Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller
|
|
- Elfrieda Pearson
- 5 years ago
- Views:
Transcription
1 Safety Application Example Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Rating: Category 3, according to EN954-1 Introduction... 1 Important User Information. 2 General Safety Information. 3 Description. 3 Example Bill of Materials. 4 Setup and Wiring.. 4 Configure... 7 Programming Performance Data Additional Resources.. 23 Introduction This safety application example describes how to connect the TLS1-GD2 guard locking switch, a light curtain and an emergency stop button into a GuardLogix controller using Guard I/O on a DeviceNet network. Features and Benefits On-machine installation with quick-disconnect wiring. Guard locking interlocks. Programmable safety logic. Integration of light curtains into a GuardLogix safety system.
2 2 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
3 3 General Safety Information This application example is for advanced users and assumes that you are trained and experienced in safety system requirements. A risk assessment should be performed to make sure all task and hazard combinations have been identified and addressed. The risk assessment may require additional circuitry to reduce the risk to a tolerable level. Safety circuits must take into consideration safety distance calculations which are not part of the scope of this document. Description Contact Rockwell Automation to find out more about our safety risk assessment services. This application shows how to control two safety contactors via a GuardLogix controller and two DeviceNet Guard I/O safety modules. These modules are wired into an emergency stop, a light curtain, and a guard locking interlock switch. Safety Function The TLS1-GD2 interlock is a solenoid-operated guard locking switch which is used to maintain a gate in a locked state until a signal is received from the machine control. The TLS1 interlock switch has two normally-closed contacts that monitor the status of the actuator and one normally-closed and one normally-open contact that monitor the status of the solenoid. In this example the normally-closed contact is used for monitoring purposes. Internally, there is a jumper between terminals 12 and 41of the TLS1- GD2 switch. This jumper is installed in the factory and must be removed for the application described in this document. This wiring configuration lets the solenoid monitoring contact be wired to the GuardLogix controller. With this configuration, the safety system can prevent startup when the door is open or unlocked. The safety gate remains closed and locked while the machine is running. Access to the hazardous area is accomplished by applying a signal to the solenoid in the TLS1-GD2 interlock. While the TLS1-GD2 interlock is unlocked or the gate is open, the hazards cannot start. For this example, the hazards are controlled by two 100S safety control relays. Also controlling the two safety contactors are a light curtain and an emergency stop button.
4 4 Example Bill of Material Setup and Wiring This safety application example uses these components. Catalog Number Description Quantity 1756-L61S GuardLogix safety controller LSP GuardLogix safety partner A4 4-slot chassis ENBT/A Ethernet communication module PA72 ControlLogix power supply DNB DeviceNet communication module DS-IB8XOB8 DeviceNet safety module with 8 inputs and 8 1 outputs 1791DS-IB12 DeviceNet safety module with 12 Inputs 1 800FM-MT44 E-stop button 40mm, maintained, twist-torelease trigger action 1 800FP-F0 800F pushbutton, red 1 800FP-F0 800F pushbutton, amber 1 TLS1-GD2 889M-F12AH-2 Guard locking switch Cord set L-P4K0160YD Pair of GuardShield light curtains 1 100S-C Safety contactors 2 For detailed information on installing and wiring, refer to the product manuals listed in the Additional Resources on page 18. System Overview
5 5 Wiring The following diagrams show the input and output wiring to the Guard I/O modules. Input Circuit
6 6 Output Circuit
7 7 See the additional wiring information on the TLS1-GD2 below. Contact Configuration Red Switches A Safety A (N.C.) B Safety B (N.C.) C Aux A (N.O.) D Solenoid Power E Solenoid A (N.C.) F Solenoid B (N.O.) The jumper between terminals 12 and 41 has been removed for this application. 12-pin, 12-wire Cordset 889M-F12AH-* Brown Gray Pink Green White Red/Blue Black Violet Gray/Pink Yellow Blue Red Solenoid Power Safety A Safety B Aux A Solenoid A Solenoid B Configure Follow these procedures to configure the Guard I/O modules. Set the MAC ID Use the rotary switches to set the MAC ID. The MAC ID is set to 63 by default. When you change the Node Address switch settings while power is on, an electrical arch can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Set the 1791DS-IB8XOB8 rotary switches to address 2 and the 1791-DS-IB12 to address 3.
8 8 Add the 1791DS-IB8XOB8 Module to the RSLogix 5000 Project In the RSLogix 5000 project, add the 1791DS-IB8X0B8 module to the I/O Configuration under the 1756-DNB DeviceNet bridge module. Set the Module Properties 1. On the General tab of the 1791DS-IB8XOB8 Module Properties dialog, fill in these fields: Name: unique module name Node number
9 9 2. Click Change to open the Module Definition dialog box. 3. Configure the module as shown. Combined status consolidates all eight input status bits into a single status signal. The same is true for the output data. For status bits for individual input, output, and test points, choose an alternative data format. 4. Make edits on the Connection and Safety tabs to match your application requirements. This application uses the default data in the Connection and Safety tabs as shown. Change this data based on the throughput requirements of your system.
10 10 Edit the Module s Input Configuration 1. Click the Input Configuration tab. 2. Select one of the following for point operation type: Standard inputs are not internally tested. Safety inputs circuits are tested internally. Safety Pulse Test input circuits are tested internally and a wired pulse-test source is connected. 3. Configure the test outputs.
11 11 4. Set up the outputs. Add the 1791DS-IB12 Module to the RSLogix 5000 Project In the RSLogix 5000 project, add the 1791DS-IB12 module to the I/O Configuration under the 1756-DNB DeviceNet bridge module.
12 12 Set the Module Properties 1. On the General tab of the 1791DS-IB12 Module Properties dialog, fill in these fields: Name: unique module name Node number 2. Click Change to open the Module Definition dialog box. 3. Configure the module as shown. -
13 Edit the Module s Input Configuration 1. Click the Input Configuration tab. 2. Select one of the following for point operation type: Standard inputs are not internally tested. Safety inputs circuits are tested internally. Safety Pulse Test input circuits are tested internally and a wired pulse-test source is connected. 13
14 14 3. Configure the test outputs. Programming This section describes how to program your GuardLogix project based on the wiring and configuration detailed in the previous sections. The programming code for this application example was generated using the Safety Accelerator Toolkit for GuardLogix Systems, SAFETY-CL002A- EN-C, This toolkit provides easy-to-use system design, programming, and diagnostic tools to assist you in the rapid development and deployment of your safety systems using Rockwell Automation s GuardLogix controller, Guard I/O modules, and safety devices.
15 Safety Tags The safety logic within this document requires the creation and use of the following safety tags. 15
16 16 Safety Logic The code shown in this document should be programmed in routines within your safety task. Here is an example of the layout. Control of the Program the Main Routine To help simplify the code, each area of the machine control has been broken into separate routines. The following code is needed to call these routines. Emergency Stop Safety Logic - Zone1 E-Stop The emergency stop safety logic is created in the Zone1_Estop routine. The E-stop instruction provides SIL 3 level diagnostics for a dualchannel emergency stop function. The E-stop monitors input channels for consistency and detects and traps faults with inconsistencies greater than 500 ms.
17 The Reset Type is configured as Automatic for continuous monitoring of input device states. Using automatic reset functionally moves the Safety Output Reset function from the E-stop instruction (Circuit Reset) to the Safety Output logic. Because the Circuit Reset function is not performed within this instruction, a dummy tag named None is used as a placeholder. Input status is not monitored because the input data will go LO if the channel faults. The safety code in the safety output routine will prevent outputs from restarting if the E-stops reset automatically. The Input OK status is used as one of the permissives in the safety output routines. 17 Light Curtain Safety Logic - Zone1 Light Curtain The light curtain safety logic should be created within the Zone1_Light_Curtain routine. The LC instruction provides SIL3 diagnostics for a dual-channel light curtain function. The LC instruction monitors dual input channels for consistency and will detect and trap (with inconsistencies greater than 500 ms). The Reset Type is configured as Automatic for continuous monitoring of input device states. Using automatic reset functionally moves the Safety Output Reset function from the LC instruction (Circuit Reset) to the Safety Output logic. Because the Circuit Reset function is not performed within this instruction, a dummy tag named None is used as a placeholder.
18 18 TLS1-GD2 Door Interlock Switch Safety Logic - Zone1 Door Interlock Switch The door interlock Switch Safety Logic should be created in the Zone1_Door_Interlock_Switch routine. The TLS1-GD2 door-locking circuit contains two elements, a gate switch and a locking solenoid with feedback contact. This routine shows how to use instructions within RSLogix 5000 software to restrict access until a configured time period has elapsed. Gate Switch Safety Logic The RIN instruction provides SIL 3 level diagnostics for a channel redundant input function. The RIN monitors input channels for consistency and detects and traps faults (inconsistencies greater than 500 ms). In this circuit, the RIN instruction monitors the status of the two channels from the TLS1-GD2 interlock switch. If the Zone 1 safety circuit is deactivated, this circuit starts a timer. This time is used to restrict access to the machine until the timer has completed.
19 19 When the timer expires, the Solenoid Enable is activated. The solenoid is turned off once the output enable is turned on. Once the solenoid enable is activated, the ROUT instruction is enabled and turns on safety output tags O1 and O2. These tags activate the solenoid and the solenoid feedback contact is the monitored by the ROUT instruction. Control of the Safety Contactors Zone 1 Contactors Safety Input Interlock Rung This rung includes the safety device input interlocks, with tag names InputOK from the light curtain, E-stop, and door interlock switch routines. If these are all on, they energize the InputsOK OTE instruction to confirm that all the devices are in the correct state. These interlock tags are driven by the individual safety device input logic rungs shown earlier. The Sts_Zone1_InputsOK tag is then included in the Output Enable Rung which drives the ROUT instruction. Output Enable Rung This rung provides the operator action required to reset or enable the safety zone output. The operator action is a HI transition of Cmd_Zone1_Reset_PB. It latches the output enable until either a demand is placed on a safety input, there is an input channel or output channel fault, or a feedback fault on the output circuit. The Sts_Zone1_InputsOK will go LO in the event of a demand on any safety input or fault on any safety input channel within the zone.
20 20 The CombinedOutputStatus, InputStatus or OutputStatus signal goes LO if any output channel on the 1791DS Guard I/O module faults or there is a connection timeout to the I/O module. The FP feedback fault present drops out the output enable in the event of a feedback fault of either the contactors or the solenoid locking switch. In that case, reset or enable cannot occur without operator action. Safety Output Rungs This rung controls the dual outputs on the 1791DS Guard I/O module named Zone1_Safety_Node_IB8XOB8. The ROUT instruction outputs, O1 and O2, are used to drive the safety outputs 01 and 02 (Tags: Zone1_Safety_Node_IB8XOB8:O.Pt01Data and Zone1_Safety_Node_IB8XOB8:O.Pt02Data) which are wired to the safety contactors. Reassignment of the feedback and output channels must be made to match your unique safety wiring configuration.
21 21 Performance Data Worst Case Reaction Time Based on Safety System Typically, both channels are HI coming from the interlock switch and the E-stop. If any one channel goes LO, the corresponding filter timer configured in the 1791DS-IB8OBV4 module starts. If the channel is still LO when the filter times out, the output is turned OFF. Worst-case, the time it takes to occur is the sum of the A to E path as described below. A Input Module Delay 16 ms + on/off delay filters B Input Connection Reaction Time Limit (CTRL) The Connection Reaction Time Limit is configured in the 1791ES Module Properties dialog box within RSLogix 5000 software. The Input Connection defaults to 4 x RPI. C GuardLogix Delay The maximum delay for the GuardLogix controller is: Period + Task Watchdog D Output Connection Reaction Time Limit E Output Module Delay = 6ms Worst Case Reaction Time = A + B + C + D + E
22 22 Typical Reaction Time of Safety System Typically, both channels are HI coming from the interlock switch and the E-stop. If any one channel goes LO, the corresponding filter timer configured in the 1791DS-IB8OBV4 module starts. If the channel is still LO when the filter times out, the output is turned off. Typically, the time it takes to occur is the sum of the A to E path as described below. A Input Module delay / (max/2) = 8ms + on/off delay filters B Input Connection Reaction Time / Input RPI C GuardLogix Delay The typical delay time for the GuardLogix controller is: (Period / 2) + Task Scan Time D Output Connection Reaction Time / Output RPI = Task Period E Output Module Delay / (max / 2) = 3ms Typical Reaction Time = A + B + C + D + E
23 23 Additional Resources For more information about the products used in this example, refer to these resources. Resource Guard I/O DeviceNet Safety Modules User Manual, publication 1791DS-UM001 GuardLogix Safety Application Instruction Set Reference Manual, publication 1756-RM095 Safety Accelerator Toolkit for GuardLogix Systems Quick Start, publication IASIMP-QS005 Safety Products Catalog S116-CA001A GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093 Description Provides general safety guidelines on using Guard I/O DeviceNet Safety modules. Describes the safety application instruction set for the GuardLogix Controller. Describes how to use GuardLogix safety system design tools on the Safety-CL002 CD. Provides an overview of safety product information. Explains how the GuardLogix Controller can be used in safety applications. You can view or download publications at To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
24 24 Allen-Bradley, ControlLogix, DeviceNet, GuardLogix, GuardShield, Rockwell Automation, and RSLogix5000 are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Copyright 2008 Rockwell Automation, Inc. All rights reserved. Printed in U.SA
PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller
Safety Application Example PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Rating: Category 3 (also see Achieving a Cat. 4 Safety Rating)
More informationGuardLogix: TLS Guardlocking Application
Safety Application Example GuardLogix: TLS Guardlocking Application Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information... 2 General Safety Information... 3 Description...
More informationGuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch
Safety Application Example GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information...
More informationGuardLogix: Safety Gate Application with SensaGuard Switch
Safety Application Example GuardLogix: Safety Gate Application with SensaGuard Switch Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Introduction...2 Important User Information...2 General Safety Information...3
More informationUsing TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller
Safety Application Example Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller Guardlocking with On-machine Components Safety Rating: Category 3, according to EN954-1
More informationUsing GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller
Safety Application Example Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller Light Curtain with On-machine Components Safety Rating: Category
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Cable Pull Switch - Products: GuardLogix Series Connection of Cable Pull Switches Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 Table
More informationGuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module
Safety Application Example GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module Safety Rating: SIL3/Category 3 (also see SIL3/CAT4 section), according
More informationSafety Function: Door Locking and Monitoring Products: TLS3-GD2 GuardLogix Controller POINT Guard Safety I/O Modules
Safety Function: Door Locking and Monitoring Products: TLS3-GD2 GuardLogix Controller POINT Guard Safety I/O Modules Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Table of Contents Introduction 3 Important
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Emergency Stop Table of Contents: Introduction 6-121 Important User Information 6-121 Safety Function Realization 6-122 General Safety Information
More informationUsing the Safety Distribution R Box
Safety Application Example Using the Safety Distribution R Box Introduction...2 Important User Information...2 General Safety Information...3 Description...4 SensaGuard Connections...8 Tongue Interlock
More informationApplication Technique. Safety Function: Safety Camera with E-stop
Application Technique Safety Function: Safety Camera with E-stop Products: Guardmaster Dual-input Safety Relay, Guardmaster SC300 Safety Camera Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 2 Safety
More informationTeaching Color-Sensing Connected Components Building Block. Quick Start
Teaching Color-Sensing Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationSafety Function: Safety Camera
Safety Function: Safety Camera Products: SC300 Safety Camera, GuardLogix Controller Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008 Application Technique 2 Safety Function: Safety Camera Important User
More informationControlLogix SIL2 System Configuration
ControlLogix SIL2 System Configuration Using RSLogix 5000 Subroutines Application Technique (Catalog Numbers 1756 and 1492) Important User Information 8 / 2011 Solid state equipment has operational characteristics
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Light Curtain Table of Contents: Introduction 6-22 Important User Information 6-22 Safety Function Realization 6-23 General Safety Information
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Pneumatic Safety Valves- Products: GuardLogix Controller, E-stop, Safety I/O Module, DM 2 Safety Valve Safety Rating: CAT. 3, PLd to EN ISO
More informationL01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!
L01 - Effective Design Methods for Integrating Safety Using Logix Controllers For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Safety Mat Stop Table of Contents: Introduction 6-204 Important User Information 6-204 General Safety Information 6-205 Safety Function Realization:
More informationColor-Sensing Connected Components Building Block. Quick Start
Color-Sensing Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
More informationSafety Function: Muting Products: Light Curtain RightSight Optical Sensors GuardLogix Controller
Safety Function: Muting Products: Light Curtain RightSight Optical Sensors GuardLogix Controller Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Table of Contents Introduction 3 Important User Information
More informationPCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer
Installation Instructions PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer Catalog Number 6189V-2PCI15R Topic Page About This Publication 1 Important User Information 2 Safety
More informationApplication Technique. Safety Function: SensaGuard Non-contact Interlock Switch
Application Technique Safety Function: SensaGuard Non-contact Interlock Switch Products: SensaGuard Switch, GuardLogix Controller Safety Rating: CAT. 4, PLe to EN ISO 13849-1: 2008 2 Safety Function: SensaGuard
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS SensaGuard Non-contact Interlock Switch with E-stop Table of Contents: Important User Information 45 General Safety Information 45 Introduction
More informationGuardLogix Controller Systems
GuardLogix Controller Systems (Catalog Numbers 1756-L61S, 1756-L62S, 1756-LSP) Safety Reference Manual Important User Information Solid state equipment has operational characteristics differing from those
More informationSmartGuard 600 Controllers
SmartGuard 600 Controllers Catalog Number 1752-L24BBB Safety Reference Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Light Curtain with Muting Table of Contents: Introduction 6-4 Important User Information 6-4 Safety Function Realization 6-42 General Safety
More informationGuardLogix Controller Systems
Safety Reference Manual GuardLogix Controller Systems Catalog Numbers 1756-L61S, 1756-L62S, 1756-L63S, 1756-L71S, 1756-L72S, 1756-L73S, 1756-L73SXT, 1756-LSP, 1756-L7SP, 1756-L7SPXT, 1768-L43S, 1768-L45S
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS E-Stop Safety Function Table of Contents: Introduction 6-18 Important User Information 6-18 General Safety Information 6-19 Safety Function Realization
More informationInView Firmware Update
Installation Instructions InView Firmware Update Topic Page Hazardous Voltage 3 Change EPROM on 2706-P72, 2706-P74 Display 3 Change EPROM on 2706-P42, 2706-P44 Displays 5 Firmware Upgrade Kit 7 2 InView
More informationLogix5000 Controllers Produced and Consumed Tags
Logix5 Controllers Produced and Consumed Tags Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix Programming Manual
More informationSimple Package Measurement Connected Components Building Block. Quick Start
Simple Package Measurement Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationPowerMonitor 5000 Unit Catalog Number Upgrade
Installation Instructions PowerMonitor 5000 Unit Catalog Number Upgrade Catalog Numbers 1426-MxE-xxx Topic Page Upgrade the Device Catalog Number with the ControlFLASH Utility 3 Determine Communication
More informationDriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.
DriveGuard Safe-Off Option for PowerFlex 70 AC Drives User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical
More informationLogix5000 Controllers Function Block Diagram
Logix5000 Controllers Function Block Diagram Catalog Numbers 1756 ControlLogix, 1769 CompactLogix, 1789 SoftLogix, 1794 FlexLogix, PowerFlex 700S with DriveLogix Programming Manual Important User Information
More informationDeviceNet Network Configuration
User Manual DeviceNet Network Configuration 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important User Information Solid-state
More informationSolar Combiner Enclosure
Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the
More informationBidirectional (2-sensor, T-type) Muting With Enable Using MSR42 Relay Connected Components Building Block
Bidirectional (2-sensor, T-type) Muting With Enable Using MSR42 Relay Connected Components Building Block Catalog Numbers MSR42, MicroLogix 1100, GuardShield Micro 400 Light Curtains Quick Start Important
More informationImport/Export Project Components. Programming Manual
Import/Export Project Components Programming Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
More informationGuardLogix 5570 Controller Systems
Safety Reference Manual GuardLogix 5570 Controller Systems Catalog Numbers 1756-L71S, 1756-L72S, 1756-L73S, 1756-L73SXT, 1756-L7SP, 1756-L7SPXT, 1756-L72EROMS, Studio 5000 Logix Designer Applications Original
More informationKinetix 6000 Axis Module and Shunt Module
Installation Instructions Kinetix 6000 and Shunt Module Catalog Numbers 2094-AMxx, 2094-BMxx 2094-AMxx-S, 2094-BMxx-S 2094-BSP2 Topic Page About This Publication 1 Important User Information 2 Before You
More informationGuardLogix Controller Systems
Safety Reference Manual Original Instructions GuardLogix Controller Systems Catalog Numbers 1756-L61S, 1756-L62S, 1756-L63S, 1756-L71S, 1756-L72S, 1756-L73S, 1756-L73SXT, 1756-LSP, 1756-L7SP, 1756-L7SPXT,
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE 440C SAFETY FUNCTION DOCUMENTS Emergency Stop with a Configurable Safety Relay Products: Emergency Stop, Guardmaster 440C-CR30 Configurable Safety Relay, 100S-C Safety Contactors
More informationApplication Technique. Safety Function: Safe Limited Speed and Safe Maximum Speed
Application Technique Safety Function: Safe Limited Speed and Safe Maximum Speed Products: TLSZR-GD2 Guard Locking Switch/Guardmaster Safety Relay/ PowerFlex 70 Drive Safety Rating: PLd, Cat. 3 to EN ISO
More informationDeviceNet Communications
DeviceNet Communications For PanelView Plus and PanelPlus CE Terminals 2711P User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical
More informationBidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block
Bidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block Catalog Numbers MSR42, MicroLogix 1100, GuardShield Micro 400 Light Curtains Quick Start Important User Information
More informationDeviceNet CLX PA75 CLX A4. GuardLogix L62S. GuardLogix SafetyPartner LSP. DeviceNet Scanner DNB
GuardLogix CLX- - 1756-PA75 CLX- - 1756-A4 GuardLogix -1756-L62S GuardLogix SafetyPartner - 1756-LSP DeviceNet Scanner - 1756-DNB Ethernet -1756-ENBT Point I/O DeviceNet 1734-ADN Point I/O 8 pt 1734-IB8
More informationControlLogix Configurable Flowmeter Module
User Manual ControlLogix Configurable Flowmeter Module Catalog Numbers 1756-CFM Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
More informationAdapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout
Installation Instructions Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout Catalog Numbers 2711-NR5T, 2711P-RAT12E2 Topic Page About This Publication 1 Important User Information 2 About
More informationInstallation Instructions
Installation Instructions (Cat. No. 1771-OBN Series B) Use this document as a guide when installing the catalog number 1771-OBN series B output module. Because of the variety of uses for the products described
More informationDigital ac/dc (24V) Input Module
Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge
More informationInView Communication Modules
Installation Instructions InView Communication Modules Catalog Numbers 2706-PxM, 2706-PxK, 2706-PxP Topic Page About This Publication 1 Important User Information 2 Power Supply Requirements 3 Mount the
More informationControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual Original Instructions ControlLogix Redundancy Update and Module Replacement Guidelines Product Family ControlLogix 5570 Controllers Important User Information Read this document and the
More informationSimple Motion Control Connected Components Building Block. Quick Start
Simple Motion Control Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationCompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
More informationProcessLogix R510.0 Server Installation Instructions
ProcessLogix R510.0 Server Installation Instructions Installation Instructions Before you begin... This publication guides you through the remaining processes required to initialize a ProcessLogix Server.
More informationThroughout this manual we use notes to make you aware of safety considerations:
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS Safe Limited Speed and Safe Maximum Speed Table of Contents: General Safety Information 6-83 Introduction 6-85 Safety Function Realization: Risk
More informationAllen-Bradley Motors
Installation Instructions Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Purpose Firmware Update Kit Contents Hardware and Software Requirements This
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS 2 Hand Control Safety Function 800Z Zero Force Buttons / MSR125 Safety Relay / GSR SI Safety Relay Table of Contents: Introduction 6-3 Important
More informationMicro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis
Quick Start Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis Catalog Numbers Bulletin 2080-LC30, 2080-LC50 Important User Information Solid-state equipment
More informationPOINT Guard I/O Safety Modules
User Manual POINT Guard I/O Safety Modules Catalog Numbers 1734-IB8S, 1734-OB8S, 1734-IE4S Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
More informationActuator Subsystems Stop Cat. 0 or 1 via an Integrated Safety Controller and PowerFlex 527 Drive with Hardwired Safe Torque Off Safety Function
Application Technique Actuator Subsystems Stop Cat. 0 or 1 via an Integrated Safety Controller and PowerFlex 527 Drive with Hardwired Safe Torque Off Safety Function Products: GuardLogix 5570 or Compact
More informationAllen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon
Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between
More informationDifferential Liquid/Gas Pressure Transmitter
Installation Instruction Differential Liquid/Gas Pressure Transmitter Catalog Number(s) 1414-CPZ10FWFAA, 1414-IPZ10FWFAA Explosion Hazard WARNING Do not use in an explosive or hazardous environment, with
More informationLogix5000 Controllers Produced and Consumed Tags
Programming Manual Logix5 Controllers Produced and Consumed Tags Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix
More informationCatalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE
Release Notes RSFieldbus Software Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE Topic Page Important User Information 2 Before You Begin 3 Software Requirements 4 Install the Software
More informationNext Generation Guardmaster Safety Relay (GSR)
Wiring Diagram Next Generation Guardmaster Safety Relay (GSR) Bulletin 0R Quick Reference Page Safety Relay Modules Input Devices Output Devices SIL CL Category Number 6 SI E-stop PowerFlex d 0 SI MAB
More informationFLEX 5000 Digital I/O Modules
User Manual Original Instructions FLEX 5000 Digital I/O Modules Catalog Numbers 5094-IB16, 5094-IB16XT, 5094-OB16, 5094-OB16XT, 5094-OW8I, 5094-OW8IXT Important User Information Read this document and
More informationLogix5000 Controllers Nonvolatile Memory Card
Programming Manual Logix5000 Controllers Nonvolatile Memory Card 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, 5069 CompactLogix, Studio 5000 Logix Emulate
More informationInstallation Instructions
Installation Instructions (Cat. No. 71-A1B, -A2B, -A3B, -A3B1, -A4B Series B) Because of the variety of uses for the products described in this publication, those responsible for the application and use
More informationLogix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network
Quick Start Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network Catalog Numbers Logix5000 Controllers, 2711P PanelView Plus Terminals Important User Information Solid-state
More informationPowerMonitor 1000 Unit Catalog Number Upgrade
Installation Instructions PowerMonitor 1000 Unit Catalog Number Upgrade Catalog Numbers 1408-UPT1-E3, 1408-UPT2-E3, 1408-UPE1-E3, 1408-UPE2-E3, 1408-UP485-ENT, 1408-UPT3-E3 Topic Important User Information
More informationIntegrated Safety & PowerFlex DriveGuard
Integrated Safety & PowerFlex DriveGuard Session Agenda Introduction to GuardLogix Approx 15min Agenda Hands-on lab Approx 1.5 hrs Topics to Cover Introduction to GuardLogix Contents GuardLogix with ControlLogix
More informationCompactBlock Guard I/O Modules ArmorBlock Guard I/O Modules POINT Guard I/O Modules
Overview Overview Control and monitor your safety devices with Guard I/O. When used with Rockwell Automation safety controllers, Guard I/O communicates on EtherNet/IP or DeviceNet using CIP Safety protocol.
More informationInstallation Instructions
Installation Instructions Cat. No. 1771 P3, P4, P5 and P5E Use this document as a guide when installing the catalog number 1771-P3, -P4, -P5 or -P5E power supplies. Because of the variety of uses for the
More informationGuard I/O EtherNet/IP Safety Modules
User Manual Guard I/O EtherNet/IP Safety Modules Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16, 1732ES-IB12XOB4, 1732ES-IB12XOBV2 Important User Information Read this document and the documents listed in
More informationInstallation Instructions
Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application
More informationFlexLogix System L33 and 1794-L34. User Manual. Allen-Bradley HMIs
FlexLogix System 1794-L33 and 1794-L34 User Manual Allen-Bradley HMIs Important User Information Because of the variety of uses for the products described in this publication, those responsible for the
More informationPowerFlex 700H AC Drive Safe Torque Off Option
User Manual PowerFlex 700H AC Drive Safe Torque Off Option Catalog Number 20C-DG01 Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
More informationSequenceManager Controls
Reference Manual SequenceManager Controls 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important user information Read this
More informationPOINT Guard I/O Safety Modules
User Manual POINT Guard I/O Safety Modules Catalog Numbers 1734-IB8S, 1734-OB8S, 1734-IE4S Important User Information Read this document and the documents listed in the additional resources section about
More informationApplication Technique. Products: Guardmaster 440C-CR30 Configurable Safety Relay, PowerFlex 755 Drive. Safety Rating: CAT. 3, PLe to ISO : 2008
Application Technique Safety Function: Actuator Subsystems Stop Category 0 or Stop Category 1 via a Configurable Safety Relay and PowerFlex 755 Drive with Hardwired Safe Torque-off Products: Guardmaster
More informationControlLogix Digital I/O Modules
User Manual ControlLogix Digital I/O Modules Catalog Numbers 1756-IA8D, 1756-IA16, 1756-IA16I, 1756-IA32, 1756-IB16, 1756-IB16D, 1756-IB16I, 1756-IB16IF, 1756-IB32, 1756-IC16, 1756-IG16, 1756-IH16I, 1756-IM16I,
More informationLogix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network
Quick Start Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network Catalog Numbers Logix5000 Controllers, 1734 POINT I/O Modules Important User Information Solid-state equipment
More informationFLEX I/O Dual Port EtherNet/IP Adapter Modules
User Manual FLEX I/O Dual Port EtherNet/IP Adapter Modules Catalog Numbers 1794-AENTR, 1794-AENTRXT Important User Information Solid-state equipment has operational characteristics differing from those
More informationAgenda. Session Agenda. Introduction to GuardLogix Approx 15min. Hands-on lab Approx 1.5 hrs
Integrated Safety Session Agenda Introduction to GuardLogix Approx 15min Agenda Hands-on lab Approx 1.5 hrs Topics to Cover Introduction to GuardLogix Contents GuardLogix with ControlLogix Functionality
More informationStudio 5000 Architect Getting Results Guide
Getting Results Studio 5000 Architect Getting Results Guide Rockwell Automation Publication ARCH-GR001I-EN-E Supersedes Publication ARCH-GR001H-EN-E Important user information Read this document and the
More informationL12 - Studio 5000 and Logix: Basics Lab. For Classroom Use Only!
L12 - Studio 5000 and Logix: Basics Lab For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter Documentation ) is intended
More informationMicro800 Controllers Starter Pack Quick Start
Quick Start Micro800 Controllers Starter Pack Quick Start Catalog Numbers Bulletin 2080-LC20, 2080-LC30, 2080-LC50 Important User Information Read this document and the documents listed in the additional
More informationControlLogix Analog I/O Modules
ControlLogix Analog I/O Modules 1756-IF16,- IF6CIS, -IF6I, -IF8, -IR6I, -IT6I, -IT6I2, -OF4, -OF6CI, -OF6VI, -OF8 User Manual Important User Information Because of the variety of uses for the products
More informationKinetix 300 Memory Module Programmer
Kinetix 300 Memory Module Programmer Catalog Number 2097-PGMR Topic About the Memory Module Programmer 1 Parts List 3 Batteries Operation 4 Using Memory Module Programmer 6 Switch On/Off Memory Module
More informationThe Guardmaster 440C-CR30 Software Configurable Safety Relay Training Demo Lab. For Classroom Use Only!
The Guardmaster 440C-CR30 Software Configurable Safety Relay Training Demo Lab For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic
More informationMicro800 Programmable Controllers
Micro800 Programmable Controllers Bulletin 2080 Selection Guide Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
More informationSimple Temperature Control Connected Components Building Block. Quick Start
Simple Temperature Control Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS Safety Function: Actuator Subsystems Stop Category 1 via the PowerFlex 525 and PowerFlex 527 Drives with Safe Torque-off Table of Contents: Important
More informationRemote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication
Remote I/O Scanner Catalog Number 1747-SN Installation Instructions 2 Remote I/O Scanner Important User Information Because of the variety of uses for the products described in this publication, those
More informationAllen-Bradley Replacements
Programming Manual Logix 5000 Produced and Consumed Tags 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, 5069 CompactLogix, Studio 5000 Logix Emulate Allen-Bradley
More informationPoint Guard I/O Safety Modules
User Manual Original Instructions Point Guard I/O Safety Modules Catalog Numbers 1734-IB8S, 1734-OB8S, 1734-IE4S, 1734-OBV2S Important User Information Read this document and the documents listed in the
More information1. Introduction. 2. Design. Safety and Emergency Stop Circuit Design Standard. Safety and Emergency Stop Circuit Design Standard.
Safety and Emergency Stop Circuit Design Standard The Safety and Emergency Stop Circuit Design Standard provide design criteria and specifications for safety and emergency stop circuits used in General
More information