LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES SECTION 16496D

Size: px
Start display at page:

Download "LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES SECTION 16496D"

Transcription

1 ( ) LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the low voltage automatic transfer switch and bypass isolation transfer switch having the ratings, features/accessories and enclosures as specified herein and as shown on the contract drawings RELATED SECTIONS 1.03 REFERENCES A. The automatic transfer switch and bypass isolation switches and all components shall be designed, manufactured and tested in accordance with the latest applicable CSA standards as follows: 1. CSA 22.2 No. 178 Automatic Transfer Switches 2. CSA 22.2 No. 5.1 Molded Case Circuit Breakers 3. CSA 22.2 No. 5.2 Molded Case Switches 4. CSA C282 Emergency Electrical power Supply for Buildings 5. CSA Z32 Electrical Systems in Health Care Facilities 1.04 SUBMITTALS -- FOR REVIEW/APPROVAL A. The following information shall be submitted to the Engineer: 1. Master drawing index 2. Front view and plan view of the assembly 3. Schematic diagram 4. Nameplate schedule 5. Component list 6. Conduit space locations within the assembly 7. Assembly ratings including: a. Short-circuit rating b. Voltage c. Continuous current rating 8. Major component ratings including: a. Voltage b. Continuous current rating c. Interrupting ratings 9. Cable terminal sizes 10. Product Data Sheets. B. Where applicable, the following additional information shall be submitted to the Engineer:

2 1. Busway connection 2. Connection details between close-coupled assemblies 3. Composite front view and plan view of close-coupled assemblies 4. Interlock schematic drawing, Kirk-key or as indicated otherwise, and sequence of operations 5. Mimic bus. C. Submit ten (10) copies of the above information SUBMITTALS FOR INFORMATION A. When requested by the Engineer, the following product information shall be submitted: 1. Descriptive bulletins. 2. Product guides/sheets 1.06 SUBMITTALS FOR CONSTRUCTION A. The following information shall be submitted for record purposes: 1. Final as-built drawings and information for items listed in section Wiring diagrams 3. Certified production test reports 4. Installation information B. The final (as-built) drawings shall include the same drawings as the construction drawings and shall incorporate all changes made during the manufacturing process. C. Submit ten (10) copies of the above information QUALIFICATIONS A. The manufacturer of the assembly shall be the manufacturer of major components and control modules installed within the assembly. B. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of five (5) years. When requested by the engineer, an acceptable list of installations with similar equipment shall be provided demonstrating compliance with this requirement. C. For the equipment specified herein, the manufacturer shall be certified as a minimum to ISO D. *Provide Seismic qualified equipment, when required, as follows: 1. The equipment and major components shall be suitable for and certified to meet all applicable seismic requirements of the [latest National Building Code of Canada (NBCC)]. 2. The Project Structural Engineer will provide site specific ground motion criteria for use by the manufacturer to establish Sa (0.2) value required. 3. The following minimum mounting and installation guidelines shall be met, unless specifically modified by the above referenced standards. a. The Contractor shall provide equipment anchorage details, coordinated with the equipment mounting provision, prepared and stamped by a licensed engineer in the province. Mounting recommendations shall be provided by the manufacturer based upon the above criteria to verify the seismic design of the equipment.

3 b. The equipment manufacturer shall certify that the equipment can withstand, that is, function following the seismic event, including both vertical and lateral required response spectra as specified in above codes. c. The equipment manufacturer shall document the requirements necessary for proper seismic mounting of the equipment. Seismic qualification shall be considered achieved when the capability of the equipment, meets or exceeds the specified response spectra REGULATORY REQUIREMENTS A. Provide a certificate of compliance with CSA 22.2 No. 178 for the transfer switches furnished under this section. The certificate of compliance is not required if the manufacturer s published data submitted and approved reflect CSA C22.2 No DELIVERY, STORAGE AND HANDLING A. Equipment shall be handled and stored in accordance with manufacturer s instructions. One (1) copy of these instructions shall be included with the equipment at time of shipment FIELD MEASUREMENTS 1.11 OPERATION AND MAINTENANCE MANUALS A. Equipment operation and maintenance manuals shall be provided with each assembly shipped, and shall include instruction leaflets and instruction bulletins for the complete assembly and each major component EXTRA PRODUCTS PART 2 PRODUCT CONSTRUCTION 2.01 MANUFACTURERS A. Eaton B. C. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. Products in compliance with the specification and manufactured by others not named will be considered only if pre-approved by the engineer ten (10) days prior to bid date. Note to Spec. Writer Insert data in blanks

4 2.02 RATINGS A. The bypass isolation automatic transfer switch shall have withstand, closing and interrupting ratings sufficient for the voltage and the available short circuit at the point of application as shown on the system drawings. B. The voltage rating of the transfer switch shall be no less than the system voltage rating. The continuous current rating of the transfer switch shall be no less than the maximum continuous current requirements of the system. C. The bypass isolation automatic transfer switch shall be 100% equipment rated for continuous duty. D. The bypass isolation automatic transfer switch shall be fully rated to protect all types of loads, inductive and resistive, from loss of continuity or power, without de-rating, either open or enclosed. E. When deemed necessary, the bypass isolation automatic transfer switch shall be Type B, 80% rated, and make use of integral overcurrent devices necessary for additional protection and coordination of circuit conductors. F. All control devices (i.e. pilot devices, relays, and metering) must be manufactured to industrial standards. All relays supplied shall be furnished with self-cleaning contacts. Transfer Switch Ampere Rating Maximum fault level available at upstream device (ka) No. of 2.03 TRANSFER SWITCH Upstream any manufacturers breaker type poles 208V 240V 480V 600V Maximum fault level available at upstream device (ka) Maximum Fuse Rating (A) Upstream Fuse type A. Transfer switches shall consist of completely enclosed contact assemblies and a separate control panel. The contact assemblies shall be operated by a non-fused motor operator or stored energy mechanism and will only be energized during a transfer operation, providing inherently double throw switching action. B. Each transfer switch shall be positively interlocked both mechanically and electrically to prevent simultaneous closing of both sources during automatic or manual operation. Each transfer switch Fuse Type 208V 240V 480V 600V ,3, J, T ,3, J, T ,3, J, T ,3, J, T ,3, R , /1600 L 100/ / / / L ,3, L ,3, L

5 shall be capable of achieving a neutral position for systems maintenance purposes. A transfer switch position indicator shall be included on the face of the transfer mechanism to display the switch position. C. Transfer switches shall be capable of being operated manually under full rated load conditions. Manual operation shall provide true quick-make, quick-break operation to prevent possible flashovers from switching the contacts slowly. D. On transfer switches requiring a fourth pole for switching the neutral, the neutral shall be fully rated with equal withstand, closing and interrupting ratings to the power poles. The neutral pole contacts shall be of identical construction as, and operate simultaneously with, the main power contacts. Switched neutral poles, which are add-on or overlap or that are not capable of breaking full rated load current are not acceptable. E. Main contacts shall be designed and type tested to withstand multiple fault currents and shall meet CSA 22.2 No. 178 and C22.2 No BYPASS ISOLATION SWITCH A. Single-sided (one-way) bypass-isolation switches shall provide manual bypass of the load to the emergency source only and permit isolation of the automatic transfer switch from all source and load conductors. All main contacts shall be manually driven and operated. B. Double-sided (two-way) bypass-isolation switches shall provide manual bypass of the load to the either source, emergency or normal, and permit isolation of the automatic transfer switch from all source and load conductors. All main contacts shall be manually driven and operated. C. Separate bypass and isolation handles shall be utilized to provide clear distinctions between these functions. All operators shall be permanently affixed and operable without opening the enclosure door (EEMAC1 only). D. For bypass operation, a single-throw isolating handle mechanism shall be operated to isolate the automatic transfer switch from the normal, emergency, and load power conductors. Bypass switches will only be permitted to operate when the isolating mechanism is in the isolation position. Emergency and normal bypass switches shall be interlocked via a mechanical interlocking plate. E. Field installation of power connections shall be at the line and load terminals of the bypass isolation switch. All power interconnections shall be silver-flashed or tin-plated copper bus. All control interwiring shall be provided with disconnect plugs MICROPROCESSOR LOGIC CONTROL A. The automatic transfer switch controllers shall meet or exceed the following standards in addition to the basic switch standards: 1. IEC EMC Testing and Measurement Techniques - Electrostatic Discharge Immunity Test 2. IEC EMC Testing and Measurement Techniques - Radio-frequency, Electromagnetic Field Immunity Test 3. IEC EMC Testing and Measurement Techniques - Electrical Fast Transient/Burst Immunity Test 4. IEC EMC Testing and Measurement Techniques - Surge Immunity Test

6 5. IEC EMC Testing and Measurement Techniques - Immunity to Conducted Disturbances, Induced by Radio-frequency Fields 6. IEC EMC Testing and Measurement Techniques - Voltage Dips, Short Interrupts and Voltage Variations Immunity Tests 7. CISPR11, Class B - Industrial, Scientific and Medical Radio-frequency Equipment - Electromagnetic Disturbance Characteristics - Limits and Methods of Measurement 8. FCC Part 15, Subpart B, Class B B. The transfer switch shall be controlled by a Eaton microprocessor-based controller. The controller shall be hardened against potential problems from transients and surges. Operation of the transfer switch and monitoring of both sources shall be managed by the controller. C. The logic control panel shall control the operation of the transfer switch. All sensing and logic shall be controlled by an onboard microprocessor for maximum reliability and minimum maintenance. The logic controller shall be connected to the transfer switch by and interconnecting wiring harness. The harness shall include a keyed disconnect plug to enable the control panel to be disconnect from the transfer switch for routine maintenance. Note to Spec. Writer (SELECT ONE): Breaker Based Transfer Switches have (2) models of Microprocessor-Based Controller units available: ATC-300+, Select Open transition breaker based transfer switches A {This Controller is versatile in its capabilities allowing for setup of most standard commercial and industrial applications. There is a system status display and the full feature set is accessible for programming adjustment from the LCD and membrane pushbuttons on the front faceplate} ATC-900, Select Open transition breaker based transfer switches A {This controller is full featured and available for use in Open transition applications. This controller also has a second set of engine start contacts for Generator to Generator applications.. It features a communications interface for connection to Power monitoring or building automation control systems through a gateway} MICROPROCESSOR-BASED CONTROLLER (ATC-300+ OPEN TRANSITION) A. The microprocessor-based controller display shall be UV resistant and include a 2-line, 16 character, backlit LCD display. The controller shall be capable of displaying transfer switch status, parameters, and diagnostic data. All set point parameters shall be password protected and programmable using the controller keypad or remotely using serial port access. B. The microprocessor-based controller shall include a mimic bus display consisting of four (4) individual LED s (3mm) for indicating the following: 1. Availability status of source 1 2. Availability status of source 2 Note to Spec. Writer Select one

7 3. Connection status of source 1 4. Connection status of source 2 C. The controller shall have a voltage range of volts (50/60 Hz) and an accuracy of +/- 1% of nominal input voltage and a frequency range of Hz and an accuracy of +/-.3 H D. Voltage and frequency dropout and pickup parameters are set as a percentage of the nominal voltage as indicated in the table below Setpoint Sources Dropout Pickup Undervoltage Source1 and % (DO + 2%) - 99% Overvoltage Source 1 and % 103% - (DO 2%) Underfrequency Source 1 and % (DO + 1Hz) 99% Overfrequency Source 1 and % 101% - (DO 1Hz) Voltage Unbalance Source 1 and % (UNBAL DO% - 2) 3% E. The normal and emergency sources shall include phase reversal protection. The preferred rotation is programmable as ABC or CBA. F. A time delay shall be provided on transfer to source 2, adjustable from 0 to 1800 seconds G. A time delay shall be provided to override a momentary power outage or voltage fluctuation, adjustable from 0 to 120 seconds H. A time delay shall be provided on retransfer from source 2 to source 1, adjustable from 0 to 1800 seconds I. A time delay shall be provided after retransfer that allows the generator to run unloaded prior to shutdown, adjustable form 0 to 1800 seconds J. A time delay shall be provided for engine failure to start, fixed setting of 6 seconds K. A pre-transfer time delay output adjustable from seconds. The contact shall be a form-c contact rated for 10-Amp at 250-Vac and 10-Amp at 30-Vdc L. All delays shall be field adjustable from the microprocessor-based controller without the use of special tools M. Additional features: 1. One Form A contact for closure of the generator start circuit. The contacts shall be of silver alloy with gold flashing. The contacts shall be rated for 5-Amp at 250-Vac and 5-Amp at 30-Vdc 2. Programmable Engine Exerciser, selectable as disabled, 7, 14, or 28 day interval, adjustable minutes, load or no load with Failsafe 3. The controller shall include a keypad pushbutton to initiate a system test 4. The controller shall include a keypad pushbutton to bypass the time delay on transfer to emergency and the time delay on retransfer to normal

8 5. The controller shall include a terminal input to accept a remote contact which closes to initiate a transfer to source 2. This feature shall be failsafe and an automatic retransfer shall occur in the event that source 2 power is lost. 6. The controller shall include a terminal input to accept a remote contact which opens to inhibit transfer to source. 7. One Form C auxiliary contact to indicate source 1 position and one Form C contact to indicate source 2 position. The contacts shall be rated for 10-Amp, 1/3-Horsepower at 250-Vac and 10- Amp at 30-Vdc. 8. One Form C contact for source 1 present. The contacts shall be rated for 10-Amp, 1/3- Horsepower at 250-Vac and 10-Amp at 30-Vdc. 9. One Form C contact for source 2 present. The contacts shall be rated for 10-Amp, 1/3- Horsepower at 250-Vac and 10-Amp at 30-Vdc. 10. Historical Data Storage to include: a. Engine Run Tim b. Source 1 Available Time c. Source 2 Available time d. Source 1 Connected time e. Source 2 Connected time f. Load Energized time g. Number of Transfers h. Date, Time and Reason for Last Sixteen (16) transfers i. Monitor Mode Event j. Fail Safe Event k. Aborted Test N. Optional accessories: 1. Non-Automatic Control: Provide a 2-Position Selector Switch, maintained contact, marked: Automatic and Non-Automatic. The transfer switch shall be transferred by actuating a two position maintained selector switch labeled Source 1 and Source 2. A 30mm pilot light shall be provided labeled Not in Automatic. 2. Manual Retransfer Control: The ATS shall remain connected to the emergency source after the normal source becomes available until a momentary pushbutton contact closure signal is received to initiate the retransfer. Should a failure of the emergency source occur while waiting for the manual return, the re-transfer proceeds automatically. 3. Communications Interface to be [Modbus 485] [Ethernet TCP/IP]. 4. Where indicated on the drawings, provide [50KA] [100KA] surge protection device on Source 1 5. Space heater with thermostat rated for [100 watts] [400 watts] Note to Spec. Writer - Optional

9 6. Where metering is indicated on the drawings include Eaton IQ250 meter, catalog number IQ250MA65100, load side 7. Remote Annunciator and Controller: a. Monitoring Functions 1. Display shall be a touchscreen color display capable of monitoring up to 8 transfer switches on one screen. 2. General screen shall include a mimic bus display for each transfer switch with indication of source availability, based on controller pickup and dropout settings, and switch position. 3. Each mimic bus display shall be marked with the designation of the transfer switch monitored. 4. Display shall include indication of switch in test mode, manual retransfer status, and go to emergency status. 5. Shall include the ability to view source data and event logs for each transfer switch. b. Control Functions 1. Control functions shall be password protected and shall include: c. Alarms a. Initiate engine test. b. Initiate a failsafe transfer to source 2. c. Initiate manual retransfer. d. Alarm silence. 1. Remote Annunciator shall provide audible and visual alarm when on source 2 2. Visual alarm upon failure of communication link. d. Mounting: Flush, modular, unless otherwise indicated. e. Communications capability to be compatible with ATS controller. -- OR MICROPROCESSOR-BASED CONTROLLER (ATC-900 OPEN TRANSITION) A. The microprocessor-based controller display shall be UV resistant and include a 4.3 inch Color TFT (480x272), backlit display. The controller shall be capable of displaying transfer switch status, parameters, and diagnostic data. All set point parameters shall be password protected and programmable using the controller keypad, USB port, or remotely using serial port access. Limited abbreviations or codes shall be used for transfer switch functions B. The microprocessor-based controller shall include a mimic bus display consisting of six (6) individual LED s (3mm) for indicating the following: Note to Spec. Writer Select one

10 1. Availability status of source 1 2. Availability status of source 2 3. Connection status of source 1 4. Connection status of source 2 5. Source 1 Preferred 6. Source 2 Preferred C. The controller shall have a voltage range of volts (50/60 Hz) with an accuracy of +/- 1% of the reading and a frequency range of Hz with an accuracy of +/-.3 Hz D. Voltage and frequency dropout and pickup parameters are set as a percentage of the nominal voltage as indicated in the table below Setpoint Sources Dropout Pickup Undervoltage Source1 and % (DO + 2%) - 99% Overvoltage Source 1 and % 103% - (DO 2%) Underfrequency Source 1 and % (DO + 1Hz) 99% Overfrequency Source 1 and % 101% - (DO 1Hz) Voltage Unbalance Source 1 and % (UNBAL DO% - 2) 3% E. The normal and emergency sources shall include phase reversal protection. The preferred rotation is programmable as ABC or CBA. F. A time delay shall be provided on transfer to source 2, adjustable from 0 to 166 minutes G. A time delay shall be provided to override a momentary power outage or voltage fluctuation, adjustable from 0 to 120 seconds. H. A time delay shall be provided on retransfer from source 2 to source 1, adjustable from 0 to 166 minutes. I. A time delay shall be provided after retransfer that allows the generator to run unloaded prior to shutdown, adjustable form 0 to 166 minutes J. time delay shall be provided for engine failure to start, adjustable 0-6 seconds. K. A pre and or post transfer time delay output adjustable from seconds. The contact shall be a form-c contact rated for 10-Amp at 250-Vac and 10-Amp at 30-Vdc. L. All delays shall be field adjustable from the microprocessor-based controller without the use of special tools. M. Additional features: 1. One Form C contact for closure of the source 1 generator start circuit for optional use with a dual generator system. The contacts shall be rated for 5-Amp at 250-Vac and 5-Amp at 30-Vdc. 2. One Form C contact for closure of the source 2 generator start circuit. The contacts shall be rated for 5-Amp at 250-Vac and 5-Amp at 30-Vdc. 3. The controller shall include two independently programmable Engine Exercisers, selectable as disabled, 7, 14, or 28 day interval, or by calendar date. Run time shall be adjustable for 0-600

11 minutes, with or without load. Upon loss of source 2 power, the ATS shall automatically return to source 1. Transfer time delays shall also be independently programmable for test events. 4. The controller shall include a keypad pushbutton to initiate a system test. 5. The controller shall include 4 user configurable inputs. Each input provides 50 volts at 10ma and can be user configured to one of the following features: a. Input to accept a remote contact which closes to initiate a transfer to source 2. This feature shall be failsafe and an automatic retransfer shall occur in the event that source 2 power is lost. b. Input to accept a remote contact which closes to initiate a transfer to source 2. This feature shall be failsafe and an automatic retransfer shall occur in the event that source 2 power is lost. c. Input to accept a remote contact which opens to inhibit transfer to source 2. d. Input to enable monitor mode to disable automatic operation of the transfer switch while continuing to display status. Monitor mode allows set point programming at the controller display. e. Input to enable lockout feature to disable automatic operations of the transfer switch following an overcurrent trip of an integral circuit breaker. f. Input to enable or disable manual retransfer to source 1 g. Input to initiate manual retransfer to source 1 h. Input to initiate a remote engine test. The test will run using the programmed engine test set points i. Input to select source 1 or source 2 as the preferred source j. Input to initiate a remote load test k. Input to indicate the bypass transfer switch is closed on a source l. Input to bypass time delays m. Input to receive engine start signal from a master controller in a three source application. 6. The controller shall include 4 user configurable outputs rated for 10-Amp at 250-Vac and 10- Amp at 30-Vdc. Each input can be user configured to one of the following features: a. Source 1 connected b. Source 2 connected c. ATS in test d. ATS not in automatic mode (Monitor Mode) e. General Alarm indication for failure to transfer, mechanical fault, or electrical fault f. Engine Test Aborted g. Engine cool down in process h. Engine start contact status i. Emergency inhibit on j. Load sequence Output used to signal select loads to disconnect prior to transfer and reconnect seconds after. Loads are reconnected sequentially. k. Selective load shed Output used to shed low priority loads when the load reaches a programmed threshold value. A load shed and load restore set point (measured in kw) are associated with this feature. l. Load bank control Output to disconnect a load bank during an engine run test if a transfer to a source 2 generator is required.

12 m. Pre and/or post transfer signal - A pre and or post transfer time delay output adjustable from seconds. 7. One Form C auxiliary contact to indicate Source 1 position and one Form C contact to indicate source 2 position. The contacts shall be rated for 10-Amp, 1/3-Horsepower at 250-Vac and 10- Amp at 30-Vdc. 8. One Form C contact for Source 1 Available. The contacts shall be rated for 10-Amp, 1/3- Horsepower at 250-Vac and 10-Amp at 30-Vdc. 9. One Form C contact for Source 2 Available. The contacts shall be rated for 10-Amp, 1/3- Horsepower at 250-Vac and 10-Amp at 30-Vdc. 10. Data Logging: a. Historical Data Storage to include: 1. Engine Run Time 2. Source 1 Available time 3. Source 2 Available time 4. Source 1 Connected time 5. Source 2 Connected time 6. Source 1 Engine Run Time 7. Source 2 Engine Run Time 8. Load Energized Time 9. Number of Transfers b. Event Summary shall include up to 100 date and time stamped events. All metered values are logged for each event. Event summaries include: 1. Transfer events 2. Alarms 3. Changes to the set points 4. Changes to the time/date 5. Resetting a historical counter 6. Engine Run test c. Event Details shall include up to 350 date and time stamped events. All metered values are logged for each event. Event details include detailed sequence of operations of a transfer event. d. Event recording shall capture 4 seconds of metered data, stored every 20 msec for certain events. The data is captured 2 seconds before and 2 seconds after the event. Oscillographic data for 10 events is stored and may be downloaded over USB. Events Include: 1. Source unavailability actions that initiate a transfer sequence (Undervoltage, Overvoltage, etc.) 2. Successful transfers (at the point of breaker/contactor closure)\ 3. Unsuccessful transfers (at the point of breaker/contactor failure to close or open) N. Optional accessories

13 1. Non-Automatic Control: Provide a 2-Position Selector Switch, maintained contact, marked: Automatic and Non-Automatic. The transfer switch shall be transferred by actuating a two position maintained selector switch labeled Source 1 and Source 2. A 30mm pilot light shall be provided labeled Not in Automatic 2. Non-Automatic Control: Provide a 3-Position Selector Switch, maintained contact, marked: Automatic and Non-Automatic. The transfer switch shall be transferred by actuating a three position maintained selector switch labeled Source 1, Off and Source 2. A 30mm pilot light shall be provided labeled Not in Automatic. 3. Manual Retransfer Control: The ATS shall remain connected to the emergency source after the normal source becomes available until a momentary pushbutton contact closure signal is received to initiate the retransfer. Should a failure of the emergency source occur while waiting for the manual return, the re-transfer proceeds automatically. 4. Device panel mounted Preferred Source Selector switch 5. Device panel mounted Source 2 Inhibit keyed switch with 30mm white pilot light indicating inhibit status. 6. Device panel mounted selector switch to initiate a load transfer to source 2. This operation shall be failsafe to initiate an automatic retransfer upon loss of source 2 power. 7. Communications Interface to be [Modbus RTU] [Modbus TCP/IP] 8. Where indicated on the drawings, provide [50KA] [100KA] surge protection device on source 1 9. Space heater with thermostat rated for [100 watts] [400 watts] 10. Integrated Load Metering The controller shall include integral load metering. When included, metered values shall be viewable from the controller LCD display. a. Source 1 Voltages (3Ф) b. Source 2 Voltages (3Ф) c. Load Voltages (3Ф) d. Source 1 Frequency e. Load Frequency f. Load Currents (3Ф) g. Load kw h. Load kvar i. Load kva j. pf 11. Remote Annunciator and Controller: a. Monitor up to eight (8) automatic transfer switches 1. 7 touchscreen color display 2. Mimic bus display for each transfer switch with indication of source availability, based on controller pickup and dropout settings, and switch position. 3. Each mimic bus display shall be marked with the designation of the transfer switch monitored. 4. Indication of switch in test mode. 5. Indication of failure of digital communication link Note to Spec. Writer - Optional

14 b. Control Functions 1. Control functions shall be password protected and shall include: a. Initiate engine test b. Initiate a failsafe transfer to source 2 c. Initiate manual retransfer c. Indicating Lights: Grouped for each transfer switch monitored. d. Label each group, indicating transfer switch it monitors, location of switch, and identity of load it serves. e. Mounting: Flush, modular, steel cabinet, unless otherwise indicated. f. Communications capability to be compatible with ATS controller. 12. Three Source Transfer Control The ATC-900 controller shall include a Master/Slave functionality for use in configuring two independent transfer switches as a three source transfer system. a. Sequence of operations - In the event of a source 1 power failure the Master ATS controller shall send an engine start signal to the slave input on the Slave controller. The slave controller shall send an engine start signal to both generators. If a preferred generator is selected, the Slave controller will count down through the time delay for engine failure and remain on the preferred generator if it is available. If the preferred generator is not available at that time, the Slave ATS will transfer to the non-preferred generator. If none-preferred is selected, the Slave ATS will transfer to the first available generator. The unused generator will be shut down as soon as the Slave ATS is connected to a good source CUSTOMER METERING {OPTION 18} Where indicated on the drawings, provide customer metering to include the following: Note to Spec. Writer: Select devices as required for item 2.07 B. Refer to section for detailed specification for metering as follows: Power Xpert Series IQ Analyzer 6000 Series IQ DP-4000 Series IQ 130/140/150 IQ 250/ SURGE PROTECTION DEVICES A. Where indicated on the drawings, provide a surge protection device 1. [CVX 50KA Surge Device Source 1 {Option 51D1}] [CVX 100KA Surge Device Source 1 {Option 51F1}] B. Where indicated on the drawings, provide a separate customer metering compartment with front hinged door and include the following: Note to Spec. Writer Select one

15 1. Current transformers where shown on the drawings or elsewhere specified shall be wired to shorting-type terminal blocks. 2. [Potential transformers including primary and secondary fuses with disconnecting means] [Fused potential taps as the potential source] for metering as shown on the drawings WIRING/TERMINATIONS A. Terminal blocks shall conform to NEMA ICS 4. Terminal blocks for remote connections shall be arranged to facilitate the entrance of external conductors from the top or bottom of the enclosure. The main transfer switch terminals shall be suitable for the termination of conductors shown on the plans ENCLOSURE A. Each transfer switch shall have an EEMAC1 general purpose enclosure unless otherwise noted. Enclosure options include EEMAC 1, 12, 3R, 4, and 4X FINISH A. The enclosure shall be painted with the manufacturer s standard painting procedures to ensure suitability for environmental conditions as referenced in the plans. EEMAC 1, 12, 3R and 4 enclosures shall be painted with the manufacturer s standard ASA 61 gray paint. EEMAC 4X shall non-painted stainless steel construction. PART 3 OPERATION 3.01 TRANSFER SWITCH OPERATION A. The following Voltage and Frequency sensing shall be supplied: 1. The voltage of each phase of the normal source shall be monitored, with dropout adjustable from 50% to 90% of nominal and pickup adjustable from [dropout setting +2%] to 100% of nominal 2. The voltage of each phase of the emergency source shall be monitored, with dropout adjustable from 50% to 90% of nominal and pickup adjustable from [dropout setting +2%] to 100% of nominal 3. The frequency of the emergency source shall be monitored, with dropout adjustable from 90% to 100% of nominal and pickup adjustable from [dropout setting +1 Hz] to 110% of nominal. 4. Voltage measurement accuracy shall be +/-2% of nominal input voltage and frequency measurement accuracy shall be +/-0.1 Hz. B. The following Time Delay features shall be supplied: 1. A time delay shall be provided to override a momentary power outage or voltage fluctuation, adjustable from 0 to 120 seconds. 2. A time delay shall be provided on transfer to emergency, adjustable from 0 to 30 minutes. Note to Spec. Writer Select one

16 3. A time delay shall be provided on retransfer from emergency to normal, adjustable from 0 to 30 minutes. This time delay shall be bypassed if emergency source fails and normal source is available. 4. A time delay shall be provided after retransfer that allows the generator to run unloaded prior to shutdown, adjustable from 0 to 30 minutes. 5. All delays shall be field adjustable from the microprocessor-based controller without the use of special tools ACCESSORIES A. Selectable 3-phase(φ) or 1-phase(φ) failure protection on normal supply. B. Selectable 3-phase(φ) or 1-phase(φ) failure protection on emergency supply. C. Pilot light indication of transfer switch position and availability of normal emergency voltage sources. D. Transfer switch position indicator E. A momentary test selector switch or pushbutton shall be provided to simulate normal source failure. F. Engine start contacts. G. Transfer motor disconnect intended for manual operation OPTIONAL ACCESSORIES A. Auxiliary relay contacts shall be provided that are energized when power is available on the normal source. B. Auxiliary relay contacts shall be provided that are energized when power is available on the emergency source. C. Exerciser: Provide an engine generator exercising timer that is selectable for either load or noload transfer. D. Pre-Transfer Signal: Provide a pre-transfer signal adjustable from seconds for up to 10 devices. E. Preferred Source Selector: Transfer switch logic shall have the ability for the user to define a preferred source, selectable between Source 1, Source 2, or None. F. Load Sequencing: Transfer switch logic shall allow the ability to perform load sequencing of 0-10 devices. PART 4 EXECUTION 4.01 EXAMINATION 4.02 FACTORY TESTING A. The following standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of CSA and EEMAC standards. 1. Insulation check to ensure the integrity of insulation and continuity of the entire system

17 2. Visual inspection to ensure that the switch matches the specification requirements and to verify that the fit and finish meet quality standards 3. Mechanical tests to verify that the switch s power sections are free of mechanical hindrances 4. Electrical tests to verify the complete electrical operation of the switch and to set up time delays and voltage sensing settings of the logic B. The manufacturer shall provide three (3) certified copies of factory test reports INSTALLATION A. The contractor shall install all equipment per the manufacturer s recommendations and the contract drawings. B. All necessary hardware to secure the assembly in place shall be provided by the contractor. C. The equipment shall be installed and checked in accordance with the manufacturer s recommendations FIELD QUALITY CONTROL A. Provide the services of a qualified factory-trained manufacturer s representative to assist the contractor in installation and start-up of the equipment specified under this section for a period of working days. The manufacturer s representative shall provide technical direction and assistance to the contractor in general assembly of the equipment, connections and adjustments, and testing of the assembly and components contained therein. B. The contractor shall provide three (3) copies of the manufacturer s field start-up MANUFACTURER S CERTIFICATION A. A qualified factory-trained manufacturer s representative shall certify in writing that the equipment has been installed, adjusted and tested in accordance with the manufacturer s recommendations. B. The Contractor shall provide three (3) copies of the manufacturer s representative s certification TRAINING A. The contractor shall provide a training session for up to five (5) owner s representatives for normal workdays at a jobsite location determined by the owner. B. The training session shall be conducted by a manufacturer s qualified representative. The training program shall consist of the instruction on the operation of the assembly, circuit breakers and major components within the assembly FIELD SERVICE ORGANIZATION A. The manufacturer of the ATS shall also have a national service organization that is available throughout Canada and is available on a call 24 hours a day, 365 days a year. B. Equipment warranty shall be extended to two years from date of installation when service representatives employed by the equipment manufacturer perform installation. Note to Spec. Writer Insert data in blanks Note to Spec. Writer Insert data in blanks

SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER

SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER ATS MOLDED CASE WITH ATC 900 CONTROLLER PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install the low voltage automatic transfer switches having the ratings, features/accessories and enclosures as specified

More information

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION ( ) LIGHTING CONTROL PANELBOARD (26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

SUGGESTED SPECIFICATION CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH WITH LOAD BREAK BYPASS/ISOLATION OPERATION WITH RPTCS MICROPROCESSOR CONTROL

SUGGESTED SPECIFICATION CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH WITH LOAD BREAK BYPASS/ISOLATION OPERATION WITH RPTCS MICROPROCESSOR CONTROL TYPE RTS30ABLC COMBINATION AUTOMATIC TRANSFER WITH BYPASS ISOLATION SWITCH RPTCS CONTROL EFFECTIVE 1/19/2011 SUGGESTED SPECIFICATION CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH WITH LOAD BREAK BYPASS/ISOLATION

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Current Voltage, Frequency Molded case (MCCB) Insulated Case (ICCB) 200

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Molded case (MCCB) Insulated Case (ICCB) Current Voltage, Frequency 200

More information

SUGGESTED SPECIFICATION SINGLE OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL

SUGGESTED SPECIFICATION SINGLE OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL TYPE RTS30ATA AUTOMATIC TRANSFER SWITCH RPTCS CONTROL EFFECTIVE 1/19/2011 SUGGESTED SPECIFICATION SINGLE OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL PART 1 - GENERAL

More information

SUGGESTED SPECIFICATION For Series 300 Automatic Transfer Switches (3ATS)

SUGGESTED SPECIFICATION For Series 300 Automatic Transfer Switches (3ATS) SUGGESTED SPECIFICATION For Series 300 Automatic Transfer Switches (3ATS) PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (3ATS) with number of poles, amperage, voltage, and withstand

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

Transfer Switches 5.1 Transfer Switch Equipment Product Selection Guide... Product Description... Application Description...

Transfer Switches 5.1 Transfer Switch Equipment Product Selection Guide... Product Description... Application Description... .1 Transfer Switch Equipment Product Selection Guide.................................... Product Description....................................... Application Description......................................2

More information

4000 SERIES Power Transfer Switches Product Features

4000 SERIES Power Transfer Switches Product Features The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. 4000 SERIES Power Transfer Switches Product Features Conventional two-position transfer

More information

Transfer Switches Magnum-Based Designs

Transfer Switches Magnum-Based Designs Transfer Switches -Based Designs Floor-Standing Transfer Switches General Description September 2011 Sheet 25046 Isolation Transfer Switch Isolation Transfer Switch General Description A bypass isolation

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Transfer Switch rated 1000 amperes in Type 1 enclosure. Closed Transition Transfer Switching ASCO Automatic Closed Transition

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

Transfer Switches Magnum-Based Designs

Transfer Switches Magnum-Based Designs -Based Designs Floor-Standing Transfer Switches General Description Sheet 25046 Isolation Transfer Switch Isolation Transfer Switch General Description A bypass isolation switch uses loadbreak isolation

More information

Model: KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model: KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model: KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Molded case (MCCB) Insulated Case (ICCB) Current Voltage, Frequency 200

More information

Transfer Switches Contactor-Based Designs

Transfer Switches Contactor-Based Designs September 2011 Sheet 215 Transfer es -Based Designs Transfer es, 100 1200A, Dual Drawout General Description Transfer es, 100 1200A, Dual Drawout Transfer General Description A bypass isolation transfer

More information

Series TS Amp. Automatic Transfer Switches

Series TS Amp. Automatic Transfer Switches Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:

More information

STANDARD SUBMITTAL PACKAGE

STANDARD SUBMITTAL PACKAGE STANDARD SUBMITTAL PACKAGE SBP1000-51( ) FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for

More information

ASCO Power Transfer Load Centers. Power Switching & Controls for Business-Critical Continuity

ASCO Power Transfer Load Centers. Power Switching & Controls for Business-Critical Continuity ASCO Power Transfer Load Centers Power Switching & Controls for Business-Critical Continuity ASCO, the world leader in power switching & controls Streamline with an Integrated System ASCO Power Transfer

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) SECTION 26 29 23 VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) PART 1 -GENERAL 1.1 SYSTEM DESCRIPTION A. Definitions: The Variable Speed AC Motor Drive (hereafter referred to as "VFD") shall be designed to

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Transfer Switches Magnum-Based Designs

Transfer Switches Magnum-Based Designs September 2011 Sheet 250 -Based Designs Floor-Standing General Description Floor-Standing Floor-Standing Transfer Switch General Description Taylor s transfer switches are designed for a variety of standby

More information

ASCO SERIES 300 Service Entrance Power Transfer Switch

ASCO SERIES 300 Service Entrance Power Transfer Switch ASCO SERIES 300 Service Entrance Power Transfer Switch The ASCO Service Entrance Power Transfer Switch combines automatic power switching with the necessary disconnecting, grounding, and bonding required

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches

Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches RTS SERIES RTS Series Medium-Voltage Circuit Breaker-Type Automatic Transfer Circuit breaker medium-voltage

More information

O & M Manual for the Generac ATC-300+ Automatic Transfer Switch Controller

O & M Manual for the Generac ATC-300+ Automatic Transfer Switch Controller O & M Manual for the Generac ATC-300+ Automatic Instruction Booklet Description Page Introduction................................ 2 Hardware Description.......................... 7 Status Monitoring and

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

Cutler-Hammer. Westinghouse Transfer Switch Equipment. IQ Transfer

Cutler-Hammer. Westinghouse Transfer Switch Equipment. IQ Transfer Westinghouse Transfer Switch Equipment IQ Transfer Setting a new standard with the most advanced microprocessor-based transfer switch logic available. It s programmable for superior reliability and versatile

More information

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP750-51(B) FTA750 Full Voltage Starting Limited Service Electric Fire Pump Controllers Product Description Description Firetrol

More information

Series 300 POWER TRANSFER SWITCHES MAXIMUM RELIABILITY & EXCELLENT VALUE FEATURES

Series 300 POWER TRANSFER SWITCHES MAXIMUM RELIABILITY & EXCELLENT VALUE FEATURES Series 300 POWER TRANSFER SWITCHES MAXIMUM RELIABILITY & EXCELLENT VALUE With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

Spec Sheet: Zenith ZXS (ZTX) Transfer switch

Spec Sheet: Zenith ZXS (ZTX) Transfer switch Spec Sheet: Zenith ZXS (ZTX) Transfer switch Description: GE Zenith s ZXS (Previously known as ZTX) Series Automatic Transfer Switches are designed for residential and light commercial critical/non-life

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

C. New or replacement products installed in existing facilities shall be consistent with existing equipment. September 2012, rev 00 26 2923 Variable Frequency Controllers PART 1. GENERAL 1.01 Description A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width

More information

GE Digital Energy Power Quality. Zenith ZTG Series. Low-Voltage Automatic Transfer Switches

GE Digital Energy Power Quality. Zenith ZTG Series. Low-Voltage Automatic Transfer Switches GE Digital Energy Power Quality Zenith ZTG Series Low-Voltage Automatic Transfer Switches GE s Zenith ZTG Series switches are built for standard applications requiring the dependability and ease of operation

More information

These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads.

These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads. 1 General 1.1 Summary These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads. 1.2 Standards The PowerHub 2 PDU shall be listed to the applicable

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

This section applies to the design and installation relating to automatic transfer switches (ATS).

This section applies to the design and installation relating to automatic transfer switches (ATS). Design Guide Basis of Design This section applies to the design and installation relating to automatic transfer switches (ATS). Design Criteria Clearly indicate in the drawings and specifications whether

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Product Overview The Series 230 automatic transfer

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

FTA1350 WYE-DELTA CLOSED FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1350 WYE-DELTA CLOSED FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1350 WYE-DELTA CLOSED FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE NOTE: The drawings included herein are for standard controllers. Actual "as built" drawings may differ from those seen here. ASCO

More information

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation SECTION 26 24 16 PANELBOARDS PART 1 -GENERAL 1.1 SUMMARY A. Section includes distribution and branch circuit panelboards, electronic grade branch circuit panelboards, [and load centers]. 1.2 REFERENCES

More information

ASCO SERIES 230 Automatic Transfer Switch

ASCO SERIES 230 Automatic Transfer Switch ASCO SERIES 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Application Product Overview The Series 230

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

Power Series Transfer Switch

Power Series Transfer Switch Service Entrance Rated Power Frame Type losed Transition Power Series Transfer Switch 1000-5000 mps Power Series 1 of 5 utomatic Transfer Switch, 100% Service Entrance Rated 1000 5000, up to 600V, 50/60

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

GE Zenith ZDEC Modular Paralleling Switchgear

GE Zenith ZDEC Modular Paralleling Switchgear GE Zenith ZDEC 2020 Modular Paralleling Switchgear ZDEC 2020 Has the Solution Healthcare and Critical Facilities Demand Generator Paralleling Systems that are Flexible design compatible with multiple brands

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.

More information

Experience, innovation and reliability

Experience, innovation and reliability automatic transfer switches 40 1200A Experience, innovation and reliability Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability

More information

SECTION MOTOR CONTROL CENTERS

SECTION MOTOR CONTROL CENTERS MOTOR CONTROL CENTERS PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the motor control centers as specified herein and as shown on the contract drawings. 1.02 RELATED SECTIONS A.

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16289 to 26 35 00, removed references to other section numbers 10/14/14 Amend text in section B

More information

SECTION METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W)

SECTION METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W) METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W) PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings.

More information

Jockey Pump Controllers

Jockey Pump Controllers BR081001EN Microprocessor Based with Color Touchscreen Product Description ACROSS THE LINE Controllers operate across-the-line. Full voltage is applied to the motor for starting by the use of a single

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95 Part 1 - GENERAL ASEA BROWN BOVERI ABB Industrial Systems Inc. Standard Drives ACH500-06E Effective 6/1/95 Sample Specification for Adjustable Frequency Drives (2 to 400 HP) for Variable Torque Applications

More information

SECTION 16482A MOTOR CONTROL CENTERS LOW VOLTAGE (FREEDOM)

SECTION 16482A MOTOR CONTROL CENTERS LOW VOLTAGE (FREEDOM) PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE A. The Contractor shall furnish and install the motor control centers as specified herein and as shown on the contract drawings. RELATED SECTIONS A. Section 16475

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch Global Headquarters-Florham Park, New Jersey ASCO was founded in 1888, and manufactured the first ATS in 1920, ASCO focuses on the development of ATS, and has become

More information

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration Data Sheet Lighting Relay Panel Overview Leverage the Power of BAS Integration Exterior with Surface Mount Trim The Series UL Listed, Lighting Control Panel provides the capability to control high voltage

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 24 11 This section specifies the furnishing, installation, and connection of the distribution switchboards. 1.2 RELATED WORK: A. Section 13 05 41, SEISMIC RESTRAINT

More information

reliable company...caterpillar

reliable company...caterpillar The markets most reliable technology... from the industryʼs most reliable company...caterpillar Caterpillar switchgear with PowerLynx technology has been designed to integrate hand-inglove with Caterpillar

More information

Power Series Transfer Switch

Power Series Transfer Switch ypass Isolation ontactor Type losed Transition Transfer Switch 100-1200 mps 1 of 5 ypass Isolation Transfer Switch 100 1200, up to 600V, 50/60 Hz 3 or 4 poles NEM 1 or 3R losed Transition UL1008 Listed

More information

SECTION ELECTRICAL CONTROL DEVICES

SECTION ELECTRICAL CONTROL DEVICES ELECTRICAL CONTROL DEVICES PART 1 GENERAL 01 02 03 04 05 SCOPE The Contractor shall furnish and install, where indicated on the drawings, equipment with electrical control devices installed as specified

More information

SECTION SURGE PROTECTIVE DEVICES

SECTION SURGE PROTECTIVE DEVICES SECTION 16289 PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Series 2400 Paralleling Switchgear

Series 2400 Paralleling Switchgear Series 2400 Paralleling Switchgear SERIES 2400 PARALLELING SWITCHGEAR TYPICAL SERIES 2400 MULTIPLE GENERATOR/UTILITY PARALLELING SWITCHGEAR Intelligent, Configurable Switchgear for Distributed Generation,

More information

soft load power transfer solutions for continuous, reliable power

soft load power transfer solutions for continuous, reliable power We Keep Your Power On A S C O P O W E R T E C H N O L O G I E S F L O R H A M P A R K, N E W J E R S E Y 0 7 9 3 2 U S A 8 0 0 9 3 7 A S C O W W W. A S C O. C O M ASIA AUSTRALIA BRAZIL CANADA GERMANY JAPAN

More information

Power Series Transfer Switch

Power Series Transfer Switch Power Frame Type Open and Delayed Transition Power Series Transfer Switch 2000-5000 mps Power Series 1 of 5 utomatic Transfer Switch 2000 5000, up to 600V, 50/60 Hz 3 or 4 poles NEM 1 or 3R Open with Inphase

More information

SECTION VARIABLE FREQUENCY DRIVES

SECTION VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 DESCRIPTION This specification section establishes the requirements for variable frequency motor drives. The associated motor(s) shall be specified separate from the drive and listed

More information

VisoVac padmount fault interrupter

VisoVac padmount fault interrupter Network Protector Catalog Data CA024003EN New Issue VisoVac padmount fault interrupter General The medium voltage padmount vacuum fault interrupter from Eaton delivers economical, reliable and flexible

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Application Product Overview The Series 230 automatic

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Power Meter PowerMonitor 500

Power Meter PowerMonitor 500 ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific

More information

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs .3 Features and Benefits Saves installation time and cost One part number to order; no need to worry that any part has been left out Pick the meter or meters you need as it is designed to fit various Eaton

More information

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Product Data Sheet Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ZEE BIPLANE IECAX480V225A Main Disconnect Panel Bevco Engineering Company, Inc. CONFIDENTIAL

More information

LiteKeeper 4. Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION 1.02 DESCRIPTION OF WORK

LiteKeeper 4. Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION 1.02 DESCRIPTION OF WORK LiteKeeper 4 Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION The work covered in this section is subject to all of the requirements in the General Conditions

More information

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control Key Benefits FM2 FEEDER Protection System Economical and compact feeder protection for low voltage feeders Comprehensive low voltage feeder management system - Integrated feeder protection and process

More information

Jockey Pump Controllers

Jockey Pump Controllers BR081001EN Microprocessor Based with Color Touchscreen Product Description ACROSS THE LINE Controllers operate across-the-line. Full voltage is applied to the motor for starting by the use of a single

More information

APC Symmetra LX. GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System

APC Symmetra LX. GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System APC Symmetra LX GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous duty, singlephase,

More information

SWITCHGEAR. XLM Switchgear

SWITCHGEAR. XLM Switchgear SWITCHEA XLM Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you get greater efficiency, reliability and dependability all

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

The ASCO 7000 Series. Protecting data centers, hospitals, airports, retail stores and other facilities

The ASCO 7000 Series. Protecting data centers, hospitals, airports, retail stores and other facilities Protecting data centers, hospitals, airports, retail stores and other facilities The ASCO 7000 Series Closed-Transition Sof t Load Power Transfer Switch gives you the flexibilit y to: Ensure the level

More information

Power Series Transfer Switch

Power Series Transfer Switch Power Frame Type losed Transition Power Series Transfer Switch 1600-5000 mps Power Series 1 of 5 utomatic Transfer Switch 1600 5000, up to 600V, 50/60 Hz 3 or 4 poles NEM 1 or 3R losed Transition UL1008

More information

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning .1 Industrial and Commercial Surge Protection Introduction Industrial and Commercial Surge Protection SPD Series for Integration into Electrical Distribution Equipment SPD Series for Mounting External

More information

DGC-2000 DIGITAL GENSET CONTROLLER

DGC-2000 DIGITAL GENSET CONTROLLER DGC-2000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-2000) offers an integrated alternative for genset control and monitoring. Control includes engine starting and shutdown

More information