1 SCHMIDT Sensor interface PROFIBUS Instructions for use
2 Table of contents 1 Important information Intended use Electrical connection Signalizations Startup Technical data Imprint: Copyright 2011 SCHMIDT Technology GmbH All rights reserved Version: A Subject to modifications Instructions for use PROFIBUS Interface Page 2
3 1 Important information The instructions for use contain all required information for a fast commissioning and a safe operation of the SCHMIDT Flow Sensors with Profibus Interface: These instructions for use must be read completely and observed carefully, before putting the unit into operation. Any claims under the manufacturer's liability for damage resulting from non-observance or non-compliance with these instructions will become void. Tampering with the device in any way whatsoever - with the exception of the designated use and the operations described in these instructions for use - will forfeit any warranty and exclude any liability. The unit is designed exclusively for the use described below (see chapter 2). In particular, it is not designed for direct or indirect personal protection. SCHMIDT Technology cannot give any warranty as to its suitability for a certain purpose and cannot be held liable for accidental or sequential damage in connection with the delivery, performance or use of this unit. Symbols used in this manual The symbols used in this manual are explained in the following section.! Danger warnings and safety instructions read them carefully! Non-observance of these instructions may lead to injury of personnel or malfunction of the device. General note All dimensions are indicated in mm. Instructions for use PROFIBUS Interface Page 3
4 2 Intended use The field bus module is used for the communication and configuration of Schmidt flow sensor via PROFIBUS. In addition to the flow velocity, the volume flow can also be output. Threshold values for monitoring can be configured. 3 Electrical connection!! Make sure, there is no voltage during electrical installation and inadvertent activation is not possible. The electrical connection must be carried out by trained and qualified personnel. Housing cover Sensor connector Cable inlets or connectors to field bus module Figure 1 Possibilities for connection The connection of the field bus module can be established, depending on the version, by means of connectors or cable inlets and terminals inside the housing.! During electrical installation ensure that no voltage is applied and inadvertent activation is not possible. Instructions for use PROFIBUS Interface Page 4
5 Operating elements inside the enclosure Terminal resistors Terminals Setting of the node address Figure 2 Operating elements Power supply The power supply of the field bus module is connected to the supply voltage of the sensor. Therefore the device can be supplied with power (24V CC 20%) via the field bus module or via the sensor plug.! Do not connect the power supply to the field bus module and to the sensor at the same time. Instructions for use PROFIBUS Interface Page 5
6 Terminal assignment Pos. Terminal Explanation 1 A Negative serial data line 2 B Positive serial data line 3 UB Operating voltage (24V +/- 20 %) 4 GND Connection to earth 5 A Negative serial data line 6 B Positive serial data line 7 UB Operating voltage (24V +/- 20 %) 8 GND Connection to earth Table 1 Terminal assignment Connection of the shield In order to reach the highest possible electromagnetic immunity, the sensor enclosure must be connected to the shield of the signal lines by fixing it between the plastic cap and the cable entry. Figure 3 Connection of the shield Plug-in connector Plug M12 Socket M12 Pin Signal 1 n.c. 2 A 3 n.c. 4 B 5 n.c. Instructions for use PROFIBUS Interface Page 6
7 User address The user address is set by means of two decimal rotary switches. Possible addresses are between 1 and 99, each address in the system may occur only once. Terminal resistor If the field bus module is integrated as end device, the terminal resistor integrated in the device must be activated. This is done by means of two slide switches. 4 Signalizations LED A DUO LED supplies information about the status of the sensor and the network. LED state Status Description Off Not connected No power supply Yellow Pre-operational The DP slave is ready. However, no cyclic data exchange is carried out with this DP slave at the moment. Green Data Exchange Mode The device works under normal conditions and is online. Data is exchanged cyclically with this DP slave. Red Alarm message of the flow sensor The message is active for at least 2.5 seconds. If the reason for the alarm is not eliminated, the time is prolonged until the alarm is reset. 1Hz: Configuration error Customer-specific parameter is outside the admissible value range Red flashing 5Hz: Faulty factory configuration Factory configuration defective Table 2 LED signals Instructions for use PROFIBUS Interface Page 7
8 Alarms and warning messages Signalize the sensor status in the operating data: Flag Warning flag Meaning Signal when exceeding measuring range Alarm flag Signal of a defective sensor Table 3 Signalizing by means of flags Warning messages activate the OB 82 in the SPS and alarm messages activate the OB 86. These organization modules must be considered and evaluated during the project planning in order to avoid that the CPU changes to the operating state STOP as soon as a warning or error message of the field bus module occurs. Instructions for use PROFIBUS Interface Page 8
9 5 Startup To integrate the SCHMIDT flow sensor via PROFIBUS module into the process control, a CD with an EDS file (SS2a093D.eds) is included in the delivery. The field bus module supports the device classes 1 and 2. After receipt of the configuration and parameter data, the module changes into the "Standard operation mode" (cyclic data exchange (data exchange to PROFIBUS DP-V0). Data exchange in the standard operation mode In the standard operation mode, the flow velocity or the volume flow and, as an option, another byte with limit value, alarm and warning flags is transmitted to the master upon request as 32 bit value. The volume flow and the flow velocity are transmitted in 1/100 of the selected unit (parameter unit selector). Bit no. Byte Flow velocity or volume flow MSB 1 Flow velocity or volume flow 2 Flow velocity or volume flow 3 Flow velocity or volume flow LSB 4 Reserved Lower flag Upper flag Warning flag Alarm flag Two configurations are available Designation Identification "32 Bit" 0xD1 "32 Bit + 0xD1 0x90 Flags" Instructions for use PROFIBUS Interface Page 9
10 Parameterization The manufacturer-specific parameters can be set. The 32-bit parameters are divided into two 16-bit parameters (lo contains the bits 0-15, hi the bits 16-31). Averaging Array Size Sets the number of values for the sliding averaging Data type: Unsigned8 Value range: 1 70 (corresponds to s) Inner Diameter Enter the pipe inner diameter to calculate the volume flow Data type: Unsigned32 Unit: 10µm Value range: Unit Selector This value is used to select the unit of the volume flow or the flow velocity. Data type: Unsigned8 Value range: Value Unit 0 m/s 1 cbm/min 2 cbm/h 3 l/s 4 cbft/min 5 cbft/h 6 reserved Lower Switching Threshold Setting of the lower switching threshold. The switching threshold refers to the selected unit. If this value is not reached, the lower flag is set. Data type: Unsigned32 Unit: see parameter Unit Selector Value range: Upper Switching Threshold Setting of the upper switching threshold. The switching threshold refers to the selected unit. If this value is exceeded, the lower flag is set. Data type: Unsigned32 Unit: see parameter Unit Selector Value range: Instructions for use PROFIBUS Interface Page 10
11 Diagnosis messages On demand the diagnostic data are transmitted from the field bus module to the master. In the operating mode Class 1, the number of diagnostic bytes is 16. In the operating mode Class 2, additional information is available and the total number of diagnostic bytes is 51. The diagnostic data in the octets 1 to 6 correspond to the Profibus standard. From octet 7 on, device-specific diagnostic information is available. Extended Diagnostic Header (Octet 7, Class 1) Length of the expected diagnostic Values: Class 1: 10, Class 2: 45 Alarms (Octet 8, Class 1) Signalizes a sensor defect (alarm flag) Value range: 0 1 Operating Status (Octet 9, Class 1) Reserved Sensor Type (Octet 10, Class 1) Reserved Maximum Measuring Range (Octet 11-12, Class 1) Measuring range of the sensor Unit: cm/s Value range: Unit Selector (Octet 13, Class 1) Unit selector (see parameter description) Warnings (Octet 14, Class 1) Signalizes that the sensor measuring range is exceeded Value range: 0 1 Supported Alarms (Octet 15, Class 1) Supported alarms Value range: 1 Supported Warnings (Octet 16, Class 1) Supported warning messages Value range: 1 Pipe Inner Diameter (Octet 17-20, Class 2) Pipe inner diameter (see parameter description) Instructions for use PROFIBUS Interface Page 11
12 Average Array Size (Octet 21, Class 2) Sliding averaging (see parameter description) Profile Version (Octet 22-23, Class 2) Reserved Software Version (Octet 24-25, Class 2) Value range: Lower Switching Threshold (Octet 26-29, Class 2) Lower switching threshold (see parameter description) Upper Switching Threshold (Octet 30-33, Class 2) Upper switching threshold (see parameter description) Total Measuring Range (Octet 34-37, Class 2) Measuring range in the selected unit Unit: see parameter Unit Selector Operating Overpressure (Octet 38, Class 2) Allowed operating overpressure of the sensor Unit: bar Value range: 0 16 Max. Switching Frequency (Octet 39, Class 2) Configuration of the pulse / switching output: Value Description Hz 3 40 Hz 4 20 Hz 5 16 Hz 6 10 Hz Compact Sensor (Octet 40, Class 2) Gives information about the installation length of the sensor Value Description mm mm mm (remote) mm mm Instructions for use PROFIBUS Interface Page 12
13 Built-in Sensor (Octet 41, Class 2) Design: Value Description 0 Not remote 1 Remote Digital Output Type (Octet 42, Class 2) Digital output type: Value Description 0 Pulse output 1 Switching output Analog Output Type (Octet 43, Class 2) Analog output type: Value Description 1 Voltage ( 0 10 V) 2 Current ( 0 20 ma) 3 Current ( 4 20 ma) Variable Unit Factor (Octet 44-47, Class 2) Reserved Serial number (Octet 48 51, Class 2) Serial number Value range: Instructions for use PROFIBUS Interface Page 13
14 6 Technical data Supply voltage (U B ) 24 VDC 20% Output circuit Baud rate PROFIBUS DP-V0 12 MBaud; 3 MBaud; 1,5 MBaud; 500 kbaud; kbaud; kbaud; 19.2 kbaud; 9.6 kbaud Address Adjustable via rotary switches Operating modes Process data Switch thresholds Warning flag Alarm flag Enclosure - dimensions Type of protection CE conformity Table 4 Data Exchange to PROFIBUS DP-V0 32 bits; volume flow, alternatively flow velocity selectable Upper and lower switching threshold adjustable for flow velocity and volume flow Signalizes if the measuring range is exceeded Signalizes if sensor is defective 67.3 x 56.5 (mm) IP 65 (enclosure) EN (electromagnetic emission) EN (electromagnetic immunity) Instructions for use PROFIBUS Interface Page 14
15 Note Instructions for use PROFIBUS Interface Page 15
16 SCHMIDT Technology GmbH Feldbergstrasse St. Georgen / Schwarzwald Phone +49 (0)7724 / Fax +49 (0)7724 / info@schmidttechnology.de Instructions for use PROFIBUS Interface Page 16
SCHMIDT Programming Tool SS 20.4xx Instructions for Use
SCHMIDT Programming Tool SS 20.4xx Instructions for Use SCHMIDT Programming Tool SS 20.4xx Table of Contents 1 Important Information... 3 2 Field of Application... 4 3 Scope of Delivery... 4 4 Programming
More informationBNI IOL Z019. IO-Link 1.1 sensor hub With extension port User s Guide
BNI IOL102002Z019 IOLink 1.1 sensor hub With extension port User s Guide Balluff Network Interface / IOLink BNI IOL102002Z019 Inhalt 1 Notes for the user 4 1.1. About this manual 4 1.2. Structure of the
More informationBNI IOL A027 BNI IOL A027
BNI IOL-771-000-A027 BNI IOL-772-000-A027 IO-Link Version 1.1 Universel IO-Link Interface With undervoltage / broken coil detection User s Guide Inhalt 1 Notes to the user 2 1.1. About this guide 2 1.2.
More informationDevice manual Profibus encoder. RM30xx RN30xx /00 06/2013
Device manual Profibus encoder RM30xx RN30xx 706355/00 06/2013 Contents 1 Preliminary note................................................. 4 1.1 Symbols used...............................................
More informationBNI IOL E012. IO-Link 1.1 sensor/actuator hub with extension port User's Guide
BNI IOL322E12 IOLink 1.1 sensor/actuator hub with extension port User's Guide Balluff Network Interface / IOLink BNI IOL322E12 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions
More informationBNI IOL K006 BNI IOL K006-C01 BNI IOL-302-S01-K006 BNI IOL-302-S01-K006-C01. IO-Link 1.1 Sensor-Hub / Actuator-Hub User s Guide
BNI IOL302000K006 BNI IOL302000K006C01 BNI IOL302S01K006 BNI IOL302S01K006C01 IOLink 1.1 SensorHub / ActuatorHub User s Guide Content 1 Notes to the user 3 1.1 About this guide 3 1.2 Structure of the guide
More informationVersaMax IP Input Module
Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm
More informationBNI IOL K023 BNI IOL K023. User s Guide
BNI IOL-712-000-K023 BNI IOL-714-000-K023 User s Guide Content 1 Notes 2 1.1. Struture of the guide 2 1.2. Typographical conventions 2 Enumerations 2 Actions 2 Syntax 2 Cross references 2 1.3. Symbols
More informationBNI IOL Z046. IO-Link 1.1 sensor/actuator hub with extension port User's Guide
BNI IOL302002Z046 IOLink 1.1 sensor/actuator hub with extension port User's Guide Balluff Network Interface / IOLink BNI IOL302002Z046 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical
More informationBNI IOL Z046. IO-Link 1.1 Sensor hub with extension port User's Guide
BNI IOL104002Z046 IOLink 1.1 Sensor hub with extension port User's Guide Balluff Network Interface / IOLink BNI IOL104002Z046 Contents 1 General 4 1.1. Structure of the Manual 4 1.2. Typographical Conventions
More informationFACTORY AUTOMATION MANUAL WCS-MBG110 WCS MODBUS RTU INTERFACE MODULE
FACTORY AUTOMATION MANUAL WCS MODBUS RTU INTERFACE MODULE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and
More informationBNI IOL K023 BNI IOL K023. User s Guide
BNI IOL-712-000-K023 BNI IOL-714-000-K023 User s Guide Content 1 s 2 1.1. About this guide 2 1.2. Struture of the guide 2 1.3. Typographical conventions 2 Enumerations 2 Actions 2 Syntax 2 Cross references
More informationProfibus DP Expansion Board
Profibus DP Expansion Board Catalog No. EXBD04 Installation and Operating Manual 10/02 MN1393 Table of Contents Section 1 General Information................................................... 1 1 Introduction.......................................................
More informationBNI IOL K006. IO Link Sensorhub digital User s Guide
BNI IOL-104-000-K006 BNI IOL-102-000-K006 IO Link Sensorhub digital User s Guide Content 1 Notes to the User 2 1.1. About this guide 2 1.2. Structure 2 1.3. Typographical conventions 2 Enumerations 2 Actions
More informationANTAL ELECTRONIC Field Bus and Communication Technology. Manual PDP2CL2. Version 3.08
ANTAL ELECTRONIC Field Bus and Communication Technology Manual PDP2CL2 Version 3.08 ANTAL ELECTRONIC Höfles 4 91322 Gräfenberg Telephone (+49) 09192/9256-0 Fax (+49) 09192/9256-78 Important Notice Antal
More informationRM30xx Profibus Brief instructions efector400
RM30xx Profibus Brief instructions efector400 706414/00 Page 1 of 14 ifm efector gmbh Contents The description may contain deviations from the user system, because different manufacturers or software versions
More informationBNI USB A501. User s Guide
BNI USB-901-013-A501 User s Guide Content 1 Notes for the user 2 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions 2 Enumerations 2 Actions 2 Syntax 2 Cross-references 2
More informationINSTRUCTION MANUAL WCS-Interface Module, DeviceNet
FACTORY AUTOMATION INSTRUCTION MANUAL WCS-Interface Module, DeviceNet WCS-DG210 Part. No. 202340 / DOCT-1305 / 11. june 2007 1 Working principle............................ 6 2 Installation and commissioning.................
More informationRMx621. Appendix to the operating manual
Appendix to the operating manual RMx621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 to PROFIBUS DP via the RS485 serial interface using the external module (HMS AnyBus Communicator
More informationBIC 1B0-ITA50-Q40KFU-SM4A4A BIC 1B0-IT005-Q40KFU-SM4A4A BIC 2B0-ITA50-Q40KFU-SM4A5A. User s Guide
BIC 1B0-ITA50-Q40KFU-SM4A4A BIC 1B0-IT005-Q40KFU-SM4A4A BIC 2B0-ITA50-Q40KFU-SM4A5A User s Guide Table of contents 1 Safety 2 1.1. Installation and startup 2 1.2. General safety instructions 2 Hazardous
More informationGFK-2415A March Type of sensor connection
VersaMax IP Expansion Module has four analog differential inputs that can be configured as current or voltage inputs. It connects to a local bus that is interfaced to a Profibus-DP / PROFINET network by
More informationBNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide
BNI PBS-104-000-Z001 BNI PBS-302-000-Z001 BNI PBS-501-000-Z001 BNI PBS-502-000-Z001 Short Guide English 1 2 3 4 Notes to the User 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical
More informationOperation Manual Profibus DP -Display HE 5120 P with digital I/O's
Operation Manual Profibus DP -Display HE 510 P with digital I/O's "HESCH" Schröder GmbH Boschstraße 8 31535 Neustadt Telefon +49 (0) 503 / 9535-0 Telefax +49 (0) 503 / 9535-99 e-mail: info@hesch.de http://www.hesch.de
More informationEL731 PROFIBUS INTERFACE
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/el731 EL731 PROFIBUS INTERFACE Revision 0-A-032816 Copyright 2016 Littelfuse Startco All rights reserved. Document Number: PM-1011-EN
More informationRMx621 /FML621. Appendix to the operating manual
Appendix to the operating manual RMx621 /FML621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 /FML621 to PROFIBUS DP via the RS485 serial interface using the external module
More informationBNI IOL Z036 BNI IOL Z037. Smart Light User s Guide
BNI IOL800000Z036 BNI IOL800000Z037 Smart Light User s Guide Content 1 Notes to the user 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical conventions 3 Enumerations 3 Actions 3 Syntax
More informationAS-i Safety Relay Output Module with Diagnostic Slave
AS-i Safety Relay Output Module with Diagnostic Slave User Manual...supports the requirements for AS-i Safety up to SIL3 Revision date: 2016-03-9 Subject to modifications without notice. Generally, this
More informationPKP Prozessmesstechnik GmbH. Borsigstrasse 24. D Wiesbaden-Nordenstadt. Tel: / Fax: / Operating manual PSA06
PKP Prozessmesstechnik GmbH Borsigstrasse 24 D-65205 Wiesbaden-Nordenstadt Tel: 06122 / 7055-0 Fax: 06122 / 7055 50 Operating manual PSA06 Electronical pressure switch Content Page 19-34 1. Foreword 19
More informationBNI IOL Z036 BNI IOL Z037. Smart Light User s Guide
BNI IOL802102Z036 BNI IOL802102Z037 Smart Light User s Guide Content 1 Notes to the user 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical conventions 3 Enumerations 3 Actions 3 Syntax
More informationHardware Manual RM CANview
Hardware Manual RM CANview 1998-2005 RM Michaelides Software & Elektronik GmbH Donaustraße 14 D-36043 Fulda Germany cv_hw_e.doc Table of Contents 1 Legal Regulations...3 2 About the CANview...4 3 Important
More informationVersaMax IP I/O Module
Module accepts four digital input signals and provides four digital outputs. It connects to a local bus that is interfaced to a Profibus-DP / PROFINET network by a Profibus Interface Unit (IC677PBI001)
More informationBNI IOL K006 BNI IOL-106-S01-K006 BNI IOL-106-S01-K006-C01. User s Guide
BNI IOL106000K006 BNI IOL106S01K006 BNI IOL106S01K006C01 User s Guide Content 1 Notes to the user 2 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions 2 Enumerations 2 Actions
More informationBNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 Short Guide
BNI DNT-104-000-Z004 BNI DNT-202-000-Z005 BNI DNT-302-000-Z005 BNI DNT-305-000-Z005 Short Guide English 1 2 3 4 Notes to the User 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical
More informationThe accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
User Manual INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
More informationBNI IOL Z012 BNI IOL-302-S01-Z012 BNI IOL Z042
BNI IOL102000Z012 BNI IOL104000Z012 BNI IOL104S01Z012 BNI IOL104S01Z012C01 BNI IOL104S01Z012C02 BNI IOL302000Z012 BNI IOL302S01Z012 BNI IOL302000Z042 User s Guide Inhalt 1 Notes for the user 2 1.1. About
More informationInstallation instructions Diagnostic electronics for vibration sensors VSE / / 2007
Installation instructions Diagnostic electronics for vibration sensors UK VSE00 70406 / 00 07 / 2007 Contents Safety instructions 3 Function and features 4 Mounting 4 Mounting of the sensors 5 Electrical
More informationSCH108BEX. Technical Manual. Scancon Encoders Huginsvej Hillerød Denmark Tlf Fax
SCH108BEX Technical Manual 1 Introduction The SCH108BEX Encoder is an Ex-proof, Absolute Multiturn Encoder designed primarily for use in oilfield applications where reliability is critical, but can also
More informationBIS L x-07-S4
BIS L-409-045-00x-07-S4 Quick Guide 41 English www.balluff.com 1 2 3 4 5 Notes to the user 5 1.1 bout this manual 5 1.2 Structure of the manual 5 1.3 Typographical conventions 5 1.4 Symbols 5 1.5 bbreviations
More informationThe accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual
More informationCC2 Series Electric functioning manual
pagina 1/29 CC2 Series Electric functioning manual CANOPEN Fieldbus Node Conforming to normative ISO 11898-1 pagina 2/29 SAFETY INSTRUCTIONS To use this product safely, basic knowledge of pneumatic equipment,
More informationOperating instructions AC010S Compact AS-i E-STOP safety module
Operating instructions AC010S Compact AS-i E-STOP safety module Sachnr. 7390636_/00 05/2007 Contents Safety instructions............................. 3 Installation / Setup............................
More informationOperating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO
Order Number: 8160.UISO Status: V3; 17.09.2010c G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 UMB ISO CONVERTER ISOCON... 6 CONFIGURATION...
More informationILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description
Inline Block IO Module for PROFIBUS With 32 Digital Outputs AUTOMATIONWORX Data Sheet 6889_en_04 Description PHOENIX CONTACT - 03/2007 & & ' ) The ILB PB 24 DO32 module is designed for use within a PROFIBUS
More informationFLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet
Fieldline Modular Device With Eight Digital Inputs Data Sheet 697000 02/2004 This data sheet is only valid in association with the FLS FLM SYS INST UM E user manual or the user manual for your bus system
More informationAS-i Safety Relay Output Module with Diagnostic Slave
AS-i Safety Relay Output Module with Diagnostic Slave User Manual Revision date: 2013-01-30...supports the requirements for AS-i Safety up to SIL3 Subject to modifications without notice. Generally, this
More informationDF PROFI II CPCI. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II CPCI KUNBUS
DF PROFI II CPCI Installation Instructions V1.7 27.02.2017 Project No.: 5302 Doc-ID.: DF PROFI II CPCI KUNBUS h:\dokumente\project\5302_df_profi_ii\anwenderdoku\installation\cpci\kunbus\version_1.6\df
More informationDF PROFI II PCIe. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II PCIe KUNBUS
DF PROFI II PCIe Installation Instructions V1.6 27.02.2017 Project No.: 5302 Doc-ID.: DF PROFI II PCIe KUNBUS h:\dokumente\project\5302_df_profi_ii\anwenderdoku\installation\pcie\kunbus\version_1.5\df
More informationBNI USB A501. USB IO-Link Master User's Guide. english
User's Guide english 1 2 4 Notes to the user 1.1 About this guide 1.2 Structure of the guide 1. Typographical conventions 1.4 Symbols 1.5 Abbreviations Safety 4 2.1 Intended use 4 2.2 General safety notes
More informationBNI PNT Z015 BNI PNT Z015 BNI PNT Z015 BNI PNT Z015 BNI PNT Z015. IP67 Modules User s Guide
BNI PNT-104-105-Z015 BNI PNT-202-105-Z015 BNI PNT-206-105-Z015 BNI PNT-302-105-Z015 BNI PNT-305-105-Z015 IP67 Modules User s Guide Content 1 Notes 3 1.1. About this guide 3 1.2. Structure of the guide
More informationOperating Manual. English. Digital-Analog Converter DACON8-UMB.
English Digital-Analog Converter www.lufft.de G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany. We reserve the right to amend technical specifications at any time. Contents 1 Please Read Before
More informationABB Drives. User s Manual. Modbus Adapter Module RMBA-01
ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview
More informationUser Manual BLCDP-2M12MT-2RFID-S
User Manual : 2010-6-18 All brand and product names are trademarks or registered trade marks of the owner concerned. Hans Turck GmbH, Mülheim an der Ruhr All rights reserved, including those of the translation.
More informationBNI PBS Z001 BNI PBS Z001 BNI PBS Z001. Quick start guide
BNI PBS-104-000-Z001 BNI PBS-102-000-Z001 BNI PBS-302-000-Z001 Quick start guide Content 1 Notes for the User 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations
More informationBNI IOL K023 BNI IOL K023. User s Guide
BNI IOL-712-000-K023 BNI IOL-714-000-K023 User s Guide 1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions 2 1.3.1 Enumerations 2 1.3.2 Actions 2 1.3.3
More informationPROFIBUS MODULE (CB15) English Operating Instructions. Contents. Warning and Caution Notes
Contents Warning and Caution Notes 1. OVERVIEW 1.1 Description and Features 1.2 Application on a PROFIBUS Link 2. INSTALLATION 2.1 Connecting the Bus Cable 2.1.1 Terminals 2.1.2 Bus Cabling 2.2 EMC Measures
More informationQuick Start Guide EAx580 EtherNet/IP encoder
Quick Start Guide EAx580 EtherNet/IP encoder 06.18 174.02.078/1 Subject to modification in technic and design. Errors and omissions excepted. Content 1 Introduction... 3 2 Safety and Operating Instructions...
More informationCVIC II - CVIL II - CVIR II - MULTICVIL II - Memory Mapping - Manual
1/36 CVIC II - CVIL II - CVIR II - MULTICVIL II - Memory Mapping - Manual N - Copyright 2011, St Herblain France All rights reserved. Any unauthorized use or copying of the contents or part thereof is
More informationBNI IOL K006 BNI IOL K006-C01 BNI IOL-302-S01-K006 BNI IOL-302-S01-K006-C01. IO-Link 1.1 Sensor-Hub / Actuator-Hub User s Guide
BNI IOL302000K006 BNI IOL302000K006C01 BNI IOL302S01K006 BNI IOL302S01K006C01 IOLink 1.1 SensorHub / ActuatorHub User s Guide Content 1 Notes to the user 2 1.1 About this guide 2 1.2 Structure of the guide
More informationBNI PBS Z001. IP67 module, Profibus IO-Link Master Short Guide
BNI PBS-502-001-Z001 IP67 module, Profibus IO-Link Master Short Guide 1 Notes for the User 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations 2 1.3.2
More informationFACTORY AUTOMATION. MANUAL Absolute Rotary Encoder with PROFIBUS Interface
FACTORY AUTOMATION MANUAL Absolute Rotary Encoder with PROFIBUS Interface R With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationBNI IOL Z036 BNI IOL Z037. Smart Light User s Guide
BNI IOL801102Z036 BNI IOL801102Z037 Smart Light User s Guide Content 1 Notes to the user 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical conventions 3 Enumerations 3 Actions 3 Syntax
More informationHMG 11. Features. Optional Additional incremental output (TTL / HTL) HMG 11. Technical data - mechanical design. Technical data - electrical ratings
Features Multiturn / SSI / Profibus / CANopen / DeviceNet / PROFINET Optical sensing method Singleturn 1 bit, multiturn 1 bit / 16 bit Blind or through hollow shaft or cone shaft ø16-0 mm Multiturn sensing
More informationDeviceNet Expansion Board
DeviceNet Expansion Board Catalog No. EXBD05 Installation and Operating Manual 10/02 Table of Contents Section 1 General Information................................................... 1 1 Introduction.......................................................
More informationBNI IOL-104-S01-Z012-C02
BNI IOL104S01Z012C01 BNI IOL104S01Z012C02 BNI IOL302S01Z013C01 User s Guide Balluff Network Interface / IOLink 1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical
More informationUser Manual Gateway component for EtherNet/IP
User Manual Gateway component for EtherNet/IP PR100066 1/7/2016 Table of Contents KUNBUS GmbH Table of Contents 1 General Information... 3 1.1 Disclaimer... 3 1.2 Notes Regarding this User Manual... 4
More informationOperating instructions Safe AS-i input module ASIM-C-M About this document. Content
7 Set-up and maintenance 7.1 Functional testing....10 7.2 Maintenance...10 EN Operating instructions.............pages 1 to 6 Original 8 Disassembly and disposal 8.1 Disassembly....10 8.2 Disposal...10
More informationBNI IOL Z012. User s Guide
BNI IOL-719-002-Z012 User s Guide Content 1 Notes for the user 3 1.1. Structure of the guide 3 1.2. Typographical Conventions 3 Enumerations 3 Actions 3 Syntax 3 Cross references 3 1.3. Symbols 3 1.4.
More informationCANopen IO X4 Fact sheet
CANopen IO X4 Fact sheet Overview The CANopen IO X4 is a very compact and cost effective CANopen IO module featuring a high-density of industrial proven IO's. The module includes a CPU-core including the
More informationUser Manual PROCESS FIELD BUS. Absolute Rotary Encoder with Profibus-DP-Interface SAG-DPB1B-XXXX-XXXX-0CC. User Manual
User Manual PROCESS FIELD BUS Absolute Rotary Encoder with Profibus-DP-Interface SAG-DPB1B-XXXX-XXXX-0CC User Manual Revision 01/07 Info SAG-DPB1B Page 1 1 General... 4 1.1 Absolute Rotary Encoder... 4
More informationPROFI-8455 PROFIBUS Remote I/O Unit
PROFI-8455 PROFIBUS Remote I/O Unit Introduction Quick Start User Guide This user guide introduces the user how to implement the PROFI-8455 into their applications in a quick and easy way. Therefore, it
More informationPolymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3
Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger
More informationSIMATIC. ET 200AL Interface module IM DP (6ES7157-1AA00-0AB0) Preface. Documentation guide. Product overview. Wiring 3.
Preface Documentation guide 1 SIMATIC ET 200AL Interface module IM 157-1 DP (6ES7157-1AA00-0AB0) Manual Product overview 2 Wiring 3 Parameters 4 Interrupts, error messages, diagnostics and system 5 alarms
More informationBNI PNT Z015 BNI PNT Z015. IP67 Module User s Guide
BNI PNT-502-105-Z015 BNI PNT-508-105-Z015 IP67 Module User s Guide Table of contents 1 General 3 1.1. About this manual 3 1.2. Structure of the manual 3 1.3. Typographical conventions 3 Enumerations 3
More informationSK CU4-CAO Part number:
SK CU4-CAO Part number: 275 271 001 CANopen Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their technical
More informationSK TU4-IOE-M12-C Part Number
SK TU4-IOE-M2-C Part Number 275 28 256 IO Extension Only qualified electricians are allowed to install and commission the module described below. An electrician is a person who, because of their technical
More informationBNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005. User s Guide
BNI DNT-104-000-Z004 BNI DNT-202-000-Z005 BNI DNT-302-000-Z005 BNI DNT-305-000-Z005 BNI DNT-305-007-Z005 User s Guide Contents 1 User instructions 3 1.1. Structure of the guide 3 1.2. Typographical conventions
More informationSK TU4-PBR Part number:
SK TU4-PBR Part number: 275 281 100 PROFIBUS DP External Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their
More informationOPERATION MANUAL. PROFIBUS Model 9163
OPERATION MANUAL PROFIBUS Model 9163 2008 burster präzisionsmesstechnik gmbh & co kg All rights reserved Manufacturer: burster praezisionsmesstechnik gmbh & co kg Talstrasse 1 5 P.O. Box 1432 76593 Gernsbach,
More information270 MHz Control Modules
2400 / 2420 / 2450 Performance Drives A D D E N D U M 270 MHz Control Modules Notices 2000.40(A2) 01 11/08 Copyright 2002-2008 by Unico, Incorporated. All rights reserved. No part of this publication may
More informationOperating instructions. C9302-K0 Control computer for XC-Boards with Profibus DP interface BAL C9302 PFB EN 1.21
Operating instructions C9302-K0 Control computer for XC-Boards with Profibus DP interface BAL C9302 PFB EN 1.21 GERMANY FRANCE Siebert Industrieelektronik GmbH Siebert France Sarl Siebertstrasse, D-66571
More informationSK TU4-CAO-C Part number:
SK TU4-CAO-C Part number: 275 281 151 CANopen External Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their
More informationQUICK START GUIDE IC-KP2-*
FACTORY AUTOMATION QUICK START GUIDE IC-KP2-* IDENTControl Compact control interfaces With regard to the supply of products, the current issue of the following document is applicable: The General Terms
More informationENCODER SERIES Pxx WITH PROFIBUS-DP INTERFACE
Profibus-DP Documentation ENCODER SERIES Pxx WITH PROFIBUS-DP INTERFACE PxxDocSTD R3/06/00 1 CONTENTS: 1. Mechanical installation:... 3 2. Electric installation:... 3 2.1 Connections... 3 2.2 Termination...
More informationUser manual Gateway component Sercos
User manual Gateway component Sercos DO0227R00 6/28/2016 Table of Contents KUNBUS GmbH Table of Contents 1 General Information... 3 1.1 Disclaimer... 3 1.2 Notes Regarding this User Manual... 3 1.3 Validity...
More informationMAXIMA + Series ROTARY LEVEL CONTROL
Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 Rev. A
More informationBNI IOL Z013 BNI IOL-302-S01-Z013. User s Guide
BNI IOL302000Z013 BNI IOL302S01Z013 User s Guide Balluff Network Interface / IOLink BNI IOL302xxxZ013 1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions
More informationSerial PROFIBUS Interface
Installation Manual Serial PROFIBUS Interface Version: EN-062016-2.3 Copyright 2016 Softing Industrial Automation GmbH Disclaimer of liability The information contained in these instructions corresponds
More informationBNI IOL Z026 BNI IOL-302-S01-Z026 User s Guide
BNI IOL302000Z026 BNI IOL302S01Z026 User s Guide 1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions 2 1.3.1 Enumerations 2 1.3.2 Actions 2 1.3.3 Syntax
More informationBNI IOL Z026 BNI IOL-302-S01-Z026. User s Guide
BNI IOL302000Z026 BNI IOL302S01Z026 User s Guide Balluff Network Interface / IOLink BNI IOL302xxxZ026 1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions
More informationOperating instructions Memory plug E /02 11/2011
Operating instructions Memory plug E30398 UK 704930/02 11/2011 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Terms used...3 2 Safety instructions...4 3 Factory setting...4 4 Functions and features...5
More informationSK CU4-PBR-C Part number:
SK CU4-PBR-C Part number: 275 271 500 PROFIBUS DP Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their
More informationAMG 11. Features. Optional. Additional incremental output (TTL / HTL) AMG 11. Technical data - mechanical design. Technical data - electrical ratings
Features Multiturn SSI / Profibus / CANopen / DeviceNet / PROFINET Optical sensing method Singleturn 1 bit, multiturn 1 bit / 16 bit EURO-flange B10 / solid shaft ø11 mm Multiturn sensing with microgen
More informationCEM M-RS485 INSTRUCTION MANUAL (M014B A)
Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could
More informationManual. Decentralized Drive Control MOVIFIT FDC-SNI Connection to PROFIBUS/DeviceNet with UFF41B Fieldbus Gateway
Drive Technology \ Drive Automation \ System Integration \ Services Manual Decentralized Drive Control MOVIFIT FDC-SNI Connection to PROFIBUS/DeviceNet with UFF4B Fieldbus Gateway Edition 0/0 950 / EN
More informationProfibus Gateway 3E V Technical Bulletin
Profibus Gateway 3E V1.0.0 Technical Bulletin TECHNICAL BULLETIN 2 Profibus Gateway 3E Liability for errors and misprints excluded. V1.0.0en/23.06.16 TECHNICAL BULLETIN Profibus Gateway 3E V1.0.0en/23.06.16
More informationSupplementary instructions Sigma X control type with PROFIBUS
Supplementary instructions Sigma X control type with PROFIBUS EN These operating instructions are only valid in combination with the "Operating instructions for diaphragm motor driven dosing pump Sigma
More informationSINGLE AND MULTI TURN ABSOLUTE ENCODER
SINGLE AND MULTI TURN ABSOLUTE ENCODER MEM-Bus with Profibus protocol Operating Manual CONTENTS 1. Safety and operating instructions... 1 Encoder purpose... 1 Installation... 1 Safety... 1 2. Generals...
More informationOperating Instructions for Low Volume Rotating Vane Flow Meter. Model: DPL-1P... DPL-1V... DPL-1E...
Operating Instructions for Low Volume Rotating Vane Flow Meter Model: DPL-1P... DPL-1V... DPL-1E... 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 5. Operating
More informationMAXIMA+ Series Rotary Level Indicator
MAXIMA+ Series Rotary Level Indicator BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE
More informationUSBoard. Operating Manual. Version November USBoard-OperatingManual Neobotix GmbH all rights reserved 1 of 25
USBoard Operating Manual Version 1.7.3 15 November 2017 USBoard-OperatingManual Neobotix GmbH all rights reserved 1 of 25 Contents 1 Introduction...3 2 Technical data...3 2.1 USBoard... 3 2.2 Ultrasonic
More information