4 Remote I/O. Digital Output Module 8-Channel Version Type 9475/ from Rev. F
|
|
- Letitia Harrell
- 5 years ago
- Views:
Transcription
1 4 Remote I/O Digital Output Module 8-Channel Version 8 channels for Ex i solenoid valves, piezo and booster-valves Intrinsically safe Ex ia IIC outputs Additional input for Plant-STOP available (acc. to IEC up to SIL 2) Galvanic isolation between outputs and system Open-circuit and short-circuit monitoring for each field circuit Connection of the field cables with plug-in terminals Modules can be replaced while powered up (hot swap) Installation in Zone 1 and Zone 2 Zone 21 and E00 The outputs are short circuit protected. All channels are individually monitored for open- and short-circuits. Monitoring can be switched off individually in each channel using parameters. Open-circuit monitoring is also active when the switching state is OFF. The interface of the Digital Output Module with the internal data bus of the BusRail is designed with redundancy. Modules 9475/ are equipped with an additional Ex i digital input for simultaneous deactivation of all outputs of a module ( Plant-STOP ). This meets the requirements on functional safety as per IEC up to SIL 2. Zones Ex i interfaces X X X X X X Installation in X X X X X E00 4/1
2 Digital Output Module 8-Channel Version 4 Selection Table Version Channels Safety data Ex ia IIC Digital Input (Plant-STOP) max. voltage U o max. current I o Order number Digital Output Module V 75 ma no 9475/ ,275 Weight 19.9 V 145 ma no 9475/ , V 107 ma no 9475/ , V 145 ma yes 9475/ , V 107 ma yes 0,275 kg Certificates PTB 99 ATEX 2220 Other certificates Explosion protection Gas explosion protection Dust explosion protection Safety data for digital outputs Ex ib IECEx, USA (FM), Canada (CSA), Russia (CTB), Shipping (DNV, GL, ABS) E II 2 (1) G EEx ib [ia] IIC/IIB T4 E II (1/2) D [Ex iad/ibd] Type U o [V] I o [ma] P o [mw) L o [mh] C o [nf] IIC IIB IIC IIB 9475/ / / / The effective internal capacitances and inductances are negligibly small Ex ia Type U o [V] I o [ma] P o [mw) L o [mh] C o [nf] IIC IIB IIC IIB 9475/ / / / The effective internal capacitances and inductances are negligibly small Safety data for digital input for deactivating all outputs ("Plant-STOP") Ex ia only type U o [V] I o [ma] P o [mw) L o [mh] C o [nf] IIC IIB IIC IIB 9475/ The effective internal capacitances and inductances are negligibly small Further information see certificates 4/2
3 4 Digital Output Module 8-Channel Version Functional safety (IEC 61508) Digital input Test report max. SIL 2 Safe state "Plant-STOP" Exida FMEDA Stahl 03/05-19R001 all outputs "OFF" Safe Failure Fraction SFF 85,8 % (Typ A) MTBF (to SN 29500) PFD AVG at T [Proof] 38 years (at 40 C) T[Proof] 1 year 5 years 10 years PFD AVG 1.53 x x x 10-3 Further information Galvanic transmission between power supply and system components between two input / output modules between inputs/outputs and system components Ex i outputs see test report 1500 V AC 500 V AC 500 V AC The outputs and the input "Plant-STOP" of an I/O module have a common minus conductor Type No-load voltage [V] U [V) I [ma] R i [Ω] 9475/ / / / Number of channels 8 Output characteristics 9475/ / / E E E00 Digital input; Ex i Function for deactivating all outputs ("Plant-STOP"), only type 9475/ , Supply voltage Internal resistance max. voltage for outputs in normal operating mode min. voltage for all deactivated outputs ("Plant-STOP") 5 V 1.6 ko 1 V 3.5 V 4/3
4 Digital Output Module 8-Channel Version 4 Settings Open-circuit and short-circuit monitoring Output safety position during communication faults Diagnostics Retrievable parameters Module faults Signal fault Open-circuit Short circuit Terminal voltage for non-linear loads Power supply Behavior with undervoltage Typical power consumption Typical power loss ON, ON without test current, OFF ON, OFF, hold last value Manufacturer, type, version, serial number Internal primary bus fault Internal redundant bus fault no response Dissimilar module configuration Hardware fault Hardware deactivation of outputs (via Systems OFF) 9475/ / / > 10 ko > 12 ko > 13 ko < 95 O > 4 V All outputs are switched to the "OFF" status Type all outputs short-circuited 9475/ W 9475/ , 9475/ W 9475/ , 6.4 W Type all outputs short-circuited 9475/ W 9475/ , 9475/ W 9475/ , 6.4 W Construction setup Module enclosure Fire protection class (UL 94) Degree of protection (IEC 60529) Polyamide 6GF HB Modules IP 30 Connections IP 20 Electrical connections Ex i field signals Display and operating interface Operation Failure Installation conditions Plug-in terminals 16 pin with catch, 2.5 mm 2, screw or connectors LED green "RUN" LED red "ERR" Mounting type on 35 mm DIN rails NS 35/15 Mounting position horizontal or vertical 4/4
5 4 Digital Output Module 8-Channel Version Ambient conditions Note Ambient temperature - 20 C C Storage temperature - 40 C C Maximum relative humidity Vibration sinusoidal (IEC ) semi-sinusoidal (IEC ) Electromagnetic compatibility 95 % (no condensation) 1 g in frequency range Hz 2 g in frequency range Hz 15 g (3 shocks per axis and direction) Tested under the following standards and regulations: EN (1998) IEC , NAMUR NE 21 You will find a list of compatible I.S. solenoid valves, indicating lamps etc on our homepage Accessories and Spare Parts Designation Illustration Description Order number Plug-in Terminal Labeling strips 02079E E mm 2 with catch, 16 pin, screw connection, blue, for connecting the field signal to I/O modules, for instrinsically safe field circuits Designation: Attention: For I/O module type 9470 and 9480 an additional terminal is necessary. Designation: mm 2 with catch, 16 pin, spring connection, blue, for connecting the field signal to I/O modules, for intrinsically safe field, with test jacks Designation: Attention: For I/O module type 9470 and 9480 an additional terminal is necessary Designation: FB No... Mod No... for plug-in terminals, sheet with 26 labels E00 Warning sign Only clean modules with damp cloths E00 DIN4 sheet for I/O module labels; 6 labels each sheet; print-out with IS Wizard software; packaging unit = 20 sheets E00 Partition For installation between intrinsically safe and non-intrinsically safe connectors of the I/O-modules. With this, the required 50 mm distance is achieved E00 4/5
6 Digital Output Module 8-Channel Version 4 Dimension drawings (all dimensions in mm) - subject to alterations 09879E00 We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without notice. The illustrations cannot be considered binding. 4/6
4 Remote I/O. Digital Output Module 8-Channel Version Series 9475/ from Rev. F
4 Remote I/O Digital Output Module 8-Channel Version 8 channels for Ex i / I.S. solenoid valves, piezo and booster valves Intrinsically safe outputs Ex ia IIC Additional input for "Outputs OFF" available
More information4 Remote I/O. Analog Output Module HART Ex i / I.S. Outputs, 8 Channels Series 9466/12
0 4 Remote I/O 8 channels for controlling HART control valves and positioners Intrinsically safe outputs Ex ia IIC Galvanic isolation between outputs and system Open-circuit and short-circuit monitoring
More informationDigital Output Module 8-Channel Version for Zone 1 Series 9475/
www.stahl.de > 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Additional Ex i control input for "Plant STOP" (acc. IEC61508 up to SIL2) >
More informationDigital Output Module 8-Channel Version for Zone 2 Series 9475/
> 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in
More informationDigital Output Module 8-Channel Version for Zone 2 Series 9475/
> 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in
More informationDigital Output Module 4-Channel Version for Zone 1 Series 9475/
www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Additional Ex i control input for "Plant STOP" (acc. IEC61508 up to SIL2) >
More informationDigital Output Module 4-Channel Version for Zone 1 Series 9475/
www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ib > Suitable for Ex i hydraulic valves and solenoid valves > Additional Ex i control input for (in accordance with IEC 61508 through
More informationEthernet CPU Module & Power Module for Zone 1 / Div. 1 Series 9441/12 and 9444/12
www.stahl.de > Fieldbus connection Industrial Ethernet PROFINET, Modbus TCP or EtherNet/IP with 100 MBit/s > Redundant Ethernet connection (Modbus TCP) is possible > Explosion protected, optical inherently
More information5 Fieldbus Technology
5 Fieldbus Technology Ex e / Ex i 10922E00 The s Ex e/ex i connect intrinsically safe Foundation Fieldbus H1 or Profibus PA field devices to a non-intrinsically safe / Ex e trunk. Up to four intrinsically
More informationOperating instructions
Operating instructions Digital Input Output Module > Contents 1 Contents 1 Contents...2 2 General information...3 2.1 Manufacturer...3 2.2 Information regarding the operating instructions...3 2.3 Conformity
More informationCPU module for zone 2 Series 9442/35
> Supports PROFIBUS DP, PROFINET, Modbus TCP and Ethernet/IP; incl. HART transmission > RS-485 (max. 12 Mbps) and Ethernet (max. 100 Mbps) interfaces > Extensive diagnostics based on NE 107 > Support of
More informationPHOENIX CONTACT - 02/2008
Ex-i solenoid driver for Group IIC gases, loop-powered, pluggable INTERFACE Data Sheet 103211_00_en PHOENIX CONTACT - 02/2008 1 Description The solenoid driver PI-EX-SD-21-25 links a signaling device installed
More informationMACX MCR-EX-SD LP(-SP)
Intrinsically safe solenoid driver for Group IIC gases, loop-powered, current limit 48 ma INTERFACE Data sheet 103468_en_01 PHOENIX CONTACT - 08/2008 1 Description The solenoid driver MACX MCR-EX-SD-24-48-LP(-SP)
More informationGrounding Systems / Ground Monitoring Device Series 8146/5075 and 8125/5071
www.stahl.de > Monitored electrostatic grounding of tank containers and drums during loading > Continuous monitoring of correct grounding > Robust design > Weather-protected plastic enclosure (IP66) or
More informationMACX MCR-EX-SL-NAM-R(-SP)
Intrinsically safe NAMUR isolating amplifier with relay output INTERFACE Data sheet 03463_en_00 PHOENIX CONTACT - 08/2008 Description The NAMUR MACX MCR-EX-SL-NAM-R(-SP) isolating amplifier has been designed
More informationPI-EX-ME-2NAM/COC-24VDC
Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 4 V DC Supply INTERFACE Data Sheet 0033_0_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/COC-4VDC
More informationDigital Input Output Module for Zone 1
Digital Input Output Module for Zone 1 Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the Operating Instructions...3
More informationPHOENIX CONTACT - 12/2007
Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Active Transistor Output, Two-Channel INTERFACE Data Sheet 0943_00_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/TO-A is a two-channel
More informationMACX MCR-EX-SL-NAM-2RO(-SP)
Intrinsically safe NAMUR isolating amplifier with two relay outputs INTERFACE Data sheet 03465_en_00 PHOENIX CONTACT - 08/008 Description The NAMUR MACX MCR-EX-SL-NAM-RO(-SP) isolating amplifier has been
More informationPI-EX-ME-2NAM/COC-120VAC
PI-EX-ME-NAM/COC-0VAC Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 0 V AC Supply INTERFACE Data Sheet 0944_00_en PHOENIX CONTACT - 0/008 Description
More informationLoop-powered Transmitter for Thermocouple Type K (NiCr-Ni)
Data sheet 302040_en MTP300i-SIL-K Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni) Properties 2-wire temperature transmitter for DIN rails Galvanic isolated TC-input with cold-junction compensation
More informationAssembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail
Switch Amplifier Features Assembly -channel isolated barrier 4 V DC supply (Power Rail) Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL
More information4 â Active barrier RN221N with optional HART diagnosis. Technical Information
Technical Information Active barrier with optional HART diagnosis Active barrier with power supply for safe separation of 4 to 20 ma current circuits Application Galvanic isolation of 4 to 20 ma current
More informationFLEX Ex Spring Clamp Terminal Base
Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationTerminal Boxes Series 8118
> Enclosure made of glass fibre reinforced polyester resin > sizes available > Terminals and cable glands fitted to order > Enclosure design with integrated metal bracket for metal cable glands. > Degree
More informationControl Buttons / Switches for Panel Mounting Series 8003
www.stahl.de > Different actuators pushbutton mushroom pushbutton mushroom stay-put button mushroom stay-put button with key lock key-operated button key-operated switch selector switch > 2 contact elements
More informationMACX MCR-EX-SL-2NAM-T(-SP)
NAMUR signal conditioner, Ex-i, 2-channel, with transistor output Data sheet 103753_en_00 PHOENIX CONTACT 2014-08-19 1 Description The 2-channel NAMUR signal conditioner MACX MCR-EX-SL-2NAM-T(-SP) has
More informationSeparating and protective. Separating and protective instruments. VEGATRENN 149AEx Separator type KFDO Barrier type Product Information
Separating and protective instruments Separating and protective instruments VEGATRENN 149AEx Separator type KFDO Barrier type 9001 Product Information Content Content 1 Product description..........................................................................
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationEngineering Guideline. pac-carriers Type for Honeywell system Experion Series C I/O
Engineering Guideline pac-carriers Type 995 for Honeywell system Experion Series C I/O pac-carrier Type 995 Engineering Guideline/Honeywell 04..009 pac-carrier Type 995 Integration of conventional process
More informationInductive sensor BI5-EM18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationTermination Board FC-GPCS-SAI16-PF. Features. Assembly. Function. Connection. SAI-1620m HART 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.
Features Assembly System board for Honeywell Safety Manager For 6-channel AI card SAI-60m For 6 modules Recommended module: HiC05 (AI) 4 V DC supply Hazardous area: pluggable screw terminals, blue Non-hazardous
More informationInductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex-zone 20 for temperatures up to -25 C SIL2 acc. to IEC 61508 Rectangular, housing DSU35 Plastic, PP-GF30-VO Two outputs for monitoring the position
More informationMicro Limit Switch Series 8064
> For universal application > Versions with snap-action contact positive opening contact > With connecting cable or with single cores when it is used as a built-in device > Width Single limit switch 11
More informationAssembly. Front view. LED yellow/red: Status output Ι/ Fault signal Function. Switch Power Rail
Switch Amplifier KCD-SR-Ex.LB Features Assembly -channel isolated barrier V DC supply (Power Rail) Dry contact or NAMUR inputs Usable as signal splitter ( input and outputs) Relay contact output Fault
More informationTechnical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection
NCN-FK-N-V-V 002 Model Number NCN-FK-N-V-V Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99
More informationInductive sensor For rotary actuators NI4-DSU35TC-2Y1X2
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationMANUAL Surge Protectors
PROCESS AUTOMATION MANUAL Surge Protectors DP-LBF-I1.36.DE and DP-LBF- I1.36.IE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationInductive sensor BI1.5-EG08-Y1-H1341
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationD5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S
D5090S INSTRUCTI MANUAL 4 A Relay Output Module for NE, DIN-Rail and Termination Board, Model D5090S D5090-4 A Relay Output Module for NE G.M. International ISM09-3 Characteristics General Description:
More informationOperating instructions (Safety-related part ATEX and IECEx) Inductive NAMUR sensors NN504A NN505A NN506A NN507A /00 08/2015
Operating instructions (Safety-related part ATEX and IECEx) Inductive NAMUR sensors NN504A NN505A NN506A NN507A 80013497/00 08/015 Remarks for safe use in hazardous areas Functions and features Use in
More informationMagnetic field sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M12 x 1 Chrome-plated brass Rated operating distance 90 mm with DMR31-15-5 magnet DC 2-wire, nom.
More informationFB-6SP and FB-12SP. Block device couplers. Data sheet 3177_en_A. 2 Features. 1 Description
Block device couplers Data sheet 3177_en_A 1 Description PHOENX CONTACT 2015-01-20 2 Features The and block couplers provide an interface between the fieldbus trunk cable and field devices on Foundation
More informationInductive sensor BI1.5-EG08-Y1-H1341
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationOperating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505
Operating Instructions Intrinsically Safe Isolation Relay for Switches Model: REL-6003 manual_rel-6_0505 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationSegment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.
egment Protector for Cabinet nstallation Features Assembly 4... 12 outputs Ex ic (FCO or Entity) or non-incendive (Div 2) Advanced fault isolation at the spur egment Protector in Zone 2/Div. 2 nstruments
More informationInductive sensor NI3-EG08K-Y1-H1341
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M8 x 1 Stainless steel, 1.4427 SO DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR)
More informationInductive sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationDeltaV Bulk Power Supplies
DeltaV Distributed Control System Product Data Sheet DeltaV Bulk Power Supplies DeltaV 5 A, 10A, 20 A, 40 A Bulk Power Supplies. DeltaV 20 A, 40 A and 80 A Bulk Power Supply Redundancy Modules. Easy to
More informationQUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:
Extract from the online catalog QUINT-PS/1AC/24DC/10 Order No.: 2866763 DIN rail power supply unit 24 V DC/10 A, primary-switched mode, 1- phase. The SFB technology (Selective Fusebreaking Technology)
More informationInductive dual sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, housing DSU35 Plastic, PP-GF30-VO Two outputs for monitoring the position of rotary actuators Mounting
More informationPSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description
SIL 3 coupling relay for safety-related switch on Data sheet 105818_en_01 PHOENIX CONTACT 2014-08-18 1 Description The PSR-PC50 SIL coupling relay can be used for power adaptation and electrical isolation
More informationMACX MCR-EX-SL-RPSSI-I(-SP)
Repeater power supply and input isolating amplifier, Ex-i Data sheet 103568_en_02 PHOENIX CONTACT 2015-03-26 1 Description The repeater power supply and input signal conditioner is designed for the intrinsically
More information97105 NAMUR. Technical data. Ordering information and accessories See page 6 and 7
90 NAMUR /, / and / directional valves Actuation: electromagnetic Indirectly controlled soft seal spool valves Port size: G /, / NPT, G /, / NPT NAMUR-interface For single and double operated actuators
More informationSegment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.
egment Protector for Cabinet nstallation Features Assembly 4... 12 outputs Ex ic (FCO or Entity) or non-incendive (Div 2) Advanced fault isolation at the spur egment Protector in Zone 2/Div. 2 nstruments
More informationInterface and Supply module. IPC 3x0i / PSC 3x0i
Interface and Supply module IPC 3x0i / PSC 3x0i Installation Guide Version 10 IBS BatchControl GmbH Im Sträßchen 2 4 Tel.: +49 2241 9199801 53925 Kall Fax.: +49 2241 9199871 Germany www.ibs-batchcontrol.com
More informationPSR-PC20. SIL coupling relay. Data sheet. 1 Description
SIL coupling relay Data sheet 106255_en_00 PHOENIX CONTACT 2015-03-13 1 Description Intended Use The PSR-PC20 SIL coupling relay can be used for power adaptation and electrical isolation in high and low-demand
More informationPHOENIX CONTACT - 05/2007
Ex Universal Module Carrier (Motherboard) for Accommodating 3-Wire Measuring Transducers, Intrinsically Safe, for a Maximum of 8 PI Ex Modules INTERFACE Data Sheet 103030_00_en PHOENIX CONTACT - 05/2007
More informationMagnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-EG08-Y1X
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationPosition Switches Series 8070
www.stahl.de > Enclosures of type of protection "Increased safety > Dimensions and characteristic values according to EN 50041 > Replaceable contact in flameproof enclosure > Positive opening contacts
More informationHERION SERIES Indirect solenoid actuated spool valves
HERION SERIES Indirect solenoid actuated spool valves for single and double acting actuators with NAMUR interface /2, /2, /, NC/APB, G/, G/2 Valves for safety systems up to SIL (IEC 08) Crossover-free
More informationInductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi
ATEX category II 2 G, Ex Zone 1 ATEX category II 2 D, Ex Zone 21 Rectangular, housing DSU35 Plastic, PP-GF30-VO Detection of angular range 0 to 360 P1-Ri-QR14 positioning element included in delivery Measuring
More informationSITOP in the SIMATIC Design
Siemens AG 2017 /2 Introduction /3 1-phase, 24 V DC (for S7-300 and ET 200M) /9 1-phase, 24 V DC (for S7-1200) /11 1-phase, 24 V DC (for S7-1500 and ET 200MP) /14 3-phase, 24 V DC (ET 200pro) Siemens KT
More informationSeries 3730 Electropneumatic Positioner Type with PROFIBUS-PA communication
Series 3730 Electropneumatic Positioner Type 3730-4 with PROFIBUS-PA communication Application Positioner for attachment to pneumatic control valves Travels 3.6 to 200 mm Opening angle 24 to 100 Smart,
More informationMINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description
Configurable signal duplicator Data sheet 102382_en_03 PHOENIX CONTACT 2012-05-02 1 Description The MINI MCR-SL-UI-2I(-SP)(-NC) configurable signal duplicator is used to electrically isolate, condition,
More informationINSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069
D09S09 D09D09 INSTRUCTION MANUAL SIL Relay Output Module DINRail Models D09S09, D09D09 D0909 SIL Relay Output Module ISM00 SIL Applications For Safety Related System and SIL, SIL Applications according
More informationQUINT-PS AC/24DC/10
Extract from the online catalog QUINT-PS-100-240AC/24DC/10 Order No.: 2938604 DIN rail power supply unit 24 V DC/10 A, primary switched-mode, 1- phase Commercial data EAN 4017918890537 Pack 1 Pcs. Customs
More informationInductive sensor For rotary actuators NI4-DSU35-2Y1X2-H1140
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationRAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description
I/O extension module, eight digital transistor outputs Data sheet 105364_en_00 PHOENIX CONTACT 2013-03-26 1 Description The I/O extension module can be used in conjunction with Radioline wireless modules
More informationIntrinsically Safe Explosion Proof Barriers
Safety Intrinsically Safe Explosion Proof For more information on this product family, visit our website. Additional resources include: New and updated product information Downloadable software demos &
More informationMagnetic Field Sensor for pneumatic cylinders BIM-INT-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationMagnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationTermination Board FC-GPCS-RIO16-PF. Features. Assembly. Function. Connection USIO/UPIO 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.
Features Assembly System board for Honeywell Universal Safety IO System board for Honeywell Universal Process IO For 6-channel cards USIO and UPIO For 6 modules Recommended modules: HiC8R (DI), HiC85R
More informationOperating Instructions
Introduction To protect the signal lines of field devices and systems in the cabinet against lightning. Pepperl+Fuchs covers the complete range of Surge Protection Barriers. Housing types Depending on
More informationPSR-PS21. SIL coupling relay. Data sheet. 1 Description
SIL coupling relay Data sheet 106253_en_00 PHOENIX CONTACT 2015-03-13 1 Description Intended Use The SIL coupling relay can be used for power adaptation and electrical isolation in high and low-demand
More informationSolConeX Wall-Mounted Socket, 16 A
SolConeX Wall-Mounted Socket, 16 A Operating instructions Additional languages www.stahl-ex.com General Information Contents 1 General Information...2 1.1 Manufacturer...2 1.2 Information Regarding the
More informationTerminal Block Catalog Numbers 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2
Technical Data Communication Adapter Catalog Number 1719-AENTR I/O Module Catalog Numbers 1719-IJ, 1719-IBN8B, 1719-IF4HB, 1719-IR4B, 1719-IT4B, 1719-OB2, 1719-OB2L, 1719-CF4H Power Supply Catalog Number
More informationD1093S INSTRUCTION MANUAL. D SIL 3 Relay Output Module with Line and Load diagnostics. DIN-Rail Model D1093S
D109S INSTRUCTION MANUAL SIL Relay Output Module with Line and diagnostics DINRail Model D109S D109 SIL Relay Output Module with Line and diagnostics ISM0096 SIL Applications For Safety Related System
More informationDeltaV Bulk Power Supplies
DeltaV Distributed Control System Product Data Sheet DeltaV Bulk Power Supplies DeltaV 5 A, 10A, 20 A, 40 A Bulk Power Supplies. DeltaV 20 A, 40 A and 80 A Bulk Power Supply Redundancy Modules. Easy to
More informationINSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F
PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4
More informationType Switching repeater. Safety manual
Type 9170 Switching repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual... 3 1.3 Area of application... 3 1.4
More informationFieldbus Isolating Repeater
Fieldbus Isolating Repeater Manual Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information about the manual...3 1.3 Further documents...3 1.4 Conformity
More informationMiniature Circuit-Breaker IEC Series 8562
> 1 to 3 pole versions > Rated current from 0.5... 40 A > 6 or 10 ka breaking capacity to DI VDE 0641, respectively E 60898 > Isolating Function to E 60947-2 > Permanently set thermal and magnetic trips
More informationTermination Board. HiCTB08-SCT-44C-SC-RA. Features. Assembly. Function. Connection. 24 V DC (I), 24 V DC (II), Fault. Zone 0, 1, 2 Div.
Termination Board HiCTB08-SCT-C-SC-RA Features Assembly For 8 modules V DC supply Supported signal types: DI/DO/AI/TI/AO Hazardous area: screw terminals, blue Safe area: screw terminals, black Function
More informationTechnical Data. General specifications. Rated operating distance s n 3 mm
0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection ATEX & IECEX certifications Usable up to SIL 2 acc. to IEC 61508 Weatherproof
More informationMagnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-EG08-Y1X-H1341
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationSafety instructions. IECEx TUN Ex ia IIC T6 Gb
Safety instructions ÜSB62-36G.C_* and ÜSB62-30W.C_* IECEx TUN 07.0002 Ex [ia Ga] IIC T6 Gb Ex ia IIC T6 Gb 0044 39878 Content 1 Area of applicability 3 2 General 3 3 Electrical data 3 3.1 Application conditions
More informationType 9160 / Transmitter supply unit / Isolating repeater. Safety manual
Type 9160 / 9163 Transmitter supply unit / Isolating repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual...
More informationQUINT-PS/ 1AC/24DC/ 5
Extract from the online catalog QUINT-PS/ 1AC/24DC/ 5 Order No.: 2866750 DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1- phase. The SFB technology (Selective Fuse Breaking Technology)
More informationTRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:
Extract from the online catalog TRIO-PS/1AC/24DC/20 Order No.: 2866381 DIN rail power supply unit, primary-switched mode, 1-phase, output: 24 V DC / 20 A Commercial data EAN 4046356046664 Pack 1 pcs. Customs
More informationTubular Light Fitting with LED Series 6036
> Extremely robust luminaire design for rough ambient conditions > Very lightweight and vibration resistant LED light fitting > Extremely long service life due to LED used > High power LEDs including driver
More informationLoad Disconnect Switches and Motor Switches
Load Disconnect Switches and Motor Switches 594 Load Disconnect Switches and Motor Switches Contents Load Disconnect Switches and Motor Switches Safety Switches made of Resin 10, 12/16, 16, 20, 25, 40,
More informationIntrinsically Safe Barriers
Intrinsically Safe Barriers Description Page No. Safety Barriers 464-472 Din Rail Isolated Barriers 473-488 477 Intrinsically Safe Barriers Product Overview We have simplified intrinsic safety! Cooper
More informationSeries 3730 Electropneumatic Positioner Type
Series 3730 Electropneumatic Positioner Type 3730-0 Application Single-acting or double-acting positioner for attachment to pneumatic control valves Reference variable Travels 4 to 20 ma 5.3 to 200 mm
More informationSafety manual. This safety manual is valid for the following product versions: Version No. V1R0
Safety manual HART TRANSPARENT driver 9107 This safety manual is valid for the following product versions: 9107-002 Version No. V1R0 0. CONTENTS 1. Observed standards... 2 2. Acronyms and abbreviations...
More informationInductive sensor with analog output BI15-M30-LI-EXI
ATEX category II 1 G, Ex-zone 0 ATEX category II 2 D, Ex-zone 21 Threaded barrel, M30 x 1.5 Chrome-plated brass Analog+ Extended operating range 2-wire, 14 30 VDC Analog output 4 20 ma Cable connection
More informationOperating and monitoring systems Panel PC SERIES 400 Device platform EAGLE PM ET-436-TX
Panel PC for panel- mounting, quad core ATOM E3845 15" display, 1024 x 768 pixels with resistive foil touch screen 8 function keys Zone 1, 2, 21, 22 und Division 2, can be installed in hazardous areas
More informationSeries 3730 Type Electropneumatic Positioner
Series 3730 Type 3730-0 Electropneumatic Positioner Application Single-acting or double-acting positioner for attachment to pneumatic control valves Set point Travel 4 to 20 ma 5.3 to 200 mm The positioner
More informationGeneral. Remote I/O A4/1.
www.stahl.de > Intrinsically safe Ex ia IIC, Ex e, Ex na or Ex nl inputs and outputs > Fieldbus communication: Modbus RTU, Profibus DP V0 and DP V1 HART, Industrial Ethernet, Modbus TCP, EtherNet/IP, PROFINET
More information