CSC-211 Multifunction Protection IED Product Guide

Size: px
Start display at page:

Download "CSC-211 Multifunction Protection IED Product Guide"

Transcription

1 CSC-211 Multifunction Protection IED Product Guide

2 Version V1.0 Doc. Code: 0SF (E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the instruction. If equipments do not agree with the instruction at anywhere, please contact our company in time. We will provide you with corresponding service. is registered trademark of Beijing Sifang Automation Co., Ltd. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted. This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible. The data contained in this manual is intended solely for the IED description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards as a result; it is possible that there may be some differences between the hardware/software product and this information product. Manufacturer: Beijing Sifang Automation Co., Ltd.

3 Overview CSC-211 series are selective, reliable and high performance multifunction protection IED (Intelligent Electronic Device), which are able to be applied for protection, control and measurement for following applications: Applicable in subtransmission network and distribution network with solidly earthed (grounded), low-resistance earthed, isolated or compensated neutral point Protection of feeders, capacitors, auxiliary transformers, bus coupler, etc. Used as backup protection IED for lines, transformers, reactors and busbar Providing control and monitoring functions of the circuit breakers, disconnector, etc. Supporting all functionalities required for automation system The standard version of CSC211 offers a wide range of protection functions by pre-configured function arrangement to fulfill most of common applications. The advanced version of CSC211, with enhanced hardware, same function library, and full programmable scheme logic with graphic software tool, is good at tailor- -made applications. The wide application flexibility and integration of the protection, monitoring and control functions in one device make the IED an excellent solution for both new installations and retrofitting of the existing stations.. 1

4 Feature Extensive multifunction IED including protection, control and monitoring functions Three pole tripping required in sub-transmission and distribution network A complete protection function library, includes: Overcurrent protection (50, 51, 67) Earth fault protection (50N, 51N, 67N) Neutral earth fault protection (50G, 51G) Sensitive earth fault protection (50Ns, 51Ns, 67Ns) Negative-sequence overcurrent protection (46) Thermal overload protection (49) Overload protection (50OL) Overvoltage protection (59) Undervoltage protection (27) Displacement voltage protection (64) Circuit breaker failure protection (50BF) Dead zone protection (50DZ) Synchro-check and energizing check (25) Auto-reclosing function (79) Unbalanced current or voltage protection Undercurrent protection (37) load shedding function Voltage transformer secondary circuit supervision (97FF) Current transformer secondary circuit supervision Fast overcurrent/busbar protection scheme using IEC61850 GOOSE- -message User definable LEDs, binary inputs and outputs. Primary apparatus local/remote control function Programmable interlock logic Tripping and closing circuit supervision Opening and closing lockout function CB status supervision Self-supervision to all modules in the IED Complete and massive reports recording, trip reports, alarm reports, startup reports and operation reports. Any kinds of reports can be stored no less than 40 items, and be memorized in case of power disconnection Up to two electric /optical Ethernet ports can be selected to communicate with substation automation system by IEC61850 or IEC protocols Up to two electric RS-485 port is able to communicate with substation automation system by IEC protocol Time synchronization via network 2

5 Feature (SNTP), pulse and IRIG-B mode Versatile human-machine interface, graphic or alphanumeric options Multifunctional software tools set for setting, monitoring, fault recording analysis, configuration, logic programming etc. 3

6 Function Protection functions Description ANSI Code IEC Logical Node Name IEC graphical symbol Current protection Overcurrent protection 50,51,67 PTOC Earth fault protection 50N, 51N, 67N PTEF 3I INV> 3I >> 3I >>> I 0INV> I 0>> I 0>>> Neutral earth fault protection Sensitive earth fault protection 50G, 51G 50Ns, 51Ns, 67Ns 3I NE> 3I NE>> Negative-sequence overcurrent protection 46 Thermal overload protection 49 PTTR Ith Overload protection 50OL PTOC 3I >OL Voltage protection Overvoltage protection 59 PTOV Undervoltage protection 27 PTUV 3U> 3U>> 3U< 3U<< Displacement voltage protection 64 V E> Breaker protection and control function Breaker failure protection 50BF RBRF 3I> BF I 0>BF I 2>BF Dead zone protection 50DZ Synchro-check and energizing check 25 RSYN Auto-reclosing 79 RREC O I Three-pole tripping 94-3 PTRC Capacitor bank protection Unbalanced current protection Unbalanced voltage protection 46NC 46NU 4

7 Function Undercurrent protection 37 I< Load shedding function Underfrequency load shedding function 81U Undervoltage load shedding function 27 Overload load shedding function Secondary system supervision CT secondary circuit supervision VT secondary circuit supervision 97FF Other functions Fast busbar protection using reverse interlocking Disturbance recorder Control functions Description ANSI Code IEC Logical Node Name IEC graphical symbol Remote/Local circuit breaker, disconnector and other switching devices control Programmable interlock logic Tripping and closing circuit supervision Opening and closing lockout function Monitoring functions Description Status of circuit breaker, disconnector and other switching device monitoring Circuit breaker operating status supervision Auxiliary contacts of circuit breaker supervision Self-supervision 5

8 Function Station communication Description Front communication port Isolated RS232 port or RJ45 Ethernet port Rear communication port 0-2 isolated electrical RS485 communication ports, support IEC protocol 0-2 Ethernet electrical/optical communication ports, support IEC protocol or IEC protocol Time synchronization port, support GPS pulse or IRIG-B code IED software tools Functions Reading measuring value Reading IED report Setting IED testing Disturbance recording analysis IED configuration Printing 6

9 Function 46NU 50 3I >>> PIOC 46NI MEASUREMENT 51/67 3I> 3I>> PTOC 50N I 0>>> PIEF 51N/67N I 0> I 0>> PTEF 59 3U> PTOV 27 3U< PTUV 50Ns 3I NE>> MONITORING INTERLOCK & 50BF 3I>BF RBRF 51Ns/67Ns 3I NE> CONTROL 49 Ith PTTR ENERGY METER CALCULATED U E> STATION COMMUNICATION Disturbance recording 79 O I RREC 25 RSYN - RS232/485 - RJ45/FO - IEC IEC

10 Protection Overcurrent protection (50, 51, 67) The protection provides following features: Two definite time stages One inverse time stage 11 kinds of IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Settable directional element characteristic angle to satisfy the different network conditions and applications Each stage can be set individually as directional/non-directional Each stage can be set individually for inrush restraint Cross blocking function for inrush detection Settable maximum inrush current First definite stage and inverse time stage can be set individually to alarm or trip VT secondary circuit supervision for directional protection. Once VT failure happens, the directional stage can be set to be blocked or to be non-directional Under voltage criteria checking (selectable), blocking of the definite time stages is possible when the measured voltage exceeds the threshold Inrush restraint function transformer energizing. In addition to considerably unbalanced fundamental current, inrush current comprises large second harmonic current which doesn t appear in short circuit current. Therefore, the inrush current may affect the protection functions which operate based on the fundamental component of the measured current. Accordingly, inrush restraint logic is provided to prevent overcurrent protection from mal-operation. Furthermore, by recognition of the inrush current in one phase, it is possible to set the protection in a way that not only the phase with the considerable inrush current, but also the other phases of the overcurrent protection are blocked for a certain time. This is achieved by cross-blocking feature integrated in the IED. The inrush restraint function has a maximum inrush current setting. Once the measuring current exceeds the setting, the overcurrent protection will not be blocked any longer. Characteristic of direction element The direction detection is performed by determining the position of current vector in directional characteristic. In other word, it is done by comparing phase angle between the fault current and the reference voltage, Figure 1 illustrates the direction detection characteristic for phase A element. The protection relay may detect large magnetizing inrush currents during 8

11 Protection Forward 90 I A Bisector ΦPh_Char 0 charging of motors, the definite time stage of overcurrent element is able to operate only when at least one phase-to-phase voltage falls less than the low voltage settable threshold.the low voltage element can be set for each definite time stage. U BC_Ref Earth fault protection (50N, 51N, 67N) -I A Figure 1 Direction detection characteristic of overcurrent protection directional element The earth fault protection can be used to clear phase to earth faults as system back-up protection. The protection provides following features: where: Two definite time stages Ф Ph_Char: The settable characteristic angle The assignment of the applied measuring values used in direction determination has been shown in Table 1 for different types of faults. Table 1 Assignment of applied current and reference voltage for directional element Phase Current Voltage A B C I a Ib I c U bc U ca U ab For three-phase short-circuit fault, without any healthy phase, memory voltage values are used to determine direction clearly if the measured voltage values are not sufficient. The detected direction is based on the voltage of previously saved cycles. Under voltage criteria To prevent any malfunction of the overcurrent element during reverse One inverse time stage 11 kinds of the IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Zero sequence directional element Negative sequence directional element is applied as a complement to zero sequence directional element. It can be enabled/disabled by setting Each stage can be set individually as directional/non-directional Settable directional element characteristic angle to satisfy the different network conditions and applications Each stage can be set individually for inrush restraint Settable maximum inrush current Inrush restraint function adopting 2 nd harmonic measured phase or earth current (settable) 9

12 Protection First definite stage and inverse time stage can be set individually to alarm or trip VT secondary circuit supervision for directional protection function. Once VT failure happens, the directional stage can be set to be blocked or to be non-directional Zero-sequence current is calculated by summation of 3 phase currents or measured from earth phase CT selectable where: Ф 0_Char: The settable characteristic angle For earth fault protection, users can choose negative sequence directional element as the complement of zero sequence directional element. It can be used in case of too low zero sequence voltage due to some fault condition e.g. the unfavorable zero-sequence. The negative sequence directional element characteristic is shown in Figure 3. Directional element 3I 2 90 The earth fault protection adopts zero sequence directional element which compares the zero sequence system quantities: 3I 0, current is calculated from the sum of the three phase currentss or measured from earth phase CT 3U 0, the voltage is used as reference voltage, if it is connected. Otherwise, 3U 0, the zero sequence voltage, calculated from the sum of the three phase voltages Forward 3I I0 3U0_Ref Φ0_Char Bisector 0 Figure 2 Direction detection characteristic of zero sequence directional element Forward -3I 2 Φ2_Char 0 3U 2_ Ref Bisector Figure 3 Direction detection characteristic of where: negative sequence directional element Ф 2_Char: The settable characteristic angle Furthermore, under the VT failure situation, it can be set to block directional earth fault protection or to apply non-directional earth fault protection. Inrush restraint function The protection relay may detect large magnetizing inrush currents during transformer energizing. In addition to considerably unbalanced fundamental current, Inrush current comprises large second harmonic current which doesn t 10

13 Protection appear in short circuit current. Therefore, the inrush current may affect the protection functions which operate based on the fundamental component of the measured current. Accordingly, inrush restraint logic is provided to prevent earth fault protection from mal-operation. Since inrush current cannot be more than a specified value, the inrush restraint provides an upper current limit in which blocking does not occur. Neutral earth fault protection (50G, 51G) The neutral earth fault protection focuses on phase to earth faults. The measuring current is the one from dedicated neutral CT. The protection provides following features: Two definite time stages One inverse time stage 11 kinds of IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Each stage can be set individually to alarm or trip Neutral current is measured from dedicated neutral CT Sensitive earth fault protection (50Ns, 51Ns, 67Ns) The function provides a high sensitive earth fault protection for cables and high impedance grounded or isolated systems where single phase short circuit current is made by capacitive current. Furthermore, the function can operate with/without selective tripping according to fault direction. Sensitive earth fault protection integrated in the IED provides following features: Two definite time stages One inverse time stage 11 kinds of IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Sensitive earth fault directional element with 3U0/3I0-Φ principle Sensitive earth fault directional element with Cos Φ principle Settable directional element characteristic angle to satisfy the different network conditions and applications Each stage can be set to be directional, or non-directional independently Each stage can be set individually to alarm or trip Displacement voltage can be checked to increase function reliability Dedicated sensitive CT VT secondary circuit supervision for directional protection function For compensated-earthed system or high resistance earthed system with outgoing cable feeders, the directional protection is provided during a single phase fault. In general, for high impedance earthed system, whenever a feeder has a high capacitive current - normally one greater than 10% of the current limited by the 11

14 Protection neutral earthed impedance a simple sensitive earth fault relay is no longer enough to give sensitive and selective protection. In this case, the protection system for the feeder consists of a directional sensitive earth fault relay whose threshold can be set to below the capacitive current. In order to discriminate forward and reverse short circuits, the IED provides two methods for sensitive earth fault direction detection which should be utilized to cover all network configurations according to the type of grounding. The following characteristic is possible for directional detection: Directional sensitive earth fault detection based on U 0 /I 0 -Φ measurement (see Figure 4) INS Forward 90 -I NS ΦNS_Char Bisector 0 3U0_ Ref Figure 4 Direction detection characteristic of the sensitive earth fault directional element by where: U 0/I 0-Φ Ф NS_Char: The settable characteristic angle Based on current vector component (Cos Φ) measurement (see Figure 5). In this way, the relay is sensitive to the active residual current and insensitive to the capacitive current Forward IS 90 -I S 0 3U0_ Ref Figure 5 Direction detection characteristic of the sensitive earth fault directional element by Cos Φ A sensitive current transformer is provided to detect the small earth fault current (weak zero sequence current) in isolated networks or in networks with high earthed impedance where the earth fault current is extremely small. Negative-sequence overcurrent protection (46) Negative sequence (or phase unbalance) protection is essentially provided for the protection of generators, motors and feeders against unbalanced loading that may arise due to phase-to-phase faults. In addition, it is useful in detecting asymmetrical short circuits with magnitudes lower than the maximum load current, especially in delta side of the transformers. The protection provide following features: 12

15 Protection Two definite time stages component. One inverse time stage 11 kinds of IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic The first definite stage and inverse stage can be set individually as alarm or trip stage Furthermore, this protection function may be used to detect interruptions, faults and polarity problems with CT. Thermal overload protection (49) The insulating material surrounding the windings ages rapidly if the temperature exceeds the design limit value. Thus, a thermal protection function is required to supplement the existing winding temperature device. The thermal overload protection estimates winding temperature and thus prevents it from thermal damaging. The memorized thermal overload protection operates based on an approximate replica of the temperature rise in the protected object caused by overload. The thermal replica can be implemented based on thermal models (Cold or Hot Curve) of IEC standard. The thermal overload in the IED is provided with one trip stage as well as one alarm stage. It is possible to set the alarm stage at a certain percentage of the setting value applied at the trip stage. The calculation is performed separately for each phase based on fundamental Overload protection (50OL) The IED supervises load flow in real time. If each phase current is greater than the dedicated setting for a set delay time, the protection will issue alarm or tripping. Overvoltage protection (59) The overvoltage protection detects abnormal network and machine high voltage conditions. Overvoltage conditions may occur possibly in the power system during abnormal conditions such as no-load, light load, or open line end on long line. The protection can be used as open line end detector or as system voltage supervision normally. The protection provides following features: Two definite time stages First stage can be set to alarm or trip Measuring voltage between phase-earth voltage and phase-phase (selectable) Three phase or single phase voltage connection Settable dropout ratio Undervoltage protection (27) The Undervoltage protection provides protection against dangerous voltage drops, especially for electric machines. 13

16 Protection The protection function provides following features: Two definite time stages optional user defined characteristic The first definite stage and inverse stage can be set to alarm or trip First stage can be set to alarm or trip Faulty phase discrimination Measuring voltage between phase-earth voltage and phase-phase selectable 3U 0 based on calculated summation of 3 phase voltage or measured injected residual voltage Current criteria supervision Circuit breaker aux. contact supervision VT secondary circuit supervision, the under voltage function will be blocked when VT failure happens Settable dropout ratio Displacement voltage protection (64) The displacement voltage protection is able to monitor the displacement voltage to detect the earth fault in power system. It is usually applied in non-solidly earthed networks where the earth fault current is limited. The displacement voltage 3U 0 can be either directly measured from VT or calculated based on connected three phases to earth voltages. In the latter case, the three voltages transformers input must be connected in an earth-wye configuration. The protection provide following features: Two definite time stages One inverse time stage 4 kinds of IEC inverse time characteristic curves as well as Breaker failure protection (50BF) The circuit breaker failure protection is able to detect a failure of the circuit breaker during a fault clearance. It ensures fast back-up tripping of surrounding breakers by tripping relevant bus sections. Once a circuit breaker operating failure occurs on a feeder/transformer, the bus section which the feeder/transformer is connected with can be selectively isolated by the protection. In addition a transfer trip signal is issued to trip the remote end circuit breaker of the feeder. In the event of a circuit breaker failure with a busbar fault, a transfer trip signal is issued to trip the remote end circuit breaker of the feeder. The current criteria are in combination with three phase currents, zero and negative sequence current to achieve a higher security. The function can be set to give three phase re-trip of the own breaker to avoid unnecessary tripping of surrounding breakers at an incorrect starting due to mistakes during testing. Two trip stages (local CB and surrounding breaker tripping) 14

17 Protection Transfer trip command to the remote line end in second stage Internal/ external initiation Three phase CBF initiation for sub-transmission system and distribution system Bus trip Settable CB Aux contacts checking Current criteria checking (including phase current, zero and negative sequence current) IFAULT Dead zone protection (50DZ) The IED provides dead zone protection to protect the area, between circuit breaker and CT in the case that CB is open, meaning dead zone. Therefore, by occurrence of a fault in dead zone, the short circuit current is measured by protection relay while CB auxiliary contacts indicate the CB is open. Line1 Line2 LineN Legend: Opened CB Closed CB Figure 6 Tripping logic when applying bus side CT Inter trip Busbar Internal/ external initiation Self-adaptive for bus side CT or line side CT When one bus side CT of feeder is applied, once a fault occurs in the dead zone, the IED trips the relevant busbar zone. Tripping logic is illustrated in Figure 6. When one line side CT is applied, when a fault occurs in the dead zone, protection relay sends a transfer trip to remote end relay to isolate the fault. Tripping logic is illustrated in Figure 7. IFAULT Line1 Line2 LineN Trip Relay Legend: Opened CB Closed CB Figure 7 Tripping logic when applying line side CT 15

18 Protection Synchro-check and energizing check (25) The synchro-check function checks voltages of the circuit breaker sides for synchronism conditions. The synchronization function ensures the stability of the network in three phase reclosing condition. To do this, the two side voltages of the circuit breaker are compared in terms of magnitude, phase angle and frequency differences. Additionally, closing can be done safely in conditions that at least one side of the CB has dead voltage. Available for automatic reclosing and manual closing (internally or externally) Based on voltage/ angle/ frequency difference Synchro-check conditions: Synch-check Energizing check, and synch-check if energizing check failure Override Modes of energizing check: Dead V 4 and dead V 3Ph Dead V 4 and live V 3Ph Live V 4 and dead V 3Ph Synchro-check reference voltage supervision If the automatic reclosing is set for synchronization check or energizing check, during the automatic reclosing period, the synchronization condition of the voltages between both sides of CB cannot be met, an alarm will be issued after default time delay. Auto-reclosing (79) For restoration of the normal service after a fault an auto reclosing attempt is mostly made for overhead lines. Experiences show that about 85% of faults have transient nature and will disappear after an auto reclosing attempt is performed. This means that the line can be re-energized in a short period. The reconnection is accomplished after a dead time via the automatic reclosing function. If the fault is permanent or short circuit arc has not disappeared, the protection will re-trip the breaker. Main features of the auto-reclosing are as follows: 4 shots automatic reclosing (selectable) Individually settable dead time for each shot Internal/external AR initiation Three phase AR operation CB ready supervision CB Aux. contact supervision Cooperation with internal synch-check function for reclosing command Unbalanced current or voltage protection (46) The purpose of the unbalance detection scheme is to remove fuse operated a capacitor bank from the network. This will prevent damaging overvoltage across the remaining capacitor units/elements where the fuse operation occurs. 16

19 Protection Unbalance detection scheme is set up to signal an alarm upon an initial failure in a bank. Upon subsequent critical failures, the bank will be tripped from the connected network. According to the used unbalanced voltage/current, the IED supports different protection schemes mentioned in the typical connections. The IED provides three analog channels to monitor unbalance status. If only one unbalanced channel is used, the other two channels can be reserved. To avoid mal-operation, breaker auxiliary contact is necessary as a criterion. Undercurrent protection (37) Under current protection is used to prevent reconnection of the charged capacitor bank to energized network when a short loss of supply voltage occurs. Once under current protection operates, the CB closing circuit will be interrupted and reset after a certain time. Additionally, time to resetting will be displayed on the HMI. Capacitor overload protection (50OL) The current overload protection is provided to protect the capacitor bank against the faults due to overvoltage which leads to dielectric breakdown. The tripping and alarming capability are provided and can be enabled or disabled separately. Load shedding function The IED provides three kinds of load shedding functions listed below. Under frequency load shedding protection The function monitors the network abnormality by detection of frequency reduction. When the system frequency falls down to a threshold frequency with following conditions satisfied, specified load will be removed. Under voltage checking Rate of frequency (df/dt) checking CB position checking Load current checking VT secondary circuit supervision Under voltage load shedding This kind of load shedding is to prevent the voltage collapse and uncontrolled loss of load. Low voltage load shedding is necessary when the network is connected with a huge system with vast power capacity. Under this condition, Low Frequency Load Shedding Scheme cannot work properly. Low Voltage Load Shedding Scheme" would be a useful criterion whenever Automatic Voltages Regulator (AVR) is out of service or not equipped with following conditions satisfied. Under voltage checking Negative sequence voltage checking Rate of voltage (du/dt) checking CB position checking 17

20 Protection Load current checking VT secondary circuit supervision Overload load shedding A Relay A The IED provides a load shedding function based on the load current passing through feeder. This function will be essential in conditions that feeder is connected to a huge network with constant frequency and additional AVR is continuously used for voltage regulation. In this case, load shedding protection should be done based on load current and monitoring of following items Under voltage checking Rate of voltage (du/dt) checking (in the case of voltage connection) Rate of frequency (df/dt) checking (in the case of voltage connection) VT secondary circuit supervision (in the case of voltage connection) Fast busbar protection scheme Relay B B Trip Relay C C GOOSE message-block Figure 8 operation when fault on the feeder C A Relay A Trip The IED provides fast busbar protection which is achieved based on operation with GOOSE signals, it is able to block the incoming feeder protection IED function by reception of a defined GOOSE signals from the outgoing feeder linked with the same busbar. B Relay B The principle illustrated in the following figure: If the fault occurs on outgoing feeder C, the protection IED C will trip and send block messenger to IED A to block IED A relevant protection function. C Relay C Figure 9 operation when fault on the Busbar 18

21 Protection Once the fault located on the busbar, there is not one protection IED of outgoing feeder to trip and block the IED A. So the IED A will trip and clear off the fault with short time delay. Secondary system supervision Current transformer secondary circuit supervision Open or short circuited CT cores can cause unwanted operation of some protection functions such as earth fault current and negative sequence current functions. Interruption of the CT secondary circuit is detected based on zero-sequence current. Once CT failure happens, each stage of earth fault protection is blocked. Voltage transformer secondary circuit supervision A measured voltage failure, due to a broken conductor or a short circuit fault in the secondary circuit of voltage transformer, may result in unwanted operation of the protection functions which work based on voltage criteria. VT failure supervision function is provided to block these protection functions and enable the backup protection functions. The features of the function are as follows: Symmetrical/asymmetrical VT failure detection 3-phase AC voltage MCB monitoring 1-phase AC voltage MCB monitoring Zero and negative sequence current monitoring Applicable in solid grounded, compensated or isolated networks 19

22 Control The primary apparatuses, such as circuit breaker, disconnector, earth disconnector, etc, can be controlled through IED in two modes, Remote mode: By Substation automation system Local mode: by dedicated keys operation on the front plate of IED, for advanced IED version only Remote or local mode can be switched by L/R key on the IED front plate. The current control mode is indicated on the LCD as an icon, L or R. All control operations are supervised under interlock logic according the requirement. The interlock logic can be programmed in the software tool by user (shown in Figure 11). For advanced IED version, the single line diagram can be displayed on the LCD (shown in Figure 11), which is able to indicate the status of circuit breaker, disconnector and other in real time. Figure 10 Example of Single line diagram displayed on the LCD CLOSE COMMAND Blk Rem Access Remote 3Ph CB Open T_Inhibition BI21 (EXT. INTERLOCK) BI22 (CB IN SERVICE) BI23 (SPRING NOT CHARGED) AND AND Interlock On CB Close BI24 (TR RELAY OPERATED) BI25 (TRIP COIL FAULTY) Figure 11 Example of CB control interlock logic diagram 20

23 Monitoring Phase-sequence of voltage and current supervision The phase-sequence of three phase voltage and current are monitored in the normal condition to determine that the secondary circuit of CT or VT is connected with IED correctly. 3I0 polarity supervision The IED compare the magnitude and phase angle of the calculated zero sequence current with the measured one to determine that the polarity is connected in a right way. The third harmonic of voltage supervision If the third harmonic voltage is excessive, the alarm without blocking protection will be given with delay time for checking of the secondary circuit of voltage transformer. Auxiliary contacts of circuit breaker supervision Current flowing through the transmission line and connected CB aux. contacts are monitored in phase segregated. Therefore, the conflict condition is reported as alarm. For example, If CB aux. contacts indicate that CB is open in phase A and at the same time flowing current is measured in this phase, related alarm is reported. Broken conductor detection The main purpose of the broken conductor detection function is to detect the broken conductors on protected transmission lines and cables. Detection can initiate an alarm or tripping. Self-supervision All modules can perform selfsupervision to its key hardware components and program, as soon as energizing. Parts of the modules are self-supervised in real time. All internal faults or abnormal conditions will initiate an alarm. The fatal faults among them will result in the whole IED blocked The sampled data from the redundant A/D sampling channels compare with each other in real time. If the difference exceeds the specified threshold, it will be considered as analog input channel fault and the protection will be blocked immediately CPU module and communication module perform real time inter- -supervision. Therefore communication interruption between them is detected and related alarm will be given CRC checks for the setting, program and configuration, etc. Fault locator The built-in fault locator is an impedance measuring function giving the distance from the IED measuring location to the fault position in km. The IED reports fault location after the IED tripping. 21

24 Communication Station communication Overview The IED is able to connect to one or more substation level systems or equipments simultaneously, through the communication ports with communica- -tion protocols supported. (Shown in Figure 12) Front communication port There is a serial RS232 port on the front plate of all the IEDs. Through this port, the IED can be connected to the personal computer for setting, testing, and configuration using the dedicated Sifang software tool. RS485 communication ports Up to 2 isolated electrical RS485 communication ports are provided to connect with substation automation system. These two ports can work in parallel for IEC Ethernet communication ports Up to 3 electrical or optical Ethernet communication ports are provided to connect with substation automation system. These two out of three ports can work in parallel for protocol, IEC61850 or IEC Server or Work Station 1 Server or Work Station 2 Work Station 3 Switch Work Station 4 Net 1: IEC61850/IEC103,Ethernet Port A Switch Net 2: IEC61850/IEC103,Ethernet Port B Switch Switch Switch Gateway or converter Switch Gateway or converter Net 3: IEC103, RS485 Port A Net 4: IEC103, RS485 Port B Figure 12 Connection example for multi-networks of station automation system Note: All four ports can work in parallel Communication protocol The IED supports station communication with IEC and IED protocols. By means of IEC61850, GOOSE peer- -to-peer communication make it possible that bay IEDs can exchange information to each other directly, and a simple master-less system can be set up for bay and system interlocking and other interactive function. Time synchronization port 22

25 Software Tools All IEDs feature a permanently integrated electrical time synchronization port. It can be used to feed timing telegrams in IRIG-B or pulse format into the IEDs via time synchronization receivers. The IED can adapt the second or minute pulse in the pulse mode automatically. Meanwhile, SNTP network time synchro- -nization can be applied. Figure 13 illustrates the optional time synchronization modes. SNTP IRIG-B Pulse Ethernet port IRIG-B port Binary input Figure 13 Time synchronizing modes 23

26 Software tools A user-friendly software tool is offered for engineering, setting, disturbance analysis and monitoring. It provides versatile functionalities required throughout the life cycle of protection IEDs. Its features are as follows: For advanced IED version, the binary inputs and binary outputs can be assigned to the required function modules (shown in Figure 14) Figure 14 Binary inputs and binary outputs edit window Modification, import and export of parameter sets sorted by protection functions with setting logicality check (shown in Figure 15) 24

27 Software Tools Figure 15 setting edit window For advanced IED version, the control function interlock logic can be programmed according requirements (shown in Figure 15) Figure 16 Interlock logic edit window Precise fault analysis: visualization of fault records in curves over time, circle diagrams, vector diagrams, bar charts and data sheet (shown in Figure 17) 25

28 Software tools Figure 17 Disturbance record waveform analysis window Intelligent setting checks rule out incorrect input Graphical visualization of characteristics and zone diagrams with direct manipulation of the curves Password-protected access for different jobs such as parameter setting, commissioning and controlling (authorized staff only) Testing and diagnostic functions decisive support in the commissioning phase 26

29 Hardware Front plate The whole front plate is divided into zones, each of them with a well-defined functionality: Run Trip Alarm LED4 LED5 LED6 LED7 LED8 CSC-211 LED9 LED10 LED11 LED12 LED13 LED14 LED15 LED16 RESET 1 4 QUIT SET 6 CSC R\L SWITCH SELECT CONFIRM TRIP CLOSE 7 2 QUIT RESET SET SIO Figure 18 The option 1 of view of IED front plate 1 Liquid crystal display (LCD), alpha- -numeric display only 2 8 LEDs 3 Navigation keys 4 Reset key 5 Quit key 6 Set key 7 RS232 communication port Figure 19 The option 2 of view of IED front plate for advanced IED version only 1 Liquid crystal display (LCD), alpha- -numeric and graphic display 2 16 LEDs 3 Quit key 4 Reset key 5 Set key 6 Navigation keys 7 RJ45 Ethernet communication port 8 R/L Remote/Local control switch key 9 LCD display switch key 10 Controlled objects select key 11 Control operation confirm key 12 Open key 13 Close key 27

30 Hardware Modules Analogue Input Module (AIM) The analogue input module is used to galvanically separate and transform the secondary currents and voltages generated by the measuring transformers. 3 dedicated high accurate current transformers (optional) are used for metering. CPU module (CPU) The CPU module handles all protection functions and logic, hardware self-supervision and performs communication and information exchange between the protection system and external equipments such as HMI, PC, monitor, control system, substation automation system, engineer station, RTU and printer, etc. Additionally, the CPU module transmits remote metering, remote signaling, SOE, event reports and record data. The module also provides binary inputs, synchronization and communica- -tion ports. The pulse, IRIG-B or SNTP mode can be applied for time synchronization. According to requirement, up to 2 isolated electrical or optical Ethernet ports (optical Ethernet ports optional) and up to 2 RS485 serial communication port can be provided to meet the demands of different substation automation system and RTU at the same time. There are 7 binary input channels (DC24V) in the CPU module for standard version. There are 3 binary input channels (DC24V) in the CPU module for advanced version. Direct binary Output Module (DOM) This module is used to provide fast tripping outputs and initiating outputs for protection functions, and signaling output, for standard version only. 10 binary output relays with 10 contacts in 5 groups are provided in the FOM of standard version. Direct binary Input & Output module (DIO) In this module, the fast binary inputs are used to connect with the signals and alarms. The fast binary outputs are used for the tripping outputs and initiating outputs for protection functions, or signaling output. 4 binary inputs and 7 binary output relays are provided in this module of standard version. 5 binary inputs and 7 binary output relays are provided in this module of advanced version. Binary Input & Output module (BIO) In this module, the output contacts are used for controlling and signaling outputs mainly. The binary inputs are used to connect with the input signals and alarms. 7 binary inputs and 9 binary output relays have been provided in this module of standard version. 5 binary inputs and 8 binary output relays are provided in this module of advanced version. Power Supply Module (PSM) The power supply module is used to provide the correct internal voltages and full isolation between the terminal and the 28

31 Hardware battery system. The module of standard version provides 9 binary input channels. And the module of advanced version provides 10 binary input channels as well. 29

32 Hardware Dimension F E A B D C Figure 20 Case of CSC211 protection IED Table 2 Dimension of the IED Legend A B C D E F Dimension (mm) E C D A B Figure 21 Cutout for flush mounting on the panel Table 3 Dimension of the cutout Legend A B C D E Dimension (mm)

33 Connection A. Typical rear terminal diagram of standard version X X I5 UUBA / IUBA UUBB / IUBB UUBC / IUBC IMB IA IB IC I4 IMA IMC X UA 02 UB 03 UC 04 UN 05 U4 06 X X BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI-COM (-) BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI-COM (-) GPS GPS - GND RS485 - B RS485 - A 2) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 Output relay 09 3) 1) Ethernet Port 1 - RJ45 Ethernet Port 2 - RJ45 CSC-211 Standard Version BI01 BI02 BI03 BI04 BI-COM(-) Null Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI08 BI09 BI-COM (-) DC 24V + output DC 24V - output Power failure alarm relay Null AUX DC + input Null AUX DC - input Null Terminal for earthing X X X Note : 1) X1 is optional module according the ordered pre-configure scheme. 2) For pre-configure scheme C01, they are three phases unbalanced voltage input channels; For preconfigure scheme C02, they are three phases unbalanced current input channels. 3) These binary inputs support DC 24V input voltage only. 31

34 Connection B. Typical rear terminal diagram of advanced version X X I5 IMB IA IB IC I4 IMA IMC X UA 02 UB 03 UC 04 UN 05 U4 06 X X ) CSC-211 Advanced Version BI01 BI02 BI03 BI04 BI05 BI-COM (-) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 2) BI01 BI02 BI03 BI-COM (-) Time synchronization - \ A Time synchronization + \ B Time synchronization - GND RS232 - RX RS232 - TX RS232 - GND RS485-1A RS485-1B RS485-1GND RS485-2A RS485-2B RS485-2GND 3) BI01 BI02 BI03 BI04 BI05 BI-COM(-) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 Output relay 08 BI01 BI02 BI03 BI04 BI05 BI-COM(-) Output relay 01 Output relay 02 Output relay 03 Output relay 04 Output relay 05 Output relay 06 Output relay 07 BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI08 BI09 BI10 BI-COM (-) DC 24V + output DC 24V - output IED tripping signal relay Signal relay IED alarm I relay IED alarm II relay Power failure alarm relay AUX DC + input Null AUX DC - input Terminal for earthing X X X Ethernet Port 1 - RJ45 Ethernet Port 2 - RJ45 32

35 Connection Note : 1) X1 is optional module according the ordered pre-configure scheme. 2) These binary inputs support DC 24V input voltage only. 3) There are total 3 CPU modules options offered in slot X4, other options are shown as following: X Option 2 BI01 BI02 BI03 BI-COM (-) Time synchronization - \ A Time synchronization + \ B Time synchronization - GND RS232 - RX RS232 - TX RS232 - GND X Option 3 BI01 BI02 BI03 BI-COM (-) Time synchronization - \ A Time synchronization + \ B Time synchronization - GND RS232 - RX RS232 - TX RS232 - GND Ethernet Port 1 - RJ45 Ethernet Port 1 - ST Ethernet Port 2 - RJ45 Ethernet Port 2 - ST Ethernet Port 3 - RJ45 33

36 Connection C. Typical analogue input connection for incoming or outgoing feeder protection or line backup protection A B C I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN Figure 22 Application of feeder protection to measure three phase and earth currents A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN Figure 23 Application of feeder protection to measure three phase and earth currents and three phase voltages (bus side) 34

37 Connection A B C I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN U01 U02 U03 U04 AIM2 UA UB UC UN Figure 24 Application of feeder protection to measure three phase and earth currents and three phase voltages (line side) 35

38 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN Figure 25 Application of feeder protection to measure three phase and earth currents and single phase voltage (Ph-Ph) (bus side) 36

39 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN Figure 26 Application of feeder protection to measure three phase and earth currents and single phase voltage (Ph-E) (bus side) 37

40 Connection A B C I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 AIM1 I02 I1 Figure 27 Application of feeder protection to measure three phase currents, earth current, and sensitive earth current 38

41 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 AIM1 I02 I1 Figure 28 Application of feeder protection to measure three phase currents, earth current and sensitive earth current, and three phase voltages (bus side) 39

42 Connection A B C I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN U01 U02 U03 U04 AIM2 UA UB UC UN * I01 AIM1 I02 I1 Figure 29 Application of feeder protection to measure three phase currents, earth current and sensitive earth current, and three phase voltages (line side) 40

43 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 I02 AIM1 I1 Figure 30 Application of feeder protection to measure three phase currents, earth current and sensitive earth current, and single phase voltage (Ph-Ph) (bus side) 41

44 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 I02 AIM1 I1 Figure 31 Application of feeder protection to measure three phase currents, earth current, and sensitive earth current, and single phase voltage (Ph-E) (bus side) 42

45 Connection D. Typical analogue input connection for transformer backup protection A B C I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 I02 AIM1 I1 Figure 32 Application of transformer backup protection to measure three phase currents, earth current, and neutral current 43

46 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 I02 AIM1 I1 Figure 33 Application of transformer backup protection to measure three phase currents, earth current and neutral current, and three phase voltages (bus side) 44

47 Connection A B C I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN U01 U02 U03 U04 AIM2 UA UB UC UN * I01 I02 AIM1 I1 Figure 34 Application of transformer backup protection to measure three phase currents, earth current and neutral current, and three phase voltages (line side) 45

48 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 I02 AIM1 I1 Figure 35 Application of transformer backup protection to measure three phase currents, earth current and neutral current, and single phase voltage (Ph-Ph) (bus side) 46

49 Connection A B C U01 U02 U03 U04 AIM2 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN * I01 I02 AIM1 I1 Figure 36 Application of transformer backup protection to measure three phase currents, earth current and neutral current, and single phase voltage (Ph-E) (bus side) 47

50 Connection E. Typical analogue input connection for synch-check function A B C A B C U05 AIM2 U06 U4 U01 U02 U03 U04 UA UB UC UN Figure 37 Typical connection for synch-check on bus coupler applications 48

51 Connection A B C U05 AIM2 U06 U4 U01 U02 U03 U04 UA UB UC UN I01 I02 AIM2 IA * * * I03 I04 I05 I06 I07 I08 IB IC IN Figure 38 Typical connection for synch-check and feeder current protection 49

52 Connection F. Typical analogue input connection for capacitor bank protection A B C Capacitor bank * * I03 I04 I05 I06 AIM1 IC1 IC2 * I07 I08 IC3 Figure 39 Typical connection for capacitor bank unbalanced current protection with three current inputs A B C Capacitor bank U03 U04 AIM1 UC1 U05 U06 U07 U08 UC2 UC3 Figure 40 Typical connection for capacitor bank unbalanced voltage protection with three voltage inputs 50

53 Connection A B C Capacitor bank I03 AIM1 * I04 I05 I06 IC1 IC2 I07 I08 IC3 Figure 41 Typical connection for capacitor bank unbalanced current protection with one current input A B C Capacitor bank U03 U04 AIM1 UC1 U05 U06 UC2 U07 U08 UC3 Figure 42 Typical connection for capacitor bank unbalanced voltage protection with one voltage input 51

54 Connection A B C A B C I1 Figure 43 Unbalanced current detection for A B C grounded capacitor bank I1 I2 I3 Figure 46 Three unbalanced currents detection A B C for capacitor bank I1 Figure 44 Neutral current differential protection A B C for grounded Split-Wye capacitor bank U1 Figure 47 Neutral voltage unbalanced protection A B C for unrounded Wye capacitor bank I1 Figure 45 Neutral current protection for ungrounded split-wye capacitor bank U1 Figure 48 Neutral voltage unbalanced detection for ungrounded split-wye capacitor bank 52

55 Connection A B C A B C U1 U1 Figure 49 Summation of Intermediate tap-point A B C voltage for grounded Wye capacitor bank A B C Figure 51 Neutral voltage protection for ungrounded split-wye capacitor bank Figure 50 Neutral voltage unbalance detection by U1 3VTs for unrounded Wye capacitor bank U1 U2 Figure 52 Three unbalanced voltages detection for Capacitor Bank U3 G. Typical analogue input connection for Load shedding function CSC-211 CSC-211 CSC-211 CSC-211 CSC-211 Figure 53 Typical connection for load shedding function 53

56 Technical data Frequency Item Standard Data Rated system frequency IEC Hz or 60Hz Internal current transformer Item Standard Data Rated current I r IEC or 5 A Nominal current range Nominal current range of sensitive CT 0.05 I r to 30 I r to 1 A Power consumption (per phase) 0.1 VA at I r = 1 A; 0.5 VA at I r = 5 A 0.5 VA for sensitive CT Thermal overload capability IEC IEC Thermal overload capability for IEC sensitive CT DL/T I r for 1 s 4 I r continuous 100 A for 1 s 3 A continuous Internal voltage transformer Item Standard Data Rated voltage V r (ph-ph) IEC V /110 V Nominal range (ph-e) Power consumption at V r = 110 V IEC DL/T V to 120 V 0.1 VA per phase Thermal overload capability (phase-neutral voltage) IEC DL/T V r, for 10s 1.5 V r, continuous Auxiliary voltage Item Standard Data Rated auxiliary voltage U aux IEC to 125V 195 to 250V Permissible tolerance IEC ±%20 U aux Power consumption at quiescent state IEC W per power supply module 54

57 Technical data Power consumption at maximum load IEC W per power supply module Inrush Current IEC T 5 ms/i 35 A Binary inputs Item Standard Data Input voltage range IEC /125 V 220/250 V Threshold1: guarantee operation IEC V, for 220/250V 77V, for 110V/125V Threshold2: uncertain operation IEC V, for 220/250V ; 66V, for 110V/125V Response time/reset time IEC Software provides de-bounce time Power consumption, energized IEC Max. 0.5 W/input, 110V Max. 1 W/input, 220V Binary outputs Item Standard Data Max. system voltage IEC V /~ Current carrying capacity IEC A continuous, 30A,200ms ON, 15s OFF Making capacity IEC W( ) at inductive load with L/R>40 ms 1000 VA(AC) Breaking capacity IEC V, 0.15A, at L/R 40 ms 110V, 0.30A, at L/R 40 ms Mechanical endurance, Unloaded IEC ,000,000 cycles (3 Hz switching frequency) Mechanical endurance, making IEC cycles Mechanical endurance, breaking IEC cycles Specification state verification IEC IEC IEC UL/CSA TŰV 55

58 Technical data Contact circuit resistance measurement Open Contact insulation test (AC Dielectric strength) IEC IEC IEC IEC IEC mΩ AC1000V 1min Maximum temperature of parts and materials IEC Front communication port Item Number 1 Data Connection Communication speed Max. length of communication cable Isolated, RS232; front panel, 9-pin subminiature connector, for software tools 9600 baud 15 m RS485 communication port Item Data Number 1 Connection Max. length of communication cable Test voltage 2-wire connector Rear port in communication module 1.0 km 500 V AC against earth For IEC protocol Communication speed Factory setting 9600 baud, Min baud, Max baud Ethernet communication port Item Electrical communication port Data Number 0 to 3 Connection Max. length of communication cable RJ45 connector Rear port in communication module 100m For IEC protocol 56

59 Technical data Communication speed 100 Mbit/s For IEC protocol Communication speed 100 Mbit/s Time synchronization Mode IRIG-B signal format Item Pulse mode IRIG-B000 Data Connection Voltage levels 2-wire connector Rear port in communication module differential input Environmental influence Item Recommended permanent operating temperature Storage and transport temperature limit Permissible humidity Data -10 C to +55 C (Legibility of display may be impaired above +55 C /+131 F) -25 C to +70 C 95 % of relative humidity IED design Case size Weight Item 4U 1/2 19inch 5kg Data 57

60 Technical Data Product safety-related Tests Item Standard Data Over voltage category IEC Category III Pollution degree IEC Degree 2 Insulation IEC Basic insulation Degree of protection (IP) Power frequency high voltage withstand test Impulse voltage test Insulation resistance IEC IEC IEC EN ANSI C37.90 GB/T DL/T IEC IEC EN ANSI C37.90 GB/T DL/T IEC IEC EN ANSI C37.90 GB/T Front plate: IP40 Rear, side, top and bottom: IP 30 2KV, 50Hz 2.8kV between the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs case earth 500V, 50Hz between the following circuits: Communication ports to case earth time synchronization terminals to case earth 5kV (1.2/50μs, 0.5J) If U i 63V 1kV if U i<63v Tested between the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs case earth Note: U i: Rated voltage 100 MΩ at 500 V 58

61 Technical Data DL/T Protective bonding resistance IEC Ω Fire withstand/flammability IEC Class V2 Electromagnetic immunity tests Item Standard Data 1 MHz burst immunity test IEC IEC IEC EN ANSI/IEEE C Electrostatic discharge IEC IEC EN Class III 2.5 kv CM ; 1 kv DM Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 1 kv CM ; 0 kv DM Tested on the following circuits: communication ports Level 4 8 kv contact discharge; 15 kv air gap discharge; both polarities; 150 pf; R i = 330 Ω Radiated electromagnetic field disturbance test Radiated electromagnetic field disturbance test Electric fast transient/burst immunity test IEC EN IEC EN IEC , IEC EN ANSI/IEEE C Frequency sweep: 80 MHz 1 GHz; 1.4 GHz 2.7 GHz spot frequencies: 80 MHz; 160 MHz; 380 MHz; 450 MHz; 900 MHz; 1850 MHz; 2150 MHz 10 V/m AM, 80%, 1 khz Pulse-modulated 10 V/m, 900 MHz; repetition rate 200 Hz, on duration 50 % Class A, 4KV Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 59

62 Technical Data Class A, 1KV Tested on the following circuits: communication ports Surge immunity test IEC IEC Conduct immunity test IEC IEC kV L-E 2.0kV L-L Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 500V L-E Tested on the following circuits: communication ports Frequency sweep: 150 khz 80 MHz spot frequencies: 27 MHz and 68 MHz 10 V AM, 80%, 1 khz Power frequency immunity test IEC Class A 300 V CM 150 V DM Power frequency magnetic field test IEC Level 4 30 A/m cont. / 300 A/m 1 s to 3 s 100 khz burst immunity test IEC kv CM ; 1 kv DM Tested on the following circuits: auxiliary power supply CT / VT inputs binary inputs binary outputs 1 kv CM ; 0 kv DM Tested on the following circuits: communication ports DC voltage interruption test Item Standard Data DC voltage dips IEC % reduction 20 ms 60

63 Technical Data 60% reduction 200 ms 30% reduction 500 ms DC voltage interruptions IEC % reduction 5 s DC voltage ripple IEC %, twice rated frequency DC voltage gradual shut down /start-up IEC s shut down ramp 5 min power off 60 s start-up ramp DC voltage reverse polarity IEC min Electromagnetic emission test Item Standard Data Radiated emission Conducted emission IEC EN CISPR22 IEC EN CISPR22 30MHz to 1GHz ( IT device may up to 5 GHz) 0.15MHz to 30MHz Mechanical tests Item Standard Data Sinusoidal Vibration response test Sinusoidal Vibration endurance test Shock response test Shock withstand test IEC EN IEC EN IEC EN IEC EN Class 1 10 Hz to 60 Hz: mm 60 Hz to 150 Hz: 1 g 1 sweep cycle in each axis Relay energized Class 1 10 Hz to 150 Hz: 1 g 20 sweep cycle in each axis Relay non-energized Class 1 5 g, 11 ms duration 3 shocks in both directions of 3 axes Relay energized Class 1 15 g, 11 ms duration 3 shocks in both directions of 3 axes 61

64 Technical Data Relay non-energized Bump test IEC Class 1 10 g, 16 ms duration 1000 shocks in both directions of 3 axes Relay non-energized Seismic test IEC Class 1 X-axis 1 Hz to 8/9 Hz: 7.5 mm X-axis 8/9 Hz to 35 Hz :2 g Y-axis 1 Hz to 8/9 Hz: 3.75 mm Y-axis 8/9 Hz to 35 Hz :1 g 1 sweep cycle in each axis, Relay energized Climatic tests Item Standard Data Cold test - Operation IEC C, 16 hours, rated load IEC Cold test Storage IEC IEC C, 16 hours Dry heat test Operation [IEC C, 16 hours, rated load IEC Dry heat test Storage IEC C, 16 hours IEC Change of temperature IEC IEC Test Nb, figure 2, 5 cycles -10 C / +55 C Damp heat static test IEC C, 93% r.h. 10 days, rated load IEC Damp heat cyclic test IEC IEC C, 93% r.h. 6 cycles, rated load CE Certificate EMC Directive Low voltage directive Item Data EN and EN (EMC Council Directive 2004/108/EC) EN (Low-voltage directive 2006/95 EC). 62

65 Technical Data Functions NOTE: Ir: CT rated secondary current, 1A or 5A; Overcurrent protection (ANSI 50, 51, 67) Item Rang or Value Tolerance Definite time characteristics Current 0.08 Ir to Ir ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s Reset time approx. 40ms Reset ratio Approx at I/In 0.5 Inverse time characteristics ±1% setting or +40ms, at 200% operating setting Current 0.08 Ir to Ir ±3% setting or ±0.02Ir IEC standard Normal inverse; Very inverse; Extremely inverse; Long inverse ANSI Inverse; Short inverse; Long inverse; Moderately inverse; Very inverse; Extremely inverse; Definite inverse user-defined characteristic T= Time factor of inverse time, A to 200.0s, step 0.001s ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC ±5% setting + 40ms, at 2 <I/ISETTING < 20, in accordance with ANSI/IEEE C37.112, ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC Delay of inverse time, B to 60.00s, step 0.01s Index of inverse time, P to 10.00, step set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time 20ms Maximum operating time 100s Reset mode instantaneous Reset time approx. 40ms, Directional element Operating area range 170 ±3, at phase to phase 63

66 Technical Data Characteristic angle 0 to 90, step 1 voltage >1V Earth fault protection (ANSI 50N, 51N, 67N) Item Rang or value Tolerance Definite time characteristic Current 0.08 Ir to Ir ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s Reset time approx. 40ms Reset ratio Approx at I/Ir 0.5 Inverse time characteristics ±1% setting or +40ms, at 200% operating setting Current 0.08 Ir to Ir ±3% setting or ±0.02Ir IEC standard ANSI user-defined characteristic Time factor of inverse time, A Normal inverse; Very inverse; Extremely inverse; Long inverse Inverse; Short inverse; Long inverse; Moderately inverse; Very inverse; Extremely inverse; Definite inverse T= to 200.0s, step 0.001s IEC ±5% setting + 40ms, at 2 <I/I SETTING < 20 ANSI/IEEE C37.112, ±5% setting + 40ms, at 2 <I/I SETTING < 20 IEC ±5% setting + 40ms, at 2 <I/I SETTING < 20 Delay of inverse time, B to 60.00s, step 0.01s Index of inverse time, P to 10.00, step set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time Maximum operating time Reset mode 20ms 100s instantaneous Reset time approx. 40ms Directional element Operating area range of zero sequence directional element 160 Characteristic angle 0 to 90, step 1 ±3, at 3U0 1V 64

67 Technical Data Operating area range of negative sequence directional element 160 Characteristic angle 50 to 90, step 1 ±3, at 3U2 2V Non-directional neutral earth fault protection (ANSI 50G, 51G) Item Rang or value Tolerance Definite time characteristic Current 0.08 Ir to Ir ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s Reset time approx. 40ms Reset ratio Approx at I/Ir 0.5 Inverse time characteristics ±1% setting or +40ms, at 200% operating setting Current 0.08 Ir to Ir ±3% setting or ±0.02Ir IEC standard ANSI user-defined characteristic Time factor of inverse time, A Normal inverse; Very inverse; Extremely inverse; Long inverse Inverse; Short inverse; Long inverse; Moderately inverse; Very inverse; Extremely inverse; Definite inverse T= to 200.0s, step 0.001s ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC ±5% setting + 40ms, at 2 <I/ISETTING < 20, in accordance with ANSI/IEEE C37.112, ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC Delay of inverse time, B to 60.00s, step 0.01s Index of inverse time, P to 10.00, step set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time Maximum operating time Reset mode 20ms 100s instantaneous Reset time approx. 40ms Characteristic angle 0 to 90, step 1 65

68 Technical Data Sensitive/normal earth fault protection (ANSI 50Ns, 51Ns, 67Ns) Item Range or value Tolerance Definite time characteristic Current from sensitive CT input to A, step A ±3 % setting value or 1 ma Current from neutral CT input 0.08 Ir to Ir ±3 % setting value or 0.02 Ir Time delay 0.00 to 60.00, step 0.01 s ±1.5 % setting value or +40 ms, at 200% operating setting Reset ratio Approx when I/In 0.5 Reset time Approx. 40 ms Inverse time characteristics Current from sensitive input to A, step A ±3 % setting value or 1 ma Current from normal input 0.08 Ir to Ir ±3 % setting value or 0.02 Ir IEC standard ANSI user-defined characteristic Normal inverse; Very inverse; Extremely inverse; Long inverse Inverse; Short inverse; Long inverse; Moderately inverse; Very inverse; Extremely inverse; Definite inverse T= A i I S T Time factor of inverse time, A to 200.0s, step 0.001s 1 k ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC ±5% setting + 40ms, at 2 <I/ISETTING < 20, in accordance with ANSI/IEEE C37.112, ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC Delay of inverse time, B to 60.00s, step 0.01s Index of inverse time, P to 10.00, step set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time Maximum operating time Reset mode Reset time 20ms 100s instantaneous approx. 40ms Directional element for sensitive earth-fault protection principles I cos Φ Φ (V0 / I0) 66

69 Technical Data Direction measurement IE and VE measured or 3V0 calculated 3U0 Minimum voltage threshold 2.00 to V, step 0.01 V ±3 % setting for measured voltage; ±5 % setting for calculated voltage Characteristic angle Φ_S FChar 0.0 to 90.0, step 1 ±3 Operating area range 160 ±3 Negative sequence current protection (ANSI 46) Item Rang or Value Tolerance Definite time characteristic Current 0.08 Ir to Ir ±3% setting value or ±0.02Ir Time delay 0.00 to 60.00, step 0.01 s ±1% setting or +40ms, at 200% operating setting Reset time 40 ms Reset ratio Approx for I2 /Ir > 0.5 Inverse time characteristics Current 0.08 Ir to Ir ±3% setting or ±0.02Ir IEC standard ANSI user-defined characteristic Normal inverse; Very inverse; Extremely inverse; Long inverse Inverse; Short inverse; Long inverse; Moderately inverse; Very inverse; Extremely inverse; Definite inverse T= A i I S T Time factor of inverse time, A to 200.0s, step 0.001s 1 k ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC ±5% setting + 40ms, at 2 <I/ISETTING < 20, in accordance with ANSI/IEEE C37.112, ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC Delay of inverse time, B to 60.00s, step 0.01s Index of inverse time, P to 10.00, step set time Multiplier for step n: k 0.05 to 999.0, step 0.01 Minimum operating time 20ms Maximum operating time 100s 67

70 Technical Data Reset time approx. 40ms Inrush restraint function Item Range or value Tolerance Upper function limit Max current for inrush restraint Ratio of 2 nd harmonic current to fundamental component current Cross-block (IL1, IL2, IL3) (settable time) 0.25 Ir to Ir ±3% setting value or ±0.02Ir 0.10 to 0.45, step s to s, step 0.01s ±1% setting or +40ms Thermal overload protection (ANSI-49) Item Rang or Value Tolerance Current 0.1 Ir to 5.00 Ir ±3% setting or ±0.02Ir Thermal heating time constant 1 to 9999 s Thermal cooling time constant 1 to 9999 s IEC cold curve t ln I I 2 2 eq I 2 eq IEC , ±5% setting or +40ms IEC hot curve t I ln I 2 2 eq I P IEC , 2 2 eq I ±5% setting or +40ms Breaker failure protection (ANSI 50 BF) Item Rang or Value Tolerance phase current Negative sequence current zero sequence current 0.08 Ir to Ir ±3% setting or ±0.02Ir Time delay of stage s to s, step 0.01s ±1% setting or +25 ms, at Time delay of stage s to s, step 0.01s 200% operating setting Reset ratio >0.95 Reset time of stage 1 < 20ms Dead zone protection (ANSI 50DZ) Item Rang or Value Tolerance 68

71 Technical Data Current 0.08 Ir to Ir ±3% setting or ±0.02Ir Time delay 0.00s to 32.00s, step 0.01s ±1% setting or +40 ms, at 200% operating setting Reset ratio >0.95 Under voltage protection (ANSI 27) Item Rang or Value Tolerance Voltage connection Phase-to-phase voltages or phase-to-earth voltages ±3 % setting or ±1 V Phase to earth voltage 5 to 75 V, step 1 V ±3 % setting or ±1 V Phase to phase voltage 10 to 150 V, step 1 V ±3 % setting or ±1 V Reset ratio 1.01 to 2.00, step 0.01 ±3 % setting Time delay 0.00 to s, step 0.01 s ±1 % setting or +50 ms, at 80% operating setting Current criteria 0.08 to 2.00 Ir ±3% setting or ±0.02Ir Reset time 50 ms Overvoltage protection (ANSI 59) Item Rang or Value Tolerance Voltage connection Phase-to-phase voltages or phase-to-earth voltages ±3 % setting or ±1 V Phase to earth voltage 40 to 100 V, step 1 V ±3 % setting or ±1 V Phase to phase voltage 80 to 200 V, step 1 V ±3 % setting or ±1 V Reset ratio 0.90 to 0.99, step 0.01 ±3 % setting Time delay 0.00 to s, step 0.01s ±1 % setting or +50 ms, at 120% operating setting Reset time <40ms Voltage displacement protection (ANSI 64) Item Rang or Value Tolerance Pickup threshold 3V0 2 to 100 V, step 1 V ± 5 % setting value or ±1 V (calculated) Time delay 0.00 to s, step 0.01s ±1 % setting or +50 ms, at 120% operating setting Reset ratio Approx

72 Technical Data Synchro-check and voltage check (ANSI 25) Operating mode Item Rang or Value Tolerance Synchronization check: Synch-check Energizing check, and synch-check if energizing check failure Override Energizing check: Dead V4 and dead V 3Ph Dead V4 and live V 3Ph Live V4 and dead V 3Ph Voltage threshold of dead line or bus Voltage threshold of live line or bus V-measurement Voltage difference 10 to 50 V (phase to earth), step 1 V 30 to 65 V (phase to earth), step 1 V 1 to 40 V (phase-to-earth), steps 1 V ± 3 % setting or 1 V ± 3 % setting or 1 V ± 1V Δf-measurement (f2>f1; f2<f1) 0.02 to 2.00 Hz, step, 0.01 Hz, ± 20 mhz Δα-measurement (α2>α1; α2<α1) 1 to 80, step, 1 ± 3 Minimum measuring time 0.05 to s, step,0.01 s, ± 1.5 % setting value or +60 ms Maximum synch-check extension time 0.05 to s, step,0.01 s, ± 1 % setting value or +50 ms Auto-reclosing (ANSI 79) Item Rang or Value Tolerance Number of reclosing shots Up to 4 Shot 1 to 4 is individually selectable AR initiating functions Dead time, separated setting for shots 1 to 4 Reclaim time Blocking duration time (AR reset Internal protection functions External binary input 0.05 s to s, step 0.01 s ± 1 % setting value or +50 ms 0.50 s to 60.00s, step 0.01 s 0.05 s to 60.00s, step 0.01 s 70

73 Technical Data time) Circuit breaker ready supervision time Dead time extension for synch-check (Max. SYNT EXT) 0.50 s to s, step 0.01 s 0.05 s to s, step 0.01 s Load shedding protection Item Rang or Value Tolerance Under Frequency Load shedding Frequency for fr =50Hz to Hz, step 0.01 Hz ±20 mhz Time delay 0.05 to 60.00s, step 0.01 ±1.5 % setting or +60 ms Under Voltage Load shedding Voltage 50 to 110 V, step 1V ±3 % setting or ±1 V Time delay ±1.5 % setting or +60 ms, at 0.10 to 60.00s, step 0.01 s 80% operating setting Overload Load shedding Phase current 0.08 to 20 A for Ir =1A ±3% setting or ±0.02Ir 0.25 to 100 A for Ir =5A Time delay 0.10 to 60.00s, step 0.01 s ±1.5 % setting or +60 ms, at 200% operating setting Blocking condition Frequency change rate Δf/Δt 1 to 10 Hz/s ±0.5 Hz/s Voltage change rate Δu/Δt 1 to 100 V/s, step 1 V/s ±3 % setting or ±1 V Blocking voltage 10 to 120V, step 1 V ±3 % setting or ±1 V Blocking current 0 to 2 Ir ±3% setting or ±0.02Ir Operating time Approx. 60 ms Reset time Approx. 60 ms Under voltage blocking reset ratio Approx. 1 VT secondary circuit supervision (97FF) Item Range or value Tolerances Minimum current 0.08Ir to 0.20Ir, step 0.01A ±3% setting or ±0.02Ir Minimum zero or negative sequence current 0.08Ir to 0.20Ir, step 0.01A ±5% setting or ±0.02Ir Maximum phase to earth voltage 7.0V to 20.0V, step 0.01V ±3% setting or ±1 V Maximum phase to phase voltage 10.0V to 30.0V, step 0.01V ±3% setting or ±1 V 71

74 Technical Data Normal phase to earth voltage 40.0V to 65.0V, step 0.01V ±3% setting or ±1 V 72

75 Ordering Pre-configure scheme of standard version Table 4 Function and hardware of the pre-configure scheme (1) Pre-configure scheme M01 M02 M03 M04 M05 M06 M07 Application (N1) Full TB CF F SF SF BCPU Non-directional overcurrent protection (50,51) 1 1 Overcurrent protection (50,51,67) Non-directional earth fault protection (50N, 51N) 1 1 Earth fault protection (50N, 51N, 67N) Non-directional sensitive earth fault protection (50Ns, 51Ns) Sensitive earth fault protection (50Ns, 51Ns, 67Ns) Neutral earth fault protection (50G, 51G) Negative sequence overcurrent protection (46) Thermal overload protection (49) 1 1 Overload protection (50OL) Overvoltage protection (59) Under voltage protection (27) Displacement voltage protection (64) 1 1 Breaker failure protection (50BF) Dead zone protection (50DZ) Synchro-check and energizing check (25) Auto-reclosing (79) Unbalanced current protection (46NI) Unbalanced voltage protection (46NU) Undercurrent protection (37) Low frequency load shedding function

76 Ordering (81U) Low voltage load shedding function (27) Overload load shedding function CT secondary circuit supervision VT secondary circuit supervision (97FF) Fast busbar protection using reverse interlocking (1) (1) (1) (1) (1) Analogue input module Analogue input module Binary input/output module (1) (1) (1) (1) (1) (1) 1 CPU module Direct binary input and output module Binary output module Power supply module Human interface Case, 4U,1/

77 Ordering Table 5 Function and hardware of the pre-configure scheme of standard version (2) Pre-configure scheme V01 V02 C01 C02 Application (N1) V V C C Non-directional overcurrent protection (50,51) Overcurrent protection (50,51,67) 1 1 Non-directional earth fault protection (50N, 51N) Earth fault protection (50N, 51N, 67N) 1 1 Non-directional sensitive earth fault protection (50Ns, 51Ns) Sensitive earth fault protection (50Ns, 51Ns, 67Ns) 1 1 Neutral earth fault protection (50G, 51G) Negative sequence overcurrent protection (46) Thermal overload protection (49) Overload protection (50OL) 1 1 Overvoltage protection (59) Under voltage protection (27) Displacement voltage protection (64) Breaker failure protection (50BF) 1 1 Dead zone protection (50DZ) 1 1 Synchro-check and energizing check (25) Auto-reclosing (79) Unbalanced current protection (46NI) 1 Unbalanced voltage protection (46NU) 1 Undercurrent protection (37) 1 1 Low frequency load shedding function (81U) Low voltage load shedding function (27) Overload load shedding function CT secondary circuit supervision 1 1 VT secondary circuit supervision (97FF) Fast busbar protection using reverse interlocking (1) (1) 75

78 Ordering Analogue input module Analogue input module Binary input/output module (1) (1) (1) (1) CPU module Binary direct input and output module Binary output module Power supply module Human interface Case, 4U,1/ NOTE: n : Quantity of standard function or standard hardware, n= 1, 2,.; (n) : Quantity of optional function or optional hardware, n= 1, 2,.; N1: Application: Full Full functions version TB For transformer backup protection CF For complicated feeder F For feeder SF For simple feeder V For dedicated voltage protection IED C For dedicated capacitor protection IED BCPU: Feeder control and protection unit with advanced interlocking logic 76

79 Ordering Pre-configure scheme of advanced version Table 6 Function and hardware of the pre-configure scheme Pre-configure scheme Application (N1) M10 AD Non-directional overcurrent protection (50,51) Overcurrent protection (50,51,67) 1 Non-directional earth fault protection (50N, 51N) Earth fault protection (50N, 51N, 67N) 1 Non-directional sensitive earth fault protection (50Ns, 51Ns) Sensitive earth fault protection (50Ns, 51Ns, 67Ns) 1 Neutral earth fault protection (50G, 51G) Negative sequence overcurrent protection (46) Thermal overload protection (49) Overload protection (50OL) 1 Overvoltage protection (59) 1 Under voltage protection (27) 1 Displacement voltage protection (64) 1 Breaker failure protection (50BF) Dead zone protection (50DZ) Synchro-check and energizing check (25) 1 Auto-reclosing (79) 1 Unbalanced current protection (46NI) Unbalanced voltage protection (46NU) Undercurrent protection (37) Low frequency load shedding function (81U) 1 Low voltage load shedding function (27) Overload load shedding function CT secondary circuit supervision 77

80 Ordering VT secondary circuit supervision (97FF) 1 Fast busbar protection using reverse interlocking Analogue input module 1 1 Analogue input module 2 1 Binary input/output module 2 CPU module 1 Direct binary input and output module 1 Power supply module 1 Front plate 1 Case, 4U,1/ NOTE: n : Quantity of standard function or standard hardware, n= 1, 2,.; (n) : Quantity of optional function or optional hardware, n= 1, 2,.; N1: Application: Full Full functions version TB For transformer backup protection CF For complicated feeder F For feeder SF For simple feeder V For dedicated voltage protection IED C For dedicated capacitor protection IED BCPU - Feeder control and protection unit with advanced interlocking logic AD Advanced version 78

81 Ordering Ordering code of standard version No.1~16 No.17~35 C S C L F T Pre-configure Scheme Feeder or backup protection scheme Voltage protection scheme Capcitor protection scheme Pre-configure scheme number 1 Pre-configure scheme number 2 M V C 0~9 0~9 HMI Language (L) note English Russian French Portuguese Spanish Rated Frequency (F) 50 Hz 5 60 Hz 6 Station Communication Protocols (T) Ethernet interface:iec ; RS485 interface: IEC Ethernet interface:iec ; RS485 interface: IEC Note: Chinese is always offered as default HMI language. 79

82 Ordering No.1~16 No.17~25 No.26~35 C S C A B M D Slot1 Analogue Input Module 1 (A) Isef +1Im I0(1A) +1Im I0(5A) +1Im Isef+3Uub+1Im I0(1A)+3Uub+1Im I0(5A)+3Uub+1Im Isef+3Iub(1A) +1Im I0(1A)+3Iub(1A) +1Im I0(5A)+3Iub(1A) +1Im Null e f g j u x Slot2 Analogue Input Module 2 (A) 3Ip(1A)+I0(1A)+2Im+4U 1 3Ip(1A)+I0(5A)+2Im+4U 2 3Ip(5A)+I0(1A)+2Im+4U 3 3Ip(5A)+I0(5A)+2Im+4U 4 4U 5 Slot3 Binary Input and Output module (B) 7BI (220V) + 9 relays 7BI (110V) + 9 relays Null 1 2 x Slot4 CPU module (M) 7BI (24V), 2 Ethernet RJ45 ports, 1 RS485 port, IRIG-B 7BI (24V), 2 Ethernet RJ45 ports, 1 RS485 port, Pulse 1 2 Slot5 Direct binary Input and Output module (D) 4BI (220V) +7 output relays 4BI (110V) +7 output relays

83 Ordering No.1~25 No.26~35 C S C O P H K Z Slot6 Binary Output Module (O) 5 relays, 2 contacts per relay 1 Null x Slot7 Power Supply Module (P) 220V DC, 9BI (220V), 1 alarm relay 110V DC, 9BI (110V), 1 alarm relay 1 2 Human Machine Interface (H) Medium, 160*80, Alphanumeric, 11 LEDs 1 Case (K) Case: 4U, ½ 19' 1 Accessories (Z) Front cover [IP54, Transparent plexiglass cover] Null 1 x 81

84 Ordering Ordering code of advanced version No.1~16 No.17~35 C S C L F T Pre-configure Scheme Feeder or backup protection scheme M Pre-configure scheme number 1 1 Pre-configure scheme number 2 0 HMI Language (L) note English Russian French Portuguese Spanish Rated Frequency (F) 50 Hz 5 60 Hz 6 Station Communication Protocols (T) Ethernet interface:iec ; RS485 interface: IEC Ethernet interface:iec ; RS485 interface: IEC Note: Chinese is always offered as default HMI language. 82

85 Ordering No.1~16 No.17~25 No.26~35 C S C A B M B Slot1 Analogue Input Module 1 (A) Isef +1Im I0(1A) +1Im I0(5A) +1Im Null x Slot2 Analogue Input Module 2 (A) 3Ip(1A)+I0(1A)+2Im+4U 3Ip(1A)+I0(5A)+2Im+4U 3Ip(5A)+I0(1A)+2Im+4U 3Ip(5A)+I0(5A)+2Im+4U Slot3 Binary Input and Output module (B) 5BI (220V) + 8 relays 5BI (110V) + 8 relays Null 1 2 x Slot4 CPU module (M) 3BI (24V), 3 Ethernet RJ45 ports, 1 RS232 port, IRIG-B 3BI (24V), 2 Ethernet RJ45 ports, 2 RS485 port, 1 RS232 port, IRIG-B 3BI (24V), 2 Ethernet optical ports, 1 RS232 port, IRIG-B Slot5 Binary Input and Output module (B) 5BI (220V) +8 output relays 5BI (110V) +8 output relays Null 1 2 x 83

86 Ordering No.1~25 No.26~35 C S C D P H K Z Slot6 Direct binary Input&Output Module (D) 5BI (220V) +7 output relays 5BI (110V) +7 output relays 1 2 Slot7 Power Supply Module (P) 220V DC, 10BI (220V), 5 signaling output relays 110V DC, 10BI (110V), 5 signaling output relays 1 2 Human Machine Interface (H) 320*240, Graphic & Alphanumeric; 16 LEDs 1 Case (K) Case: 4U, ½ 19' 1 Accessories (Z) Front cover [IP54, Transparent plexiglass cover] Null 1 x 84

87 Address: No.9 Shangdi 4th Street, Haidian District, Beijing, P.R.C Tel: , ext.8998 Fax: Website:

CSC-211 Multifunction Protection IED Product Guide

CSC-211 Multifunction Protection IED Product Guide CSC-211 Multifunction Protection IED Product Guide Version:V1.20 Doc. Code: 0SF.492.057(E) Issued Date:2013.12 Copyright owner: Beijing Sifang Automation Co., Ltd Note: The company keeps the right r to

More information

CSC-161 Line Protection IED Product Guide

CSC-161 Line Protection IED Product Guide CSC-161 Line Protection IED Product Guide Version V1.10 Doc. Code: 0SF.492.052(E) Issued Date 2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the

More information

CSC-121 Breaker Protection IED Product Guide

CSC-121 Breaker Protection IED Product Guide CSC-121 Breaker Protection IED Product Guide Version V1.10 Doc. Code: 0SF.492.053(E) Issued Date 2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

CSC-150 Busbar Protection IED Product Guide

CSC-150 Busbar Protection IED Product Guide CSC-150 Busbar Protection IED Product Guide Version V1.0 Doc. Code: 0SF.492.056(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the

More information

CSC-121 Breaker Protection IED Technical Application Manual

CSC-121 Breaker Protection IED Technical Application Manual CSC-121 Breaker Protection IED Technical Application Manual Version:V1.01 Doc. Code: 0SF.455.058 (E) Issued Date:2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd Note: the company keeps the right

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

CSC-150 Busbar Protection IED Technical Application Manual

CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual Compiled: Jin Rui Checked: Hou Changsong Standardized: Li Lianchang Inspected: Cui

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network. Landsnet-Icegrid Requirements for protection and control systems. Principles for the Icelandic power transmission network. Introduction.... 4 System requirements... 6 Validity:... 6 Requirements for protection:...

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

Perfect protection smallest space

Perfect protection smallest space www.siemens.com/energy/protection Perfect protection smallest space The SIPROTEC Compact device range redefines protection technology Answers for energy. SIPROTEC Compact is the ideal solution for almost

More information

CSC-150 Busbar Protection IED Technical Application Manual

CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual CSC-150 母线保护装置 技术应用说明书 编制 : 校核 : 标准化审查 : 审定 : 版本号 :V1.02 文件代号 : 出版日期 :2015.9 Version:V1.02 Doc. Code: 0SF.450.087(E) Issued Date:2015.9 Copyright

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES Introduction The supply of electrical energy occupies an important position in the life of modern society. Operation of commerce, industry, transport,

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Maximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays

Maximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays Maximize protection Sepam series 10, 20, 40, 60, 80 Modular range of digital protection relays Fast Dependable Simple Increase energy availability 100% available energy Fast response Maximum dependability

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

CSC-326 Transformer Protection IED Product Guide

CSC-326 Transformer Protection IED Product Guide CSC-326 Transformer Protection IED Product Guide Version:V1.11 Doc. Code: 0SF.492.054(E) Issued Date: 2013.12 Copyright owner: Beijing Sifang Automation Co., Ltd Note: The company keeps the t right to

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile GE Grid Solutions MiCOM Agile P746 Numerical Busbar Protection The MiCOM Agile P746 centralized numerical busbar protection provides complete protection for all voltage levels up to extra voltage busbar

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ-200 series protection, control, measurement and monitoring IEDs Contents AQ-200 series protection and control IEDs 3 AQ-200 benefits 3 Arcteq innovation: ultra-accurate measurement technology

More information

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line

More information

Application Notes on Generator Protection Schemes

Application Notes on Generator Protection Schemes Application Notes on Generator Protection Schemes Single Line Diagram Examples 1. Introduction The application notes provide selected single line diagrams for the SIPROTEC 4 generator protection device

More information

2 nd Edition INTRODUCTION

2 nd Edition INTRODUCTION 2 nd Edition INTRODUCTION TPU S220 compact protection and control relay, part of Efacec CLP-500 platform, is a cost-effective and secure solution for line/feeder protection. They can also be used for backup

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays PROTECTION MiCOM P12x/y Three phase and earth fault overcurrent relays The MiCOM P12x/y relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault

More information

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation

More information

MiCOM P14x AREVA T&D. Feeder Management Relays

MiCOM P14x AREVA T&D. Feeder Management Relays P R OT E C T I O N MiCOM P14x Feeder Management Relays MiCOM P14x feeder management relays provide an integrated solution for the complete protection, control and monitoring of overhead lines and underground

More information

Three phase and earth fault overcurrent relays

Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and 6-154 kv networks automation, have different functionality

More information

RMS Product Presentation

RMS Product Presentation RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4 Content FPC 400 USER MANUAL Apr 2017 Feeder F3 Motor M4 Busbar B3 Transformer T4 1 USER MANUAL FPC 400-4/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia 2016. All rights reserved.

More information

Current Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date

Current Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date Offshore Spotlight ENERGY Issue 02 Oct 2013 www.siemens.com/reyrolle Current Matters Siemens Protection Devices Ltd Protecting your electrical assets... today and tomorrow The Device issue In-depth looks

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

MiCOM P14x. Feeder Management Relays

MiCOM P14x. Feeder Management Relays 01 Feeder Management Relays feeder management relays provide an integrated solution for the complete protection, control and monitoring of overhead lines and underground cables from distribution to transmission

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

High-speed transformer differential protection for up to five terminals

High-speed transformer differential protection for up to five terminals Transformer Protection Relay High-speed transformer differential protection for up to five terminals Advanced differential protection and three restricted earth fault (REF) elements minimize damage and

More information

SIPROTEC Compact Overcurrent Protection 7SJ81 for Low-Power CT and VT Applications

SIPROTEC Compact Overcurrent Protection 7SJ81 for Low-Power CT and VT Applications SIPROTEC Compact Overcurrent Protection SJ for Low-Power CT and VT Applications Overcurrent Protection SJ for Low-Power CT and VT Applications Page Description / Function overview / Applications / Application

More information

MiCOM P12x/y. Three phase and earth fault overcurrent relays

MiCOM P12x/y. Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Relion 630 series Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Integrated load-shedding and protection solution The PML630 is a freely-configurable

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

Power systems 5: Protection

Power systems 5: Protection Power systems 5: Protection Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. As you will recall from our Introduction to Electrical

More information

Perfect protection smallest space

Perfect protection smallest space www.siemens.com/siprotec Perfect protection smallest space The SIPROTEC Compact device range redefines protection technology Answers for infrastructure and cities. SIPROTEC Compact is the ideal solution

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

(1) Description of Operation 7SR224 Recloser Controller

(1) Description of Operation 7SR224 Recloser Controller (1) Description of Operation 7SR224 Recloser Controller DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and the publication numbers under which they can be ordered,

More information

7SR11 and 7SR12 Description of Operation

7SR11 and 7SR12 Description of Operation 7SR11 and 7SR12 Description of Operation Document Release History This document is issue 2012/02. The list of revisions up to and including this issue is: 2012/02 AC auxiliary power supply added 2012/01

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

Customized 1MRK BEN Product version: 1.1 Revision: Issued: March 2007 Data subject to change without notice

Customized 1MRK BEN Product version: 1.1 Revision: Issued: March 2007 Data subject to change without notice Product version: 1.1 Revision: Issued: March 2007 Data subject to change without notice Page 1 Features A control, protection, and monitoring IED with extensive functional library and configuration possibilities

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

SIPROTEC 4 7SJ64 Multifunction Protection Relay with Synchronization

SIPROTEC 4 7SJ64 Multifunction Protection Relay with Synchronization SIPROTEC 4 7SJ64 Multifunction Protection Relay with Synchronization Function overview Description The SIPROTEC 4 7SJ64 can be used as a protective control and monitoring relay for distribution feeders

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 5.90 Release otes GE Publication umber: GER-4401 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 5.90 release that introduces

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

Line distance protection IED REL 670

Line distance protection IED REL 670 Line distance protection IED REL 670 Product version: 1.1 Revision: A Issued: November 2007 Data subject to change without notice Page 1 Features A protection, control, and monitoring IED with extensive

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 4.43 Release Notes GE Publication Number: GER-4380Rev1 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 4.43 release that introduces

More information

Connectivity Packages. User's Guide - ANSI Version

Connectivity Packages. User's Guide - ANSI Version Connectivity Packages 1MRS756194 Issued: 30.11.2006 Version: A/30.11.2006 Connectivity Packages Contents Copyrights... 5 1. Introduction...... 7 1.1. Intended audience...... 7 1.2. Related documents.........

More information

4. CIRCUIT BREAKERS. Functional Emergency Switching

4. CIRCUIT BREAKERS. Functional Emergency Switching 4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit

More information

Synchro-check relay. Application

Synchro-check relay. Application Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to

More information