarms to see if there are active alarms that prevent the UPS system from transferring to static bypass. 6. In systems with kirk-keys, insert the key in the lock on the unit output breaker UOB and turn to unlock. 7. Close the unit output breaker UOB. 8. Open the maintenance bypass breaker MBB. The system transfers to normal operation. 9. In systems with kirk-keys, turn the key in the lock of the maintenance bypass breaker MBB to lock open. The key is released A 001

35 Operation kva 480 V, kva 400 V 10.In systems with kirk-keys, insert the key in the solenoid key release unit. Shut Down Single System from Normal to Maintenance Bypass Operation Use this procedure to shut down a single system to maintenance bypass operation with the load supplied through the MBB. NOTE: Only operate a breaker when the associated breaker LED is green. Front View of Single UPS 1. From the home screen on the display, select Control > Shutdown Wizard. Select Shut down ending in Maintenance Bypass and follow the steps which appear on the screen. NOTE: The following is a generic shutdown procedure. Always follow the steps of the Shutdown Wizard which are specific to your system. 2. Initiate transfer to static bypass by tapping the Transfer Load to static bypass button on the display interface. In systems with kirk-keys, the key is released from the solenoid key release unit. If the UPS system does not transfer to requested static bypass, go to Status > Active Alarms to see if there are active alarms that prevent the UPS system from transferring to static bypass. 3. In systems with kirk-keys, insert the key in the lock on the maintenance bypass breaker MBB and turn to unlock. 4. Close the maintenance bypass breaker MBB on the front of the I/O cabinet. In systems with kirk-keys, the key is held in the lock A

36 kva 480 V, kva 400 V Operation 5. Open the unit output breaker UOB. 6. In systems with kirk-keys, turn the key in the lock on the unit output breaker UOB to lock open. The key is released. 7. In systems with kirk-keys, insert the key in the solenoid key release unit. 8. Initiate transfer to forced static bypass by tapping the Inverter OFF button on the front of the UPS system. 9. Open the static switch input breaker SSIB on the front of the I/O cabinet. 10.Open the battery breakers in your specific battery solution. 11.Open the unit input breaker UIB on the front of the I/O cabinet. Start Up Parallel System from Maintenance Bypass Operation Use this procedure to start up a parallel system from maintenance bypass operation with the load supplied through the MBB and all other breakers open. NOTE: Only operate a breaker when the associated breaker LED is green. Front View of One Parallel UPS and System Bypass Cabinet 1. Close the unit input breaker UIB on the front of the I/O cabinet. This will power up the display interface after approximately 30 seconds. 2. From the home screen on the display, select Control > Startup Wizard. Select Startup from Maintenance Bypass and follow the steps which appear on the screen. NOTE: The following is a generic startup procedure. Always follow the steps of the Startup Wizard which are specific to your system. 3. Close the static switch input breaker SSIB on the front of the I/O cabinet. 4. Close the battery breakers in your specific battery solution A 001

37 Operation kva 480 V, kva 400 V 5. Initiate transfer to static bypass by tapping the Transfer Load to static bypass button on the display interface. In systems with kirk-keys, the key is released from the solenoid key release unit. If the UPS system does not transfer to static bypass, go to Status > Active Alarms to see if there are active alarms that prevent the UPS system from transferring to static bypass. 6. Close the unit output breaker UOB. 7. Repeat steps 1 to 6 for the remaining UPS units in the parallel system before continuing. 8. In systems with kirk-keys, insert the key from the solenoid key release unit in the lock on the system isolation breaker SIB and turn to unlock. 9. Close the system isolation breaker SIB. 10.Open the maintenance bypass breaker MBB. The system transfers to normal operation. 11.In systems with kirk-keys, turn the key in the lock of the maintenance bypass breaker MBB to lock open. The key is released. 12.In systems with kirk-keys, insert the key in the solenoid key release unit. Shut Down Parallel System from Normal to Maintenance Bypass Operation Use this procedure to shut down a parallel system to maintenance bypass operation with the load supplied through the MBB. NOTE: Only operate a breaker when the associated breaker LED is green. Front View of One Parallel UPS and System Bypass Cabinet A

38 kva 480 V, kva 400 V Operation 1. From the home screen on the display, select Control > Shutdown Wizard. Select Shut down ending in Maintenance Bypass and follow the steps which appear on the screen. NOTE: The following is a generic shutdown procedure. Always follow the steps of the Shutdown Wizard which are specific to your system. 2. Initiate transfer to static bypass by tapping the Transfer Load to static bypass button on the display interface. In systems with kirk-keys, the key is released from the solenoid key release unit in the System Bypass Cabinet. If the UPS system does not transfer to requested static bypass, go to Status > Active Alarms to see if there are active alarms that prevent the UPS system from transferring to static bypass. 3. In systems with kirk-keys, insert the key in the lock on the maintenance bypass breaker MBB and turn to unlock. 4. Close the maintenance bypass breaker MBB in the System Bypass Cabinet. In systems with kirk-keys, the key is held in the lock. 5. Open the system isolation breaker SIB. 6. In systems with kirk-keys, turn the key in the lock on the system isolation breaker SIB to lock open. The key is released. 7. In systems with kirk-keys, insert the key in the solenoid key release unit. 8. Perform the following steps for each UPS unit in the parallel system: a. Open the unit output breaker UOB. b. Initiate transfer to forced static bypass by tapping the Inverter OFF button on the front of the UPS system. c. Open the static switch input breaker SSIB on the front of the I/O cabinet. d. Open the battery breakers in your specific battery solution. e. Open the unit input breaker UIB on the front of the I/O cabinet A 001

39 Operation kva 480 V, kva 400 V Start Up and Add UPS to a Running Parallel System Use this procedure to start up a UPS and add it to a running parallel system. NOTE: Only operate a breaker when the associated breaker LED is green. 1. Close the unit input breaker UIB on the front of the I/O cabinet. This will power up the display interface after approximately 30 seconds. 2. From the home screen on the display, select Control > Startup Wizard. Select Startup UPS into a parallel system and follow the steps which appear on the screen. NOTE: The following is a generic startup procedure. Always follow the steps of the Startup Wizard which are specific to your system. 3. Close the static switch input breaker SSIB on the front of the I/O cabinet. 4. Close the battery breakers in your specific battery solution. 5. Close the unit output breaker UOB. 6. Turn the inverter on by tapping the Inverter ON button on the front of the UPS A

40 kva 480 V, kva 400 V Operation Isolate this Single UPS from the Parallel System Use this procedure to shut down one UPS in a running parallel system. NOTE: Before initiating this procedure, ensure that the remaining UPS units can supply the load. NOTE: Only operate a breaker when the associated breaker LED is green. 1. From the home screen on the display, select Control > Shutdown Wizard. Select Shut down UPS in a parallel system and follow the steps which appear on the screen. NOTE: The following is a generic shutdown procedure. Always follow the steps of the Shutdown Wizard which are specific to your system. 2. Turn off the UPS by pressing the Inverter OFF key on the front of the UPS. 3. Open the unit output breaker UOB. 4. Open the static switch input breaker SSIB on the front of the I/O cabinet. 5. Open the battery breakers in your specific battery solution. 6. Open the unit input breaker UIB on the front of the I/O cabinet A 001

41 Operation kva 480 V, kva 400 V Transfer UPS from Normal to Requested Static Bypass Operation 1. From the home screen on the display select Control > Operational Mode. 2. Press the Transfer to Requested Static Bypass button. NOTE: If the conditions for performing a transfer is not met, the button will be grayed out 3. Verify that the status below the button changes to Requested Static Bypass. Transfer UPS from Requested Static Bypass Operation to Normal Operation 1. From the home screen on the display select Control > Operational Mode. 2. Press the Transfer to Inverter Operation button. NOTE: If the conditions for performing a transfer is not met, the button will be grayed out 3. Verify that the status below the button changes to Normal. Start a Boost Charge of the Batteries Boost charge gives the possibility of a doing a fast recharge of a discharged battery A

42 kva 480 V, kva 400 V Operation NOTE: Boost charge must be enabled by Schneider Electric during start-up for this option to be available. 1. From the home screen on the display select Control > Charger Mode. 2. Select Boost Charge to initiate a single boost charge of the batteries. The UPS system starts boost charging the batteries. To stop the boost charge and go back to float charge, select Float Charge. Access a Configured Network Management Interface The below procedure describes how to access the network management interface from a web interface. It is also possible to use the following interfaces: Telnet and SSH SNMP FTP SCP NOTE: Ensure that only one network management interface in the entire system is set to synchronize time. Use Microsoft Internet Explorer 7.x or higher on Windows operating systems only or Mozilla Firefox or higher on all operating systems to access the web interface of the network management interface. Other commonly available browsers may work but have not been fully tested. You can use either of the following protocols when you use the web interface: The HTTP protocol (enabled by default), which provides authentication by user name and Pin but no encryption. The HTTPS protocol, which provides extra security through Secure Socket Layer (SSL); encrypts user names, Pin, and data being transmitted; and authenticates Network Management Cards by means of digital certificates. 1. Access the network management interface by its IP address (or its DNS name, if a DNS name is configured). 2. Enter the user name and password. 3. To enable or disable the HTTP or HTTPS protocol, use the Network menu on the Administration tab, and select the Access option under the Web heading on the left navigation menu A 001

43 Maintenance Maintenance kva 480 V, kva 400 V User-Replaceable Parts Part Filter Kit (GVMDFW-KIT) Replacement Procedure Replace the Top Filter in the Power Section, page 39 Replace the Three Bottom Filters in the Power Section, page 40 Replace the Top Filter in the Power Section Rear View of Power Cabinet Front Door 1. Open the front door of the power cabinet. 2. Turn the filter locks to release the filter. 3. Lift up the filter. 4. Take the replacement filter from the installation kit and install the new filter. 5. Turn the filter locks to secure the filter A

Galaxy VX. UPS System Operation 02/

Galaxy VX. UPS System Operation 02/ Galaxy VX Operation 02/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the

More information

Galaxy Shore Connection 500 kva. Operation 04/

Galaxy Shore Connection 500 kva. Operation 04/ Galaxy 7000 Shore Connection 500 kva Operation 04/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Symmetra MW kw 380/400/480 V Operation. UPS System with External Bypass 01/

Symmetra MW kw 380/400/480 V Operation. UPS System with External Bypass 01/ Symmetra MW 800 1600 kw 380/400/480 V Operation UPS System with External Bypass 01/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider

More information

Symmetra PX. 250/500 kw 400/480 V Single and Parallel Operation 10/

Symmetra PX. 250/500 kw 400/480 V Single and Parallel Operation 10/ Symmetra PX 250/500 kw 400/480 V Single and Parallel Operation 10/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

TeSys Programmer. Firmware Update Utility for LTMR & LTMCU User Manual. January 2017

TeSys Programmer. Firmware Update Utility for LTMR & LTMCU User Manual. January 2017 TeSys Programmer Firmware Update Utility for LTMR & LTMCU User Manual January 2017 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016.

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016. Galaxy VM System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric

More information

StruxureWare. Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN /2017

StruxureWare. Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN /2017 StruxureWare Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN52-0413-00 03/2017 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install, operate, service

More information

PowerLogic TM Series E4800 Multi-Circuit Meters. Configuration Guide

PowerLogic TM Series E4800 Multi-Circuit Meters. Configuration Guide PowerLogic TM Series E4800 Multi-Circuit Meters Configuration Guide PowerLogic TM E4800 Series 930-112-01 02/2009 Hazard Categories and Special Symbols Read these instructions carefully and look at the

More information

Galaxy VM. 160/200 kva Parallel capable up to 800 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity

Galaxy VM. 160/200 kva Parallel capable up to 800 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity Galaxy VM 160/200 kva Parallel capable up to 800 kva Three-phase power protection Galaxy VM trusted partner for your business continuity Highly efficient, easy-to-deploy, three-phase power protection that

More information

PowerLogic ION7550 RTU option

PowerLogic ION7550 RTU option 70052-0213-02 PRODUCT OPTION 01/2011 PowerLogic ION7550 RTU option The PowerLogic ION7550 Remote Terminal Unit (RTU) option is designed for data acquisition from WAGES (water, air, gas, electricity, steam)

More information

Dell Network Management Card. User's Guide. w w w. d e l l. c o m s u p p o r t. d e l l. c o m

Dell Network Management Card. User's Guide. w w w. d e l l. c o m s u p p o r t. d e l l. c o m Dell Network Management Card User's Guide w w w. d e l l. c o m s u p p o r t. d e l l. c o m Notes and Warnings NOTE: A NOTE indicates important information that helps you make better use of your software.

More information

Multi-Loader. User manual 06/ BBV48778

Multi-Loader. User manual 06/ BBV48778 Multi-Loader User manual 06/2009 BBV48778 www.schneider-electric.com Contents Important information 4 Before you begin 5 Documentation structure 6 Setup procedure 7 Introduction 8 Receipt of the Multi-Loader

More information

Modbus Register Map: Galaxy 300

Modbus Register Map: Galaxy 300 Modbus Map: Galaxy 300 Notes: 1. 16-bit are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word in in n+1 n+1 (i.e. (i.e.

More information

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

StruxureWare Power Monitoring Expert 8.0 Data Center Edition StruxureWare Power Monitoring Expert 8.0 Data Center Edition Breaker Performance Guide 7EN02-0367-01 06/2015 Safety information Important information Read these instructions carefully and look at the

More information

Conext CL-60 Inverter Firmware Upgrade Process

Conext CL-60 Inverter Firmware Upgrade Process Conext CL-60 Inverter Firmware Upgrade Process http://solar.schneider-electric.com 976-0380-01-01/B August 2017 Application Note EXCLUSION FOR DOCUMENTATION UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER

More information

Smart Mode Measurements

Smart Mode Measurements Smart Mode Measurements Technical Reference for Maintenance PME 7.2.3 V1.0 Safety Information Important Information Read these instructions carefully before trying to install, configure, or operate this

More information

MGE Galaxy kva 208V. Operation

MGE Galaxy kva 208V. Operation MGE Galaxy 4000 40 75 kva 208V Operation Table of Contents About This Manual... 1 Companion Manuals... 1 Find Updates to this Manual... 1 Overview... 2 Operator Interface Keys and Indicators... 2 LED

More information

PowerLogic TM Series EM4800 Multi-Circuit Meters. Configuration Guide

PowerLogic TM Series EM4800 Multi-Circuit Meters. Configuration Guide PowerLogic TM Series EM4800 Multi-Circuit Meters Configuration Guide PowerLogic TM EM4800 Series 930-112-01-B.00 01/2011 Hazard Categories and Special Symbols Read these instructions carefully and look

More information

Operation. Symmetra MW II. Parallel System with Internal Bypass Static Switch. Normal Normal. UPS Summary. X405 UPS Summary.

Operation. Symmetra MW II. Parallel System with Internal Bypass Static Switch. Normal Normal. UPS Summary. X405 UPS Summary. X008B X010 X007 X021 X022 X012 X008A X014A X011 X405 X013 X017 X014B UPS Summary UPS Summary ~ ~ ~ ~ Normal Normal Normal Normal Operation Symmetra MW II Parallel System with Internal Bypass Static Switch

More information

MultiTech Router Commissioning for Com X 200/210/510

MultiTech Router Commissioning for Com X 200/210/510 Knowledge Base 7EN42-0166 05/2017 MultiTech Router Commissioning for Com X 200/210/510 This document describes installation recommendations and how to commission a MultiTech rcell Series router for use

More information

Integrate APC Smart UPS

Integrate APC Smart UPS Publication Date: November 18, 2016 Abstract This guide provides instructions to configure APC Smart-UPS to send the syslog events to EventTracker. Scope The configurations detailed in this guide are consistent

More information

Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)

Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL

More information

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters 976-0312-01-01 Revision A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND

More information

PowerPak Power Distribution Unit

PowerPak Power Distribution Unit WaveStar PowerPak Power Distribution Unit Permissive Signals for Manual Dual Redundant System Ctrl Nr: DOC15029 Revision: 002 PowerPak Manual Dual Redundant PDU Thank you for your recent purchase of a

More information

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation

More information

SmartOnline 40kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America

SmartOnline 40kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America SmartOnline 40kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America MODEL NUMBER: SU40K Description Tripp Lite's SU40K (40kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

StruxureWare Power Monitoring 7.0

StruxureWare Power Monitoring 7.0 StruxureWare Power Monitoring 7.0 OPC Server Assistant 7EN02-0309-00 02/2012 Contents Safety information 5 Introduction 7 Scope 7 Optional OPC Server License 8 OPC Server Type 8 OPC Server Support 9 Creating/Updating

More information

Galaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups

Galaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups Galaxy VX Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 to 1500

More information

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence.

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence. 29-30 Brunel Road, Churchfields Industrial Estate, St. Leonards-on-Sea East Sussex. TN38 9RT. United Kingdom Sales & Service : 01424 853 013 All Other Departments : 01424 853 464 Fax : 01424 852 268 magnuspower.sales@akersolutions.com

More information

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application MUST900 Modular UPS 30-300 kva modular UPS - up to 900 Datacenter & servers Internet centers Local Area Networks (LAN) Telecommunication devices Emergency application Smart Energy Solutions HOT SWAP 0.9

More information

Table Of Contents. 1. Introduction... 1

Table Of Contents. 1. Introduction... 1 User Manual Table of Content Table Of Contents 1. Introduction... 1 1.1 Brief Introduction to Web Interfaces... 1 1.2 How to Log In... 1 1.3 General Setting... 2 1.3.1 Date and Time Setting... 2 1.3.2

More information

Acti 9 Communication System

Acti 9 Communication System Acti 9 Communication System Diagnostics User Manual 05/2012 DOCA0042EN-00 www.schneider-electric.com This document contains general descriptions and/or general technical specifications of the products

More information

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial SmartOnline 100-127V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial MODEL NUMBER: SU3000RTXLCD3U Description Tripp Lite Smart Online UPS systems

More information

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial SmartOnline 100-127V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial MODEL NUMBER: SU3000RTXLCD2U Description Tripp Lite Smart Online UPS systems

More information

Galaxy VM. Three-phase power protection. Galaxy VM trusted partner for your business continuity

Galaxy VM. Three-phase power protection. Galaxy VM trusted partner for your business continuity Galaxy VM Three-phase power protection Galaxy VM trusted partner for your business continuity Highly efficient, easy-to-deploy, three-phase power protection that seamlessly integrates into the electrical,

More information

User Manual. Modular Online UPS. For 30KW Power Module

User Manual. Modular Online UPS. For 30KW Power Module User Manual Modular Online UPS For 30KW Power Module Uninterruptible Power Supply System Version: 4.3 Table of Contents 1. Safety... 1 1.1 Important Safety Instructions... 1 1.2 EMC... 1 1.3 Installation

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SVT30KX Highlights On-line double-conversion topology, VFI operation

More information

M90 & M90L Modular Online Three-Phase UPS

M90 & M90L Modular Online Three-Phase UPS M90 & M90L Modular Online Three-Phase UPS 15kVA, 20kVA, 30kVA, 40kVA, 45kVA, 60kVA Models User & Installation Manual www.xpcc.com 2017. All rights reserved. (Rev 3/16/17) Table of Contents Safety...4 Important

More information

Installing and Configuring Rialto Analytic Appliances

Installing and Configuring Rialto Analytic Appliances Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation

More information

SmartOnline 120V 1.5kVA 1.2kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial

SmartOnline 120V 1.5kVA 1.2kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial SmartOnline 120V 1.5kVA 1.2kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial MODEL NUMBER: SU1500RTXL2UN Highlights 1500VA / 1.5kVA / 1200

More information

SmartOnline 277/480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double- Conversion UPS for North America

SmartOnline 277/480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double- Conversion UPS for North America SmartOnline 277/480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double- Conversion UPS for North America MODEL NUMBER: SU80KTV Highlights 80,000 VA (80kVA) tower UPS with 4 hot-swappable power

More information

Contents 1 Warnings, Cautions, and Notes Description Features... 1

Contents 1 Warnings, Cautions, and Notes Description Features... 1 EnCell Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 1 3 Features... 1 3.1 STANDARD FEATURES... 1 3.2 FRONT PANEL FEATURES... 2 3.2.1 Display... 2 3.2.2 OK LED... 2 3.2.3 FAULT LED...

More information

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

More information

User s Manual Type DTWG Web Server Version 1.1

User s Manual Type DTWG Web Server Version 1.1 User s Manual Type DTWG Web Server Version 1.1 Russelectric Inc. South Shore Park, Hingham, Massachusetts 02043 Service 800 654-3020 www.russelectric.com 90E1730002 rev. A03 Table of Contents SECTION

More information

RGM180 Display Series

RGM180 Display Series Quick Start Guide RGM180 Display Series BG0509 REV.A2 RGM180 QUICKSTART LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or

More information

Generator Performance Guide 7EN /2015

Generator Performance Guide 7EN /2015 Generator Performance Guide 7EN02-0368-00 05/2015 Safety information Important information Read these instructions carefully and look at the equipment to become familiar with the device before trying

More information

Postfach 2327, Offenburg * Helmholtzstr. 13, Offenburg. Technical Data. Model protecto ER

Postfach 2327, Offenburg * Helmholtzstr. 13, Offenburg. Technical Data. Model protecto ER On-line UPS-system according to DIN EN 62040-3 (VFI-SS-111) with sinus soidal output voltage in each operation mode, RS232 interface and Shutdown-Software for Windows NT/2000/XP/2003/Vista, Novell and

More information

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit Important Safety Messages SAVE THESE INSTRUCTIONS - This section contains important instructions that should be followed during installation

More information

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...

More information

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Instruction Bulletin 30072-452-48 Retain for future use. 30072-452-48 Altivar 61/71 Heatsink Fan Kits VZ3V1212 and VZ3V1216

More information

ALL PSU Ltd ROTATION+ 6kVA - 10kVA PARALLEL ON LINE DOUBLE CONVERSION

ALL PSU Ltd ROTATION+ 6kVA - 10kVA PARALLEL ON LINE DOUBLE CONVERSION ALL PSU Ltd Unit D6 Laser Quay, Culpeper Close Medway City Estate, Rochester, Kent, ME2 4HU Phone: 01634-725527 Fax: 01634-739111 E-mail: sales@allpsu.co.uk Web: www.allpsu.co.uk ROTATION+ 6kVA - 10kVA

More information

SmartOnline SVX Series 90kVA 400/230V 50/60Hz Modular Scalable 3-Phase On-Line Double- Conversion Medium-Frame UPS System, 5 Battery Modules

SmartOnline SVX Series 90kVA 400/230V 50/60Hz Modular Scalable 3-Phase On-Line Double- Conversion Medium-Frame UPS System, 5 Battery Modules SmartOnline SVX Series 90kVA 400/230V 50/60Hz Modular Scalable 3-Phase On-Line Double- Conversion Medium-Frame UPS System, 5 Battery Modules MODEL NUMBER: SVX90KM3P5B Highlights 90kVA/90kW Modular, Scalable,

More information

USER MANUAL 2012 V1.1

USER MANUAL 2012 V1.1 SMART MINI POWER SDM630 USER MANUAL 2012 V1.1-1 - Installation and Operation Instructions Important Safety Information is contained in the Maintenance section. Familiarise yourself with this information

More information

THOR Modular. Modular UPS system. Online double-conversion Scalable Decentralized Parallel. Modular. 10, 20, 30, 40kVA modules kVA systems

THOR Modular. Modular UPS system. Online double-conversion Scalable Decentralized Parallel. Modular. 10, 20, 30, 40kVA modules kVA systems Power Supplies Modular THOR Modular Modular UPS system Online double-conversion Scalable Decentralized Parallel Modular 10, 20, 30, 40kVA modules 10-520kVA systems Power factor 1.0 at 10/20kVA/kW modules

More information

SmartOnline SV Series 40kVA Medium-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, 2 Battery Modules

SmartOnline SV Series 40kVA Medium-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, 2 Battery Modules SmartOnline SV Series 40kVA Medium-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, 2 Battery Modules MODEL NUMBER: SV40KM2P2B Highlights Scalable capacity up to

More information

SmartOnline SV Series 20kVA Small-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, No SVBM Battery Module

SmartOnline SV Series 20kVA Small-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, No SVBM Battery Module SmartOnline SV Series 20kVA Small-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, No SVBM Battery Module MODEL NUMBER: SV20KS1P0B Highlights Scalable capacity up

More information

Modbus Register Map: Galaxy 5000 & Galaxy 5500

Modbus Register Map: Galaxy 5000 & Galaxy 5500 Modbus Map: Galaxy 5000 & Galaxy 5500 Notes: 1. 16-bit registers are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word

More information

SmartOnline 120V 3kVA 2.7kW Double- Conversion UPS, 3U Rack/Tower, Extended Run, WEBCARDLX Network Interface, LCD, USB, DB9

SmartOnline 120V 3kVA 2.7kW Double- Conversion UPS, 3U Rack/Tower, Extended Run, WEBCARDLX Network Interface, LCD, USB, DB9 SmartOnline 120V 3kVA 2.7kW Double- Conversion UPS, 3U Rack/Tower, Extended Run, WEBCARDLX Network Interface, LCD, USB, DB9 MODEL NUMBER: SU3000RTXLCD3N Highlights Zero transfer time suitable for advanced

More information

SmartOnline SVX Series 120kVA Modular, Scalable 3-Phase, On-line Double-Conversion 400/230V 50/60Hz UPS System

SmartOnline SVX Series 120kVA Modular, Scalable 3-Phase, On-line Double-Conversion 400/230V 50/60Hz UPS System SmartOnline SVX Series 120kVA Modular, Scalable 3-Phase, On-line Double-Conversion 400/230V 50/60Hz UPS System MODEL NUMBER: SVX120KL Highlights 120kVA / 120kW modular, scalable, 3-phase, Large-Frame tower

More information

Galaxy VX. From 500 kw to1500 kw N+1 Parallel solutions up to 4000 kw 480 V. schneider-electric.com

Galaxy VX. From 500 kw to1500 kw N+1 Parallel solutions up to 4000 kw 480 V. schneider-electric.com Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 kw to1500 kw N+1

More information

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer K01-SNMP004-00 TABLE OF CONTENTS INTRODUCTION... 1 INSTALLATION GUIDE...

More information

Schneider Electric Floating License Manager

Schneider Electric Floating License Manager Schneider Electric Floating License Manager EIO0000001078 11/2012 Schneider Electric Floating License Manager User Manual 12/2012 EIO0000001078.01 www.schneider-electric.com The information provided in

More information

StruxureWare Power Monitoring Expert for Healthcare 7.2

StruxureWare Power Monitoring Expert for Healthcare 7.2 StruxureWare Power Monitoring Expert for Healthcare 7.2 Commissioning Guide 7EN42-0070-04 09/2013 Safety Information Read these instructions carefully and look at the equipment to become familiar with

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

Product Specifications

Product Specifications Product Specifications Models: USC-10001, USC-10002 USC-20001, USC-20002 USC-30001, USC-30002 Guide Specification for UniStar C Series Rack/Universal 1, 2, 3Kva Single-Phase, On-Line Double Conversoin

More information

SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial

SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial MODEL NUMBER: SU3000RTXL3UHV Highlights 3000VA / 3kVA / 2400 watt on-line double-conversion

More information

DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents

DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B 1.0 Introduction DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in

More information

Installation Instructions

Installation Instructions Installation Instructions Variable Frequency Drive (VFD) 7 ½ - 25 Ton Units with 2 Wire Control WARNING UNINTENDED EQUIPMENT OPERATION Modifying or changing parame eters whose function is not described

More information

SmartOnline 80kVA Modular 3-Phase UPS System, On-line Double-Conversion International UPS (not expandable to 120kVA)

SmartOnline 80kVA Modular 3-Phase UPS System, On-line Double-Conversion International UPS (not expandable to 120kVA) SmartOnline 80kVA Modular 3-Phase UPS System, On-line Double-Conversion International UPS (not expandable to 120kVA) MODEL NUMBER: SU80KX Description Tripp Lite's SU80KX (80kVA) SmartOnline Modular 3-Phase

More information

Socomec Netys PR RT U P S TOWER / RACK MOUNT

Socomec Netys PR RT U P S TOWER / RACK MOUNT Socomec Netys PR RT Ideal solution for protecting small servers, networking devices and peripherals. Assures service continuity to critical applications. Designed for professional applications: the sinevawe

More information

SmartOnline 10kVA On-Line, Double-Conversion UPS, 6U Rack/Tower, 3-Phase input, 1-Phase output

SmartOnline 10kVA On-Line, Double-Conversion UPS, 6U Rack/Tower, 3-Phase input, 1-Phase output SmartOnline 10kVA On-Line, Double-Conversion UPS, 6U Rack/Tower, 3-Phase input, 1-Phase output MODEL NUMBER: SU10KRT3/1X Highlights 10,000VA (10kVA) SmartOnline 6U rack/tower UPS 3 phase, 4-Wire + Ground,

More information

EcoStruxure Power Commission Installation Guide

EcoStruxure Power Commission Installation Guide EcoStruxure Power Commission DOCA0134EN 03/2019 EcoStruxure Power Commission Installation Guide 03/2019 DOCA0134EN-04 www.schneider-electric.com The information provided in this documentation contains

More information

SmartOnline 240 & 120V 20kVA 18kW Double- Conversion UPS in 25U enclosure, Pre-installed Network Card, USB, DB9, Bypass, Hardwire

SmartOnline 240 & 120V 20kVA 18kW Double- Conversion UPS in 25U enclosure, Pre-installed Network Card, USB, DB9, Bypass, Hardwire SmartOnline 240 & 120V 20kVA 18kW Double- Conversion UPS in 25U enclosure, Pre-installed Network Card, USB, DB9, Bypass, Hardwire MODEL NUMBER: SU20KRTHWTFASSM Highlights 20kVA / 20,000VA / 18,000W on-line

More information

Conext CL-60 EasyConfig Tool

Conext CL-60 EasyConfig Tool Conext CL-60 EasyConfig Tool Owner s Guide 975-0773-01-01 Revision B 08-2017 http://solar.schneider-electric.com Copyright 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider

More information

SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial

SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output 100/110/120V

More information

Square D Clipsal Pascal Automation Controller

Square D Clipsal Pascal Automation Controller Square D Clipsal Pascal Automation Controller SLC5500PACA For Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal Pascal Automation Controller 63249-420-258A2 Instruction

More information

Pulsar EXtreme 2000/3000 VA

Pulsar EXtreme 2000/3000 VA www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 2000/3000 VA Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 51033211EN/AC - Page 1 Introduction Thank you for selecting

More information

SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, WEBCARDLX Network Interface, LCD, USB, 8 Outlets

SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, WEBCARDLX Network Interface, LCD, USB, 8 Outlets SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, WEBCARDLX Network Interface, LCD, USB, 8 Outlets MODEL NUMBER: SMART1500RM2UN Highlights Corrects under- and overvoltages from

More information

EATON 5S 850/1200/1600

EATON 5S 850/1200/1600 www.eaton.com EATON 5S 850/1200/1600 Installation and user manual Packaging EATON 5S 1 2 3 5 Caution! l Before installing the Eaton 5S, read the booklet 3 containing the safety instructions to be respected.

More information

Ethernet Modbus X80 Gateway Device Type Manager

Ethernet Modbus X80 Gateway Device Type Manager Ethernet Modbus X80 Gateway Device Type Manager EIO0000001315 10/2012 Ethernet Modbus X80 Gateway Device Type Manager User Manual 10/2012 EIO0000001315.00 www.schneider-electric.com The information provided

More information

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3 Overview Safety notes 1 SITOP power supply Manual Description, device design, dimension drawing 2 Mounting/removal 3 Mounting position, mounting clearances 4 Installation 5 Technical data 6 Safety, approvals,

More information

Switched Rack Power Distribution Unit

Switched Rack Power Distribution Unit Switched Rack Power Distribution Unit AS-216-520-30A-L530 Installation and Quick Start Contents Product Description and Inventory...................... 1 AS-216-520-30A-L530....................... 1 Additional

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

USER MANUAL. PowerFrame TM Personal. UPS Monitoring Software

USER MANUAL. PowerFrame TM Personal.   UPS Monitoring Software USER MANUAL PowerFrame TM Personal UPS Monitoring Software www.bxterra.com 1 TABLE OF CONTENTS Introduction... Structure... Applications... Features... System Requirements... Supported Operating Systems...

More information

HPE UPS Network Module User Guide

HPE UPS Network Module User Guide HPE UPS Network Module User Guide Abstract This document includes installation, configuration, and operation information for the HPE UPS Network Module. This document is for the person who installs and

More information

Galaxy VM kva 480 V UPS. Installation 02/

Galaxy VM kva 480 V UPS. Installation 02/ Galaxy VM 180 225 kva 480 V UPS Installation 02/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Acuvim II Series Power Meter SNMP Protocol User's Manual

Acuvim II Series Power Meter SNMP Protocol User's Manual Acuvim II Series Power Meter SNMP Protocol User's Manual Copyright 2018 V2.00 This manual may not be altered or reproduced in whole or in part by any means without the expressed written consent of Accuenergy.

More information

SIMATIC NET. Industrial Ethernet Security SCALANCE S615 Getting Started. Preface. Connecting SCALANCE S615 to the WAN 1

SIMATIC NET. Industrial Ethernet Security SCALANCE S615 Getting Started. Preface. Connecting SCALANCE S615 to the WAN 1 Preface Connecting SCALANCE S615 to the WAN 1 SIMATIC NET VPN tunnel between SCALANCE S615 and 2 SINEMA RC Server Industrial Ethernet Security Getting Started 07/2017 C79000-G8976-C390-02 Legal information

More information

2 Upgrading the ComBox Firmware

2 Upgrading the ComBox Firmware Conext Series of Devices solar.schneider-electric.com Firmware Update Guide 1 2 Upgrading the ComBox Firmware HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH This Firmware Update Guide is in addition

More information

Electrical network protection Sepam series 20 Sepam series 40 Quick start

Electrical network protection Sepam series 20 Sepam series 40 Quick start 03146790FE+01+NP00000000 Electrical network protection Sepam series 20 Sepam series 40 Quick start PE50465 Storage Sepam may be stored in its original packaging in a closed sheltered location: b ambient

More information

Power Management Module

Power Management Module Power Management Module 30 300 kva Installation and Operation 10/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

MUST 900 UPS. Finally the benefits of Modular ups are for all. 3 Phase Modular. Hot swappable, scalable 30kVA to 900kVA

MUST 900 UPS. Finally the benefits of Modular ups are for all. 3 Phase Modular. Hot swappable, scalable 30kVA to 900kVA MUST 900 3 Phase Modular UPS Hot swappable, scalable 30kVA to 900kVA Finally the benefits of Modular ups are for all MUST 900 The MUST 900 series is an uninteruptible power supply, three phase input/output,

More information

Remote Management Card

Remote Management Card Remote Management Card RMCARD205 / RMCARD305 User s Manual Rev. 01 The Remote Management Card allows a UPS system and environmental sensor to be managed, monitored, and configured. 2015, CyberPower Systems,

More information

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance

More information

Modular, scalable, high-efficiency power protection for data centers

Modular, scalable, high-efficiency power protection for data centers Scalable to 20 kw Modular, scalable, high-efficiency power protection for data centers The Symmetra TM PX 20 kw is a world-class, high-efficiency, ENERGY STAR qualified power protection system designed

More information

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter Install Guide Revision C (12/18) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Revision C (12/18) Turn off all power supplying equipment

More information