1 Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch

2 Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches Table of Contents Overview 1-2 Model Information 3 Cisco Specifications 4 Temperature Data 5 Baffle Temperature Views 6-7 Model with baffle, grommet and blanking removed 8 Corporate Headquarters P.O. Box 551 Edinboro, PA TRY.GLCC ( ) Phone: Fax: glcc@greatcabinets.com Great Lakes Manufacturing, Inc Enterprise Road Corry, PA Phone: Fax: werackyourworld.com glm@greatmanufacturing.net Western Distribution 4750 Joule Street Reno, NV Phone: Fax: glcc@greatcabinets.com Great Lakes International Ltd. Aerbridge House, Unit 14 Dunshaughlin Business Park Dunshaughlin Co. Meath Ireland Phone: Fax: Great Lakes Hungary KFT Zsurló utca Székesfehérvár Hungary Phone: Fax:

3 Overview Most modern data centers contain at least one large core switch to handle large bandwidth applications such as SAN storage systems or high volume data processing. These core switches are similar in design to a blade server in that they have expansion cards to accommodate various network configurations that allow the customer to deploy network infrastructure that is customized to fit their needs. This design requires cooling systems which are unique to switch hardware as air intake and exhaust can occur on the sides of the equipment. This configuration is commonly known as Side to Side Airflow (see Fig. 1). Modern servers are typically modeled in a front-to-back (see Fig. 2) airflow design and most data centers use the hot-aisle/cold-aisle layout (see Fig. 3) which was designed for equipment utilizing front to back cooling. This presents unique challenges when deploying core-switch hardware. Great Lakes has helped customers develop planning and product solutions to accommodate these switches in applications all over the world. Through the use of state of the art environmental measuring equipment, CFD Fig. 1: Side-to-side airflow (computational fluid dynamic modeling) and test facility equipment environments, Great Lakes has created a best practices document for deploying Cisco switch gear. Great Lakes has worked closely with its customers to provide product solutions and best practices to ensure their equipment is operating within the Cisco recommended specifications as found in their site preparation guidelines 1. Fig. 2: Front-to-back airflow in a 1U server Fig. 3: Hot-aisle/Cold-aisle Layout 1 Catalyst 9500 Series Switch Installation Guide. Cisco. Aug < Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 1

4 Overview By closely following the Cisco Site preparation guidelines, Great Lakes has developed several product offerings to meet the needs of the customer deploying a Cisco core switch in their data center. Great Lakes has taken a considerable amount of time engineering, testing and standardizing products to comply with Cisco core switches. Each Great Lakes enclosure is designed to be used with current hot-aisle/cold-aisle best practices. Any unused RMU is populated with filler panels as well as brush grommet installed along the sides of the enclosure to prevent recirculation inside the enclosure. The constraints of the testing performed for this document will focus on the Cisco Site Installation Guide. Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 2

5 Model Information In addition to collecting data from equipment deployed in real-world data centers, Great Lakes uses CFD (computational fluid dynamic software) to test enclosure deployments to establish best practices for IT hardware. Specifications of the room designed for the CFD analysis of the switches is detailed below: Overall room size: 1030 sq. ft. Room height: 11 ft. Raised floor: 2 ft. above base floor 2 x 40 kw CRAC unit designed to deliver air under-floor with air intake on top - Set Point: 65 o F - Airflow rate: 11,992 CFM 8 x Floor Tiles: 50% open area (no baffles) CFD room model containing each variation of Cisco Switch and Great Lakes baffle kit. Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 3

6 Cisco Catalyst 9513: Overview Intake Side Cisco 6500 switch shown; representative of 9500 switch Exhaust Side Cisco 6500 switch shown; representative of 9500 switch Specifications: Dimensions 14 RMU H x 17.37"W x 28.0"D Power 2.9 kw Operating Temp. 32 F F Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 4

7 Cisco Catalyst 9513 Great Lakes recommends the GL840ES-3042 networking enclosure with ESSAB14D baffles for this application. Operating Temperatures Ensure that the system is operating in an environment no colder than 50 F (10 C) or hotter than 95 F (35 C). Side Clearance for airflow Verify that there is a minimum of 6" (15 cm) of clearance between the sides of the rack and both the chassis air intake grill and the chassis air exhaust grill GL840ES-3042: 44 RMU, 84"H x 30"W x 42"D ESSAB14: Baffles provide 6" of clearance from the switch ESSAB14D ESSAB14D GL840ES-3042 with Cisco 6500 switch installed; representative of 9500 switch Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 5

8 Cisco Catalyst 9513 INTAKE EXHAUST Intake side views Exhaust side views INTAKE EXHAUST Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 6

9 Cisco Catalyst 9513 Thermal Plane Elevation 4 Airflow (CFM) Power Usage Front Rear 3000W Point Measured Temp in F Enclosure Intake Baffle Intake Baffle Exhaust 80.8 Enclosure Exhaust Top View Cross Section Thermal Plane Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 7

10 Model with baffle, blanking panels and grommet removed Intake side view INTAKE Exhaust side view EXHAUST Airflow (CFM) Power Usage Front Rear W Point Measured Temp in F 1 Enclosure Intake Baffle Intake Baffle Exhaust 85.8 Enclosure Exhaust Top View Cross Section Thermal Plane Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 8

11 Conclusion The use of enclosure airflow management best practices (e.g. filler panels and grommets to prevent conditioned air and hot exhaust air from mixing) in conjunction with baffle kits, ensures that side airflow equipment is able to function properly while not interfering with a traditional hot-aisle/cold-aisle layout which is designed for front to back cooling methodologies. Significant cooling gains can be seen through the use of baffles as part of hot-aisle/cold-aisle best practices in reducing by pass and recirculated airflow. By directing the side exhaust airflow toward the hot aisle, less hot air mixing occurs and the hot air is directed back to the returns, improving the cooling system efficiency by maintaining a higher delta T. The thermal planes below show a comparison of the 9513 switch running in the same enclosure, however the enclosure on the left uses a baffle kit and data center best practices while the enclosure on the right is modeled without baffles, brush grommet and filler panels. 1 The enclosure with baffles, grommet and filler panels, (left image), has very well segregated air and very consistent low intake temperatures at the switch (point 1). Higher temperatures are seen on the intake side with the baffles and best practices removed (image right). Higher temperatures at the switch intake are seen at point 2. Air is able to move freely and recirculate throughout the enclosure with out baffles, brush grommet, and filler panels with baffles and best practices 9513 without baffles and best practices Great Lakes Cisco Core Switch Product Solutions: ESSAB14D Rev. 0 Pg. 9

Data center solutions for successful companies Cooling solutions

Data center solutions for successful companies Cooling solutions Data center solutions for successful companies Cooling solutions WeRackYourWorld.com great lakes cooling solutions Power and cooling are of prime importance to anyone working in a data center. As information

More information

Data center solutions for successful companies. cable management solutions

Data center solutions for successful companies. cable management solutions Data center solutions for successful companies cable management solutions the right solutions for your cable management needs Great Lakes Cable Management Solutions provide data center managers and IT

More information

1.866.TRY.GLCC WeRackYourWorld.com

1.866.TRY.GLCC WeRackYourWorld.com cool it. 1.866.TRY.GLCC WeRackYourWorld.com In order to maximize space in the data center and accommodate for increased data, rack-mount enclosures are becoming populated with high-density servers and

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels The use of a hot aisle/cold aisle configuration in the data center has long been considered a best practice

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Cabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers

Cabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers Cabinet Level Containment IsoFlo Cabinet Isolated Airfl ow Cabinet for Raised Floor Data Centers IsoFlo Cabinet Cabinet Level Containment Tate s IsoFlo cabinet completely isolates the IT cooling from the

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies About Upsite Technologies Upsite Technologies, Inc., a pioneer, and industry thought leader specializing in data center airflow management, provides a full suite of products and services designed to enable

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

Temperature monitoring and CFD Analysis of Data Centre

Temperature monitoring and CFD Analysis of Data Centre Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Improving Rack Cooling Performance Using Blanking Panels

Improving Rack Cooling Performance Using Blanking Panels Improving Rack Cooling Performance Using Blanking By Neil Rasmussen White Paper #44 Revision 1 Executive Summary Unused vertical space in open frame racks and rack enclosures creates an unrestricted recycling

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Viable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ

Viable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Rethinking Datacenter Cooling

Rethinking Datacenter Cooling Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

New Techniques for Energy-Efficient Data Center Cooling

New Techniques for Energy-Efficient Data Center Cooling New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Data Centre Products. Airflow Management Solutions

Data Centre Products. Airflow Management Solutions Data Centre Products Airflow Management Solutions Computational Fluid Dynamics (CFD) model of an optimised data centre illustrating cold-aisle isolation and Eaton s Heat Containment System (HCS). See CFD

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

Rack Selection Guide for NetShelter SX

Rack Selection Guide for NetShelter SX Rack Selection Guide for NetShelter SX Choosing the right rack based on application and equipment type Click here to download the new White Paper #201: How to Choose an IT Rack Rack Selection Guide for

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

APC APPLICATION NOTE #146

APC APPLICATION NOTE #146 #146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

HPE Performance Optimized Datacenter (POD) Networking Guide

HPE Performance Optimized Datacenter (POD) Networking Guide HPE Performance Optimized Datacenter (POD) Networking Guide Abstract This document provides networking guidance for the various HPE PODs. Part Number: 663145-003R November 2015 Edition: 4 Copyright 2011,

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

Data Center Airflow Management Basics: Comparing Containment Systems

Data Center Airflow Management Basics: Comparing Containment Systems WHITE PAPER Data Center Airflow Management Basics: Comparing Containment Systems Edited by David Knapp Product Marketing Manager Published: February 2017 US & Canada +1-800-834-4969 Toronto, Ontario, Canada

More information

Containment Accessories Floor Mounting Template

Containment Accessories Floor Mounting Template P R O D U C T A P P L I C AT I O N Frame Supported Hot Aisle Containment (HAC) Solution The Frame Supported Hot Aisle Containment (HAC) Solution by Chatsworth Products (CPI) features a frame supported

More information

Cooling Strategies for Ultra-High Density Racks and Blade Servers

Cooling Strategies for Ultra-High Density Racks and Blade Servers Cooling Strategies for Ultra-High Density Racks and Blade Servers By Neil Rasmussen White Paper #46 Executive Summary Rack power of 10kW per rack or more can result from the deployment of high-density

More information

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,

More information

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

POWERING A CONNECTED ASIA. Pacnet Hong Kong DataSpace1 Technical Specifications. Advanced Data Center Facility for Multi-Site Enterprises

POWERING A CONNECTED ASIA. Pacnet Hong Kong DataSpace1 Technical Specifications. Advanced Data Center Facility for Multi-Site Enterprises POWERING A CONNECTED ASIA Pacnet Hong Kong DataSpace1 Technical Specifications Advanced Data Center Facility for Multi-Site Enterprises Pacnet Hong Kong DataSpce1 (HKDS1) provides an ideal environment

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

APC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications

APC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications APC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications The Cisco Unified Computing System is a next-generation data center platform that unites compute, network,

More information

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations

More information

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments COOLING SOLUTIONS SmartRack Close-Coupled Cooling for IT Environments Efficient, flexible, manageable cooling reduces costs and simplifies installation. Efficient, flexible, manageable cooling for IT environments

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Server Room & Data Centre Energy Efficiency. Technology Paper 003 Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:

More information

How to Sell APC s Cisco Approved Solution for Nexus 7018

How to Sell APC s Cisco Approved Solution for Nexus 7018 NetShelter SX Side Airflow Solution for Cisco Nexus 7018 How to Sell APC s Cisco Approved Solution for Nexus 7018 Objectives Explain Sales Strategy for the Side Airflow Solution for Nexus 7018 Explain

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

CFD Modeling of an Existing Raised-Floor Data Center

CFD Modeling of an Existing Raised-Floor Data Center CFD Modeling of an Existing Raised-Floor Data Center Amir Radmehr 1, Brendan Noll 2, John Fitzpatrick 2, Kailash Karki 1 1. Innovative Research, Inc. 3025 Harbor Lane N, Suite 300, Plymouth, MN 2. University

More information

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Effectiveness and Implementation of Modular Containment in Existing Data Centers WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation DC ASSESSMENT SERVICES AISLE CONTAINMENT AIRFLOW MANAGEMENT Achieving true 24/7/365 operation

More information

Data Center Optimization Services. Maximize Your Data Center

Data Center Optimization Services. Maximize Your Data Center Data Center Optimization Services Maximize Your Data Center Energy savings was definitely the key driver in my decision to use the SmartAire dampers and DirectAire panels. - Larry Hood Senior Construction

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

Ten Cooling Solutions to Support High- Density Server Deployment

Ten Cooling Solutions to Support High- Density Server Deployment Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,

More information

SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS

SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS CONTENTS PAGE 1. GENERAL... 5-1 1.1. Introduction... 5-1 1.2. Equipment Layout Requirements... 5-1 2. EQUIPMENT FRAMES... 5-2 2.1. Introduction...

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Reverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers

Reverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers Reverse Flow Cabinet ContraFlo Cabinet Reverse Flow Cabinet for Raised Floor Data Centers ContraFlo TM Cabinet Reverse Flow Cabinet The ContraFlo cabinet turns airflow upside down to offer an alternative

More information

Site Preparation for ClearCube Installation. Rev. F

Site Preparation for ClearCube Installation. Rev. F Site Preparation for ClearCube Installation Rev. F EXECUTIVE SUMMARY Because of the centralized nature of the ClearCube architecture, installation of the system requires a certain degree of site preparation.

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

1.0 Executive Summary

1.0 Executive Summary Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.

More information

FOM 2.4 The Performance Indicator: Assessing & Visualizing Data Center Cooling Performance

FOM 2.4 The Performance Indicator: Assessing & Visualizing Data Center Cooling Performance FOM 2.4 The Performance Indicator: Assessing & Visualizing Data Center Cooling Performance Mark Seymour AFCOM DCW 12th Sept. 2016 Future Facilities - speaking on behalf of The Green Grid 1 The Green Grid

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden)

Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden) Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden) Motivation Background Our Research Agenda Modeling Thermal Behavior Static Workload Provisioning Dynamic Workload Provisioning Improving

More information

Data Center Projects: Establishing a Floor Plan

Data Center Projects: Establishing a Floor Plan Data Center Projects: Establishing a Floor Plan White Paper 144 Revision 1 by Neil Rasmussen and Wendy Torell > Executive summary A floor plan strongly affects the power density capability and electrical

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Energy Saving Best Practices

Energy Saving Best Practices Energy Saving Best Practices BICSI Meeting West Kingston, RI 16 October 2008 Vinnie Jain, CDCP Advanced Marketing Manager Ortronics/Legrand VJ-1July08 IT Spending on the Rise 600 500 400 $B 300 200 100

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Improving Data Center Efficiency

Improving Data Center Efficiency Improving Data Center Efficiency Controlling Bypass Airflow in your Data Center Bypass airflow can have a significant impact on the cooling capacity and efficiency of any data center. One key part of

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

» BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE

» BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE » BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE CoolControl Cold Aisle Containment Blanking Panels Hot Aisle Containment Network Switch Cooling Data Centre Optimisation

More information

APC InfraStruXure Solution Overview

APC InfraStruXure Solution Overview APC InfraStruXure Solution Overview We re waiting for your call or email. 800--0 uptime@uptimeu.com Wiring Closets ( Racks) Small Server Rooms ( Racks) Small Data Centers ( 0 Racks) Medium Data Centers

More information

Data Center Lifecycle and Energy Efficiency

Data Center Lifecycle and Energy Efficiency Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014

More information

Critical Facilities Round Table SUN Microsystems Friday, March 25, Thursday, March 24, 2005 Wright Line LLC,

Critical Facilities Round Table SUN Microsystems Friday, March 25, Thursday, March 24, 2005 Wright Line LLC, Critical Facilities Round Table SUN Microsystems Friday, March 25, 2005 Thursday, March 24, 2005 Wright Line LLC, 2003 1 Topic of Discussion Can standardization, non-uniform and high heat densities co-exist

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information