Next Generation Data Center Facilities Design. Presenter: Ping Lin
|
|
- Karin Park
- 5 years ago
- Views:
Transcription
1 Next Generation Data Center Facilities Design Presenter: Ping Lin
2 What is the greatest facility problem with your primary data center? 1. Excessive Heat 2. Insufficient raised floor area 3. Insufficient power 4. Poor location 5. Excessive facility cost 6. None of the above 29% 29% 21% 13% 6% 3% Source: Gartner Best Practices in Data Center Facilities Conference Poll Results (112) Dec.14, 2004
3 Heat Density Trends Uptime Institute trends have not changed Source: Uptime Institute, 2000
4 Major Causes of Electronic Equipment Failures Source: U.S. Air Force Avionics Integrity Program
5 High Density Server Market Forecast Source : IMEX Research 2003
6 Server Thermal Footprint Examples
7 Advanced TCA Shelf (Telco) 2~3KW Power Consumption Per Shelf
8 Rack Cooling Technologies Trend Traditional IT Equipment Close Cabinet Air Cooling Modern IT Equipment Close Cabinet Air Cooling High Density IT Equipments Enclosed Cabinet Air Cooling
9 Cool the Cabinet - Not the Room RackCooler: 8 kw, cooling module mounted on standard racks Knurr: 10 kw Internal cooling module, closed air-circuit Ecobay: 10.5 kw/cab, Internal cooling module, closed air-circuit
10 Traditional Approaches 180~360 Days Increasing Power & Cooling Capacity
11 Plug & Play Solution Close Loop Circulation Built-in in Evaporator
12 Power & HVAC Distributed Process Patch Panel Smoke Detector IDS + Firewall & Router Switch KVM Switch Intrusion Detector Thermal Detector Server Remote Power Manager Voltage Detector Alarm Rack Mount UPS & Battery Built-in Cooler
13 Distributed Process Design Benefits Standardize & Mass Production. Higher Availability & Mobility. Lower Construction & Operation Cost. Higher Agility of Plug & Play Operation. Hot Swappable & Better MTTR. Embedded CQiCenter for 24x7 Guarding. Cooling the Cabinet Not Cooling The Room. Transparent & Graphic User Interface. Built-in in Air Conditioner to Prevent Overheat. Instead of Traditional IT Equipment Room.
14 Standardize Vs. Customize Standardize Customize - Modularize - Pretest Systems In The Factory - System Hot Swappable - Scalable - Lower Cost - One Time Engineering - Onsite Assembly & Test & Maintenance - Design In First Day - Difficult to Expansion - Very Expensive Standardization Will Reducing Human Error & Increasing Availability ity
15 Distributed Rack Monitoring System Wireline & Wireless LAN CQiCenter RS816/1624 I/O WAN Wireline & Wireless Voltage & Current Detection Temp. Sensor Smoke Detector Access Control Intrusion Detector Others Sensor Local & Remote Alarm Malfunction Detection HVAC Or Fan Control Fire Suppression Door Lock Control Surveillance & Recording Power On/Off & Reboot
16 Distributed RMS Features Remote Power On / Off / Reboot Equipments Hotspot Detection Built-in in HVAC Control ( Valve or Compressor) Rack Temperature Detection Force Convection Fan Control AC/DC Voltage & Current Detection UPS & SMR Malfunction Detection Smoke Detection Access Control & Intrusion Detection Surveillance Recording Trigger Local & Remote Alarming
17 CQi RMS Solution Power Fail? Overheat? Security? Alarm? Reboot? 12 V Battery CQiCenter for System M&C Ether Switch Remote or CQiCenter Built-in Server Reboot? Auto Reboot Manual Reboot Power up Sequencing Safety Shut Down Reboot? Fail? Reboot? Alert? Log?
18 CQiCenter Benefits Improve MTBF Minor problems are identified before they are service impacting Preventative actions can be scheduled when needed, not necessary driven by a schedule Improve MTTR Better remote diagnostics facilitate accurate dispatch of personnel, test equipment, replacement parts, etc. Near real time cost control (energy, lighting, dispatch, etc.) Risk Mitigation and Management Capture and manage events before they are service impacting Corrective or proactive actions can be taken Microsoft Operation Manager Integration technology leverages existing enterprise management Microsoft system investments Integration to existing infrastructure management systems with the t SNMP leverages existing infrastructure investments and maximizes the amount of data available Allows a building to be operated with the consideration of the interrelationships and interdependencies of all installed systems
19 CQiCenter Design Philosophy Follow International Standard Sensor Network Platform Open System Architecture Programmable System Platform IT Oriented API & SDK Transparent & Browser UI
20 CQiCenter Vs. PC Sensor Network Platform Personal Computer Platform Applications & AP Tool User Applications DBMS or Office User Applications DBMS or Office Applications & AP Tool Sensor Server & Tool CQiKit OS Server Toolkit Command Shell OS System Software & Tool LAN or WAN System BUS Sensor Node Autonomous Mode CQiBIOS CQiController RAM BIOS Mother Board Hardware & BIOS Sensors & Actuators Power Climate Security Alarm Display Printer Storage HID Peripheral Device
21 CQiCenter Architecture Predefine Operating Parameter Real Time Event Trigger Program Or Manual Trigger AI DI CI DO CO Internal Or External Command Control Any Logic Associated Between I/O
22 SDK for Application Development *CQiMOM MOM Collaborative Health Mgnt CQiSNMP Monitoring & Control via SNMP CQikit CQiWeb CQiExcel Tcl / tk Serial Server CQiCommand Operating System Web Server & Browser UI MS Excel Add-in Driver Application Development Toolkit For Multi-CQiCenter Connection Marco Command & Device Driver OS Independent * Under Development
23 CQiCenter Software Power Point Excel Excel Chart MOM OpenView Programming Tool Browser User Interface
24 CQiCenter Networking Dial-up Network Dedicate Network RS485 or Ethernet 256 Sets CQi & SNMP Protocol
25
SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER
SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online
More informationEnabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific
Enabling Business Critical Continuity for Unified Communications Andy Liu Product Manager, Asia Pacific Emerson Creating Technology and Solutions for a World in Action #1 AC & DC Power System #1 OEM Embedded
More informationDelivered the Way Yo u Want
SENSAPHONE IMS-4000 Infrastructure Monitoring System Mo nito r What Yo u Want Delivered the Way Yo u Want THE SENSAPHONE IMS-4000 MONITORS AND REPORTS THE INFORMATION THAT YOU NEED TO KNOW: Get critical
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationEngineering and Manufacturing Excellence in Data Centre Infrastructure
Engineering and Manufacturing Excellence in Data Centre Infrastructure Since 1982 Australia s Largest PDU Manufacturer NetSense DCIM Software Intelligent Power PDU s SafetyNet Series 5 CREMS E-Rack 19
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationAPMTM UPS 18kW - 90kW The Flexpower Technology for mission critical applications
APM UPS 18kW - 90kW The Flexpower Technology for mission critical applications WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationLiebert. APM from 30 to 300 kw. The Compact Row Based UPS With FlexPower Technology
Liebert APM from 30 to 300 kw The Compact Row Based UPS With FlexPower Technology LIEBERT APM from 30 to 300 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationFeatures and Benefits: Power IQ DCIM Monitoring Solutions
1 : Power IQ DCIM Monitoring Solutions Vendor-agnostic Management Energy Efficiency Through one web browser, monitor any device from major manufactures such as APC, Avocent, BayTech, Chatsworth, Cyber
More informationSmartRow Solution Intelligent, Integrated Infrastructure for the Data Center
SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center Deploy a Fully Configured Data Center in Just Weeks Availability, Capacity, Efficiency. You need them and now you can have them
More informationThe Most Comprehensive DCIM Solution
The Most Comprehensive DCIM Solution NetZoomDC TM is the complete, enterprise Data Center Infrastructure Management (DCIM) software which Models, Manages, Monitors and Maximizes data center assets, space,
More informationComprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
More informationAPMTM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology
APM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology T M LIEBERT APM UPS Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More information<Insert Picture Here> Managing Oracle Exadata Database Machine with Oracle Enterprise Manager 11g
Managing Oracle Exadata Database Machine with Oracle Enterprise Manager 11g Exadata Overview Oracle Exadata Database Machine Extreme ROI Platform Fast Predictable Performance Monitor
More informationSymmetra PX. Symmetra PX 48kW Scalable from 16kW to 48kW. Modular, Scalable, High-Efficiency Power Protection for Data Centers
Modular, Scalable, High-Efficiency Power Protection for Data Centers Symmetra PX 48kW Scalable from 16kW to 48kW > High Performance, Right-Sized 3-Phase Power Protection with Industry-Leading Efficiency,
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationEaton Open Data Centre Solutions. Kari Koli
Eaton Open Data Centre Solutions Presenter: Stefan Coote Kari Koli 2008 Eaton Corporation. All rights reserved. Eaton Worldwide Founded in 1911 by J.O. Eaton World Headquarters in Cleveland, Ohio USA Customers
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationTechnical Manual Nova: Cabinet Security Management System (CSMS)
Technical Manual Nova: Cabinet Security Management System (CSMS) KP_nova_TM_160501_EN 1 Publication May, 2016, Keyprocessor BV Paasheuvelweg 20 1105BJ Amsterdam, The Netherlands www.keyprocessor.com/nova
More informationCisco MCS 7845-H1 Unified CallManager Appliance
Data Sheet Cisco MCS 7845-H1 Unified CallManager Appliance THIS PRODUCT IS NO LONGER BEING SOLD AND MIGHT NOT BE SUPPORTED. READ THE END-OF-LIFE NOTICE TO LEARN ABOUT POTENTIAL REPLACEMENT PRODUCTS AND
More informationWho Needs Remote Power Management for Power Distribution, Power Measurement and Power Control of 48 VDC Equipment?
Who Needs Remote Power Management for Power Distribution, Power Measurement and Power Control of 48 VDC Equipment? A Network Power Management White Paper Who Needs Remote Power Management for Power Distribution,
More informationSmartCabinet Intelligent, Integrated Containment for IT Infrastructure
TM SmartCabinet Intelligent, Integrated Containment for IT Infrastructure WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds,and services mission critical technologies that enable vital
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationControl systems. Efficient room control
Control systems Efficient room control AIRCONTROL Efficient room control with X-AIRCONTROL Humidity Occupancy Increasingly demanding requirements on energy efficiency as well as the latest EU regulations
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More informationTel: AC Power for Business-Critical Continuity TM
Tel: +852-2690-4118 AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across your enterprise
More information24/48V Battery Bank Ah High Cycling Long Life
Outdoor Power Cabinets, 48V DC Free Cooled with Combined Air-Con. PreFactory assembled with 19 inch Power sub rack, 2 or 4 battery Shelf s, 3U DCAC Panel combined with rectifiers 2U or 4U Power Module
More informationRiMatrix S Make easy.
RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationLiebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight
Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight LIEBERT icom THERMAL SYSTEM CONTROLS All for One, One for All Optimize a Single Cooling Unit With an Intelligent
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationT66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management
T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationRun a Smart Workplace Introducing the Digital Building. Digital Building Solutions
Digital Building Solutions Run a Smart Workplace Introducing the Digital Building Maximize efficiency and productivity Enhance infrastructure flexibility & network security Reduce installation and operating
More informationInnovative. Engineering. Power. structure source. Making the complex, simple. Structure Source PDU s
Structure Source PDU s Innovative Power Engineering High Quality Power Distribution for the Data Centre structure source Making the complex, simple structure source product range Rack and Server Power
More informationHow to Improve Energy Efficiency & Reduce Maintenance
How to Improve Energy Efficiency & Reduce Maintenance Getting the most from your energy management system John Wallace Emerson Climate Technologies Retail Solutions Discussion Topics Introduction to an
More informationDC POWER SUPPLIES DNX 110/220 V
DC POWER SUPPLIES DNX 110/220 V ISO 9001 Power supply systems DNX are dedicated to supply the equipment which needs for its operation direct voltage 110 / 220, with emphasis on maximum reliability and
More informationProduct brochure. Eaton 9PXM UPS. A scalable, modular, flexible solution for a wide range of applications. Plan > Grow > Manage
Product brochure Eaton 9PXM UPS A scalable, modular, flexible solution for a wide range of applications. Plan > Grow > Manage Highest level of reliability. Lowest cost of ownership. The Eaton 9PXM UPS
More informationWe protect IT DC-MONITORING. When more surveillance leads to added value. Member of the DATA CENTER GROUP
We protect IT DC-MONITORING When more surveillance leads to added value Member of the DATA CENTER GROUP DC-MonIToring How more surveillance leads to added value What is your data center doing right now?
More informationour experience...your solution Controlling and Monitoring Gateway
our experience......your solution Controlling and Monitoring Gateway FEATURES Clearly readable dark-blue display (4x20), 8 key keyboard and 8 signaling LEDs provides a comprehensive overview of the system
More informationRemote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products
Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements
More informationPDU Solutions. PDU Solutions
Canovate offers a full range of PDU s from basic and metered ones to IP PDU s with per socket switching capability and wireless sensor connectivity. Our PDU s can be used in the most complex ISP and Colocation
More informationproudly presents HW group Environment Monitoring Systems
Sumpftrasse 32 6300 Zug Switzerland www.temperatur-sensor.ch proudly presents HW group Environment Monitoring Systems Jens Albrecht, B.S. EE CEO About HW group s.r.o company HW group produces IP sensors
More informationenalyzer enalyzer security
enalyzer enalyzer security A documentation that provides an in depth description, that can be read as is, or forwarded to IT departments demanding more technical information. Copenhagen, May 2018 www.enalyzer.com
More informationReliable Power and Thermal Management in The Data Center
Reliable Power and Thermal Management in The Data Center Deva Bodas Corporation April 19, 2004 Deva.Bodas@.com 1 Agenda 2 Data center manageability challenges & trends Current state of power & thermal
More informationData Center Infrastructure Management (DCIM) Demystified
software is quickly becoming the core engine of data center operations. Only 5 years ago, manual spreadsheets, sometimes supplemented with Visio diagrams, were accepted as the default tools for data center
More informationATTOM. Micro Data Center. Let s Simplify IT. readily scalable solution. Design once and deploy anywhere.
ATTOM TM Micro Data Center Attom micro data center is a plug and play, fully integrated solution with built in power, cooling, rack, monitoring and security systems. Simplifying IT with this premanufactured,
More informationPower Control and Distribution
Power Control and Distribution MasterSwitch Series Remote power distribution units for network administrators, Co-Location facilities, ISPs, and applications where remote control of outlets is required
More informationData Center Infrastructure Management (D.C.I.M.)
Data Center Infrastructure Management (D.C.I.M.) Garies Chong, RCDD, DCDC. BICSI Southeast Asia District Chair Managing Director of EMS Wiring Systems Pte Ltd Data Center Infrastructure Management (D.C.I.M.)
More informationEDGE LM XLMA Series Data Module
TM TM EDGE LM XLMA Series Data Module The EDGE LM Data Modules can be deployed indoors or outdoors and have been designed to provide density and rack adaptable IT space for environments enabling low to
More informationSmartMod Intelligent, Integrated Infrastructure for the Data Center
SmartMod Intelligent, Integrated Infrastructure for the Data Center Deploy a High-Capacity, Efficient and Secure Infrastructure in Just Months Building a new data center in a short timeframe is nearly
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationModular and Scalable Power Converters in the UPS Industry
A-PDF Split DEMO : Purchase from www.a-pdf.com to remove the watermark Modular and Scalable Power Converters in the Industry Ian Wallace Eaton Corporation, Innovation Center 1 Eaton Overview Eaton Electric
More informationDude Solutions Business Continuity Overview
Dude Solutions Business Continuity Overview Table of Contents Overview.... 2 Primary and Disaster Recovery Data Centers.... 2 Network Infrastructure.... 3 Emergency Processes.... 3 Power and Cooling Systems....
More informationHIGH EFFICIENCY Central Chiller
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationChecklist for building an edge data center
Checklist for building an edge data center Building an edge data center to provide a cloud computing environment within a service provider central office can be a complex endeavor. It requires lots of
More informationPOWERING TECHNOLOGY. Reliably powering your business. Solving your power needs. DC POWER SYSTEMS
POWERING TECHNOLOGY Reliably powering your business. Solving your power needs. DC POWER SYSTEMS P O W E R I N G T E C H N O L O G Y UNIPOWER Systems today incorporates products from the former Power-One
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationModular, scalable, high-efficiency power protection for data centers
Scalable from 16 kw to 160 kw Modular, scalable, high-efficiency power protection for data centers The right-sized UPS for demanding business-critical applications The Schneider Electric Symmetra PX 96/160
More informationCisco MCS 7835-H2 Unified Communications Manager Appliance
Cisco MCS 7835-H2 Unified Communications Manager Appliance Cisco Unified Communications Solutions unify voice, video, data, and mobile applications on fixed and mobile networks enabling easy collaboration
More informationPower IQ for econnect
1 Center Energy, Power, Environmental, and Access Control Monitoring Software In today s data center, being efficient with power and cooling resources is just as important as maintaining uptime. Power
More information2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.
[Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationBuilding Management Solutions. for Data Centers and Mission Critical Facilities
Building Management Solutions for Data Centers and Mission Critical Facilities How Efficient is Your Data Center? Recent years have seen rapid growth in global demand for computing capacity, resulting
More informationKako optimizovati operativni rad data
Sanja Milovanović, ENEL PS Dani tehnološkog umeća DATUM Beograd, 2017 Kako optimizovati operativni rad data Data Center Infrastructure Management DCIM centra 1 Data Center Management: Good Questions DC
More informationPDU Inspired by Your Data Center. W IEC PDU Series
PDU Inspired by Your Data Center W IEC PDU Series Intelligent kwh PDU - W series Power Efficiency Management With today s increasing demand for high technology power management solutions, PDU kwh measurement
More information1.1 ANNUAL DATA CENTER HEALTH CHECK
Statement of Work Maintenance Service 1.0 Executive Summary - 1 - Service Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service 4.0 Assumptions 5.0 Scope of Responsibility
More informationHigh Availability & Security for Data Center
High Availability & Security for Data Center Pressures from new IT technology Keeping up with complex system changes Staying in control of capacity, energy, and availability All content in this presentation
More informationSolutions Guide for Cisco UCS B and C Series Servers
Solutions Guide for Cisco UCS B and C Series Servers The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a
More informationSolution Overview Vectored Event Grid Architecture for Real-Time Intelligent Event Management
Solution Overview Vectored Event Grid Architecture for Real-Time Intelligent Event Management Copyright Nuvon, Inc. 2007, All Rights Reserved. Introduction The need to improve the quality and accessibility
More informationData Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. TelecityGroup Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se
More information200 kw, Tier 3, Chilled Water, 5250 ft 2
[eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,
More informationData Center Optimized Controls
Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.
More informationCTC Low Temperature Process Chillers
INNOVATE DESIGN APPLY CTC Low Temperature Process Chillers 5-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough When it comes to process cooling, every application is unique in
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationFCU (FREE COOLING UNIT)
FCU (FREE COOLING UNIT) FCU reduces the AC running hours on the telecom site Controller Features: Can control upto two AC and one free cooling unit Temperature control Humidity sensor Structural Features:
More informationLoad up on the NEW SERIES EL ELECTRONIC LOADS. from Kepco
146-1968 MORE WATTS PER VERTICAL INCH Load up on the NEW SERIES EL ELECTRONIC LOADS from Kepco Model EL 2K-- Single Channel Unit Model EL 1K--100D Dual Channel Unit 1KW - 5KW Modules 4U Height Parallel
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationEnvironmental Monitor (RSMICRO)
Environmental Monitor (RSMICRO) Monitored Basic & Temperature and humidity are two of the most critical conditions to monitor in computing space. While temperature is often given moderate attention, relative
More informationAC-DC Converter REC /60-K20
Thanks to the variety of modules available, the REC3200-230-48-K20 system offers the perfect solution for all areas of applications requiring a power output of up to 3,2kW. Modular Battery Charger / Inverter
More informationLiebert PDX from 15 to 120 kw
Liebert PDX from 5 to 0 kw The Thermal Management Solution for Small and Medium Data Centers Electronic Expansion Valve Efficiency Digital Scroll Partial Load icom Control TCO Optimization Integrated Solution
More informationLiebert PDX. The Cooling Solution for Small and Medium Data Centers. Digital Scroll. Part Load. Competent Partner Efficiency
Liebert PDX The Cooling Solution for Small and Medium Data Centers Competent Partner Efficiency Digital Scroll Part Load icom Control TCO Optimization Integrated Solution Operational Cost Reduction New
More informationThe Simply Smart Way to Optimize Building Control and Performance
Connected Buildings ComfortPoint Open Building Management System The Simply Smart Way to Optimize Building Control and Performance For Consultants and Specifiers ComfortPoint Open BMS. Simply Smart. Honeywell
More informationWIRELESS ENVIRONMENTAL MONITORS
Packet Powers compact wireless Environmental Monitors makes it easy and affordable to monitor all environmental conditions in your facility. From installation to monitoring in minutes 1 Place wireless
More informationEN60849/IEC60849 compliant
EN60849/IEC60849 compliant Full compliance with EN60849/IEC60849 standards System status can be confirmed on Remote Microphones Fireman s Microphone included as standard equipment Simultaneous dual-origin
More informationSept 29, Schneider Electric s Micro Data Center Solutions
Sept 29, 2015 Schneider Electric s Micro Data Center Solutions Micro Data Center Solutions ..by 2018 Digital traffic is expanding annually by 23%+, creating the need to scale digital infrastructure Source:
More informationOptimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc.
Optimize Your Data Center Gary Hill VP, Business Development DVL Group, Inc. Data Center Age Profile Gartner Group Survey Legacy Data Centers Challenges Under Powered - Room or Racks Inadequate Air Delivery
More informationSmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity
SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationHigh Reliability & Efficiency
GE Critical Power New High Reliability & Efficiency Single phase VH & VCL Series imagination at work High Reliability & Efficiency Single phase VH & VCL Series New VH Series 700/1000/1500/2000 VA Uninterruptible
More informationLiebert. DCL up to 35 kw. Modular Rack Cooling
Liebert DCL up to 35 kw Modular Rack Cooling LIEBERT DCL up to 35 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication
More informationSelf-Contained Equipment Cabinets
Self-Contained Equipment Cabinets The water and dust proof self-contained cabinets houses all the services required to service, power backup and protect your network core or distribution equipment required
More information