DCA - 10 / DCA TTS Systems

Size: px
Start display at page:

Download "DCA - 10 / DCA TTS Systems"

Transcription

1 DCA - 10 / DCA - 20 Two Channell Load Cell Amplifie er Refere ence Manua al TTS Systems 14 Highpoint Business Village, Henwood,, Ashford, Kent,, TN24 8DH Telephone +44 (0) Telefax info@tts-systems.com internett Version 1 Page 1 of 12

2 DCA 10 / DCA 20 Amplifier Table of Contents DCA-10 and DCA-20 Two Channel Amplifier for Strain Gauges... 3 Mode of Operation... 3 Principle of Operation... 4 Connecting the Transducers... 4 Commissioning the DCA-10 and DCA Calibration by keypad Selection of the channel(s) to be calibrated Selection of the function to perform Calibration... 5 Using the Ranging Facility... 6 The module DCA - 10 / DCA - 20 is to receive data The module DCA - 10 / DCA - 20 is to return data... 8 Connection Diagram DCA - 10:... 9 General Arrangement Diagram DCA - 10:... 9 Connection Diagram DCA - 20: General Arrangement Diagram DCA - 20: Technical Data DCA - 10 / DCA IMPORTANT SAFETY INFORMATION To conform with the Health and Safety at Work Act (1974) this product should be installed, used and maintained by competent persons in accordance with normal safety procedures, the information contained herein and any other relevant norms or standards. Version 1 Page 2 of 12

3 DCA-10 and DCA-20 Two Channel Amplifier for Strain Gauges The modules DCA-10 and DCA-20 have been developed to allow connection to strain gauges that are configured as a full bridge resistive network. The modules are typically used with load cells / transducers in web tension applications. Calibration of the tare and span is performed by microprocessors. The unit has several analogue output signals producing V for both indication and control functions. The excitation voltage for the measuring elements is also provided and is fixed at 10V. The input range per load cell to the amplifier is between 2mV to 25mV. Two load cells can be connected to each amplifier separately to provide independent individual outputs or when used as a pair they provide an average value. The power supply to the unit is 24V DC. The amplifiers are modular units and can be mounted onto a DIN rail, type TS35. Special features: Automatic zeroing Automatic calibration to rating Proportional calibration by applying a fraction of the full scale load Three measuring ranges to increase the range of low forces without the need for re-calibration Dampened outputs for connection to measuring devices Optional operation via keys or RS 485 serial link The following modes of operation are possible: Two load cells on one sensing roll to give a separate signal for channel A and channel B plus the average A+B signal. Separate independent load cells on individual rolls to give isolated signals for both channel A and channel B (do not use A+B outputs in this mode) Mode of Operation There are two modes for commissioning the module. Mode 1 On board keypad Mode 2 RS 485 via PC [TTS Systems can supply a USB to RS485 converter interface] By default the module is supplied in keypad mode. Selection of Modes The module is supplied in keypad mode as a default. If you wish to use the RS 485 mode the following procedure is required. Switch off power to the module Pressing the UP and ENTER keys simultaneously on power up will place the module in the RS 485 serial link mode. The LED RS485 would illuminate to confirm the module is in communication mode. The remaining LED s will display the bus address in binary format. The required address can now be selected by using the keypad UP and ENTER keys. The ENTER key has the function as DOWN. To save the address you have to keep pressed the last used key and at the same time press the second key. To revert back to keypad mode the bus address 0 has to be entered. Attention! If an address other than zero (0) is selected it is not possible to carry out the calibration via the keypad. The LED OK being permanently lit shows this is in the operational mode. Calibration of the module using the keypad Adjustment for zeroing the dead weight and calibration to the required load is carried out by using the two keys located on the front of the housing. The procedure involves selection of the calibration channel(s) then either the zero offset [Zero], calibration [Cal] or proportional calibration [Prop]. Version 1 Page 3 of 12

4 Once confirmation of the selected function is made the module will indicate whether to unload or load the sensing roller before carrying out the required function. Principle of Operation For correct operation the amplifier output must be zeroed and calibrated to remove the dead weight (zero or tare). During this operation the microprocessor will negate the effects of the deadweight to provide a zero reference value. On completion the amplifier will indicate 0V when no web is present. The next stage is to place a load onto the sensing roller according to the MAXIMUM tension required. The amplifier will adjust automatically to give an output voltage on the appropriate channel(s) that will be equal to 10V at full scale. Please note that the sensing roller load must follow the production web path. If full loading is not possible then the proportional mode must be selected and a reference voltage scaled proportionally to this load is created before calibration can proceed. The appropriate output channel(s) will then assume this voltage whereby the full-scale output will be equal to 10V. Changing the measuring range without new calibration or load cells If different materials with different tensions are used the measuring range of the amplifier can be increased without the need to re-calibrate and making use of the same load cell rating. The switching between the ranges is carried out by the active low digital inputs. With this method it is possible to adjust the signal output to provide 0 10V proportional to 25%, 50% or 75% of the actual calibrated load. Connecting the Transducers When interfacing the transducers the following points should be taken into account. The convention adopted here is that when using with TTS transducers these should be orientated such that the red spot is positioned away from the web angle bisector as shown in the following diagrams. A B C If the wiring is incorrect the amplifier may fail to calibrate successfully to give the 0 10V output. It is a straightforward procedure to establish that the amplifier is correctly wired. 1. Connect a meter to load cell signal terminals. Check channels A and 8888 B. Meter positive should be on Sig + and meter negative on Sig of Sig + the transducer. 2. Note the no load voltage and observe the polarity. Sig - 3. Load the sensing roll and note the output voltage again and observe the polarity. 4. Calculate the difference between the No load and Loaded voltage (in millivolts). 5. If the load cell is correctly wired when increasing the load the resultant signal should be positive going i.e. if the off set voltage is minus 7 millivolts on the no load condition and the resultant voltage with load is minus 3 millivolts this would indicate that the transducer and the wiring are correctly orientated. Version 1 Page 4 of 12

5 Commissioning the DCA-10 and DCA-20 Calibration by keypad 1. Selection of the channel(s) to be calibrated By repeated usage of the key UP the channel to be calibrated is selected The following channels can be calibrated: Standard condition LED is lit Channel A and channel B together LED A and B are lit Channel A LED A is lit Channel B LED B is lit After selection of the required channel the ENTER key has to be pressed for confirmation. 2. Selection of the function to perform By repeatedly pressing the UP key the desired function is selected. The following functions are possible: Zero tare LED ZERO is lit Calibration LED CAL is lit Proportional Calibration LED CAL and LED PROP are lit Return to the selection of the channel (non of the above LED s are lit) On arriving at the required function the ENTER key has to be pressed to confirm the selection 3. Calibration a) Zero adjustment Following the selection of the channel(s) to be calibrated as described above and by placing the module into zero mode the LED ZERO should be lit. The LED UNLOAD should also be lit and automatic zeroing can then be performed. Remove all material on the sensing roll and confirm this by pressing ENTER. The LED UNLOAD goes off and the automatic zeroing is performed. Do not put any weights on the roll during this process. After the process is finished the LED OK should light up for approximately 2 seconds. All other LED s should be off. If the zeroing function was not successful (as range was exceeded), the LED ERROR will light to show this. Correct error and start procedure again. The device is ready for the next adjustment or for operation b) Span Adjustment (Calibration) Following the selection of the channel(s) to be calibrated as described above and by placing the module into calibration mode the LED CAL should be lit. The LED LOAD should also be lit and automatic calibration can then be performed. This point will automatically be selected if you have carried out a zero function. Place a load on the sensing roller as described in the load cell manual. Confirm this by pressing ENTER. The LED LOAD goes off and the automatic calibration process is performed. Do not touch the sensing roll during this process. After the process is finished the LED OK should light up for approximately 2 seconds. All other LED s should be off. If the calibration function was not successful (as range was exceeded or there was insufficient load) the LED ERROR will light to show this. Correct error and start procedure again. The device is ready for the next adjustment or for operation Version 1 Page 5 of 12

6 c) Proportional calibration If you do not have a full load to apply to the sensing roll then you will need to select proportional calibration mode. Following the selection of the channel(s) to be calibrated as described above and by placing the module into proportional calibration mode the LED CAL and the LED PROP should be lit. THE LED CAL will blink. You can now adjust the required tension for the load as a percentage value given in Volts (in 40mV steps) with the keys UP and ENTER measured across the PROP OUT terminals. At this point the ENTER key will function as DOWN. Once this is done you can leave the adjustment mode by pressing down the last used key and at the same time the second key. Place the proportional load on the sensing roller as described in the load cell manual. Confirm this by pressing, ENTER. The LED LOAD and LED PROP go off and the automatic calibration process is performed. Do not touch the sensing roll during this process. After the process is finished the LED OK should light up for approximately 2 seconds. All other LED s should be off. If the calibration function was not successful (as range was exceeded or there was insufficient load) the LED ERROR will light to show this. Correct error and start procedure again. The device is ready for the next adjustment or for operation Example: If the required TOTAL load is 100kg but the available load is only 25kg then 2.5V has to be created across the PROP CAL output terminals i.e. 25% of 10V is 2.5V 5.0V is equal to 50%, 7.5V is equal to 75% etc. Formulae is given as Proportional Load x 10 in Volts Full Sale Load Using the Ranging Facility The digital input (terminals 13,14 or 15, 16 DCA - 20 ) or (terminals 9,10 or 12,13 DCA - 10) have to be connected to GND. This can be tested by varying the load on the sensing roll in accordance to the range selected to indicate that the appropriate output terminals still give 0 10V at the new load with 25%, 50% or 75% of the calibrated value. Version 1 Page 6 of 12

7 Calibration via the RS485 serial point The communication with the amplifier is done via the RS 485 serial link with the following described protocols. Parameter of the serial link: 9600 Baud, 8 data bits, No Parity, 1 stop bit ( N-1) The module DCA - 10 / DCA - 20 is to receive data. Addressing the module : Starting Module Module Number of Type of Data byte 1 Data byte 2 Data byte n End of Block sign address address data bytes data sign Check STX ADR ADR LEN TYP DAT DAT DAT ETX BCC When the module DCA-10 / DCA-20 recognises an incorrect build up of the data frame or an incorrect BCC it will answer with the sign NAK. If the data frame has been received correctly, the DCA-10 / DCA-20 will show the sign ACK and will wait for the sign ENQ in order to confirm with the sign EOT if the receipt is correct. This finishes the communication and the amplifier carries out the required function. Example of a data frame: To zero channel A and B at module address 04h: Starting sign STX (02h) Module address ADR (04h) Module Address ADR (04h) Number of data bytes LEN (03h) Type of data TYP (00h) Data byte 1 DAT (01h) Data byte 2 DAT (01h) Data byte 3 DAT (01h) End of sign ETX (03h) Block Check BCC (01h) The sent data bytes will carry out the following functions: Data byte Function Possible selection Data byte 1 Selects the calibration via RS 485 Always High Data byte 2 Selects the channel to be calibrated 0 = no selection 1 = channel A and B 2 = only channel A 3 = only channel B Data byte 3 Selects the range to be calibrated 0 = no selection 1 = zero point (TARE) 2 = amplification 3 = proportional calibration Data byte 4 Low byte percentage value 00 hex 99 hex Data byte 5 High byte percentage value 00 hex 99 hex * The information for the 4 th and 5 th data byte is only required for the proportional calibration. Example: If you want to calibrate 25,00% of the required load the following data has to be sent: Low byte = 00 High byte = 25 Notes The master always sends the module address twice, so that an interruption in the supply will not be responsible for addressing the wrong module. The calculation of the BCC- bytes on all the transmitted data except STX and BCC are linked by an EXCLUSIVE OR. No more than 10 byte data can be transferred as one block. If address 0 is sent then all modules that are connected to the bus are addressed Version 1 Page 7 of 12

8 The module DCA - 10 / DCA - 20 is to return data Request to the module : Starting Module Module Number of Type of Request to sign address address data bytes data send STX ADR ADR LEN TYP ENQ Enter 0 in LEN. Example of a data frame : To receive a measured value on channel A at address 04h: Starting sign STX (02h) Module address ADR (04h) Module address ADR (04h) Number of data bytes LEN (00h) Type of data TYP (01h) Request to send ENQ (05h) The module replies with the following data : Start sign Module Number of Type of Data byte 1 Data byte 2 Data byte n End sign Block address data bytes data Check STX ADR LEN TYP DAT DAT DAT ETX BCC Note : If the receiving device sees the wrong construction of a data frame or a wrong BCC, it will answer with the sign NAK. The DCA-10 / DCA-20 is requested to send a new data frame. This has to be repeated 3 times at most. If the data frame was received correctly the receiving device will send the message ACK and waits for the sign EOT from the module DCA-10 or DCA-20. The communication is now finished. The request for sending will enable the following function: Type Byte Function Possible Selection Type Selects the data to be sent 0 = send all analogue values 1 = send value of channel A 2 = send value of channel B 3 = send status report The status message can have the following meaning: Data byte = 0 calibration successful or Data byte = 1 calibration unsuccessful If you request the analogue values the values received will always consist of two data bytes. The first representing the low-byte and the second the high-byte of the measured tension. Together these bytes form a 12Bit value, which has to be scaled to a maximum tension of 10V. Meaning of symbols : STX = starting sign = 02 hex ADR = adjusted address on DCA-20 = 00 hex FF hex LEN = number of data bytes to be transferred = 00 hex FF hex TYP = not used, hence always = 00 hex DAT = usable data = 00 hex FF hex ETX = end sign = 03 hex BCC = block check = 00 hex FF hex NAK = negative receipt = 15 hex ACK = positive receipt = 06 hex ENQ = request to send = 05 hex EOT = end of transfer = 04 hex Version 1 Page 8 of 12

9 Connection Diagram DCA - 10: General Arrangement Diagram DCA - 10: Version 1 Page 9 of 12

10 Connection Diagram DCA - 20: General Arrangement Diagram DCA - 20: Version 1 Page 10 of 12

11 Technical Data DCA - 10 / DCA - 20 Supply voltage : 24 Vdc ±10% / ripple 5% Consumption : max. 2,5 W Suitable bridge Bridge resistance Tension for bridge supply Zero adjustment (TARE) Possible offset range Adjustment for amplification Possible input range Overload capability of inputs Input resistance Range switching : full Wheatstone bridge only : 350 Ω : 10 V / max. 30 ma : automatic : 12,5 mv is equal to max. 50 % of sensor signal at 25mV end range : automatic : 2 mv to 25 mv : /- 50 mv : 1 MΩ : 25%,50%,75%,100% by switching : inputs 9,10 und 12,13 (DCA - 10) : inputs 13,14 and 15,16 (DCA - 20) Signal outputs Max. frequency Monitor output Max. frequency : V / max. 5 ma : 5kHz : V / max. 5 ma : 0,3 Hz Linearity error : 0,005% Temperature drift : 0,002%/K Zero point error Amplification error : +/- 5 mv : +/- 5 mv RS485 serial link : 9600 Baud, 8 Data bits, 1 Stop bit, No Parity Ambient temperature : C Connections : screw type terminals 2,5 mm² Material of housing : green insulating material Mounting of housing : snap on fixing arrangement for TS35 Housing measurements : see diagram Weight : 250g (DCA - 10) : 225 g (DCA - 20) ISS Modification Date Change Checked 1.1 ENG Changed description of calibration when using gain GL SN 25, 50 or 75% on page ENG Upgraded power specification from 1.5 to 2.5W AWA AWA Version 1 Page 11 of 12

12 Copyright This document and any software described in it are copyrighted with all rights reserved. Under copyright laws, neither the documentation nor the software may be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine readable form, in whole or in part, without prior written consent of Total Tension Solutions Ltd (TTS). Failure to comply with this condition may result in prosecution. All computer programs embedded into the microcontroller or supplied on disk are the property of TTS. The programs are protected under copyright law and are licensed for use only by the user. TTS does not warrant that the components or software will function properly in every environment. Although TTS has tested the components, software and reviewed the documentation, TTS makes no warranty or representation, either express or implied, with respect to this software or documentation, their quality, performance, merchantability, or fitness for a particular purpose. This software and documentation are licensed as is and you, the licensee, by making use thereof, are assuming the entire risk as to their quality and performance. In no event will TTS be liable for direct, indirect, special, incidental, or consequential damages arising out of the use or inability to use the software or documentation or components, even if advised of the possibility of such damages. In particular, and without prejudice to the generality of the foregoing, TTS has no liability for any programs or data stored or used with TTS software, including the costs of recovering such programs or data. Disclaimer: TTS s policy is one of constant development and improvement. We reserve the right to alter, modify, correct and upgrade our software programs and publications and products without notice and without incurring liability. Copyright:: 1998 Total Tension Solutions Ltd 14 Highpoint Business Village Henwood Industrial Park Ashford Kent TN24 8DH Telephone Fax info@tts-systems.com Version 1 Page 12 of 12

High Performance Tension Controller HPTC Electrical Connection Manual

High Performance Tension Controller HPTC Electrical Connection Manual High Performance Tension Controller HPTC Electrical Connection Manual TTS Systems Limited 14, Highpoint Business Village, Henwood, Ashford, Kent, TN24 8DH Contents Electrical Overview... 3 Power Supply

More information

CALIBRE. I2C for Windows USB Manual WINI2CUCA93 Issue /18/03

CALIBRE. I2C for Windows USB Manual WINI2CUCA93 Issue /18/03 I2C for Windows USB Manual WINI2CUCA93 Issue 1.0 Calibre UK Ltd 1999 Welcome to the Calibre I 2 C for Windows application. This application is designed to allow non-specialist users to run I 2 C Bus operations

More information

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB Strain gauge Measuring Amplifier GSV-A8 Instruction manual GSV-A8, GSV-A8USB, GSV-A6USB GSV-A8USB SubD5 (front side) GSV-A8USB M2 (front side) GSV-A6USB (rear side) GSV-A8USB K6D (front side) Version:

More information

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3 POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual General Description The POWER SERIES Plus digital switchboard meters incorporate the latest DSP microprocessor technology.

More information

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2 POWER SERIES Plus 3 in 1 AC Voltage Digital Switchboard Meter User s Manual General Description The POWER SERIES Plus digital switchboard meters incorporate the latest DSP microprocessor technology. Careful

More information

RS-485 MicroLinK HM Setup Software Installation Operation & Specifications Manual

RS-485 MicroLinK HM Setup Software Installation Operation & Specifications Manual RS-485 MicroLinK HM RS-485 HART Protocol Modem HART Device to Modbus Accumulator DIN Rail Mount 101-0035 Setup Software Installation Operation & Specifications Manual The RS-485 MicroLink-HM 101-0035 is

More information

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB Strain gauge Measuring Amplifier GSV-1A8 Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB GSV-1A8USB SubD1 (front side) GSV-1A8USB M12 (front side) GSV-1A16USB (rear side) GSV-1A8USB K6D (front side)

More information

M260 Load Cell Amplifiers

M260 Load Cell Amplifiers E L 4 - + 2-3 1-2 M260 Load Cell Amplifiers Description. This fast start guide shows basic installation, setup, and calibration for most applications. For more specific information contact Minsterport.

More information

MODEL AAMA - UNIVERSAL SIGNAL CONDITIONING MODULE

MODEL AAMA - UNIVERSAL SIGNAL CONDITIONING MODULE Bulletin No. AAMA-G Drawing No. LP0368 Released 05/13 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL AAMA - UNIVERSAL SIGNAL CONDITIONING MODULE 3-WAY ISOLATION OF ANALOG SIGNALS UNIVERSAL

More information

Model SC500. Programmable Single-Channel Transducer Indicator/Conditioner DESCRIPTION FEATURES

Model SC500. Programmable Single-Channel Transducer Indicator/Conditioner DESCRIPTION FEATURES Programmable Single-Channel Transducer Indicator/Conditioner DESCRIPTION The SC series models are self-calibrating microprocessorbased transducer signal conditioners when used with sig mod equipped transducers.

More information

Single-Axis Counter BDD 611

Single-Axis Counter BDD 611 Single-Axis Counter BDD 611 Technical Description, User's Guide english No. 611-150 D/E. Edition 0705; Subject to modification. Replaces edition 0701. www.balluff.com Balluff GmbH Schurwaldstrasse 9 73765

More information

POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual IM2492WVPF-1

POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual IM2492WVPF-1 POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual General Description The POWER SERIES Plus digital switchboard meters incorporate the latest DSP microprocessor technology.

More information

Copyright Extract from Conditions of Sale Safety Warning

Copyright Extract from Conditions of Sale Safety Warning KD420 User Manual Copyright 2004-2013 KK Systems Ltd. No reproduction of any part of this document, in any form, is allowed without prior written permission from KKSystems Ltd. All other copyrights and

More information

LCI Load Cell Junction Box with Fault Monitor

LCI Load Cell Junction Box with Fault Monitor LCI Load Cell Junction Box with Fault Monitor User Manual www.mantracourt.co.uk The LCI Load Cell Failure Alarm Manual Chapter 1 Introduction to the LCI...2 Chapter 2 Installing the LCI...3 Figure 2.1

More information

MODEL 9250 Preliminary data sheet

MODEL 9250 Preliminary data sheet Delivery: ex stock Warranty: 24 months Universal Instrumentation Amplifier for strain gage, potentiometric, DC/DC and incremental sensors MODEL 9250 Preliminary data sheet NEW burster TEDS Highlights Ultra-fast

More information

IO-LC1, IO-LC3 I/O Expansion Modules 1-3 Loadcell Inputs, 1 Digital In, 2 Out

IO-LC1, IO-LC3 I/O Expansion Modules 1-3 Loadcell Inputs, 1 Digital In, 2 Out IO-LC1, IO-LC3 I/O Expansion Modules 1-3 Loadcell Inputs, 1 Digital In, 2 Out The IO-LC1 and IO-LC3 are I/O Expansion Modules that can be used in conjunction with specific Unitronics OPLC controllers.

More information

MP-2000 Dual Channel LVDT/RVDT Readout/Controller

MP-2000 Dual Channel LVDT/RVDT Readout/Controller Large backlit dual channel display Menu driven setup and calibration 100 to 240 VAC line powered MIN, MAX, TIR, A+B and A-B functions 2.5, 3.3, 5 and 10kHz selectable excitation Analog and RS232 outputs

More information

LCI User Manual mantracourt.com

LCI User Manual mantracourt.com LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence

More information

CALIBRE. I2C Communications Adapter Windows 95 / 98 Driver Manual ICADLL/95 Issue /07/1999

CALIBRE. I2C Communications Adapter Windows 95 / 98 Driver Manual ICADLL/95 Issue /07/1999 I2C Communications Adapter Windows 95 / 98 Driver Manual ICADLL/95 Issue 2.2 16/07/1999 Calibre UK Ltd 1999 Welcome to the Calibre I 2 C for Windows 95 / 98 driver. This driver is designed to users to

More information

MTP INSTRUCTION MANUAL

MTP INSTRUCTION MANUAL DT-118B MTP INSTRUCTION MANUAL Pocket Autoranging Digital Multimeter 3 in 1 Model MTP-1025 Auto Ran ging DMM Hz% A OFF V AU TO PO WER OFF MTP Instruments Table of Contents Introduction Page 1 Features

More information

TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL. Transducer Techniques R

TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL. Transducer Techniques R TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL Transducer Techniques R 42480 RIO NEDO, TEMECULA, CA 92590 (909) 719-3965 FAX (909) 719-3900 URL: http://www.ttloadcells.com E-mail: tti@ttloadcells.com

More information

11 Serial Communications

11 Serial Communications 11.1 COMMUNICATIONS PACKAGES There are a number of communication packages that can be used with the Quantum III to facilitate setup, record parameter data, view internal activity on a soft-scope and permit

More information

Analogue Signal Transmitter AST 3 From prog.name A001A140. Operating instructions, Quick installation

Analogue Signal Transmitter AST 3 From prog.name A001A140. Operating instructions, Quick installation GB Analogue Signal Transmitter AST 3 From prog.name A001A140 Operating instructions, Quick installation Operating instructions, Quick operation Contents Introduction... 1 Operating instruction General...

More information

Peak/Valley Hold Unit (PVHU) User Manual V3.00

Peak/Valley Hold Unit (PVHU) User Manual V3.00 Peak/Valley Hold Unit (PVHU) User Manual V3.00 Part Number: DO-UM0084/30/UE Applies to Firmware Version: V3.01 Reference: Peak_Valley Hold Unit (PVHU) User Manual.docx Date: 30 May 2016 Version: 3.00 Peak/Valley

More information

Analog Amplifier FAA-27. Technical Manual. Flintec GmbH Bemannsbruch Meckesheim GERMANY.

Analog Amplifier FAA-27. Technical Manual. Flintec GmbH Bemannsbruch Meckesheim GERMANY. Analog Amplifier FAA-27 Technical Manual Flintec GmbH Bemannsbruch 9 74909 Meckesheim GERMANY www.flintec.com Table of Contents 1. Safety Instructions... 2 2. Declaration Of Conformity... 3 3. Front View,

More information

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX DOCUMENT NO: TDC 0550 MANUAL - 2 1.0) INTRODUCTION. PAGE 2 1.1) ABOUT THIS MANUAL. PAGE 2 1.2) INTRODUCTION. PAGE

More information

System StrainSmart Data Acquisition System. Micro-Measurements FEATURES DESCRIPTION MODEL 5100B SCANNER SPECIFICATIONS

System StrainSmart Data Acquisition System. Micro-Measurements FEATURES DESCRIPTION MODEL 5100B SCANNER SPECIFICATIONS FEATURES From 5 to 1200 input channels can be configured as needed at any time Inputs accepted from strain gages and strain-gagebased transducers (Model 5110A), thermocouples (Model 5120A), sensors with

More information

Instruction Manual. Instrument Amplifier HE 017

Instruction Manual. Instrument Amplifier HE 017 Instruction Manual Instrument Amplifier HE 017 List of contents INSTRUCTION MANUAL: HE 017 Date: 20.4.99 Art.-No.: 320999 S General Safety Instructions.......................................... S 1 General

More information

DCS Series. Digital Counting Scale. Setup Manual

DCS Series. Digital Counting Scale. Setup Manual DCS Series Digital Counting Scale Setup Manual Revision 1.1 February 12, 1997 1996-1997 Transcell Technology, Inc. Contents subject to change without notice. Transcell Technology, Inc. 975 Deerfield Parkway

More information

USER MANUAL. WBI414F21 AC current transducer

USER MANUAL. WBI414F21 AC current transducer 1 Designing, Manufacturing and Supplying WB Series Electric Isolated Sensor and Digital Electrical Transducer since 1989 USER MANUAL WBI1F21 AC current transducer www.wb-my.com wblch@wbdz.cn Technical

More information

udrive-usd-g1 Embedded DOS micro-drive Module Data Sheet

udrive-usd-g1 Embedded DOS micro-drive Module Data Sheet 4D SYSTEMS udrive-usd-g1 Embedded DOS micro-drive Module Document Date: 4 rh November 2011 Document Revision: 4.0 Note: This revision of the Dcoument applies to udrive PmmC Rev23 or above. 2011 4D Systems

More information

Technical data. Your advantages

Technical data. Your advantages Technical data Nominal torque: 10.000 Nm to 25.000 Nm, bidirectional Customer-specific calibration upon request Rotational speed: 8.000 rpm Accuracy: ±0,5 % Temperature range: -30 C to +85 C Protection

More information

DRIVE Billing Relate Software DRIVE Billing

DRIVE Billing Relate Software DRIVE Billing DRIVE Billing SUPPORT SERVICES Relate is committed to strong customer services and satisfaction. At all times you will be able to make contact with our company and technical services teams. You can make

More information

USER MANUAL. WBI412F41 AC current transducer

USER MANUAL. WBI412F41 AC current transducer Designing, Manufacturing and Supplying WB Series Electric Isolated Sensor and Digital Electrical Transducer since 989 USER MANUAL WBI2F AC current transducer www.wb-my.com wblch@wbdz.cn Technical Service:

More information

RMCN22BD Analog Converter ma - for Zelio Analog

RMCN22BD Analog Converter ma - for Zelio Analog Characteristics Analog Converter - 4..20 ma - for Zelio Analog Main Commercial Status Range of product Product or component type Analogue input type Analogue output type Commercialised Zelio Analog Voltage/Current

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

TM3TI4 module TM3-4 inputs temperature

TM3TI4 module TM3-4 inputs temperature Characteristics module TM3-4 inputs temperature Complementary Analogue input resolution Permissible continuous overload Input impedance LSB value Conversion time Sampling duration Main Range of product

More information

Operating Instructions Differential Pressure Transducer PS27

Operating Instructions Differential Pressure Transducer PS27 Operating Instructions Differential Pressure Transducer PS27 halstrup-walcher GmbH Stegener Straße 10 79199 Kirchzarten/Germany Phone: +49 (0) 76 61/39 63 0 Fax: +49 (0) 76 61/39 63 99 E-mail: info@halstrup-walcher.com

More information

ph/orp CONTROLLER PH/ORP800 INSTRUCTION MANUAL

ph/orp CONTROLLER PH/ORP800 INSTRUCTION MANUAL R ph/orp CONTROLLER PH/ORP INSTRUCTION MANUAL Table of Contents Introduction... Order Code... Mounting... Electrical Connections... Operator Interface... Operation... Calibration... Digital Communication...

More information

WIEG-EXT Wiegand to RS485 extender module.

WIEG-EXT Wiegand to RS485 extender module. WIEG-EXT Wiegand to RS485 extender module. Designed for embedding into products manufactured by third-parties, this Wiegand to RS485 extender is designed to transfer wiegand data from Access Control Card

More information

USER MANUAL. WBV412U01 AC voltage transducer

USER MANUAL. WBV412U01 AC voltage transducer Designing, Manufacturing and Supplying WB Series Electric Isolated Sensor and Digital Electrical Transducer since 1989 USER MANUAL WBV412U01 AC voltage transducer www.wb-my.com wblch@wbdz.cn Technical

More information

NPA. Amphenol Advanced Sensors. Surface-Mount Pressure Sensor Series. Features

NPA. Amphenol Advanced Sensors. Surface-Mount Pressure Sensor Series. Features NPA Surface-Mount Pressure Sensor Series The NPA product series is provided in a miniature size as a cost effective solution for applications that require calibrated performance. Packaged in a SOIC14 pin

More information

Tisio CE Release Notes

Tisio CE Release Notes Tisio CE Release Notes Copyright Copyright 2005, 2006, 2007 and 2008 by ThinPATH Systems, Inc. The information contained in this document is subject to change without notice. ThinPATH Systems, Inc. shall

More information

XEELAS NODE MANUAL X-COM VERSION 1.0

XEELAS NODE MANUAL X-COM VERSION 1.0 This document is the official manual for the Xeelas LoRa Node. In this document, all the functions and technical specifications are described. X-COM VERSION 1.0 XEELAS NODE MANUAL Manual for Software version

More information

8-Channel Relay Output Board Via I 2 C Protocol. I2C-Relay8

8-Channel Relay Output Board Via I 2 C Protocol. I2C-Relay8 I2C-Relay8 User Manual Table of Contents What Does it Do?... 3 What Do I Need to Make it Work?... 3 What Else Does it Work With?... 4 How to Use This Device... 5 Setting Up the Controller... 5 Powering

More information

WG 20. The WG 20 achieves an extraordinarily. accuracy for hazardous-area. applications.

WG 20. The WG 20 achieves an extraordinarily. accuracy for hazardous-area. applications. Modular Housings for Hazardous Areas For transmission of 0(4)... 20-mA signals from hazardous areas or supply of intrinsically safe 2-wire transmitters. The Task The power supply/isolator is used to supply

More information

MTS-2000 USER S MANUAL

MTS-2000 USER S MANUAL MTS-2000 USER S MANUAL USER s MANUAL - March 2010 MTS-2000 METER TEST SYSTEM Pay special attention to the warnings and safety instructions that accompany the above symbol wherever it is found within this

More information

ETConcept Systems Engineering. User s Guide

ETConcept Systems Engineering. User s Guide Wiegand to RS485 Converter User s Guide Nov-08 Copyright 2008. All rights reserved including the right of reproduction in whole or in part in any form. Contents List of Accessories Included... 1 List

More information

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description Description LAUREL ELECTRONICS, INC. Features Laureate Digital Panel Meter for Load Cell & Microvolt Input 20, 50, 100, 250 & 500 mv ranges Span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999

More information

Dual Channel LVDT/RVDT Readout/Controller

Dual Channel LVDT/RVDT Readout/Controller SPECIFICATIONS Large backlit dual channel display Menu driven setup and calibration 100 to 240 VAC line powered MIN, MAX, TIR, A+B and A-B functions 2.5, 3.3, 5 and 10kHz selectable excitation Analog and

More information

S82S (3/7.5-W Models)

S82S (3/7.5-W Models) Switch Mode Power Supply (3/7.5-W Models) CSM DS_E_4_3 Miniature DIN Rail Mounting DC-DC Power Supplies 65 mm depth enables mounting onto control panels with 100 mm depth. Inputs: 10.2 to 27.6 VDC (DC

More information

S2Tech srl Via Imperia, 28 Milano ITALY Tel: Fax:

S2Tech srl Via Imperia, 28 Milano ITALY Tel: Fax: Page: 1/6 MRL200 - MULTIROPE SENSOR QTY 1 MultiRope MRL rope sensor [A] QTY 2 screws (engraved with ID) Hex head, normal [C] or flanged type[d] QTY 1 Deflection rod [B] 8) Multirope MRL sensor is installed

More information

Gateway 1400 Reference Manual

Gateway 1400 Reference Manual Profibus-DP Gateway 1400 Reference Manual Copyright All Rights Reserved. No part of this document may be copied, reproduced, republished, uploaded, posted, transmitted, distributed, stored in or introduced

More information

Issue 03/2013. The Electronic Load

Issue 03/2013. The Electronic Load Issue 03/2013 ZS Electronic Loads, PL Series Interface overview RS-232 USB / GPIB LAN System bus Analog X Analog isolated / X Standard ption / not available PL506 PL1006 Voltage Current Resistance 3) Model

More information

PSD Strain Gauge or Load Cell Hand Held Display TEDS enabled

PSD Strain Gauge or Load Cell Hand Held Display TEDS enabled TEDS Enabled TEDS enabled 2 label options available for the PSD PSD Strain Gauge or Load Cell Hand Held Display TEDS enabled User Manual www.mantracourt.co.uk What is TEDS?...2 Basic concept...2 How it

More information

TM221M16R controller M IO relay

TM221M16R controller M IO relay Product data sheet Characteristics TM221M16R controller M221 16 IO relay Complementary Main Discrete I/O number 16 Number of I/O expansion module Supply voltage limits Inrush current Power consumption

More information

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The

More information

UniPak UP448 Bridge Input Isolating Signal Conditioner

UniPak UP448 Bridge Input Isolating Signal Conditioner 6-wire Bridge Connection Excitation for to 350 Ω Load Cells 500 Volt (3-way) Isolation Excellent Accuracy (0.0%) DIP Switch Configuration Digital Input Tare Calibration RS85 Modbus RTU Superior Flexible

More information

Transducers for Pt-100/1000, Resistors

Transducers for Pt-100/1000, Resistors Transducers for Pt-100/1000, Resistors Microprocessor-based technology General Description Isolating transducers with digital programming of ranges, for DIN-rails or for printed circuit boards. Modules

More information

ACLD Channel Opto-isolated Digital Input Board

ACLD Channel Opto-isolated Digital Input Board ACLD-9182 16 Channel Opto-isolated Digital Input Board @ Copyright 1996 All Rights Reserved. Manual edition 01, January 1996 The information in this document is subject to change without prior notice in

More information

Strain Gauge Converter

Strain Gauge Converter EN Z-SG General Description Module Z-SG is a strain gauge signal converter. Measurements taken using the 6-wires or 4-wires technique are available through Modbus-RTU serial protocol or the analog output.

More information

LYNCA VA6- F Amplifier Board for Two Servo Solenoid Valves and Two Pressure Valves USER MANUAL. General Information. Page 1

LYNCA VA6- F Amplifier Board for Two Servo Solenoid Valves and Two Pressure Valves USER MANUAL. General Information. Page 1 Page 1 LYNCA VA6F Amplifier Board for Two Servo Solenoid Valves and Two Pressure Valves USER MANUAL General Information VA6F is a multichannel valve amplifier module developed to drive hydraulic valve

More information

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 42000

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 42000 Universal high-voltage isolator. Input voltages up to Vin = ±3600 V. The Task In high-voltage systems, unipolar or bipolar voltage signals ranging from 100 V to 3600 V must be galvanically isolated and

More information

Instruction and Maintenance Manual

Instruction and Maintenance Manual Instruction and Maintenance Manual CO and CO2 Contact GRYF HB, spol. s r.o. Cechova 314 Havlickuv Brod 580 01 tel.: +420 569 426 627 fax: +420 569 426 627 Czech Republic www.gryf.eu CO a CO2 Instrument

More information

Standard-Signal Isolation Amplifiers. VariTrans A 21000

Standard-Signal Isolation Amplifiers. VariTrans A 21000 Standard-Signal Isolation Amplifiers The first standard-signal isolation amplifier with protective separation and broad-range power supply in the 6-mm class. The Task Isolation and conversion of 0... 20

More information

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process and Ratiometric Signals Features Reads process signals from ±200 mv to ±600V or ±2 ma to ±5A full scale Ratiometric mode for bridges and

More information

User s Manual. Models Digital Force Gauge. Additional User Manual Translations available at

User s Manual. Models Digital Force Gauge. Additional User Manual Translations available at User s Manual Models 475055 Digital Force Gauge Additional User Manual Translations available at www.extech.com Introduction Congratulations on your purchase of Extech s Model 475055 Digital Force Gauge

More information

Model HNG100, Version 1+

Model HNG100, Version 1+ HOISTNET GATEWAY Model HNG100, Version 1+ Installation and User Manual V1.2 20.08.2018 DRAFT CASWA Pty Ltd 2014 CASWA Pty Ltd 2014 1 Page CONTENTS 1 OVERVIEW... 3 2 SPECIFICATIONS... 3 2.1 Physical Specifications...

More information

7561-PSD Manual Portable Battery Powered Indicator

7561-PSD Manual Portable Battery Powered Indicator 7561-PSD Manual Portable Battery Powered Indicator Lebow Products Inc. 1728 Maplelawn Drive P.O. Box 1089 Troy, Michigan 48084-1089 (800) 803-1164 Phone: (248) 643-0220 FAX: (248) 643-0259 Visit our web

More information

RS-485 Fiber-Optic Link RS-485 to Multi-Mode Fiber-Optic converter ST Fiber Connectors DIN Rail Mount

RS-485 Fiber-Optic Link RS-485 to Multi-Mode Fiber-Optic converter ST Fiber Connectors DIN Rail Mount Fiber-Optic Link to Multi-Mode Fiber-Optic converter ST Fiber Connectors DIN Rail Mount 101-0079 Installation Operation & Specifications Manual Auto-direcon control Supports BAUD rates up to 115,200 Fiber

More information

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.4 UK

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.4 UK WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue

More information

CoMo Logic. Electronics & Software. Single-Channel y(t) ControlMonitor. Type 5875A...

CoMo Logic. Electronics & Software. Single-Channel y(t) ControlMonitor. Type 5875A... Electronics & Software CoMo Logic Single-Channel y(t) ControlMonitor Type 5875A... The CoMo Logic monitor has a graphics display and charge mode input for monitoring time-dependent measurands in production

More information

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01 ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview

More information

ioselect Z-NET Z-SG Bridge Input Isolating I/O Module

ioselect Z-NET Z-SG Bridge Input Isolating I/O Module -wire Bridge Connection Excitation for to 30 Ω Load Cells 00 Volt (3-way) Isolation Excellent Accuracy (0.0%) DIP Switch Configuration Digital Input Tare Calibration RS8 Modbus RTU Superior Flexible Power:

More information

Installation & Operation

Installation & Operation LED Readout Installation & Operation WARRANTY Accurate Technology, Inc. warrants the ProScale Systems against defective parts and workmanship for 1 year commencing from the date of original purchase. Upon

More information

Transmitter WST 3 From prog. name W001A100. Technical Manual

Transmitter WST 3 From prog. name W001A100. Technical Manual GB Transmitter WST 3 From prog. name W001A100 Technical Manual Transmitter WST 3 Contents 1. Introduction Functions... 1-2 Technical data... 1-4 2. Installation General... 2-1 Electrical installation...

More information

TM221CE24R controller M IO relay Ethernet

TM221CE24R controller M IO relay Ethernet Product data sheet Characteristics TM221CE24R controller M221 24 IO relay Ethernet Complementary Main Discrete I/O number 24 Number of I/O expansion module Supply voltage limits Network frequency Inrush

More information

EDBG. Description. Programmers and Debuggers USER GUIDE

EDBG. Description. Programmers and Debuggers USER GUIDE Programmers and Debuggers EDBG USER GUIDE Description The Atmel Embedded Debugger (EDBG) is an onboard debugger for integration into development kits with Atmel MCUs. In addition to programming and debugging

More information

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4. Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting

More information

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Belimo Gateway MP to Modbus RTU - UK24MOD

Belimo Gateway MP to Modbus RTU - UK24MOD Product information UK24MOD MODBUS RTU Belimo Gateway MP to Modbus RTU - UK24MOD Contents Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical

More information

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS Characteristics battery control module - 24..28.8 V DC - 24 V - 20 A - for regulated SMPS Main Range of product Product or component type Input voltage Output voltage Maximum output current Phaseo Battery

More information

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4. Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting

More information

Samba PLC+HMI SM35-J-RA22

Samba PLC+HMI SM35-J-RA22 Samba PLC+HMI SM35-J-RA22 SM43-J-RA22 Technical Specifications Ordering Information Item SM35-J-RA22 PLC with Flat panel, Color touch display 3.5 SM43-J-RA22 PLC with Flat panel, Color touch display 4.3

More information

TABLE OF CONTENTS. Communication Functions

TABLE OF CONTENTS. Communication Functions TABLE OF CONTENTS Chapter 1: Chapter 2: Chapter 3: Chapter 4: General Features....................................................... 1-1 Functions......................................................

More information

Configuring Vicor IBC Converters with nipols

Configuring Vicor IBC Converters with nipols APPLICATION NOTE AN:001 Configuring Vicor IBC Converters with nipols Contents Page Introduction 1 Is an IBC or BCM Module More Appropriate for the Application? 2 What is the Necessary Input Range for the

More information

UNIVERSAL CURRENT CONVERTER

UNIVERSAL CURRENT CONVERTER UNIVERSAL CURRENT / VOLTAGE CONVERTER AC/DC Current / Voltage Analyzer The is the first CURRENT / VOLTAGE CONVERTER & ANALYZER ALL IN ONE - of the market. It allow you to connect all isolated current sensors.

More information

Faults on the system Proximity switch connection technology:

Faults on the system Proximity switch connection technology: Speed monitor for connection to a base unit from the PNOZmulti modular safety system Approvals Unit features Monitoring of 2 independent axes Connection of 2 incremental encoders or 4 proximity switches

More information

MAX Modular Analogue Expandable System

MAX Modular Analogue Expandable System MAX Modular Analogue Expandable System Features Modular System with plugin modules Two Motherboard Sizes giving capacity for 5 or 11 plug-in modules Totally user configurable Housed in IP65 die-cast enclosure

More information

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011 Technical Data 2CDC504084D0201 ABB i-bus KNX Product description The device is used to record analogue data. Four conventional sensors can be connected to the device. The connection to the bus is established

More information

Installation instructions Inclination sensor EC2019 EC / / 2013

Installation instructions Inclination sensor EC2019 EC / / 2013 Installation instructions Inclination sensor UK EC219 EC245 739215 / 3 1 / 213 Inhalt 1 Safety instructions 3 2 Mounting 4 3 Electrical connection 4 4 Dimensions 4 5 Technical Data 5 6 Characteristics

More information

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES Digital Panel Indicators A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input Analogue Output

More information

Fieldbus Independent I/O Modules 1 AI DMS Manual

Fieldbus Independent I/O Modules 1 AI DMS Manual Fieldbus Independent 1 AI DMS 750-491 Manual Version 1.1.4 ii General Copyright 2005 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved. WAGO Kontakttechnik GmbH & Co. KG Hansastraße 27 D-32423 Minden

More information

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement Acquisition Measurement Control The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input

More information

PRODIS. PD-ADC Digital Process Meter for analog Sensors. Digital Process Meters. Datasheet

PRODIS. PD-ADC Digital Process Meter for analog Sensors. Digital Process Meters. Datasheet Digital Process Meters Digital Process Meter for analog Sensors Datasheet Copyright ASM GmbH Am Bleichbach 18-24 85452 Moosinning Germany The information presented in this data sheet does not form part

More information

TM221CE40T controller M IO transistor PNP Ethernet

TM221CE40T controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221CE40T controller M221 40 IO transistor PNP Ethernet Complementary Main Discrete I/O number 40 Number of I/O expansion module Supply voltage limits Inrush current

More information

User's Guide. MiniTec TM Series Model MN25 MultiMeter

User's Guide. MiniTec TM Series Model MN25 MultiMeter User's Guide MiniTec TM Series Model MN25 MultiMeter Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment (a

More information

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS POWER MONITORING ENERCEPT Networked Power Transducer (Modbus RTU) DANGER US Patent No. 6,373,238 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in

More information

TM3DI16G module TM3-16 inputs spring

TM3DI16G module TM3-16 inputs spring Characteristics module TM3-16 inputs spring Main Range of product Product or component type Range compatibility Modicon TM3 Discrete input module Modicon M221 Modicon M241 Modicon M251 Discrete input number

More information

DXP-40 FEATURES APPLICATIONS DESCRIPTION CONFIGURATION

DXP-40 FEATURES APPLICATIONS DESCRIPTION CONFIGURATION FEATURES Individually digitized transducer data Continuous Expert System diagnostics Dynamic digital filtering 750,000 count resolution psr channel 20 updates/sec. Multi-function set-up and calibration

More information