1 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli Electrical Networks Asset Manager PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

2 Approval Amendment Record Approval Date Version Description 18/03/ Initial issue under MTM. Supercedes MainCo document MESP PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 15

3 Table of Contents 1. Purpose Scope Abbreviations Definitions References & Legislation Standards Latest Issues and Amendments Background Housing Control Supply SCADA Voltage Control Interfaces General Rectifier ACCB Interface Rectifier DCCB Interface Rectifier DC Isolator Interface (where there is no Rectifier DCCB) Local Control Panel SCADA Interface Protection Functions General AC Overcurrent and Earth Fault System Rectifier Assembly DC Frame Earth Leakage AC Undervoltage, Phase Failure, Phase Loss and Phase Reversal Lockout Functions Monitoring Functions Cubicle Requirements Labelling Terminal Strips and Wiring Testing Factory Tests Test Certificates Documentation and Support Documentation Requirements PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 15

4 15.2 Design Drawings Drawing Format Installation Manual Appendix A Design Management Requirements Appendix B Technical Data Schedule Form PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 15

5 1. Purpose This document is the technical specification for a Control & Protection System for an MTM Rectifier Unit. 2. Scope This specification shall be applied in full for all new Rectifier Unit Control & Protection Systems to be installed in MTM Substations. 3. Abbreviations ACCB - Alternating Current Circuit Breaker DCCB - Direct Current Circuit Breaker Electrol - Electrical Systems Control Centre MTM - Metro Trains Melbourne SCADA - Supervisory Control and Data Acquisition RTU - Remote Terminal Unit (of the SCADA system) 4. Definitions Lock Out Shall Should The ACCB or DCCB is tripped by the operation of one or more protective devices and cannot be reclosed until an operator has attended on site to reset the lockout Is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. should can also be used if a requirement is a design goal but not a mandatory requirement. 5. References & Legislation 5.1 Standards The Rectifier Unit Control & Protection System shall comply with Australian Standards including: AS 2067 AS/NZS 3000 Substations and high voltage installations exceeding 1 kv a.c. Wiring Rules 5.2 Latest Issues and Amendments Reference to all standards shall be read as a reference to the latest edition of that standard and amendments available at the time of tendering. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 15

6 6. Background The Rectifier Unit Control & Protection System covered by this document will be used in MTM Traction Substations. These Substations primarily convert electricity from high voltage AC to 1500V DC power for the MTM Electric Train System. The Rectifier Assembly is one part of the Substation Rectifier Unit which consists of the Rectifier ACCB, Rectifier Transformer, Rectifier Assembly, Rectifier Unit Control & Protection System and Rectifier DCCB or Isolator as illustrated below. Rectifier Unit Rectifier ACCB Rectifier Transformer Rectifier Assembly Rectifier DCCB or Isolator Control & Protection System for 1500V DC Rectifier Unit Local Control Panel RTU Substation Battery (Control Supply) SCADA System Electrical Systems Control Centre The function of the Control & Protection System is to provide the control, protection and monitoring of the whole Rectifier Unit and all of its components. The Control & Protection System consists of all the components and systems required for this including switches, protection relays, control relays, indicating lights, cables, test blocks, terminal strips, transducers etc. The Control & Protection System is the main interface between the Rectifier Unit and the Substation RTU which then allows remote monitoring by the Electrical Systems Control Centre via the SCADA system. 7. Housing 7.1 The Control & Protection System components shall be mounted in a dedicated control cubicle. 7.2 The Cubicle should be located adjacent to the Rectifier Assembly. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 15

7 8. Control Supply 8.1 The Control Supply will be from the Substation Control Battery. It may be 50V, 110V or 125V DC depending on the location and will be specified separately in a scope of works document. 8.2 The negative of the Control Supply may or may not be connected to the substation earth at the Substation Control Battery. 8.3 All Control Relays shall have one side of their coils connected to the Control Supply Negative and shall be energised by the switching of the Control Supply Positive, either by switches or other relay contacts. 9. SCADA Voltage 9.1 The substation SCADA operating voltage may be 48V, 110V or 125V DC depending on the location. 9.2 It is important to note that the SCADA operating voltage may be different to the Control Supply voltage. 9.3 All SCADA Interposing Relays shall have coils rated to operate at the SCADA operating voltage. 10. Control Interfaces 10.1 General The precise details of the control functions required will depend on the particular installation, however general requirements are described in the following sections Rectifier ACCB Interface The Rectifier ACCB is the primary Rectifier Unit control and protection device The Rectifier Unit shall be switched on and off by the Rectifier ACCB The protection tripping of the Rectifier Unit shall be performed by the Rectifier ACCB, except in the case of DC faults The control of the closing of the Rectifier ACCB shall be inhibited by: The AC Under Voltage device Loss of the Control Supply The protection Lockout device Any other thing considered appropriate The Control & Protection System shall provide a selectable output interface to the ACCB which is capable of operating both conventional coil-operated (by means of a Control & Protection System voltage pulse) and PLC switched (by means of voltagefree contacts) ACCBs The Control & Protection System shall include a single-shot closing circuit which prevents instant re-closure of the ACCB in the event that it fails to remain closed after the initial attempt. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 15

8 10.3 Rectifier DCCB Interface Under normal operating conditions, the Rectifier DCCB acts as a slave of the Rectifier ACCB. If present, the Rectifier DCCB shall be closed by the successful closing of the Rectifier ACCB and opened by the opening of the Rectifier ACCB The normal operation, as described in shall be controlled via a single auxiliary contact of the Rectifier ACCB. Reserved terminals shall be included on the Control & Protection System terminal strip for the marshalling of this contact If the Rectifier DCCB trips automatically, the Rectifier ACCB shall be tripped and the Rectifier Unit shall be locked-out An auxiliary contact of the Rectifier DCCB shall be used to perform the function described in An indication of this event shall be provided on the Local Control Panel and to the SCADA system via a set of changeover contacts Rectifier DC Isolator Interface (where there is no Rectifier DCCB) The Rectifier DC Isolator shall be normally closed A mechanical or key interlock system shall be provided to prevent the Isolator from being opened or closed if the Rectifier ACCB is closed Local Control Panel A Local Control Panel shall be provided for the Rectifier Unit and located on the Control & Protection System Cubicle The Local Control Panel shall have the following components mounted on the front of it: Control Switch Rectifier ACCB status indicating lights Rectifier DCCB status indicating lights Protection Trip indicating lights (both AC and DC) SCADA Isolating Control Switch Any permanent monitoring indications not directly connected to the SCADA system Indicating lights shall be long life, high reliability light emitting diodes (LEDs). If lights are used for fault indications they shall be permanently on until they are manually reset, even if there has been a Control Supply power failure A means shall be provided for the resetting of any trip indication lights and for the testing of all indication lights The Control Switch shall be used to locally switch the Rectifier Unit on and off. It shall be a rotary, spring return to neutral switch with a pistol grip handle The SCADA Isolating Control Switch shall disable remote operation of the Rectifier Unit. It shall not isolate any remote indications. The switch shall be a rotary switch, shall have a yellow escutcheon plate, and shall be labelled C&I Isolating Switch The Panel shall be labelled Rectifier Unit Control. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 15

9 10.6 SCADA Interface The Control & Protection System shall interface with the SCADA system via the substation RTU All points that are to be controlled or indicated to the SCADA system shall be connected by a 3-wire system in accordance with MESP Technical Specification for SCADA cabling in Substations Each point to be controlled shall be operated via interposing relays. The relay coils of each controlled point shall be connected to an independent common Each point that is indicated shall be indicated by a set of changeover contacts. Each point shall have its own independent common connection Each point that is both controlled and indicated shall be brought to sequential terminals on the terminal strip SCADA control of the Rectifier ACCB shall be provided via: Operate Close Interposing Relay Operate Open Interposing Relay The interposing relay coil shall have a minimum resistance of 2000 Ω and be rated to operate at the SCADA operating voltage. The operate pulse time of the SCADA system is 1 second Both Open and Closed Indications of the Rectifier ACCB and DCCB or DC Isolator shall be provided to the SCADA system. These indications shall be via direct auxiliary contacts of the equipment. The terminal strip shall have an allowance for this. 11. Protection Functions 11.1 General The Control & Protection System shall provide all the protection functions necessary for the safe operation and protection of the Rectifier Unit and its components The following protection functions are mandatory as a minimum: AC Overcurrent AC Earth Fault Rectifier Assembly DC Frame Earth Leakage Rectifier Unit Input AC Undervoltage and Phase Failure 11.2 AC Overcurrent and Earth Fault System The AC Overcurrent and Earth Fault system shall include Test Disconnect Terminals for secondary injection testing. The preferred type of test link block is a Weidmuller type WTL 6/1 however other types may be used if approved by MTM during the design phase The preferred Rectifier Unit AC Protection Relay is an AREVA MiCom P123 series relay. Any alternative relay proposed must be approved by MTM during the design phase and shall: PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 9 of 15

10 Contain a selectable inverse time curve identical to the specification for the Rectifier curve of the MiCom P123 series relay Be programmable to allow multi-stage trip settings Have latching LEDs or mechanical flags that are capable of being programmed to indicate each tripping function of the relay Be microprocessor based and capable of storing the details of the 5 most recent trips, complete with date and time stamps. A Watchdog Timer function The Watchdog Timer function of the Rectifier Unit AC Protection Relay shall be connected to the SCADA terminal strip for direct connection to the SCADA system. The failure of the Watchdog Timer function shall not cause a protection trip Rectifier Assembly DC Frame Earth Leakage The Rectifier Assembly contains a DC Frame Earth Leakage Relay that is connected between the Rectifier Assembly enclosure and the substation earth Upon operation of the Rectifier Assembly DC Frame Earth Leakage Relay, the Control & Protection System shall trip the Rectifier ACCB If the Rectifier Unit does not include a Rectifier DCCB, the Control & Protection System shall trip the Section DCCBs in the substation via device 94B, Section DCCB Tripping Relay. This device is located on the Control Supply Switchboard Provision shall be made to allow an auxiliary contact of the Rectifier Assembly DC Frame Earth Leakage relay to be wired to the main terminal strip through a set of Test Disconnect Terminals for connection to the RTU AC Undervoltage, Phase Failure, Phase Loss and Phase Reversal The AC Undervoltage (3 phase), Phase Failure, Phase Loss and Phase Reversal protection shall include a definite time delay for all functions that is adjustable between 1 and 10 seconds. This would nominally be set at 5 seconds and shall not be affected by any disturbance of the AC supply Lockout Functions The occurrence of a lockout event shall prevent the Rectifier ACCB and Rectifier DCCB (or Section DCCBs where a Rectifier DC Isolator is fitted) from being re-closed until the Rectifier Unit has been inspected, the fault isolated and the lockout device manually reset via the Local Control Panel The following protection functions shall be considered lockout events: Rectifier Assembly DC Frame Earth Leakage AC Earth Fault Contacts from critical Rectifier Transformer temperature detection Contacts from critical Rectifier Assembly over-temperature detection Any other critical fault that requires an inspection before re-closure PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 10 of 15

11 12. Monitoring Functions 12.1 All monitoring functions shall interface with the SCADA system The Control Supply voltage shall be monitored and an indication of the loss of supply shall be given to the SCADA interface. The device monitoring the supply shall have a normally open and a normally closed changeover output contact The monitoring functions shall include warnings that the Rectifier Unit is approaching the rated voltage and current values All warning indications should have normally open and normally closed changeover output contacts. 13. Cubicle Requirements 13.1 Labelling All devices, enclosures and circuits shall be clearly and permanently labelled for easy identification. The device numbers, etc. will be determined by MTM, and advice given before manufacture. Refer to MESP Substation Device Naming, Numbering and Labelling All labels shall be of the Traffolyte type with engraved black lettering on white background A label "Rectifier Unit Control" shall be provided toward the top of the cubicle on the front All components mounted on the front shall be labelled by name and device numbers where applicable All components mounted inside the cubicle shall be labelled by their device number or fuse number, where applicable. Components visible on both the outside and inside of the cubicle shall be labelled inside and outside All wiring shall be clearly and permanently marked for easy identification. Each wire shall be uniquely identified and marked in the same way at both ends of the cable, with the same marking identified on the relevant drawings Terminal Strips and Wiring A separate terminal strip shall be provided inside the cubicle for the connection of all external cabling Terminals shall be grouped together in functional groups and shall be segregated by voltage At least 50 spare terminals shall be available for the marshalling of other control and protection devices. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 11 of 15

12 14. Testing Tests shall be performed on the Control & Protection System as described below 14.1 Factory Tests The manufacturer shall design a comprehensive test plan to be undertaken as factory testing which will be approved by MTM prior to manufacture All parts of the Control & Protection System able to be factory tested shall be factory tested for insulation functionality and operation MTM reserves the right to appoint a representative to witness these tests. Seven working days notification shall be given to MTM of intention to carry out factory testing Test Certificates The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations The test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. 15. Documentation and Support 15.1 Documentation Requirements All documentation shall be provided in English One electronic and eight paper copies of the each document shall be provided and the content shall be identical in each copy Every page of the documentation shall be clearly identified in relation to the document to which it belongs and the version of that document. All pages of multipage documents shall be uniquely numbered. It shall be possible to readily determine if all pages of a document are present Manuals shall be A4 size and shall be bound in durable covers or in 4-D ring binders Design Drawings The following drawings must be supplied: i. A single Control & Protection Circuit Diagram ii. iii. iv. Construction details of the Rectifier Unit Control & Protection System Cubicle including dimensions. Physical layout and arrangement of the components in the Cubicle and on the Local Control Panel Mounting requirements for the Cubicle. v. Physical layout and arrangement of the cable connections and terminal blocks in the Cubicle. vi. All other drawings required for Installation, Testing, Commissioning, Operation and Maintenance including a complete parts list. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 12 of 15

13 15.3 Drawing Format All drawings must comply with VRIOGS Infrastructure Drafting Standard and shall be submitted for MTM approval prior to manufacturing Files shall be provided in Microstation format on compact disk (CD) Installation Manual An Installation Manual shall be provided and shall include instructions which enable the assembly to be properly installed, tested and commissioned. This shall include all necessary drawings. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 13 of 15

14 16. Appendix A Design Management Requirements This appendix describes the documentation which should be provided as a minimum at each stage of the procurement process. The documentation shall comply with the specifications above. Tender Submission The following documents are to be provided as part of the tender submission: General Arrangement drawing of the Rectifier Unit Control & Protection System Cubicle Proposed factory testing procedure The Technical Data Schedule in Appendix B filled in. Contract Documentation One set of PDF copies of the documentation described in section 15.2 should be provided for review and approval by MTM four weeks after the Contact Award Date. No manufacture shall commence until the drawings have been approved. An allowance of five working days should be made by the supplier for the review and approval of submitted drawings. Any required alterations will require resubmission and another review of the drawings. Pre-Delivery Documentation The supplier shall provide five hard copies of the following documents at the time of delivery: Installation Manual Test results Approved drawings In addition to the hard copies, the supplier shall provide copies of the final layouts and schematic drawings in electronic format (PDF and Microstation) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 14 of 15

15 17. Appendix B Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance thereof. a Does the Rectifier Unit Control & Protection System fully comply with this Specification? YES/NO b. Type of Cubicle construction c. Height of Cubicle (mm) d. Width of Cubicle (face with Local Control Panel) (mm) e. Depth of Cubicle (mm) f. Type of mounting g. Weight of Cubicle (fitted out) (kg) h. Terminal strips total spare terminals i. Is a copy of the proposed testing procedure attached? YES / NO PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 15 of 15

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Specification Electrical Networks L1-CHE-SPE-128 Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Version: 1 Issued: February 2016 Owner: Head of Engineering - Electrical Approved

More information

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical

More information

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Engineering Specification Electrical TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Version: 2 Issued: October 2017 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

DESIGN PRACTICE NOTE NEGATIVE BUSBAR SHUNTS

DESIGN PRACTICE NOTE NEGATIVE BUSBAR SHUNTS Approval Amendment Record Approval Date Version Description 27/05/2013 1 Initial issue under MTM. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 6 Table of Contents

More information

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES SURGE PROTECTION IN SIGNAL Approval Amendment Record Approval Date Version Description 11/05/2016 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is

More information

11 kv Indoor Switchgear - SCADA Controlled

11 kv Indoor Switchgear - SCADA Controlled Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0521 NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN This document details the installation, testing

More information

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE Document Number: ECP 11-0501 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0501 SECONDARY SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the end-to-end process

More information

Title Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP)

Title Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Reference Number POP 07 - (RIC Standard: EP 99 00 00 04 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

COMMUNICATION LINKS FOR SIGNALLING

COMMUNICATION LINKS FOR SIGNALLING Engineering Standard - Design Signalling & Operational Control Systems COMMUNICATION LINKS FOR SIGNALLING Version: 2 Issued: April 2016 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

MiCOM P111. Three phase and earth fault overcurrent relays

MiCOM P111. Three phase and earth fault overcurrent relays Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP) Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

Miniature Circuit-Breaker IEC Series 8562

Miniature Circuit-Breaker IEC Series 8562 > 1 to 3 pole versions > Rated current from 0.5... 40 A > 6 or 10 ka breaking capacity to DI VDE 0641, respectively E 60898 > Isolating Function to E 60947-2 > Permanently set thermal and magnetic trips

More information

REYROLLE 2RMLG. Operating Recommendations

REYROLLE 2RMLG. Operating Recommendations 2RMLG Operating Recommendations SAFETY The commissioning and maintenance of protection equipment should only be carried out by skilled personnel trained in protective relay operation and capable of observing

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics SIA-C Overcurrent and Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered Main characteristics The SIA-C is a overcurrent protection relay with self powered and dual powered (self

More information

RMS Product Presentation

RMS Product Presentation RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company

More information

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation 2T15 Multi Range Digital Setting Time Delay Relay Technical Bulletin Features Four time ranges -.99s, -9.9s, -99s, -99s High accuracy & repeatability timing compensated for output relay delay Time settings

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

SECTION APPENDIX B SFC DOCUMENT SUBMITTAL SCHEDULE

SECTION APPENDIX B SFC DOCUMENT SUBMITTAL SCHEDULE SECTION 16262 - APPENDIX B SFC DOCUMENT SUBMITTAL SCHEDULE PART 1 - GENERAL 1.01 RELATED SECTIONS A. Section 01300 Submittals B. Section 16262 Static Frequency Converter C. Section 16262A Appendix A SFC

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for Type NZMH4-...

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for Type NZMH4-... Circuit Breakers, 09/054 Moeller Electric Corporation Auxiliary Contacts for Type Contacts Type Suffix Price N.O. = normally open N.C. = normally closed when ordering with basic N.O. N.C. Standard auxiliary

More information

K1D012ULH cam changeover switch - 2-pole A - screw mounting

K1D012ULH cam changeover switch - 2-pole A - screw mounting Characteristics cam changeover switch - 2-pole - 90-12 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product mounting Fixing

More information

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for NZM(H)6(B)-...

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for NZM(H)6(B)-... Circuit Breakers, Disconnect Switches, Molded Case Switches 09/064 Moeller Electric Corporation Auxiliary Contacts for. Contacts Type Suffix Price N.O. = normally open N.C. = normally closed when ordering

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/pgr-4700 PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY REVISION 2-B-032218 Copyright 2018 by Littelfuse, Inc. All rights reserved.

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Microlok Data Design Records (Addressing, File Control, Checking, and FAT Testing)

Microlok Data Design Records (Addressing, File Control, Checking, and FAT Testing) Discipline: Engineering (Signalling) Category: Procedure Microlok Data Design Records (Addressing, File Control, Checking, and FAT Testing) ESD-05-11 Applicability ARTC Network Wide Primary Source Signal

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

SM100. On-Line Switchgear Condition Monitoring

SM100. On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring Introduction Weis is a specialist company with over 40 years of experience in the commissioning, testing & maintenance of

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics SIA-B Overcurrent & Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered / Standard CTs Main characteristics The SIA-B is an protection relay with self powered and dual powered (Self-powering

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Bulletin Installation of solar photovoltaic systems Rules , , , , and Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic

More information

K1K015NZ4 cam stepping switch - 2-pole A - screw mounting

K1K015NZ4 cam stepping switch - 2-pole A - screw mounting Characteristics cam stepping switch - 2-pole - 60-12 A - screw mounting Complementary Number of steps 5 Main Range of product Product or component type Component name [Ith] conventional free air thermal

More information

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS Introducing the DIN Series High-quality, high-performance circuit breakers Features (1) All models fully comply with IEC regulations

More information

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.

More information

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR AUGUST 14, 2001 REVISION 1 Publication: SE-135-M Document: S95-C135-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

K1F006ALH cam switch - 6-pole A - screw mounting

K1F006ALH cam switch - 6-pole A - screw mounting Characteristics cam switch - 6-pole - 45-12 A - screw mounting Complementary Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product mounting

More information

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility GE Grid Solutions MiCOM Agile P99x Test Block, Multi-finger Test Plug and Single-finger Test Plug The MiCom Agile P991 test block offers safe and configurable facilities for monitoring and secondary injection

More information

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11 Technical Information Product Details Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11 Contents The Sunny String Monitor SSM24 11 is specifically designed for monitoring large PV generators.

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

PROTECT Electronics Co. Ltd

PROTECT Electronics Co. Ltd Independent static overcurrent relay Document ID: 24-13-15848-00 Budapest, 2006 User s manual version information Version Datum Modification Compiled by.00 May 1995 First Hungarian version Póka.01 June

More information

Recording and Reporting of High Voltage and Low Voltage Switching

Recording and Reporting of High Voltage and Low Voltage Switching 1 SCOPE This document details the procedures to be adopted prior to, during, and on completion of Switching operations, and details the manner in which HV and LV Switching shall be recorded in order to

More information

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

6 Check that the earth system is complete, undamaged and bonded to earth points ( including capacitor and control).

6 Check that the earth system is complete, undamaged and bonded to earth points ( including capacitor and control). NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

K1F037MCH cam voltmeter switch - 3L and 3L-N A - for Ø 22 mm

K1F037MCH cam voltmeter switch - 3L and 3L-N A - for Ø 22 mm Characteristics cam voltmeter switch - 3L and 3L-N - 60-12 A - for Ø 22 mm Main Range of product Product or component type Component name [Ith] conventional free air thermal current Mounting location Fixing

More information

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection

More information

7XG225-3RMLG Test Block System Answers for infrastructure & cities.

7XG225-3RMLG Test Block System Answers for infrastructure & cities. Reyrolle Protection Devices 7XG5-3RMLG Test Block System Answers for infrastructure & cities. Siemens Protection Devices Limited 7XG5-3RMLG Test Block System Application Test blocks enable test technicians

More information

K1F003MCH cam ammeter switch - 3 circuits A - for Ø 22 mm

K1F003MCH cam ammeter switch - 3 circuits A - for Ø 22 mm Product data sheet Characteristics cam ammeter switch - 3 circuits - 90-12 A - for Ø 22 mm Complementary Main Range of product Product or component type Component name [Ith] conventional free air thermal

More information

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Iso DIN. User Manual. 1 channel Earth Fault Monitoring Page 1 of 5 2017 03 20 User Manual Iso DIN Iso DIN User Manual 1 channel Earth Fault Monitoring Megacon AB Ranhammarsvägen 20 S 168 67 Bromma Sweden Tel: 08 402 42 50 sales@megacon.se www.megacon.se eee

More information

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue Short Form Catalogue SIGMA Advanced Generator Protection and Control Generator protection, synchronizing and load sharing Power management system Easy to install and commission Control most governors/avrs

More information

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input Safety + standard I/O in one module Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category IP20

More information

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC Characteristics adjustable off-delay timing relay - 0.05..1 s - 240 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time delay

More information

K1B004TLH cam switch - 1 pole A - screw mounting

K1B004TLH cam switch - 1 pole A - screw mounting Characteristics cam switch - 1 pole - 30-12 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product mounting Fixing mode Cam

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction ACOPOSinverter P74 User's Manual Version: 2.20 (August 2016) Model no.: MAACPIP74-ENG Original instruction All information contained in this manual is current as of its creation/publication. We reserve

More information

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics SIL-A Overcurrent and Earth Fault Relay for Primary and Secondary Distribution Main characteristics The SIL-A is an overcurrent and earth fault protection relay for primary and secondary distribution with

More information

RM4TR31 three-phase network control relay RM4-T - range V

RM4TR31 three-phase network control relay RM4-T - range V Characteristics three-phase network control relay RM4-T - range 160..220 V Complementary [Us] rated supply voltage Control threshold undervoltage Control threshold overvoltage Output contacts Main Range

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for NZM(H)9-...

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for NZM(H)9-... Circuit Breakers, 09/074 Moeller Electric Corporation Auxiliary Contacts for Contacts Type Suffix Price N.O. = normally open N.C. = normally closed when ordering with basic device N.O. N.C. Standard auxiliary

More information

MOTOR PROTECTION CIRCUIT BREAKERS

MOTOR PROTECTION CIRCUIT BREAKERS MOTOR PROTECTION CIRCUIT BREAKERS PAGE -2 PAGE -2 SMA Thermal trip adjustment ranges 9-32A (5 choices) Breaking capacity Icu at 400V: 50kA Suitable for mounting in consumer switchboards with minimum 58mm

More information

CONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual

CONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual 50 and 50 Digital I/O Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD. (INDIA) VT. LTD. 5. INCOMING SULY CONDUCTOR TERMINATIONS AND DEVICES FOR DISCONNECTING AND SWITCHING OFF 5.1 Incoming supply conductor terminations The electrical equipment of the machine shall have only

More information

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B GE Energy Connections Grid Solutions MMLZ Technical Data Sheet Auxiliary Modules Publication reference: MMLZ/EN TDS/B MMLZ Technical Data Sheet FEATURES Wide choice of application specific models Fully

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

2C138. Sensitive Earth Fault Relay. Features. Application. Operation Technical Bulletin 2C138 Sensitive Earth Fault Relay Features High sensitivity (0.1% of I n ) 2 nd & 3rd harmonic & HF noise suppression - tuned to 50 Hz Optional reset functions Instantaneous (Fast),

More information

NPIH800 NPIH800R. First Handling Guide Earth overcurrent relay

NPIH800 NPIH800R. First Handling Guide Earth overcurrent relay Earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPIH800 and NPIH800R relays, multifunction digital protections

More information

STANDARD SUBMITTAL PACKAGE

STANDARD SUBMITTAL PACKAGE STANDARD SUBMITTAL PACKAGE SBP1000-51( ) FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for

More information

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION ( ) LIGHTING CONTROL PANELBOARD (26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting

More information

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC Characteristics time delay relay for star-delta starter - 0.05..1 s - 24 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time

More information

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.: Extract from the online catalog QUINT-PS/1AC/24DC/10 Order No.: 2866763 DIN rail power supply unit 24 V DC/10 A, primary-switched mode, 1- phase. The SFB technology (Selective Fusebreaking Technology)

More information