LTEC Heat Pump DDC Controller
|
|
- Mitchell Wells
- 5 years ago
- Views:
Transcription
1 Document No. 09 Rev., May, 00 LTEC Heat Pump DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) HP (Heat Pump) DDC Controller (Figure ). There are two platforms available, reduced point and full point (Figure ); each platform handles various application sets. Each application set has a default input/outputwiring configuration, shown in the wiring diagrams. See Figure through Figure 8. The Heat Pump Controller applications are provided in the following configurations: Single stage compressor with or without reversing relay, outside air damper, and auxiliary or perimeter heat control. Multistage compressor with or without reversing relay, outside air damper, and auxiliary or perimeter heat control. In addition to the listed inputs above, each platform can accept a series 080 through 08 LTEC room temperature sensor () with optional digital display, occupancy override push button and set point adjustment. Warning/Caution Notations WARNING CAUTION Personal injury/loss of life may occur if a procedure is not performed as specified. Equipment damage, or loss of data may occur if the user does not follow procedure as specified. /" (mm) " (mm) LON000R Figure. LTEC Controller open cover. Product Numbers 8 /8" (.mm) 8 /" (0mm) V V V AI/ DI AI/ DI AI/ DI AI/ DI AI/ DI J J J J J J A0 A0 D0 Vac H D0 Vac H D0 Vac H D0 Vac H 8 D0 9 Vac H 0 D0 Vac H D0 Vac H D08 Vac H Vac H H Part Number Application Input/Output 08 LTEC Heat Pump IN, DO 09 LTEC Heat Pump IN, 8 DO, AO LO /8" (8mm) HI LON00R Figure. LTEC Controller. Page of 9
2 Document No. 09 Rev., May, 00 Required Tools Pencil ESD wrist strap Small flat blade screwdriver Medium flat blade screwdriver Wire stripper Medium duty electric drill ¼ in (mm) hex nut bit Network Management Tool Bus interface and cables Prerequisites Room temperature sensor (), if required, is installed Power source of Vac, 0 Hz Class power trunk is available and has a sufficient VA rating for the controller, sensors and actuators If required, the controller enclosure is installed Supply to the unit is OFF Installation WARNING: The power must be turned OFF prior to wiring the unit. The following sections are included in these instructions: Controller Mounting Power Wiring Bus Wiring Replacing a Controller Controller Mounting. Using the controller as a template, position the controller vertically and mark the mounting hole locations on the mounting surface (terminal box or mounting enclosure).. Using the # selftapping screws (included), fasten the controller to the terminal box or enclosure.. Connect the Network Trunk (NOT polarity sensitive) cable to terminals and on J, (Figure ). Network Management Tool Connection Room Temperature Sensor Connection Service Pin LON00R Network Trunk Analog or Digital Input V AI/ DI V AI/ DI AI/ DI AI/ DI V AI/ DI J J J able on reduced point controller boards. J J J Cover Release Tabs A0 A0 A0 D0 Vac H D0 Vac H D0 Vac H D0 Vac H 8 D0 9 Vac H 0 D0 Vac H D0 Vac H D08 Vac H Vac H H Figure. LTEC Wiring Designations. Mounting Holes () Analog Output Digital Output Vac Power. With primary power disconnected, connect vac power to terminal block J.. Connect the EGrnd terminal (E) to an earth ground. A proper ground source is required to protect the electronic circuits, for example, a cold water pipe, power panel ground (green wire) or other comparable ground sources.. Connect the input and output wiring for the appropriate HP (Heat Pump) application. Refer to the Terminal Designations section for complete information on LTEC wiring designations for 08 and 09 controllers. Page of 9
3 Document No. 09 Rev., May, 00. For input type selection, (digital, voltage, or current) see the jumper and connection information in Table. Each DO provides a normally open (NO) and Vac hot (H) terminal. Terminate both connections of a Vac load directly to the controller board. Floating control actuators require DOs and use wire connections. The Vac Common is switched through the Triac when the associated DO is energized. CAUTION: The controllers Digital Outputs (Dos) control Vac only. The maximum rating is VA for each DO. Use an interposing Vac relay for any of the following: VA requirements higher than the maximum 0 or 0 Vac or higher Control load requires DC power Separate transformers used to power the load Need for dry contacts 8. Plug the room temperature sensor () cable into the port on the left side of the controller. See Figure. 9. Remove one of the controller neuron ID labels (two part label located at the top of the controller board). Record this number as directed in a floor plan layout, job log or place the selfadhesive label on the outside of the controller case or inside the cover. This number is unique to the controller electronics. Power Wiring Each Controller requires a source of Vac, 0 Hz Class II power supply. The base rating of the controller and the sum of the sensor, actuators and relay connected dictates the VA rating. Bus Trunk wiring Bus wiring must be accomplished using approved cables only. These include unshielded and shielded (where specified) two conductor AWG Level IV cable. WARNING: Use the recommended LonWorks cable: AWG shielded or unshielded, Level IV per NEMA standards (not equivalent to EIA/TIA Level cable). Connect Air brand cable, / pair, stranded, unshielded, blue plenum jacketed, Level IV, Part Number WP00 or an approved equal for bus wiring. Bus wiring is NOT polarity sensitive. The LTEC Controllers use the FTT0 transceiver that allows free topology wiring. This includes Ttaps, stars, branches, loops as well as standard daisy chain. In all cases, max bus wire length, including each sensor cable, cannot exceed 00 meters (0 feet). For bus lengths that exceed 00 meters, (0 feet) a twoport or threeport repeater can be used (Part number 80 and 8 respectively). This will allow three separate bus lengths of 00 meters. See the LonTalk Two and Three Port Repeater installation instructions, (P/N: 00) for additional information and limitations. Each bus segment ( without repeater, with repeater) requires a pair of terminating resistors (Part number 8 9 packs of 00) that can be located together anywhere on the segment, at the field panel or repeater. Page of 9
4 Document No. 09 Rev., May, 00 Terminal Designations Figure shows the LTEC wiring designations and locations for both controllers. All inputs and outputs physical connections are preconfigured per application number selected. The wiring diagrams (Figure through Figure 8) are shown using the full point controllers (shaded terminals). Reduced point controllers should be used when the additional input/output points are not required. AI/DI AI/DI AI/DI AI/DI AI/DI LON008R V V V J J J J Figure. Terminal Designations. Input Ports LTECs have configurable, flexible input ports. Table lists each input port and indicates the input options available for that port. Some models have only the first four inputs, while others have five inputs. (Only VAV models have the integral flow sensor port). Table. LTEC Input Port Configuration Options. Input Type/Number Configurable Options Notes RJ input jack Temperature sensor 080 through 8 wall modules Setpoint adjustment Override button AI/DI 00K thermistor Temperature Input AI/DI 00K thermistor Temperature Input AI/DI Percent Input Temperature transmitter 00Vdc or 00/0 ma AI/DI AI/DI Percent Input Temperature transmitter Percent Input Temperature transmitter 00Vdc or 00/0 ma 00Vdc or 00/0 ma Integral Flow Sensor n/a VAV/CV only Page of 9
5 Document No. 09 Rev., May, 00 AI/DI AI/DI AI/DI AI/DI AI/DI LON009R LON000R LON00R LON00R LON0009R Table. Input Configuration and Jumper Settings. 00 K thermistor 00 Vdc input 00/ 0 ma input J J J J LON00R J LON00R J J LON00R LON00R T T J J LON00R LON00R 00Vdc 00 Vdc LON000R 00 Vdc J J LON000R J LON00R J J LON00R LON008R 0mA 0mA LON00R 00 ma (0 ma) J J LON009R J LON00R J J. Resistor, 99 Ω %, part number (8) for AI current input (00 ma).. See Figure for physical location of s and external terminal block connections.. The location of physical inputs must match a specific application wiring diagram; see Figure through Figure 8. Output Ports LTECs have configurable, flexible output ports. Wiring diagrams (Figure through Figure 8) indicate how these outputs are used in each application. Each application has preassigned output configurations. Some models have only the first six Digital outputs and no Analog outputs, while other have all eight Digital outputs and two Analog outputs. Replacing a Controller Replacement of a LTEC requires you to record, reenter, and/or update the initial point values from the old controller before replacing it. LTEC Network Connections (data sharing between controllers; Connections tab in Network Management Tool) () do not need to be recorded if using s Replace feature. will reapply the Connections after the Replace. However, if the old controller is to be deleted in, then all connections will need to be recorded first so they can be reentered after the new controller is added. Page of 9
6 Document No. 09 Rev., May, 00. To record Initial Values, before disconnecting the old controller, do one of the following: If the controller is communicating with the field panel, update the controller initial values at the field panel. If the controller does not communicate with the field panel, but does communicate with the, record the appropriate configuration points on Table at the end of these instructions. If the old controller is not communicating at all, record all data available in the Point Definition Report, or from the last valid initial values uploaded from the controller.. Disconnect power to the controller (remove the power connector, terminal block J).. Disconnect all input and output removable terminal blocks and insure they do not short out.. Remove the and network (RJ) connectors.. Remove the controller board by pressing the internal tabs and lifting the board out (or the complete controller, by removing the mounting screws).. Install the new controller board (or base and board).. Install jumpers. Ensure jumpers for AI/DI and AI/DI are configured to match the removed controller, see Table. Ensure AI/DI, AI/DI and AI/DI, external jumpers, remain in place or are reinstalled. 8. Remove one of the Neuron ID labels (two part label located at the top of the controller board). Record this number as directed; on a floor plan layout, job log or inside the cover. This number is unique to the controller electronics. It is imperative that the old neuron label be removed or covered. 9. Reconnect input and output terminal blocks. 0. Reconnect and network (RJ) connectors.. Reconnect power to controller, terminal block J.. Connect to the LTEC or L model MEC.. Run and use Replace to replace the old controller with new one. If the replacement controller was previously used elsewhere (not in factory packaging) the factory defaults must be reestablished as follows: Using, select the controller, select Application Configuration and apply the Set to Defaults command.. Apply the appropriate Configuration Template.. Restore initial values as follows: MMI: If a field panel update was performed, the LTECs initial values will be loaded automatically. : If a field panel update was NOT performed, set the initial values previously recorded in Table.. : Verify LTEC Connections are correct, update as needed.. Save the peak database (.pkd file) to flash/file as needed. Replacement installation is complete. Disposal As an aid to environmentally responsible disposal, the larger plastic components bear a recycle symbol. The controller should not be disposed of with domestic waste. The printed circuit board and plastic components should be disposed of separately in accordance with local regulations. Page of 9
7 Document No. 09 Rev., May, 00 LTEC HP Application Wiring Diagrams Room Sensor Network Trunk *Mixed Temp Sensor Spare Temp Sensor Fan Status DI *Low Temp Sensor DI Jumper OCC Sensor DI V V V AI/ DI AI/ DI AI/ DI J AI/ DI J AI/ DI J J J A0 A0 A0 D0 Vac H D0 Vac H D0 Vac H D0 Vac H 8 D0 9 Vac H 0 D0 Vac H D0 Vac H D08 Vac H OA Damper Act. 00 Vdc Perimeter Htg. Coil 00 Vdc Terminal Fan Relay Reversing Relay DO DX Stage Clg. Aux Heat Stage OA Damper Act. Perimeter Htg. Coil J Vac H H Vac Power Ground LON80WDR able on reduced point controller boards. *Required Sensor Figure. Application 80 HP with Reversing Relay and Auxiliary Heat (08 or 09). Room Sensor Network Trunk *Mixed Temp Sensor Spare Temp Sensor Fan Status DI *Low Temp Sensor DI Jumper OCC Sensor DI V V V AI/ DI AI/ DI AI/ DI J AI/ DI J AI/ DI J J J A0 A0 A0 D0 Vac H D0 Vac H D0 Vac H D0 Vac H 8 D0 9 Vac H 0 D0 Vac H D0 Vac H D08 Vac H OA Damper Act. 00 Vdc Perimeter Htg. Coil 00 Vdc Terminal Fan Relay DX Stage Clg. DX Stage Htg. Aux Heat Stage OA Damper Act. Perimeter Htg. Coil J Vac H H Vac Power Ground LON80WDR able on reduced point controller boards. *Required Sensor Figure. Application 80 HP without Reversing Relay, with Auxiliary Heat (08 or 09). Page of 9
8 Document No. 09 Rev., May, 00 Room Sensor Network Trunk *Mixed Temp Sensor Spare Temp Sensor Fan Status DI *Low Temp Sensor DI Jumper OCC Sensor DI V V V AI/ DI AI/ DI AI/ DI J AI/ DI J AI/ DI J J J A0 A0 A0 D0 Vac H D0 Vac H D0 Vac H D0 Vac H 8 D0 9 Vac H 0 D0 Vac H D0 Vac H D08 Vac H OA Damper Act. 00 Vdc Perimeter Htg. Coil 00 Vdc Terminal Fan Relay Reversing Relay DX Stage DX Stage OA Damper Act. Aux Heat Stage Aux Heat Stage J Vac H H Vac Power Ground LON80WDR able on reduced point controller boards. *Required Sensor Figure. Application 80 HP stage with Reversing Relay and Auxiliary Heat (08 or 09). Room Sensor Network Trunk *Mixed Temp Sensor Spare Temp Sensor Fan Status DI *Low Temp Sensor DI Jumper OCC Sensor DI V V V AI/ DI AI/ DI AI/ DI J AI/ DI J AI/ DI J J J A0 A0 A0 D0 Vac H D0 Vac H D0 Vac H D0 Vac H 8 D0 9 Vac H 0 D0 Vac H D0 Vac H D08 Vac H OA Damper Act. 00 Vdc Perimeter Htg. Coil 00 Vdc Terminal Fan Relay DX Stage Clg. DX Stage Clg. DX Stage Htg. DX Stage Htg. Aux Heat Stage OA Damper Actuator J Vac H H Vac Power Ground LON80WDR able on reduced point controller boards. *Required Sensor Figure 8. Application 80 HP stage without Reversing Relay, with Auxiliary Heat (08 or 09). Page 8 of 9
9 Document No. 09 Rev., May, 00 Table. Record of Controller Modified Initial Values. Point Number Descriptor Initial Value Point Number Descriptor Initial Value Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. 00 LonMark, LonWorks, and Neuron are trademarks of Echelon Corporation registered in the US and other countries. Landis and Staefa Division 000 Deerfield Parkway Buffalo Grove, IL 0089 U.S.A. Your feedback is important to us. If you have comments about this document, please send them to Document No. 09 Printed in the U.S.A. Page 9 of 9
LTEC Unit Ventilator DDC Controller
Document No. 09 Rev., May, 00 LTEC Unit Ventilator DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) UV (Unit Vent)
More informationBACnet PTEC Unit Conditioner/Fan Coil P. Controller. Control Applications. Accessories. Product Description. Warning/Caution Notation
Installation Instructions BACnet PTEC Unit Conditioner/Fan Coil Controller Figure 1. BACnet PTEC Unit Conditioner/Fan Coil Controller. Control Applications 6540, 6541, 6550, 6551, 6552, 6553 and 6554 Product
More informationTEC Unit Conditioner Controller
Document No. 540-1026 TEC Unit Conditioner Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2040 and 2041 2050 through 2054 Product Description
More informationBACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation
BACnet PTEC Heat Pump Multi-Stage Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 6673, 6674 Product Description These instructions explain
More informationTEC Terminal Box (VAV) Controller
Document No. 540-1025 TEC Terminal Box (VAV) Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2020 through 2027 Product Description These
More informationTEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.
Document No. 540-1031 TEC VAV with 0-10V AO Heat Modulation and CO2 Monitoring Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2843,
More informationTEC Heat Pump Multi-Stage Controller. Control Applications. Accessories. Product Description. Product Numbers. Warning/Caution Notation
Document No. 540-1024 TEC Heat Pump Multi-Stage Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2273 and 2274 Product Description These
More informationBACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation
BACnet PTEC Terminal Box (VAV) Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 6600 through 6607 Product Description These instructions
More informationRoom Pressurization Controller Electronic Output
Document No. 540-1033 Room Pressurization Controller Electronic Output Product Description These instructions explain how to field install or replace a Room Pressurization Controller (RPC) Electronic Output
More informationRoom Pressurization Controller Pneumatic Output
Document No. 540-1032 Room Pressurization Controller Pneumatic Output Product Description These instructions explain how to field install (pages 1 through 3) or replace (pages 3 through 4) a Room Pressurization
More informationSiemens TEC Extended I/O Controller
Document No. 540-1028 TEC Extended I/O Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2497 Product Description These instructions explain
More informationTRUNK TX RX + - S + - S DO LEDS FLN TRUNK TERMINATIONS INPUT/OUTPUT TERMINATIONS TRANSMIT LED
Heat Pump Controller Single Stage COVR CONTROLLR BOARD MOUNTING HOL (2) C H DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 DI 3 DI 2 FLN TX RX + - S BST RTS MOUNTING RAIL + - S TC0168R5 POWR TRMINATIONS DO LDS FLN TRMINATIONS
More informationSLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)
SLX Series Document No. 997-1000 Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L) Free Programmable Controllers (SLX-PC-203, SLX-PC-300, SLX-PC-400, SLX-PC-500
More informationDESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications
3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for
More informationRWD68U Universal Controller
Document No. 155-738 RWD68U Universal Controller Description Features Product Number The Universal Controller is intended for heating, air conditioning, ventilation and refrigeration in comfort control
More informationFree Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit
Document No. 155-324 Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit Description Features Application Product Number Room temperature controller for four-pipe fan coil units.
More informationHardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN
Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN November 2005 Tracer MP581 Programmable Controller Hardware
More informationInstallation and Operation. Tracer MP501 Controller CNT-SVX08B-EN
Installation and Operation Tracer MP501 Controller CNT-SVX08B-EN Installation and Operation Tracer MP501 Controller CNT-SVX08B-EN April 2005 CNT-SVX08B-EN Tracer MP501 Controller Installation and Operation
More informationNEUROLOGIC RESEARCH CORPORATION MODEL 2500
NEUROLOGIC RESEARCH CORPORATION MODEL 2500 NETWORK HUMISTAT Compact, self-contained dehumidifier controller. 0.5 degrees C accuracy typical. RH sensor is digitally calibrated for 2% accuracy. Open communication
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationPXC Compact Unitary Equipment Controller (UEC)
Document No. 553-169 PXC Compact Unitary Equipment Controller (UEC) Product Description The PXC Unitary Equipment Controller (UEC) is an MS/TP device that can be configured as a programmable, stand-alone
More informationTerminal Equipment Controller Enclosure
Document No. 550-196 Terminal Equipment Controller Enclosure Product Description A Terminal Equipment Controller enclosure is a general-purpose metal cabinet with a removable cover that houses an electronic
More informationContent. Product Description
EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product
More informationRTD-W Installation Instructions
RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485
More informationTEC Controller Extended I/O Application 2497 with Slave Mode Application Application Note Building Technologies
TEC Controller Extended I/O Application 2497 with Slave Mode Application 2489 Application Note 140-1074 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 4 Hardware Outputs... 4
More informationBA/BS4S Temperature Sensor Installation & Operating Instructions
Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.
More informationSiemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control
Technical Specification Sheet Document No. 149-844 August 12, 2011 Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control Returns from power failure without operator intervention.
More informationCTR21, CTR22, CTR23, and CTR24 Wall Modules
CTR21, CTR22, CTR23, and CTR24 Wall Modules FEATURES SPECIFICATION DATA The CTR21, CTR22, CTR23, and CTR24 family of wall modules include: Models with setpoint adjustment. Models with occupied/unoccupied
More informationOpen Processor with Square D Driver
Document No. 565-922 Open Processor with Square D Driver PRODUCT DESCRIPTION Each Open Processor (Figure 1) contains the main processor, memory, and communications circuitry for connecting APOGEE to another
More informationFX-2 Control Board ASY-360-XXX Setup and Configuration Guide
FX-2 Control Board ASY-360-XXX Setup and Configuration Guide Micro Air Corporation Phone (609) 259-2636 124 Route 526. WWW.Microair.net Allentown NJ 08501 Fax (609) 259-6601 Table of Contents Introduction...
More informationFEATURES DESCRIPTION MODEL 110B. Power Supply
FEATURES Extends wiring distance of FT-10 LonWorks Networks. (2) channels using a single Model 110B. Up to 10 channels using (5) Model 110B. Low cost alternative to routers configured as repeaters. Wring
More informationMAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new Controller.
More informationModular Room Control (MRC) Series Expansion Board
Installation Instructions Issue Date December 13, 2002 Modular Room Control (MRC) Series Expansion Board Application The Modular Room Control (MRC) system has the ability to expand its input/output capabilities
More informationActuator Commissioning Tool
Document No. 129-287 Actuator Commissioning Tool Product Description The 985-047 Actuator Commissioning Tool provides a portable instrument for exercising, calibrating, and testing resistive, proportional
More informationH7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors
H765B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors APPLICATION The H765B, H7635B, H7655B Duct-Mount and H7635C Outdoor-Mount Humidity/Temperature Sensors are universal Relative
More informationTECH/DATA SHEET. Application. Model Chart. Installation. slon-v1. slon-v2. slon VAV Controller
TECH/DATA SHEET s-v1 s-v2 s VAV Controller Application Solidyne s s-v1 and s-v2 VAV Controllers are interoperable MARK -compliant variable air volume controllers. These controllers provide pressure independent
More informationOpenAir Electronic Damper Actuator GDE/GLB Rotary Non-spring Return
OpenAir Electronic Damper Actuator GDE/GLB Rotary Non-spring Return Document No. 9-67 EA678R a b e d c f a. Actuator b. Position indicator c. Mounting bracket d. Mounting screws e. 4 mm hex key f. Shaft
More informationSiemens BACnet Programmable TEC Unit Conditioner Controller
Technical Specification Sheet Document No. 149-831 September 24, 2014 Siemens BACnet Programmable TEC Unit Conditioner Controller Returns from power failure without operator intervention. No calibration
More informationTemperature controller Ducted systems
2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master
More informationInstalling the Tracer MP503 Input/Output Module Ordering number: ,
Installing the Tracer MP503 Input/Output Module Ordering number: 4950 0490, 4950 0590 Product overview The Tracer MP503 input/output (I/O) module is a field-installed device used to monitor inputs and
More informationSiemens BACnet Programmable TEC Unit Vent Controller for Smoke Control
Technical Specification Sheet Document No. 149-841 August 12, 2011 Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control The Siemens BACnet PTEC Unit Vent Controller provides high performance
More informationPowermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control
Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control Description Features Application The Powermite 599 MT Series SAS Electronic Valve Actuator requires a 24 Vac
More informationReplacing the Power Supply
APPENDIX B This appendix includes information on how to replace the power supply for the Cisco AS550XM universal gateway and contains the following sections: Safety Recommendations, page B-1 Required Tools
More informationSiemens BACnet Programmable TEC Unit Vent Controller
Technical Specification Sheet Document No. 149-833 August 12, 2011 Siemens BACnet Programmable TEC Unit Vent Controller The Siemens BACnet PTEC Unit Vent Controller provides high performance Direct Digital
More informationInstallation & Operation Guide
Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief
More informationMicroTech 2000 Water Source Heat Pump Unit Controller
Installation Manual IM 660-4 Group: Controls Part Number: IM 660 Date: June 2012 Supersedes: IM 660-3 MicroTech 2000 Water Source Heat Pump Unit Controller NOTICE Use this manual to physically install
More informationSiemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller
Technical Specification Sheet Document No. 149-831 August 12, 2011 Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller No calibration required, thereby reducing maintenance costs. PID
More informationRDF Series Room Temperature Controllers
Document No. 19-49 RDF Series Room Temperature Controllers Product Description Room Temperature Controllers with LCD for twopipe (with and without an electrical heater) and fourpipe fan coil units. Installation
More informationBACnet Flow Controller for Fan Filter Units
MANUAL SERVICE + INSTALLATION BACnet Flow Controller for Fan Filter Units BFC Series v300 Issue Date: 08/23/17 2017 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General
More informationBACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies
BACnet PTEC Controller Constant Volume - Cooling Only, Application 6660 Application Note 140-1107 Building Technologies Table of Contents Overview... 4 BACnet... 5 Hardware Inputs... 5 Room Unit Identification...
More informationTAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta
TAC Xenta TAC Xenta 101-VF 3-Speed Fan Coil Controller TAC Xenta 101-VF is a zone controller intended primarily for fan coil applications with the ability to control fans with multiple speeds, with one
More informationDS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION
DS 10.103A 10/99 MN 500 WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION Order Type: MNN-50-100 MicroNet NCP 500 Controller I/A Series MicroNet 500 Series Controllers
More informationTAC Xenta 121-FC Programmable Fan Coil Application
TAC Vista TAC Xenta 121-FC Programmable Fan Coil Application TAC Xenta 121-FC is an easily programmable controller intended for both 2-pipe and 4-pipe applications, with or without re-heat. It can be configured
More informationTX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013
Technical Specification Sheet Document No. 149-476 July 18, 2013 TX-I/O Product Range TX-I/O is a range of I/O modules, with associated power and communication modules, for use within the APOGEE Automation
More informationH7625A, H7635A Humidity/Temperature Sensors
H765A, H7635A Humidity/Temperature Sensors WALL-MOUNT MODELS APPLICATION The H765A, H7635A Wall-Mount Humidity/Temperature Sensors are universal Relative Humidity transmitters that can be powered with
More informationNon-communicating room controllers
3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,
More informationTX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018
Technical Specification Sheet Document No. 149-476 February 20, 2018 TX-I/O Product Range TX-I/O is a range of I/O modules, with associated power and communication modules, for use within the APOGEE Automation
More informationInstallation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING
Installation and Operation Manual ETV Platinum Plus Electronic Tempering Valve with Safeguard WARNING This Heat-Timer control is strictly an operating control; it should never be used as a primary limit
More informationISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL
ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 ES-Key 18 Input module (selectable polarity) with 3 outputs (selectable polarity) with 1 analog (selectable 0-5V or 4-20mA)
More informationNon-communicating room controllers
3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For
More informationTAC Xenta 121-HP Programmable Heat Pump Application
TAC Vista TAC Xenta 121-HP Programmable Heat Pump Application TAC Xenta 121-HP is an easily programmable controller intended for heat pumps, with or without re-heat. It can be configured for use with 1,
More informationActuating Terminal Equipment Controller (ATEC) VAV with Reheat. Start-up Procedures Building Technologies Restricted
Actuating Terminal Equipment Controller (ATEC) VAV with Reheat Start-up Procedures 140-1202 Building Technologies 2015-05-06 Restricted Table of Contents... 4 Verifying Power to the Controller... 4 Setting
More informationSylk I/O Devices APPLICATION FEATURES PRODUCT DATA
Sylk I/O Devices APPLICATION PRODUCT DATA The Sylk IO devices are part of the Spyder family. The three IO devices are designed to seamlessly integrate with Spyder with relay controllers using only Sylk
More informationSiemens BACnet VAV Actuator
Technical Specification Sheet Document No. 149-481 May 30, 2012 Siemens BACnet VAV Actuator Setpoints and control parameters assigned and changed locally or remotely. Setpoints and control parameters stored
More informationRXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications
s 3 856 Desigo RXC Room controller RXC39.5 Communicating room controller for fan-coil applications The RXC39.5 room controller is used for temperature control in individual rooms. For fan-coil systems
More informationMX1 Reversible AC Motor Controller. Supplementary Wiring Examples
MX1 Reversible AC Motor Controller Supplementary Wiring Examples DANGER Electrocution Hazard! Ensure all power is disconnected before servicing or wiring. Install all electrical equipment and wiring in
More informationJunos WebApp Secure 5.0 Hardware Guide
Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a
More informationSpyder Lon Programmable, VAV/Unitary Controllers
Spyder Lon Programmable, VAV/Unitary Controllers Controller Model Programmable Type Universal Inputs (UI) Table. Controller configurations. Digital Inputs (DI) PRODUCT DESCRIPTION PRODUCT DATA The PUL0S,
More informationSiemens BACnet Programmable TEC Constant Volume
Technical Specification Sheet Document No. 149-852 September 24, 2014 Siemens BACnet Programmable TEC Constant Volume Returns from power failure without operator intervention. No calibration required,
More informationPLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!
TUC2 / TUCH2 Model Series Installation Instructions PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION! APPLICATION The TUC2 provides temperature space monitoring with a backlit LCD. The TUCH2 provides
More informationDatasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview
Datasheet BACnet B-ASC Powered Terminal Unit Programmable Controllers Overview Applications Meets the requirements of the following applications: Fan Coil Units Heat Pumps Chilled Beams Reversible Ceiling
More informationSiemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller
Technical Specification Sheet Document No. 149-834 August 23, 2010 Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller The Siemens BACnet PTEC VAV with Series Fan and
More informationETM-2050/ETM-2051 Service Manual
Introduction Novar s Electronic Thermostat Modules (ETMs) are intelligent control modules that provide local, direct digital control of unitary, packaged, staged HVAC systems. This document: Describes
More informationAppController overview and specifications
AppController CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-477-01 2/28/2018 Verify that you have the most current version of this
More informationActuating Terminal Equipment Controller (ATEC) VAV with Reheat - Cooling and Heating, Application Application Note
Actuating Terminal Equipment Controller (ATEC) VAV with Reheat - Cooling and Heating, Application 2501 Application Note 140-1220 Building Technologies Table of Contents Overview... 4 Hardware Inputs...
More informationENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.
TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application
More informationTX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007
Technical Specification Sheet Document No. 149-476 January 24, 2007 TX-I/O Product Range Description TX-I/O is a line of I/O modules with associated power and communication modules for use within the APOGEE
More informationField Installation Manual External Bolt-On Economizer for ComPac I Air Conditioners
Field Installation Manual External Bolt-On Economizer for ComPac I Air Conditioners Models: ComPac AVPA 42-48-60 The following instructions describe how to install the Marvair External Bolt-On Field Installed
More informationProduct Manual SZ2141
Product Manual SZ11 Refrigeration Controller Communicating Controls Description The SZ11 is a microprocessor-based refrigeration controller and alarm interface designed to control three coolers or freezers
More informationXT-9100 Technical Bulletin
System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX
More informationIQ-SBS LCU Series Installation Instructions
Installation Instructions LCU-1 The IQ-SBS LCU-1 is a self-contained device for integrating control of facility lighting with IQ-SBS. The LCU-1 controls lighting zones, accepts input from override switches
More informationX47.CE Product Guide
X47.CE Product Guide Table of Contents Table of Contents... Page 1 Overview and General Concept... Page 2 Features... Page 2 Technical Overview... Page 3 Installation... Page 5 Commissioning... Page 5
More informationSED2 VFD NEMA Type 3R Bypass/Air Conditioner
SED2 VFD NEMA Type 3R Bypass/Air Conditioner Description The NEMA Type 3R Bypass with Air Conditioner allows SED2 to be employed in a harsh environment. The SED2 is designed specifically for HVAC applications
More information599 Series Zone Valve Actuator SF Series Electronic Valve Actuator, 2-position Control
599 Series Zone Valve Actuator SF Series Electronic Valve Actuator, 2-position Control Technical Instructions EA1021R1 Description The 599 SF Series electronic zone valve actuators, accepts 24 Vac, 120
More informationCOND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.
Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER
More informationElectrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationRXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13
s 3 875 RXB Room controller Communicating room controller for fan-coil applications FC-13 RXB39.1 The RXB39.1 room controller is used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil
More informationTAC Xenta 301. Controller, Freely Programmable
TAC Xenta TAC Xenta 300 Controller, Freely Programmable TAC Xenta 300 belongs to a family of freely programmable controllers designed for small and medium-sized heating and air handling systems. A TAC
More informationRXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station
s 3 836 3836P01 Desigo TRA PL-Link IO Block Use with PXC3 series room automation station RXM39.1 The PL-Link IO Block contains the inputs and outputs controlled by a room automation station via PL-Link.
More informationT7560A1036 Digital Wall Module
T7560A1036 Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. T7560A1036
More informationSubmittal Data Sheet intelligent Touch Manager DCM601A71
For use with the following VRV Models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXTQ, FXUQ, FXZQ, VAM For use with the following Daikin SkyAir Models: FAQ, FBQ, FCQ, FHQ, FTQ Capacity:
More informationSiemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller
Technical Specification Sheet Document No. 149-851 September 24, 2014 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides
More informationInstallation Guide. Room Temperature Sensors. Mounting. Location and Cover Removal (All) STE-6011 Only. STE-6010/6013/6015 Only
Room Temperature Sensors STE-6010/6011/6013/6015 Mounting Location and Cover Removal (All) Install the sensor on an inside wall where it can sense the average room temperature and be away from direct sunlight,
More informationDual Digital Module Technical Guide
Factory Packaged Controls Coil Products Dual Digital Module Table of Contents OVERVIEW... 3 INSTALLATION AND WIRING... 4 Environmental Requirements...4 Mounting...4 Power Supply and Communications...4
More informationStryker Lon Configurable Controllers
Stryker Lon Configurable Controllers SPECIFICATION DATA FEATURES GENERAL The CVL4022AS-VAV1 and CVL4024NS-VAV1 controllers are part of the Stryker family. The controllers are Free Topology Transceiver
More informationVC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide
Beyond Comfort VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide August 10 th, 2010 (For Commercial and Lodging HVAC Fan Coil Applications) 028-0296-R1-LIT-VC3000-E01 Index
More informationInstallation Instructions for UL Rev A
NetController II Installation Instructions for UL 864 30-3001-1008 Rev A Mounting Screw Andover Continuum Power Supply Connector Third-Party Power Supply Connector I/O Bus Connector Cover Mounting Screw
More informationSuitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.
TUC03 Configurable Terminal Unit Controller Product Bulletin The TUC03 Configurable Terminal Unit Controller is designed specifically to provide direct digital control of terminal unit applications with
More informationAppController overview and specifications
AppController CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-477-01 10/25/2018 Verify that you have the most current version of this
More informationBACnet Terminal Box (VAV) Controller
Technical Specification Sheet May 30, 2012 BACnet Terminal Box (VAV) Controller Figure 1. BACnet Terminal Box Controller. The BACnet Terminal Box Controller (Figure 1) provides high performance Direct
More information