SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER

Size: px
Start display at page:

Download "SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER"

Transcription

1 ATS MOLDED CASE WITH ATC 900 CONTROLLER PART 1 GENERAL SCOPE Furnish and install the low voltage automatic transfer switches having the ratings, features/accessories and enclosures as specified herein and as shown on the contract drawings. RELATED SECTIONS REFERENCES The automatic transfer switches and all components shall be designed, manufactured and tested in accordance with the latest applicable standards of UL and NEMA as follows: UL 1008 Transfer Switches UL Tests for Safety-Related Controls Employing Solid-State Devices NFPA 70 National Electrical Code NFPA 99 Essential Electrical Systems of Health Care Facilities NFPA 110 Emergency and Standby Power Systems NEMA ICS 10 AC Transfer Switch Equipment IEEE 446 Recommended Practice for Emergency and Standby Power Systems SUBMITTALS FOR REVIEW/APPROVAL The following information shall be submitted to the Engineer: Front view and plan view of the assembly Schematic diagram Conduit space locations within the assembly. 4. Assembly ratings including: a. Withstand and Closing rating b. Voltage c. Continuous current rating d. Short-Time rating if applicable e. Short-circuit rating if ordered with integral protection Cable terminal sizes Product Data Sheets. Where applicable, the following additional information shall be submitted to the Engineer: Busway connection Connection details between close-coupled assemblies Composite front view and plan view of close-coupled assemblies 16496E-1 02/17/14

2 05 06 SUBMITTALS FOR CONSTRUCTION The following information shall be submitted for record purposes: 4. Final as-built drawings and information for items listed in section 04 Wiring diagrams Certified production test reports Installation information Seismic certification as specified The final (as-built) drawings shall include the same drawings as the construction drawings and shall incorporate all changes made during the manufacturing process. QUALIFICATIONS The manufacturer of the assembly shall be the manufacturer of the major components within the assembly. For the equipment specified herein, the manufacturer shall be ISO 9001 or 9002 certified. C. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of five (5) years. When requested by the Engineer, an acceptable list of installations with similar equipment shall be provided demonstrating compliance with this requirement. * Provide Seismic tested equipment as follows: The equipment and major components shall be suitable for and certified by actual seismic testing to meet all applicable seismic requirements of the [latest International Building Code (IBC)] [latest California Building Code (CBC) with OSHPD Amendments]. [The equipment shall have OSHPD Special Seismic Certification (OSP) Pre-Approval.] The Project Structural Engineer will provide site specific ground motion criteria for use by the manufacturer to establish SDS values required. The IP rating of the equipment shall be 5 4. The Structural Engineer for the Site will evaluate the SDS values published on the [Manufacturer s] [OSHPD] website to ascertain that they are "equal to" or "greater than" those required for the Project Site. The following minimum mounting and installation guidelines shall be met, unless specifically modified by the above referenced standards. a. b. c. The Contractor shall provide equipment anchorage details, coordinated with the equipment mounting provision, prepared and stamped by a licensed civil engineer in the state. Mounting recommendations shall be provided by the manufacturer based upon the above criteria to verify the seismic design of the equipment. The equipment manufacturer shall certify that the equipment can withstand, that is, function following the seismic event, including both vertical and lateral required response spectra as specified in above codes. The equipment manufacturer shall document the requirements necessary for proper seismic mounting of the equipment. Seismic qualification shall be considered * Note to Spec. Writer - Optional 16496E-2 02/17/14

3 achieved when the capability of the equipment, meets or exceeds the specified response spectra REGULATORY REQUIREMENTS Provide a certificate of compliance with UL 1008 for the transfer switches furnished under this section. DELIVERY, STORAGE AND HANDLING Equipment shall be handled and stored in accordance with manufacturer s instructions. One (1) copy of these instructions shall be included with the equipment at time of shipment. FIELD MEASUREMENTS OPERATION AND MAINTENANCE MANUALS Equipment operation and maintenance manuals shall be provided with each assembly shipped, and shall include instruction leaflets and instruction bulletins for the complete assembly and each major component. EXTRA PRODUCTS PART 2 PRODUCTS MANUFACTURERS C. Eaton * * D. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. Products in compliance with the specification and manufactured by others not named will be considered only if pre-approved by the engineer ten (10) days prior to bid date. CONSTRUCTION Switching devices for 30 Amp through 1000 Amp transfer switches shall be molded case switch type. All breaker transfer switches shall be UL listed for application in their intended enclosures for 100% of their continuous ampere rating. C. The automatic transfer switch shall be of double throw construction operated by a reliable electrical mechanism momentarily energized. D. Each transfer switch shall be positively interlocked both mechanically and electrically to prevent simultaneous closing of both sources under either automatic or manual operation. * Note to Spec. Writer Insert data in blanks 16496E-3 02/17/14

4 E. F. G. H. I. J. K. Main contacts shall be silver composition and mechanically held in both normal and emergency positions. Switches shall operate delayed transition, with a time delay in the neutral position adjustable from 0 to 120 seconds The switching panel shall consist of completely enclosed contact assemblies and a separate control or transformer panel. Control power for all transfer operations shall be derived from the line side of the source to which the load is being transferred. The transformer shall be multi-tap for ease of voltage adjustment in the field. Transfer switches shall be capable of being operated manually under full rated load conditions. Manual operation shall be accomplished by a permanently attached manual operator, or by integrally mounted pushbuttons. Removable manual operating handles, and handles that may move in the event of an electrical operation during the manual operation, are not acceptable. Manual operators requiring source or load disconnection prior to manual operation are not acceptable. On transfer switches requiring a fourth pole for switching the neutral, the neutral shall be identical to the other power poles. Switched neutral poles which are add-on or overlap, or that are not capable of breaking full rated load current are not acceptable. On transfer switches requiring a solid neutral, the neutral shall be fully rated. Where shown on drawings, transfer switches applied as service entrance equipment shall include molded case circuit breakers with thermal magnetic trip units on [source 1] [source 2][source 1 and 2]. Ground fault protection shall be provided for all switches rated 1000 amperes or more applied on 480Y/277 Vac systems. 02 MICROPROCESSOR LOGIC The transfer switch shall be equal to an Eaton ATC-900 type microprocessor-based controller. The controller shall be hardened against potential problems from transients and surges. Operation of the transfer switch and monitoring of both sources shall be managed by the controller. The automatic transfer switch controllers shall meet or exceed the following standards in addition to the basic switch standards: IEC EMC Testing and Measurement Techniques - Electrostatic Discharge Immunity Test IEC EMC Testing and Measurement Techniques - Radio-frequency, Electromagnetic Field Immunity Test IEC EMC Testing and Measurement Techniques - Electrical Fast Transient/Burst Immunity Test 4. Test IEC EMC Testing and Measurement Techniques - Surge Immunity IEC EMC Testing and Measurement Techniques - Immunity to Conducted Disturbances, Induced by Radio-frequency Fields IEC EMC Testing and Measurement Techniques - Voltage Dips, Short Interrupts and Voltage Variations Immunity Tests 16496E-4 02/17/14

5 7. CISPR11, Class B - Industrial, Scientific and Medical Radio-frequency Equipment - Electromagnetic Disturbance Characteristics - Limits and Methods of Measurement 8. FCC Part 15, Subpart B, Class B ENCLOSURE Each transfer switch shall be provided in a [NEMA 1] [NEMA 12] [NEMA 3R] [NEMA 4x] enclosure suitable for use in environments indicated in the drawings. NEMA 1, 12 or 3R enclosures shall be painted with the manufacturer s standard light gray ANSI 61paint. Nema 4X shall be [304] [316] stainless steel. CONTROLLER DISPLAY AND KEYPAD The microprocessor-based controller display shall be UV resistant and include a 4.3 inch Color TFT (480x272), backlit display. The controller shall be capable of displaying transfer switch status, parameters, and diagnostic data. All set point parameters shall be password protected and programmable using the controller keypad, USB port, or remotely using serial port access. The microprocessor-based controller shall include a mimic bus display consisting of six (6) individual LED s (3mm) for indicating the following: 4. Availability status of source 1 Availability status of source 2 Connection status of source 1 Connection status of source 2 Source 1 Preferred Source 2 Preferred VOLTAGE AND FREQUENCY SENSING The controller shall have a voltage range of volts (50/60 Hz) with an accuracy of +/- 1% of the reading and a frequency range of Hz with an accuracy of +/-.3 Hz. Voltage and frequency dropout and pickup parameters are set as a percentage of the nominal voltage as indicated in the table below. Setpoint Sources Dropout Pickup Undervoltage Source1 and % (DO + 2%) - 99% Overvoltage Source 1 and % 103% - (DO 2%) Underfrequency Source 1 and % (DO + 1Hz) 99% Overfrequency Source 1 and % 101% - (DO 1Hz) Voltage Unbalance Source 1 and % (UNBAL DO% - 2) 3% C. The normal and emergency sources shall include phase reversal protection. The preferred rotation is programmable as ABC or CB 16496E-5 02/17/14

6 06 07 TIME DELAYS C. D. E. F. A time delay shall be provided to override a momentary power outage or voltage fluctuation, adjustable from 0 to 120 seconds. A time delay shall be provided on transfer to source 2, adjustable from 0 to 166 minutes. A time delay shall be provided for engine failure to start, adjustable 0-6 seconds. A time delay shall be provided on retransfer from source 2 to source 1, adjustable from 0 to 166 minutes. A time delay shall be provided after retransfer that allows the generator to run unloaded prior to shutdown, adjustable form 0 to 166 minutes. *A pre and or post transfer time delay output adjustable from seconds. The contact shall be a form-c contact rated for 10-Amp at 250-Vac and 10-Amp at 30-Vdc. G. All delays shall be field adjustable from the microprocessor-based controller without the use of special tools. ADDITIONAL FEATURES One Form C contact for closure of the source 1 generator start circuit for optional use with a dual generator system. The contacts shall be rated for 5-Amp at 250-Vac and 5-Amp at 30- Vdc. One Form C contact for closure of the source 2 generator start circuit. The contacts shall be rated for 5-Amp at 250-Vac and 5-Amp at 30-Vdc. C. The controller shall include two independently programmable Engine Exercisers, selectable as disabled, 7, 14, or 28 day interval, or by calendar date. Run time shall be adjustable for minutes, with or without load. Upon loss of source 2 power, the ATS shall automatically return to source Transfer time delays shall also be independently programmable for test events. D. E. The controller shall include a keypad pushbutton to initiate a system test. The controller shall include 4 user configurable inputs. Each input provides 50 volts at 10ma and can be user configured to one of the following features: Input to accept a remote contact which closes to initiate a transfer to source This feature shall be failsafe and an automatic retransfer shall occur in the event that source 2 power is lost. Input to accept a remote contact which closes to initiate a transfer to source This feature shall be failsafe and an automatic retransfer shall occur in the event that source 2 power is lost. Input to accept a remote contact which opens to inhibit transfer to source 4. Input to enable monitor mode to disable automatic operation of the transfer switch while continuing to display status. Monitor mode allows set point programming at the controller display. Input to enable lockout feature to disable automatic operations of the transfer switch following an overcurrent trip of an integral circuit breaker. * Note to Spec. Writer Optional 16496E-6 02/17/14

7 F. G. H. I. J. 7. Input to enable or disable manual retransfer to source Input to initiate manual retransfer to source 8. Input to initiate a remote engine test. The test will run using the programmed engine test set points Input to select source 1 or source 2 as the preferred source. Input to initiate a remote load test. Input to indicate the bypass transfer switch is closed on a source. Input to bypass time delays 1 Input to receive engine start signal from a master controller in a three source application. The controller shall include 4 user configurable outputs rated for 10-Amp at 250-Vac and 10- Amp at 30-Vdc. Each input can be user configured to one of the following features: Source 1 connected Source 2 connected ATS in test ATS not in automatic mode (Monitor Mode) General Alarm indication for failure to transfer, mechanical fault, or electrical fault. Engine Test Aborted Engine cool down in process Engine start contact status Emergency inhibit on 10. Load sequence Output used to signal select loads to disconnect prior to transfer and reconnect seconds after. Loads are reconnected sequentially. 1 Selective load shed Output used to shed low priority loads when the load reaches a programmed threshold value. A load shed and load restore set point (measured in kw) are associated with this feature. 1 Load bank control Output to disconnect a load bank during an engine run test if a transfer to a source 2 generator is required. 1 Pre and/or post transfer signal - A pre and or post transfer time delay output adjustable from seconds. One Form C auxiliary contact to indicate Source 1 position and one Form C contact to indicate source 2 position. The contacts shall be rated for 10-Amp, 1/3-Horsepower at 250- Vac and 10-Amp at 30-Vdc. One Form C contact for Source 1 Available. The contacts shall be rated for 10-Amp, 1/3- Horsepower at 250-Vac and 10-Amp at 30-Vdc. One Form C contact for Source 2 Available. The contacts shall be rated for 10-Amp, 1/3- Horsepower at 250-Vac and 10-Amp at 30-Vdc. Data Logging Historical Data Storage to include: a. Engine Run Time 16496E-7 02/17/14

8 b. c. d. e. f. g. h. i. Source 1 Available time Source 2 Available time Source 1 Connected time Source 2 Connected time Source 1 Engine Run Time Source 2 Engine Run Time Load Energized Time Number of Transfers ATS MOLDED CASE WITH ATC 900 CONTROLLER Event Summary shall include up to 100 date and time stamped events. All metered values are logged for each event. Event summaries include: a. Transfer events b. Alarms c. Changes to the set points d. Changes to the time/date e. Resetting a historical counter f. Engine Run test Event Details shall include up to 350 date and time stamped events. All metered values are logged for each event. Event details include detailed sequence of operations of a transfer event. 4. Event recording shall capture 4 seconds of metered data, stored every 20 msec for certain events. The data is captured 2 seconds before and 2 seconds after the event. Oscillographic data for 10 events is stored and may be downloaded over US Events Include: a. Source unavailability actions that initiate a transfer sequence (Undervoltage, Overvoltage, etc.) b. Successful transfers (at the point of breaker/contactor closure) c.unsuccessful transfers (at the point of breaker/contactor failure to close or open) 08 OPTIONAL ACCESSORIES *Non-Automatic Control: Provide a 2-Position Selector Switch, maintained contact, marked: Automatic and Non-Automatic. The transfer switch shall be transferred by actuating a two position maintained selector switch labeled Source 1 and Source 2. A 30mm pilot light shall be provided labeled Not in Automatic. *Non-Automatic Control: Provide a 3-Position Selector Switch, maintained contact, marked: Automatic and Non-Automatic. The transfer switch shall be transferred by actuating a three position maintained selector switch labeled Source 1, Off and Source 2. A 30mm pilot light shall be provided labeled Not in Automatic. C. *Manual Retransfer Control: The ATS shall remain connected to the emergency source after the normal source becomes available until a momentary pushbutton contact closure signal is received to initiate the retransfer. Should a failure of the emergency source occur while waiting for the manual return, the re-transfer proceeds automatically. D. *Device panel mounted Preferred Source Selector switch * Note to Spec. Writer Optional 16496E-8 02/17/14

9 E. F. G. H. I. J. K. ATS MOLDED CASE WITH ATC 900 CONTROLLER *Device panel mounted Source 2 Inhibit keyed switch with 30mm white pilot light indicating inhibit status. *Device panel mounted selector switch to initiate a load transfer to source This operation shall be failsafe to initiate an automatic retransfer upon loss of source 2 power. *Communications Interface to be [Modbus RTU] [Modbus TCP/IP]. * Where indicated on the drawings, provide a [50KA] [80KA] [100KA] [200KA] surge protection device on source *Space heater with thermostat rated for 100 watts. *Integrated Load Metering The controller shall include integral load metering. When included, metered values shall be viewable from the controller LCD display Source 1 Voltages (3Ф) Source 2 Voltages (3Ф) Load Voltages (3Ф) Source 1 Frequency Source 2 Frequency Load Frequency Load Currents (3Ф) Load kw Load kvar Load kva pf *Customer Metering Where indicated on the drawings, provide customer metering to include the following: Note to Spec. Writer: Select devices as required for item 09.K. Refer to section for detailed specification for metering as follows: Power Xpert Series (Paragraph 02A) Power Xpert Meter Series 2000 (Paragraph 0B) IQ-100 Series (Paragraph 0D) IQ 250/260 Series(Paragraph 02E) L. *Remote Annunciator and Controller: Monitor up to eight (8) automatic transfer switches. a. 7 touchscreen color display b. Mimic bus display for each transfer switch with indication of source availability, based on controller pickup and dropout settings, and switch position. * Note to Spec. Writer Optional 16496E-9 02/17/14

10 c. d. e. a. ATS MOLDED CASE WITH ATC 900 CONTROLLER Each mimic bus display shall be marked with the designation of the transfer switch monitored. Indication of switch in test mode,. Indication of failure of digital communication link. Control Functions Control functions shall be password protected and shall include: Initiate engine test. Initiate a failsafe transfer to source Initiate manual retransfer. Indicating Lights: Grouped for each transfer switch monitored. 4. Label each group, indicating transfer switch it monitors, location of switch, and identity of load it serves. Mounting: Flush, modular, steel cabinet, unless otherwise indicated. Communications capability to be compatible with ATS controller. M. *Three Source Transfer Control The ATC-900 controller shall include a Master/Slave functionality for use in configuring two independent transfer switches as a three source transfer system. Sequence of operations - In the event of a source 1 power failure the Master ATS controller shall send an engine start signal to the slave input on the Slave controller. The slave controller shall send an engine start signal to both generators. If a preferred generator is selected, the Slave controller will count down through the time delay for engine failure and remain on the preferred generator if it is available. If the preferred generator is not available at that time, the Slave ATS will transfer to the non-preferred generator. If none-preferred is selected, the Slave ATS will transfer to the first available generator. The unused generator will be shut down as soon as the Slave ATS is connected to a good source. * Note to Spec. Writer Optional 16496E-10 02/17/14

11 PART 3 ADDITIONAL REQUIREMENTS Note to Spec Writer: Select from the table below to fill in the data required for 0A Table 16496A-1 Transfer Switch Rating When Used With Rating When Ampere Rating Upstream Circuit Breaker Used With Upstream Fuses Suggested Breaker Rating 240V (ka) 480V (ka) 600V (ka) Maximum Fuse Rating Fuse Type 480V (ka) A J, T A J, T A J, T A J, T A J, T A (3pole) J, T (4pole) A (3pole) L (4pole) A (3pole) 35 (4pole) L WITHSTAND AND CLOSING RATINGS The transfer switch shall have a specific breaker withstand and closing rating of KA at volts. PART EXECUTION EXAMINATION 4.02 FACTORY TESTING The following standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of UL and NEMA standards E-11 02/17/14

12 C. Insulation check to ensure the integrity of insulation and continuity of the entire system Visual inspection to ensure that the switch matches the specification requirements and to verify that the fit and finish meet quality standards 4. Mechanical tests to verify that the switch's power sections are free of mechanical hindrances Electrical tests to verify the complete electrical operation of the switch and to set up time delays and voltage sensing settings of the logic The manufacturer shall provide a certified copy of factory test reports. Transfer switch shall include a label indicating order number, catalog number and date INSTALLATION The Contractors shall install all equipment per the manufacturer s recommendations and the contract drawings All necessary hardware to secure the assembly in place shall be provided by the contractor FIELD QUALITY CONTROL *Provide the services of a qualified factory-trained manufacturer s representative to assist the contractor in installation and start-up of the equipment specified under this section for a period of working days. The manufacturer s representative shall provide technical direction and assistance to the contractor in general assembly of the equipment, connections and adjustments, and testing of the assembly and components contained therein. MANUFACTURER S CERTIFICATION *A qualified factory-trained manufacturer s representative shall certify in writing that the equipment has been installed, adjusted and tested in accordance with the manufacturer s recommendations. The Contractor shall provide a copy of the manufacturer s representative s certification. TRAINING *The [Contractor] OR [Manufacturer s qualified representative] shall conduct a training session for up to five (5) owner s representatives for normal workdays at a jobsite location determined by the owner. The training program shall consist of the instruction on the operation of the transfer switch and the major components within the assembly. FIELD SERVICE ORGANIZATION The manufacturer of the ATS shall also have a national service organization that is available throughout the contiguous United States and is available on call 24 hours a day, 365 days a year. * Note to Spec. Writer Optional 16496E-12 02/17/14

LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES SECTION 16496D

LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES SECTION 16496D (26 36 23.04) LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the low voltage automatic transfer switch and

More information

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION ( ) LIGHTING CONTROL PANELBOARD (26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

SUGGESTED SPECIFICATION SINGLE OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL

SUGGESTED SPECIFICATION SINGLE OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL TYPE RTS30ATA AUTOMATIC TRANSFER SWITCH RPTCS CONTROL EFFECTIVE 1/19/2011 SUGGESTED SPECIFICATION SINGLE OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL PART 1 - GENERAL

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Current Voltage, Frequency Molded case (MCCB) Insulated Case (ICCB) 200

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Molded case (MCCB) Insulated Case (ICCB) Current Voltage, Frequency 200

More information

SUGGESTED SPECIFICATION CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH WITH LOAD BREAK BYPASS/ISOLATION OPERATION WITH RPTCS MICROPROCESSOR CONTROL

SUGGESTED SPECIFICATION CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH WITH LOAD BREAK BYPASS/ISOLATION OPERATION WITH RPTCS MICROPROCESSOR CONTROL TYPE RTS30ABLC COMBINATION AUTOMATIC TRANSFER WITH BYPASS ISOLATION SWITCH RPTCS CONTROL EFFECTIVE 1/19/2011 SUGGESTED SPECIFICATION CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH WITH LOAD BREAK BYPASS/ISOLATION

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

Model: KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model: KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model: KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Molded case (MCCB) Insulated Case (ICCB) Current Voltage, Frequency 200

More information

Transfer Switches 5.1 Transfer Switch Equipment Product Selection Guide... Product Description... Application Description...

Transfer Switches 5.1 Transfer Switch Equipment Product Selection Guide... Product Description... Application Description... .1 Transfer Switch Equipment Product Selection Guide.................................... Product Description....................................... Application Description......................................2

More information

SUGGESTED SPECIFICATION For Series 300 Automatic Transfer Switches (3ATS)

SUGGESTED SPECIFICATION For Series 300 Automatic Transfer Switches (3ATS) SUGGESTED SPECIFICATION For Series 300 Automatic Transfer Switches (3ATS) PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (3ATS) with number of poles, amperage, voltage, and withstand

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) SECTION 26 29 23 VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) PART 1 -GENERAL 1.1 SYSTEM DESCRIPTION A. Definitions: The Variable Speed AC Motor Drive (hereafter referred to as "VFD") shall be designed to

More information

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP750-51(B) FTA750 Full Voltage Starting Limited Service Electric Fire Pump Controllers Product Description Description Firetrol

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

GE Digital Energy Power Quality. Zenith ZTG Series. Low-Voltage Automatic Transfer Switches

GE Digital Energy Power Quality. Zenith ZTG Series. Low-Voltage Automatic Transfer Switches GE Digital Energy Power Quality Zenith ZTG Series Low-Voltage Automatic Transfer Switches GE s Zenith ZTG Series switches are built for standard applications requiring the dependability and ease of operation

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

4000 SERIES Power Transfer Switches Product Features

4000 SERIES Power Transfer Switches Product Features The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. 4000 SERIES Power Transfer Switches Product Features Conventional two-position transfer

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Series TS Amp. Automatic Transfer Switches

Series TS Amp. Automatic Transfer Switches Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:

More information

STANDARD SUBMITTAL PACKAGE

STANDARD SUBMITTAL PACKAGE STANDARD SUBMITTAL PACKAGE SBP1000-51( ) FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for

More information

Transfer Switches Magnum-Based Designs

Transfer Switches Magnum-Based Designs Transfer Switches -Based Designs Floor-Standing Transfer Switches General Description September 2011 Sheet 25046 Isolation Transfer Switch Isolation Transfer Switch General Description A bypass isolation

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Spec Sheet: Zenith ZXS (ZTX) Transfer switch

Spec Sheet: Zenith ZXS (ZTX) Transfer switch Spec Sheet: Zenith ZXS (ZTX) Transfer switch Description: GE Zenith s ZXS (Previously known as ZTX) Series Automatic Transfer Switches are designed for residential and light commercial critical/non-life

More information

ASCO Power Transfer Load Centers. Power Switching & Controls for Business-Critical Continuity

ASCO Power Transfer Load Centers. Power Switching & Controls for Business-Critical Continuity ASCO Power Transfer Load Centers Power Switching & Controls for Business-Critical Continuity ASCO, the world leader in power switching & controls Streamline with an Integrated System ASCO Power Transfer

More information

Transfer Switches Contactor-Based Designs

Transfer Switches Contactor-Based Designs September 2011 Sheet 215 Transfer es -Based Designs Transfer es, 100 1200A, Dual Drawout General Description Transfer es, 100 1200A, Dual Drawout Transfer General Description A bypass isolation transfer

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16289 to 26 35 00, removed references to other section numbers 10/14/14 Amend text in section B

More information

Transfer Switches Magnum-Based Designs

Transfer Switches Magnum-Based Designs September 2011 Sheet 250 -Based Designs Floor-Standing General Description Floor-Standing Floor-Standing Transfer Switch General Description Taylor s transfer switches are designed for a variety of standby

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

Transfer Switches Magnum-Based Designs

Transfer Switches Magnum-Based Designs -Based Designs Floor-Standing Transfer Switches General Description Sheet 25046 Isolation Transfer Switch Isolation Transfer Switch General Description A bypass isolation switch uses loadbreak isolation

More information

ASCO SERIES 230 Automatic Transfer Switch

ASCO SERIES 230 Automatic Transfer Switch ASCO SERIES 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Application Product Overview The Series 230

More information

O & M Manual for the Generac ATC-300+ Automatic Transfer Switch Controller

O & M Manual for the Generac ATC-300+ Automatic Transfer Switch Controller O & M Manual for the Generac ATC-300+ Automatic Instruction Booklet Description Page Introduction................................ 2 Hardware Description.......................... 7 Status Monitoring and

More information

ASCO SERIES 300 Service Entrance Power Transfer Switch

ASCO SERIES 300 Service Entrance Power Transfer Switch ASCO SERIES 300 Service Entrance Power Transfer Switch The ASCO Service Entrance Power Transfer Switch combines automatic power switching with the necessary disconnecting, grounding, and bonding required

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch Global Headquarters-Florham Park, New Jersey ASCO was founded in 1888, and manufactured the first ATS in 1920, ASCO focuses on the development of ATS, and has become

More information

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Product Data Sheet Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ZEE BIPLANE IECAX480V225A Main Disconnect Panel Bevco Engineering Company, Inc. CONFIDENTIAL

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W)

SECTION METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W) METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W) PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings.

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Product Overview The Series 230 automatic transfer

More information

Series 300 POWER TRANSFER SWITCHES MAXIMUM RELIABILITY & EXCELLENT VALUE FEATURES

Series 300 POWER TRANSFER SWITCHES MAXIMUM RELIABILITY & EXCELLENT VALUE FEATURES Series 300 POWER TRANSFER SWITCHES MAXIMUM RELIABILITY & EXCELLENT VALUE With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ONE ARTIS ZEEGO / ZEEGO.ZEN ARTIS ZEE MULTIPURPOSE SINGLE PLANE IECAX480V125A Main Disconnect Panel Bevco Engineering

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

SECTION ELECTRICAL CONTROL DEVICES

SECTION ELECTRICAL CONTROL DEVICES ELECTRICAL CONTROL DEVICES PART 1 GENERAL 01 02 03 04 05 SCOPE The Contractor shall furnish and install, where indicated on the drawings, equipment with electrical control devices installed as specified

More information

These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads.

These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads. 1 General 1.1 Summary These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads. 1.2 Standards The PowerHub 2 PDU shall be listed to the applicable

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Power Series Transfer Switch

Power Series Transfer Switch Service Entrance Rated Power Frame Type losed Transition Power Series Transfer Switch 1000-5000 mps Power Series 1 of 5 utomatic Transfer Switch, 100% Service Entrance Rated 1000 5000, up to 600V, 50/60

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Transfer Switch rated 1000 amperes in Type 1 enclosure. Closed Transition Transfer Switching ASCO Automatic Closed Transition

More information

reliable company...caterpillar

reliable company...caterpillar The markets most reliable technology... from the industryʼs most reliable company...caterpillar Caterpillar switchgear with PowerLynx technology has been designed to integrate hand-inglove with Caterpillar

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

FTA1350 WYE-DELTA CLOSED FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1350 WYE-DELTA CLOSED FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1350 WYE-DELTA CLOSED FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE NOTE: The drawings included herein are for standard controllers. Actual "as built" drawings may differ from those seen here. ASCO

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95 Part 1 - GENERAL ASEA BROWN BOVERI ABB Industrial Systems Inc. Standard Drives ACH500-06E Effective 6/1/95 Sample Specification for Adjustable Frequency Drives (2 to 400 HP) for Variable Torque Applications

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

C. New or replacement products installed in existing facilities shall be consistent with existing equipment. September 2012, rev 00 26 2923 Variable Frequency Controllers PART 1. GENERAL 1.01 Description A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width

More information

This section applies to the design and installation relating to automatic transfer switches (ATS).

This section applies to the design and installation relating to automatic transfer switches (ATS). Design Guide Basis of Design This section applies to the design and installation relating to automatic transfer switches (ATS). Design Criteria Clearly indicate in the drawings and specifications whether

More information

SECTION 16482A MOTOR CONTROL CENTERS LOW VOLTAGE (FREEDOM)

SECTION 16482A MOTOR CONTROL CENTERS LOW VOLTAGE (FREEDOM) PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE A. The Contractor shall furnish and install the motor control centers as specified herein and as shown on the contract drawings. RELATED SECTIONS A. Section 16475

More information

Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches

Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches RTS SERIES RTS Series Medium-Voltage Circuit Breaker-Type Automatic Transfer Circuit breaker medium-voltage

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

Series 230 Automatic Transfer Switch

Series 230 Automatic Transfer Switch Series 230 Automatic Transfer Switch The Recognized Leader in Power Transfer Switch Technology Offers the Most Advanced Transfer Switches in the World. Application Product Overview The Series 230 automatic

More information

Power Meter PowerMonitor 500

Power Meter PowerMonitor 500 ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific

More information

Experience, innovation and reliability

Experience, innovation and reliability automatic transfer switches 40 1200A Experience, innovation and reliability Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability

More information

GE Zenith ZDEC Modular Paralleling Switchgear

GE Zenith ZDEC Modular Paralleling Switchgear GE Zenith ZDEC 2020 Modular Paralleling Switchgear ZDEC 2020 Has the Solution Healthcare and Critical Facilities Demand Generator Paralleling Systems that are Flexible design compatible with multiple brands

More information

soft load power transfer solutions for continuous, reliable power

soft load power transfer solutions for continuous, reliable power We Keep Your Power On A S C O P O W E R T E C H N O L O G I E S F L O R H A M P A R K, N E W J E R S E Y 0 7 9 3 2 U S A 8 0 0 9 3 7 A S C O W W W. A S C O. C O M ASIA AUSTRALIA BRAZIL CANADA GERMANY JAPAN

More information

Jockey Pump Controllers

Jockey Pump Controllers BR081001EN Microprocessor Based with Color Touchscreen Product Description ACROSS THE LINE Controllers operate across-the-line. Full voltage is applied to the motor for starting by the use of a single

More information

SECTION MOTOR CONTROL CENTERS

SECTION MOTOR CONTROL CENTERS MOTOR CONTROL CENTERS PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the motor control centers as specified herein and as shown on the contract drawings. 1.02 RELATED SECTIONS A.

More information

UW Purchase Specification Section

UW Purchase Specification Section Page 1 of 9 PART 2 GENERAL 2.01 DESCRIPTION A. Purpose 1. This section covers electrical service meters and sub-meters for use in the Owner's power distribution systems. 2.02 QUALIFICATIONS A. Approved

More information

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration Data Sheet Lighting Relay Panel Overview Leverage the Power of BAS Integration Exterior with Surface Mount Trim The Series UL Listed, Lighting Control Panel provides the capability to control high voltage

More information

Learning Module 29: Transfer Switch Equipment. 101 Basic Series

Learning Module 29: Transfer Switch Equipment. 101 Basic Series Learning Module 29: Transfer Switch Equipment 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 What Is A Transfer Switch? 6 Non-Automatic (Manual)

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

Power Series Transfer Switch

Power Series Transfer Switch ypass Isolation ontactor Type losed Transition Transfer Switch 100-1200 mps 1 of 5 ypass Isolation Transfer Switch 100 1200, up to 600V, 50/60 Hz 3 or 4 poles NEM 1 or 3R losed Transition UL1008 Listed

More information

SECTION SURGE PROTECTIVE DEVICES

SECTION SURGE PROTECTIVE DEVICES SECTION 16289 PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 24 11 This section specifies the furnishing, installation, and connection of the distribution switchboards. 1.2 RELATED WORK: A. Section 13 05 41, SEISMIC RESTRAINT

More information

Tmax molded case circuit breakers Specification guide

Tmax molded case circuit breakers Specification guide Tmax molded case circuit breakers Specification guide Tmax Specification Guide 1 Specification Number: 26 28 16.14 Product Name: MOLDED CASE CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings

More information

Power Series Transfer Switch

Power Series Transfer Switch Power Frame Type Open and Delayed Transition Power Series Transfer Switch 2000-5000 mps Power Series 1 of 5 utomatic Transfer Switch 2000 5000, up to 600V, 50/60 Hz 3 or 4 poles NEM 1 or 3R Open with Inphase

More information

SECTION VARIABLE FREQUENCY DRIVES

SECTION VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 DESCRIPTION This specification section establishes the requirements for variable frequency motor drives. The associated motor(s) shall be specified separate from the drive and listed

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

The ASCO 7000 Series. Protecting data centers, hospitals, airports, retail stores and other facilities

The ASCO 7000 Series. Protecting data centers, hospitals, airports, retail stores and other facilities Protecting data centers, hospitals, airports, retail stores and other facilities The ASCO 7000 Series Closed-Transition Sof t Load Power Transfer Switch gives you the flexibilit y to: Ensure the level

More information

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...

More information

VisoVac padmount fault interrupter

VisoVac padmount fault interrupter Network Protector Catalog Data CA024003EN New Issue VisoVac padmount fault interrupter General The medium voltage padmount vacuum fault interrupter from Eaton delivers economical, reliable and flexible

More information

Jockey Pump Controllers

Jockey Pump Controllers BR081001EN Microprocessor Based with Color Touchscreen Product Description ACROSS THE LINE Controllers operate across-the-line. Full voltage is applied to the motor for starting by the use of a single

More information

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control Key Benefits FM2 FEEDER Protection System Economical and compact feeder protection for low voltage feeders Comprehensive low voltage feeder management system - Integrated feeder protection and process

More information

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.

More information

Product Specifications

Product Specifications Product Specifications Models: USC-10001, USC-10002 USC-20001, USC-20002 USC-30001, USC-30002 Guide Specification for UniStar C Series Rack/Universal 1, 2, 3Kva Single-Phase, On-Line Double Conversoin

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

ASCO Medium Voltage Power Transfer Switches

ASCO Medium Voltage Power Transfer Switches ASCO Medium Voltage Power Transfer Switches Product information and specification guide ASCO protects medium voltage loads by offering maintainable and highly proven power transfer switches. The switches

More information

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent

More information

Power Series Transfer Switch

Power Series Transfer Switch Power Frame Type losed Transition Power Series Transfer Switch 1600-5000 mps Power Series 1 of 5 utomatic Transfer Switch 1600 5000, up to 600V, 50/60 Hz 3 or 4 poles NEM 1 or 3R losed Transition UL1008

More information

BSPD Surge Protective Devices

BSPD Surge Protective Devices BUSSMANN Supersedes December 2016 SERIES BSPD Surge Protective Devices High capacity Type 1 and Type 2 SPDs for overvoltage protection on Contents Description Page Introduction 2 Applications 2 Features

More information

Cutler-Hammer. Westinghouse Transfer Switch Equipment. IQ Transfer

Cutler-Hammer. Westinghouse Transfer Switch Equipment. IQ Transfer Westinghouse Transfer Switch Equipment IQ Transfer Setting a new standard with the most advanced microprocessor-based transfer switch logic available. It s programmable for superior reliability and versatile

More information