DCIM Data Center Infrastructure Management
|
|
- Jeffery Campbell
- 5 years ago
- Views:
Transcription
1 DCIM Data Center Infrastructure Management Part 2 Implementation Challenges & Strategic Advantages - Predictive Analysis August 8, 2013 Presented by Julius Neudorfer Sponsored by
2 Today s Topics Implementation Challenges! Strategic Advantages of DCIM Predictive and Proactive maintenance analysis to improve overall availability Capacity planning to improve operational and energy efficiency
3 Implementation Challenges Environmental Sensor installation Temperature Humidity-Airflow-Static Pressure Cabled or Wireless Energy Monitoring- Level of Granularity UPS (power measurement may be built-in not energy) Power Distribution PDU, Rack, IT Device Cooling CRAH, Chillers, Pumps, Fans
4 Facilities Monitoring Points
5 Implementation Retrofit Issues Electrical Panels Energy Monitoring Requires Adding Current Sensors (CT) and Voltage Sensors (PT) to Electrical Panels Live Hot Work not permitted by OSHA May Require Shutdown of Panel (and load!) Adding Intelligent Rack PDUs Typically Plug-in to existing receptacles Require IT Power down, unless PS Redundant A-B
6 Existing System Integration Existing BMS and IT systems may already have a wide range of sensors and can provide some of the data Integration of these systems can avoid installing duplicate sensors However, while it seems simple on face value, it is sometimes far easier said then done
7 Communications IT Equipment TCP/IP (IT Network Standards) SNMP Simple Network Management Protocol IPMI Intelligent Platform Management Interface (INTEL) Facilities Building Management Systems (BMS) BACNet (ASHRAE) Modbus (dedicated serial wiring) LON Network unshielded twisted pair (UTP) cable BACNet-Modbus/TCP (over UDP) Interoperability and Compatibility Issues Vendor specific and propriety
8 Communications Wireless Ethernet 802.x (WiFi: A-B-G-N, etc.) Zigbee Mesh Network Vendor Proprietary Dedicated Hardwire (BacNet-Modbus) Ethernet: Separate management network or over production network Vendor interoperability IT MIBs Facilities Modbus Register Mapping
9 Frequency of Data Gathering Real-Time (1-60 seconds) Frequency: 1, 5, 15 or 60 Minutes Trending: Hourly, Daily, Weekly, Monthly Frequency of Polling increases data base size Number of Monitoring Points (devices, nodes) can impact size, speed and cost of system
10 Challenges Multi-Vendor Integration The ability to accept or poll data from different vendor equipment or monitoring of existing Facilities Systems: Power/Energy UPS Floor Level Distribution: PDU/Wall Panel Branch Circuit Cooling Systems Cooling Systems (Temperature - ΔT & Humidity) CRAC, CRAH, Chillers, Pumps, Cooling Towers External Conditions: Temperature and Humidity Room Environmental Conditions: Cold Aisle & Hot Aisle At each Rack - via IT systems
11 Challenges - Integration of IT Equipment The ability to accept or poll data from different vendor equipment or monitoring of existing IT Systems: Power Draw (Per Rack or Device) Servers, Storage, Switches Utilization CPU, Disk Space, Bandwidth, Etc. Cooling Intake Temperature & Exhaust Temperature (ΔT)
12 Strategic Advantages of DCIM Predictive and proactive maintenance analysis to improve overall availability Capacity planning to improve operational and energy efficiency
13 Potential Benefits Facility Power Provisioning Branch Circuits Receptacle Types Cooling Airflow Optimization Match to Rack Level Heat Load Less Hot Spots Less Overcooling Improved Energy Efficiency Proactive Monitoring & Preventive Maintenance Detect Performance Changes
14 Real-time Monitoring Allows Proactive Maintenance Basic Facility Power (kva/kw Real-Time/Instantaneous) Energy (KWH Power over Time) - PUE Temperature & Humidity Actionable: Baseline > Alarm set points Trends > Early Warning Proactive Maintenance Resource and Energy Optimization
15 Electrical Energy Measurement
16 Improved Availability Proactive Maintenance Early detection reduces chances of system or component level failure by of performance degradation Preemptive service rather than reactive break-fix or simple scheduled periodic intervals
17 Baseline and Trends Provide Early Problem Detection Proactive Maintenance IT Load Cooling Energy Total Chiller 150 CRAH-Fans CRAH-Humidity 100 Pumps-CW Condenser Fans 50?????? Pumps-Condenser 0 Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec
18 Potential Benefits IT Equipment typically refreshes every 3 years Planning Simulation and Modeling Capacity Management Better Provisioning Moves, Adds and Changes
19 Cohesive Alignment of IT and Facilities IT Asset Management Rack-Row Provisioning: Power Cooling Networking Better Facilities Resource Allocation
20 Benefits of Predictive Modeling Total Cost of Ownership TCO Energy Saving Better System Management under varying conditions Model Changes > Implement > Review Outcome Labor saving Reduces or eliminates manual power usage surveys Reduces or eliminates manual temperature surveys Avoid Human Error and manual data center (Spreadsheets) Result - Reduced TCO
21 Improved Availability Predictive Analysis Cooling systems Avoids overstressing some cooling system components by potential overloading or imbalanced due to poorly distributed heat loads Avoids or minimizes creating potential future hot spots as IT equipment is added which could reduce equipment reliability
22 Improved Availability Predictive Analysis IT Equipment Insures proper airflow under dynamic IT loading conditions Avoids or minimizes creating potential future hot spots as IT equipment is added which could reduce IT equipment reliability Cooling Failure Scenarios Impact on IT equipment Airflow and temperature visualization during cooling unit failure
23 Predictive Modeling CRAC Failure Failed Simplified example for clarity
24 Stranded Capacity Stranded capacity is inability to fully utilize the entire design capacity of the: Entire data center Row Rack This is due to a less than optimal allocation of the primary resources due many variables, but perhaps caused by a lack of proper planning
25 Avoid Stranded Capacity Caused by Mismatch Apparent Capacity - Facility Level Space Total / % Available Power Total / % Available Cooling Total / % Available Usable Capacity - Row/Rack Level Space Power Cooling Space Power Cooling
26 IT Capacity Planning Tool Predictive Modeling can provide the ability to determine if and where new IT equipment can be deployed Rack Level Space U Total/Available Power Total/Available Cooling Total/Available Network Ports Total/Available
27 Causes of Stranded Capacity Hidden Mismatch of Cooling Requirements Average Density vs Rack Density Space Density Example: Bladeserver = 5kW Power Cooling Space: 10,000 sq/ft Power: 1,000 kw critical load design (UPS) Cooling: 1,000 kw (N+2) 12 x 30 Ton CRACs Density: 100 Watts Sq/Ft vs Watts per Rack
28 CFD Modeling for Predictive Analysis Airflow Management is one of the biggest issues when implementing adding or changing IT equipment Especially when moving toward higher densities or dynamic heat loads caused by virtualized IT Can help avoid stranded capacity issues due to Heat Density sometimes caused by less than optimal initial placement of IT equipment that is difficult to move once operational
29 CFD Modeling for Predictive Analysis Rack Density! Load 50% of Total Power Average Density: 100 Watts Sq/Ft Layout 330 Racks = 3 kw per rack (avg) 3 each = 15 kw
30 Before beginning DCIM project Be clear about your problems, and your expectations of the vendor deliverables Ensure your DCIM vendor can integrate with existing BMS or other monitoring systems Understand and plan for sensor installation challenges - (i.e. downtime) Resource allocation - Vendors require your cooperation and coordination!
31 DCIM is not just hardware and software It is a philosophical commitment to a holistic approach by Facilities and IT to work together to improve the overall energy efficiency, operations and availability of the data center
32 The Bottom Line There are multiple benefits to a successful DCIM project, some are directly cost justifiable (i.e. improved energy and operational efficiency), while others are less tangible, such as improved equipment deployment and potential increase of availability DCIM is a long term investment of both capital, time and labor which can run into the millions. It begs the ROI question, how long will it take to recover the cost
33 No Trees (virtual or real) were hurt or destroyed in the preparation of this presentation Thank you Julius Neudorfer Sponsored by
34 August 8, 2013 Datacenter Clarity LC Jay Hendrix Siemens AG 2013 All rights reserved. usa.siemens.com/datacenters
35 Datacenter Clarity LC High definition asset visualization and analytics Collaboration and process management Real-time monitoring, alarm and event notification DCIM Computational Fluid Dynamics (CFD) Key performance indicator dashboard Infrastructure life cycle management Open interface and protocol support
36 Datacenter Clarity LC Powered by Siemens PLM software Smarter decisions Optimized efficiencies Proven technologies Future proof architecture
37 Contact Siemens Infrastructure & Cities, Inc. Infrastructure and Cities Sector 1000 Deerfield Parkway Buffalo Grove, IL Jay Hendrix Building Technologies Head of Data Center Solutions North America
DCIM Data Center Infrastructure Management Measurement is the first step
DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by
More informationDCIM Data Center Infrastructure Management
DCIM Data Center Infrastructure Management Part 3 Operational Management Moves Adds and Changes & Electrical Infrastructure November 5, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Operational
More informationData Center Infrastructure Management ( DCiM )
Page 1 Data Center Infrastructure Management ( DCiM ) DCiM is defined by technology researchers and analysts as the integration of information technology (IT) and facility management disciplines to centralize
More informationPredictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime
July 17, 2013 Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime siemens.com/answers Predictive Resilience Table of content What is DCIM & Its Business Value Extract Maximum
More informationSystem architecture. Datacenter Clarity LC provides flexible client-server architectures configured to meet the needs of each organization,
Datacenter Clarity LC Tech sheet Overview As part of the Integrated Data Center Management Suite (IDCMS), Datacenter Clarity LC * provides tools for operating and optimizing data centers. This includes:
More informationLeveraging DCIM to Increase Energy Efficiency and Savings
August 6, 2013 Leveraging DCIM to Increase Energy Efficiency and Savings Siemens AG 2013 All rights reserved. usa.siemens.com/datacenters Contents Challenges of Today s Data Centers Turning Challenges
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationComprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
More informationTotal Building Solutions for Data Centers. The next generation of intelligence. usa.siemens.com/datacenters
Total Building Solutions for Data Centers The next generation of intelligence usa.siemens.com/datacenters Executive Summary Data center managers need to be able to leverage information to make their operations
More informationRemote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products
Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationData Center Infrastructure Management (DCIM) Demystified
software is quickly becoming the core engine of data center operations. Only 5 years ago, manual spreadsheets, sometimes supplemented with Visio diagrams, were accepted as the default tools for data center
More informationCRAH Retrofit and Energy Savings Project
CRAH Retrofit and Energy Savings Project Danny Johnson Director, Technical Operations Silicon Valley Leadership Group - Data Center Efficiency Summit October 24, 2012 2260 E. El Segundo Boulevard - A Digital
More informationsiemens.com/dcim We are the trusted technology partner for energy-efficient, safe and secure buildings and infrastructure.
Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 Tel: (847) 215-1000 Fax: (847) 215-1093 Subject to changes and errors. The information given in this
More informationsurvey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.
:: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach
More informationSystem architecture. Datacenter Clarity LC provides flexible client-server architectures configured to meet the needs of each organization,
Datacenter Clarity LC Tech sheet Overview Datacenter Clarity LC * is part of the Siemens BT Integrated Datacenter Management Suite (IDCMS). Clarity LC provides tools for operating and optimizing data centers,
More informationData Center Power Savings
Data Center Power Savings Data Center Power Savings Keith Mastrian, Regional Sales Manager, Raritan Data center power usage effectiveness (PUE), developed by The Green Grid, has received a lot of attention.
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationRAMP DCIM Data Center Infrastructure Management Software
RAMP DCIM Data Center Infrastructure Management Software RFP TEMPLATE 1-866-612-3637 SALES@TUANGRU.COM TUANGRU.COM DCIM RFP TEMPLATE Dear Sir or Madam, Your company has been invited to submit your company
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationFeatures and Benefits: Power IQ DCIM Monitoring Solutions
1 : Power IQ DCIM Monitoring Solutions Vendor-agnostic Management Energy Efficiency Through one web browser, monitor any device from major manufactures such as APC, Avocent, BayTech, Chatsworth, Cyber
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationPLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy
PLAYBOOK F O R C H A N G E How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy The world is becoming more digital every day. The demand for feature-rich,
More informationOver IP Group. Data Centre Infrastructure Management (DCIM)
Over IP Group Data Centre Infrastructure Management (DCIM) Mission To Protect the World s Network Through Innovation Let s Get Connected Over IP Group Agenda The Aim of CenterOS DCIM What is the CenterOS
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationData Center Infrastructure Management (D.C.I.M.)
Data Center Infrastructure Management (D.C.I.M.) Garies Chong, RCDD, DCDC. BICSI Southeast Asia District Chair Managing Director of EMS Wiring Systems Pte Ltd Data Center Infrastructure Management (D.C.I.M.)
More informationData Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationCA ecometer. Overview. Benefits. agility made possible. Improve data center uptime and availability through better energy management
PRODUCT SHEET: CA ecometer CA ecometer Improve data center uptime and availability through better energy management agility made possible CA ecometer helps you to visualize, monitor, and better manage
More informationModius OpenData v3.3. Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis
Modius OpenData v3.3 Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis Modius Inc. 832 Folsom, Suite 1001 San Francisco, CA 94107 888.323.0066 info@modius.com www.modius.com
More informationAPPLYING DATA CENTER INFRASTRUCTURE MANAGEMENT IN COLOCATION DATA CENTERS
APPLYING DATA CENTER INFRASTRUCTURE MANAGEMENT IN COLOCATION DATA CENTERS Table of Contents Executive Summary 3 The Colocation Market 4 An Introduction to DCIM 5 The Value of DCIM for Colocation Providers
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationMeasurement and Management Technologies (MMT) for more energy efficient Data Center and Telecommunication Facilities
Information and Communication Technology Portfolio Review San Francisco, CA March 2011 Project Name: Measurement and Management Technologies (MMT) for more energy efficient Data Center and Telecommunication
More informationData Center Optimized Controls
Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.
More informationPower Monitoring in the Data Centre
Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags
More informationTwo-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center
Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center Adapting to Change Concern over the pace of technology change is increasing among data center managers. This was reflected
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationMeasurement and Management Technologies (MMT)
IBM Systems Lab Services and Training Measurement and Management Technologies (MMT) Data Center Solutions for a Smarter Planet AGENDA IBM Energy Efficiency Program & Accomplishments IBM CO2 Reduction Commitment
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationARTO LIND ABB Ability Datacenter Automation. The way to monitor & control your DC infrastructure (DCIM) Datacenter Infrastructure Management
ARTO LIND ABB Ability Datacenter Automation The way to monitor & control your DC infrastructure (DCIM) Datacenter Infrastructure Management Data Center common functionality DCIM needs to be open to handle
More informationEnergyLok Environmental Monitoring System 300 Product Training. Stephanie Christensen National Account Manager 03/24/16
EnergyLok Environmental Monitoring System 300 Product Training Stephanie Christensen National Account Manager 03/24/16 Introduction Environmental Monitoring Defined Consists of a variety of solutions developed
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationIncreasing Data Center Efficiency through Metering and Monitoring Power Usage
White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationCisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project
Cisco Lab Setpoint Increase Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify key technology, policy and
More informationDCIM Solutions to improve planning and reduce operational cost across IT & Facilities
DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationLiebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity
Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationwhere we are, where we could be, how we can get there. 12/14/2011
Central Plant Optimization ASHRAE National Capitol Chapter - PES Wednesday, Nov 7, 2011 Dave Klee, LEED AP Director, Optimized Building Solutions Johnson Controls, Inc. 1 1 J o http://www.johnsoncontrols.com/cpo
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationCOOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS
COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS Dr Jon Summers Scientific Leader in Data Centers Part-time Academic in Thermofluids at the
More informationEmerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity
Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment AC Power For Business-Critical Continuity Enhanced Performance And Management Of Dynamic IT Spaces IT space is
More informationWIRELESS ENVIRONMENTAL MONITORS
Packet Powers compact wireless Environmental Monitors makes it easy and affordable to monitor all environmental conditions in your facility. From installation to monitoring in minutes 1 Place wireless
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationFt Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work
Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive
More informationROI CASE STUDY MAY Logicalis Achieves 159% ROI* with CA DCIM Solution
ROI CASE STUDY MAY 2015 Logicalis Achieves 159% ROI* with CA DCIM Solution 2 ROI CASE STUDY: LOGICALIS MAY 2015 Logicalis increases efficiency and maximizes availability with CA DCIM UK service provider
More informationCatch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable
Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable Urs Iten, Director Global Portfolio Management Data Center siemens.com/datacenters
More informationJack van der Horst, Regional Technology Manager, Asia Pacific. ABB
ABB DATA CENTER FORUM 2017, 11 JULY 2017, TUESDAY ABB Ability Data Center Automation Datacenter Automation for improved operations and reduced risks Jack van der Horst, Regional Technology Manager, Asia
More informationThe State of Data Center Health Management Strategy 2017
Strategic Alliance Partner Health Management Strategy The State of Data Center Health Management Strategy 2017 Fall 2017 Introduction Data has become one of the most valuable assets for 21st century businesses.
More informationDensity in the Data Center
Density in the Data Center INDUSTRY BRIEF Aug 2014 Density in the datacenter refers to the electric power consumed per square foot of floor space (or unit volume of space), number of servers, and the cooling
More informationBuilding Management Solutions. for Data Centers and Mission Critical Facilities
Building Management Solutions for Data Centers and Mission Critical Facilities How Efficient is Your Data Center? Recent years have seen rapid growth in global demand for computing capacity, resulting
More informationLiebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight
Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight LIEBERT icom THERMAL SYSTEM CONTROLS All for One, One for All Optimize a Single Cooling Unit With an Intelligent
More informationCHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM
CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable) Commercial Buildings New or Existing Institutional Buildings: Educational Facilities New
More informationOptimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc.
Optimize Your Data Center Gary Hill VP, Business Development DVL Group, Inc. Data Center Age Profile Gartner Group Survey Legacy Data Centers Challenges Under Powered - Room or Racks Inadequate Air Delivery
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationPower IQ for econnect
1 Center Energy, Power, Environmental, and Access Control Monitoring Software In today s data center, being efficient with power and cooling resources is just as important as maintaining uptime. Power
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationData Center Efficiency and Retrofit Best Practices
White Paper August 2014 IT@Intel Data Center Efficiency and Retrofit Best Practices The use of best practices enables us to increase data center efficiency and capacity, optimize the return on invested
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More information2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016
2016 COOLING THE EDGE SURVEY Conducted by Vertiv Publication Date: August 30, 2016 TWO STAGE POWER DISTRIBUTION Table of Contents Section I: Methodology Section II: Key Findings 1. Strategic Importance
More informationSmartRow Solution Intelligent, Integrated Infrastructure for the Data Center
SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center Deploy a Fully Configured Data Center in Just Weeks Availability, Capacity, Efficiency. You need them and now you can have them
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationThe End of Redundancy. Alan Wood Sun Microsystems May 8, 2009
The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationNovember/December 2011
November/December 2011 Company is justifiably proud of its new facilities Helping companies plan, design, operate, and eventually refresh or repurpose their data centers more efficiently and effectively
More informationRack PDU Marketing Playbook
PLAYBOOK Rack PDU Marketing Playbook Emerson Network Power Rack Power Distribution Unit (Rack PDU) Family Emerson Network Power offers the industry s only complete portfolio of Adaptive, Managed and Basic
More information