evd4 RBX615 Application manual

Size: px
Start display at page:

Download "evd4 RBX615 Application manual"

Transcription

1 Medium voltage products evd4 RBX615 Application manual RBX615 Standard configurations 1 1. Protection functions Overcurrent protection Thermal protection Motor stall protection Loss of load protection Earth fault protection Phase discontinuity protection Unbalance protection Overvoltage protection Negative phase sequence current Undervoltage protection Residual overvoltage protection Motor startup supervision 7 2. Protection related functions Circuit-breaker failure protection K86 master trip Emergency start 8 3. Supervision functions Trip coil and current circuit supervisions 9 4. Condition monitoring functions Circuit-breaker monitor alarm Motor runtime counter Control functions Circuit-breaker control Earthing switch control Withdrawable motorized truck control Autorecloser Measurement function Digital fault recorder General logics Local/remote selector Circuit-breaker open command Circuit-breaker close command Enable close operation Enable close operation with motor Inputs and Outputs Inputs Outputs LEDs LEDs (feeder protection) LEDs (motor protection) Cumulative blocks Cumulative start Cumulative operate Cumulative alarm Variants Fixed version Motorized truck version No auto-reclose function 24

2

3 RBX615 Standard configurations RBX615 is available in five standard configurations: Feeder 1, 2, 3 and Motor 1, 2. The standard signal configuration can be changed by means of the graphical signal matrix or the optional graphical application functionality of the Protection and Control IED Manager PCM600. Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions using various logical elements, including timers and flip-flops. By combining protection functions with logic function blocks, the IED configuration can be adapted to user-specific application requirements. Description Non-directional overcurrent protection and non-directional earth fault protection Non-directional overcurrent protection and directional earth fault protection based on measurement of the phase voltages Directional overcurrent protection, directional earth fault protection based on measurement of the phase voltages and undervoltage and overvoltage protection Motor protection based on the current measurement Motor protection based on the current and voltage measurements Configuration Feeder 1 (F1) Feeder 2 (F2) Feeder 3 (F3) Motor 1 (M1) Motor 2 (M2) Functions IEC IEC IEC-ANSI Pre-configurations Protections F1 F2 F3 M1 M2 Three-phase non-directional overcurrent protection, low stage PHLPTOC1 3I> (1) 51P-1 (1) - Three-phase non-directional overcurrent protection, high stage PHHPTOC1 3I>> (1) 51P-2 (1) PHHPTOC2 3I>> (2) 51P-2 (2) Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC1 3I>>> (1) 50P/51P (1) Three-phase directional overcurrent protection, low stage DPHLPDOC1 3I> (1) 67-1 (1) DPHLPDOC2 3I> (2) 67-1 (2) Three-phase directional overcurrent protection, high stage DPHHPDOC1 3I>> Non-directional earth-fault protection, low stage EFLPTOC1 I0> (1) 51N-1 (1) EFLPTOC2 I0> (2) 51N-1 (2) Non-directional earth-fault protection, high stage EFHPTOC1 I0>> (1) 51N-2 (1) Non-directional earth-fault protection, instantaneous stage EFIPTOC1 I0>>> (1) 50N/51N (1) DEFLPDEF1 I0> (1) 67N-1 (1) - - Directional earth-fault protection, low stage DEFLPDEF2 I0> (2) 67N-1 (2) Directional earth-fault protection, high stage DEFHPDEF1 I0>> 67N NSPTOC1 I2> (1) 46 (1) Negative-sequence overcurrent protection NSPTOC2 I2> (2) 46 (2) Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD - - Residual overvoltage protection Three-phase undervoltage protection Three-phase overvoltage protection ROVPTOV1 U0> (1) 59G (1) ROVPTOV2 U0> (2) 59G (2) ROVPTOV3 U0> (3) 59G (3) PHPTUV1 3U< (1) 27 (1) PHPTUV2 3U< (2) 27 (2) PHPTUV3 3U< (3) 27 (3) PHPTOV1 3U> (1) 59 (1) PHPTOV2 3U> (2) 59 (2) PHPTOV3 3U> (3) 59 (3) Three-phase positive-sequence undervoltage protection PSPTUV1 U1< 47U Three-phase negative-sequence overvoltage protection NSPTOV1 U2> 47O Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR1 3Ith>F 49F - - MNSPTOC1 I2>M (1) 46M (1) Negative-sequence overcurrent protection for motors MNSPTOC2 I2>M (2) 46M (2) Underpower protection LOFLPTUC1 3I< Rotor block JAMPTOC1 Ist> 51LR Motor start-up STTPMSU1 Is2t n< 49,66,48,51LR Protection against phase reversal PREVPTOC I2>> 46R Three-phase thermal overload for motors MPTTR1 3Ith>M 49M Circuit-breaker fault CCBRBRF1 3I>/I0>BF 51BF/51NBF Three-phase inrush current detector INRPHAR1 3I2f> available O on request 1

4 Functions IEC IEC IEC-ANSI Pre-configurations Control F1 F2 F3 M1 M2 TRPPTRC1 Master Trip (1) 94/86 (1) Trip management TRPPTRC2 Master Trip (2) 94/86 (2) Fixed circuit-breaker control FCBXCBR1 I O CB I O CB Withdrawable circuit-breaker control WCBXCBR1 I O CB I O CB Earthing switch indication ESSXSWI1 I O ES I O ES Earthing switch control MESXSWI1 I O ES I O ES Truck control TRXSWI I O DC I O DC HBGAPC1 HBC HBC H-Bridge control HBGAPC2 HBC HBC Emergergency startup ESMGAPC1 ESTART ESTART Auto-reclosing DARREC1 O I 79 O O O - - Supervision and monitoring Circuit-breaker condition monitoring SSCBR1 CBCM CBCM Coil switch supervision (Open) OCSSCBR1 TCS (Open) TCM (Open) Coil switch supervision (Close) CCSSCBR1 TCS (Close) TCM (Close) Fuse failure supervision SEQRFUF1 FUSEF Motor runtime counter MDSOPT1 OPTS OPTM Measurement Disturbance recorder RDRE1 - - Three-phase current measurement CMMXU1 3I 3I Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0 Residual current measurement RESCMMXU1 I0 In Three-phase voltage measurement VMMXU1 3U 3U - - Residual voltage measurement RESVMMXU1 U0 Vn - - Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0 - - Three-phase power and energy measurement PEMMXU1 P, E P, E - - Sensor temperature VDSTMP VDTS VDTM - - available O on request Presentation of standard configurations The functional diagrams describe the IED's functionality from the protection, measuring, condition monitoring, disturbance recording, control and interlocking perspectives. The diagrams show the default functionality with simple symbol logics forming principle diagrams. Protection function blocks are part of the functional diagrams; they are identified on the basis of their IEC name. Some function blocks, such as PHHPTOC, are used several times in the configuration. To separate the blocks from each other, the IEC name, IEC symbol and ANSI function number are appended with a running number, that is, an instance number, from one upwards. With the Signal Matrix and Application Configuration in PCM600, it is possible to modify the standard configuration according to the actual needs. The IED is delivered from the factory with default connections described in the functional diagrams for binary inputs, binary outputs, function-to-function connections and alarm LEDs. The Signal Matrix is used for GOOSE signal input engineering and for making cross-references between the physical I/O signals and the function blocks. The Signal Matrix tool cannot be used for adding or removing function blocks, for example, GOOSE receive function blocks. 2

5 1. Protection functions 1.1. Overcurrent protection The overcurrent protection function has a sub-function for every protection: PHIPTOC for instantaneous stage, PHHPTOC for high stage and PHLPTOC for low stage overcurrent. Moreover, there is the transformer inrush detection INRPHAR. If the overcurrent threshold value is reached, an output signal of start (ST_XX_X) is given out, if the imposed time DT is also reached then an operate command (ST_XX_X) is created. In the first case a recorder registers the analogic measured values of the parameter; in the second case a protection trip switches on. These outputs actually go into trip or recorder functions that will be shown later on. All the start and operate outputs are then collected in a common operate command (COMM_OP_CMD) and in the start one (COMM_ST_CMD) 1.2. Thermal protection The increased utilization of power systems closer to the thermal limits has generated a need for a thermal overload function also for power lines. A thermal overload is in some cases not detected by other protection functions, and the introduction of the thermal overload function T1PTTR allows the protected circuit to operate closer to the thermal limits. An alarm level gives an early warning to allow operators to take action before the line trips. The early warning is based on the three-phase current measuring function using a thermal model with first order thermal loss with the settable time constant. If the temperature rise continues the function will operate based on the thermal model of the line. The outputs of this function are operate and start signals. 3

6 1.3. Motor stall protection The stalled motor protection JAMPTOC is used for protecting the motor in stall or mechanical jam situations during the running state. When the motor is started, a separate function is used for the startup protection (STTPMSU) and JAMPTOC is normally blocked during the startup period. When the motor has passed the starting phase, JAMPTOC monitors the magnitude of phase currents. The function starts when the measured current exceeds the breakdown torque level, that is, above the set limit Loss of load protection The loss of load protection LOFLPTUC is used to detect a sudden load loss which is considered as a fault condition. LOFLPTUC starts when the current is less than the set limit. It operates with the definite time (DT) characteristics, which means that the function operates after a predefined operate time and resets when the fault current disappears Earth fault protection The earth fault protection is divided in three sub-functions, each one for a specific protection code: DEFHPDEF for directional earth-fault protection high stage, DEFLPDEF for directional earth-fault protection low stage and EFHPTOC for non-directional earth-fault protection high stage. As usual there are the operate and start commands which are later collected in the common ones. 4

7 1.6. Phase discontinuity protection The phase discontinuity protection PDNSPTOC is used for detecting unbalance situations caused by broken conductors. The function starts and operates when the unbalance current I2/I1 exceeds the set limit. I1 and I2 represent positive and negative phase sequence currents. As before, it gives out start and operate commands Unbalance protection The unbalance protection, based on negative-phase-sequence current function MNSPTOC, protects electric motors from phase unbalance. A small voltage unbalance can produce a large negative-sequence current flow in the motor. For example, a 5 percent voltage unbalance produces a stator negative-sequence current of 30 percent of the full load current, which can severely heat the motor. MNSPTOC detects the large negative-sequence current and disconnects the motor Overvoltage protection The three-phase overvoltage protection PHPTOV is applied on power system elements, such as generators, transformers, motors and power lines, to protect the system from excessive voltages that could damage the insulation and cause insulation breakdown. The three-phase overvoltage function includes a settable value for the detection of overvoltage either in a single phase, two phases or three phases. PHPTOV includes both definite time (DT) and inverse definite minimum time (IDMT) characteristics for the delay of the trip. As with the other protection blocks, it has 2 outputs signals of operate and start. 5

8 1.9. Negative phase sequence current The negative phase-sequence current protection NSPTOC is used for increasing sensitivity to detect single phase and phaseto-phase faults, unbalanced loads due to, for example, broken conductors or to unsymmetrical feeder voltages. Similarly to the other protection functions, there are start and operate commands which are collected later in common ones Undervoltage protection The three-phase undervoltage protection PHPTUV is used to disconnect from the network devices, for example electric motors, which are damaged when subjected to service under low voltage conditions. PHPTUV includes a settable value for the detection of undervoltage either in a single phase, two phases or three phases Residual overvoltage protection The residual overvoltage protection ROVPTOV is used in distribution networks where the residual overvoltage can reach nonacceptable levels, for example, in high impedance earthing. The function starts when the residual voltage exceeds the set limit. As usual, the outputs are start and operate commands. 6

9 1.12. Motor startup supervision The motor startup supervision function STTPMSU is designed for protection against excessive starting time and locked rotor conditions of the motor during starting. For good and reliable operation of motor, the thermal stress during the motor starting is maintained within the allowed limits. The starting of motor is supervised by monitoring the TRMS magnitude of all the phase currents or by monitoring the status of the circuit-breaker connected to the motor. STTPMSU also protects the motor from an excessive number of startups. Upon exceeding the specified number of startups within a certain duration, STTPMSU blocks further starts. The restart of the motor is also inhibited after each start and continues to be inhibited for a set duration. When the motor start lock is enabled, STTPMSU gives the time remaining until the restart of the motor. In the case of an emergency start, the logic does not block the motor startup. The outputs of this block deal with the operate/trip signals due to thermal stress and stalling protection (OPR_IIT and OPR_STALL), the signal of motor startup in progress (MOT_START) and the lockout condition (LOCK_START). 7

10 2. Protection related functions 2.1. Circuit-breaker failure protection The CCBRBRF function is the protection which acts in case of failure of the CB in opening the circuit. It is possible to see from the logic blocks that if there are, at the same time, the trip opening command, coming from a protection trip, and the closed status of the CB, it means that the CB is not opening the circuit. In this case the CCBRBRF function gives out the CB failure alarm (CB_FAULT_ALM) and the two inside timers run until the set re-trip time value has elapsed (TRRET) and until the set CB failure delay value has elapsed (TRBU). In the first case a re-trip command (CBFP_RETRIP) is sent to the CB itself, in the second case a backup command (CBFP_BUTRUP) is sent to the chosen backup breakers, normally upstream ones K86 master trip The K86 master trip function is the one responsible for putting the CB in locked-out status. In fact, if the PROTECT_TRIP command is incoming and at the same time the auto-reclose function is not acting (it is off or unsuccessful) it means that the CB should trip. Otherwise, if a protection trips, the CB should not lock out because the auto-reclose function has to be able to re-close the circuit. Also, the inputs of external trip (#2) and of emergency open (#8) can open the CB giving the ALL_ PROTECT_TRIP command. This command gives the operate command to the TRPPTRC function which means tripping the CB putting it in the lock-out status. The aim of this function is to lock out the tripped CB until a general reset command (input #7) deletes this status, recorded in CL_LKOUT. Therefore, in case of incoming ALL_PROTECT_TRIP command, the TRPPTRC function puts the CB in K86_TRIPPED status, that means in a lock-out one. In case of K86-tripped CB, it is possible to unlock the functionality of the CB via the HMI. Press the Clear button, select TRPPTRC and cancel it; then move into the LEDs page and deactivate them Emergency start An emergency condition can arise in cases where the motor needs to be started despite knowing that this can increase the temperature above limits or cause a thermal overload that can damage the motor. The emergency start function ESMGAPC allows motor startups during such emergency conditions. ESMGAPC is only to force the IED to allow the restarting of the motor. After the emergency start input is activated, the motor can be started normally. ESMGAPC itself does not actually restart the motor. 8

11 3. Supervision functions 3.1. Trip coil and current circuit supervisions The open coil switch supervision function OCSSCBR is designed to supervise control circuits. A dedicated circuit verifies the continuity of the coil to detect any invalidity in the control circuit. A coil switch failure is reported to the corresponding function block in the IED configuration and gives out in case the related alarm. On the other hand the current circuit supervision function CCRDIF, is used for monitoring residual current transformer secondary circuits. CCRDIF internally calculates the sum of phase currents (I_A, I_B and I_C) and compares the sum against the measured single reference current (I_REF). If the CCRDIF detects a fault in the measurement circuit, it issues an alarm. 9

12 4. Condition monitoring functions 4.1. Circuit-breaker monitor alarm The circuit-breaker condition monitoring function (SSCBR) is used to monitor different parameters of the circuit-breaker. The breaker requires maintenance when the number of operations has reached a predefined value. For proper functioning of the circuit-breaker, it is essential to monitor the circuit-breaker operation, spring charge indication, breaker wear, travel time, number of operation cycles and accumulated energy. The energy is calculated from the measured input currents as the sum of current phases values. Alarms are generated when the calculated values exceed the threshold settings. Specifically, the inputs of this function are the information on the CB status coming from the CB function, such as the position of the CB (open or closed) and the condition of the spring (charged, discharged). The SSCBR function monitors a large variety of parameters and gives out an alarm for every warning condition. For example, alarms related to excessive travel time of CB opening or closing (TRV_T_OP_ALM, TRV_T_CL_ALM), failure in spring recharging (SPR_CHR_ALM), threshold value of operations done by the CB (CB_OPR_ALM), residual life based on tripping current value (CB_LIFE_ALM), long CB non-operating time (MON_ALM). All these outputs are therefore the alarms related to the good operability of the CB and the need for some maintenance Motor runtime counter The motor runtime counter function MDSOPT calculates the accumulated operation time of the motor. The unit of time for accumulation is hour. The function generates a warning and an alarm when the accumulated operation time exceeds the set limits. 10

13 5. Control functions 5.1. Circuit-breaker control The circuit-breaker control function WCBXCBR is intended for withdrawable circuit-breaker control and status information purposes. This function executes commands and evaluates block conditions and different time supervision conditions. The function performs an execution command only if all the conditions indicate that a switch operation is allowed. The actuation of the command consists of operating the open and closed shunt releases. WCBXCBR is also assigned to monitor the truck status. Actually, if all the conditions to operate the truck are satisfied (CB and earthing switch open, truck moving input command enabled), the truck itself is allowed to move. Otherwise the CB function will block the RL2 not permitting the insertion of the truck. Other commands are the possibility to open ENA_OPEN (always on) or to close, depending on the admission of the CLOSE_ENABLE command; these two operations can also be blocked. The previously analyzed open command, on the other hand, gives the signal of the CB opening, whereas the close command will be explained later on. All these signals, however, act on the authorization of opening or closing the CB along with the right of blocking or unlocking the RL1 and RL2 coils. Regarding the outputs of this WCBXCBR function, there are mainly the ones related to the CB position (CB_OPEN and CB_CLOSE), which is detected by inductive position sensors and checked by the OKPOS (see the table), the charged spring indicator, the truck position (test or service, see the picture) checked by the TRUCK_OK and the status of the coils acting on RL1 and RL2 (released/not released). Status (POSITION) OPENPOS CLOSEPOS OKPOS 1=Open 1=True 0=False 1=True 2=Closed 0=False 1=True 1=True 3=Faulty/Bad (11) 1=True 1=True 0=False 0=Intermediate (00) 0=False 0=False 0=False ANSI truck symbols for the intermediate, service, test and faulty position 11

14 5.2. Earthing switch control The earthing switch indication function ESSXSWI indicates the open, closed and undefined states of the earthing switch. Before this function acts, there is a check for intermediate position of the earthing switch. Basically, it verifies that the command given is either open position or closed position to avoid intermediate status. In fact, the ESSXSWI function receives the signals and checks that there are not intermediate or faulty situations by comparing the values. As can be seen in the table, if the signals are coherent, the OKPOS check will give the output of open (ES_OPEN) or closed (ES_CLOSE), otherwise it will indicate the presence of an intermediate status or a faulty/bad execution. Status (POSITION) OPENPOS CLOSEPOS OKPOS 1=Open 1=True 0=False 1=True 2=Closed 0=False 1=True 1=True 3=Faulty/Bad (11) 1=True 1=True 0=False 0=Intermediate (00) 0=False 0=False 0=False These statuses are displayed on the HMI by means of standard single line diagram symbols, as shown below. Earth Switch symbols for the intermediate, open, closed and faulty position 12

15 5.3. Withdrawable motorized truck control The truck control function TRXSWI is intended for truck control purposes. TRXSWI executes commands and evaluates block conditions and different time supervision conditions. The function performs an execution command only if all conditions indicate that a switch operation is allowed. The actuation of the command consists in controlling the H-Bridge driving the truck motor. The condition to operate the motor is the status of the truck: it should be enabled. So CB and ES should be open and the respective input #4 enabled. Once these conditions are satisfied, the TRXSWI function enables the H-Bridge and gives the moving direction. These commands are read by the HBGAPC function: this is a switching circuit used to apply a controlled voltage to a DC motor. The voltage applied across the motor can be either positive, that is, forward operation, or negative, that is, reverse operation. In case of an overcurrent or over-temperature signal, the function launches a fault alarm signal Autorecloser About 80 to 85 percent of faults in MV overhead lines are transient and automatically cleared with a momentary de-energization of the line. The rest of the faults, 15 to 20 percent, can be cleared by longer interruptions. The de-energization of the fault location for a selected time period is implemented through automatic reclosing, during which most of the faults can be cleared. In case of a permanent fault, the automatic reclosing is followed by final tripping. A permanent fault must be located and cleared before the fault location can be re-energized. The function provides five programmable auto-reclose shots which can perform one to five successive auto-reclosings of desired type and duration, for instance one high-speed and one delayed auto-reclosing. This DARREC function receives as inputs the operate command from the different protection functions and some information related to the CB status, such as spring and open/closed statuses. The different operate commands are separated because in this way it is possible to set different delay times for the AR function. The output of this function is related to the AR operations themselves, such as the open command (OPEN_AR), the reclose one (RECLOSE_AR), the in progress status (AR_IN_PROG) and the status (AR_ON, AR_READY). Moreover, it also indicates the possible faults in the AR procedure, such as the locked status and the unsuccessful action. 13

16 6. Measurement function 6.1. Digital fault recorder The RDRE function is the one responsible for recording the signals coming from the transducers once the set threshold is elapsed: that is why it has as inputs the start commands of the various protections, along with the operate ones. Moreover, it also considers the status of the auto-reclose function and its possible commands. 14

17 7. General logics 7.1. Local/remote selector The local/remote selector function defines the type of control chosen, that is, whether we act from remote (e.g. digital inputs) or from local (HMI). The respective outputs specify this choice. To change this status from remote to local (and vice versa) use the R/L button on the HMI Circuit-breaker open command The function that supervises the circuit-breaker open command is made up of two different blocks which may give that signal: the remote command and the trip due to the protections. In the first case, there should firstly be the remote opening input signal, then the truck in the service position and the remote status selected. In the case of protection trip, on the other hand, just one signal due to a protection system is enough to give the open command, such as the K86 master trip, the open phase of the auto-reclose function, or the PROTECTION_TRIP command (linked to various protections). If one of the two cases is on, there is the output of OPEN_COMMAND signal; in the specific case of open command due to a protection trip, there is also the TRIP_OPEN_CMD signal. 15

18 7.3. Circuit-breaker close command The close CB command is similar to the open one but it is not related to protection function. In fact, the close command can just be given by a remote input (along with the truck in the service position and the remote selection) or by the reclose phase of the auto-reclose function. If one of the two cases is on, there will be a CLOSE_COMMAND output signal Enable close operation This function enables the CB closing output signal (CLOSE_CMD&ENABLED), which goes into the WCBXCBR function launching the closing command (AU_CLOSE) and unlocking the RL1 (AU_UNLRL1). This function starts with the common rights necessary to open the CB, which are the status of CB open, the charged spring and the absence of an opening command. There are also two possible truck conditions: the service and the test ones. In the first case, different rights are needed to operate the closing command: first of all, of course, the truck in the service position, then the earthing switch open, the input that enables the closure of the CB on, the good status of the opening coil and the absence of the K86 master trip and of the auto-reclosing procedure. In the case of the truck in the test position, on the other hand, just the position itself and the local selection are needed. Be aware that in test position the CB can only be operated from local. Once one of these two conditions is fulfilled, the function gives out a CLOSE_ENABLE output that, along with the previously seen CLOSE_COMMAND coming from a remote input, gives the CLOSE_CMD&ENABLED. 16

19 7.5. Enable close operation with motor In case of motorized truck, other rights dealing with the motor condition are necessary to give the close command. Mainly, the motor should not be locked out and there should not be a thermal lock protection on. 17

20 8. Inputs and outputs 8.1. Inputs There are twelve digital inputs available in the plug. Each of them gives the related command used by the functions. I/O Description BI Number Without I/O expansion module With I/O expansion module evd4 - Binary Inputs Card Function Configurable Bl 1 I/O expansion (-X200) Ext. Protections Alarm yes yes Bl 2 I/O expansion (-X200) Ext. Protections Trip yes yes Bl 3 I/O expansion (-X200) MCB closed yes yes Bl 4 I/O expansion (-X200) Enable truk moving yes yes Bl 5 I/O expansion (-X200) Enable to close in insert pos. yes yes Bl 6 I/O expansion (-X200) Blocking OC inst. stage yes yes Bl 7 I/O expansion (-X200) General Reset yes yes Bl 8 I/O expansion (-X200) Emergency opening yes yes Bl 9 I/O expansion (-X200) Earthing switch close yes yes Bl 10 I/O expansion (-X200) Earthing switch open yes yes Bl 11 Basic Card (-X300) CB remote closing no yes Bl 12 Basic Card (-X300) CB remote opening no yes Bl 13 Basic Card (-X300) CB closed signalling no no Bl 14 Basic Card (-X300) CB open signalling no no Bl 15 Basic Card (-X300) Springs charged signalling no no Bl 16 Power Supply (-X100) Truck in test position no no Bl 17 Power Supply (-X100) Truck in service position no no Available in plug 18

21 8.2. Outputs In case of absence of the auto-reclose function, the respective output is available. BO Number Without I/O expansion module With I/O expansion module evd4 - Binary Outputs Card Function Configurable BO 1 I/O expansion (-X200) General operate indication yes yes BO 2 I/O expansion (-X200) General start indication yes yes BO 3 I/O expansion (-X200) Cumulative Alarm yes yes BO 4 I/O expansion (-X200) Unsuccess AR yes yes BO 5 Power Supply (-X100) K86 tripped yes yes BO 6 Power Supply (-X100) CBFP open upstream yes yes BO 7 Power Supply (-X100) Locking electromagnet on operating mechanism (-RLE1) BO 8 Power Supply (-X100) Shunt closing release (-MBC) no no BO 9 Power Supply (-X100) Shunt opening release (-MBO1) no no BO 10 Power Supply (-X100) Watchdog no yes BO 11 Power Supply (-X100) CB ready no yes BO 12 Basic Card (-X300) Locking electromagnet on truck (-RLE2) no no Available in plug no no 19

22 9. LEDs 9.1. LEDs (feeder protection) 20

23 21

24 9.2. LEDs (motor protection) LED Pages 1 and 3 are the same as the ones of Feeder protection. LED Page 2 is however different, as can be seen below. 22

25 10. Cumulative blocks Cumulative start This function collects all the start commands coming from the different protection functions and gives out the PROT_START command if any of them is launched by the respective protection Cumulative operate This function gives a PROTECT_TRIP output which is driven by any of the operate commands of the various protection functions. This command goes into the K86 master trip function causing the CB protection trip Cumulative alarm The cumulative alarm function has as inputs all the possible alarm signals coming from the various diagnostic functions, and if one of them is on, it gives out the CUMULATIVE_ALARM signal. 23

26 11. Variants The blocks shown in this manual are as comprehensive as possible, however you may find some small differences with your configuration. But, the only variants you should be aware of regard the availability of some outputs or LEDs Fixed version If you have an evd4 - fixed version: LEDs: there is no LED related to -RLE2. This LED is then available. Input: #4 is available as there is no truck Motorized truck version If you have an evd4 with motorized truck: Input: #4 is available as the motor is responsible for moving the truck No auto-reclose function If you do not have the auto-reclose function configured: Output: 1 is available as there no need for auto-reclose operation status. LEDs: 2 are available for the same reason given in the previous point. 24

27 25

28 For more information please contact: ABB S.p.A. Power Products Division Unità Operativa Sace-MV Via Friuli, 4 I Dalmine Tel.: Fax: info.mv@it.abb.com ABB Oy Distribution Automation P.O. Box 699 FI VAASA, Finland Phone: Fax: VCD Rev. -, en Appl. Manual (evd4-rbx615) (gs) ABB AG Calor Emag Medium Voltage Products Oberhausener Strasse 33 Petzower Strasse 8 D Ratingen D Glindow Phone: +49(0)2102/ , Fax: +49(0)2102/ calor.info@de.abb.com The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product. Copyright 2011 ABB. All rights reserved.

Relion 615 series. Feeder Protection and Control REF615 DNP3 Point List Manual

Relion 615 series. Feeder Protection and Control REF615 DNP3 Point List Manual Relion 615 series Feeder Protection and Control REF615 DNP3 Document ID: 1MRS756711 Issued: 03.07.2009 Revision: B Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

Equipped with Relion technology. evd4 Breaker Integrated Protection RBX615 Operation Manual

Equipped with Relion technology. evd4 Breaker Integrated Protection RBX615 Operation Manual Equipped with Relion technology evd4 Breaker Integrated Protection RBX615 Document ID: 1MRS757100 Issued: 2011-12-13 Revision: B Product version: 2.0 Copyright 2011 ABB. All rights reserved Copyright

More information

Relion 615 series. Motor Protection and Control REM615 Modbus Point List Manual

Relion 615 series. Motor Protection and Control REM615 Modbus Point List Manual Relion 615 series Motor Protection and Control REM615 Modbus Document ID: 1MRS756877 Issued: 03.07.2009 Revision: A Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

Relion 615 series. Feeder protection and control REF615

Relion 615 series. Feeder protection and control REF615 Relion 65 series Feeder protection and control REF65 Compact and versatile solution for utility and industrial power distribution systems REF65 is a dedicated feeder IED perfectly aligned for the protection,

More information

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual

Relion 615 series. Feeder Protection and Control REF615 Modbus Point List Manual Relion 615 series Feeder Protection and Control REF615 Modbus Document ID: 1MRS756581 Issued: 03.07.2009 Revision: C Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

RED615 ANSI Line differential protection and control

RED615 ANSI Line differential protection and control DESCRIPTIVE BULLETIN RED615 ANSI Line differential protection and control RED615 is a phase-segregated, twoend line differential protection and control relay for protection, control, measurement and supervision

More information

Relion 615 Series. Motor Protection and Control REM615 ANSI DNP3 Point List Manual

Relion 615 Series. Motor Protection and Control REM615 ANSI DNP3 Point List Manual Relion 615 Series Motor Protection and Control REM615 ANSI 3 List Manual Document ID: 1MAC254287-MB Issued: 4/14/2011 Revision: B Product version: 4.0 Copyright 2011 ABB. All rights reserved. Copyright

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

Relion product family. Remote monitoring and control REC615 Protection of cable feeders with superior fault detection and location

Relion product family. Remote monitoring and control REC615 Protection of cable feeders with superior fault detection and location elion product family emote monitoring and control EC615 Protection of cable feeders with superior fault detection and location U12 0. 0 kv P 0.00 kw Q 0.00 kvar I2 0 A ESC A 1 15 AN DC IN CONSOE/S1 S2

More information

Relion 620 series. Transformer protection and control RET620 Flexibility for utility and industrial power distribution systems

Relion 620 series. Transformer protection and control RET620 Flexibility for utility and industrial power distribution systems Relion 620 series Transformer protection and control RET620 Flexibility for utility and industrial power distribution systems Compact protection and control with voltage regulation for two-winding power

More information

Feeder Protection REF615. Product Guide

Feeder Protection REF615. Product Guide Product Guide Contents 1 Description.............................. 3 2 Standard configurations................. 3-4 3 Protection functions.................... 4-5 4 Application...........................

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...7 4. Application...9 5. Supported ABB solutions...12 6.

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Operation Manual Feeder Protection Relay REF615

Operation Manual Feeder Protection Relay REF615 Feeder Protection Relay REF615 Document ID: 1MRS756376 Issued: 02.07.2008 Revision: C Product version: 1.1 Copyright 2008 - ABB. All rights reserved Copyright This document and parts thereof must not

More information

Relion 615 series. Transformer Protection and Control RET615 Application Manual

Relion 615 series. Transformer Protection and Control RET615 Application Manual Relion 615 series Transformer Protection and Control RET615 Document ID: 1YHT530003D05 Issued: 2014-05-14 Revision: C Product version: 4.1 Copyright 2014 ABB. All rights reserved Copyright This document

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Feeder Protection REF615 ANSI. Product Guide

Feeder Protection REF615 ANSI. Product Guide Product Guide Contents 1 Description............................. 3 2 Standard configurations................ 3-4 3 Protection functions................... 4-5 4 Application.......................... 6-7

More information

Relion 615 series. Transformer Protection and Control RET615 ANSI Modbus Point List Manual

Relion 615 series. Transformer Protection and Control RET615 ANSI Modbus Point List Manual Relion 615 series Transformer Protection and Control RET615 ANSI Modbus Document ID: 1MAC207644-MB Issued: 01/20/2010 Revision: A Product version: 2.0 Copyright 2010 ABB. All rights reserved Copyright

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

Relion 620 series. Motor Protection and Control REM620 Product Guide

Relion 620 series. Motor Protection and Control REM620 Product Guide Relion 620 series Motor Protection and Control Product Guide Contents 1. Description... 3 2. Default configuration...3 3. Protection functions...9 4. Application... 9 5. Supported ABB solutions... 14 6.

More information

RELION PRODUCT FAMILY Grid Automation Remote Monitoring and Control REC615 Product Guide

RELION PRODUCT FAMILY Grid Automation Remote Monitoring and Control REC615 Product Guide RELION PRODUCT FAMILY Grid Automation Remote Monitoring and Control REC615 Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...13 4. Application... 14 5.

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

Grid Automation packaged solutions Optimal automation of medium voltage grids

Grid Automation packaged solutions Optimal automation of medium voltage grids Grid Automation packaged solutions Optimal automation of medium voltage grids Application principles of the Zone concept Grid Automation (GA) packaged solutions The zone concept offers a method to analyze

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Generator and interconnection protection REG615 Compact and versatile solution for utility and industrial power distribution systems

Generator and interconnection protection REG615 Compact and versatile solution for utility and industrial power distribution systems Relion 65 series Generator and interconnection protection REG65 Compact and versatile solution for utility and industrial power distribution systems Compact generator and extensive interconnection protection

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

RELION PRODUCT FAMILY Grid Automation Recloser Protection and Control RER615 Product Guide

RELION PRODUCT FAMILY Grid Automation Recloser Protection and Control RER615 Product Guide RELION PRODUCT FAMILY Recloser Protection and Control RER615 Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...10 4. Application... 10 5. Supported ABB

More information

Relion 615 series. Transformer Protection and Control RET615 Product Guide

Relion 615 series. Transformer Protection and Control RET615 Product Guide Relion 615 series Transformer Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...14 4. Application... 15 5. Supported ABB solutions...

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

User Manual. AQ-F215 Simulator

User Manual. AQ-F215 Simulator User Manual AQ-F215 Simulator Instruction manual AQ-F215 Simulator 2 (28) Revision 1.00 Date 16.5.2014 Changes N/A Revision 1.01 Date 13.3.2018 Changes Updated visual look Readability improvements Instruction

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Relion 615 series. Line Differential Protection and Control RED615 Product Guide

Relion 615 series. Line Differential Protection and Control RED615 Product Guide Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...12 4. Application... 12 5. Supported ABB

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ-200 series protection, control, measurement and monitoring IEDs Contents AQ-200 series protection and control IEDs 3 AQ-200 benefits 3 Arcteq innovation: ultra-accurate measurement technology

More information

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Relion 620 series. Feeder protection and control REF620 Flexibility for utility and industrial power distribution systems

Relion 620 series. Feeder protection and control REF620 Flexibility for utility and industrial power distribution systems Relion 60 series Feeder protection and control REF60 Flexibility for utility and industrial power distribution systems Compact protection and control for a wide variety of feeder applications REF60 is

More information

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

RELION PROTECTION AND CONTROL 615 series ANSI Engineering Manual

RELION PROTECTION AND CONTROL 615 series ANSI Engineering Manual RELION PROTECTION AND CONTROL 615 series ANSI Document ID: 1MAC108982-MB Issued: 2018-02-26 Revision: E Product version: 5.0 FP1 Copyright 2018 ABB. All rights reserved Copyright This document and parts

More information

Feeder Protection Relay REF 610. Product Guide

Feeder Protection Relay REF 610. Product Guide Product Guide Contents 1 Description.............................. 3 2 Protection functions....................... 3 3 Measurement............................ 4 4 Disturbance recorder......................

More information

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4 Content FPC 400 USER MANUAL Apr 2017 Feeder F3 Motor M4 Busbar B3 Transformer T4 1 USER MANUAL FPC 400-4/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia 2016. All rights reserved.

More information

Connectivity Packages. User's Guide - ANSI Version

Connectivity Packages. User's Guide - ANSI Version Connectivity Packages 1MRS756194 Issued: 30.11.2006 Version: A/30.11.2006 Connectivity Packages Contents Copyrights... 5 1. Introduction...... 7 1.1. Intended audience...... 7 1.2. Related documents.........

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

MiCOM P220, P225 and P226C

MiCOM P220, P225 and P226C PROTECTION MiCOM P220, P225 and P226C MOTOR PROTECTION RELAY MOTOR AND OVERCURRENT PROTECTION RELAY MiCOM P220 MiCOM P225 MiCOM P226C The MiCOM P22x protection relay range is designed for motor protection

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

Relion 615 series. Generator and Interconnection Protection REG615 Product Guide

Relion 615 series. Generator and Interconnection Protection REG615 Product Guide Relion 615 series Generator and Interconnection Protection Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...9 4. Application... 9 5. Supported ABB solutions...

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual Overcurrent and Earth-Fault Relay MRS75094-MUM Issued: 4.09.998 Version: D/4..2005 Overcurrent and Earth-Fault Relay Contents. About this manual...5.. Copyrights...5.2. Trademarks...5.3. Guarantee...5.4.

More information

PRODUCT GUIDE. REM615 ANSI 5.0 FP1 Motor protection and control

PRODUCT GUIDE. REM615 ANSI 5.0 FP1 Motor protection and control PRODUCT GUIDE REM615 ANSI 5.0 FP1 Motor protection and control 2 REM615 ANSI 5.0 FP1 MOTOR PROTECTION AND CONTROL Table of contents 03 1. Description 03-09 2. Standard configuration 10-12 3. Protection

More information

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Relion 630 series Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Integrated load-shedding and protection solution The PML630 is a freely-configurable

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Relion 615 series. Motor Protection and Control REM615 DNP3 Point List Manual

Relion 615 series. Motor Protection and Control REM615 DNP3 Point List Manual Relion 615 series Motor Protection and Control REM615 DNP3 Document ID: 1MRS756880 Issued: 2013-02-21 Revision: D Product version: 4.0 FP1 Copyright 2013 ABB. All rights reserved Copyright This document

More information

AQ-200 SERIES PROTECTION,CONTROL, MEASUREMENT AND MONITORING IEDS

AQ-200 SERIES PROTECTION,CONTROL, MEASUREMENT AND MONITORING IEDS AQ-200 SERIES PROTECTION,CONTROL, MEASUREMENT AND MONITORING IEDS CONTENTS AQ-200 series protection, control, measurement and monitoring IEDs... 3 AQ-200 benefits... 3 Arcteq Innovation: Ultra-accurate

More information

Relion product family. Grid Automation Remote Monitoring and Control REC615 IEC /104 Point List Manual

Relion product family. Grid Automation Remote Monitoring and Control REC615 IEC /104 Point List Manual Relion product family Grid Automation Remote Monitoring and Control REC615 IEC 60870-5-101/104 Document ID: 1MRS757808 Issued: 2015-03-06 Revision: C Product version: 1.1 Copyright 2015 ABB. All rights

More information

GRE120. Motor Protection and Control for MV Systems

GRE120. Motor Protection and Control for MV Systems Motor Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/51P, 50/51N). Dependent and independent time characteristics (IDMTL and DTL). Restricted earth

More information

ABB ABILITY SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS JANUARY 2019 PRODUCT GUIDE SSC600

ABB ABILITY SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS JANUARY 2019 PRODUCT GUIDE SSC600 ABB ABILITY SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS JANUARY 2019 PRODUCT GUIDE Smart Substation Control and Protection Contents 1. Description... 3 2. Protection functions... 3 3.

More information

Relion 620 series. Feeder Protection and Control REF620 Product Guide

Relion 620 series. Feeder Protection and Control REF620 Product Guide Relion 620 series Feeder Protection and Control Product Guide Contents 1. Description... 3 2. Default configurations...3 3. Protection functions...9 4. Application... 10 5. Supported ABB solutions... 19

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

Perfect protection smallest space

Perfect protection smallest space www.siemens.com/energy/protection Perfect protection smallest space The SIPROTEC Compact device range redefines protection technology Answers for energy. SIPROTEC Compact is the ideal solution for almost

More information

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for energy 7SR11 and 7SR12 Argus Overcurrent Relays 74T/CCS Trip & Close Circuit Supervision 60VTS VT Supervision Control 79

More information

Electrical Integration with Smart Communication

Electrical Integration with Smart Communication Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide Directional or Non-Directional Earth-Fault Product Guide Issued: 17.06.19994 Status: Updated Version: C/16.10.2002 Data subject to change without notice Features Directional or non-directional low-set

More information

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays PROTECTION MiCOM P12x/y Three phase and earth fault overcurrent relays The MiCOM P12x/y relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault

More information

WiAutoLink Frequently Asked Questions

WiAutoLink Frequently Asked Questions Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual

Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual Relion 611 series Feeder Protection and Control REF611 Modbus Document ID: 1MRS757463 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Copyright This document

More information

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Reyrolle Protection Devices 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Siemens Protection Devices Limited 2 7SR10 Argus Contents Contents Technical Manual Chapters 1. Description of Operation

More information

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy Reyrolle Protection Devices 7SR10 & 7SR0 Argus Overcurrent Protection Relay Answers for energy 7SR10 7SR0 Argus Overcurrent Protection Relay Additional Functionality 7SR0n Directional Relay 7/59 Under/Over

More information

Relion Protection and Control. 630 series Engineering Manual

Relion Protection and Control. 630 series Engineering Manual Relion Protection and Control 630 series Document ID: 1MRS756800 Issued: 2014-11-28 Revision: E Product version: 1.3 Copyright 2014 ABB. All rights reserved Copyright This document and parts thereof must

More information

Three phase and earth fault overcurrent relays

Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

Numerical Protective and Management Relays

Numerical Protective and Management Relays Numerical Protective and Management Relays Presented at: The Institution of Engineers (India) Andaman and Nicobar State Centre Port Blair Dr. H. K. Verma Deputy Director and Professor of Electrical Engineering

More information

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage

More information

4. CIRCUIT BREAKERS. Functional Emergency Switching

4. CIRCUIT BREAKERS. Functional Emergency Switching 4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit

More information