DATA SHEET Automatic Genset Controller, AGC-4

Size: px
Start display at page:

Download "DATA SHEET Automatic Genset Controller, AGC-4"

Transcription

1 DATA SHEET Automatic enset, AC-4 Single or synchronising gensets Power plant control Fast synchronising Control and protection Customised logic and control SW emulation of application DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: Fa: Document no.: J SW version: 4.3. or later

2 1. Application information 1.1. eneral information Application Application emulation Inputs and outputs Included functions Protections Single line application diagrams Terminal overview Power management applications Application Description Power management functions Easy configuration of single line diagrams Safe power management system Optional power management applications Optional functionality 2.1. Display layouts Option Y Option Y Option Y Option Y Option X Option X Available options Available variants Available software options Available accessories Hardware options and slot number location Technical information 3.1. Specifications and dimensions Technical specifications Unit dimensions in mm (inches) Ordering information 4.1. Order specifications and disclaimer Order specifications Disclaimer...30 DEIF A/S Page 2 of 30

3 Application information 1. Application information 1.1 eneral information Application The Automatic enset, AC, is a control unit containing all necessary functions for protection and control of a genset. It can be used as a single unit for one genset, or a number of ACs can be connected in a complete power management system for synchronising projects, islanded or paralleled to the mains. The AC contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the sunshine proof LCD display. The AC is a compact all-in-one unit designed for the following applications: Standard plant modes Island mode Automatic Failure Fied power Peak shaving Load takeover power eport Remote maintenance Applications Power plant with synchronising generators or a stand-alone generator. Can also be used in critical power plants. Critical power/emergency standby plants, black start generator. Power plant with fied kw setpoint (including building load). Power plant where generator supplies peak load demand paralleled to the mains. Plant mode where the load is moved from mains to generator, e.g. peak demand periods or periods with risk of power outages. Power plant with fied kw setpoint (ecluding building load). Used when the generator has to supply the load while a distribution transformer needs to be disconnected for service. The plant modes are configurable, and it is possible to change the plant mode on the fly both in single and in power management applications. All modes can be combined with Automatic Failure mode (AMF). Remote maintenance requires a DEIF RMB bo (separate product) and a set of cables (option J8). The plant/genset is easily controlled from the display unit, or a HMI/scada system can be implemented using one of the communication options. Three display units can be installed per control unit Application emulation In order to verify and test the functionality of the application, it is possible to use the emulation tool of the AC. Being connected to the AC gives the possibility to test a majority of the functionality, e.g. plant modes and logics, handling, mains and generator operation. Application emulation is useful for training, customising plant requirements and testing basic functionality that needs to be set up or verified. DEIF A/S Page 3 of 30

4 Application information In a power management system it is possible to control the entire plant, being connected only to one of the connected AC controllers Inputs and outputs The number of inputs and outputs in the AC can be tailored depending on the option selection. This table includes the number of I/Os in the standard unit (no options present). The four outputs of the governor/avr card in slot #4 are not included in the table. In-/outputs Occupied Available for other configuration Multi-selectable inputs 0 3 Digital inputs 2 for ON/OFF feedbacks (4 if MB is present)/1 E-stop RPM (MPU) 0 1 Relays for engine control 4 (start prepare/crank/stop/run) 0 9 (7 if MB is present) Relays for control 2 (4 if MB is present) 2 (0 if MB is present) Relay 1 (status/watchdog) 1 Open collector outputs 0 2 DEIF A/S Page 4 of 30

5 Application information Included functions eneral functions AC-4 standard (Y3) AC-4 D (Y1) AC-4 mains (Y4) AC-4 BTB (Y5) Synchronising Short time parallel USB interface to PC Temperature-dependent cooling down Time-based cooling down Emergency cooling down kwh meter Day/week/month/total kvarh meter Day/week/month/total Engine running hours counter, emergency, normal Start attempt counter Maintenance counter Breaker operation counter Free PC utility SW (Windows) Permission settings in PC utility SW for limited SCADA access Password-protected setup Power derate Nominal settings for rental gensets Battery test, crank or asymmetry Lube oil renewal support (frequency and voltage) Fan control of 4 fans Fuel pump logic Engine block heater control Customised display views Command timers Master clock Pulse input counters Current thermal demands DEIF A/S Page 5 of 30

6 Application information Control functions AC-4 standard (Y3) AC-4 D (Y1) Start/stop sequences AC-4 mains (Y4) AC-4 BTB (Y5) Synchronising Close before ecitation (fast synchro.) Nos. of s/contactors to be controlled 2 1 2/1 1 Run coil Stop coil with wire break Relay outputs for speed control Event log with real-time clock Alarm log with real-time clock Battery crank test log with real-time clock M-Logic Logic configuration tool for plant customising AC-4 standard (Y3) AC-4 D (Y1) AC-4 mains (Y4) AC-4 BTB (Y5) Selectable input events, e.g. plant status Selectable output events, e.g. plant commands DEIF A/S Page 6 of 30

7 Application information Protections Protections No. of ANSI AC-4 standard (Y3) AC-4 D (Y1) AC-4 mains (Y4) Reverse power 2 32R Short circuit 2 50P AC-4 BTB (Y5) Overcurrent 4 51 Voltage-dependent overcurrent 1 51V Overvoltage 2 59P Undervoltage 3 27P Overfrequency 3 81O Underfrequency 3 81U Unbalanced voltage 1 47 Unbalanced current 1 46 Underecitation or VAr import 1 32RV Overecitation or VAr import 1 32FV Overload 5 32F Busbar/mains overvoltage 3 59P Busbar/mains undervoltage 4 27P Load shed, three levels via current via busbar frequency via overload via fast overload Busbar/mains overfrequency 3 81O Multi-config. inputs with wire break alarms, three inputs 2 NA Emergency stop 1 1 Overspeed 2 12 Low auiliary supply 1 27DC High auiliary supply 1 59DC enerator eternal trip 1 5 Tie/mains eternal trip 1 5 Synchronisation failure alarms 25 Breaker open failure 52BF Breaker close failure 52BF Breaker position failure 52BF Close before ecitation failure 1 48 DEIF A/S Page 7 of 30

8 Application information Protections No. of ANSI AC-4 standard (Y3) AC-4 D (Y1) AC-4 mains (Y4) AC-4 BTB (Y5) Phase sequence error 1 47 Deload error 1 34 Crank failure 1 48 Running feedback error 1 34 MPU wire break 1 NA Start failure 1 48 Hz/V failure 1 53 Stop failure 1 48 Stop coil, wire break alarm 1 5 Engine heater 1 26 Battery test alarm 1 NA Ma. ventilation/radiator fan 2 NA Not in Auto 1 34 Fuel fill check 1 NA Single line application diagrams 1. Automatic mains failure and fied power/base load Standard, 1 controller 2. Island 3. Peak shaving, load takeover and mains power eport Display Display Display Transducer (TAS-331D) (MB) Busbar (MB) Consumers enerator (B) enerator (B) Consumers enerator (B) Diesel generator set Diesel generator set Diesel generator set DEIF A/S Page 8 of 30

9 Application information Optional 4. Multiple gensets, load sharing (1 controller per genset) Power managment Display 1 Display 2 See separate page in this data sheet Busbar Analogue loadsharing enerator (B 1) enerator (B 2) Diesel generator set 1 Diesel generator set 2 DEIF A/S Page 9 of 30

10 1.1.7 Terminal overview This terminal strip overview shows the terminals of an AC with commonly used HW options. The diagram might not reflect your actual unit due to different option configuration. OPTION M B ON B OFF MB ON MB OFF B OFF MB ON MB OFF HORN STATUS ma OUT ma OUT TRANSISTOR OUTPUTS (MAX 10 ma) OPTION M13.8 OPTION H2/H3/H A1 A2 A3 B1 B2 B AC-4 data sheet UK Application information OPTION E1 OPTION M PID PID B ON OPTION M14.6 OPTION M12/ U/kvar COM Hz/kW kvar SHARE COM kw SHARE CAN A CAN B MPU POWER ±10 V DC EXT SET CANbus Modbus Profibus LOAD SHARIN COMMON FOR E-STOP L1 L2 L3 STOP COIL PREPARE MULTI INPUTS RUN N CRANK E-STOP DEIF A/S Page 10 of 30

11 Application information 1.2 Power management applications The purpose of the power management system is to implement one control system that controls all s and all gensets. This can for instance be for fuel optimised purposes, for easy implementation of plant logic or for safety reasons Application The plant modes supported by the power management options are: Standard plant modes Island mode Automatic Failure Fied power Peak shaving Load takeover power eport Applications Power plant with synchronising generators or a stand-alone generator. Can also be used in critical power plants with a start signal from an eternal (ATS) controller Critical power/emergency standby plants, black start generator Power plant with fied kw setpoint (including building load) Power plant where generator supplies peak demand Plant mode where the load is moved from mains to generator, e.g. peak demand periods or periods with risk of power outages Power plant with fied kw setpoint (ecluding building load) The plant modes are configurable, and it is possible to change the plant mode on the fly both in single and in power management applications. The plant can be divided by one to eight bus tie s making it possible to run the plant with different plant modes, e.g. for test purposes or when splitting up the load in primary and secondary loads Description The AC can be equipped with a power management option (4, 5, 7 or 8). Using this possibility, the AC will be able to handle simple or advanced applications for a great number of power plant projects within synchronising gensets, critical power/emergency standby applications or power producing applications. The following number of units can be controlled: 16 mains feeders with mains and tie 8 bus tie s on the generator bus or load bus 16 generators (256 in plant management applications) with generator s The complete power management system can easily be monitored from the PC utility SW through a graphical supervision page. Running status, hours in operation, status, condition of mains and busbars and fuel consumption are just some of the values that are presented. DEIF A/S Page 11 of 30

12 Application information Power management functions PM functions AC-4 D AC-4 mains AC-4 BTB Multi-master system Redundant CANbus Short-time parallel (in same controller (MB/TB)) Load-dependent start/stop Priority selection, manual and automatic Running hours Load profile Manual Fuel optimised round relay ATS control Safety stop of D Load management Secured mode (start one etra generator) Quick setup for rental groups Heavy consumer control/generator request Asymmetric LS for optimal generator load level Plant PF control feeder control, feeders paralleled feeder control, main-tie-main for critical power Base load running for maintenance (island plants) Analogue load sharing for back-up with option 3 Section power control DEIF A/S Page 12 of 30

13 Application information Easy configuration of single line diagrams The setup of the application is easily configured using a PC and the DEIF PC utility software. Your PC tool visualises it - the AC-4 realises it. The basic plant control is set up by a few basic plant conditions including mains feeder handling and operation of the generators Safe power management system Multi-master system Redundant CANbus Redundant controller The AC power management system is designed as a multi-master system for increased reliability. In a multi-master system all vital data is transmitted between the ACs, giving all units knowledge of the present power management status (calculations and position) in the application. This philosophy makes the application immune to failing master controllers and makes the AC suitable for all types of applications, i.e. emergency standby/critical power applications. In critical power/emergency standby applications requiring etra operation reliability, redundant CANbus communication lines can be used to ensure reliable CANbus communication for power management if one of the CAN lines are damaged. With the Critical Power option (T1) it is possible to have redundant controllers in the application. The redundant controller is connected on the CAN line as a hot standby unit and is therefore always updated with the system status and ready to become the primary controller. DEIF A/S Page 13 of 30

14 Application information Optional power management applications 5. Island operation. 6. Parallel with mains. The tie is selectable depending on applicational needs. Display 1 Display 2 Display mains Busbar CANbus enerator (B 1) enerator (B 2) (MB) Consumers Tie (TB) Display 1 Display 2 Diesel generator set 1 Diesel generator set 2 Busbar CANbus enerator (B 1) enerator (B 2) Diesel generator set 1 Diesel generator set 2 7. Main - tie - main application. Ring bus may be used depending on applicational needs. Display mains 1 Display mains 2 Display mains 3 Display mains Consumers Consumers Consumers Consumers Tie Tie 3 4 Display BTB Display BTB Display D 1 Display BTB Display BTB Bus tie 4 Bus tie Bus tie Bus tie CANbus CANbus Diesel generator set 1 DEIF A/S Page 14 of 30

15 Application information 8. H-coupling. The tie controlled by the AC mains is selectable depending on applicational needs. The bus tie can be present without an AC controller (open/closed feedbacks are needed). Display mains 17 Display mains (MB 17) (MB 18) Consumers Consumers Tie (TB 17) Tie TB 18) Display 1 Display 2 Display BTB 33 Display 3 Display 4 BTB 33 Busbar CANbus BUSBAR CANBUS enerator (B 1) enerator (B 2) enerator (B 3) enerator (B 4) Diesel generator set 1 Diesel generator set 2 Diesel generator set 3 Diesel generator set 4 9. X mains and 1 D. The tie controlled by the AC mains is selectable depending on applicational needs. Display mains 17 Display mains 18 Display mains 19 Display mains 20 Display mains (MB 17) (MB 18) (MB 19) (MB 20) (MB 21) Consumers Consumers Consumers Consumers Consumers Tie (TB 17) Tie (TB 18) Tie (TB 19) Tie (TB 20) Tie (TB 21) Busbar Display 1 CANbus enerator (B 1) Diesel generator set 1 DEIF A/S Page 15 of 30

16 Optional functionality 2. Optional functionality 2.1 Display layouts Option Y1 Engine and generator control (island). Used for island applications and for synchronising gensets. Alarm Automatic en-set Power Self check ok Alarm multi-line AC Alarm Inh. INFO VIEW SEL JUMP LO START Run On Auto Load BACK STOP MODE Option Y3 enerator and mains control. Typically used by rental companies or for single genset applications with one mains. Alarm Automatic en-set Power Self check ok Alarm multi-line AC Alarm Inh. INFO VIEW SEL JUMP LO START Run On On Auto Load BACK STOP MODE Option Y4 Tie and mains control. Used for AC mains. Alarm Automatic en-set Power Self check ok Alarm multi-line AC MAINS Alarm Inh. INFO VIEW SEL JUMP LO START On On Auto Load BACK STOP MODE DEIF A/S Page 16 of 30

17 Optional functionality Option Y5 Bus tie control. Used for AC BTBs. Alarm Alarm INFO Automatic en-set multi-line AC BUS TIE VIEW Power Self check ok Alarm Inh. SEL JUMP LO On Auto BACK MODE Option X3 Additional operator's panel - AOP-1. Used for plant and/or genset control and status/alarm indication. AOP Option X4 Additional operator's panel - AOP-2. Used for plant and/or genset control and status/alarm indication (maimum 5 per AC). AOP-2 DEIF A/S Page 17 of 30

18 Optional functionality 2.2 Available options Available variants Type Variant Description Item no. Note AC-4 12 AC-4 without display AC-4 13 AC-4 w. display + J One 3 m display cable is included as standard AC-4 07 AC-4 BTB without display AC-4 06 AC-4 BTB w. display J One 3 m display cable is included as standard AC-4 09 AC-4 without display + A AC-4 08 AC-4 w. display + A J One 3 m display cable is included as standard AC-4 14 AC-4 Fle with display + A1 + D1 + EF H7 + M12 + N + J1 AC-4 15 AC-4 Fle without display + A1 + D1 + EF H7 + M12 + N AC-4 16 AC-4 Fle with display + A1 + D1 + EF J1 AC-4 17 AC-4 Fle without display + A1 + D1 + EF One 3 m display cable is included as standard One 3 m display cable is included as standard DEIF A/S Page 18 of 30

19 Optional functionality Available software options A A1 Description Loss of mains protection package Time-dependent undervoltage (27t) Undervoltage and reactive power low (27Q) Vector jump (78) df/dt (ROCOF) (81) Slot no. A4 Positive sequence (mains voltage low) (27) SW A5 Directional overcurrent (67) SW C2 Negative sequence voltage high (47) Negative sequence current high (46) Zero sequence voltage high (59) Zero sequence current high (50) Power-dependent reactive power (40) Inverse time overcurrent (51) (according to IEC ) Option Option type D Voltage/VAr/cos phi control Not available for AC mains and AC bus tie H D1 Constant voltage control (stand-alone) Constant reactive power control (parallel with mains) Constant power factor control (parallel with mains) Reactive load sharing (island paralleling with other generators) Load sharing/power management/plant management 3 Load sharing with analogue lines 3 HW/ SW SW SW SW Note If M12 is present, 3 is a software option 4 Power management, 16 gensets, 8 bus tie s 7 SW Not with 5 or 8 5 Power management, 16 gensets, 8 bus tie s, 16 mains 7 SW Not with 4 or 8 8 Power management, 16 gensets (island mode) 7 SW Not with 4 or 5 Serial communication H7 CANbus (J1939): 7 SW Not with H5, H13 or H6 DEIF A/S Page 19 of 30

20 Optional functionality I T H5 Caterpillar Cummins CM850/570 Detroit Diesel (DDEC) Deutz (EMR) Iveco (NEF/CURSOR) John Deere (JDEC) Description MTU SmartConnect MTU ADEC MTU MDEC M302/M303 Perkins Scania (EMS) Scania (EMS S6) Volvo Penta (EMS) Volvo (EMS2) Slot no. Option Option type Note 8 Included in option H5 H13 MTU ADEC M.501 SW Option H13 is only functional if H5 is already selected. Application emulation I1 Emulation, PC-controlled emulation of your application SW Special applications T1 Critical power, redundant controller, short-circiut limitation SW Option T1 is only functional if 4, 5 or 8 is already selected. (ANSI# as per IEEE Std C (R2001) in parenthesis). Please notice that not all options can be selected for the same unit. Please refer to the chapter "Hardware overview" in this data sheet for further information about the location of the options in the unit. DEIF A/S Page 20 of 30

21 Optional functionality Available accessories Accessory J K Cables Description Option type J1 Display cable with plugs, 3 m. UL94 (V1) approved Other J2 Display cable with plugs, 6 m. UL94 (V1) approved Other J4 PC cable for option N-programming (Ethernet cable crossed), 3 m. UL94 (V1) approved Other J6 Display cable with plugs, 1 m. UL94 (V1) approved Other J7 PC cable for utility software (USB), 3 m. UL94 (V1) approved Other J8 Display CAN cable for DU-2 connection and 2 plugs for cables for the Remote Maintenance Bo Documentation Other K1 Designer's Reference Handbook (hard copy) Other K2 CD-ROM with complete documentation Other Note RMB connector kit L Display gasket for IP54 Other Standard is IP52 Q Measurement accuracy Hardware X Q1 Verified class 0.5 Other Additional displays X2 Additional standard display (DU-2). CANbus comm. Other Two options X2 can be ordered for each AC unit X3 Additional operator's panel (AOP-1): 16 configurable LEDs and 8 configurable push-buttons X4 Additional operator's panel (AOP-2): 16 configurable LEDs, 8 configurable buttons and 1 status relay. CANbus comm. Other Other Five options X4 can be ordered for each AC unit Y Display layout Hardware Y1 Engine and generator control (island) Other Available for AC genset controller Y3 enerator and mains control Other Available for AC genset controller Y4 Tie and mains control Other Available for AC mains controller DEIF A/S Page 21 of 30

22 Optional functionality Accessory Description Option type Y5 Bus tie control Other Available for AC BTB controller Note Hardware options and slot number location CAN A CAN B Ethernet Ethernet Service port Display 9 Power Self check ok Alarm inhibit : The numbers in the drawing above refer to the slot numbers indicated in the table below. DEIF A/S Page 22 of 30

23 Optional functionality Slot # Option/standard 1 Terminal 1-28, power supply Standard Description 8-36V DC supply, 11 W; 1 status output relay; 5 relay outputs; 2 pulse outputs (kwh, kvarh or configurable open collector outputs); 5 digital inputs 2 Terminal 29-36, communication H2 Modbus RTU (RS485) H3 Profibus DP H9 Modbus RS232 for modem H8.2 Eternal I/O modules M binary inputs M relay outputs 3 Terminal 37-64, in-/outputs/load sharing M digital inputs; 4 relay outputs (SW option if 3 is present) Active power load sharing; reactive power load sharing (requires D1) (SW option if M12 is present) 4 Terminal 65-72, governor, AVR, in-/outputs Standard 4 relay E1 2 +/-25 ma out E2 2 0(4)...20 ma out EF2 1 +/-25 ma out; 1 0(4)...20 ma out EF4 1 +/-25 ma out; 2 relay EF5 1 +/-25 ma out; 1 PWM out; 2 relay EF6 2 +/-25 ma out; 1 PWM out 5 Terminal 73-89, AC measuring Standard 3 generator voltage; 3 generator current; 3 busbar/mains voltage 6 Terminal 90-97, in-/outputs F1 2 0(4)...20 ma out, transducer M digital inputs M relay outputs M ma inputs 7 Terminal , engine I/F DEIF A/S Page 23 of 30

24 Optional functionality Slot # Option/standard Standard H7 Description 8-36V DC supply, 5 W; 1 magnetic pick-up (MPU); 3 multi-inputs; 7 digital inputs; 4 relay outputs J1939 engine comm. and MTU ADEC 8 Terminal , engine communication, in-/outputs H5/H13 MTU (ADEC/MDEC) + J1939 (engine brands available in option H7) H6 Cummins CS H8.8 Eternal I/O modules M digital inputs M relay outputs M ma inputs 9 LED I/F N - Modbus TCP/IP - EtherNet/IP - SMS/ alarms There can only be one hardware option in each slot. It is e.g. not possible to select option H2 and option H3 at the same time, because both options require a PCB in slot #2. Besides the hardware options shown on this page, it is possible to select the software options mentioned in the chapter "Available options". It is possible to have option H7 and option 5 at the same time, but as soon as an engine protocol has been selected in menu 7561, the CAN-A output will be locked for engine communication. If option H7 is selected, it is not possible to have options H5, H13 and H6 even though slot #8 is free. It is only possible to select one of the options H8.2 and H8.8. DEIF A/S Page 24 of 30

25 Technical information 3. Technical information 3.1 Specifications and dimensions Technical specifications Accuracy Class C Temperature coefficient: +/-0.2% of full scale per 10 C Class 0.5 with option Q1 Operating temperature Storage temperature Positive, negative and zero sequence alarms: class 1 within 5% voltage unbalance Class 1.0 for negative sequence current Fast overcurrent: 3% of 350%*In Analogue outputs: class 1.0 according to total range Option EF4/EF5: class 4.0 according to total range To IEC/EN C ( F) C ( F) if Modbus TCP/IP (option N) is available in the controller. (UL/cUL Listed: ma. surrounding air temperature: 55 C/131 F) C ( F) Climate 97% RH to IEC Operating altitude Measuring voltage Measuring current Current overload m above sea level Derating m above sea level: Ma. 480V AC phase-phase 3W4 measuring voltage Ma. 690V AC phase-phase 3W3 measuring voltage V AC +/-20% (UL/cUL Listed: 600V AC phase-phase) Consumption: ma VA/phase -/1 or -/5 A AC (UL/cUL Listed: from CTs 1-5 A) Consumption: ma. 0.3 VA/phase 4 I n continuously 20 I n, 10 sec. (ma. 75 A) 80 I n, 1 sec. (ma. 300 A) Measuring frequency Au. supply Hz Terminals 1 and 2: 12/24V DC ( V continuously, 6 V 1 sec.). Ma. 11 W consumption Terminals 98 and 99: 12/24V DC ( V continuously, 6 V 1 sec.). Ma. 5 W consumption The au. supply inputs are to be protected by a 2 A slow blow fuse. (UL/cUL Listed: AW 24) DEIF A/S Page 25 of 30

26 Technical information Binary inputs Analogue inputs Multi-inputs Relay outputs Open collector outputs Analogue outputs Load sharing lines alvanic separation Optocoupler, bi-directional ON: V DC Impedance: 4.7 kω OFF: <2V DC V DC: not galvanically separated. Impedance: 100 kω 0(4)...20 ma: impedance 50 Ω. Not galvanically separated RPM (MPU): V AC, Hz, ma. 50 kω 0(4)...20 ma: 0-20 ma, +/-1%. Not galvanically separated Binary: ma. resistance for ON detection: 100 Ω. Not galvanically separated Pt100/1000: C, +/-1%. Not galvanically separated. To IEC/EN60751 VDO: Ω, +/-2%. Not galvanically separated V DC: V DC, +/-1%. Not galvanically separated Electrical rating: 250V AC/30V DC, 5 A. (UL/cUL Listed: 250V AC/24V DC, 2 A resistive load) Thermal 50 C: 2 A: continuously. 4 A: t on = 5 sec., t off = 15 sec. (Unit status output: 1 A) Supply: V DC, ma. 10 ma (terminal 20, 21, 22 (com)) 0(4)...20 ma and +/-25 ma. alvanically separated. Active output (internal supply). Load ma. 500 Ω. (UL/cUL Listed: ma. 20 ma output) Update rate: transducer output: 250 ms. Regulator output: 100 ms V DC. Impedance: 23.5 kω Between AC voltage and other I/Os: 3250 V, 50 Hz, 1 min. Between AC current and other I/Os: 2200 V, 50 Hz, 1 min. Between analogue outputs and other I/Os: 550 V, 50 Hz, 1 min. Between binary input groups and other I/Os: 550 V, 50 Hz, 1 min. DEIF A/S Page 26 of 30

27 Technical information Response times (delay set to min.) Busbar: Over-/undervoltage: <50 ms Over-/underfrequency: <50 ms Voltage unbalance: <250 ms Mounting enerator: Reverse power: <250 ms Overcurrent: <250 ms Fast overcurrent: <40 ms Directional overcurrent: <150 ms Over-/undervoltage: <250 ms Over-/underfrequency: <350 ms Overload: <250 ms Current unbalance: <250 ms Voltage unbalance: <250 ms Reactive power import: <250 ms Reactive power eport: <250 ms Voltage-dependent I>: <250 ms Negative sequence I: <500 ms Negative sequence U: <500 ms Zero sequence I: <500 ms Zero sequence U: <500 ms Overspeed: <500 ms Digital inputs: <250 ms Emergency stop: <200 ms Multi-inputs: 800 ms Wire failure: <600 ms : df/dt (ROCOF): <130 ms (4 periods) Vector jump: <40 ms Positive sequence: <60 ms Time-dependent undervoltage, U t <: <50 ms Undervoltage and reactive power low, U Q <: <250 ms DIN-rail mount or base mount with si screws Safety To EN , installation category (overvoltage category) III, 600 V, pollution degree 2 To UL 508 and CSA 22.2 no , overvoltage category III, 600 V, pollution degree 2 EMC/CE To EN , EN , IEC Vibration Shock (base mount) Hz: 2 mm pp Hz: 0.7 g. To IEC & IACS UR E Hz: 0.15mm pp Hz: 1 g. To IEC Response (class 2) Hz: 2 g. To IEC Endurance (class 2) 10 g, 11 ms, half sine. To IEC Response (class 2) 30 g, 11 ms, half sine. To IEC Endurance (class 2) 50 g, 11 ms, half sine. To IEC Bump 20 g, 16 ms, half sine. To IEC (class 2) Material All plastic materials are self-etinguishing according to UL94 (V1) DEIF A/S Page 27 of 30

28 Technical information Plug connections Protection overnors and AVRs Approvals UL markings AC current: mm 2 stranded wire. (UL/cUL Listed: AW 18) AC voltage: mm 2 stranded wire. (UL/cUL Listed: AW 20) Relays: (UL/cUL Listed: AW 22) Terminals : mm 2 stranded wire. (UL/cUL Listed: AW 24) Other: mm 2 stranded wire. (UL/cUL Listed: AW 24) Display: 9-pole Sub-D female Service port: USB A-B Unit: IP20. Display: IP52 (IP54 with gasket: option L). (UL/cUL Listed: Type Complete Device, Open Type). To IEC/EN Multi-line 2 interfaces to all governors and AVRs using analogue, relay control or CANbased J1939 communication See interfacing guide at UL/cUL Listed to UL508 Applies to VDE-AR-N 4105 Wiring: use 60/75 C copper conductors only Mounting: for use on a flat surface of type 1 enclosure Installation: to be installed in accordance with the NEC (US) or the CEC (Canada) AOP-2: Maimum ambient temperature: 60 C Wiring: use 60/75 C copper conductors only Mounting: for use on a flat surface of type 3 (IP54) enclosure. Main disconnect must be provided by installer Installation: to be installed in accordance with the NEC (US) or the CEC (Canada) Weight DC/DC converter for AOP-2: Tightening torque: 0.5 Nm (4.4 lb-in) Wire size: AW Base unit: 1.6 kg (3.5 lbs.) Option J1/J4/J6/J7: 0.2 kg (0.4 lbs.) Option J2: 0.4 kg (0.9 lbs.) Option J8: 0.3 kg (0.58 lbs.) Display: 0.4 kg (0.9 lbs.) DEIF A/S Page 28 of 30

29 Technical information Unit dimensions in mm (inches) 115 (4.528) 165 (6.486) 144 (5.669) 15 (0.59) 115 (4.528) 215(8.465) 230 (9.055) 115 (4.528) Display or AOP 220 (8.661) 20.0 (0.787) DEIF A/S Page 29 of 30

30 Ordering information 4. Ordering information 4.1 Order specifications and disclaimer Order specifications Variants Mandatory information Additional options to the standard variant Item no. Type Variant no. Option Option Option Option Option Eample: Mandatory information Additional options to the standard variant Item no. Type Variant no. Option Option Option Option Option AC-4 Fle with display + A1 + D1 + EF J1 16 C2 M12 The AC mains unit is only usable with option 5; this option is already included when ordered. The AC bus tie unit is only usable with option 4 or 5. Specify the AC type: D/mains/BTB unit. Accessories Mandatory information Item no. Type Accessory Eample: Mandatory information Item no. Type Accessory Accessories for AC-4 USB cable, 3 m (J7) Disclaimer DEIF A/S reserves the right to change any of the contents of this document without prior notice. DEIF A/S Page 30 of 30

Generator Protection Unit, GPU-3 Gas Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General

Generator Protection Unit, GPU-3 Gas Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General DATA SHEET Generator Protection Unit, GPU-3 Gas Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax:

More information

Generator Paralleling Controller, GPC-3 Gas Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General

Generator Paralleling Controller, GPC-3 Gas Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General DATA SHEET Generator Paralleling Controller, GPC-3 Gas Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General DEIF A/S Frisenborgvej 33 DK-7800 Skive

More information

Generator Protection Unit, GPU-3 Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General

Generator Protection Unit, GPU-3 Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General DATA SHEET Generator Protection Unit, GPU-3 Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45

More information

DATA SHEET Automatic Genset Controller, AGC-3

DATA SHEET Automatic Genset Controller, AGC-3 DATA SHEET Automatic enset, AC-3 Operation modes Engine control enerator protection (ANSI) Display /busbar protection (ANSI) M-Logic (Micro PLC) eneral DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45

More information

Generator Paralleling Controller, GPC-3 DATA SHEET

Generator Paralleling Controller, GPC-3 DATA SHEET DATA SHEET Regulation modes Load sharing Fixed frequency Fixed power Frequency droop Generator protection (ANSI) 2 x reverse power (32) 5 x overload (32) 6 x overcurrent (50/51) 2 x overvoltage (59) 3

More information

Generator Protection Unit, GPU-3 DATA SHEET

Generator Protection Unit, GPU-3 DATA SHEET DATA SHEET Generator protection (ANSI) 2 x reverse power (32) 5 x overload (32) 6 x overcurrent (50/51) Inverse time overcurrent (51) 2 x overvoltage (59) 3 x undervoltage (27) 3 x over-/underfrequency

More information

Automatic Gen-set Controller Multi-line D

Automatic Gen-set Controller Multi-line D Multi-line 2 4921240295D SW version.20.0 or later Standard functions Operation modes Automatic mains failure Island operation Fixed power/base load Peak shaving Load take over Mains power export Push-buttons

More information

Generator Protection Unit, GPU-3 DATA SHEET

Generator Protection Unit, GPU-3 DATA SHEET DATA SHEET Generator Protection (ANSI) 2 x reverse power (32) 5 x overload (32) 6 x overcurrent (50/51) 2 x overvoltage (59) 3 x undervoltage (27) 3 x over-/underfrequency (81) Voltage dependent overcurrent

More information

DATA SHEET Paralleling and Protection Unit, PPU-3

DATA SHEET Paralleling and Protection Unit, PPU-3 DATA SHEET Paralleling and Protection Unit, PPU-3 Regulation modes Generator protection M-Logic (Micro PLC) Busbar protection Free PC utility software Approved by all major classification societies DEIF

More information

AGC 200 Advanced Gen-set Controller DATA SHEET

AGC 200 Advanced Gen-set Controller DATA SHEET AGC 200 Advanced Gen-set Controller DATA SHEET Operation modes Automatic mains failure Island operation Fixed power/base load Peak shaving Load take over Mains power export Protection (ANSI) 5 x Overload

More information

Generator Paralleling Controller, GPC-3 Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General

Generator Paralleling Controller, GPC-3 Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General DATA SHEET Generator Paralleling Controller, GPC-3 Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.:

More information

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications DATA SHEET Advanced enset Controller, 200 Operation modes Display and unit front eneral Engine control M-Logic Optional applications DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45

More information

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications DATA SHEET Advanced enset Controller, 200 Operation modes Display and unit front eneral Engine control M-Logic Optional applications DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45

More information

DATA SHEET. AGC PM Automatic Genset Controller, Plant Management

DATA SHEET. AGC PM Automatic Genset Controller, Plant Management DATA SHEET AGC PM Automatic Genset Controller, Plant Management Management of up to 992 gensets Island and parallel operation Plant black start capabilities Fuel-optimised control Integrated genset protection

More information

PPM Protection and Power Management DATA SHEET

PPM Protection and Power Management DATA SHEET PPM DATA SHEET Power Management Multiple master system Redundant internal communication Load-dependent start/stop Fuel optimisation logic Programmable start priority Heavy consumer control Blackout start

More information

SPARE PART ONLY. Basic Gen-set Controller Multi-line H SW version 2.31.X or later. Data sheet. Standard functions

SPARE PART ONLY. Basic Gen-set Controller Multi-line H SW version 2.31.X or later. Data sheet. Standard functions Multi-line 2 492124027H SW version 2.1.X or later DEIF A/S Applications AMF (no synchronising) Island mode (stand alone) Generator controls Engine start/stop Configurable start sequence Protection and

More information

Basic Gen-set Controller multi-line F SW version 2.31.X or later

Basic Gen-set Controller multi-line F SW version 2.31.X or later multi-line 2 492124027F SW version 2.1.X or later Standard functions DEIF A/S Applications AMF (no synchronising) Island mode (stand alone) Generator controls Engine start/stop Configurable start sequence

More information

DEIF A/S. Generator Paralleling Controller multi-line L. Type GPC / GS. Compact system in one unit

DEIF A/S. Generator Paralleling Controller multi-line L. Type GPC / GS. Compact system in one unit Compact system in one unit Generator Paralleling Controller multi-line 2 4921240189L Generator synchronisation, protection and control True 3-phase RMS measurements, voltages and currents galvanically

More information

AGC 200 Automatic Advanced Gen-set Controller DATA SHEET

AGC 200 Automatic Advanced Gen-set Controller DATA SHEET 200 Automatic DATA SHEET Operation modes Automatic mains failure/ats Island operation Fixed power/base load Peak shaving Load takeover Mains power export Multiple gen-set load sharing (128) Display and

More information

Generator Protection Unit, GPU Hydro Multi-line A SW version 2.4X.X

Generator Protection Unit, GPU Hydro Multi-line A SW version 2.4X.X Multi-line 2 4921240335A SW version 2.4X.X Standard functions Applications Measuring system DEIF A/S Generator protection for hydro turbine driven generators Functions 2 sets of alarm set points Alarm

More information

DATA SHEET Genset Controller, GC-1F

DATA SHEET Genset Controller, GC-1F DATA SHEET Genset Controller, Engine control Generator monitoring Generator protection (ANSI) Mains monitoring Mains protection (ANSI) Engine monitoring Display panel DEIF A/S Frisenborgvej 33 DK-7800

More information

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution DATA SHEET Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.:

More information

Generator Controller GC-1F

Generator Controller GC-1F Controller 4921240310D Standard functions DEIF A/S Engine control Start preparation (preheating or prelubrication) Start/stop sequences with selectable no. of start attempts Fuel solenoid selection (coil

More information

Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus

Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus DATA SHEET Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus DEIF A/S Frisenborgvej 33 DK-7800 Skive

More information

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution DATA SHEET Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.:

More information

DATA SHEET IOM 200 analogue interface for AGC 200

DATA SHEET IOM 200 analogue interface for AGC 200 DATA SHEET IOM 200 analogue interface for AGC 200 CAN interface to AGC 200 series TTL interface to PC LED indicators for unit and CANbus status GOV/AVR outputs selectable for DC current or DC voltage DEIF

More information

Generator Controller GC-1

Generator Controller GC-1 4921240293F Standard functions DEIF A/S Engine control Start preparation (preheater or prelubrication) Start/stop sequences with selectable no. of start attempts Fuel solenoid selection (coil type) Idle

More information

No longer for sale. Generator Controller GC-1. Data sheet. Standard functions

No longer for sale. Generator Controller GC-1. Data sheet. Standard functions 4921240293F DEIF A/S Engine control Start preparation (preheater or prelubrication) Start/stop sequences with selectable no. of start attempts Fuel solenoid selection (coil type) Idle speed control Local

More information

Engine Controller EC-1

Engine Controller EC-1 Engine Controller 4921240292E Standard functions Engine control Engine monitoring DEIF A/S Start preparation (preheater or prelubrication) Start/stop sequences with selectable no. of start attempts Fuel

More information

PPU Power Management (PPM)

PPU Power Management (PPM) PPU anagement (PP) 4921240291H Standard functions DEIF A/S management Load dependent start/stop Programmable start priority Heavy consumer control Blackout start sequence Supervision/control of a shore

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS AGC 200 Advanced Gen-set Controller Mounting Terminal strip overview I/O lists Wiring Document no.: 4189340610C SW version 3.5X.X or later Table of contents 1. ABOUT THIS DOCUMENT...

More information

Automatic Sustainable Controller, ASC Mounting Board slot positions Terminal strip overview I/O lists Wiring

Automatic Sustainable Controller, ASC Mounting Board slot positions Terminal strip overview I/O lists Wiring INSTALLATION INSTRUCTIONS Automatic Sustainable Controller, ASC Mounting Board slot positions Terminal strip overview I/O lists Wiring DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45

More information

DATA SHEET Compact Genset Controller, CGC 200

DATA SHEET Compact Genset Controller, CGC 200 DATA SHEET Compact Genset Controller, CGC 200 Auto start and parameter monitoring Warnings and shutdown protections Includes 5 digital inputs, 5 relay outputs Configurable for other applications Licence-free

More information

Delomatic 4, DM-4 Marine & Offshore DATA SHEET

Delomatic 4, DM-4 Marine & Offshore DATA SHEET Delomatic 4, DATA SHEET Application Power management control and protection of complex marine and offshore applications including diesel, gas and turbine generators, as well as tie breakers and shore connections

More information

MULTI-LINE 2 APPLICATION NOTES

MULTI-LINE 2 APPLICATION NOTES MULTI-LINE 2 APPLICATION NOTES Converting PPM-2 to PPM 300 Parameter conversion Wiring Options I/O list Modbus DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

Delomatic 4, DM-4 Land DATA SHEET

Delomatic 4, DM-4 Land DATA SHEET Delomatic 4, DATA SHEET Application Features Power Management control and protection of complex power systems including diesel, gas and turbine generators, as well as mains and tie breakers Highly flexible

More information

Option H3 Serial communication Profibus DP

Option H3 Serial communication Profibus DP MULTI-LINE 2 DESCRIPTION OF OPTIONS Option H3 Serial communication Profibus DP Description of option Functional description Parameters Data tables Document no.: 4189340443H Multi-line 2 Option H3, Serial

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Generator Paralleling Controller, GPC-3, and variants Generator Protection Unit, GPU-3, and variants Paralleling and Protection Unit, PPU-3 Mounting Board slot positions I/O lists

More information

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET & DIN, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version:

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version: MULTI-LINE 2 APPLICATION NOTES Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com

More information

Multiple Generator Automatic Synchronising System

Multiple Generator Automatic Synchronising System R Millennium Power Manufacturing Corp. R Multiple Generator Automatic Synchronising System Synchronising System Type Choice Independent Control Cabinet Type Feature: Independent Control Cabinet Type Functions:

More information

Basic Gen-set Controller G (UK) SW version 2.1X.X. Terminal strip overview

Basic Gen-set Controller G (UK) SW version 2.1X.X. Terminal strip overview Basic Gen-set Controller 4189340302G (UK) SW version 2.1X.X Mounting Board slot positions Terminal strip overview DEIF A/S I/O lists Wiring DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614

More information

MIC-2 Multi-instrument DATA SHEET

MIC-2 Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional) I/O modules

More information

Genset control and protection with safety system

Genset control and protection with safety system APPLICATION NOTES Generator Protection Unit, GPU-3 APPLICATION NOTES Genset control and protection with safety system Application description Functional description Wiring I/O lists Basic setup Flowcharts

More information

MIC-2 MKII, Multi-instrument DATA SHEET

MIC-2 MKII, Multi-instrument DATA SHEET MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

Engine & Genset Controls Z, page 1 of 12

Engine & Genset Controls Z, page 1 of 12 Multi Differential Relay, MDR-2 Generator Protection Unit, GPU-2 Paralleling and Protection Unit, PPU-2 Multi Differential Relay for protection against short circuits and currents Engine and generator

More information

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version:

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version: MULTI-LINE 2 APPLICATION NOTES Converting to Parameter conversion Wiring Options I/O list Modbus DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com

More information

Installation Manual. Multi Power Controller MPC-1 multi-line D

Installation Manual. Multi Power Controller MPC-1 multi-line D Installation Manual Multi Power Controller MPC-1 multi-line Complete control system in one package: - island operation - parallel with mains operation - emergency generator control 3-phase AC measurements

More information

DATA SHEET DEPRECATED - PCM5 1. Document no.: N/A

DATA SHEET DEPRECATED - PCM5 1. Document no.: N/A DATA SHEET DEPRECATED - PCM DEIF A/S Frisenborgvej DK-800 Skive Tel.: +4 64 64 Fax: +4 64 6 info@deif.com www.deif.com Document no.: N/A AWC 00 PCM data sheet - DEPRECATED. AWC 00 system. System specifications...

More information

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3 QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3 What's in the delivery? Getting started The first steps PC

More information

Comprehensive Modular Genset Controller

Comprehensive Modular Genset Controller Inteligen Learn More Comprehensive Modular Genset Controller Brief Description The Inteligen is a comprehensive controller for single and multiple generating sets operating in standby or parallel to the

More information

DATA SHEET Selectable AC transducer, TAS-321 DG

DATA SHEET Selectable AC transducer, TAS-321 DG DATA SHEET Selectable AC transducer, TAS-321 DG Bi-directional current measurement on AC networks Power measurement using 2 phases on 3-phase networks Class 0.5 (IEC688) measurement Easy configuration

More information

DATA SHEET Selectable AC transducer, TAS-331DG

DATA SHEET Selectable AC transducer, TAS-331DG DATA SHEET Selectable AC transducer, TAS-331DG Measures power or reactive power on 3-phase AC networks Class 0.5 (IEC-688) measurement Supply and measuring voltage up to 690 V Easy configuration via PC

More information

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET Measurement input, auto range Up to 1000 V AC L-L Up to 12.5 A (sinusoidal) 16 400 Hz Output Up to four analogue outputs Relay output RS 485 Modbus

More information

NOT RECOMMENDED FOR NEW DESIGNS

NOT RECOMMENDED FOR NEW DESIGNS DATA SHEET DELOMATIC 4, DM-4 Gas Gas engine control Integrated speed governor Integrated air/gas mix control Combined heat and power control Generator control and monitoring Mains failure protections integrated

More information

Option M2 Configurable engine control cards Multi-line 2 version B SW version 2.4X.X

Option M2 Configurable engine control cards Multi-line 2 version B SW version 2.4X.X Description of options Option M2 Configurable engine control cards Multi-line 2 version 2 4189340482B SW version 2.4X.X Description of options Functional description DEIF A/S Display units Additional functions

More information

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S Multi-instrument 4921210107G Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Intelligent Suitable for all 3-phase network topologies Replaces transducers Accuracy U,

More information

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC QUICK START GUIDE Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615

More information

Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs

Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs QUICK START GUIDE Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

TYPE APPROVAL CERTIFICATE

TYPE APPROVAL CERTIFICATE TYPE APPROVAL CERTIFICATE Certificate No: TAA00000KD Revision No: 1 This is to certify: That the Electrical Measuring and Protection Relay with type designation(s) PPU-3, GPU-3 - Generator Controllers

More information

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC QUICK START GUIDE Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615

More information

HT-DST4602 Evolution. Genset Controller. AMF and PARALLEL genset controller. Parallel Applications HUEGLI TECH SWITZERLAND

HT-DST4602 Evolution. Genset Controller. AMF and PARALLEL genset controller. Parallel Applications HUEGLI TECH SWITZERLAND HT-DST4602 Evolution Parallel Applications 7 color TFT display (800 x 480 pixel) Split and Compact Version PLC functions included with PID blocks True RMS measure for both sources current & voltage Active

More information

Genset Controller Unit Model EMS - GC10. Installation Manual Section

Genset Controller Unit Model EMS - GC10. Installation Manual Section Genset Controller Unit Model EMS - GC10 Installation Manual 00-02-0794 Section 75 2013-01-28 In order to consistently bring you the highest quality, full featured products, we reserve the right to change

More information

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC QUICK START GUIDE Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615

More information

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3 OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3 Display and push-button functions Alarm handling Log list

More information

EMS-GC10 Genset Controller. Modbus Communication Mapping Manual Section 75

EMS-GC10 Genset Controller. Modbus Communication Mapping Manual Section 75 EMS-GC10 Genset Controller Modbus Communication Mapping Manual 1311311 2013-10-10 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to change

More information

AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200

AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200 QUICK START GUIDE AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614

More information

easygen- 3100XT/3200XT(-LT) Introduction Presentation

easygen- 3100XT/3200XT(-LT) Introduction Presentation easygen- 3100XT/3200XT(-LT) Introduction Presentation PAGE 1 marked Overview 61010, 6200 easygen-3100xt-p1 easygen-3200xt-p1 PAGE 2 easygen-3200xt series controls benefits High Flexibility and Reduced

More information

Engines & Gen-sets N, page 1 of 6

Engines & Gen-sets N, page 1 of 6 Uni-line ANSI code 27, 59 ANSI code 59 ANSI code 27 RMV-112D RMV-122D RMV-12D Under- /overvoltage protection: Overvoltage protection (2 levels Undervoltage protection (2 levels 1 minimum and 1 maximum

More information

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options Description of options Option A and B, Loss of mains protection package Automatic Gen-set controller 4189340394B SW 2.3X.X Description of options Functional descriptions DEIF A/S Parameter list DEIF A/S,

More information

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300 QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107B 1. Introduction

More information

InteliLite MRS17 Click Here to Learn More

InteliLite MRS17 Click Here to Learn More InteliLite MRS17 Click Here to Learn More Comprehensive Genset Controller Brief Description The InteliLite is a cost effective controller for generator sets in stand-by and prime power applications. The

More information

DATA SHEET. Advanced Energy Meter, AEM 380 & AEM 305

DATA SHEET. Advanced Energy Meter, AEM 380 & AEM 305 DATA SHEET Advanced Energy Meter, AEM 380 & AEM 305 Easy installation MID-approved 5 optional communication interfaces Phase error detection Low power consumption Two tariffs Two-pulse output DEIF A/S

More information

Multifunction Transducer MT440

Multifunction Transducer MT440 Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up

More information

APPLICATION NOTES H-coupling

APPLICATION NOTES H-coupling APPLICATION NOTES H-coupling Application description Functional description Wiring Basic setup Flowcharts Document no.: 4189340548A SW version 3.3X.X or later Table of contents 1. WARNINGS AND LEGAL INFORMATION...

More information

Option P1 Event and alarm printer Description of option Functional description Parameter list

Option P1 Event and alarm printer Description of option Functional description Parameter list MULTI-LINE 2 DESCRIPTION OF OPTIONS Option P1 Event and alarm printer Description of option Parameter list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com

More information

RTU500 series Data Sheet Power Supply CP-E 24/2.5

RTU500 series Data Sheet Power Supply CP-E 24/2.5 Data Sheet Power Supply CP-E 24/2.5 Power Supply CP-E 24/2.5 Application The primary switch mode power supply offers two voltage input ranges. This enables the supply with AC or DC. Furthermore it is equipped

More information

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300 QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107C 1. Introduction

More information

InteliLite SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET GEN-SET CONTROLLER Description AirGate Modern communications made simple. ComAp s powerful AirGate technology is provided in a range of our controllers and makes remote Internet connection to

More information

Comprehensive Modular Genset Controller

Comprehensive Modular Genset Controller InteliGen Comprehensive Modular Genset Controller Brief Description InteliGen is a comprehensive AMF-controller for single and multiple generating sets operating in standby or parallel modes. A modular

More information

Product Sheet ECO. Types ECG, AMF Technical data. product sheet eco ecg-amf - technical data gb v1.0.docx

Product Sheet ECO. Types ECG, AMF Technical data.  product sheet eco ecg-amf - technical data gb v1.0.docx ECO Types ECG, AMF Technical data Product overview ECO ECG and ECO AMF are microprocessor controlled devices for use in low voltage single genset applications for standby power generation. The front-side

More information

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink Characteristics variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink Main Range of product Altivar 32 Product or component type Product destination Product specific application

More information

Voltage Transducer UMT516 / MT516

Voltage Transducer UMT516 / MT516 Voltage Transducer UMT516 / MT516 True RMS AC voltage measurements Voltage auto range measurements up to 600V # Wide frequency measurement range 16 400 Hz High accuracy class 0.2 (IEC-688), 0.1 on communication

More information

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name Product data sheet Characteristics XPSMF3542 Preventa safety PLC compact - Profibus DP protocol Main Range of product Product or component type Safety module name Safety module application Nov 13, 2018

More information

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types Millenium 3 General Characteristics Millenium 3 Compact Range Millenium 3 Expandable Range Millenium 3 Communication Options Millenium 3 Range General environment characteristics for CB, CD, XD, XR and

More information

Compact Genset Controller, CGC 200 Mounting Terminals and wiring Commissioning, using the Utility Software and/or the front panel

Compact Genset Controller, CGC 200 Mounting Terminals and wiring Commissioning, using the Utility Software and/or the front panel INSTALLATION AND COMMISSIONING INSTRUCTIONS Compact Genset Controller, CGC 200 Mounting Terminals and wiring, using the Utility Software and/or the front panel DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.:

More information

SENTRON ATC Automatic Transfer Control Device

SENTRON ATC Automatic Transfer Control Device Siemens A 2010 SENTRON - SENTRON switching, protection and measuring devices The SENTRON, when equipped with two motor-driven circuit breakers, serves as a transfer system that automatically or manually

More information

M-Logic Internal Logic Controller Description of M-Logic Functional description List of possible selections for logics

M-Logic Internal Logic Controller Description of M-Logic Functional description List of possible selections for logics MULTI-LINE 2 APPLICATION NOTES M-Logic Internal Logic Controller Description of M-Logic Functional description List of possible selections for logics DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614

More information

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output Product datasheet Characteristics XPSMF4000 Preventa safety PLC compact - Safe Ethernet Main Range of product Product or component type Safety module name Safety module application Preventa Safety automation

More information

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer Installation and start up instructions TAS-331DG Selectable AC transducer 4189300008G (UK) Watt or var transducer Supply and measuring voltage up to 690V DEIF A/S Configuration via PC-interface possible

More information

Circuit Breakers Type CTI 25M, CTI 45MB

Circuit Breakers Type CTI 25M, CTI 45MB Data sheet Circuit Breakers Type CTI 25M, CTI 45MB Circuit breakers for short circuit and overload protection of motor applications cover the current range 0.1 45 A (AC-3 rating). The product range is

More information

Zelio Control-modular measurement and control relays 1

Zelio Control-modular measurement and control relays 1 Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and

More information

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview Supplementary Protectors / Miniature Circuit Breakers Page System overview 10/003 10/001 Supplementary protectors

More information

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET GEN-SET CONTROLLER Description The range offers a wide choice of integrated control solutions for gen-sets operating in single standby mode. Based on the field proven InteliLite architecture,

More information

DATA SHEET. Advanced Power Meter, APM 380 & APM 305

DATA SHEET. Advanced Power Meter, APM 380 & APM 305 DATA SHEET Advanced Power Meter, APM 380 & APM 305 Easy installation Monitors all 3 phases 5 optional communication interfaces Phase error detection Low power consumption Two-pulse output DEIF A/S Frisenborgvej

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET GEN-SET CONTROLLER Description The range offers a wide choice of integrated control solutions for gen-sets operating in single standby mode. Based on the field proven InteliLite architecture,

More information

Circuit Breakers, Type CTI 25M, CTI 45MB, CTI 100

Circuit Breakers, Type CTI 25M, CTI 45MB, CTI 100 MAKING MODERN LIVING POSSIBLE Data sheet Circuit Breakers, Type CTI 25M, CTI 45MB, CTI 100 Circuit breakers for short circuit and overload protection of motor applications cover together with the circuit

More information

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Warnings and legal information Installation and terminals Communication I/O options Alarming Utility software More information Specifications

More information

GC2000 Generator Controller Power Management and Protection

GC2000 Generator Controller Power Management and Protection GC2000 Generator Controller Power Management and Protection Control. Monitor. Protect. A powerful generator controller and power management system for marine and offshore applications SELCO s GC2000 provides

More information