Size: px
Start display at page:

Download "Data Center Infrastructure Management ( DCiM )"

Transcription

1 Page 1

2 Data Center Infrastructure Management ( DCiM ) DCiM is defined by technology researchers and analysts as the integration of information technology (IT) and facility management disciplines to centralize monitoring, visualization, management, optimization and intelligent capacity planning of a data center s critical systems. DCiM solutions provide the decision support technology to drive greater efficiencies and ROI from the Data Center. 2

3 Features: IT and/or Facilities Monitoring Visualization Management Key Elements to DCiM Outcomes: Planning Optimization Efficiencies ROI Risk Mitigation 3

4 Other Drivers of DCiM Identify Excessive Power Consumption Electricity amounts to 40% of data centre costs Poor Data Centre Utilization Average 65% are overprovisioning just to adapt to capacity requirements Inefficient Use of Resources Greater than 50% of data centres see shortages by 2012 Expensive Business Processes Weeks to months just to get things done Over Provisioning, Under Provisioning 85% of data centres have inaccurate visibility into their real capacity Sources: McKinsey & Company, AFCOM, Uptime Institute, Forrester Research, and Gartner

5 DCIM Feature Currently Installed Real-time environmental monitoring and alarming 83% Real-time power monitoring at device or circuit level 56% Trending and analysis of historical operational data 55% Capacity planning for power, cooling, and space 53% Real-time cooling optimization 28% Tracking physical location of IT assets 59% Tracking of IT asset inventory 61% Datacenter Dynamics Focus Nov, 2012

6 DCIM Feature Currently Installed Real-time environmental monitoring and alarming 83% Geist Real-time power monitoring at device or circuit level 56% Trending and analysis of historical operational data 55% Capacity planning for power, cooling, and space 53% Real-time cooling optimization 28% Tracking physical location of IT assets 59% Tracking of IT asset inventory 61% ~ Datacenter Dynamics Focus Nov, 2012

7 9 Core Elements DCIM Capacity Planning Automation Control Modeling Colocation Management Reporting Dashboards Real-Time Monitoring Change Management Visualization Asset Management

8 Today DCIM Capacity Planning Automation Control Modeling Colocation Management Reporting Dashboards Real-Time Monitoring Change Management Visualization Asset Management

9 Environet 4.0 DCIM Capacity Planning Automation Control Modeling Colocation Management Reporting Dashboards Real-Time Monitoring Change Management Visualization Asset Management

10 Layer Key Question Example Strategic / Business Objectives Defining the I What business outcome do we want to accomplish with monitoring? Improve uptime, automate manual processes, reporting, control, reduce cost, measure ROI, verify efficiency gains, Critical Thinking Financing Monitoring System Features What information do we need in order to accomplish our goals? What high level support and budget do we have available for a monitoring system? What features do I need to accomplish my goals? rack level vs. branch level monitoring, environmentals, airflow, asset management Justification to C Suite. TCO budget (not just system cost). ROI calculations Dashboards, alarm management, capacity planning, asset management, cost analysis Monitoring System Technologies What technical details are needed? Multiple protocol support, web based, integration friendly Based on John Stanley and Jonathan Koomey The Science of Measurement: Improving Data Center Performance with Continuous Monitoring and Measurement of Site Infrastructure. Oakland, CA: Analytics Press. October 23, 2009.

11 Top 5 Monitoring Strategies AFCOM Communiqué May 2011 Be vendor neutral Choose an open solution SNMP, Modbus, BACnet, Legacy Systems Prepare for scale Flexibility to meet future demands Strive to understand relationships of information How do different areas affect other areas Choose a holistic solution How does the monitoring system interact with other systems Steve Yellen Principal, Aperture Research Institute

12 Convergence Building Management Systems (BMS) Modbus BACNet LON JBus Canbus OPC N2 Niagara Proprietary Network Management Systems (NMS) SNMP ICMP HTTP Convergence Of Monitoring Single Pane Of Glass Security Systems IP CCTV WiFi Hardwired I/O Proprietary Systems MFG Defined

13 Features of a Comprehensive Monitoring & Notification Solution Multiple protocol monitoring Hardwired I/O monitoring Multiple methods of annunciating alerts Custom graphical displays Web based 3D modeling Mobile access Multiple sites into one interface (single pane of glass) Datacenter metrics

14 Features of a Comprehensive Monitoring & Notification Solution Capacity planning One-line diagrams (power, cooling) Asset management Space management Ability to monitor ALL aspects of the datacenter In-band and out-of-band communications Comparative analysis (Thermographic, Energy Spectrum, Side-by-Side) Historical data and reports

15 Beware of Data Overload! More data isn t always better How does the system interpret that data and help you to make sense of it? What are the Key Performance Indicators? Capacities Loads Custom What are the Metrics? PUE Power Utilization Effectiveness DCiE Data Center Infrastructure Efficiency SEER Seasonal Energy Efficiency Rating

16 Life in a Data Center The DCiM / BAS Challenges Enough Humidity Yet?

17 Life is Changing The DCiM / BAS Challenges Profound on the increase in reliance on information technology (IT) systems to support business-critical applications 71% senior-level personnel believe their company s business model is dependent on its data center to generate revenue and/or conduct e- commerce. This unprecedented reliance on data center availability and total cost of ownership (TCO). Downtime the number one reason IT managers loss their jobs Recommendations for fortifying these infrastructures to minimize downtime and achieve the highest possible return on investment (ROI).

18 Ponemon Institute Unplanned Data Center Downtime The average cost of data center downtime was approximately $5,600 per minute. The average reported incident length of 90 minutes, the average cost of a single downtime event was approximately $505,500 Root Cause of Unplanned Outages 5% 10% 5% 12% 29% UPS Failure Human Error Heat or CRAC Failure Generator 15% 24% IT Eq. Failure Other

19 DCiM and Building Automation System (BAS) Real-time monitoring and management platform for all interdependent systems across IT and facility infrastructure Integrate information technology and facility management to centralize monitor and control Intelligent capacity planning of a data center critical systems Provide a comprehensive view of all resources within the data center Achieved through our implementation of specialized hardware, software and sensors

20 DCiM and Building Automation System (BAS) Real-time monitoring and management platform for all interdependent systems across IT and facility infrastructure Integrate information technology and facility management to centralize monitor and control Intelligent capacity planning of a data center critical systems Provide a comprehensive view of all resources within the data center Achieved through our implementation of specialized hardware, software and sensors

21 DCiM and Building Automation System What We Would Like it to Do Rack Info Disaster Recovery SNMP Fire Suppression Critical Alarms Fuel Oil Leak Detection Switch UPS Power Generator Meters PDU CCTV Humidity CRAC Chiller Alarming Security Card Access Temperature HVAC Under Floor Biometric VFD s

22 What is the Problem? BAS (Legacy Systems and many Current Systems) They where tasked to control the office area Most are sole-source and closed software license They cannot handle of integration challenge Does not have the tools to provide global control strategies across multiple sub-system systems Do not provide the tools to allow management on the enterprise level Data Center Sub-Systems Legacy systems do not have a communication port No strategy for global control and monitoring No understood disaster recovery plan

23 Best Practice Current DCiM / BAS should include: Upgrade legacy BAS to current platform by using legacy gateway drivers The BAS needs to be open licensed moving away from sole-source BAS needs to support all data center sub-network protocols BACnet IP and MSTP LON Modbus SNMP Wiegand BAS should be Web based and can be parsed The system should made all data flat and support global control strategies Get data to the enterprise level

24 Best Practices Data Center Sub-Systems: On any new sub-system should be spec d to have a communication port and standardize on the fewest protocols as possible On legacy sub-system without a communication port add them. worse case monitor auxiliary alarm contact Create a disaster recovery plan in strategic programming and action plan Other Practices: Use of refrigerant-based cooling instead of water-based solutions Eliminating hot spots and high heat densities by bringing precision cooling closer to the load via row-based precision cooling solutions Fortifying cooling and IT equipment investments with regular preventive maintenance and service visits.

25 Best Practices Cooling Infrastructure Optimization Computational Fluid Dynamics (CFD) services We run multiple scenarios and many, many iterations of the model to develop a complete and customized thermal solution for your data center.

26 Problem Mixing Best Practices Cooling Infrastructure Optimization Humidity Management Under Floor Plenum Venturi Effect Vortex Generation Legacy Racks Cause Recirculation Short Circuiting Leakage Poor Return Path Distribution Under Floor Obstructions Perf Tile Location Pressure Distribution Poor Rack Layout Typical Data Center is overcooled by 2.6X (Uptime Institute Study)

27 Demand Based Cooling System Increased Capacity Additional IT Load with Existing Cooling Infrastructure Energy Savings Reduces 20-30% in Cooling Costs Thermal Safety Redundancy With Existing Systems

28 Cold Aisle Containment (CAC)

29 Cold Aisle Containment (CAC) Advantages: Increased Cooling Efficiency Elimination of Mixing Reduced Cooling Costs Higher Cooling Predictability Concerns: Under-floor pressure and Distance to CRAC of Influence Limits Server Density Redundancy Increased Susceptibility to Unsafe Thermal Conditions

30 EC Motors Reducing Energy Cost and Improving Data Center Efficiency Motor and System Retrofits

31 EC Fan Technology AC Motor DC Motor Slippage (copper + iron losses) Friction losses (mechanical power) Variable speed controls require a VFD to be installed Reducing losses and increasing efficiency (no slippage) Lower rise in air temperature on air stream Built in speed control

32 EC Fan Technology Blades curve in direction of wheel rotation Air velocity > impeller tip speed Energy Transfer is result of high impeller velocities Most efficient at low speeds Blades curve against the direction of wheel rotation Air velocity < impeller tip speed More energy efficient than forward curved fan Moves air in straight line

33 Standard.90 W/cfm Exiting CRAC/CRAH Units Good.60 W/cfm Exiting CRAC/CRAH Units Better EC Fans.30 W/cfm Exiting CRAC/CRAH Units 9/13/

34 26-Ton Stulz unit (DX) Before (7.5 HP motor) CFM Amps kw W/CF M 8, % % 10, % 11, % 11, % 11, /13/

35 Dfdfh Thank You Dfgdf gdfgdfg For Your Time! Fdfhdh dzfgdfg

DCIM Data Center Infrastructure Management

DCIM Data Center Infrastructure Management DCIM Data Center Infrastructure Management Part 2 Implementation Challenges & Strategic Advantages - Predictive Analysis August 8, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Implementation

More information

DCIM Data Center Infrastructure Management Measurement is the first step

DCIM Data Center Infrastructure Management Measurement is the first step DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Data Center Infrastructure Management (D.C.I.M.)

Data Center Infrastructure Management (D.C.I.M.) Data Center Infrastructure Management (D.C.I.M.) Garies Chong, RCDD, DCDC. BICSI Southeast Asia District Chair Managing Director of EMS Wiring Systems Pte Ltd Data Center Infrastructure Management (D.C.I.M.)

More information

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight LIEBERT icom THERMAL SYSTEM CONTROLS All for One, One for All Optimize a Single Cooling Unit With an Intelligent

More information

Data Center Infrastructure Management (DCIM) Demystified

Data Center Infrastructure Management (DCIM) Demystified software is quickly becoming the core engine of data center operations. Only 5 years ago, manual spreadsheets, sometimes supplemented with Visio diagrams, were accepted as the default tools for data center

More information

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions

More information

CA ecometer. Overview. Benefits. agility made possible. Improve data center uptime and availability through better energy management

CA ecometer. Overview. Benefits. agility made possible. Improve data center uptime and availability through better energy management PRODUCT SHEET: CA ecometer CA ecometer Improve data center uptime and availability through better energy management agility made possible CA ecometer helps you to visualize, monitor, and better manage

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Comprehensive Data Center Energy Management Solutions

Comprehensive Data Center Energy Management Solutions FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime

Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime July 17, 2013 Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime siemens.com/answers Predictive Resilience Table of content What is DCIM & Its Business Value Extract Maximum

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

Data Center Optimized Controls

Data Center Optimized Controls Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.

More information

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. :: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach

More information

Data Center Infrastructure Management (DCIM) By Jesse Zhuo

Data Center Infrastructure Management (DCIM) By Jesse Zhuo Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

ABB Ability TM Data Center Automation

ABB Ability TM Data Center Automation ABB Ability TM Data Center Automation The next generation of building automation and electrical controls: industrial strength, mission critical converged solutions for data centers. Building a data center

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Optimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc.

Optimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc. Optimize Your Data Center Gary Hill VP, Business Development DVL Group, Inc. Data Center Age Profile Gartner Group Survey Legacy Data Centers Challenges Under Powered - Room or Racks Inadequate Air Delivery

More information

DCIM Data Center Infrastructure Management

DCIM Data Center Infrastructure Management DCIM Data Center Infrastructure Management Part 3 Operational Management Moves Adds and Changes & Electrical Infrastructure November 5, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Operational

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Modius OpenData v3.3. Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis

Modius OpenData v3.3. Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis Modius OpenData v3.3 Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis Modius Inc. 832 Folsom, Suite 1001 San Francisco, CA 94107 888.323.0066 info@modius.com www.modius.com

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

New Techniques for Energy-Efficient Data Center Cooling

New Techniques for Energy-Efficient Data Center Cooling New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,

More information

Kako optimizovati operativni rad data

Kako optimizovati operativni rad data Sanja Milovanović, ENEL PS Dani tehnološkog umeća DATUM Beograd, 2017 Kako optimizovati operativni rad data Data Center Infrastructure Management DCIM centra 1 Data Center Management: Good Questions DC

More information

POWER AND THERMAL MANAGEMENT SOLUTIONS

POWER AND THERMAL MANAGEMENT SOLUTIONS POWER AND THERMAL MANAGEMENT SOLUTIONS Power has long been a critical public utility we depend on in our homes and daily lives. Companies are under pressure to provide the necessary hardware and software

More information

Measurement and Management Technologies (MMT) for more energy efficient Data Center and Telecommunication Facilities

Measurement and Management Technologies (MMT) for more energy efficient Data Center and Telecommunication Facilities Information and Communication Technology Portfolio Review San Francisco, CA March 2011 Project Name: Measurement and Management Technologies (MMT) for more energy efficient Data Center and Telecommunication

More information

Geist EMEA. Geist USA. Geist APAC

Geist EMEA. Geist USA. Geist APAC Product Overview Headquartered in Lincoln, Nebraska, Geist designs and manufactures industryleading technology and software to power, cool, monitor and manage critical data center infrastructure. We produce

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products

Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable

Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable Urs Iten, Director Global Portfolio Management Data Center siemens.com/datacenters

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

DC Energy, Efficiency Challenges

DC Energy, Efficiency Challenges DC Energy, Efficiency Challenges Choosing a density strategy Implementing a high density environment Maximizing the efficiency benefit Anticipating the dynamic data center Key points on energy usage in

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

ARTO LIND ABB Ability Datacenter Automation. The way to monitor & control your DC infrastructure (DCIM) Datacenter Infrastructure Management

ARTO LIND ABB Ability Datacenter Automation. The way to monitor & control your DC infrastructure (DCIM) Datacenter Infrastructure Management ARTO LIND ABB Ability Datacenter Automation The way to monitor & control your DC infrastructure (DCIM) Datacenter Infrastructure Management Data Center common functionality DCIM needs to be open to handle

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

Building Management Solutions. for Data Centers and Mission Critical Facilities

Building Management Solutions. for Data Centers and Mission Critical Facilities Building Management Solutions for Data Centers and Mission Critical Facilities How Efficient is Your Data Center? Recent years have seen rapid growth in global demand for computing capacity, resulting

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!

More information

Leveraging DCIM to Increase Energy Efficiency and Savings

Leveraging DCIM to Increase Energy Efficiency and Savings August 6, 2013 Leveraging DCIM to Increase Energy Efficiency and Savings Siemens AG 2013 All rights reserved. usa.siemens.com/datacenters Contents Challenges of Today s Data Centers Turning Challenges

More information

siemens.com/dcim We are the trusted technology partner for energy-efficient, safe and secure buildings and infrastructure.

siemens.com/dcim We are the trusted technology partner for energy-efficient, safe and secure buildings and infrastructure. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 Tel: (847) 215-1000 Fax: (847) 215-1093 Subject to changes and errors. The information given in this

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

PLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy

PLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy PLAYBOOK F O R C H A N G E How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy The world is becoming more digital every day. The demand for feature-rich,

More information

APPLYING DATA CENTER INFRASTRUCTURE MANAGEMENT IN COLOCATION DATA CENTERS

APPLYING DATA CENTER INFRASTRUCTURE MANAGEMENT IN COLOCATION DATA CENTERS APPLYING DATA CENTER INFRASTRUCTURE MANAGEMENT IN COLOCATION DATA CENTERS Table of Contents Executive Summary 3 The Colocation Market 4 An Introduction to DCIM 5 The Value of DCIM for Colocation Providers

More information

Data Center Lifecycle and Energy Efficiency

Data Center Lifecycle and Energy Efficiency Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Tridium - Introduction

Tridium - Introduction Tridium - Introduction The Connected Data Centre Jimmy Jose Jan 2017 A Mission Critical Facility needs clear information for decision making Imagine all your building, system, repair and operational data

More information

SMART VENTILATION MANAGEMENT: CHANGING THE WAY WE THINK ABOUT VENTILATION

SMART VENTILATION MANAGEMENT: CHANGING THE WAY WE THINK ABOUT VENTILATION SMART VENTILATION MANAGEMENT: CHANGING THE WAY WE THINK ABOUT VENTILATION VENTILATION: THE KEY TO HEALTHY & EFFICIENT BUILDINGS At Ventacity Systems we believe that ventilation deserves more attention

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

ROI CASE STUDY MAY Logicalis Achieves 159% ROI* with CA DCIM Solution

ROI CASE STUDY MAY Logicalis Achieves 159% ROI* with CA DCIM Solution ROI CASE STUDY MAY 2015 Logicalis Achieves 159% ROI* with CA DCIM Solution 2 ROI CASE STUDY: LOGICALIS MAY 2015 Logicalis increases efficiency and maximizes availability with CA DCIM UK service provider

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

System architecture. Datacenter Clarity LC provides flexible client-server architectures configured to meet the needs of each organization,

System architecture. Datacenter Clarity LC provides flexible client-server architectures configured to meet the needs of each organization, Datacenter Clarity LC Tech sheet Overview Datacenter Clarity LC * is part of the Siemens BT Integrated Datacenter Management Suite (IDCMS). Clarity LC provides tools for operating and optimizing data centers,

More information

Innovative Data Center Energy Efficiency Solutions

Innovative Data Center Energy Efficiency Solutions Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal

More information

APC by Schneider Electric Elite Data Centre Partner

APC by Schneider Electric Elite Data Centre Partner Data Centre Solutions...energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration

More information

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

1.0 Executive Summary

1.0 Executive Summary Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

Total Building Solutions for Data Centers. The next generation of intelligence. usa.siemens.com/datacenters

Total Building Solutions for Data Centers. The next generation of intelligence. usa.siemens.com/datacenters Total Building Solutions for Data Centers The next generation of intelligence usa.siemens.com/datacenters Executive Summary Data center managers need to be able to leverage information to make their operations

More information

Data Center Infrastructure Management Creating The Efficient Converged Data Center

Data Center Infrastructure Management Creating The Efficient Converged Data Center Data Center Infrastructure Management Creating The Efficient Converged Data Center How to manage IT and facilities infrastructure Advantage of a holistic approach Architectural requirements Trellis a new

More information

DCIM and how it helps deliver the InteropNet. Paul Goodison CEO, Cormant Inc CORMANT

DCIM and how it helps deliver the InteropNet. Paul Goodison CEO, Cormant Inc CORMANT DCIM and how it helps deliver the InteropNet Paul Goodison CEO, Cormant Inc. 1 855 CORMANT pgoodiso@cormant.com Agenda The Current Data Center Management Paradigm What is DCIM? DCIM Adoption in an Enterprise

More information

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

System architecture. Datacenter Clarity LC provides flexible client-server architectures configured to meet the needs of each organization,

System architecture. Datacenter Clarity LC provides flexible client-server architectures configured to meet the needs of each organization, Datacenter Clarity LC Tech sheet Overview As part of the Integrated Data Center Management Suite (IDCMS), Datacenter Clarity LC * provides tools for operating and optimizing data centers. This includes:

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

DATA CENTRE & COLOCATION

DATA CENTRE & COLOCATION DATA CENTRE & COLOCATION RISING DEMAND FOR HOSTED SERVICES When it comes to hosted IT infrastructure, organisations are looking for highly resilient, highly available and highly scalable facilities at

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

The Energy. David L. Moss Dell Data Center Infrastructure

The Energy. David L. Moss Dell Data Center Infrastructure The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square

More information

Sept 29, Schneider Electric s Micro Data Center Solutions

Sept 29, Schneider Electric s Micro Data Center Solutions Sept 29, 2015 Schneider Electric s Micro Data Center Solutions Micro Data Center Solutions ..by 2018 Digital traffic is expanding annually by 23%+, creating the need to scale digital infrastructure Source:

More information

Data Center Efficiency and Retrofit Best Practices

Data Center Efficiency and Retrofit Best Practices White Paper August 2014 IT@Intel Data Center Efficiency and Retrofit Best Practices The use of best practices enables us to increase data center efficiency and capacity, optimize the return on invested

More information

Changing the way companies run their data centers

Changing the way companies run their data centers Infrastructure Management & Monitoring for Business-Critical Continuity TM Changing the way companies run their data centers The Aperture TM Suite Optimize performance of your data center without COmpromising

More information

About Geist. geistglobal.com

About Geist. geistglobal.com About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure. We produce affordable, quality products

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working

More information

Data Centre Solutions Expertly Engineered APC Management Software

Data Centre Solutions Expertly Engineered APC Management Software Data Centre Solutions Expertly Engineered APC Management Software Data Centre Solutions Expertly Engineered A vendor neutral software suite, which provides a unified view and analysis of complex IT physical

More information

Energy Efficiency Solutions for Your Data Center

Energy Efficiency Solutions for Your Data Center Energy Efficiency Solutions for Your Data Center Chapter One: Cooling Assessments Click a section below You Know You Need a Cooling Assessment When Cooling Assessments Yield Benefits Now and in the Future

More information