Relion 615 series. Transformer Protection and Control RET615 Application Manual

Size: px
Start display at page:

Download "Relion 615 series. Transformer Protection and Control RET615 Application Manual"

Transcription

1 Relion 615 series Transformer Protection and Control RET615

2

3 Document ID: 1YHT530003D05 Issued: Revision: C Product version: 4.1 Copyright 2014 ABB. All rights reserved

4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative. ABB Nanjing SAC Power Grid Automation Co., Ltd. No. 11 Phoenix Road, Jiangning Development Zone Nanjing China Telephone: Facsimile: Customer hotline:

5 Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/ or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network. It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

6 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN and EN for the EMC directive, and with the product standards EN and EN for the low voltage directive. The product is designed in accordance with the international standards of the IEC series.

7 Table of contents Table of contents Section 1 Section 2 Section 3 Introduction...5 This manual...5 Intended audience...5 Product documentation...6 Product documentation set...6 Document revision history...6 Related documentation...7 Symbols and conventions...7 Symbols...7 Document conventions...8 Functions, codes and symbols...8 RET615 overview...11 Overview...11 Product version history...11 PCM600 and IED connectivity package version...12 Operation functionality...12 Optional functions...12 Physical hardware...12 Local HMI...14 Display...15 LEDs...16 Keypad...16 Web HMI...17 Authorization...18 Audit trail...19 Communication...21 Ethernet redundancy Standard configurations...25 Addition of control functions for primary devices and the use of binary inputs and outputs...28 LED functionality...28 Connection diagrams...30 Presentation of standard configurations...38 Standard configuration A...39 Applications...39 Functions...40 Default I/O connections...41 RET615 1

8 Table of contents Default disturbance recorder settings...43 Functional diagrams...43 Functional diagrams for protection...44 Functional diagrams for disturbance recorder and supervision functions...50 Functional diagrams for control and interlocking...52 Standard configuration B...56 Applications...56 Functions...57 Default I/O connections...58 Default disturbance recorder settings...60 Functional diagrams...60 Functional diagrams for protection...61 Functional diagrams for disturbance recorder and supervision functions...67 Functional diagrams for control and interlocking...69 Standard configuration C...73 Applications...73 Functions...74 Default I/O connections...75 Default disturbance recorder settings...77 Functional diagrams...77 Functional diagrams for protection...78 Functional diagrams for disturbance recorder and supervision functions...84 Functional diagrams for control and interlocking...86 Standard configuration D...90 Applications...90 Functions...91 Default I/O connections...92 Default disturbance recorder settings...94 Functional diagrams...94 Functional diagrams for protection...95 Functional diagrams for disturbance recorder and supervision functions Functional diagrams for control and interlocking Standard configuration E Applications Functions Default I/O connections Default disturbance recorder settings Functional diagrams Functional diagrams for protection RET615

9 Table of contents Functional diagram for disturbance recorder and supervision functions Functional diagrams for control and interlocking Standard configuration F Applications Functions Default I/O connections Default disturbance recorder settings Functional diagrams Functional diagrams for protection Functional diagram for disturbance recorder and supervision functions Functional diagrams for control and interlocking Standard configuration G Applications Functions Default I/O connections Default disturbance recorder settings Functional diagrams Functional diagrams for protection Functional diagram for disturbance recorder and trip circuit supervision Functional diagrams for control and interlocking Standard configuration H Applications Functions Default I/O connections Default disturbance recorder settings Functional diagrams Functional diagrams for protection Functional diagram for disturbance recorder and supervision functions Functional diagrams for control and interlocking Standard configuration J Applications Functions Default I/O connections Default disturbance recorder settings Functional diagrams Functional diagrams for protection Functional diagrams for disturbance recorder and supervision Functional diagrams for control and interlocking Standard configuration K RET615 3

10 Table of contents Applications Functions Default I/O connections Default disturbance recorder settings Functional diagrams Functional diagrams for protection Functional diagrams for disturbance recorder and supervision Functional diagrams for control and interlocking Section 4 Section 5 Section 6 Requirements for measurement transformers Current transformers Current transformer requirements for non-directional overcurrent protection Current transformer accuracy class and accuracy limit factor Non-directional overcurrent protection Example for non-directional overcurrent protection IED physical connections Inputs Energizing inputs Phase currents Residual current Phase voltages Residual voltage RTD/mA inputs Auxiliary supply voltage input Binary inputs Optional light sensor inputs Outputs Outputs for tripping and controlling Outputs for signalling IRF Glossary RET615

11 1YHT530003D05 C Section 1 Introduction Section 1 Introduction 1.1 This manual The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. 1.2 Intended audience This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and principles. RET615 5

12 Section 1 Introduction 1YHT530003D05 C 1.3 Product documentation Product documentation set Planning & purchase Engineering Installation Commissioning Operation Maintenance Decommissioning, deinstallation & disposal Quick start guide Quick installation guide Brochure Product guide Operation manual Installation manual Connection diagram Engineering manual Technical manual Application manual Communication protocol manual IEC Engineering guide Point list manual c c GUID-12DC16B2-2DC1-48DF C8B C V1 EN Figure 1: The intended use of documents during the product life cycle Product series- and product-specific manuals can be downloaded from the ABB Website Document revision history Document revision/date Product version History A/ First release B/ Content updated C/ Content updated to correspond to the product version Download the latest documents from the ABB Website 6 RET615

13 1YHT530003D05 C Section 1 Introduction Related documentation Name of the document Modbus Communication Protocol Manual IEC Communication Protocol Manual IEC Engineering Guide Engineering Manual Installation Manual Operation Manual Technical Manual Document ID 1MRS MRS MRS MRS MRS MRS YHT530004D Symbols and conventions Symbols The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property. The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices. RET615 7

14 Section 1 Introduction 1YHT530003D05 C Document conventions A particular convention may not be used in this manual. Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push-button navigation in the LHMI menu structure is presented by using the push-button icons. To navigate between the options, use and. HMI menu paths are presented in bold. Select Main menu/settings. LHMI messages are shown in Courier font. To save the changes in non-volatile memory, select Yes and press. Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE Functions, codes and symbols Table 1: RET615 functions, codes and symbols Function IEC IEC IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, low stage, instance 2 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, high stage, instance 2 Negative-sequence overcurrent protection, instance 1 Table continues on next page PHLPTOC1 3I> (1) 51P-1 (1) PHLPTOC2 3I> (2) 51P-1 (2) PHHPTOC1 3I>> (1) 51P-2 (1) PHHPTOC2 3I>> (2) 51P-2 (2) PHIPTOC1 3I>>> (1) 50P/51P (1) PHIPTOC2 3I>>> (2) 50P/51P (2) EFLPTOC1 Io> (1) 51N-1 (1) EFLPTOC2 Io> (2) 51N-1 (2) EFHPTOC1 Io>> (1) 51N-2 (1) EFHPTOC2 Io>> (2) 51N-2 (2) NSPTOC1 I2> (1) 46 (1) 8 RET615

15 1YHT530003D05 C Section 1 Introduction Function IEC IEC IEC-ANSI Negative-sequence overcurrent protection, instance 2 Negative-sequence overcurrent protection, instance 3 Negative-sequence overcurrent protection, instance 4 NSPTOC2 I2> (2) 46 (2) NSPTOC3 I2> (3) 46 (3) NSPTOC4 I2> (4) 46 (4) Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1) Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2) Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 PHPTUV1 3U< (1) 27 (1) PHPTUV2 3U< (2) 27 (2) Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1) Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2) Positive-sequence undervoltage protection, instance 1 Positive-sequence undervoltage protection, instance 2 Negative-sequence overvoltage protection, instance 1 Negative-sequence overvoltage protection, instance 2 Three-phase thermal overload protection for power transformers, two time constants Stabilized and instantaneous differential protection for 2W transformers Numerical stabilized low impedance restricted earth-fault protection High impedance based restricted earth-fault protection PSPTUV1 U1< (1) 47U+ (1) PSPTUV2 U1< (2) 47U+ (2) NSPTOV1 U2> (1) 47O- (1) NSPTOV2 U2> (2) 47O- (2) T2PTTR1 3Ith>T 49T TR2PTDF1 3dI>T 87T LREFPNDF1 diolo> 87NL HREFPDIF1 diohi> 87NH Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1) Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2) Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1) Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2) Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3) Multi-purpose protection, instance 1 1) MAPGAPC1 MAP (1) MAP (1) Multi-purpose protection, instance 2 1) MAPGAPC2 MAP (2) MAP (2) Multi-purpose protection, instance 3 1) MAPGAPC3 MAP (3) MAP (3) Multi-purpose protection, instance 4 1) MAPGAPC4 MAP (4) MAP (4) Multi-purpose protection, instance 5 1) MAPGAPC5 MAP (5) MAP (5) Multi-purpose protection, instance 6 1) MAPGAPC6 MAP (6) MAP (6) Control Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB Table continues on next page RET615 9

16 Section 1 Introduction 1YHT530003D05 C Function IEC IEC IEC-ANSI Disconnector control, instance 1 DCXSWI1 I <-> O DCC (1) I <-> O DCC (1) Disconnector control, instance 2 DCXSWI2 I <-> O DCC (2) I <-> O DCC (2) Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1) Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2) Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3) Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1) Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2) Tap changer position indication TPOSSLTC1 TPOSM 84M Condition monitoring Circuit-breaker condition monitoring SSCBR1 CBCM CBCM Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1) Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2) Fuse failure supervision SEQRFUF1 FUSEF 60 Runtime counter for machines and devices MDSOPT1 OPTS OPTM Measurement Disturbance recorder RDRE1 - - Three-phase current measurement, instance 1 CMMXU1 3I 3I Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B) Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 I1, I2, I0 Sequence current measurement, instance 2 CSMSQ2 I1I(B), I2I(B), I0I(B) Residual current measurement, instance 1 RESCMMXU1 Io In Residual current measurement, instance 2 RESCMMXU2 Io(B) In(B) Three-phase voltage measurement VMMXU1 3U 3U Residual voltage measurement RESVMMXU1 Uo Vn I1I(B), I2I(B), I0I(B) Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0 Three-phase power and energy measurement PEMMXU1 P, E P, E RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD) 1) Multi-purpose protection is used for example for RTD/mA based protection. 10 RET615

17 1YHT530003D05 C Section 2 RET615 overview Section 2 RET615 overview 2.1 Overview RET615 is a dedicated transformer protection and control IED (intelligent electronic device) for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems. RET615 is a member of ABB s Relion product family and part of its 615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable-unit design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC standard for communication and interoperability between substation automation devices. Once the standard configuration IED has been given the application-specific settings, it can directly be put into service. The 615 series IEDs support a range of communication protocols including IEC with GOOSE messaging, IEC and Modbus Product version history Product version Product history 2.0 Product released 3.0 New configurations E, F, G and H Additions to configuration A, B, C, D, J and K Application configurability support Analog GOOSE support Large display with single line diagram Enhanced mechanical design Increased maximum amount of events and fault records Frequency measurement and protection RTD/mA measurement and protection Voltage measurement and protection Fuse failure supervision Three-phase power and energy measurements Multi-port Ethernet option 4.1 Additions/changes for configurations A-H Dual fibre optic Ethernet communication option (COM0032) Generic control point (SPCGGIO) function blocks Additional logic blocks Button object for SLD Controllable disconnector and earth switch objects for SLD Additional multi-purpose protection instances Increased maximum amount of events and fault records High-availability seamless redundancy (HSR) protocol Parallel redundancy protocol (PRP-1) Parallel use of IEC and IEC protocols Two selectable indication colors for LEDs (red or green) Online binary signal monitoring with PCM600 RET615 11

18 Section 2 RET615 overview 1YHT530003D05 C PCM600 and IED connectivity package version Protection and Control IED Manager PCM600 Ver. 2.6 or later RET615 Connectivity Package Ver. 4.1 or later Parameter Setting Firmware Update Disturbance Handling Signal Monitoring Lifecycle Traceability Signal Matrix Communication Management Configuration Wizard Label Printing IED User Management Application Configuration Graphical Display Editor Differential Characteristics Tool Event Viewer Download connectivity packages from the ABB Website Operation functionality Optional functions Arc protection Modbus TCP/IP or RTU/ASCII IEC RTD/mA measurements and multi-purpose protection (configurations A, B, C and D only) 2.3 Physical hardware The IED consists of two main parts: plug-in unit and case. The content depends on the ordered functionality. 12 RET615

19 1YHT530003D05 C Section 2 RET615 overview Table 2: Plug-in unit and case Main unit Slot ID Plug-in unit Content options - HMI Small (4 lines, 16 characters) Large (8 lines, 16 characters) X100 Auxiliary power/bo module V DC/ V AC; or V DC 2 normally-open PO contacts 1 change-over SO contact 1 normally-open SO contact 2 double-pole PO contacts with TCS 1 dedicated internal fault output contact X110 BIO module 8 binary inputs 4 signal output contacts X120 AI/BI module 6 phase current inputs (1/5A) 1 residual current input (1/5A) Case X130 AI/BI module Only with configurations E, F, G, H and K: 3 phase voltage inputs ( V) 1 residual voltage input ( V) 4 binary inputs X000 Optional RTD/mA module Optional for configurations A, B, C, D and J: 2 generic ma inputs 6 RTD sensor inputs Optional BIO module Optional for configurations A, B, C, D and J: 6 binary inputs 3 signal output contacts Optional communication module See the technical manual for details about different types of communication modules. Rated values of the current and voltage inputs are basic setting parameters of the IED. The binary input thresholds are selectable within the range V DC by adjusting the binary input setting parameters. The connection diagrams of different hardware modules are presented in this manual. See the installation manual for more information about the case and the plug-in unit. Table 3: Number of physical connections in standard configurations Conf. Analog channels Binary channels CT VT RTD/mA BI BO A (14) 1) 10 (13) 1) 6/2 2) 8 10 B 7 - C 7 - Table continues on next page - 8 (14) 1) 10 (13) 1) 6/2 2) (14) 1) 10 (13) 1) 6/2 2) 8 10 RET615 13

20 Section 2 RET615 overview 1YHT530003D05 C Conf. Analog channels Binary channels CT VT RTD/mA BI BO D (14) 1) 10 (13) 1) 6/2 2) 8 10 E F G H J (14) 1) 10 (13) 1) 6/2 2) 8 10 K ) With optional BIO module 2) With optional RTD/mA module 2.4 Local HMI The LHMI is used for setting, monitoring and controlling the IED. The LHMI comprises the display, buttons, LED indicators and communication port. 14 RET615

21 1YHT530003D05 C Section 2 RET615 overview REF615 Overcurrent Dir. earth-fault Voltage protection Phase unbalance Thermal overload Breaker failure Disturb. rec. Triggered CB condition monitoring Supervision Arc detected Autoreclose shot in progr. A V3 EN Figure 2: Example of the LHMI Display The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size. Table 4: Small display Character size 1) Rows in the view Characters per row Small, mono-spaced (6x12 pixels) 5 20 Large, variable width (13x14 pixels) 4 8 or more 1) Depending on the selected language Table 5: Large display Character size 1) Rows in the view Characters per row Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels) 8 8 or more 1) Depending on the selected language RET615 15

22 Section 2 RET615 overview 1YHT530003D05 C The display view is divided into four basic areas A V3 EN Figure 3: Display layout 1 Header 2 Icon 3 Content 4 Scroll bar (displayed when needed) LEDs Keypad The LHMI includes three protection indicators above the display: Ready, Start and Trip. There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the operation mode can be selected with the LHMI, WHMI or PCM600. The LHMI keypad contains push-buttons which are used to navigate in different views or menus. With the push-buttons you can give open or close commands to objects in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode. 16 RET615

23 1YHT530003D05 C Section 2 RET615 overview A V1 EN Figure 4: LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port 2.5 Web HMI The WHMI allows accessing the IED via a Web browser. The supported Web browser versions are Internet Explorer 7.0, 8.0 and 9.0. WHMI is disabled by default. WHMI offers several functions. Programmable LEDs and event lists System supervision Parameter settings Measurement display Disturbance records Phasor diagram Single-line diagram The menu tree structure on the WHMI is almost identical to the one on the LHMI. RET615 17

24 Section 2 RET615 overview 1YHT530003D05 C A V4 EN Figure 5: Example view of the WHMI The WHMI can be accessed locally and remotely. Locally by connecting the laptop to the IED via the front communication port. Remotely over LAN/WAN. 2.6 Authorization The user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords. The default passwords can be changed with Administrator user rights. User authorization is disabled by default for LHMI but WHMI always uses authorization. 18 RET615

25 1YHT530003D05 C Section 2 RET615 overview Table 6: Username VIEWER OPERATOR Predefined user categories User rights Read only access Selecting remote or local state with Changing setting groups Controlling Clearing indications (only locally) ENGINEER Changing settings Clearing event list Clearing disturbance records Changing system settings such as IP address, serial baud rate or disturbance recorder settings Setting the IED to test mode Selecting language ADMINISTRATOR All listed above Changing password Factory default activation For user authorization for PCM600, see PCM600 documentation Audit trail The IED offers a large set of event-logging functions. Normal process-related events can be viewed by the normal user with Event Viewer in PCM600. Critical system and IED security-related events are logged to a separate nonvolatile audit trail for the administrator. Audit trail is a chronological record of system activities that allows the reconstruction and examination of the sequence of events and changes in an event. Past user and process events can be examined and analyzed in a consistent method with the help of Event List and Event Viewer in PCM600. The IED stores 2048 system events to the nonvolatile audit trail. Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the FIFO principle. User audit trail is defined according to the selected set of requirements from IEEE The logging is based on predefined usernames or user categories. The user audit trail events are supported in IEC , PCM600, LHMI and WHMI. Table 7: Audit trail events Audit trail event Configuration change Description Configuration files changed Firmware change Setting group remote User changed setting group remotely Table continues on next page RET615 19

26 Section 2 RET615 overview 1YHT530003D05 C Audit trail event Setting group local Control remote Control local Test on Test off Setting commit Time change View audit log Login Logout Firmware reset Audit overflow Description User changed setting group locally DPC object control remote DPC object control local Test mode on Test mode off Settings have been changed Administrator accessed audit trail Reset issued by user or tool Too many audit events in the time period PCM600 Event Viewer can be used to view the audit trail events together with normal events. Since only the administrator has the right to read audit trail, authorization must be properly configured in PCM600. The audit trail cannot be reset but PCM600 Event Viewer can filter data. Some of the audit trail events are interesting also as normal process events. To expose the audit trail events also as normal process events, define the level parameter via Configuration/Authorization/ Authority logging. Table 8: Comparison of authority logging levels Audit trail event None Configurati on change Authority logging level Setting group Setting group, control Settings edit Configuration change Firmware change Setting group remote Setting group local Control remote Control local Test on Test off Setting commit Time change View audit log Login Table continues on next page All 20 RET615

27 1YHT530003D05 C Section 2 RET615 overview Audit trail event Authority logging level Logout Firmware reset Audit overflow 2.7 Communication The IED supports a range of communication protocols including IEC 61850, IEC and Modbus. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the IEDs, is only enabled by the IEC communication protocol. The IEC communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC protocol. Disturbance recordings are available to any Ethernet-based application in the standard COMTRADE file format. The IED can send and receive binary signals from other IEDs (so-called horizontal communication) using the IEC GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. Furthermore, the IED supports sending and receiving of analog values using GOOSE messaging. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC standard. The IED can simultaneously report events to five different clients on the station bus. The IED can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC and Modbus. All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The IED can be connected to Ethernetbased communication systems via the RJ-45 connector (100Base-TX) or the fibreoptic LC connector (100Base-FX). For the correct operation of redundant loop topology, it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches. Otherwise, connecting the loop topology can cause problems to the network. The IED itself does not support link-down detection or RSTP. The ring recovery process is based on the aging of the MAC addresses, and the link-up/linkdown events can cause temporary breaks in communication. For a better performance of the self-healing loop, it is recommended that the external switch furthest from the IED loop is assigned as the root switch (bridge priority = 0) and the bridge priority increases towards the IED loop. The end links of the IED loop can be attached to the same external switch or to two adjacent external switches. A self-healing Ethernet ring requires a communication module with at least two Ethernet interfaces for all IEDs. RET615 21

28 Section 2 RET615 overview 1YHT530003D05 C Client A Client B Network A Network B Managed Ethernet switch with RSTP support Managed Ethernet switch with RSTP support GUID AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN Figure 6: Self-healing Ethernet ring solution The Ethernet ring solution supports the connection of up to 30 IEDs. If more than 30 IEDs are to be connected, it is recommended that the network is split into several rings with no more than 30 IEDs per ring. Each IED has a 50-μs store-and-forward delay, and to fullfill the performance requirements for fast horizontal communication, the ring size is limited to 30 IEDs Ethernet redundancy IEC specifies a network redundancy scheme that improves the system availability for substation communication. It is based on two complementary protocols defined in the IEC standard: parallel redundancy protocol PRP and high-availability seamless redundancy HSR protocol. Both the protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection. Therefore, both are able to overcome the failure of a link or switch with a zero-switchover time, thus fulfilling the stringent real-time requirements for the substation automation horizontal communication and time synchronization. PRP specifies that each device is connected in parallel to two local area networks. HSR applies the PRP principle to rings and to the rings of rings to achieve costeffective redundancy. Thus, each device incorporates a switch element that forwards frames from port to port. The HSR/PRP option is available for REF615, REM615, RET615 and REU RET615

29 1YHT530003D05 C Section 2 RET615 overview PRP Each PRP node, called a doubly attached node with PRP (DANP), is attached to two independent LANs operated in parallel. These parallel networks in PRP are called LAN A and LAN B. The networks are completely separated to ensure failure independence, and they can have different topologies. Both networks operate in parallel, thus providing zero-time recovery and continuous checking of redundancy to avoid communication failures. Non-PRP nodes, called singly attached nodes (SANs), are either attached to one network only (and can therefore communicate only with DANPs and SANs attached to the same network), or are attached through a redundancy box, a device that behaves like a DANP. COM600 SCADA Ethernet switch IEC PRP Ethernet switch REF615 REF620 RET620 REM620 REF615 GUID-334D26B1-C3BD-47B6-BD9D A5E9D V1 EN Figure 7: PRP solution In case a laptop or a PC workstation is connected as a non-prp node to one of the PRP networks, LAN A or LAN B, it is recommended to use a redundancy box device or an Ethernet switch with similar functionality between the PRP network and SAN to remove additional PRP information from the Ethernet frames. In some cases, default PC workstation adapters are not able to handle the maximum-length Ethernet frames with the PRP trailer. There are different alternative ways to connect a laptop or a workstation as SAN to a PRP network. Via an external redundancy box (RedBox) or a switch capable of connecting to PRP and normal networks By connecting the node directly to LAN A or LAN B as SAN By connecting the node to the IED interlink port RET615 23

30 Section 2 RET615 overview 1YHT530003D05 C HSR HSR applies the PRP principle of parallel operation to a single ring, treating the two directions as two virtual LANs. For each frame sent, a node, DANH, sends two frames, one over each port. Both frames circulate in opposite directions over the ring and each node forwards the frames it receives, from one port to the other. When the originating node receives a frame sent to itself, it discards that to avoid loops; therefore, no ring protocol is needed. Individually attached nodes, SANs, such as laptops and printers, must be attached through a redundancy box that acts as a ring element. For example, a 615 series IED with HSR support can be used as a redundancy box. GUID A7-3AEC-42B2-BC4D-3083B V1 EN Figure 8: HSR solution 24 RET615

31 1YHT530003D05 C Section 3 Section Standard configurations RET615 is available in eight alternative standard configurations. The standard signal configuration can be altered by means of the graphical signal matrix or the graphical application functionality of the Protection and Control IED Manager PCM600. Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions utilizing various logical elements including timers and flip-flops. By combining protection functions with logic function blocks the IED configuration can be adapted to user specific application requirements. Table 9: Standard configurations Description Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the high-voltage (HV) side Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earthfault protection for the high-voltage (HV) side Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earthfault protection for the low-voltage (LV) side Three-phase transformer differential protection with voltage protection for two-winding transformers, numerical restricted earth-fault protection for the high-voltage (HV) side Three-phase transformer differential protection with voltage protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side Three-phase transformer differential protection with voltage protection for two-winding transformers, high-impedance based restricted earth-fault protection for the high-voltage (HV) side Three-phase transformer differential protection with voltage protection for two-winding transformers, high-impedance based restricted earth-fault protection for the low-voltage (LV) side Three-phase transformer differential protection with voltage protection for two-winding transformers Transformer backup protection with voltage protection Std. conf. A B C D E F G H J K Table 10: Supported functions Function A B C D E F G H J K Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, low stage, instance 2 Table continues on next page x HV) HV) HV) HV) HV) HV) HV) HV) HV) LV) LV) LV) LV) LV) LV) LV) LV) LV) RET615 25

32 Section 3 1YHT530003D05 C Function A B C D E F G H J K Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 Non-directional earth-fault protection, low stage, instance 1 HV) HV) HV) HV) HV) HV) HV) HV) HV) LV) LV) LV) LV) LV) LV) LV) LV) LV) HV) HV) HV) HV) HV) HV) HV) HV) HV) LV) LV) LV) LV) LV) LV) LV) LV) LV) HV)1) HV)2) HV)1) HV)2) HV)2) Non-directional earth-fault protection, low stage, instance 2 LV)3) LV)4) LV)3) LV)4) LV)4) Non-directional earth-fault protection, high stage, instance 1 HV)1) HV)2) HV)1) HV)2) HV)2) Non-directional earth-fault protection, high stage, instance 2 LV)3) LV)4) LV)3) LV)4) LV)4) Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Negative-sequence overcurrent protection, instance 3 Negative-sequence overcurrent protection, instance 4 HV) HV) HV) HV) HV) HV) HV) HV) HV) LV) LV) LV) LV) LV) LV) LV) LV) LV) HV) LV) Residual overvoltage protection, instance 1 HV)5) HV)5) HV)5) HV)5) HV)5) Residual overvoltage protection, instance 2 HV)5) HV)5) HV)5) HV)5) HV)5) Three-phase undervoltage protection, instance 1 HV) HV) HV) HV) HV) Three-phase undervoltage protection, instance 2 HV) HV) HV) HV) HV) Three-phase overvoltage protection, instance 1 HV) HV) HV) HV) HV) Three-phase overvoltage protection, instance 2 HV) HV) HV) HV) HV) Positive-sequence undervoltage protection, instance 1 Positive-sequence undervoltage protection, instance 2 Negative-sequence overvoltage protection, instance 1 Negative-sequence overvoltage protection, instance 2 Three-phase thermal overload protection for power transformers, two time constants Stabilized and instantaneous differential protection for 2W transformers Numerical stabilized low impedance restricted earth-fault protection HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) LV)6) HV) LV)6) HV) Table continues on next page 26 RET615

33 1YHT530003D05 C Section 3 Function A B C D E F G H J K High impedance based restricted earth-fault protection HV) LV)7) HV) LV)7) HV) Circuit breaker failure protection HV)2) HV)2) HV)2) HV)2) HV)2) HV)2) HV)2) HV)2) HV)2) HV)2) Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) Arc protection, instance 2 o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) Arc protection, instance 3 o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) Multi-purpose protection, instance 1 9) o 10) o 10) o 10) o 10) o 10) Multi-purpose protection, instance 2 9) o 10) o 10) o 10) o 10) o 10) Multi-purpose protection, instance 3 9) o 10) o 10) o 10) o 10) o 10) Multi-purpose protection, instance 4 9) o 10) o 10) o 10) o 10) o 10) Multi-purpose protection, instance 5 9) o 10) o 10) o 10) o 10) o 10) Multi-purpose protection, instance 6 9) o 10) o 10) o 10) o 10) o 10) Control Circuit-breaker control HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) Disconnector control, instance 1 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Disconnector control, instance 2 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Earthing switch control 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Disconnector position indication, instance 1 Disconnector position indication, instance 2 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Disconnector position indication, instance 3 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Earthing switch indication, instance 1 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Earthing switch indication, instance 2 10) 10) 10) 10) 10) 10) 10) 10) 10) 10) Tap changer position indication Condition monitoring Circuit-breaker condition monitoring HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Fuse failure supervision Runtime counter for machines and devices Measurement Disturbance recorder Three-phase current measurement, instance 1 HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) Three-phase current measurement, instance 2 LV) LV) LV) LV) LV) LV) LV) LV) LV) LV) Sequence current measurement, instance 1 HV) HV) HV) HV) HV) HV) HV) HV) HV) HV) Sequence current measurement, instance 2 LV) LV) Residual current measurement, instance 1 HV) HV) HV) HV) HV) HV) Table continues on next page RET615 27

34 Section 3 1YHT530003D05 C Function A B C D E F G H J K Residual current measurement, instance 2 LV) LV) LV) LV) Three-phase voltage measurement HV) HV) HV) HV) HV) Residual voltage measurement HV) HV) HV) HV) HV) Sequence voltage measurement HV) HV) HV) HV) HV) Three-phase power and energy measurement HV) HV) HV) HV) HV) RTD/mA measurement o o o o o = included, = optional at the time of order HV = The function block is to be used on the high voltage side in the application LV = The function block is to be used on the low voltage side in the application 1) Io selectable by parameter and default value is Io measured 2) Io calculated is always used 3) IoB selectable by parameter, IoB measured as default 4) IoB calculated is always used 5) Uo selectable by parameter, Uo measured as default 6) IoB measured and 3IB are always used 7) IoB measured is always used 8) IoB calculated and 3IB are always used 9) Multi-purpose protection is used, for example, RTD/mA based protection 10) Available in IED and SMT but not connected to anything in logic Addition of control functions for primary devices and the use of binary inputs and outputs LED functionality If extra control functions intended for controllable primary devices are added to the configuration, additional binary inputs and/or outputs are needed to complement the standard configuration. If the number of inputs and/or outputs in a standard configuration is not sufficient, it is possible either to modify the chosen IED standard configuration in order to release some binary inputs or binary outputs which have originally been configured for other purposes, or to integrate an external input/output module, for example RIO600, to the IED. The external I/O module s binary inputs and outputs of can be used for the less timecritical binary signals of the application. The integration enables releasing some initially reserved binary inputs and outputs of the IED s standard configuration. The suitability of the IED s binary outputs which have been selected for primary device control should be carefully verified, for example make and carry and breaking capacity. If the requirements for the primary device control circuit are not met, using external auxiliary relays should be considered. The IED has dynamic programmable LEDs. The presentation of the LEDs in this manual differs from the actual function blocks in the configurations. 28 RET615

35 1YHT530003D05 C Section 3 GUID D-C F-8CF0-DC654779B178 V1 EN Figure 9: Drawing symbol used in the manual and the default connection of the LED function blocks in the configurations RET615 29

36 Section 3 1YHT530003D05 C 3.2 Connection diagrams GUID-529F6F D6F-8C55-04F6C14BFD94 V2 EN Figure 10: Connection diagram for the A and K configurations 30 RET615

37 1YHT530003D05 C Section 3 GUID-80F82A C09-A25D-86131D51331B V2 EN Figure 11: Connection diagram for the B configuration RET615 31

38 Section 3 1YHT530003D05 C GUID-32E5D770-0A2D-4FF3-9EAF-E7A82DB8A66C V2 EN Figure 12: Connection diagram for the C and J configurations 32 RET615

39 1YHT530003D05 C Section 3 GUID-FC955C0D-4BF9-40A8-B DE884FFE1 V2 EN Figure 13: Connection diagram for the D and J configurations RET615 33

40 Section 3 1YHT530003D05 C GUID-D26C5FA8-D7E AA36-B77D1A53392C V1 EN Figure 14: Connection diagram for the E configuration 34 RET615

41 1YHT530003D05 C Section 3 GUID-787C00E6-BEC E01D9F5EF V Figure 15: Connection diagram for the F configuration RET615 35

42 Section 3 1YHT530003D05 C GUID-AE41CEEF-C6E F0A-A5B962EBBC9C V1 EN Figure 16: Connection diagram for the G configuration 36 RET615

43 1YHT530003D05 C Section 3 GUID-4F C97B AAF-EB9816A13113 V1 EN Figure 17: Connection diagram for the H configuration RET615 37

44 Section 3 1YHT530003D05 C GUID-59EE E74-A3C1-3F2C9B6D3EB1 V1 EN Figure 18: Connection diagram for the E, F, G and H configurations (transformer current differential protection with phase-to-earth voltage protection and measurement) 3.3 Presentation of standard configurations Functional diagrams The functional diagrams describe the IED's functionality from the protection, measuring, condition monitoring, disturbance recording, control and interlocking perspective. Diagrams show the default functionality with simple symbol logics forming principle diagrams. The external connections to primary devices are also shown, stating the default connections to measuring transformers. The positive measuring direction of directional protection functions is towards the outgoing feeder. The functional diagrams are divided into sections with each section constituting one functional entity. The external connections are also divided into sections. Only the relevant connections for a particular functional entity are presented in each section. 38 RET615

45 1YHT530003D05 C Section 3 Protection function blocks are part of the functional diagram. They are identified based on their IEC name but the IEC based symbol and the ANSI function number are also included. Some function blocks, such as PHHPTOC, are used several times in the configuration. To separate the blocks from each other, the IEC name, IEC symbol and ANSI function number are appended with a running number, that is an instance number, from one upwards. If the block has no suffix after the IEC or ANSI symbol, the function block has been used, that is, instantiated, only once. The IED s internal functionality and the external connections are separated with a dashed line presenting the IED s physical casing. Signal Matrix and Application Configuration With Signal Matrix and Application Configuration in PCM600, it is possible to modify the standard configuration according to the actual needs. The IED is delivered from the factory with default connections described in the functional diagrams for binary inputs, binary outputs, function-to-function connections and alarm LEDs. The Signal Matrix is used for GOOSE signal input engineering and for making cross-references between the physical I/O signals and the function blocks. The Signal Matrix tool cannot be used for adding or removing function blocks, for example, GOOSE receive function blocks. The Application Configuration tool is used for these kind of operations. If a function block is removed with Application Configuration, the function related data disappears from the menus as well as from the data model, with the exception of some basic function blocks, which are mandatory and thus cannot be removed from the IED configuration by removing them from the Application Configuration. 3.4 Standard configuration A Applications The standard configuration includes three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the highvoltage (HV) side. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600. RET615 39

Relion 615 series. Transformer Protection and Control RET615 Product Guide

Relion 615 series. Transformer Protection and Control RET615 Product Guide Relion 615 series Transformer Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...14 4. Application... 15 5. Supported ABB solutions...

More information

Operation Manual Feeder Protection Relay REF615

Operation Manual Feeder Protection Relay REF615 Feeder Protection Relay REF615 Document ID: 1MRS756376 Issued: 02.07.2008 Revision: C Product version: 1.1 Copyright 2008 - ABB. All rights reserved Copyright This document and parts thereof must not

More information

RED615 ANSI Line differential protection and control

RED615 ANSI Line differential protection and control DESCRIPTIVE BULLETIN RED615 ANSI Line differential protection and control RED615 is a phase-segregated, twoend line differential protection and control relay for protection, control, measurement and supervision

More information

Relion 620 series. Transformer protection and control RET620 Flexibility for utility and industrial power distribution systems

Relion 620 series. Transformer protection and control RET620 Flexibility for utility and industrial power distribution systems Relion 620 series Transformer protection and control RET620 Flexibility for utility and industrial power distribution systems Compact protection and control with voltage regulation for two-winding power

More information

Relion 615 series. Feeder protection and control REF615

Relion 615 series. Feeder protection and control REF615 Relion 65 series Feeder protection and control REF65 Compact and versatile solution for utility and industrial power distribution systems REF65 is a dedicated feeder IED perfectly aligned for the protection,

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Relion 615 series. Feeder Protection and Control REF615 DNP3 Point List Manual

Relion 615 series. Feeder Protection and Control REF615 DNP3 Point List Manual Relion 615 series Feeder Protection and Control REF615 DNP3 Document ID: 1MRS756711 Issued: 03.07.2009 Revision: B Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series. Motor Protection and Control REM615 Modbus Point List Manual

Relion 615 series. Motor Protection and Control REM615 Modbus Point List Manual Relion 615 series Motor Protection and Control REM615 Modbus Document ID: 1MRS756877 Issued: 03.07.2009 Revision: A Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

Relion 615 series. Transformer Protection and Control RET615 ANSI Modbus Point List Manual

Relion 615 series. Transformer Protection and Control RET615 ANSI Modbus Point List Manual Relion 615 series Transformer Protection and Control RET615 ANSI Modbus Document ID: 1MAC207644-MB Issued: 01/20/2010 Revision: A Product version: 2.0 Copyright 2010 ABB. All rights reserved Copyright

More information

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual Relion 615 series Feeder Protection and Control REF615 Modbus Document ID: 1MRS756581 Issued: 03.07.2009 Revision: C Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

Equipped with Relion technology. evd4 Breaker Integrated Protection RBX615 Operation Manual

Equipped with Relion technology. evd4 Breaker Integrated Protection RBX615 Operation Manual Equipped with Relion technology evd4 Breaker Integrated Protection RBX615 Document ID: 1MRS757100 Issued: 2011-12-13 Revision: B Product version: 2.0 Copyright 2011 ABB. All rights reserved Copyright

More information

Relion 615 series. Voltage Protection and Control REU615 Application Manual

Relion 615 series. Voltage Protection and Control REU615 Application Manual Relion 615 series Voltage Protection and Control REU615 Document ID: 1MRS757054 Issued: 2016-05-20 Revision: H Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved Copyright This document

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

Connectivity Packages. User's Guide - ANSI Version

Connectivity Packages. User's Guide - ANSI Version Connectivity Packages 1MRS756194 Issued: 30.11.2006 Version: A/30.11.2006 Connectivity Packages Contents Copyrights... 5 1. Introduction...... 7 1.1. Intended audience...... 7 1.2. Related documents.........

More information

Electrical Integration with Smart Communication

Electrical Integration with Smart Communication Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Feeder Protection REF615. Product Guide

Feeder Protection REF615. Product Guide Product Guide Contents 1 Description.............................. 3 2 Standard configurations................. 3-4 3 Protection functions.................... 4-5 4 Application...........................

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

Relion Protection and Control. 615 series Cyber Security Deployment Guideline

Relion Protection and Control. 615 series Cyber Security Deployment Guideline Relion Protection and Control 615 series Document ID: 1MRS758280 Issued: 2016-05-20 Revision: B Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved Copyright This document and parts thereof

More information

Relion 615 series. Line Differential Protection and Control RED615 Application Manual

Relion 615 series. Line Differential Protection and Control RED615 Application Manual Relion 615 series Line Differential Protection and Control RED615 Document ID: 1MRS756498 Issued: 2016-05-20 Revision: M Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved Copyright This

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Relion Protection and Control. 615 series IEC Communication Protocol Manual

Relion Protection and Control. 615 series IEC Communication Protocol Manual Relion Protection and Control 615 series IEC 60870-5-103 Communication Protocol Manual Document ID: 1MRS756710 Issued: 2016-05-20 Revision: G Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved

More information

RELION PROTECTION AND CONTROL 615 series ANSI Cyber Security Deployment Guideline

RELION PROTECTION AND CONTROL 615 series ANSI Cyber Security Deployment Guideline RELION PROTECTION AND CONTROL 615 series ANSI Document ID: 1MAC052704-HT Issued: 2018-02-26 Revision: A Product version: 5.0 FP1 Copyright 2018 ABB. All rights reserved Copyright This document and parts

More information

RELION PRODUCT FAMILY Grid Automation Remote Monitoring and Control REC615 Product Guide

RELION PRODUCT FAMILY Grid Automation Remote Monitoring and Control REC615 Product Guide RELION PRODUCT FAMILY Grid Automation Remote Monitoring and Control REC615 Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...13 4. Application... 14 5.

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...8 4. Application...16 5. Supported ABB solutions...22

More information

Protection and Control IED Manager PCM600 Getting Started Guide

Protection and Control IED Manager PCM600 Getting Started Guide Protection and Control IED Manager PCM600 Document ID: 1MRS757866 Issued: 2018-04-18 Revision: C Product version: 2.9 Copyright 2018 ABB. All rights reserved Copyright This document and parts thereof

More information

Relion 620 series. Feeder Protection and Control REF620 Product Guide

Relion 620 series. Feeder Protection and Control REF620 Product Guide Relion 620 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Default configurations...3 3. Protection functions...10 4. Application...10 5. Supported ABB solutions...15

More information

Relion 615 series. Generator and Interconnection Protection REG615 Product Guide

Relion 615 series. Generator and Interconnection Protection REG615 Product Guide Relion 615 series Generator and Interconnection Protection Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...9 4. Application... 9 5. Supported ABB solutions...

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...7 4. Application...9 5. Supported ABB solutions...12 6.

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

PRODUCT GUIDE. REM615 ANSI 5.0 FP1 Motor protection and control

PRODUCT GUIDE. REM615 ANSI 5.0 FP1 Motor protection and control PRODUCT GUIDE REM615 ANSI 5.0 FP1 Motor protection and control 2 REM615 ANSI 5.0 FP1 MOTOR PROTECTION AND CONTROL Table of contents 03 1. Description 03-09 2. Standard configuration 10-12 3. Protection

More information

Protection and Control IED Manager PCM600 Product Guide

Protection and Control IED Manager PCM600 Product Guide Protection and Control IED Manager Product Guide Protection and Control IED Manager Product version: 2.9 Contents 1. Description... 3 2. Project explorer... 3 3. Parameter setting... 3 4. Graphical application

More information

Relion 615 series. Transformer Protection and Control RET615 Modbus Point List Manual

Relion 615 series. Transformer Protection and Control RET615 Modbus Point List Manual Relion 615 series Transformer Protection and Control RET615 Modbus Document ID: 1MRS756878 Issued: 2016-05-20 Revision: G Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved Copyright This

More information

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Relion 630 series Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Integrated load-shedding and protection solution The PML630 is a freely-configurable

More information

Relion 615 Series. Motor Protection and Control REM615 ANSI DNP3 Point List Manual

Relion 615 Series. Motor Protection and Control REM615 ANSI DNP3 Point List Manual Relion 615 Series Motor Protection and Control REM615 ANSI 3 List Manual Document ID: 1MAC254287-MB Issued: 4/14/2011 Revision: B Product version: 4.0 Copyright 2011 ABB. All rights reserved. Copyright

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

Generator and interconnection protection REG615 Compact and versatile solution for utility and industrial power distribution systems

Generator and interconnection protection REG615 Compact and versatile solution for utility and industrial power distribution systems Relion 65 series Generator and interconnection protection REG65 Compact and versatile solution for utility and industrial power distribution systems Compact generator and extensive interconnection protection

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Feeder Protection REF615 ANSI. Product Guide

Feeder Protection REF615 ANSI. Product Guide Product Guide Contents 1 Description............................. 3 2 Standard configurations................ 3-4 3 Protection functions................... 4-5 4 Application.......................... 6-7

More information

Relion 615 series. Line Differential Protection and Control RED615 Product Guide

Relion 615 series. Line Differential Protection and Control RED615 Product Guide Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...12 4. Application... 12 5. Supported ABB

More information

Relion. Substation Merging Unit SMU615 Product Guide

Relion. Substation Merging Unit SMU615 Product Guide Relion Substation Merging Unit Product Guide Contents 1. Description... 3 2. Application configurations...3 3. Communication... 5 4. Application... 5 5. Process bus... 7 6. Self-supervision... 7 7. Secondary

More information

Relion 615 series. Voltage Protection and Control REU615 Product Guide

Relion 615 series. Voltage Protection and Control REU615 Product Guide Relion 615 series Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...6 4. Application...8 5. Supported ABB solutions...10 6. Control...12 7. Measurement...12

More information

Relion product family. Remote monitoring and control REC615 Protection of cable feeders with superior fault detection and location

Relion product family. Remote monitoring and control REC615 Protection of cable feeders with superior fault detection and location elion product family emote monitoring and control EC615 Protection of cable feeders with superior fault detection and location U12 0. 0 kv P 0.00 kw Q 0.00 kvar I2 0 A ESC A 1 15 AN DC IN CONSOE/S1 S2

More information

Protection and Control IED Manager PCM600 Product Guide

Protection and Control IED Manager PCM600 Product Guide Product Guide Contents 1. Description...3 2. Project explorer...4 3. Parameter setting...4 4. Graphical application configuration...4 5. Signal matrix...5 6. Graphical display editor...5 7. Hardware configuration...6

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

RELION 615 SERIES Motor Protection and Control REM615 ANSI Application Manual

RELION 615 SERIES Motor Protection and Control REM615 ANSI Application Manual RELIN 615 SERIES Motor Protection and Control REM615 ANSI Document ID: 1MAC254299-MB Issued: 2018-02-26 Revision: A Product version: 5.0 FP1 Copyright 2018 ABB. All rights reserved Copyright This document

More information

Relion 611 series. Busbar and Multipurpose Differential Protection and Control REB611 Product Guide

Relion 611 series. Busbar and Multipurpose Differential Protection and Control REB611 Product Guide Relion 611 series Busbar and Multipurpose Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configuration...3 3. Protection functions...5 4. Application...5 5. Supported

More information

Relion Protection and Control. 615/620 series ANSI Modbus Communication Protocol Manual

Relion Protection and Control. 615/620 series ANSI Modbus Communication Protocol Manual Relion Protection and Control 615/620 series ANSI Modbus 615 series Product version 2.0 620 series Product version 1.0 Document ID: 1MAC052634-MB Issued: 11/23/2010 Revision: D Copyright 2010 ABB. All

More information

Power Products. Protection and Control IED Manager PCM600 Product Guide

Power Products. Protection and Control IED Manager PCM600 Product Guide Power Products Protection and Control IED Manager Product Guide Contents 1. Description............................ 3 2. Tool variants........................... 3 3. Connectivity packages...................

More information

COM600 series, Version 5.0 Modbus Serial Slave (OPC) User's Manual

COM600 series, Version 5.0 Modbus Serial Slave (OPC) User's Manual CO600 series, Version 5.0 odbus Serial Slave (OPC) User's anual 1RS756913 Issued: 9.10.2009 Version: E/24.5.2017 CO600 series, Version 5.0 odbus Serial Slave (OPC) User's anual Contents: 1. About this

More information

RELION PROTECTION AND CONTROL 615 series ANSI Modbus Communication Protocol Manual

RELION PROTECTION AND CONTROL 615 series ANSI Modbus Communication Protocol Manual RELION PROTECTION AND CONTROL 615 series ANSI Modbus Communication Protocol Manual Document ID: 1MAC057386-MB Issued: 2018-02-26 Revision: A Product version: 5.0 FP1 Copyright 2018 ABB. All rights reserved

More information

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual Overcurrent and Earth-Fault Relay MRS75094-MUM Issued: 4.09.998 Version: D/4..2005 Overcurrent and Earth-Fault Relay Contents. About this manual...5.. Copyrights...5.2. Trademarks...5.3. Guarantee...5.4.

More information

Relion 620 series. Motor Protection and Control REM620 Product Guide

Relion 620 series. Motor Protection and Control REM620 Product Guide Relion 620 series Motor Protection and Control Product Guide Contents 1. Description... 3 2. Default configuration...3 3. Protection functions...9 4. Application... 9 5. Supported ABB solutions... 14 6.

More information

Protection System Simulator SIM600. Installation Manual

Protection System Simulator SIM600. Installation Manual Protection System Simulator SIM600 1MRS756102 Issued: 08.12.2008 Version: B Protection System Simulator SIM600 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. Guarantee...

More information

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations siemens.com/siprotec5 SIPROTEC 5 Table of content Introduction New functions of V7.8 SIPROTEC 5 - the core of Digital Substation

More information

Relion Protection and Control. 615 series ANSI Modbus Communication Protocol Manual

Relion Protection and Control. 615 series ANSI Modbus Communication Protocol Manual Relion Protection and Control 615 series ANSI Modbus Document ID: 1MAC052634-MB Issued: 01/20/2010 Revision: C Product version: 2.0 Copyright 2010 ABB. All rights reserved Copyright This document and

More information

Relion 611 series. Voltage Protection and Control REU611 Product Guide

Relion 611 series. Voltage Protection and Control REU611 Product Guide Relion 611 series Voltage Protection and Control Product Guide Contents 1. Description... 3 2. Standardized configuration...3 3. Protection functions...6 4. Application... 6 5. Supported ABB solutions...

More information

Bay protection functions REB500 Application Manual

Bay protection functions REB500 Application Manual png Substation Automation Products Application Manual Document ID: 1MRK 505 353-UEN Issued: March 2016 Revision: A Product version: 8.2 Copyright 2016 ABB. All rights reserved Copyright This document

More information

Relion product family. Grid Automation Remote Monitoring and Control REC615 DNP3 Communication Protocol Manual

Relion product family. Grid Automation Remote Monitoring and Control REC615 DNP3 Communication Protocol Manual Relion product family Grid Automation Remote Monitoring and Control REC615 DNP3 Document ID: 1MRS757804 Issued: 2015-03-06 Revision: B Product version: 1.1 Copyright 2015 ABB. All rights reserved Copyright

More information

Relion Protection and Control. 611 series Modbus Communication Protocol Manual

Relion Protection and Control. 611 series Modbus Communication Protocol Manual Relion Protection and Control 611 series Modbus Document ID: 1MRS757461 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Copyright This document and parts thereof

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

Lars Frisk, Frantz Kruger, Integrator Partner Seminar 2012 Bay level product news Relion & supporting products

Lars Frisk, Frantz Kruger, Integrator Partner Seminar 2012 Bay level product news Relion & supporting products Lars Frisk, Frantz Kruger, Integrator Partner Seminar 2012 Bay level product news Relion & supporting products Bay level product news Relion & Relion supporting products Relion for generation, transmission

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

COM600 Station Automation Series External OPC Client Access 3.1. User's Guide

COM600 Station Automation Series External OPC Client Access 3.1. User's Guide COM600 Station Automation Series External OPC Client Access 3.1 1MRS755564 Issued: 10.03.2005 Version: C/21.12.2007 COM600 Station Automation Series External OPC Client Access 3.1 Contents: 1. About this

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation

More information

Grid Automation Controller COM600 How it fits into the Smart Grid?

Grid Automation Controller COM600 How it fits into the Smart Grid? ABB Oy Distribution Automation Grid Automation Controller How it fits into the Smart Grid? May 27, 2014 Slide 1 1MRS756763 E Content Technical Presentation May 27, 2014 Slide 2 Description Grid Automation

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

Laurent Sowazi, EPMV-DA/ Africa Channel Partner event, 2016 ABB Distribution Automation Making Grids Smarter. ABB November 23, 2016

Laurent Sowazi, EPMV-DA/ Africa Channel Partner event, 2016 ABB Distribution Automation Making Grids Smarter. ABB November 23, 2016 Laurent Sowazi, EPMV-DA/ Africa Channel Partner event, 2016 ABB Distribution Automation Making Grids Smarter Slide 1 Distribution Automation Footprint Global deliveries Finland (Vaasa) Home market deliveries

More information

Motor Control and Protection Unit M10x AO Module User Guide

Motor Control and Protection Unit M10x AO Module User Guide Motor Control and Protection Unit M10x AO Module User Guide The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility

More information

Relion product family. Grid Automation Remote Monitoring and Control REC615 Modbus Communication Protocol Manual

Relion product family. Grid Automation Remote Monitoring and Control REC615 Modbus Communication Protocol Manual Relion product family Grid Automation Remote Monitoring and Control REC615 Modbus Document ID: 1MRS757803 Issued: 2015-03-06 Revision: B Product version: 1.1 Copyright 2015 ABB. All rights reserved Copyright

More information

CAP 505. User s Guide

CAP 505. User s Guide CAP 505 1MRS752292-MUM CAP 505 Issued: 04.10.2002 Version: L/05.01.2005 1. About this manual...7 1.1. Copyrights...7 1.2. Trademarks...7 1.3. General...7 1.4. Use of symbols...8 1.5. Abbreviations...8

More information

COM600 series 5.0 Operator's Manual

COM600 series 5.0 Operator's Manual COM600 series 5.0 1MRS756705 Issued: 13.2.2009 Version: F/24.5.2017 COM600 series 5.0 Contents: 1. About this manual... 5 1.1. Copyright... 5 1.2. Disclaimer... 5 1.3. Conformity... 6 1.4. Trademarks...

More information

Substation Automation Products. Distributed busbar protection REB500 Communication Protocol Manual, IEC 61850

Substation Automation Products. Distributed busbar protection REB500 Communication Protocol Manual, IEC 61850 Substation Automation Products Communication Protocol Manual, IEC 61850 Document ID: 1MRK 511 342-UEN Issued: May 2015 Revision: - Product version: 8.10 Copyright 2015 ABB. All rights reserved Copyright

More information

Relion 615 series. Line Differential Protection and Control RED615 Product Guide

Relion 615 series. Line Differential Protection and Control RED615 Product Guide Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...6 4. Application...8 5. Supported ABB solutions...13

More information

Ethernet Network Redundancy in SCADA and real-time Automation Platforms.

Ethernet Network Redundancy in SCADA and real-time Automation Platforms. Ethernet Network Redundancy in SCADA and real-time Automation Platforms www.copadata.com sales@copadata.com Content 1. ABSTRACT... 2 2. INTRODUCTION... 2 IEC 61850 COMMUNICATION SERVICES... 2 APPLICATION

More information

PRODUCT GUIDE. REG615 Generator protection and control

PRODUCT GUIDE. REG615 Generator protection and control PRODUCT GUIDE REG615 Generator protection and control 2 REG615 GENERATOR PROTECTION AND CONTROL Table of contents 004 Description 004 008 Standard configurations 009 Protection funtions 009 Application

More information

Relion Protection and Control. 611 series IEC Engineering Guide

Relion Protection and Control. 611 series IEC Engineering Guide Relion Protection and Control 611 series IEC 61850 Document ID: 1MRS757465 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Copyright This document and parts

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Protection and Control IED Manager PCM600 Cyber Security Deployment Guideline

Protection and Control IED Manager PCM600 Cyber Security Deployment Guideline Protection and Control IED Manager PCM600 Document ID: 1MRS758440 Issued: 2018-04-18 Revision: C Product version: 2.9 Copyright 2018 ABB. All rights reserved Copyright This document and parts thereof

More information

Relion Protection and Control. 615 series DNP3 Communication Protocol Manual

Relion Protection and Control. 615 series DNP3 Communication Protocol Manual Relion Protection and Control 615 series DNP3 Document ID: 1MRS756709 Issued: 2012-05-11 Revision: D Product version: 4.0 Copyright 2012 ABB. All rights reserved Copyright This document and parts thereof

More information

evd4 RBX615 Application manual

evd4 RBX615 Application manual Medium voltage products evd4 RBX615 Application manual RBX615 Standard configurations 1 1. Protection functions 3 1.1. Overcurrent protection 3 1.2. Thermal protection 3 1.3. Motor stall protection 4 1.4.

More information

Document ID: 1VCD Product Name: MyRemoteCare Gateway Document Name: Operation Manual Issued: Revision: R0001 Product Version: 1.

Document ID: 1VCD Product Name: MyRemoteCare Gateway Document Name: Operation Manual Issued: Revision: R0001 Product Version: 1. Document ID: 1VCD601158 Product Name: Document Name: Operation Manual Issued: 2012-06-15 Revision: R0001 Product Version: 1.0 Copyright 2012 ABB. All rights reserved Copyright This document and parts thereof

More information

Grid Automation Products. SAM600 Process Bus I/O System Operation Manual

Grid Automation Products. SAM600 Process Bus I/O System Operation Manual b Grid Automation Products SAM600 Process Bus I/O System Document ID: 1MRK 511 434-UEN Issued: June 2017 Revision: A Product version: 1.2 Copyright 2016-2017 ABB. All rights reserved Copyright This document

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756170 Issued: 02.03.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...15 1. Introduction...17 1.1. This Manual...17 1.2. Use of symbols...17 1.3.

More information

Distributed busbar protection REB500 Operation Manual

Distributed busbar protection REB500 Operation Manual REB500 Substation Automation Products Operation Manual Document ID: 1MRK 500 121-UEN Issued: May 2015 Revision: - Product version: 8.10 Copyright 2015 ABB. All rights reserved Copyright This document

More information

Distribution Management System Open++ Opera v.3.3. User Manual

Distribution Management System Open++ Opera v.3.3. User Manual Distribution Management System Open++ Opera v.3.3 User Manual 1MRS 751464-MUM Issued: 31.12.1999 Version: D/29.8.2003 Program Revision: 3.3D We reserve the right to change data without prior notice. User

More information

Device Management Basic HART DTM 6.0 Installation

Device Management Basic HART DTM 6.0 Installation Device Management Basic HART DTM 6.0 Installation System Version 6.0 Power and productivity for a better world TM Device Management Basic HART DTM 6.0 Installation System Version 6.0 NOTICE This document

More information

A low-cost, economical solution for distribution feeder protection

A low-cost, economical solution for distribution feeder protection SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Relion 605 series. Self-powered feeder protection REJ603 Application Manual

Relion 605 series. Self-powered feeder protection REJ603 Application Manual Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection REJ603 Document ID: 1MDU07221-YN Issued: 2017-10-30 Revision: D Product version: 3.0 Copyright 2017 ABB. All rights

More information

Substation automation products. MicroSCADA Pro for substation automation

Substation automation products. MicroSCADA Pro for substation automation Substation automation products for substation automation Perfect control anywhere, anytime is an investment for today and tomorrow. Start, for instance, with monitoring or gateway functionality and integrate

More information

RELION PRODUCT FAMILY Grid Automation Recloser Protection and Control RER615 Product Guide

RELION PRODUCT FAMILY Grid Automation Recloser Protection and Control RER615 Product Guide RELION PRODUCT FAMILY Recloser Protection and Control RER615 Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...10 4. Application... 10 5. Supported ABB

More information

RELION 615 SERIES Transformer Protection and Control RET615 ANSI Modbus Point List Manual

RELION 615 SERIES Transformer Protection and Control RET615 ANSI Modbus Point List Manual RELION 615 SERIES Transformer Protection and Control RET615 ANSI Modbus Document ID: 1MAC203705-MB Issued: 2018-02-26 Revision: A Product version: 5.0 FP1 Copyright 2018 ABB. All rights reserved Copyright

More information