1 Communication Common Work Results for Communications 1. Purpose a. Coastal Carolina University facilities requiring cabling installation. This document provides the minimum performance criteria for the components and sub-systems comprising a complete cabling system that shall accommodate Coastal Carolina University s requirements. b. Product specifications, general design considerations, and installation guidelines are provided in this written document. The contractor shall meet or exceed all requirements for the cabling system described in this document. c. Coastal Carolina University s cabling infrastructure requires an Commscope NETCONNECT Open Cabling Systems performance warranty or equivalent Single Manufacturer Solution. The Category 6 portion of the cabling system shall comply with the link and channel performance requirements of the latest revision of TIA/EIA 568-B.2-1 Performance Specifications for 4-pair 100 Ohm Category 6 Cabling. Coordinate exceptions to warranties for special circumstances with CCU. d. The contractor is required to furnish all labor, supervision, tooling, miscellaneous mounting hardware and consumables for each cabling system installed. The contractor must also be an Commscope-authorized NETCONNECT Design & Installation Contractor (ND&I) and maintain current status with the warranting manufacturer Commscope, including all training requirements or an equivalent 25 year System Warranty. The contractor shall staff each installation crew with the appropriate number of trained personnel, in accordance with their manufacturer/warranty contract agreement, to support the Commscope NETCONNECT 25-Year System Performance Warranty requirements. After installation, the Contractor shall submit all documentation to support the warranty in accordance with the manufacturer s warranty requirements, and to apply for said warranty on behalf of Coastal Carolina University. The warranty shall cover the components and labor associated with the repair/replacement of any failed link, within the warranty period, which is a valid warranty claim. A 25 year single manufacturer end to end system channel warranty shall be included. e. The contractor must have a BICSI certified RCDD review the drawings and meet with University representatives from Facilities and the Information Technology Services (ITS) group to discuss the project and to ensure that a structured cabling system is installed that provides a comprehensive telecommunications infrastructure f. ITS Room locations will be centralized in each building and stacked for multifloor buildings. Storage rooms for media equipment (A/V carts, televisions, Communications Updated April

2 recorders, etc.) will be located adjacent to ITS Rooms and will consist of one per floor on multi-floor buildings. g. In any rooms that are to be used as specialty rooms for recording video, sound or other productions, special consideration will be given to location and access within the building in regards to unwanted noise or interference from HVAC, acoustics, etc. Special power and lighting requirements will be considered also. h. Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area. Receptacles mounted on racks shall include NEMA L5-30A type receptacles as well as standard duplex receptacles. i. A/V outlet, data outlet, power outlet and TV outlet will be provided for all electronic flat screen display panels and TVs, in locations determined by CCU. All TV locations shall receive three Category 6 cables and one coaxial cable. j. A/V outlet, data outlet, power outlet and TV outlet will be provided for all LCD projectors, screens (some motorized) and other multi-media equipment in all classrooms and meeting rooms. k. At each wireless data point, a junction box with a conduit routed back to the ITS Room will be provided above the accessible ceiling. All wireless access points shall be provided with two Category 6A cables. l. TIA/EIA-568-B.1 requires that a minimum of two telecommunications outlet/connectors be installed for each work area. m. Horizontal cabling shall contain no more than one transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector. Four spare CAT5 cables shall be installed in each cable tray for new construction projects. n. Bridged taps and splices shall not be installed in the horizontal cabling. o. Splitters shall not be installed as part of the optical fiber cabling. p. The maximum allowable horizontal cable length is 295 feet. This maximum allowable length does not include an allowance for the length of 16 feet to the workstation equipment or in the horizontal cross-connect. q. Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-B.1 when tested according to test procedures of this standard. r. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. Communications Updated April

3 2. Scope. s. Flame-Spread Index: 25 or less. t. Smoke-Developed Index: 50 or less. u. Backboards: Plywood, fire-retardant treated on all six sides, ¾ by 96 by 48 installed 6 above finished floor. v. Boxes and conduits with pull strings will be provided as needed for Fire Department radio repeaters and security card access stations within all buildings. Locations will be coordinated with CCU. w. Security camera locations will require a single gang flush to exterior finish junction box (weatherproof for exterior) with a 3/4 conduit back to the ITS Room and a CAT6 cable. Locations will be coordinated with CCU. a. This document defines the cabling system and subsystem components to include cable, termination hardware, supporting hardware, and associated appurtenances required for a complete telecommunications system supporting voice and data. The intent of this document is to provide all pertinent information to allow the contractor to bid the materials, labor, supervision, tooling, and \miscellaneous mounting hardware and consumables required for a complete system. It is, however, the responsibility of the contractor to identify any and all items required for a complete system not identified in this specification. 3. Applicable Documents. a. The cabling system described in this specification is derived in part from industry standards. The documents below are incorporated by reference. i. This Technical Specification and Associated Drawings ii. ANSI/TIA/EIA-568-B, Commercial Building Telecommunications Cabling Standard iii. ANSI/TIA/EIA 568-B.2-1, Performance Specification for 4-Pair 100 Ohm Category 6 Cabling iv. TIA/TSB-140, Additional Guidelines For Field-Testing Length, Loss And Polarity Of Optical Fiber Cabling Systems v. ANSI/TIA/EIA-569-A, Commercial Building Standard for Telecommunications Pathways and Spaces vi. ANSI/TIA/EIA-606-A, Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Communications Updated April

4 vii. ANSI/J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications viii. Building Industries Consulting Services International (BICSI) Telecommunications Distribution Methods Manual (TDMM) 10th edition ix. National Fire Protection Agency (NFPA) NFPA 70, National Electrical Code (NEC) x. Commscope NETCONNECT Design and Installation Contractor Agreement (current) b. If a conflict exists between applicable documents, then the order in the list above shall dictate the order of precedence in resolving conflicts. This order of precedence shall be maintained unless a lesser order document has been adopted as code by a local, state or federal entity, and is therefore enforceable as law by a local, state or federal inspection agency. c. Specifications provided by the Information Technology Services and Facilities Management departments and other special codes may apply. d. If this document and any of the documents listed above are in conflict, the more stringent requirement shall apply. All documents listed are believed to be the most current versions; the contactor is responsible for determining and adhering to the most recent versions when developing the proposal for installation 4. Facilities Description a. Coastal Carolina University s facilities vary in function and size. Most buildings have individual offices for faculty and staff; in certain areas, personnel may be situated in modular office furniture with hard wall offices around the exterior of the floor. Classrooms may have fixed seating or be large open rooms. Generally, a ceiling distribution cabling system using cable trays and conduits is used. These specifications apply primarily to new buildings and major renovations, but should be followed as closely as possible for all telecommunications cabling installations. b. Multi-mode fiber (50/125µm) and singlemode fiber optic backbone shall be employed between the data Main Cross-Connect (MC) and each telecommunications room (TR) for data connectivity in all new buildings. When applicable, high pair-count Category 5e CMR riser cables are employed between the voice MC and each TR for voice connectivity. Within the data MC and the each TR, backbone fiber strands shall be terminated and housed in rackmount fiber optic enclosures. Within the voice MC and each TR, backbone copper pairs shall be terminated in rack-mount 48 port Cat 5e patch panels. 5. Telecommunications System Description Communications Updated April

5 a. Coastal Carolina University s data distribution network is based on a star topology. As a standard configuration each work area communications outlet contains two Category 6 jacks, all jacks are terminated using Category 6 horizontal cables pulled and terminated on Category 6 insulation displacement connector patch panels in the telecommunications room. Patch cords/equipment cords are used to connect each jack to the appropriate service connector. Generally, high pair count Category 5 CMR or CMP backbone/riser cables are employed between the Entrance facilities or Main telecommunications room and each telecommunications room for voice connectivity. Category 6 cables singlemode and 50/125 μm multi-mode fiber optic cables are used as backbone/riser cables for data. Fiber panels shall be located at the top of all data racks. 6. Special Requirements a. While standards are carefully monitored to ensure that the components and practices are technologically current, it is possible that some applications may require special consideration. Many buildings contain special purpose facilities and equipment with unique telecommunications requirements. Special telecommunications requirements may require deviation from these specifications. Information Technology Services needs to be notified of these special requirements as early in the design process as possible. b. The following list contains some of the facilities that typically require special telecommunication consideration. i. Computer labs or classrooms ii. Video conference rooms iii. Laboratories iv. Research or Science equipment v. Areas containing E-Boards (Digital Signage) vi. Information Kiosks vii. Data centers or server rooms viii. Offices requiring CCTV or video playback c. Items not specifically identified in this document as a standard should obtain approval from appropriate Information Technology Services staff prior to implementation. 7. Building Entrance Facilities Communications Updated April

6 a. The entrance facility is the location where the pathways for communications services penetrate the building to connect to the voice and data systems within the building. The entrance facilities are generally 4-inch rigid steel conduit that extends from the perimeter of the building to the telecommunications main equipment room. 8. Conduit Routing a. Coastal Carolina University representatives shall designate the shortest practical route for the communications cable to connect from the building to the point of connection with the university telephone and network cabling systems. Conduit shall be installed from the facility points of entry to the telecommunications infrastructure as determined by Information Technology Services. Each building entry should first stub out into a Quazite Heavy Duty hand hole with Heavy Duty lid. The first hand hole should be no more than 15 feet from the building unless otherwise approved by a Coastal Carolina University representative. Additional Quazite Heavy Duty hand hole and lid combinations should be placed (where necessary) along each conduit route to maximize usability. Final hand hole quantity and spacing must be approved by a Coastal Carolina University Information Technology Services representative. 9. Facilities Entrance Diversity a. Special facilities entrance requirements may be necessary for some new buildings that will house voice and data equipment when Coastal Carolina University representatives determine that the scope and importance of the facility require it. b. In the event that diverse cable facility entrances are not deemed necessary, provisions shall be made for no less than four 4-inch conduits for access from the university cable system to the telecommunications main equipment room. No less than two 4-inch conduits should exit the building from different locations for the purpose of providing redundant routes. Each of these conduits must be labeled "TELE MDF ONLY" and connect to the university telecommunications infrastructure. c. Entrance facilities must adhere to all BICSI requirements. Information Technology Services must approve any deviations from the BICSI TDMM. 10. Cabling System Testing All cables and termination hardware shall be 100% tested for defects in installation and to verify cable performance under installed conditions. All conductors and fibers of each installed cable shall be verified useable by the Contractor prior to system acceptance. Any defect in the cabling system installation including but not limited to cable, connectors, feed-through couplers, patch panels, and connector blocks shall Communications Updated April

7 be repaired or replaced in order to ensure 100% useable conductors in all installed cables. All cables shall be tested in accordance with this document, the ND&I Contract agreement, and best industry practices. If any of these are in conflict, the Contractor shall be responsible to bring any discrepancies to the attention of the project team for clarification and/or resolution. a. Performance Verification i. Copper Category 6 data cable shall be performance verified using an automated test set. Test results shall be automatically evaluated by the equipment, using the most up-to-date criteria from the TIA/EIA Standard currently ANSI/TIA/EIA-568-B.2, and the result shown as pass/fail. Test results shall be printed directly from the test unit or from a download file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved. ii. Fiber 11. Firestop Systems All 50/125 μm multi-mode optical fiber and/or Singlemode optical fiber must be manufactured by CORNING Cable Systems. After installation, it must be performance verified using an automated test set. Test results shall be automatically evaluated by the equipment, using the most up-to-date criteria from the TIA/EIA Standard currently ANSI/TIA/EIA-568-B.3, and the results shown as pass/fail. Test results shall be printed directly from the test unit or from a download file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved. a. A firestop system is comprised of the item or items penetrating the fire-rated structure, the opening in the structure and the materials and assembly used to seal the penetrated structure. Firestop systems comprise an effective block for fire, heat, vapor and a pressurized water stream. b. Firestop methods should be employed that meet the requirements of all applicable codes and/or laws. 12. Grounding And Bonding a. The facility shall be equipped with a Telecommunications Bonding Backbone (TBB). This backbone shall be used to ground all telecommunications cable shields, equipment, racks, cabinets, raceways, and other associated hard- Communications Updated April

8 ware that has the potential for acting as a current-carrying conductor. The TBB shall be installed independently of the building electrical ground and of the building ground and shall be designed in accordance with the recommendations contained in the ANSI/TIA/EIA-607-A Telecommunications Bonding and Grounding Standard. b. The main entrance facility/equipment room in each building shall be equipped with a telecommunications main grounding bus bar (TMGB). Each telecommunications closet shall be provided with a telecommunications grounding bus bar (TGB). The TMGB shall be connected to the building electrical entrance grounding facility. The intent of this system is to provide a grounding system that is equal in potential to the building electrical ground system. Therefore, ground loop current potential is minimized between telecommunications equipment and the electrical system to which it is attached. c. Product specifications i. All racks, metallic backboards, cable sheaths, metallic strength members, splice cases, cable trays, etc. entering or residing in the TC or ER shall be grounded to the respective TGB or TMGB using a minimum #6 AWG stranded copper bonding conductor and compression connectors. Where metallic panels attached to the rack to not have sufficient metal to metal contact to provide an adequate path to ground, they shall be bonded to the rack using a minimum #14 AWG copper conductor. The copper conductor size shall be upgraded based on the largest power conductor feeding any rack-mount equipment. The conductor shall be continuous; attaching all isolated components in a daisy chain fashion from top to bottom and bonded to the rack using an appropriate compression connector. ii. All wires used for telecommunications grounding purposes shall be identified with green insulation. Non-insulated wires shall be identified at each termination point with a wrap of green tape. All cables and busbars shall be identified and labeled in accordance with the System Documentation Section of this specification. 13. Ground System Installation a. The TBB shall adhere to the recommendations of the ANSI/TIA/EIA-607-A standard, and shall be installed in accordance with best industry practices. Installation and termination of the main bonding conductor to the building service entrance ground, at a minimum, shall be performed by a licensed electrical contractor. 14. Raceway/Tray Systems a. The general requirements for raceway/tray systems are as follows: Communications Updated April

9 i. Communication tray shall be installed to provide a pathway to the Telecommunications room. Pathways that include tray, home-run conduits, adequately sized hangers or some combination are required. Any break in continuous cable tray must have appropriate 4 conduit to accommodate existing and future cable runs connecting to the next tray segment. Use of appropriate 4 conduit for cable tray entry into Telecommunications room is acceptable if tray entry does not meet code. ii. Communication tray systems shall be for exclusive use by Information Technology Services and Media Services. iii. The systems shall be designed for no more than 40% fill for the expected life of the building. iv. The systems must be metallic and continuous, and all separate pieces must be bonded where they are joined. v. The systems must be grounded to the building grounding system with a minimum 6 AWG copper conductor. Refer to Section 11.0 for specific Grounding and Bonding requirements. vi. Use insulated metallic bushings for attached metallic conduits. Ground and bond the conduits to the tray (Figure A at the end of this document). vii. The tray shall be ladder or wire basket style and the model/type must be approved by Information Technology Services. viii. Ladder-style tray must not be center hung. MPHusky or an Information Technology Service approved manufacture shall be used. ix. The wire basket-style tray shall be U shaped and constructed of round wire mesh. The basket tray shall be installed trapeze-style or wallmounted. It must not be center hung. Snaketray or an Information Technology Services approved manufacturer shall be used. x. End-of-tray cable waterfalls must be used where wire drops down to prevent abrasions and cuts from metal tray edges. xi. The tray must be no closer than 6 inches from the structural ceiling, ducts, pipes, or any other possible obstructions. A minimum separation of 5 inches from lighting, especially fluorescent lighting, is required. xii. The tray must maintain 18-inch clearance from sprinkler heads. xiii. The complete cable tray system must meet Information Technology Services approval. Communications Updated April

10 15. J-Hooks xiv. Compliance to this standard requires that the end of rigid or flex conduit must: 1. Have a bushing 2. Lie within the side and end planes of the cable tray 3. Lie within the tolerated distance as illustrated (Figure B) 4. Be anchored to a rigid support 5. Be grounded and bonded to the cable tray with a minimum 14 AWG copper conductor. Refer to Section 11.0 for specific Grounding and Bonding requirements. a. The use of J-Hooks to support horizontal wiring in lieu of continuous conduit or a combination of conduit and tray must be approved by Information Technology Services in writing prior to installation. There are concerns regarding the connectivity environment when J-Hooks are used to suspend horizontal wiring systems. These concerns include loading limitations and bend radius integrity along with possible electromagnetic interference. b. When there is a request for J-Hooks to be installed as a substitution for continuous conduit or a combination of conduit and tray, it is the responsibility of the Architect, Electrical Engineer, Owners Representative, Professional Voice and Data Consultant, or other requesting party to provide documentation from both the cable manufacturer and the J-Hook manufacturer stating that their wire and J-Hooks are compatible and will address bend radius control, loading limitations, and EMI rejection. A plan showing the placement of each J- Hook including load capacity and bend radius control must also be provided to Information Technology Services. 16. Cabling System Labeling a. The contractor shall develop and submit for approval a labeling system for the cable installation. Coastal Carolina University will negotiate an appropriate labeling scheme with the successful contractor. At a minimum, the labeling system shall clearly identify all components of the system: racks, cables, panels and outlets. The labeling system shall designate the cables origin and destination and a unique identifier for the cable within the system. Racks and patch panels shall be labeled to identify the location within the cabling system infrastructure. All labeling information shall be recorded on the as-built drawings and all test documents shall reflect the appropriate labeling scheme. All label printing will be machine generated using indelible ink ribbons or cartridges. Self-laminating labels will be used on cable jackets, appropriately sized to the OD of the cable, and placed within view at the termination point Communications Updated April

11 on each end. Outlet labels will be the manufacturer s labels provided with the outlet assembly. 17. As-Built Drawings a. The installing Contractor will be provided with 2 sets of D or E-size drawings at the start of the project. One set will be designated as the central location to document all as-built information as it occurs throughout the project. The central set will be maintained by the Contractor s foreman on a daily basis, and will be available to the technical representative upon request during the course of the project. Anticipated variations from the build-to drawings may include such things as cable routing and actual outlet placement. No variations will be allowed to the planned termination positions of horizontal and backbone cables or grounding conductors unless approved in writing by the Owner. b. The Contractor shall provide the central drawing set to the Owner at the conclusion of the project. The marked up drawing set will accurately depict the as-built status of the system including termination locations, cable routing, and all administration labeling for the cabling system. In addition, a narrative will be provided that describes any areas of difficulty encountered during the installation that could potentially cause problems to the telecommunications system. 18. Test Documentation a. Test documentation shall be provided in a three-ring binder(s) within three weeks after the completion of the project. The binder(s) shall be clearly marked on the outside front cover and spine with the words Test Results, the project name, and the date of completion (month and year). The binder shall be divided by major heading tabs: Horizontal and Backbone. Each major heading shall be further sectioned by test type. Within the horizontal and backbone sections, scanner test results (Enhanced Category 5 or Category 6), fiber optic attenuation test results, OTDR traces (if any), and green light test results shall be segregated by tab. Test data within each section shall be presented in the sequence listed in the administration records. The test equipment name, manufacturer, model number and last calibration date will also be provided at the end of the document. The test document shall detail the test method used and the specific settings of the equipment during the test. b. Scanner tests shall be printed on 8-1/2 x 11 paper. Hand written test results (attenuation results and green light results) shall be documented on the attached test form (Appendix C). OTDR test results shall be printed or attached and copied on 8-1/2 x 11 paper for inclusion in the test documentation binder. Communications Updated April

12 c. When repairs and re-tests are performed, the problem and corrective action taken shall be noted, and both the failed and passed test data shall be collocated in the binder. 19. Cabling System Warranty a. The Contractor shall facilitate a 25-year system performance warranty between the Manufacturer and the Owner. An extended component warranty shall be provided which warrants functionality of all components used in the system for 25 years from the date of acceptance. The performance warranty shall warrant the installed 250 MHz horizontal copper, and both the horizontal and the backbone optical fiber portions of the cabling system. Copper links shall be warranted to the link performance minimum expected results defined in ANSI/TIA/EIA-568-B.2-1. Fiber optic links shall be warranted to the link and segment performance minimum expected results defined in ANSI/TIA/EIA-568-B Post Installation Maintenance a. The Contractor shall furnish an hourly rate with the proposal submittal which shall be valid for a period of one year from the date of acceptance. This rate will be used when cabling support is required to affect moves, additions, and changes (MACs) to the system. MACs shall not void the Contractor s nor Manufacturer s warranty. 21. Project Management / General a. The contractor shall establish a point of contact with Coastal Carolina University who will be responsible for reporting progress and updating Coastal Carolina University s Technical Representatives, (Facilities Project Manager, ITS Application Services, ITS Network Services) with issues that Coastal Carolina University must address to facilitate the cabling system installation. The contractor s POC shall provide weekly written reports to Coastal Carolina University s Technical Representatives detailing progress. Requests for access to limited access or restricted areas shall be made no later than the day prior to the required access. Information critical to the completion of the task or project shall be communicated to the University s Technical Representatives, as the requirement becomes known. Casual information shall be passed during the scheduled progress report. b. The contractor shall maintain Coastal Carolina University s facility in a neat and orderly manner during the installation of the communications cabling system. All data rooms shall be cleaned thoroughly prior to network equipment installation. All lock construction cores must be changed to CCU cores prior to network equipment installation. All contractor and subcontractor work must be completed in data rooms prior to network equipment installation. Coastal Carolina University s facilities shall be maintained in broom clean condition at the completion of work each day. At the completion of work in each area, the Communications Updated April

13 contractor will perform a final cleaning of debris prior to moving the installation crew to the next work area. c. Cbord must be scheduled at least 6 months in advance of when needed for programming of the system. 22. Cabling System Acceptance a. The Customer s technical representative will make periodic inspection of the project in progress. One inspection will be performed at the conclusion of cable pulling, prior to closing of the false ceiling, to inspect the method of cable routing and support, and the firestopping of penetrations. A second inspection will be performed at completion of cable termination to validate that cables were dressed and terminated in accordance with ANSI/TIA/EIA specifications for jacket removal and pair untwist, compliance with Manufacturer s minimum bend radius, and that cable ends are dressed neatly and orderly. 23. Final Inspection a. Upon completion of the project, the Customer s technical representative will perform a final inspection of the installed cabling system with the Contractor s project foreman. The final inspection will be performed to validate that all horizontal and backbone cables were installed as defined in the drawing package, and that the installation meets the aesthetic expectations of the Customer. 24. Test Verification a. Upon receipt of the test documentation, the Customer reserves the right to perform spot testing of a representative sample of the cabling system to validate test results provided in the test document. Customer testing will use the same method employed by the Contractor, and minor variations will be allowed to account for differences in test equipment and test variability. If significant discrepancies are found, the Contractor will be notified for resolution. 25. System Performance a. During the three week period between final inspection and delivery of the test and as-built documentation, the Customer will activate the cabling system. The Customer will validate operation of the cabling system during this period. 26. Final Acceptance a. Completion of the installation, in-progress and final inspections, receipt of the test, receipt of the as-built documentation, and successful performance of the system for a two week period will constitute acceptance of the system. Frequency (MHz) Insertion Loss (Attenuation) db/100m Cat6 CMR Cat6 CMP Standard Maximum Typical Maximum Typical Communications Updated April

14 TABLE-1-A HORIZONTAL DATA CABLING INSERTION LOSS PERFORMANCE NEXT (db) Frequency (MHz) Cat6 CMR Cat6 CMP Standard Minimum Typical Minimum Typical TABLE-1-B HORIZONTAL DATA CABLING NEXT PERFORMANCE PSNEXT (db) Frequency (MHz) Standard Cat6 CMR Cat6 CMP Minimum Typical Minimum Typical Communications Updated April

15 TABLE-1-C HORIZONTAL DATA CABLING PSNEXT PERFORMANCE ELFEXT (db) Frequency Cat6 CMR Cat6 CMP (MHz) Standard Minimum Typical Minimum Typical TABLE-1-D HORIZONTAL DATA CABLING ELFEXT PERFORMANCE PSELFEXT (db) Frequency Cat6 CMR Cat6 CMP (MHz) Standard Minimum Typical Minimum Typical Communications Updated April

16 TABLE-1-E HORIZONTAL DATA CABLING PSELFEXT PERFORMANCE RL (db) Frequency Cat6 CMR Cat6 CMP (MHz) Standard Minimum Typical Minimum Typical TABLE-1-F HORIZONTAL DATA CABLING RETURN LOSS PERFORMANCE ACR (db) Frequency Cat6 CMR Cat6 CMP (MHz) Standard Minimum Typical Minimum Typical Communications Updated April

17 Frequency MHz TABLE-1-G HORIZONTAL DATA CABLING ACR PERFORMANCE PSACR (db) Frequency Cat6 CMR Cat6 CMP (MHz) Standard Minimum Typical Minimum Typical TABLE-1-H HORIZONTAL DATA CABLING PSACR PERFORMANCE ard ard ard ard Return Loss db Stand- Min NEXT db Stand- Min FEXT db Stand- Insertion Loss db Stand- Max Min Communications Updated April

18 TABLE-2 Insertion Loss Return Loss NEXT FEXT Frequency db db db db MHz Standard Max. Standard Min. Standard Min. Standard Min TABLE-3 HORIZONTAL DATA CROSS-CONNECT PERFORMANCE CHARACTERISTICS (EXCEED TIA/EIA-568-B.2 CATEGORY 6 AND ISO/IEC CLASS E) Communications Updated April

19 Figure A: Conduit to Cable Tray Configurations Structured Cabling 1. Design Considerations. b. The interbuilding backbone shall be comprised of both copper and optical fiber. Cable sizing shall be in consultation with Information Technology Services for specific building requirements. c. Interbuilding backbone fiber and copper cables shall be sized to include no less than 50% spare for future use. Consult with Information Technology Services for cable sizing requirements on a per building basis. d. Interbuilding backbone cables comprised of steel or metallic parts must be grounded on both ends of the cable (as specified in section 11.0, Grounding and Bonding). Communications Updated April

20 e. Proper firestopping of all backbone pathways shall be maintained as specified in section 10.0, Fire Stop Systems. f. Interbuilding copper and backbone cables shall be installed without exceeding the minimum bend radius and the maximum vertical rise recommended by the cable manufacturer and must not exceed the maximum allowed pulling tension of the cable(s). 2. Interbuilding Backbone Copper (Riser) a. Cabling i. The interbuilding copper backbone cable(s) shall be a 50 pair 100 ohm unshielded, balanced, twisted-pair, Category 3 cable with round solid conductors. It shall also be armored. ii. The cable shall be UL tested and listed, and it shall meet or exceed the requirements of Category 3 cable as specified in TIA/EIA-568-B.1 and all applicable national and municipal fire codes. b. Terminations i. Interbuilding backbone copper cabling shall be terminated on 66 protected termination blocks in the telecommunications riser rooms on both ends. Protection panels should be mounted on the telephone backboard in the telecommunications room. Main Communication room terminations must be done in accordance with Information Technology Services standards. ii. The cable shall be continuous without splices, unless required by code or specified differently by Information Technology Services. iii. Interbuilding copper backbone cables must be properly secured to the walls to prevent horizontal movement as specified in BICSI TDMM Chapter 5 (11th edition or subsequent releases), the NEC, and all applicable national and municipal codes. 3. Interbuilding Backbone Fiber Optic (Riser) a. Cabling i. The interbuilding optical fiber backbone cable(s) may be a hybrid (singlemode/multi-mode) cable consisting of 8.3/125 μm singlemode and 50/125 μm multi-mode optical fiber. Typically, there shall be no fewer than 12 strands of singlemode and 12 strands of multi-mode. All backbone fiber optic cabling must use Corning glass. Actual cable sizing shall be determined after consultation with Information Technology Services. Communications Updated April

21 ii. Optical fiber cables shall meet or exceed all applicable national and local building fire codes. b. Fiber Terminations i. Specifically, there shall be no fewer than 24 stands of singlemode and 12 strands of multimode connecting this building with the Wall Building ii. The interbuilding optical fiber backbone cable(s) shall be installed with a service loop of no less than 25 feet at each end. iii. Interbuilding fiber backbone cables must be properly secured to the walls to prevent movement as specified in BICSI TDMM Chapter 5 (11th edition or subsequent releases), the NEC, and all applicable national and local building codes. iv. Velcro cable ties shall be used for securing fiber optic cable. v. All fiber optic cables are to be continuous without splicing, unless otherwise specified by Information Technology Services. vi. The singlemode strands of each interbuilding backbone fiber optic cable shall be placed first in the fiber optic cabinet, followed by the multimode strands of the corresponding cable. All terminations should be made using SC connectors unless otherwise noted in this document or in writing from a Coastal Carolina University representative. The last 2 singlemode strands on each end of the fiber run shall be fusion spliced onto SC/APC pigtails for CATV. vii. 12 gauge stranded copper wire should be installed with fiber optic cabling to act as a tracer. viii. Fiber optic cabinets shall be labeled according to Information Technology Services labeling scheme. Contact Information Technology Services for the correct designation. c. Fiber-Optic Enclosures i. Fiber-optic rack-mounted enclosures shall consist of an EIA-approved 19-inch enclosure that is four rack units tall (7 inches) with a minimum of 72 duplex port capacity and mounted in a standard relay rack. ii. Individual fiber couplers must be removable from the panel. iii. Individual couplers must be replaceable without causing interruption of service to adjacent fiber strands. Communications Updated April

22 iv. Dust covers must be provided for any unused couplers in each enclosure. v. The enclosure shall be black. vi. Enclosures shall be labeled per Information Technology Services specifications. vii. Exterior cross connect or termination points shall be provided with American Products Mini Fort Series enclosure. 4. Interbuilding Backbone Routing a. Interbuilding backbone conduit routes shall be determined by Information Technology Services as close to project completion as possible to most adequately connect to infrastructure existing at that time 5. Telecommunications Pathways and Spaces. a. Electrical contractors will generally be the installer of the telecommunications pathways, primarily cable tray, conduit and outlet boxes. The drawings must clearly define the pathways and spaces. The BICSI Telecommunications Distributions Methods Manual covers all parts of the telecommunications structured cabling system and will be used by Coastal Carolina University representatives to ensure proper installation. It should also be referenced by the designer and the contractors to determine: Telecommunications room location, dimensions, equipment layout and furnishings. Heating, cooling, lighting, fire protection, power and grounding requirements. The number and size of slots, sleeves, and conduits needed to provide pathways for backbone cabling and determine fill ratios. These pathways and spaces are designed to be used for the life of the building and should be sized accordingly. There must be at least one telecommunications room per floor in all buildings and they must be stacked vertically in multi-floor buildings. These telecommunications rooms are designed to be secure designated spaces for housing specialty equipment and devices and should not be used or combined with any other services such as plumping, electrical, HVAC, housekeeping or storage. All HVAC mini-split air distribution units installed in data rooms shall be positioned as far away from network equipment as possible. b. Any provided faceplate specifications should take precedence over general outlet descriptions. 6. Telecommunications Cabling System a. The Telecommunications Contractor will be responsible for pulling and terminating the cables following all federal, state and local codes, accepted industry standards and the manufacturer s instructions. The telecommunications contractor must work closely with the electrical contractor to ensure that the pathways are installed correctly and that they will allow for proper installation Communications Updated April

23 of the cabling system. Visual inspections and upon completion of the project test results will be used to verify proper installation practices were followed. b. Each telecommunications outlet (TO) location, unless otherwise noted, shall be provided with two Category 6 cables. Cabling shall be terminated on device faceplate, routed back to cable tray via 1 conduit (unless noted otherwise), and then routed to patch panels in the telecommunications room. The cabling system will consist of Commscope NETCONNECT Category 6 components and cable as specified in this document. Termination of telecommunication outlets must be performed using a non-impact tool. Each Category 6 cable shall be terminated on an 8-position, 8-conductor Category 6 jack to the T568B color code in the work area and in the telecommunications room. Each telecommunications outlet (TO) location, unless otherwise noted, shall be provided with two Category 6 cables. c. In building cabling between MDF and IDF rooms shall contain the following: i. 48 Cat6 Risers terminated on patch panels ii. 12 Strand OM3 SC/UPC connectors iii. 12 Strand SM with SC/UPC connectors d. Building to building cabling infrastructure: i. 46 Strand SM with SC/UPC connectors ii. 2 Strand SM with SC/APC connectors (terminated on strand 47 & 48) iii. 12 Strand OM3 SC/UPC connectors iv. 50 pair copper Cat5 7. Work Area Telecommunications Outlets: No less than one work area communications outlets should be placed per 100 square foot increment of useable floor space and sized to accommodate four Category 6 cables and connectors (e.g. A 90 square foot room should have at least one, a 101 square foot. room should have at least two). Outlets should be within 3 of an electrical outlet and installed at the same height, unless otherwise specified. Outlets should be placed so that the work area or workstation cable does not exceed 5 meters (16 ft) in length. This length is figured into the total horizontal cabling length and must not be exceeded. a. Office Outlets i. No less than two 4-port angled 110Connect faceplates. Faceplates shall be constructed of ABS molding compound and be 4.53 X 2.77 X.60 in size. Each faceplate shall contain no less than two Category 6 cables terminated on Category 6, 8-position, 8-conductor jacks Commscope NETCONNECT part number (-6=blue) following manufacturer s instructions. Fill vacant positions with blank insert Commscope part number Faceplates shall accommodate two labels and provide a clear polycarbonate cover for each. Faceplates shall be white in color unless otherwise noted. Faceplates shall Communications Updated April

24 be Commscope part number or an approved equivalent. The faceplates shall be mounted to in-wall single gang boxes. b. Academic Room Outlets i. No less than two Category 6 cables terminated on Category 6, 8- position, 8-conductor jacks Commscope NETCONNECT part number (-6=blue) following manufacturer s instructions. Use 4-port angled mount 110Connect faceplates. Fill vacant positions with blank insert Commscope part number Faceplates shall be constructed of ABS molding compound and be 4.53 X 2.77 X.60 in size. Faceplates shall accommodate two labels and provide a clear polycarbonate cover for each. Faceplates shall be white in color unless otherwise noted. Faceplates shall be Commscope part number or an approved equivalent. Faceplates may be wall mounted or may be mounted on a surface mount box as required. c. Dorm Outlets i. Two Category 6 cables terminated on two Category 6, 8-position, 8- conductor jacks Commscope NETCONNECT part number following manufacturer s instructions, one F type connector Commscope part number and one blank insert Commscope part number per student. Use 4-port angled mount 110Connect faceplates. Fill vacant positions with blank insert Commscope part number Faceplates shall be constructed of ABS molding compound and be 4.53 X 2.77 X.60 in size. Faceplates shall accommodate two labels and provide a clear polycarbonate cover for each. Faceplates shall be white in color unless otherwise noted. Faceplates shall be Commscope part number or an approved equivalent. Faceplates may be wall mounted or may be mounted on a surface mount box as required. d. Wireless Outlets i. No less than one Category 6 cable terminated on Category 6, 8- position, 8-conductor jack(s) Commscope NETCONNECT part number (-6=blue) following manufacturer s instructions. Use 4- port angled mount 110Connect faceplates. Fill vacant positions with blank insert Commscope part number Faceplates shall be constructed of ABS molding compound and be 4.53 X 2.77 X.60 in size. Faceplates shall accommodate two labels and provide a clear polycarbonate cover for each. Faceplates shall be white in color unless otherwise noted. Faceplates shall be Commscope part number or an approved equivalent. Faceplates shall be mounted on a single gang junction box easily accessible above ceiling grid in locations determined on plans. All wireless access points shall receive two Category 6A cables. Communications Updated April

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

Communications. UNM IT/Telecommunications Guide Specification Communications

Communications. UNM IT/Telecommunications Guide Specification Communications The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary

More information

f) Telecommunications Equipment Rooms

f) Telecommunications Equipment Rooms SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Los Angeles Community College District Design Standards

Los Angeles Community College District Design Standards LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure

More information

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6 Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network

More information

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled. 27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part

More information

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction

More information

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

SPECIFICATION STANDARD

SPECIFICATION STANDARD PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and

More information

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017. Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations

More information

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

TIA/EIA 568A Sub-system HORIZONTAL CABLING

TIA/EIA 568A Sub-system HORIZONTAL CABLING TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,

More information

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC.

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. 1.01 General Requirements This section details general requirements for plenum sound masking installations. 1.1 Contract

More information

SECTION COMMUNICATIONS BACKBONE CABLING

SECTION COMMUNICATIONS BACKBONE CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED

More information

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120 DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified

More information

Master Format Division 27 - Communications

Master Format Division 27 - Communications CLEMSON UNIVERSITY Master Format Division 27 - Communications Charlie Breece, RCDD CCIT Network Services and Telecommunications 2012 Master Format Division 27 Communications DIVISION 27 COMMUNICATIONS

More information

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien

More information

LACCD IT Design Standards

LACCD IT Design Standards LACCD IT Design Standards March 1 2009 This document establishes a uniform standard for the design of IT Structured Cabling for LACCD. It ensures a secure, consistent, robust system with physical and low-voltage

More information

ANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions

ANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions ANSI/BICSI-001-2009, Information Transport Systems Design Standard for K-12 Educational Institutions Terry W. Hochbein RCDD/NTS/OSP ATSR Architects/Engineers Forward PURPOSE This Standard specifies minimum

More information

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside

More information

Structured Cabling Guidelines

Structured Cabling Guidelines Informatics Planning and Services Structured Cabling Guidelines Version 1.7 August 2015 Informatics Planning and Services 1 Version 1.7 TABLE OF CONTENTS SECTION 1 STATEMENT OF PURPOSE... 1 SECTION 2 APPLICABLE

More information

Technology Standards

Technology Standards June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the

More information

ANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com

ANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com A The urpose: stablish a generic telecommunications cabling standard that will support a multivendor environment nable the planning and installation of a structured cabling system for commercial buildings

More information

Cabling a Data Center to TIA-942 Standard

Cabling a Data Center to TIA-942 Standard Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center

More information

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology

More information

Communications Infrastructure Specification

Communications Infrastructure Specification Communications Infrastructure Specification This document defines the communications installation guidelines for the University of Arkansas. Page 1 Revision Information Revision Number: Rev 2.2 Issue Date:

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC 5-, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC 5-,

More information

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS

More information

ANSI/TIA/EIA-568-B Cabling Standard NOTE

ANSI/TIA/EIA-568-B Cabling Standard NOTE 95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial

More information

FIBER OPTIC HARDWARE STEVE PAULOV

FIBER OPTIC HARDWARE STEVE PAULOV C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.

More information

Communication

Communication 27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and

More information

Information Transport Systems and Spaces

Information Transport Systems and Spaces Division 27 Master Specification for Information Transport Systems and Spaces 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor 1.3 Submittals

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

Telecommunications Structured Cabling Systems

Telecommunications Structured Cabling Systems Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

Element Z General Design Requirements Owner Standards and Other Requirements

Element Z General Design Requirements Owner Standards and Other Requirements Element Z General Design Owner and Other IS Network Services & PART 1 - General Information...2 1.01 Background...2 1.02 Scope...2 1.03 Additions, changes, testing, and acceptance...2 1.04 Special cases

More information

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents

More information

Newark, Delaware Architectural Engineering Senior Thesis Portfolio

Newark, Delaware Architectural Engineering Senior Thesis Portfolio Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE The Omega MPP enclosure is based on a 19" frame, with 4 empty module slots for MPP modules. Highly flexible : any mix between twisted pair and optical fiber modules.

More information

With the publication. Make the right connection: Bonding a shielded system. installation

With the publication. Make the right connection: Bonding a shielded system. installation Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being

More information

Bonding and grounding NETCONNECT copper cabling systems

Bonding and grounding NETCONNECT copper cabling systems White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding

More information

CERTIFICATION PLUS SM

CERTIFICATION PLUS SM CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation

More information

Structured Cabling Guidelines For The State Of Oregon

Structured Cabling Guidelines For The State Of Oregon Structured Cabling Guidelines For The State Of Oregon Compiled by; TABLE OF CONTENTS 1. INTRODUCTION 2 2. SPECIFICATIONS 4 3. SIX SUBSYSTEMS OF A STRUCTURED CABLING SYSTEM: 5 3.1. Building Entrance/Entrance

More information

ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY

ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY Introduction A classroom is measured by its effectiveness in facilitating the exchange of information. The following general guidelines have been developed

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

PANGEN SYSTEM WARRANTY. Warranty Guide

PANGEN SYSTEM WARRANTY. Warranty Guide PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &

More information

Data Cabling / Low Voltage Technology Specifications

Data Cabling / Low Voltage Technology Specifications P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall

More information

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS NOCCCD Cabling Infrastructure Standards - Page 1 2.3 SCOPE OF WORK MATRI TO BE INCLUDED IN DISTRICT PROJECTS For each project, a Scope of Work Matrix is to be created by the construction manager and updated

More information

ANSI/TIA-568-C Cat 6A Field Test Specifications

ANSI/TIA-568-C Cat 6A Field Test Specifications This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

UNIVERSITY OF CALICUT (Purchase Division)

UNIVERSITY OF CALICUT (Purchase Division) No. 12831/PURCHASE-ASST-A1/2013/CU UNIVERSITY OF CALICUT (Purchase Division) Calicut University. P.O., Dated, 07.06.2013. TENDER NOTICE Sealed and competitive tenders are invited for the installation of

More information

SECTION TELEPHONE AND COMPUTER CABLING

SECTION TELEPHONE AND COMPUTER CABLING SECTION 16700 TELEPHONE AND COMPUTER CABLING PART 1 - GENERAL Verify the computer and telephone cabling standards with MINES CCIT and Telecommunications departments. Telephone and computer lines shall

More information

The 5400 Series Raceway from The Wiremold

The 5400 Series Raceway from The Wiremold 5400 Nonmetallic Raceway Nonmetallic Raceway with Twin Snap Cover System Available Factory Prewired The 5400 Series Raceway from The Wiremold Company provides wire and cable management for data, voice,

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Date: Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of stations meets DD 9, applicable

More information

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management UMass Lowell October 1, 2011 Network and Voice Infrastructure Specifications Version 5.1 Prepared by Network Engineering and Network Project Management TABLE OF CONTENTS NETWORK AND VOICE INFRASTRUCTURE

More information

2 Telecommunications Data Center Facility Requirements

2 Telecommunications Data Center Facility Requirements Generic Requirements for Telecommunications Data Center Equipment and Spaces GR-3160-CORE Table of Contents Table of Contents Generic Requirements Notice of Disclaimer..................... iii Preface...........................................

More information

BACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.

BACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect. Structured Cabling Systems BACKBONE CABLING Bldg 3 Entrance Closet Telco Closet Bldg 2 Telco Closet Intermediate Cross Connect Main Cross Connect Backbone Cabling ER HC/FD UTP STP-A Optical Fiber HC/FD

More information

Siemon PON Fiber Cabling Solutions

Siemon PON Fiber Cabling Solutions Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility

More information

AT&T Switched Ethernet Service SM

AT&T Switched Ethernet Service SM Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks

More information

ANSI/TIA-568-C Cat 6 Field Test Specifications

ANSI/TIA-568-C Cat 6 Field Test Specifications This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6 Permanent Links. It is offered as a general guide. Suitability

More information

The 5500 Series from The Wiremold Company

The 5500 Series from The Wiremold Company 5500 Nonmetallic Raceway Multi-Channel Surface Nonmetallic Raceway Available Factory Prewired. The 5500 Series from The Wiremold Company provides wire and cable management for data, voice, video, and power

More information

Classroom WiFi Network Infrastructure Plan

Classroom WiFi Network Infrastructure Plan Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to

More information

Design Guidelines for Facilities Construction:

Design Guidelines for Facilities Construction: Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,

More information

Cabling Infrastructure

Cabling Infrastructure Presented by: Jim McGlynn PE RCDD/LAN Specialist O Neal/Gaj A telecommunications and technology consulting firm that specializes in the hospitality industry. Program Discussion: Goals Technology Definitions

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

SECURE NETWORK INFRASTRUCTURE POLICY

SECURE NETWORK INFRASTRUCTURE POLICY Responsible University Administrator: Vice Provost for Academic Affairs Responsible Officer: Chief Information Officer Origination Date: N/A Current Revision Date: 02/19/13 Next Review Date: 02/19/17 End

More information

Data Center Design and the ANSI/TIA-942 Standard

Data Center Design and the ANSI/TIA-942 Standard Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications

More information

University of Arkansas at Little Rock

University of Arkansas at Little Rock University of Arkansas at Little Rock Policy Name: Infrastructure Cabling and Wiring Standards Policy Number: 702.1 Effective Date: September 24, 2008 Policy: University of Arkansas at Little Rock (UALR)

More information

Anixter Standards Reference Guide

Anixter Standards Reference Guide Anixter: The Cabling System Experts Anixter is a leading global supplier of communications and security products, electrical and electronic wire and cable, fasteners and other small components. We help

More information

FTTE Revisited for New Technologies

FTTE Revisited for New Technologies FTTE Revisited for New Technologies A new look into FTTE design to allow great flexibility as well as compliance to the latest 40G and 100G. Gautier Humbert, RCDD, CDCDP Business Development Manager Eastern

More information

Cabling Infrastructure

Cabling Infrastructure Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements

More information

COUNTY OF SAN JOAQUIN

COUNTY OF SAN JOAQUIN COUNTY OF SAN JOAQUIN General Services Department 44 North San Joaquin Street, Suite 590 Stockton, California 95202-2778 (209) 468-3357, Fax (209) 468-2186 GABRIEL E. KARAM Director Capital Projects Facilities

More information

Interconnect Product CATALOG Q700

Interconnect Product CATALOG Q700 onents.com Interconnect Product CATALOG Q700 Quest Network Quest Network Warranty Products Warranty Que st Technology International Inc., carries a LIFETIME warranty on all Category- Rated link components

More information

SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS

SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS CONTENTS PAGE 1. GENERAL... 5-1 1.1. Introduction... 5-1 1.2. Equipment Layout Requirements... 5-1 2. EQUIPMENT FRAMES... 5-2 2.1. Introduction...

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

EXHIBIT 6. Number: A1201-S-02 Revision: 4 DRAFT Category: Information Technology Telecommunications Issued: November, 2011

EXHIBIT 6. Number: A1201-S-02 Revision: 4 DRAFT Category: Information Technology Telecommunications Issued: November, 2011 Maricopa County Standard Number: A1201-S-02 Category: Information Technology Telecommunications Issued: November, 2011 Initiated by: Office of Enterprise Technology Reviewed by: OET Revised: Al Brown,

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

The Riser as a Contract Document. Peter Sharp, RCDD

The Riser as a Contract Document. Peter Sharp, RCDD The Riser as a Contract Document Peter Sharp, RCDD IBI Group 1 1 Who am I? Presenter Credentials Electrical Engineer Specialties in communications, electronics and computer sciences, In practice for 40

More information

9/27/04 cci Cablecom Inc. 1

9/27/04 cci Cablecom Inc. 1 cci Cablecom Inc. 1 CCI Cablecom Inc. is a privately held, women owned corporation headquartered in Aurora, CO. We manufacture a variety of voice and datacom products. Cable applications Include: Local

More information

Universal connectivity grid design guide

Universal connectivity grid design guide Universal connectivity grid design guide SYSTIMAX Solutions from CommScope May 2017 Contents Introduction 3 Commercial building network overview 3 Zone cabling 4 Universal connectivity grid 4 UCG cell

More information

Fiber Backbone Cabling in Buildings

Fiber Backbone Cabling in Buildings White Paper Fiber Backbone Cabling in Buildings www.commscope.com Contents Introduction 3 Backbone Cabling Speeds 3 Optical Fiber in the Backbone 4 b/s Optical Fiber Backbone 4 Migrating to 40 Gbps and

More information

REQUEST FOR PROPOSAL:

REQUEST FOR PROPOSAL: REQUEST FOR PROPOSAL: FIBER CABLING INSTALLATION TO CONNECT SIX ADDITIONAL VIEWING STATIONS AT THE EMERGENCY OPERATION CENTER (EOC) WITH THE REGIONAL VIDEO COMMAND CENTER (RVCC) VIDEO FEED I. DESCRIPTION

More information

Wire Communications Design jfm 07. An Inside Look at Outside Plant

Wire Communications Design jfm 07. An Inside Look at Outside Plant An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure

More information

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT CAPACITY WITH OPTION TO SEGMENT CHANNELS FIBER CABLE TO UPGRADE CURRENT BUILDING NETWORK

More information

ARIADROP: Fiber to the MDU (FTTM)

ARIADROP: Fiber to the MDU (FTTM) DROP: Fiber to the MDU (FTTM) 05 Issue BECAUSE PERFORMANCE MATTERS DROP: Fiber to the MDU (FTTM) DROP DS-BS- 04/07/05 Overview Technologies DROP System is designed to provide both labor and material savings

More information