Precision Digital Modbus Register Tables Serial Communication
|
|
- Chester Rice
- 5 years ago
- Views:
Transcription
1 This document describes how to communicate with the Trident Model PD765 and Javelin D Model PD644 meters using the Modbus RTU Serial Communication Protocol. The user should be familiar with Modbus serial communication and the meters. Refer to the meter instruction manuals and the serial communication adapters for setup and wiring instructions. Register Overview : Process Value (PV), Max PV, Min PV in integer and floating point formats, with interspersed relay status for block reading, Initialize, Reset Max & Min display, Alarm & Relay status, Relay acknowledge, Linear/Square Root selection, Remote Process scaling initiation : Input selection, Decimal points, Adjust, Bypass, Cutoff, Filter, Lock, Baud, Parity, Modbus Address, and Byte-to-byte timeout, Display Intensity : Remote Scaling for Process inputs : Relays; Set & Reset points, Turn-on & Turn-off delays, Operating Mode. 40 4: 4-0 ma output; Mode, Filter, Sensor Break, Overrange, Underrange, Maximum allowed, Minimum allowed, Display, Display, Output, Output, Data (ma), Data (bits) : Product ID, Firmware Version, and Manufacturing Serial. Register Name Access Address (hex) (0000) Display Read Only -999 to User Defined Represents the display without the Decimal point setting in (000) Alarm and Relay status Read both, Relays = In Alarm = relay energized Bits 06, Read alarm status and energized/non-energized status of relays. Alarms are read only, so the upper byte is ignored for writes. Writing to a relay is only allowed when the relay is in the meter-disabled (Modbus accessible) mode. When writing, bits through 5 are ignored. Alm = Alarm. Rly = Relay Alm Alm Rly Rly (000) Maximum Display Read -999 to User defined 06 Represents the Maximum display, excluding the decimal point, since last power up or Max Value reset. Decimal point setting in 400. Writing any will reset the Maximum display to the present display (0003) Minimum Display Read -999 to User defined 06 Represents the Minimum display, excluding the decimal point, since last power up or Min Value reset. Decimal point setting in 400. Writing any will reset the Minimum display to the present display ( ) Display Read Only -999 to User defined Floating point Represents the display including the Accessing or by itself will return 0xFFFF. PRECISION DIGITAL CORPORATION 89 October Hill Road Holliston MA 0746 USA Tel (508) Fax (508)
2 Register Name Access Address (hex) (0006) Alarm and Relay status Read both, Relays = In Alarm = relay energized Bits 06, Mirror of ( ) Maximum Display Read Only -999 to User defined Floating point Represents the Maximum display, including the decimal point, since last power up or Max Value reset. Accessing or by itself will return 0xFFFF ( A) Minimum Display Read Only -999 to User Defined Floating point Represents the Minimum display, including the decimal point, since last power up or Min Value reset. Accessing 4000 or 400 by itself will return 0xFFFF. 400 (000B) Linear/Square Root 0xFF00 = Sq. rt 0x0000 = Linear Bit 06, Determines process input function. 0x0000 for linear function. 0xFF00 for square root. Any other write is ignored and has no effect (000C) Alarm Acknowledge Only Not applicable Bits 06 Clear Relay n alarm condition. Set bit equal to to acknowledge. Only has effect on relays programmed to allow manual acknowledging. Alm = Alarm; X = don t care (000D) Initialize Meter Only 0xFF00 to initialize. Bit 06 X X X X X X Alm Alm X X X X X X X X 0xFF00 to reinitialize the meter. Writing any other data has no effect (000E) Remote Scale ma Only 0xFF00 to execute remote scaling. Bit 06 Used to remote scale the ma input. Writing any other data has no effect (000F) Remote Scale Volts Only 0xFF00 to execute remote scaling. Bit 06 Used to remote scale the Volts input. Writing any other data has no effect (0064) Input selection Not applicable Word; bit flags See Table, page (0065) Active Decimal Point,, 3, or 6 6 = no to 3 = number of digits to right of dp. Mirror of bits 6-4 of 400. Only process decimal points can be written. Writing a non-process dp returns 0xFFFF (0066) Current & Voltage decimal points 0x00CV, where C & V =,, 3, or 6. Word See table. If an out of range is sent for either or both decimal points, no change is made for that. Valid settings are none,,, and 3 decimal places (0067) Adjust -99 to +99 C or F Actually represents -9.9 to Offset is only applied to temperature inputs. If Adjust is greater than C and the temperature units are switched to F, it will be set to 9.9 (lower than -, set to -9.9). Page
3 Register Name Access Address (hex) 4005 (0068) Bypass to 999 Percent of full scale or F Actually represents 0. to If the input steps greater than the bypass, it will be displayed immediately, with no filtering occurring. The number represents percent of full-scale for process inputs and F for temperature inputs. No effect if filter = (0069) Cutoff 0 to 9999 User Defined Represents the cutoff without the Valid only for process inputs (006A) Filter 0, to 99 Unit-less Display filtering. 0 = no filtering. New = old + ((new - old)/filter) (006B) Lock 0x0000 to 0x9999 (Packed BCD) See Note 5, page (006C) Baud 0 to 6 0 = 300, = 600, = 00, 3 = 400, 4 = 4800, 5 = 9600, & 6 = 900. Changes to this register are saved but don t take effect until next meter reset (Modbus command or power-up). Writing out of range data results in a baud rate of (006D) Parity 0 to Word; bit flags 0 =, = Odd, = Even. Changes to this register are saved but don t take effect until next meter reset (Modbus command or power-up). Writing out of range data results in a parity setting of Even (006E) Byte-to-byte timeout 0 to.54 Seconds This is the timeout between bytes of a Modbus frame. Note that a less than the minimum for the present baud rate cannot be saved. Minimums are: 300 baud = 0.06 secs, 600 = = 0.0 and 0.0 for 400 to 900. Changes to this register are saved but don t take effect until next meter reset (Modbus command or power-up). Writing out of range data results in a timeout of.54 seconds. 40 (006F) Modbus Address Read to 47 Changes to this register are saved but don t take effect until next meter reset (Modbus command or power-up). Writing out of range data results in an address of (0070) Display Intensity Read to 8 8 is the brightest level. Writing out of range data results in level brightness (00C8) 0 (00C9) 0 03 (00CA 00CB) 05 (00CC 00CD) Display &, ma -999 to 9999 User Defined Input &, ma -999 to s of μa (-9.99 to 0.00 ma) Floating point Used to remotely scale the ma input. This data represents the display without a Used to remotely scale the ma input. If data sent is out of range, default s of 400 and 000, respectively, will be used instead. This data represents the input points in ma. For example: ma. Page 3
4 Register Name Access Address (hex) (00CE) 07 (00CF) (00D0 00D) 0 (00D 00D3) Display &, Volts Input &, Volts -999 to 9999 User Defined PD644: 0 to 3000 PD765: -999 to 000 PD644: Tenths of Volts (000.0 to V) Floating point PD765: 0 s of mv (-9.99 to 0.00 V) Used to remotely scale the Volts input. If data sent is out of range, default s of 0 and 000, respectively, will be used instead. This data represents the display without a Used to remotely scale the Volts input. If data sent is out of range, default s of 0 and 000, respectively, will be used instead. This data represents the input points in volts. For example: V (0C to 030) Relay : Set point Reset point Turn-on delay Turn-off delay Mode -999 to to to 99 0 to 99 Bits 4,,, 0 User Defined User Defined Seconds Seconds Word: bits Set and Reset points represent the display without the See Table 3, page 8, for operating modes and bit assignments (03 to 035) Relay : Set point Reset point Turn-on delay Turn-off delay Mode -999 to to to 99 0 to 99 Bits 4,,, 0 User Defined User Defined Seconds Seconds Word: bits Set and Reset points represent the display without the See Table 3, page 8, for operating modes and bit assignments (090) 40 (09) 40 (09) 403 (093) 4 (094) Mode Filter Sensor Break y000 0yyy 0, to 9 0 to s of μa Overrange 0 to s of μa Underrange 0 to s of μa Selects output option and where the data source for the 4-0 ma output. See Table 4, page 9. This feature is not available through manual programming. 4-0 ma filtering: 0 = no filtering. Writing out of range data results in a of 0. New = old + ((new - old)/filter) Due to hardware variations, actual output range is designed to be at least.00 to 3.00 ma. Writing out of range data results in a of 3.00 ma. This feature is not available through manual programming. Due to hardware variations, actual output range is designed to be at least.00 to 3.00 ma. Writing out of range data results in a of.00 ma. This feature is not available through manual programming. Due to hardware variations, actual output range is designed to be at least.00 to 3.00 ma. Writing out of range data results in a of 3.00 ma. Page 4
5 Register Name Access Address (hex) (095) Maximum allowed 0 to s of μa This feature is not available through manual programming. Due to hardware variations, actual output range is designed to be at least.00 to 3.00 ma. Writing out of range data results in a of 3.00 ma (096) Minimum allowed 0 to s of μa This feature is not available through manual programming. Due to hardware variations, actual output range is designed to be at least.00 to 3.00 ma. Writing out of range data results in a of 0.00 ma (097) Display Value -999 to User Defined 6, 4-0mA out scaling. Represents the display without the (098) Display Value -999 to User Defined 6, 4-0mA out scaling. Represents the display without the (099) Output 0 to s of μa 4-0mA out scaling. Represents the ma output at Display without Writing out of range data results in a of 3.99 ma (09A) 4 (09B) Output Data in ma or Data in bits 0 to s of μa 0 to 399 or 0 to s of μa (00.00 to 3.99 ma) or DAC bits 4-0mA out scaling. Represents the ma output at Display without Writing out of range data results in a of 3.99 ma. If 4-0mA out mode is set to Serial Comm., ma (0x83) this register is in 0 s of μa. Due to hardware variations, the actual output range is at least.00 to 3.00 ma. Writing out of range data results in a of 3.99 ma. If 4-0mA out mode is set to Serial Comm., bits (0x84), this register is in DAC bits. See Table 4, page (38C 38F) ( ) (394 39B) Product Identifier Read Only Not applicable Firmware Version Read Only Not applicable Mfg. Serial Read Only Not applicable ASCII characters ASCII characters ASCII characters 8 characters indicating the product firmware number 8 characters indicating the firmware version number 6 (max) characters indicating the manufacturing serial number information. Page 5
6 Notes Note. The Register numbers and addresses follow the Modbus format: 3xxxx are for Input Registers and are read-only. 4xxxx are for Holding Registers and are read/write. Although there are no specific 3x Registers, all 4x Registers are mirrored into 3x register space, and are therefore capable of being read by Modbus function (Read Input Registers). All data addresses in Modbus messages are referenced to zero (0), while Register addresses are referenced to one (). For example, Register 4000 is sent in the Modbus message as 0x0063 (00- = hex). If two addresses are shown separated by a, they form a register pair to make the parameter into a 4-byte (3 bit). Note. Range: Writing a that is outside the parameters range will force it to be limited to the closest within the range. For example, if the range is -.99 to +.99 and the sent is 3., the used is.99. Likewise for the lower side of the range. Exceptions are noted in the comments. Note 3. Data Types: Data format is highest byte first. Word = 6 bit = to 3767 Long = -,47,483,648 to,47,483,647 Float = IEEE floating point format, 4 bytes Decimal point setting in 400. These s represent the number without regard to the The decimal point setting can be found in Holding Register 400. For example, if the number.34 is displayed, a read of 4000 will return 34 (0xD). Register 400 will contain (0x000) to indicate a decimal point setting of two places to the right of the Floating point versions of these numbers, with the decimal point included, are also available. Examples (register s are shown in hexadecimal): Process Registers Register 4000 Register 400 displayed D F9D F3B6.34 D A4 3.4 D 000 4F6 CCCD -3.4 FBE 000 CF6 CCCD Note 4. Remote scaling procedure: a. the desired s for the display, Display &. b. the desired s for the input, Input &, for ma or volts. Note that the s written to the PD765 are (ma * 00) or (volts * 00) because of the meter s input specifications (4 digit, 0.00 ma and 0.00 volt input ranges) and s written to the PD644 are (volts * 0) because of the meter s input specifications (4 digit, volt input range). c. to the remote scaling register for either ma or volts. Warning! The scaling process takes the input s in ma or volts and converts them to A/D counts. Therefore, do NOT execute a remote scaling register write without first writing the display and input registers. In a similar vein, don t write to the ma (volts) registers and then execute a remote scale command for the volts (ma) input. Note 5. A read of the Lock register will return 0x0000 if the meter is unlocked, otherwise it will return 0xFFFF to indicate a locked meter. unlock, the correct lock number must be written, which will then clear the lock number to 0x0000. If the wrong lock number is written, the reply will return 0xFFFF. If the correct lock number is written, the reply will be 0x0000. An unlocked meter can be locked by writing any non-zero, but the must be in BCD (i.e. only nybbles between 0 and 9. If a nybble between A and F is sent, no change to lock status will occur and the return will be 0xFF00). Note 6. Modbus is a Registered Trademark of Schneider Automation Inc. Page 6
7 Tables Table. Input configuration Temperature sensor type and units are only used when temperature is input selected. Decimal point is automatically set for PD765, if temperature input is selected. Invalid selections will result in default settings (shown by the asterisks). Defaults are based on the input selected: for example, if RTD is selected, thermocouple type selection is not allowed and decimal point is forced to none. Bit(s) 5 4, 3,, 0, 9, 8 7, 6, 5, 4, 3,,, 0 F or C Active decimal point setting Temperature sensor type Input selected 0 C PD765 0x0000 J * PD765 F 0x x000 K 0x0000 Volts * 0x * 0x000 T 0x00 ma 0x x0300 T, 0. 0x00 RTD 0x x00 E 0x003 TC 0x0500 0x Ω RTD * α 00 Ω RTD α * Default settings for invalid selections Page 7
8 Table. Decimal Point Selections for PD644 and PD765 Decimal Point for PD644 Bit(s) x000 Decimal Point Decimal Point Selections for PD644 and PD765 0x 3.4 0x.34 0x3.34 Decimal Point for PD765 Bit(s) x Decimal Point for ma Decimal Point for Volts The relationship between these decimal point settings and the one found in 400 (and mirrored in 400) is that the decimal point setting in 400 is the active (presently displayed) decimal point, and the settings found in 4003 are the settings for the ma and Volts inputs. If the ma input is selected, the decimal point setting in bits 4 to of 400 will be the same as the one in bits 7 to 4 of If the voltage input is selected, the decimal point setting in bits 4 to of 400 will be the same as the one in bits 3 to 0 of If a temperature input is selected, the settings in 4003 may or may not be the same as the active setting (in 400). There is no storage for the decimal point settings for the RTD or thermocouple inputs because these are fixed. Table 3. Relay Configuration Bit(s) Normal/ Fail-Safe 0 Operation 0 Normal 0 Automatic reset Fail-Safe Auto & Manual reset Latching 3 Latching with Clear 4 Pump Alternation 5 Unused 6 Unused 7 Off (Disabled) (Modbus accessible) Page 8
9 Table ma Output Modes Bit(s) Output Option ma Data Source 0 PD644 0 Display No 4-0 ma 4-0 ma installed PD Max Display Min Display Serial Comm., ma Serial Comm., bits The data for the 4-0 ma output is the display (process). The data for the 4-0 ma output is the Maximum display. The data for the 4-0 ma output is the Minimum display. The data for the 4-0 ma output is register 4. The data for the 4-0 ma output is register 4. 0 Relays 5 Unused Table ma 6 Unused Available Register Table This table shows available registers versus firmware versions for various Precision Digital products. PD765 PD644 Version 3.xxx Version.xxx 4000 to to to to to to to to to to 4 40 to 40 4 to to to Unused Disclaimer The information contained in this document is subject to change without notice. Precision Digital makes no representations or warranties with respect to the contents hereof, and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose. LIMModbus_A.doc 06/09
PRECISION DIGITAL CORPORATION
PRECISION DIGITAL CORPORATION Serial Communication Protocol This document describes how to communicate with the Trident Model PD765, Javelin T Model PD740, and Javelin D Model PD644 meters using the Precision
More informationPD765 TRIDENT. Trident Series Process & Temperature Meters.
PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) Type 4X, NEMA 4X, IP65 Front 1/8 DIN Shallow
More information12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)
4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type
More informationPD765 TRIDENT. Trident Series Process & Temperature Meters.
PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56" (14.2 mm) or 1.20" (30.5 mm) Linear or Square Root with Low-Flow Cutoff
More informationTrident and Trident X2 Digital Process and Temperature Panel Meter
Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products
More informationHigh Voltage DC Meter
High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications
More information4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM100(1402)
4511 MODBUS RTU Configuration Manual 4131 Universal trip amplifier 4131MCM100(1402) 4131 CONTENTS Introduction... 3 Modbus basics... 3 Modbus RTU... 3 Supported Function Codes... 3 Modbus Parameters and
More informationUsing the MODBUS Protocol with Athena Series C (1ZC, 16C, 18C, and 25C) Controllers
Using the MODBUS Protocol with Athena Series C (1ZC, 16C, 18C, and 25C) Controllers Athena and Multi-Comm are trademarks of Athena Controls, Inc. MODBUS is a trademark of AEG Schneider Automation, Inc.
More informationProcess & Temperature Digital Panel Meter
Process & Temperature Digital Panel Meter TRIDENT PD765 4-20 ma, ± 10 V, TC & RTD Inputs NEMA 4X, IP65 Front Shallow Depth Case 3.6" Behind Panel Universal Power Supply 85-265 VAC Two Relays Option with
More information4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM100(1402)
4511 MODBUS RTU Configuration Manual 4114 Universal transmitter 4114MCM100(1402) 4114 CONTENTS Introduction... 3 Modbus basics... 3 Modbus RTU... 3 Supported Function Codes... 3 Modbus Parameters and factory
More informationH3 Series. Nanmac Corporation. Dual-Line 6-Digit Temperature Meter.
H3 Series Dual-Line 6-Digit Temperature Meter Temperature J, K, T, E, R, S, B, N, C Thermocouples 100 or 1000 Ω Platinum, 10 Ω Copper, 120 Ω Nickel RTDs 1 or 0.1 Resolution Averages up to 10 RTD Sensors
More informationHIGH-VOLTAGE DC METER
HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications
More information4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM101(1445) For 4511 devices from ser. no:
4511 MODBUS RTU Configuration Manual 4131 Universal trip amplifier 4131MCM101(1445) For 4511 devices from ser. no: 141590001 4131 CONTENTS Introduction... 1 Modbus basics... 1 Modbus RTU... 1 4511 Supported
More information4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4116MCM101(1445) For 4511 devices from ser. no:
4511 MODBUS RTU Configuration Manual 4116 Universal transmitter 4116MCM101(1445) For 4511 devices from ser. no: 141590001 4116 CONTENTS Introduction... 1 Modbus basics... 1 Modbus RTU... 1 4511 Supported
More informationChapter. Modbus. In This Chapter...
Modbus Communication Chapter 7 In This Chapter... Modbus Protocol....7 2 Registers....7 2 Connection with the DirectLOGIC PLC....7 8 Connection with the C-more and C-more Micro HMI panels....7 10 Modbus
More information4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM101(1445) For 4511 devices from ser. no:
4511 MODBUS RTU Configuration Manual 4114 Universal transmitter 4114MCM101(1445) For 4511 devices from ser. no: 141590001 4114 CONTENTS Introduction... 3 Modbus basics...3 Modbus RTU...3 4511 Supported
More informationPD Helios Dual-Line 6-Digit Temperature Meter. Actual Size Digit
PD2-7000 Helios Dual-Line 6-Digit Temperature Meter Actual Size Digit Temperature Large 1.80" Digits Dual-Line 6-Digit Display Readable from up to 100 Feet (30 Meters) Away Superluminous Sunlight Readable
More informationPD7000. PROVU Dual-Line 6-Digit Temperature Meter SERIES.
PD7000 PROVU Dual-Line 6-Digit Temperature Meter PR VU SERIES Temperature J, K, T, E, R, S, B, N, C Thermocouples 00 or 000 Ω Platinum, 0 Ω Copper, 0 Ω Nickel RTDs or 0. Resolution Averages up to 0 RTD
More informationTrident & Trident X2 PD765
Trident & Trident X2 PD765 Quick Start Guide Thank you for purchasing the Trident PD765 process meter! This quick start guide will briefly describe some of the common setup procedures for this meter. This
More informationDUAL-LINE TEMPERATURE METER
DUAL-LINE TEMPERATURE METER PROPLUS YPP7000 J, K, T, E, R, S, B, N, C Thermocouples 100 or 1000 Ω Platinum, 10 Ω Copper, 120 Ω Nickel RTDs 1 or 0.1 Resolution Averages up to 10 RTD Sensors Automatic Cold
More informationdual-line 6-dIGIt process MeteR
dual-line 6-dIGIt process MeteR ProVu Se r i e S provu Model pd6000 0-20 ma, 4-20 ma, 0-5 V, 1-5 V, and ±10 V Inputs NEMA 4X, IP65 Front Universal 85-265 VAC or 12/24 VDC Input Power Large Dual-Line 6-Digit
More informationSnooper Model PD865 Modbus Serial Input Instruction Manual
Snooper Model PD865 Modbus Serial Input Modbus RTU Master, Slave, or Snooper Mode 6-Digit Display, 0.56" (14 mm) High, Red LEDs, Sunlight Readable Linear, Square Root, or Programmable Exponent 16-Point
More informationProtocol VIT5. Communications RS485. Version 1.0. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.
4.6.5. 0. 0. V 0. I. 2.0. 0. C 0. I. 2.0. 0. C 0. I. 2.0. 0. C 4.6.5. 0. 0. V 4.6.5. 0. 0. V 0. I. 2.0. 0. C 4.6.5. 0. 0. V 4.6.5. 0. 0. V VIT5 0. I. 2.0. 0. C Version 1.0 RS485 4.6.5. 0. 0. V Communications
More informationInstruction Manual July sitrans RD200
Instruction Manual July 2007 sitrans RD200 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.
More informationR1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)
Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE
More informationPAXDP Modbus Register Table REVISED 12/03/12 LP0916A
PAXDP Modbus Register Table REVISED 12/03/12 LP0916A 1 For Input Registers, replace the 4xxxx with a 3xxxx in the below register address. The 3xxxx are a mirror of the 4xxxx Holding Registers. 2 An attempt
More informationThis command can be used for reading the current value of one or several input channels, according to the table below.
RUA ÁLVARO CHAVES, 155 PORTO ALEGRE RS BRASIL 90220-040 PHONE: (51) 3323 3600 FAX: (51) 3323 3644 info@novus.com.brinfo@ novus.com.br COMMUNICATION MANUAL INTRODUCTION The DigiRail-2A is provided with
More informationModbus Protocol For FTS/FTM 3x&8x
[ 公司地址 ] Modbus Protocol For FTS/FTM 3x&8x V3.0 Introduction This document describes the protocol detail of Modbus for FTSXX Hardware interface - The interface on the sensor is RS-485. - Hardware named
More informationMODBUS EXPANSION CARD
2100 MODBUS EXPANSION CARD MAP v2.1 FOR HARDWARE v2.0 ONLY FOR FIRMWARE v2.0, v4.0, v4.1, v4.3 PF2100 MODBUS EXPANSION CARD MAP v2.1 PROFIRE ENERGY INC. FIRMWARE VERSION HISTORY FIRMWARE VERSION HISTORY
More informationTRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement
TRACKER 220 SERIES Digital Panel Indicators A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input Analogue Output
More informationMaster-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL (Rev. 3.1)
Master-Touch and ValuMass Modbus Communications Master-Touch and ValuMass flowmeters are shipped with the RS232 communications protocol as the factory default. Prior to connecting a flowmeter to a RS485
More informationIntech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.
Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-A8VI Installation Guide. The 2300 series stations are designed to
More informationEMDX3 Multifunction meter Cat No ModbusTable LGR EN v1.01.xls
GENERAL MODBUS TABLE ORGANIZATION Starting of the Starting of the Group s Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 36096 8D00
More informationPRECISION DIGITAL CORPORATION Since 1974 Dual-Line Large Display
Helios PRECISION DIGITAL CORPORATION Since 1974 Dual-Line Large Display Readable from up to 100 Feet (30 Meters) Away Superluminous Sunlight Readable Display Large 1.80" (46 mm) Digits Six Full Digits
More informationPeakTech Prüf- und Messtechnik
PeakTech 2025 Communication protocol Connection settings: Supported: Vendor ID: Product ID: Mode: Frame size: Comments: Yes USB 0x2571 0x4100 RAW HID 8 bytes Dependent on USB implementation you may receive
More informationModel IR4000M. HART Field Device Specification Multi-Point Monitor. Instruction Manual 07-08
Model IR4000M HART Field Device Specification Multi-Point Monitor The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically
More informationModbus RTU Serial Communications User Manual
Modbus RTU Serial Communications User Manual Supplement to 51-52-25-66 51-52-25-71A 10/99 Copyright, Notices, and Trademarks Printed in U.S.A. Copyright 1999 by Honeywell Inc. Revision A October 28, 1999
More informationOptidrive Applications Support Library
Optidrive Applications Support Library Application Note Title AN-ODV-3-038 Related Products Optidrive Eco Overview Level 3 Modbus RTU Control and Register Mapping 1 Fundamental - No previous experience
More informationThe Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement
Acquisition Measurement Control The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input
More informationE2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09
Application Note Title AN-ODE-01 E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/08 1.03 Revised to new format PAE 09/03/09 General This document
More informationHelios Large Display Temperature Meter
Helios Large Display Temperature Meter Instruction Manual USB Install Temperature Large 1.80" Digits Dual-Line 6-Digit Display Readable from up to 100 Feet (30 Meters) Away Superluminous Sunlight Readable
More informationUser Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6. /8 DIN Process Indicators and Controllers C100, C150, C160 and V100
User Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6 1 /8 DIN Process Indicators and Controllers C100, C150, C160 and V100 Electrical Safety This equipment complies with the
More informationPD Large Display Feet & Inches Process Meter. Feet & Inches process. Actual Size Digit
PD2-6001 Large Display Feet & Inches Process Meter Actual Size Digit Feet & Inches process Feet & Inches Display Ideal for Level Applications Large 1.80ꞌꞌ Dual-Line 6-Digit Display Readable from up to
More informationINSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.
INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,
More informationD0 DCM Module Setup Direct
D0 DCM Module Setup 3 In This Chapter.... Important Module Information Using DirectSOFT5 to Configure s 1 and Port 2 Registers Using Ladder Logic to Configure s (DL05) Using Ladder Logic to Configure s
More informationSPECIFICATIONS SPECIFICATIONS. Input VDC. NEMA 4X/IP65 front VDC option. Temp SPECIFICATIONS
PD603 Sabre P Process Meter Sabre Series 0-20 ma, 4-20 ma; ±10 VDC (0-5, 1-5, 0-10 V) Display 4-digit, 0.56" (14.2 mm) Enclosure 1/8 DIN NEMA 4X/IP65 front Power 85-265 VAC or 12-36 VDC option Operating
More informationModbus Manual Version Modbus Manual for PF4/5
Modbus Manual Version 1.1 - Modbus Manual for PF4/5 Seite 2 1. Table of contents 1 Modbus protocol... 3 1.1. Structure of the Modbus protocol... 3 1.1.1 Modbus RTU / TCP... 3 1.2 Modbus Data Format...
More informationPD6000 Analog Input Process Meter Instruction Manual
PD6000 Analog Input Process Meter 0-20 ma, 4-20 ma, 0-5 V, 1-5 V, and ±10 V Inputs NEMA 4X, IP65 Front Universal 85-265 VAC or 12/24 VDC Input Power Large Dual-Line 6-Digit Display, 0.60" & 0.46" Dual-Scale
More informationLD-RTD / LD-TC Temperature Controller
1 LD-RTD / LD-TC Temperature Controller Available in either an RTD model or a thermocouple model, these units accept all common temperature probe types, and offer a technically advanced, but cost effective
More informationSOFTWARE FUNCTIONAL REQUIREMENTS SPECIFICATION. Athena DeviceNet Interface Module Revision /26/2001
SOFTWARE FUNCTIONAL REQUIREMENTS SPECIFICATION Athena DeviceNet Interface Module Revision 1.40 2/26/2001 Page 2 of 2 TABLE OF CONTENTS 1. RODUCTION...6 1.1 Overview...6 1.2 Document Scope...6 1.3 Definitions...6
More informationUser Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250
User Guide IM/C250 MOD_3 Modbus (RTU) Communications Option C250 and V250 Electrical Safety This instrument complies with the requirements of CEI/IEC 61010-1:2001-2 "Safety requirements for electrical
More informationModbus TCP/IP Option Instruction Manual
W A L C H E M An Iwaki America Company WebMaster Modbus TCP/IP Option Modbus TCP/IP Option Instruction Manual s800v005, s801v004 and higher Five Boynton Road Hopping Brook Park Holliston, MA 01746 USA
More informationW600/W900 Modbus. Instruction Manual
W6/W Modbus Instruction Manual WALCHEM, Iwaki America Inc. Five Boynton Road Hopping Brook Park Holliston, MA 76 USA : TEL: -- WEB: www.walchem.com Notice 7 WALCHEM, Iwaki America Inc. (hereinafter Walchem
More informationFlex Series User Guide
User Programmable Current 4..20mA Digital RS485 Dual & Single Axis Up to 360º 2016 Flex Series User Guide Sensor Installation, Wiring, Flexware App Instructions Page 1 of 33 Page 2 of 33 Table of Contents
More informationOperating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160
Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2 Level Indicator L150 and L160 Electrical Safety This equipment complies with the requirements of CEI/IEC 61010-1:2001-2 "Safety requirements
More informationThis document is for information purposes only and is subject to change without notice.
Notice 7 WALCHEM, Iwaki America Inc. (hereinafter Walchem ) Boynton Road, Holliston, MA 76 USA () - All Rights Reserved Printed in USA Proprietary Material The information and descriptions contained herein
More informationIntrinsically Safe Temperature Concentrator System
Intrinsically Safe Temperature Concentrator System Up to 32 Channels per Network HART and PC configurable 2, 3 & 4-wire RTD or Thermocouple Transmitter like Sensor Diagnostics and performance, RTD ±0.1
More informationDataVU 5 - Interface Manual Modbus
DataVU 5 - Interface Manual Modbus 59482 Contents 1 Introduction 5 1.1 Preface... 5 1.2 Typographical conventions... 6 1.2.1 Warning signs... 6 1.2.2 Note signs... 6 1.2.3 Representation modes... 6 2
More informationSimplified information where and how you want it.
ConsolIdator 4 & 8 Multi-channel controllers Simplified information where and how you want it. ConsoliDator 4 Model PD940 ConsoliDator ConsoliDator 4 Features Four 4-20 Inputs Four 4-20 Outputs ConsoliDator
More informationHART 7.x Field Device Specification for STT700 SmartLine Temperature Transmitters Document Number: 34-TT Revision: 1.0 Release: June 2017
HART 7.x Field Device Specification for STT700 SmartLine Temperature Transmitters Document Number: 34-TT-00-05 Revision: 1.0 Release: June 2017 Honeywell Process Solutions Copyrights, Notices and Trademarks
More informationDataVU 5 - Interface Manual Modbus
DataVU 5 - Interface Manual Modbus 59482 Contents 1 Introduction 5 1.1 Preface... 5 1.2 Typographical conventions... 6 1.2.1 Warning signs... 6 1.2.2 Note signs... 6 1.2.3 Representation modes... 6 2
More informationGE MDS, LLC. NETio Series. Protocol Communications Supplement. March 2013 Part No A01, Rev. C
GE MDS, LLC. NETio Series Protocol Communications Supplement March 2013 Part No. 05-4672A01, Rev. C Modbus Protocol NETio Architectural Implementation As described in detail below, the Modbus RTU protocol
More informationI/O Module. Modbus Manual DMB Series.
I/O Module Modbus Manual DMB Series www.drago-automation.de Before Startup When operating the signal converter, certain parts of the module can carry dangerous voltage! Ignoring the warnings can lead to
More informationInterface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016
Interface Definition RISH EM 2340/1320/30/40 1 2-60-006-00-00494_Rev. D - 8/2016 2 Section DIGITAL MULTIFUNCTION INSTRUMENT Contents 1. Introduction Programmable Multi-function Energy Meter Installation
More informationE2 Modbus RTU Register Map
Application Note AN ODE 01 E2 Modbus RTU Register Map Author: Peter Evans, Invertek Drives Ltd Revision: 1.02 11 June 2008 Software Version: 1.02 General This document details the Modbus RTU memory mapping
More informationSeries SD6 Limit with DeviceNet
Series SD6 Limit with DeviceNet DeviceNet Communications This appendix describes the DeviceNet protocol as it is implemented in the Series SD6 controller. It primarily describes the objects and attributes
More informationC Heat Trace Controller
C910-85 Heat Trace Controller MODBUS PROTOCOL INTERFACE MAPPING For Firmware version V.0.3 THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceC910Modbus-AR-H585 02/13 CONTENTS Section 1 Introduction... 3 Section
More informationJavelin D Model PD644 Instruction Manual
Javelin D Model PD644 Measures DC Voltage up to 300 VDC 4 Digit Display, 0.56" (14 mm) High, Red LEDs Maximum/Minimum Display NEMA 4X, IP65 Front 4-20 ma Transmitter Universal Power Supply 85-265 VAC 12-36
More informationPD6210 / PD6310. PROVU Dual-Line 6-Digit Batch Controllers. Batch control SERIES. Precision Digital Corporation
PD6210 / PD6310 PROVU Dual-Line 6-Digit Batch Controllers PR VU SERIES Batch control Common batch controller Features Start / Pause / Stop, Change Batch with Front Panel Buttons Display Batch Total, Rate,
More informationTemperature-Humidity Sensor Configuration Tool Rev. A 1/25/
Rev. A 1/25/213 172 Contents Contents Temperature-Humidity Sensor Configuration Tool... 3 Read Sensor Screen... 3 Manual Calibration Screen... 4 Register View Screen... 5 Modbus Registers... 6 Reprogram
More informationRemote Level Display with Explosion Proof Enclosure
Remote Level Display with Explosion Proof Enclosure Features Modern, Sleek and Practical Enclosure Display Mountable at 0, 90, 180, & 270 Degrees Explosion-Proof, IP68, NEMA 4X Enclosure SafeTouch Through-Glass
More informationABB Instrumentation. Specification DataFile COMMANDER 100. the-easy-to use 1. /8 DIN controller with extensive application capabilities
COMMANDER Universal Process Controller Specification DataFile PID controller with one shot autotune single loop, heat/cool and ramp/soak as standard Quick code, front face or PC configuration easy commissioning
More informationPROVU PD7000 Temperature Meter Instruction Manual
PROVU PD7000 Temperature Meter Instruction Manual USB Install Temperature Thermocouple: J, K, T, E, R, S, B, N, C RTD: 100Ω Pt, 10Ω Cu, 120Ω Ni, 1000Ω Pt inputs 1 or 0.1 Resolution Displays up to 3300
More information5020 Modbus Translator. User s Guide
Siemens Energy, Inc. Oil & Gas Solutions 10730 Telge Road Houston, Texas 77095 USA Document No. SEI-OG-DLS-004 Page 1 of 10 Siemens AG 2011 Table of Contents 1 OVERVIEW... 3 2 INSTALLATION... 3 3 OPERATION...
More informationTR600 with RS485 Appendix 1
c ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN
More informationOPTRIS CT communication interface
OPTRIS CT communication interface 1. Serial interface parameters Protocol Baud rate: 9600 115200, set by user (factory default: 9600) Data bits: 8 Parity: none Stop bits: 1 Flow control: off The protocol
More informationPC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM
PC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM Modbus is a trademark of Modicon, Inc. Manual content copyright 2015 Extreme Telematics Corporation. All Rights Reserved. Ver 3.2 10/07/15
More informationD1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES
D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES D1000 FEATURES Complete sensor to RS-232/RS-485 interface. 500V rms analog input isolation. 15 bit measurement resolution. Continuous self-calibration;
More informationCATALOG. Digital Indicators & Controllers. Simplifi ed information where and how you want it. Short Form. predig.com/videos
Digital Indicators & Controllers predig.com/videos C US Simplifi ed information where and how you want it. FLOW LEVEL PRESSURE TEMPERATURE PRECISION DIGITAL CORPORATION Since 1974 www.predig.com TABLE
More information115S Serial I/O Module User Manual
ELPRO Technologies Pty Ltd, 9/12 Billabong Street, Stafford Q 4053, Australia. Tel: +61 7 33528600 Fax: +61 7 33528677 Email: sales@elprotech.com Web: www.elprotech.com Thank you for your selection of
More informationDPM-500. Dual-Line 6-Digit Process Meter FEATURES
DPM-00 USB Install FEATURES 0-0 ma, -0 ma, 0- V, - V, and ±0 V Inputs NEMA X, IP6 Front Input Power Options Include 8-6 VAC or - VDC Large Dual-Line 6-Digit Display, 0.60" & 0.6" Dual-Scale for Applications
More informationGeneral Specifications. P2-SCM Serial Communications
General Specifications Module Type Intelligent Modules per Base I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic
More informationSimplified information where and how you want it.
ConsolIdator 4 & 8 Multi-channel controllers Simplified information where and how you want it. ConsoliDator 4 Model PD940 ConsoliDator ConsoliDator 4 Features Four 4-20 Inputs Four 4-20 Outputs ConsoliDator
More informationPM Multifunction meter Cat No. F3N200 - ModbusTable BT EN v1.01.xls
PM Multifunction meter Cat No. FN200 - ModbusTable BT EN v.0.xls GENERAL MODBUS TABLE ORGANIZATION Starting of the Group s Starting of the Group s System Version (Release) System Version (Build) Group
More informationModbus user manual PRO1-Mod & PRO380-Mod
Index 1. Introduction and settings 2. Read data 3. Write data 1. Introduction and settings This user manual explains how to read and write the data of the PRO1-Mod and PRO380-Mod in Commix 1.4. To communicate
More informationPDA1002 DIN-Rail Mounting Kit for Two Modules
PDA1002 DIN-Rail Mounting Kit for Two Modules PRECISION DIGITAL CORPORATION 89 October Hill Road Holliston MA 01746 USA Tel (800) 343-1001 Fax (508) 655-8990 www.predig.com Disclaimer The information contained
More informationPF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016
PF3107-00 MODBUS REGISTER MAP v1.4 Revised TRADEMARKS AND COPYRIGHT All content is subject to copyright and may not be reproduced in any form without the express written consent of the author. 2016 Profire
More informationDIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features Instruction Manual
DIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features 4-20 ma, 1-5 V, 0-5 V, or 0-10 V Field Selectable Inputs Full Six Digit Display for Total, 4½ Digit + Extra
More informationOperating Instructions
Operating Instructions CM4 Serial Communication Protocol CM4 Protocol License Agreement Carefully review the following terms and conditions before proceeding. In the event that you do not agree to these
More informationModbus Register Map: InRow ACRD60x / ACRC60x
Modbus Map: InRow ACRD60x / ACRC60x Notes: 1. 16-bit registers (INT16, UINT16, ENUM) are transmitted MSB first (i.e., big-endian). 2. INT32 and UINT32 are most-significant word in n+0, least significant
More informationMODEL IR5500 Infrared Open Path Gas Detector HART Field Device Specification
MODEL IR5500 Infrared Open Path Gas Detector HART Field Device Specification The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the
More informationOptidrive VTC Modbus RTU Register Map
Application Note AN-VTC- 39 Optidrive VTC Modbus RTU Register Map Author: Ning Xu, Invertek Drives Ltd Revision: 2.21 6 September 2006 General This document details the Modbus RTU memory mapping implemented
More informationProcess & Temperature Meter LI5X Instruction Manual
Process & Temperature Meter LI5X Accepts Current, Voltage, TC, & RTD Inputs 4 Digit Display, 0.56" (14 mm) High, Red LEDs Linear or Square Root with Low-Flow Cutoff Maximum/Minimum Display UL Type 4X,
More informationPD6080/PD6081 PROVU Super Snooper Modbus Scanners
PD6080/PD6081 PROVU Super Snooper Modbus Scanners PR VU SERIES USB Install MODBUS S C A N N E R S Modbus RS-485 RTU Serial Communications as Master, Slave, or Snooper RS-485 Serial Communications Standard
More informationIt is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.
MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling
More informationMultiCube. Modbus Data Tables. August Northern Design (Electronics) Ltd Bradford UK
MultiCube Modbus Data Tables August 2005 Modbus Data Tables Northern Design (Electronics) Ltd Bradford UK 1. Introduction This document is intended as a supplement to the MultiCube Modbus Options Installation
More informationMPV. Process Panel Display. Dual-Line Rate and Total
Process Panel Display Dual-Line Rate and Total measuring monitoring analyzing MPV Pulse or Analog s Displays Rate and Total Simultaneously Square Root Extraction 5, 10, or 24 V DC Flowmeter Power Supply
More informationDeutschmann Module Unigate. CL-Profibus DP. Modbus - Profibus DP Programmer s Manual
Deutschmann Module Unigate CL-Profibus DP Modbus - Profibus DP Programmer s Manual Profibus General Information To use the Deutschmann Unigate CL Module, the script must be programmed on the module. Additionally,
More informationPRODUCT FAMILY: SOLO Controllers Number: AN-LC-009
THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT IS SUPPLIED "AS IS", WITHOUT ANY GUARANTEE OF ANY KIND. These documents are provided by our technical support department to assist others.
More informationTRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features
TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation
More information