1 HONEYWELL ECEL 5000 OPEN SYSTEM GENERAL INFORMATION LonWorks service LED LonWorks service button terminal assignment label BEFORE INSTALLATION IMPORTANT INSTALLATION INSTRUCTIONS It is recommended that the controller be kept at room temperature for at least hours before applying power; this is to allow the evaporation of any condensation resulting from low shipping / storage temperatures. DI 2 DI 3 AI LON 1 LON 2 DI 1 AI 1 AI 2 R123 COM Rel 1 NO Rel 2 NO Rel 3 NO V 0 V ~ 0441 US requirement, only: This device must be installed in a UL-listed enclosure offering adequate space to maintain the segregation of line voltage field wiring and Class 2 field wiring. CAUTION To avoid electrical shock or equipment damage, you must switch OFF the power supply before attaching / removing connections to/from any terminals. removable LonWorks terminal plug input terminals relay output terminals removable power supply terminal plug Fig. 1. Top view (optional terminal cover removed) fuse MOUNTING Both models have the same dimensions (W x L x H = 110 x 180 x 60 mm) (see Fig. 2) and conform to IP20 (without optional terminal protection cover) or IP30 (with optional terminal protection cover; width is then 130 mm). The is equipped with: three relays, three digital inputs, and three analog inputs, which may be used as slow digital inputs or as NTC20k temperature sensor inputs. See also Table 1 on page 2 for a complete overview of terminals and their functions. The two models of the Excel Smart I/O differ only in their power supply: FCL2A1: power supply FCL3A1: power supply terminal protection cover (optional) 130 Fig. 2. dimensions (in mm) The is suitable for mounting on a standard rail (DIN EN x 7,5), on walls/ceilings, as well as for installation in wiring cabinets or fuse boxes. U.S. Registered Trademark Copyright 2011 Honeywell Inc. All Rights Reserved
2 ECEL SMART I/O COMPACT INSTALLATION INSTRUCTIONS DIN Rail Mounting/Dismounting (oval hole) (oval hole) eyelets for cable binders eyelet for eyelets for cable binder cable binders stirrup; pull to dismount from rail Fig. 3. Housing base (view from below) (round hole) (oval hole) The can be mounted onto the DIN rail simply by snapping it into place. It is dismounted by gently pulling the stirrup located in the base of the housing (see Fig. 3). When mounted on a DIN rail, the unit must be secured in place with a stopper to prevent sliding. Wall/Ceiling Mounting/Dismounting The can be mounted on walls or ceilings in any desired orientation. In the case of ceiling mounting, however, it should not be operated at ambient temperatures exceeding 50 C. The unit is mounted by inserting 3.5-mm dowel screws through the corresponding s. protection cover's cut-out tabs and snap it (by hand) into place on the housing. To remove the cover, place a screwdriver in the leverage slot and pry it loose. Terminal Assignment The features two rows of terminal blocks located on one side for the connection of cables to the inputs and relay outputs as well as for connecting the removable power supply terminal plug and removable LONWORKS terminal plug. NOTE: All relay and power supply terminal blocks are orange-colored. NOTE: According to VDE guidelines, it is not allowed to mix low-voltage and high-voltage signals on the relays. The is equipped with an adhesive terminal assignment label on the top of the housing (see Fig. 1 on page 1). Table 1. Overview of terminals and functions terminal # 1+2 function removable LONWORKS connection plug FCL2A1 model FCL3A1 3 digital input #1 4 analog input #1 5 analog input #2 6, 7, 8, 9 terminals serving all signals 10 digital input #2 11 digital input #3 12 analog input #3 154 mm not used round hole (diameter: 4 mm) relay common for relays 1, 2, and 3 relay #1, normallyopen contact oval hole (4x7 mm) 100 mm not used relay #2, normallyopen contact relay #3, normallyopen contact Fig. 4. Drilling template (view from above) removable power supply plug When equipped with the optional terminal protection cover (see section "Terminal Protection Cover" on page 6), the conforms to IP30. After mounting the onto the wall or ceiling, provide for cable access by snipping out the terminal See also section Configuring the Inputs and Outputs on page 4. 2
3 ECEL SMART I/O COMPACT INSTALLATION INSTRUCTIONS Power Supply General Information NOTE: All wiring must comply with applicable electrical codes and ordinances. Refer to job or manufacturers drawings for details. Local wiring guidelines (e.g. VDE 0100) may take precedence over recommendations provided in these installation instructions. NOTE: To comply with CE requirements, devices having a voltage of or Vdc but lacking a supply cord, plug, or other means for disconnecting from the power supply must have the means of disconnection incorporated in the fixed wiring. This means of disconnection must have a contact separation of at least 3 mm at all poles. Use a minimum of 18 AWG (1.0 mm 2 ) and a maximum of 14 AWG (2.5 mm 2 ) for all power wiring. Power is supplied via a removable terminal plug (attached to terminals 25 and 26) permitting individual Excel Smart I/O Compacts to be disconnected from the power supply without disturbing the operation of other devices powered by the same source. See Fig. 5. FCL2A1 device 3 device 2 FCL3A1 FCL3A1 with Power Supply Power supply: [±20%], 50 or 60 Hz, connected. Power consumption: < 3 VA (device unloaded) LonWorks Communications General Information The is equipped with a freetopology transceiver for communication on LONWORKS networks. The LONWORKS network is insensitive to polarity, eliminating the possibility of installation errors due to miswiring. Different network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible (see also Excel 50/500 LONWORKS Mechanisms Interface Description, EN0B-0270GE51). Connecting to the LONWORKS Network IMPORTANT Do not bundle wires carrying field device signals or LONWORKS communications together with highvoltage power supply or relay cables. Specifically, maintain a min. separation of 3 inches (76 mm) between such cables. Local wiring codes may take precedence over this recommendation. IMPORTANT Try to avoid installing in areas of high electromagnetic noise (EMI). device 2 device 1 N L (15% / +10%) 50 / 60 Hz device 1 N (+/-20%) L (15% / +10%) 50 / 60 Hz The unit must be wired to the LONWORKS network using level IV 22 AWG (Belden part number 9D220150) or plenum-rated level IV 22 AWG (Belden part number 9H ) nonshielded, twisted-pair, solid-conductor wire. When possible, use Honeywell 111AK3781, AK3782, AK3791, or AK3792 cable (US part numbers). See Excel 50/5000 LONWORKS Mechanisms, EN0B-0270GE51, for details, including maximum lengths. Use wire with a minimum size of 20 AWG (0.5 mm 2 ) and a maximum size of 14 AWG (2.5 mm 2 ). Fig. 5. Connection to power supply D Schönaich Made in Germany Excel Smart I/O Compact D Schönaich Made in Germany Excel Smart I/O Compact NOTE: Do not reverse the polarity of the power connection cables, and avoid ground loops (i.e. avoid connecting one field device to several controllers) as this may result in short circuits damaging your device. FCL2A1 with Power Supply The FCL2A1 with power supply is equipped with a built-in transformer. Power supply: [-15% / +10%], 50/60 Hz). Power consumption: < 6 VA (device unloaded) termination module Fig. 6. Connection to LonWorks network and termination module (here: daisy-chain network configuration) The is connected to the LONWORKS network via a removable terminal plug (attached to terminals 1 and 2) permitting individual s to be connected / disconnected from the LONWORKS network without disturbing the operation of other devices. 3
4 ECEL SMART I/O COMPACT INSTALLATION INSTRUCTIONS Depending upon the chosen network configuration, one or two terminations (see section "LONWORKS Termination" on page 6) may be required. Inputs/Outputs Wiring the Inputs/Outputs Use a minimum size of 20 AWG (0.5 mm 2 ) and a maximum of 14 AWG (2.5 mm 2 ) for all input/output connections. The maximum length of all input/output cables is 400 m. Two wires with a total thickness of 14 AWG can be twisted together and connected using a wire nut (include a pigtail with this wire group and attach the pigtail to the individual terminal block). Deviations from this rule can result in improper electrical contact. Local wiring codes may take precedence over this recommendation. power power Rel 3 Rel 2 Rel 1 R123 AI3 DI3 DI2 AI2 AI1 DI1 LON2 LON1 ON ON ON COM Analog Inputs The is equipped with three analog inputs. The analog inputs may be used as NTC20k temperature sensor inputs or as slow digital inputs. The analog inputs do not support 0 10 V input. software detects inputs as Table 3. Slow digital input characteristics resistive input (dry contact) high/low switching at current out of terminal closed < 200 Ω < 1.5 Vdc < 0.3 ma open > 50 kω > 3.5 Vdc < 0.1 ma Table 4. Accuracy, resolution of inputs (NTC20k sensors) temperature range accuracy resolution -50 to -40 C (-58 to -40 F) 4.11 K 1.42 K -40 to -30 C (-40 to -22 F) 2.12 K 0.77 K -30 to -20 C (-22 to -4 F) 1.39 K 0.44 K -20 to -10 C (-4 to 14 F) 0.65 K 0.27 K ST3 ST2 ST1 COM 3-stage fan N L AI as DI as NTC20kOhm totalizer AI as slow DI Fig. 7. Overview of inputs and outputs Configuring the Inputs and Outputs You can configure the s inputs and outputs using Honeywell's LNS plug-in or CARE. NOTE: The switching logic functionality can be configured using CARE, only. The LNS plug-in does not support the switching logic functionality. DI -10 to 0 C (14 to 32 F) 0.42 K 0.17 K 0 to 10 C (32 to 50 F) 0.27 K 0.12 K 10 to 50 C (50 to 122 F) 0.30 K 0.11 K 50 to 70 C (122 to 158 F) 0.45 K 0.19 K 70 to 90 C (158 to 194 F) 1.17 K 0.35 K 90 to 100 C (194 to 212 F) 1.44 K 0.48 K 100 to 120 C (212 to 8 F) 2.29 K 0.92 K 120 to 150 C (8 to 302 F) 5.11 K 2.3 K Digital Inputs The is equipped with three digital inputs suitable for use as fast digital inputs (static digital inputs or push-buttons for flip-flop) or as totalizer inputs (square waves). software detects inputs as Table 2. Digital input characteristics resistive input (dry contact) voltage input current out of terminal closed < 400 Ω < 0.8 Vdc max. 2.5 ma open > 1.5 kω > 2.0 Vdc ma Totalizer input: digital input #1: up to 20 Hz; reacts on falling edge; digital input #2: up to 5 Hz; configurable (using Honeywell s LNS plug-in) to react on rising or falling edge; digital input #3: up to 5 Hz; configurable (using Honeywell s LNS plug-in) to react on rising or falling edge. For all NTC20k sensor inputs, temperatures of -50 C are interpreted as being due to a sensor break, and temperatures of +150 C are interpreted as being due to a sensor shortcircuit. Relay Outputs The is equipped with three normally-open relay outputs. Current Limitations NOTE: If inductive components are to be connected to the relays and if these relays switch more often than once every two minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN 45014). A min. current of 50 ma is required to ensure a reliable contact. The normally-open contacts are designed for a max. continuous current of 3 A at max. and cos φ = 1. The d.c. characteristic is shown in Fig. 8. 4
5 ECEL SMART I/O COMPACT INSTALLATION INSTRUCTIONS switching voltage (Vdc) ohmic load Table 5. LONWORKS Service LED Behaviors and Meanings LED blinking pattern LED remains OFF after power-up. LED is lit continuously after first power-up. LED flashes at power-up, goes OFF, then is lit continuously. meaning Defective device hardware. Suspect power supply problems, clock problems, or defective Neuron Chip. Defective hardware. Controller lacks application switching current (A) Fig. 8. Relay characteristic Replacing the Fuse NOTE: Before replacing the fuse (see also Fig. 1 on page 1), disconnect the from the power source by detaching the removable terminal plug attached to terminals 25 and 26. CAUTION Depending upon actual wiring, even after you have switched OFF the power supply, the relays may still be under high voltage. Troubleshooting The features a LONWORKS service LED and corresponding LONWORKS service button (see Fig. 1) for commissioning and troubleshooting. When the service button is pressed, the service pin message is broadcast. See Table 5 for a description of the meaning of the various different possible behaviors of the LONWORKS service LED. For more information on standard service LED behavior, refer to Motorola LONWORKS Technology Device Data Manual, page AL-190. Possible Problems and Recommended Actions Check to see if the LONWORKS service LED's behavior is changed when you switch the power OFF/ON. Please contact Honeywell if this does not solve the problem a 6b 6c 6d LED flashes briefly periodically. LED repeatedly blinks ON for 1 s and OFF for 1 s. OFF duration 10 s. Afterwards, the service LED turns ON and remains ON, indicating completion of the blanking process. OFF duration 1 s. Afterwards, the service LED is lit continuously. OFF duration is s, depending on application size and system clock. Afterwards, service LED repeatedly blinks ON for 1 s and OFF for 1 s. OFF duration is indefinite ( s to load internal EEPROM; remains OFF). LED remains OFF after a short ON duration. LED flashes for 1 minute in following pattern: 5x ON/OFF, 5 sec OFF, 5x ON/OFF LED flashes continuously in following pattern: 4x ON/OFF followed by 5 sec pause. Controller is probably experiencing continuous watchdog resets, or external memory or EEPROM is corrupt. Controller is unconfigured but has an application. Using EEBLANK on a Neuron 3150 Chip-based custom node. First power-up with a new PROM on a Neuron 3150 Chip-based customized node. Application-less firmware state exported. First power-up with a new PROM on a Neuron 3150 Chip-based customized node. Unconfigured firmware state exported. First power-up with new PROM on Neuron 3150 Chip-based customized node. Configured firmware state exported. Controller is configured and running normally. Controller has received WINK command from network. Other physical outputs are unaffected. Neuron communication failure or sensor break. 5
6 ECEL SMART I/O COMPACT INSTALLATION INSTRUCTIONS Accessories Terminal Protection Cover Required for wall/ceiling mounting. Set of eight covers. order no.: AL_COV_L LONWORKS Termination One or two LONWORKS terminations are required, depending on the given LonWorks bus layout. See section "Connecting to the LONWORKS Network" on page 3. The following LONWORKS termination module is available: LONWORKS connection / termination module (mountable on DIN rails and in fuse boxes), order no.: AL-Term SHIELD SHIELD 2 6 PLUG-IN JUMPER LON TERMINATION REMOVABLE SCREW-TYPE 3-POLE TERMINAL BLOCK FTT/LPT BUS TOPOLOGY; R: 105 Ohm FTT/LPT FREE TOPOLOGY; R: 52.3 Ohm PARK POSITION; NO TERMINATION FREE TOPOLOGY: 52.3 Ohm BUS TOPOLOGY: 105 Ohm μ 100 μ 52.3 Ohm 105 Ohm 100 μ 100 μ 2 2 Fig. 9. LONWORKS connection and termination module Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Strasse Schönaich / Germany Phone: (49) Fax: (49) Subject to change without notice. Printed in Germany
Excel 10 W7754K,P,Q FAN COIL UNIT CONTROLLERS
HONEYWELL EXCEL 5000 OPEN SYSTEM GENERAL INFORMATION LonWorks service LED LonWorks service button left DIP switch (USED = wall module connected) right DIP switch (USED = terminal 11 enabled) terminal assignment
More informationExcel 10 W7754K,P,Q,R,S,T,V FAN COIL UNIT CONTROLLERS
HONEYWELL EXCEL 5000 OPEN SYSTEM GENERAL INFORMATION LonWorks SERVICE BUTTON LonWorks SERVICE LED LEFT DIP SWITCH (USED = WALL MODULE CONNECTED) RIGHT DIP SWITCH (USED = TERMINAL 11 ENABLED) TERMINAL ASSIGNMENT
More informationExcel Web XL1000B/C TABLE OF CONTENTS HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION INSTRUCTIONS
HONEYWELL EXCEL 5000 OPEN SYSTEM Excel Web XL1000B/C INSTALLATION INSTRUCTIONS TABLE OF CONTENTS Overview of Hardware... 2 Terminal Blocks... LonWorks Interface... Ethernet Interface... RS22C Serial Interface
More informationExcel Web XL1000B/C TABLE OF CONTENTS HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION INSTRUCTIONS
HONEYWELL EXCEL 5000 OPEN SYSTEM Excel Web XL1000B/C INSTALLATION INSTRUCTIONS TABLE OF CONTENTS Overview of Hardware... 2 Terminal Blocks... LonWorks Interface... Ethernet Interface... RS22C Serial Interface
More informationT7560A1036 Digital Wall Module
T7560A1036 Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. T7560A1036
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM FEATURES SPECIFICATION DATA Fully compatible with all current Excel 10 and Excel 20 to 800 controllers. Low power consumption. Integral 20kΩ
More informationExcel Smart I/O Compact XFCL2A1 AND XFCL3A1
GENERAL The Excel Smart I/O Compact is suitable for installation at strategic locations throughout your buildings. It features three digital inputs, three analog inputs, three relay outputs, as well as
More informationC7110C1001A / C7110D1009A WALL MODULES
HONEYWELL EXCEL 5000 OPEN SYSTEM GENERAL The C7110C1001A and C7110D1009A are combined CO2 / temperature wall modules designed for applications in indoor ventilation and air conditioning systems. In conjunction
More informationT7460A,B,C,D,E,F WALL MODULES
T7460A,B,C,D,E,F WALL MODULES HONEYWELL EXCEL 5000 OPEN SYSTEM SPECIFICATION DATA FEATURES Mountable on 2.36 in. (60 mm) wall outlet box or directly on a wall. Models with setpoint adjustment. Models with
More informationN20010, N NON-SPRING RETURN DAMPER ACTUATOR 20/34 Nm (177/300 lb-in) FOR MODULATING CONTROL SPECIFICATIONS GENERAL FEATURES PRODUCT DATA
N21, N341 NON-SPRING RETURN DAMPER ACTUATOR 2/34 Nm (177/3 lb-in) FOR MODULATING CONTROL SPECIFICATIONS Supply voltage Nominal voltage PRODUCT DATA 24 Vac 2%, 5/6 Hz; 24 Vdc -1...+2% 24 Vac, 5/6 Hz; 24
More informationSLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)
SLX Series Document No. 997-1000 Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L) Free Programmable Controllers (SLX-PC-203, SLX-PC-300, SLX-PC-400, SLX-PC-500
More informationDESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications
3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for
More informationN0524/N1024, N POS/N POS
N0/N0, N00-POS/N00-POS NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING / -POSITION CONTROL PRODUCT DATA SPECIFICATIONS Supply voltage N0/N0 Vac/dc -%/+0%, 0/60 Hz N00-POS/N00-POS 0 Vac -%/+0%,
More informationT7460A,B,C,D,E,F WALL MODULES
HEYWELL EXCEL 5 OPEN SYSTEM T746A,B,C,D,E,F WALL MODULES SPECIFICATI DATA FEATURES Mountable on 6 mm wall outlet box or directly on a wall. Models with setpoint adjustment. Models with bypass (override)
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM GENERAL The T7560A,B Digital Wall Modules (DWM) display and provide space temperature,, Occupied/Unoccupied override, and fan mode/speed
More informationN05010/N10010 NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING / 2-POSITION CONTROL SPECIFICATIONS
N/N NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING / -POSITION CONTROL SPECIFICATIONS Supply voltage Nominal voltage PRODUCT DATA Vac/dc -%/+%, /6 Hz Vac/dc, /6 Hz All values
More informationXT-9100 Technical Bulletin
System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX
More informationML7421A,B Electric Linear Valve Actuators
ML7421A,B Electric Linear alve Actuators FEATURES Quick and easy installation No separate linkage required No adjustments Force-limiting end switches Manual operator Synchronous motor Corrosion-resistant
More informationDS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION
DS 10.103A 10/99 MN 500 WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION Order Type: MNN-50-100 MicroNet NCP 500 Controller I/A Series MicroNet 500 Series Controllers
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module INSTALLATION INSTRUCTIONS CAUTION: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation
More informationContent. Product Description
EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product
More informationLTEC Heat Pump DDC Controller
Document No. 09 Rev., May, 00 LTEC Heat Pump DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) HP (Heat Pump) DDC Controller
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationRXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications
s 3 856 Desigo RXC Room controller RXC39.5 Communicating room controller for fan-coil applications The RXC39.5 room controller is used for temperature control in individual rooms. For fan-coil systems
More informationRXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02
s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled
More informationEAGLE Controller. Installation & Commissioning Instructions TABLE OF CONTENTS
EAGLE Controller Installation & Commissioning Instructions TABLE OF CONTENTS Safety Information... 2 General Safety Information... 2 Information as per EN 60730... 2 WEEE Directive... 2 Standards, Approvals,
More informationNEUROLOGIC RESEARCH CORPORATION MODEL 2500
NEUROLOGIC RESEARCH CORPORATION MODEL 2500 NETWORK HUMISTAT Compact, self-contained dehumidifier controller. 0.5 degrees C accuracy typical. RH sensor is digitally calibrated for 2% accuracy. Open communication
More informationFEATURES DESCRIPTION MODEL 110B. Power Supply
FEATURES Extends wiring distance of FT-10 LonWorks Networks. (2) channels using a single Model 110B. Up to 10 channels using (5) Model 110B. Low cost alternative to routers configured as repeaters. Wring
More informationExpansion Module HZS 541-1S
Expansion Module HZS 541-1S 12.10.2015 Page 1 System Description The external HZS 541-1S expansion module provides users of biomass heating systems with additional 230 V AC relay outputs, analog inputs
More informationNon-communicating room controllers
3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For
More informationENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.
TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application
More informationExcel Web II CONTROL SYSTEM
HONEYWELL EXCEL 5000 OPEN SYSTEM Safety Information General Safety Information Information as per EN 60730 WEEE Directive Standards, Approvals, etc. 3rd-Party Software Licenses Excel Web II CONTROL SYSTEM
More informationHoneywell I/O MODULES
Honeywell I/O MODULES HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION AND MISSIONING INSTRUCTIONS CONTENTS Safety Information... 2 General Safety Information... 2 Safety Information as per EN60730-1... 2
More informationIO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs
IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs The IO-DI8-TO8 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 digital inputs,
More informationProduct and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING
Product and Applications Description Note If the application program is not loaded completely by the ETS, you had better interrupt the 24 V voltage supply of the I/O-module during the loading interval.
More informationNon-communicating room controllers
3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,
More informationRXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13
s 3 875 RXB Room controller Communicating room controller for fan-coil applications FC-13 RXB39.1 The RXB39.1 room controller is used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil
More informationRXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station
s 3 836 3836P01 Desigo TRA PL-Link IO Block Use with PXC3 series room automation station RXM39.1 The PL-Link IO Block contains the inputs and outputs controlled by a room automation station via PL-Link.
More informationFLEX Ex Spring Clamp Terminal Base
Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification
More informationNEUROLOGIC RESEARCH CORPORATION MODEL 2150
NEUROLOGIC RESEARCH CORPORATION FOUR DIGITAL INPUT / FOUR DIGITAL OUTPUT NETWORK NODE - Very compact design available in DIN Rail and NEMA 4X enclosures. - LonWorks FTT-10A network interface with all inputs
More informationT775S Series 2000 Expansion Module
T775S Series 000 Expansion Module INSTALLATION INSTRUTIONS PRODUT DESRIPTION The T775S008 Relay Expansion Module is a four relay device for use with the T775L007 and T775P00 Series 000 Electronic Stand-Alone
More informationIO-AO6X I/O Expansion Module 6 Isolated Analog Outputs
IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated
More informationLION System. Product Data. Copyright 2007 Honeywell GmbH All Rights Reserved 3.4
LION System Product Data GENERAL The LION System (consisting of the CLLIONLC01 Controller Module and connected LION Panel Bus or WORKS Bus Input/Output Modules) provides highly cost-effective freely programmable
More informationOperating Instructions VEGAMET 381
Operating Instructions VEGAMET 381 in out Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6 2.1 Authorised personnel...
More informationProduct and functional description
Product and functional description The RS 525/23 Universal Dimmer is a KNX device with one dimmer output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The bus
More informationCTR21, CTR22, CTR23, and CTR24 Wall Modules
CTR21, CTR22, CTR23, and CTR24 Wall Modules FEATURES SPECIFICATION DATA The CTR21, CTR22, CTR23, and CTR24 family of wall modules include: Models with setpoint adjustment. Models with occupied/unoccupied
More informationEAGLEHAWK NX Controller
EAGLEHAWK NX Controller Installation & Commissioning Instructions TABLE OF CONTENTS TABLE OF CONTENTS... 1 Safety Information... 2 General Safety Information... 2 Information as per EN 60730... 2 WEEE
More informationDigital Frequency Divider INSTRUCTION MANUAL CONTENTS. 1. Working Principle Installation Setting Up Technical Data 4.
Digital Frequency Divider INSTRUCTION MANUAL CONTENTS 1. Working Principle 2 2. Installation 2 3. Setting Up 3 4. Technical Data 4 Code: 189/1a 1 WORKING PRINCIPLE The DFD has been designed to generate
More informationExcel 10 Q7750A ZONE MANAGER BEFORE INSTALLATION. Parts Checklist INSTALLATION INSTRUCTIONS
Excel 10 Q7750A ZONE MANAGER BEFORE INSTALLATION These Installation Instructions are applicable for the Q7750A Excel 10 Zone Manager. There are two versions of the Q7750A: 1. 1000-series Twisted Pair Topology
More informationThe Solution. Multi-Input Module IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION
The Solution Multi-Input Module INSTALLATION INSTRUCTIONS Model: MIM-62 IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION MIM-62 connects up to 6 monitored entrapment protection
More informationSolid-state Timer H3YN
Solid-state Timer H3YN Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple
More informationRXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02
s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled
More informationProduct and functional description
Product and functional description The RS 520/23 shutter / blind actuator is a KNX device with one relay output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The
More informationIQ-SBS LCU Series Installation Instructions
Installation Instructions LCU-1 The IQ-SBS LCU-1 is a self-contained device for integrating control of facility lighting with IQ-SBS. The LCU-1 controls lighting zones, accepts input from override switches
More informationVoltage Current Front-mounting bracket
Switching Power Supply S8PS Compact DIN-Rail Mounting Industrial Power Supplies with Capacities Up to 600 W Models range from 0 W to 600 W. Universal input: voltage range 0 to 240 VAC. Power Factor Correction
More informationRMB Peripheral Units Installation Guide
RMB Peripheral Units Installation Guide Part Number 65-000101 2011 by Kentrox, Inc. All rights reserved. Copyright 2011 by Kentrox, Inc. All Rights Reserved. The material discussed in this publication
More informationINJ-24A Series Quick Installation Guide
INJ-24A Series Quick Installation Guide Moxa High-Power PoE+ Injector Edition 4.1, August 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777
More informationLOCAL DISPLAY UNIT (LDU)
LOCAL DISPLAY UNIT (LDU) The LDU200 is a LonWorks -based networked user interface panel used to display data and edit setpoint variables for vivariums, bio-containment, laboratory spaces, operating rooms,
More informationCentraLine I/O MODULES
CentraLine I/O Modules Installation & Commissioning Instructions CentraLine I/O MODULES INSTALLATION AND MISSIONING INSTRUCTIONS CONTENTS Safety Information... 2 General Safety Information... 2 Safety
More informationEAGLE Controller. Installation & Commissioning Instructions TABLE OF CONTENTS
EAGLE Controller Installation & Commissioning Instructions TABLE OF CONTENTS Safety Information... General Safety Information... Information as per EN 60730... WEEE Directive... Standards, Approvals, etc....
More informationEAGLEHAWK Controller. Product Data. U.S. Registered Trademark Copyright 2016 Honeywell Inc. All Rights Reserved
EAGLEHAWK Controller Product Data GENERAL EAGLEHAWK is a BACnet-compliant heating, ventilation, air conditioning (HVAC) building controller. It runs the CentraLine Niagara framework, integrating all trades
More informationAndover ContinuumTM Infinet II
Andover ContinuumTM Infinet II i2920 System Controllers The Andover Continuum Infinet II i2920 System Controller is designed to meet the needs of your most demanding control and monitoring applications
More informationUser Manual. MS657140X Industrial Fast Ethernet Switch 8x 10/100Base-TX
User Manual MS657140X Industrial Fast Ethernet Switch 8x 10/100Base-TX CE MARKING This equipment complies with the requirements relating to electromagnetic compatibility, EN 55022 class A for ITE, the
More informationRNN5-STD NETWORK NODE FOR AMR SYTEMS
RNN5-STD NETWORK NODE FOR AMR SYTEMS GENERAL PRODUCT DATA CONTENTS Contents... 1 General... 1 Applications... 1 Features... 1 Technical Details... 1 Specifications... 2 CE Norms and Standards... 2 Installation...
More informationControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet
General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.
More informationPHOENIX CONTACT - 07/2006
Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,
More informationDALI Professional Controller-4. Control unit Operating instructions
LI Professional Controller-4 Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Configuration 5 Design 5 Connections
More informationPHOENIX CONTACT Features
Electronic monitoring relay for temperature monitoring Data sheet 107385_en_00 1 Description PHOENIX CONTACT - 2016-05-10 Features Safety and system availability requirements are constantly on the increase
More informationProduct and functional description
Product and functional description Connection example The universal dimmer submodule N 528/41 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,
More informationis then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 6 A Compact design, only 50 mm wide Simple DIN rail mounting Absolutely interruption-free buffering of mains failures through immediately
More informationTRIO-DIODE/12-24DC/2X10/1X20
Redundancy module INTERFACE Data sheet 104278_en_00 1 Description PHOENIX CONTACT 20100423 Features TRIO DIODE is the DINrail mountable redundancy module from the TRIO POWER product range. Using the redundancy
More information4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT
4 10/100/1000T + 2 1000 Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch User Manual V1.0 September-2013 FCC Warning This Equipment has been tested and found to comply with
More informationT7270B2009 WIRELESS WALL MODULE
T7270B2009 WIRELESS WALL MODULE HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS STANDARDS AND NORMS The ZAPP System complies with CE and EN 300 220-1 and EN 301 489-1. IMPORTANT!
More informationSolid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)
Solid-state Timer Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple
More informationLNP series. 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input.
LNP-0500-24 series 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input User Manual FCC Warning This Equipment has been tested and found to comply with
More informationTRC-190 User s Manual
User s Manual Edition 3.2, May 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only
More informationProduct and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005
Product and Applications Description Application Programs The application programs of the dimmer UP 525/01 consist of two elements: the actuating and the sensor program element. The tasks actuating program
More informationTM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector
Characteristics expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus type [Ue] rated operational
More informationTCNM-ACBB1 Installation Manual
The TCNM-ACBB1 is a connection box that can be used as an accessory to facilitate system connections for installation and device replacement of several Banner family reading devices. System cabling is
More informationWireless Fixture Adapter (WFA100-SN) Installation Instructions
Installation Instructions The Daintree Wireless Fiture Adapter () forms part of Daintree s Controlscope Manager (CSM) in commercial and industrial buildings. It transmits and receives messages over the
More informationDX561 Digital Input/Output Module
Ordering Data DATA SHEET DX561 Digital Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R2301 1TNE 968 901 R3101 DX561, digital input/output module, 8 DI
More informationProduct and functional description
Product and functional description Connection example The universal dimmer main module N 528/31 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,
More informationPanelView Plus/VersaView CE Terminals and Display Modules
Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3
More informationExtension module for lighting control
s 3 842 DESIGO RXC Extension module for lighting control Extension to the RXC30 / RXC31 / RXC38 room controller RXC40.1 RXC40.5 The RXC40 extension module is used in conjunction with an RXC30, RXC31 or
More informationCube67 - Modular I/O station
Compact modules Cube67 DI16 C 8xM12 Cube67 DI8 C 4xM12 Cube67 DI8 C 8xM8 Digital inputs Art.-No. UL 56602 UL 56612 UL 56622 approx. 50 ma approx. ma Terminator integrated Configuration PIN 2 input/diagnostic
More information1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882
1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature
More informationH3CA-8H-AC/100/110/120
Solid-State Timer 1/16 DIN, Digital-Set Timer with 0.1 Second to 9,990 Hours Range 8 field-selectable operation modes Universal AC/DC supply voltage timers available Operations include ON-delay, Repeat
More informationUser Manual. MS657208X Industrial Gigabit Ethernet Switch 8x 10/100/1000Base-T
User Manual MS657208X Industrial Gigabit Ethernet Switch 8x 10/100/1000Base-T CE MARKING This equipment complies with the requirements relating to electromagnetic compatibility, EN 55022 class A for ITE,
More informationTXM1.8U TXM1.8U-ML. Universal modules TX-I/O
s 8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility
More informationMIC-2 MKII, Multi-instrument DATA SHEET
MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)
More informationSuper universal modules
s 8 174 TX-I/O Super universal modules TXM1.8X TXM1.8X-ML Two fully compatible versions: TXM1.8X: 8 inputs/outputs with LED signal / fault indication TXM1.8X-ML: As TXM1.8X, but with additional local override
More informationLTEC Unit Ventilator DDC Controller
Document No. 09 Rev., May, 00 LTEC Unit Ventilator DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) UV (Unit Vent)
More informationTKL19 (RTUL19) Installation Manual. Tema1.0_L19_IM_1.0_EN Pagina 1 di 24
TKL19 (RTUL19) Installation Manual Tema1.0_L19_IM_1.0_EN Pagina 1 di 24 CONTENTS 1.1 Wall Set Up for the Cable Trays... 3 1.2 Electrical Connections... 4 1.3 LONWORKS Data Cables... 6 1.4 Mounting the
More informationBA/BS4S Temperature Sensor Installation & Operating Instructions
Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.
More informationEAGLEHAWK Controller. Product Data. U.S. Registered Trademark Copyright 2016 Honeywell Inc. All Rights Reserved
EAGLEHAWK Controller Product Data GENERAL EAGLEHAWK is a BACnet-compliant heating, ventilation, air conditioning (HVAC) building controller. It runs the CentraLine Niagara framework, integrating all trades
More informationTXM1.8U TXM1.8U-ML. Universal modules TX-I/O
s 8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility
More informationProduct Information. DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design)
Product Information DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design) ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle Phone +49.2355.806-0 Fax +49.2355.806-189 E-Mail:
More informationOverview. Seen as an extension of the main HVAC controller when configuring, allowing you to save engineering time.
Datasheet Lighting Expansion Modules Overview Applications On/Off lighting 1-10 V dimming lighting The Expansion Modules are microprocessor-based interfaces that extend the number of inputs and outputs
More information02/11/2015
35 mm - 1 Relay 8A OUR1 Part number 88867105 Multi-function or mono-function Multi-range Multi-voltage Relay output 1 or 2 : 8 A - 250 V (10 A UL) LED status indicator Option of connecting an external
More informationOPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS
OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating
More information