MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits
|
|
- Primrose Collins
- 5 years ago
- Views:
Transcription
1 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution for generator, reactor, motor and busbar applications where fast clearance of faults is required. Combined with the P79x, a standalone metrosil and resistor unit, it provides simplified scheme engineering for single or three-phase differential applications. Customer Benefits Simple scheme engineering Reliable algorithm Supervision functions included in the same protection box As well as offering the same application benefits as traditional high impedance electromechanical protection schemes, it combines the added benefits of numerical technology to provide advanced communications, event records, fault records, disturbance records and ancillary protection features.
2 02 APPLICATION When circulating current protection schemes are subjected to through faults, the sudden and often asymmetrical growth in the system current can cause the line current transformers to reach saturation. Under these conditions the variation in current transformer magnetising characteristics can cause large ratio errors with a consequent circuit imbalance and maloperation of the protective relays. To ensure stability, it is common practice to employ high impedance relays set to operate at a slightly higher voltage than that developed in the worst theoretical case of this condition for a given through fault current. On a balanced earth fault system for example, this is when one current transformer of a group is saturated whilst the others remain unaffected. The saturated transformer presents a low impedance path in parallel with the relay and limits the voltage applied. For internal faults this limitation does not exist and voltages of twice the setting are easily reached resulting in fast operation of the differential relay. The P72x relay together with the P79x unit, is designed for applications where sensitive settings with stability on heavy through faults are required. It offers a reliable protection for busbars, transformers windings, generators, reactors and motors. FUNCTIONAL OVERVIEW OVERVIEW Two models are available: MiCOM P721 is a single-phase high impedance differential protection. It is suitable for restricted earth fault or balanced earth fault applications. MiCOM P723 can be configured either as high impedance differential three-phase protection (87) or as high impedance differential earth protection (87N). The connection setting determines whether 87 or 87N is being used. MAIN functions Phase segregated high impedance differential protection (87A, 87B, 87C) The application of P723 numerical relay as differential protection for machines and busbar installations is based on the high impedance differential principle. This principle requires stabilising resistors in each phase and a metrosil is generally required across the relay circuit. These are included in the P79x accessory as shown in Figure 1. Stability for any type of fault occurring outside the protected zone and satisfactory operation for faults within the zone are achieved. Figure 1 shows the typical application diagram where P723 is configured as a phase segregated high impedance differential protection. Protected Plant I diff R ST Metrosil P79x 87P 87N Remote Comm. Port Local Communication Self Monitoring Fault Records Measurements Disturbance Record 95P LEDs 95N 50BF Binary Input / Output P72x P72x and P79x together offer a simple and reliable high impedance differential protection
3 03 PROTECTION functions OVERVIEW ANSI Features P721 P723 87P Phase segregated high impedance current differential protection 95P Phase bus-wire supervision 87N Restricted earth fault protection 95N Earth bus-wire supervision 87CZ Check zone input 50BF Breaker failure detection GENERAL FEATURES Features P721 P723 Number of opto-isolated inputs 2 5 Number of relay output contacts 4 8 Event recording Fault recording Disturbance recording 5 5 Instantaneous records 5 5 Setting groups 2 2 Auxiliary timers 4 4 Communication protocols Modbus RTU (rear port) DNP3 (rear port) IEC (rear port) Modbus RTU (front port) Setting software MiCOM S1 Studio Logic equations AND, OR and NOT gates 8 Boolean equations Measurements Neutral supervision/differential currents (INdiff) Phase supervision/differential currents (IAdiff, IBdiff and ICdiff) Maximum differential currents (ImaxAdiff, ImaxBdiff and ImaxCdiff) Maximum differential neutral currents (ImaxNdiff) Figure 1: P723 configured as phase segregated high impedance differential busbar protection
4 04 High impedance differential earth fault protection (87N) The P721 has a single differential element and may only function as an 87N protection. The P723 can be configured as 87N when only one analogue current input is required. Restricted earth fault protection is included to cover a larger percentage of the transformer windings than might be possible with the main biased differential transformer protection. 87N is commonly referred as restricted earth fault (REF) protection for star windings and balanced earth fault (BEF) protection for delta windings. Figures 2 and 3 show the P72x configured for these applications. GENERAL SCHEME LOGIC The schemes in figures 4 and 5 describe the logic of the three-phase high impedance differential protection and high impedance differential earth fault protection relays. External blocking inputs are available to allow the user to configure an input to enable or disable the differential element. A selectable logic input is also available as a check zone input from another P72x or differential relay. [87] DIFF Blocking Logic 1 / 2 & DT [87CZ] Check Zone & Start [87] DIFF Temporized [87] tdiff [95] SUP DT Start [95] SUP Temporized [95] tsup Figure 4: General scheme of the three-phase high impedance differential protection [87N] DIFF Start [87N] DIFF Blocking Logic 1 / 2 & DT Temporized [87N] tdiff [95N] SUP Start [95N] SUP DT Temporized [95N] tsup Figure 2: BEF protection for the delta winding of a power transformer with supply system earthed Figure 5: General scheme of high impedance differential earth fault protection CONTROL AND INDICATION Control Two blocking logics are available where for example opto inputs can be independently configured to block the differential element or any of the auxiliary timer functions. Logic equations The MiCOM P72X relays integrate complete logic equations to allow customization of the product based on customer application. Up to 8 independent Boolean equations can be used. Each equation offers the possibility to use AND, OR & NOT logical gates. Up to 16 parameters can be used for each equation. Every result of equation can be time delayed and assigned to any output relays, trip, trip latching and/or HMI LEDs. Figure 3: REF protection of a 3 phase, 4 wire system applicable to star connected generators or power transformer windings with neutral earthed at generator/transformer star point
5 05 Optos Protection elements Automatic Control Gate Logic Timers Relay contacts LED's Phase segregated outputs are available from the buswire supervision such that each phase can be stabilised by short circuiting the bus-wires as required. The differential elements are internally blocked due to bus-wire supervision (although this will not negate the requirement for external shorting of bus-wires). LEDs Four programmable LEDs are available. Alarms Protection and control functions generate alarms on the screen and LEDs as configured. Certain alarms can be inhibited or automatically reset by preliminary parameter setting. Alarms can be stored in non-volatile memory. SUPERVISORY functions Open circuit failures of the CTs or bus-wires will cause a spill current to flow through the differential element and operation will occur if this current is greater than the setting. Two methods are used to prevent nuisance tripping due to open circuit conditions: 1. Bus-wire supervision elements are provided to monitor for a continuous low level of spill current. After a time delay, this relay would usually short circuit the AC bus-wires to ensure stability and also give an alarm. The disadvantage of this scheme is that the differential elements must be set higher than the bus-wire supervision elements (and usually above maximum load conditions) if nuisance tripping is to be avoided. This may create sensitivity issues. 2. Duplicate differential elements (main and check zones) fed from separate CTs using segregated (phase by phase) bus-wires. Tripping is only permitted when both differential elements operate. The advantage of this scheme is that the differential settings can remain very sensitive (below full load current values), but this will require a total duplication of the scheme. The selectable logic input from another P72x deployed as a check zone is available for this function. The above two methods are usually used in conjunction with each other, although to reduce costs either scheme could be used independently. Bus-wire Shorting To limit the power dissipated in the resistance, after the differential trip protection [87] or bus-wire supervision [95] are activated, the bus-wires must be short-circuited. This function is latched in the internal logic. The bus-wire shorting signal can be connected as shown in figures 1, 2 and 3. CB Failure function The CB failure output from the P72x is an input to the breaker failure scheme. The general scheme for the breaker failure detection function is shown in figure 6. Trip [87] tdiff Idiff< Pick up timer CB Fail time tbf Figure 6 CBF detection logic & CB Fail OPERATION AND CONfIGuRATION Setting groups External conditions may request the need for different settings. provide two independent setting groups. The active setting group can be switched to the other from the local HMI or from external conditions (opto input change of state or DCS control). Multi-language user interface (HMI) All functions, including protection, automation, communication, LEDs, inputs and outputs, can be programmed and modified using the front panel user interface (Human Machine Interface, HMI). The backlit LCD informs the user about settings, measurements & faults thanks to the pull-down structure menu allowing easy and quick access to any data. Moreover, even if the relay is delivered with the language specified at the order, the user can change the language used within the relay from the HMI.
6 06 Clear Key Enter Key The P721 and P723 measure the neutral supervision/differential currents (I Ndiff ). Trip Led Alarm Led Read Key The P723 measures the maximum differential currents (Imax Adiff, Imax Bdiff and Imax Cdiff ). The P721 and P723 measure the maximum differential neutral currents (Imax Ndiff ). Fault records Device fail Power supply [ Cursor Keys 25 time-tagged fault records that indicate the faulted phase, protection operation, active setting group, pre-fault and differential fault currents magnitudes are available. Disturbance records Freely Programmable Leds RS 232 A disturbance record is generated for every trip. In addition, the disturbance recorder can be triggered by an opto-isolated input, or a remote control signal. Battery is not used anymore MEASuREMENTS AND RECORDING Measurements The following measurements are available for display and remote measurements: The P723 measures Phase supervision/ differential currents (I Adiff, I Bdiff and I Cdiff ). Up to five records of 3 seconds each one can be stored. The disturbance records are 32 samples per cycle. Event records 250 time-tagged event records can be stored. Events include operation and reset of inputs/ outputs, alarms, internal signals, and contacts. All events are time stamped to 1ms, and can be accessed either locally or remotely. Figure 7: Disturbance Record
7 07 COMMUNICATION & SYNCHRONIZATION The offers a wide range of communication protocols, allowing its utilisation in most of the network control and data acquisition systems (via Modbus, IEC , and DNP3.0). It has been designed for permanent multi-drop connection through the rear RS485 communication port. The incorporates an internal clock used for the time tagging of alarms, events, fault and disturbance record. The relay s internal clock is synchronise to the timing information to an accuracy of 1ms.To avoid any drifting of the time tagging clock, it s necessary to periodically synchronize the relays. To do this P72x offers two solutions: 1. Synchronization from the substation control system via the rear communication port 2. Synchronization from an external GPS clock via a dedicated digital input STABILISING RESISTOR AND VARISTOR ACCESSORY The P79x accessory contains a number of fixed resistors that provide stability during external faults. In addition to the stabilising resistors, a varistor is included for each phase. Two models are available: the P791 used in single phase applications and the P793 used in three phase applications. Stabilising resistor Three options of internal stabilising resistors are offered. In each option is possible to get 4 combinations of serial and parallel connections to give various values of resistance as required by the application. Varistor Varistors are used to limit the peak voltage developed by the current transformers under internal fault conditions to a value below the insulation level of the current transformers, relay and interconnecting wiring, which are typically able to withstand approximately 3000V peak. Two options of varistors are available. The half power option may withstand up to 10kJ of transient energy and the full power up to 20kJ. Figures 8 and 9 show P721/P791 and P723/P793 connection diagram. See P79x brochure for more information. A B C P791 Auxiliary supply WD RL1 RL2 RL3 RL Watch dog RL1 to RL4 are programmable outputs P791 L1 to 2 are programmable inputs L L2 MiCOM P721 Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus * RS485 communication port Figure 8: MiCOM P721/P791 diagram connection Simple and reliable high impedance differential scheme protection
8 08 A B C PROTECTED ZONE Three-Phase High Impedance Differential TC1 CT1 TC2 CT2 TCN CTN Auxiliary supply P793 P793 L1 to 5 are programmable inputs L L L L L5 WD RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8 MiCOM P723 (*) Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus * Watch dog RL1 to RL8 are programmable outputs RS485 communication port Figure 9: MiCOM P723/P793 diagram connection Device Track Record - High Impedance Differential Protection MiCOM P12x series relays used in high-impedance applications since 1998 MiCOM P14X series relays used in high-impedance applications since 1999 Schneider Electric 35, rue Joseph Monier CS Rueil-Malmaison Cedex, France Tel: 33 (0) RCS Nanterre Capital social As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Design: Schneider Electric Printing: 2010 Schneider Electric - All rights reserved EnergyAutomation-DS-P72x-2200-EN
MiCOM P721 & P723. High Impedance Differential Protection. P72x/EN TDS/B21. Technical Data Sheet. This document does not replace the Technical Manual
MiCOM P721 & P723 High Impedance Differential Protection P72x/EN TDS/B21 Technical Data Sheet This document does not replace the Technical Manual Note: The technical manual for this device gives instructions
More informationMiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS
MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring
More informationMiCOM P111. Three phase and earth fault overcurrent relays
Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features
More informationMiCOM P521. Fast Feeder Differential Protection
01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationMiCOM P521. Fast feeder differential protection
01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationMiCOM P122C Time-Overcurrent Protection
Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance
More informationThree phase and earth fault overcurrent relays
01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM
More informationMiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays
01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety
More informationMiCOM P12x/y. Three phase and earth fault overcurrent relays
01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM
More informationMiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation
MiCOM P123R Overcurrent Relays Upgrade Documentation MiCOM P123R Page 1/14 CONTENTS MiCOM P123R ADDENDUM: MiCOM P12X UPDATE DOCUMENTATION 3 P12X/EN IT/EB6: INTRODUCTION 4 P12x/EN TD/Eb6: TECHNICAL DATA
More informationVIP 40/45 VIP 400/410
40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered
More informationMiCOM P14x. Feeder Management Relays
01 Feeder Management Relays feeder management relays provide an integrated solution for the complete protection, control and monitoring of overhead lines and underground cables from distribution to transmission
More informationMiCOM P124 T&D. Self and Dual Powered Overcurrent Relays
PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can
More informationMiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays
PROTECTION MiCOM P12x/y Three phase and earth fault overcurrent relays The MiCOM P12x/y relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault
More informationAuxiliary Units for 7SR23 High Impedance Protection Energy Management
Reyrolle Protection Devices Auxiliary Units for High Impedance Protection Energy Management Siemens Protection Devices Limited 2 Auxiliary Units for High Impedance Protection Description 7XG15 High Impedance
More information7SR23 DAD High Impedance Protection Relay Energy Management
Reyrolle Protection Devices 7SR23 DAD High Impedance Protection Relay Energy Management 2 Siemens Protection Devices Limited 7SR23 DAD High Impedance Relay User Interface 20 character x 4 line backlit
More informationMiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile
GE Grid Solutions MiCOM Agile P746 Numerical Busbar Protection The MiCOM Agile P746 centralized numerical busbar protection provides complete protection for all voltage levels up to extra voltage busbar
More informationMaximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays
Maximize protection Sepam series 10, 20, 40, 60, 80 Modular range of digital protection relays Fast Dependable Simple Increase energy availability 100% available energy Fast response Maximum dependability
More informationMiCOM Px3x Series. Self Monitoring. Supplementary Functional Description
MiCOM Px3x Series Self Monitoring Supplementary Functional Description Issue: 02b Release: 11 / 2011 [Self-Monitoring] MiCOM Px3x Series 2 The following document is intended to clarify the Px3x self-monitoring
More informationBusbar protection REB 670
Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features
More informationCurrent Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date
Offshore Spotlight ENERGY Issue 02 Oct 2013 www.siemens.com/reyrolle Current Matters Siemens Protection Devices Ltd Protecting your electrical assets... today and tomorrow The Device issue In-depth looks
More information7SR23 DAD High Impedance Protection Relay Answers for energy.
Reyrolle Protection Devices 7SR23 DAD High Impedance Protection Relay Answers for energy. Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3. Performance
More informationMiCOM Agile P642, P643, P645
GE Grid Solutions MiCOM Agile P642, P643, P645 Advanced Transformer Protection, Control and Condition Monitoring Transformers are high capital cost assets in electrical power systems. Internal faults are
More informationMiCOM P220, P225 and P226C
PROTECTION MiCOM P220, P225 and P226C MOTOR PROTECTION RELAY MOTOR AND OVERCURRENT PROTECTION RELAY MiCOM P220 MiCOM P225 MiCOM P226C The MiCOM P22x protection relay range is designed for motor protection
More informationMiCOM P14x. Feeder Management Relays. Protection Relays
01 Feeder Management Relays feeder management relays provide an integrated solution for the complete protection, control and monitoring of overhead lines and underground cables from distribution to transmission
More informationRelion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation
Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May
More informationNPW800R RETROFITTING. Power and Volatge Protection Relay
RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)
More informationThis application note describes configuring automatic bus transfer (ABT) logic with two V57 relays.
[ ] Automatic Bus Transfer Automation Bus transfer 1 Introduction This application note describes configuring automatic bus transfer (ABT) logic with two V57 relays. In the Figure 1 is presented the single
More informationVAMP 11V. Voltage and Frequency Protection Relays. Protection
01 Voltage and Frequency Protection Relays is a basic numerical relay that provides reliable and effective voltage or voltage and frequency protection with automation, control and measurement functions.
More informationMiCOM P111 Numerical three phase and earth fault overcurrent relay description
Numerical three phase and earth fault overcurrent relay description PC15101b relays provide features for easy adaptation to different applications and operation conditions. IEC 60870-5-103 and Modbus RTU
More informationMiCOM P24x. Rotating Machine Management Relay. Protection Relays
1 Rotating Machine Management Relay Improving competitiveness and performance while adapting to a rapidly changing business environment is key to any business. MiCOM P241 in 4TE New solutions must be developed
More informationSensitive definite time or inverse time earth-fault stage for back-up residual earthfault
Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive
More informationMiCOM E2. Self Powered Converter USB / RS232 E2/EN FT/A11. User Guide. Software Version USBPx20 V1.01
MiCOM E2 Self Powered Converter USB / RS232 E2/EN FT/A11 Software Version USBPx20 V1.01 User Guide User Guide E2/EN FT/A11 MiCOM E2 Page 1/15 CONTENTS 1. PRESENTATION OF MICOM E2 USB/RS232 CABLE 3 2.
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationOvercurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin
Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection
More informationDGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field
DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description
More informationEarth-fault Relay SPAJ 110 C. Product Guide
Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral
More informationSubstation Automation Products. High impedance differential busbar protection REB650 Relion 650 series
Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,
More informationTransformer Protection and Control RET630 Numerical transformer protection in medium voltage networks
GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement
More informationMiCOM P14x AREVA T&D. Feeder Management Relays
P R OT E C T I O N MiCOM P14x Feeder Management Relays MiCOM P14x feeder management relays provide an integrated solution for the complete protection, control and monitoring of overhead lines and underground
More informationRelion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation
Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation
More informationVAMP 11F. Overcurrent Protection Relays. Protection
Protection 01 VAMP 11F Overcurrent Protection Relays VAMP 11F is a basic numerical relay that provides reliable and effective overcurrent protection with automation, control and measurement functions.
More informationMiCOM Agile P541 & 542. Grid Solutions. High-speed current differential unit protection. Key Benefits. Key Features. Current Differential Protection
GE Grid Solutions MiCOM Agile P541 & 542 High-speed current differential unit protection The P54x is designed for all overhead line and cable applications, as it interfaces readily with the longitudinal
More informationSensitive Earth-fault Relay SPAJ 111 C. Product Guide
Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent
More informationHID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin
g GE Consumer & Industrial Multilin HID High Impedance Differential Module Instruction manual GEK-113064 Copyright 2005 GE Multilin GE Multilin 215 Anderson Avenue L6E 1B3 Markham, ON -CANADA T (905) 294
More informationResidual overvoltage relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one
More information7SR242 Duobias Transformer Protection Relay Answers for energy.
Reyrolle Protection Devices 7SR242 Duobias Transformer Protection Relay Answers for energy. 2 Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3.
More informationHigh impedance protection relay
High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted
More informationCombined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide
Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with
More informationReyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy
Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,
More informationGRD110 FEATURES APPLICATION
FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted
More informationCombined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide
Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with
More informationRMS Product Presentation
RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company
More informationSubstation Automation Products. Generator protection REG670/650 Relion 670 and 650 series
Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent
More informationBus Bar Protection Applications Seminar
Bus Bar Protection Applications Seminar April 3, 2006 College Station TX ZONE 1 23 24 ZONE 2 1 2 11 12 13 22 ZONE 1 ZONE 2 23 24 1 2 3 21 22 Presentation Outline Introduction to Bus Bar Protection Bus
More informationATS Automatic transfer switches Advanced version
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 ATS CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 5. CONFORMITY 4 6. EQUIPMENTS
More informationPower Systems Communications Implementation of IEC61850 in a Substation Environment
Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details
More informationDS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication
GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation
More informationIMP/ 001 / 014 Policy for the Protection of Distribution Networks
Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy
More informationFeeder protection relay SPAA 121 C. Product Guide
Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase
More informationHigh Impedance Protection Relay SPAE010, SPAE011. Product Guide
SPAE010, SPAE011 SPAE010, SPAE011 1MRS750383-MBG Issued: April 1999 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features High impedance type differential current earth-fault
More informationMiCOM Agile P345 & P348
GE Grid Solutions MiCOM Agile P345 & P348 Generator Protection for Variable Speed, Double Fed Induction Machines Pumped storage is one of the most efficient and flexible forms of storing bulk electrical
More information1. Project Description
Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal
More informationRELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs
RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and
More informationSM100. On-Line Switchgear Condition Monitoring
On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring Introduction Weis is a specialist company with over 40 years of experience in the commissioning, testing & maintenance of
More informationPower quality enhancements for IEC 61850
Power quality enhancements for IEC 61850 April 2011 / White paper by D. Cumming, Schneider Electric (CAN) Make the most of your energy Summary Keywords... p 2 Executive summuary... p 2 Introduction...
More informationPower systems 5: Protection
Power systems 5: Protection Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. As you will recall from our Introduction to Electrical
More informationLet reliability and flexibility be your drive. Linergy. Distribution and connection systems from 0.5 A to 4000 A
Let reliability and flexibility be your drive Linergy Distribution and connection systems from 0.5 A to 4000 A All Schneider Electric distribution and connection systems have now been brought together
More informationBranch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.
Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:
More informationFlair 21D - 22D - 23D - 23DM Self-powered, adjustment-free fault passage indicators
Technical leaflet - MV network management 01 Self-powered, adjustment-free fault passage indicators EMS58355 1 Customer benefits At the cutting edge of technology, they are used on underground MV networks
More informationSIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics
SIA-B Overcurrent & Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered / Standard CTs Main characteristics The SIA-B is an protection relay with self powered and dual powered (Self-powering
More informationPerformance. Simplicity. Sepam, over 20 years of experience of the world leader. Sepam protection relays. For your peace of mind
Performance to serve your installation better Effective b Thermal based on temperature rise calculation with predictive data to optimize process control. b Directional phase overcurrent for ring networks.
More informationMiCOM P342/3/4/5 Generator Protection Relays
PROTECTION MiCOM P342/3/4/5 Generator Protection Relays The MiCOM generator protection relays provide flexible and reliable integration of protection, control, monitoring and measurement functions. MiCOM
More informationINTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box
INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families
More informationPowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet
PowerLogic power-monitoring units power meter Technical data sheet Distributed By: MetersUSA www.metersusa.com Meters@MetersUSA.com 1 224 365 5935 Basic energy meters Functions and characteristics PB105460
More informationTWO-WINDING TRANSFORMER DIFFERENTIAL
E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is
More informationRELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs
RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and
More informationGRE120. Motor Protection and Control for MV Systems
Motor Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/51P, 50/51N). Dependent and independent time characteristics (IDMTL and DTL). Restricted earth
More informationRemote communication options include IEC Ethernet communications or Modbus (RS485).
2019 The MELPRO D series relay is suitable for feeder protection, motor protection and transformer protection applications. The relay offers multiple step time grading for over-current protection co-ordination.
More informationPowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006
PowerLogic power-monitoring units Technical data sheet 2006 Functions and characteristics E90463 The PowerLogic PM500 Power Meter provides all measurement capabilities required to monitor an electrical
More informationCSC-150 Busbar Protection IED Technical Application Manual
CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual Compiled: Jin Rui Checked: Hou Changsong Standardized: Li Lianchang Inspected: Cui
More informationSynchro-check relay. Application
Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to
More informationIdentify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements
Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence
More informationRelion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation
Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,
More informationGRD130 - FEATURES APPLICATION
FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationApplication Notes on Generator Protection Schemes
Application Notes on Generator Protection Schemes Single Line Diagram Examples 1. Introduction The application notes provide selected single line diagrams for the SIPROTEC 4 generator protection device
More informationFeeder/ Motor Protection Relay VAMP 40
Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable
More informationCSC-150 Busbar Protection IED Product Guide
CSC-150 Busbar Protection IED Product Guide Version V1.0 Doc. Code: 0SF.492.056(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationNumerical motor protection in medium voltage networks Motor Protection and Control REM620
Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,
More informationPowerLogic EM4000 series
PowerLogic Multi-circuit energy meters Technical datasheet Functions and characteristics PB113714 The compact PowerLogic multi-circuit energy meter from Schneider Electric enables reliable monitoring building
More information(1) Description of Operation 7SR224 Recloser Controller
(1) Description of Operation 7SR224 Recloser Controller DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and the publication numbers under which they can be ordered,
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More information1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output
More informationReyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy
Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103
More information7SR21 Non-Directional 7SR22 Directional Overcurrent Relay
7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules
More informationSubstation Automation Products. Line differential protection RED670 Relion 670 series
Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,
More information7SR191 Capa Capacitor Protection Relay Energy Management
Reyrolle Protection Devices 7SR191 Capa Capacitor Protection Relay Energy Management 7SR191 Contents Contents Technical Manual Chapters 1. Description of Operation 2. Settings & Instruments 3. Performance
More informationProtection relays.
Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation
More information