ATCO Electric Ltd. Dawes Substation and Telecommunications Tower Project Facility Application

Size: px
Start display at page:

Download "ATCO Electric Ltd. Dawes Substation and Telecommunications Tower Project Facility Application"

Transcription

1 Decision Dawes Substation and Telecommunications Tower Project Facility Application February 19, 2014

2 The Alberta Utilities Commission Decision : Dawes Substation and Telecommunications Tower Project Facility Application Application No Proceeding ID No February 19, 2014 Published by The Alberta Utilities Commission Fifth Avenue Place, Fourth Floor, 425 First Street S.W. Calgary, Alberta T2P 3L8 Telephone: Fax: Website:

3 The Alberta Utilities Commission Calgary, Alberta Decision Dawes Substation and Telecommunications Tower Project Application No Facility Application Proceeding ID No Introduction and background 1. (ATCO) filed a facility application with the Alberta Utilities Commission (AUC or the Commission) on November 27, 2013, registered as Application No (the application), pursuant to sections 14, 15, 18 and 21 of the Hydro and Electric Energy Act. ATCO requested a new 240/144-kilovolt (kv) substation, two single circuit 240-kV transmission lines and one double circuit 144-kV transmission line. The application was assigned as Proceeding ID No On December 17, 2013, the Commission issued information requests to ATCO to clarify details of the application with respect to the environmental evaluation and the project need. ATCO responded to the information requests on January 6, On January 13, 2014, the Commission issued a notice of application with a deadline of February 5, 2014, for submissions to express objections, concerns or support for the application. The notice of application was sent directly to all occupants, residents and landowners as well as other stakeholders that were contacted as part of the participant involvement program. 4. On January 22, 2014, Alberta Parks submitted correspondence to the Commission indicating that it had received the notice of application and did not have any concerns with the project as proposed by ATCO. 5. No objections or concerns were received by the February 5, 2014 submission deadline. 2 Discussion 6. In accordance with Section 35 of the Electric Utilities Act, the Alberta Electric System Operator (AESO) directed ATCO to submit the application. 7. In its information response to the Commission, ATCO confirmed that the need for the project was approved by the Commission in Decision ATCO further confirmed that the application meets the need as approved in Decision ATCO stated that the development of the proposed transmission facilities are required to support current and future industrial development in the area. The proposed project would consist of the following activities: 1 Decision : Alberta Electric System Operator - Algar Area 144-kV Transmission Reinforcement Needs Identification Document, Application No , Proceeding ID No. 2293, April 18, AUC Decision (February 19, 2014) 1

4 construct a new 240/144-kV substation to be designated as Dawes 2011S substation construct two new approximately one kilometre single circuit 240-kV transmission lines, designated as 9L07 and 9L89, to connect the proposed Dawes 2011S substation to the existing 240-kV transmission line 9L07 with an in-out configuration at the proposed Dawes 2011S substation construct one new approximately 1.3 kilometres double circuit 144-kV transmission line, designated as 7L170/7L194, to connect the proposed Dawes 2011S substation to the existing 144-kV transmission line 7L36 alter the existing 240-kV transmission line 9L07 by: operating the portion of existing line from McMillan 885S substation to the proposed Dawes 2011S substation 2011S as 240-kV transmission line 9L89 operating the portion of existing line from Dawes 2011S substation to the existing Dover 888S substation as 240-kV transmission line 9L07 decommission and salvage a portion of existing transmission line 9L07 between the connection points, approximately 42 metres in length alter the existing 144-kV transmission line 7L36, previously approved to be renumbered as 7L194, by: operating the portion of existing line from Algar 875S substation to the proposed Dawes 2011S substation as 144-kV transmission line 7L170 operating the portion of existing line from the approved Willow Lake 2009S substation to the proposed Dawes 2011S substation as 144-kV transmission line 7L194 decommission and salvage approximately 50 metres of existing transmission line 7L36 between the proposed connection points for the proposed double circuit 144-kV transmission line 7L170/7L194 with an in-out connection alter the existing Algar 875S substation to add one 144-kV circuit breaker connect these facilities to the Alberta Interconnected Electric System 9. Upon completion of the proposed development, ATCO submitted that the proposed Dawes 2011S substation would include the following major equipment: one 240/144-kV, 180/240/300-megavolt-ampere transformer three 240-kV circuit breakers three 144-kV circuit breakers one 125-kilowatt backup generator one self-supporting steel lattice telecommunications tower one control building 2 AUC Decision (February 19, 2014)

5 an enclosure surrounded by a chain-link fence and other substation equipment as described in the application 10. The proposed Dawes 2011S substation would be situated in the Regional Municipality of Wood Buffalo, approximately 50 kilometres southwest of the Urban Services Area of Fort McMurray. The substation would be located in the southeast quarter of Section 19 and southwest quarter of Section 20, Township 84, Range 11, west of the Fourth Meridian on Crown Land. The proposed substation would require a site approximately 286-metres by 365-metres with a fenced area of approximately 163-metres by 193-metres. The AESO directed ATCO to allow for sufficient land for the ultimate substation configuration. 11. ATCO submitted that the proposed alterations to the existing Algar 875S substation would include the addition of one 144-kV circuit breaker and associated protection and control facilities. The substation is located in the northwest quarter of Section 19, Township 84, Range 11, west of the Fourth Meridian. 12. Upon completion of the proposed development, ATCO submitted that the Algar 875S substation would include the following major equipment: one 144/4.16/25-kV transformer two 144-kV circuit breakers one 144-kV circuit switcher an enclosure surrounded by a chain-link fence and other substation equipment as described in the application 13. To accommodate the proposed substation development, two single circuit 240-kV transmission lines, approximately one kilometre in length and designated as 9L07 and 9L89, are proposed to connect the proposed Dawes 2011S substation to the existing 240-kV transmission line 9L07 with an in-and-out configuration at the proposed Dawes 2011 substation. 14. Further, ATCO submitted that a double circuit 144-kV transmission line, designated as 7L170/7L194, is proposed to connect the proposed Dawes 2011S substation to the existing 144-kV transmission line 7L ATCO stated that it worked closely with Alberta Environment and Sustainable Resource Development (AESRD) on the routing and siting of the project. ATCO stated that AESRD is in support of the routing and siting of the proposed transmission lines and substation. 16. ATCO submitted that the proposed Dawes 2011S substation site was chosen as it would be compatible with the surrounding land uses and it would reduce the overall impact of the proposed substation on stakeholders and the surrounding environment. 17. ATCO submitted that the proposed route for transmission lines 9L07 and 9L89 was selected as it would be adjacent to existing industrial disturbances and would minimize disturbances to the natural systems in the area. AUC Decision (February 19, 2014) 3

6 18. ATCO submitted that the proposed route for the double circuit transmission line 7L170/7L104 would be adjacent to existing disturbances to the extent possible which would minimize disturbances to the natural systems in the area. 19. ATCO conducted a participant involvement program prior to filing the application. The program was comprised of notification and consultation with all landowners, occupants, agencies and other interested parties within 800-metres of the rights-of-way for the proposed transmission lines and the existing Algar 875S substation and within 2000 metres of the proposed Dawes 2011S substation. ATCO confirmed there are no objections to the project. Further, ATCO stated that it is in on-going communications with stakeholders and would continue to work with them to address concerns. 20. ATCO submitted an environmental evaluation and an environment protection plan as part of the application. The environmental evaluation and environment protection plan addressed measures that ATCO would implement to reduce the environmental impacts. 21. ATCO committed to complete a pre-construction rare plant survey by June 2014 and continue to consult with the AESRD Fish and Wildlife Division to determine the required preconstruction wildlife surveys to be undertaken in the project area. 22. ATCO stated that the project would comply with the Environmental Protection Guidelines for Transmission Lines and other relevant regulations and guidelines. 23. ATCO stated that a noise impact assessment was conducted for the project and submitted a noise impact assessment summary form as part of the application. The noise impact assessment predicted the project would not exceed permissible sound levels and would be in compliance with AUC Rule 012: Noise Control (AUC Rule 012). 24. ATCO stated that the project falls within the area of the Lower Athabasca Regional Plan (LARP) and that the project is consistent with the LARP. 25. ATCO s estimated project cost (within +20%/-10% accuracy) for the project development is $48,623, Findings 26. The Commission finds that the application, as proposed by ATCO, satisfies the need as directed by the AESO. 27. With respect to ATCO s application, the Commission finds that it complies with the requirements prescribed in sections 14, 15, 18 and 21 of the Hydro and Electric Energy Act and AUC Rule The Commission finds that the participant involvement program, as described above, meets the requirements of AUC Rule 007: Applications for Power Plants, Substations, Transmission Lines, and Industrial System Designations (AUC Rule 007). No objections were received in response to the notice of application. 4 AUC Decision (February 19, 2014)

7 29. The Commission acknowledges that ATCO will comply with the relevant sections of the Environmental Protection Guidelines for Transmission Lines and other relevant regulations and guidelines. 30. The Commission acknowledges that the project falls within the area of the LARP and accepts that the project is consistent with the LARP. 31. The Commission is satisfied that the technical and environmental aspects of the project, as submitted by ATCO, fulfil the requirements of AUC Rule 007. The Commission accepts that the proposed development would not result in any adverse impacts to the environment. 32. The Commission further finds that the noise impact assessment submitted by ATCO fulfils the requirements of AUC Rule Having considered the social, economic, and environmental impacts of the proposed project, the Commission finds that the application is in the public interest pursuant to Section 17 of the Alberta Utilities Commission Act. Therefore, the Commission approves the project as proposed by ATCO. 4 Decision 34. Pursuant to Sections 14, 15, 19 and 21 of the Hydro and Electric Energy Act, the Commission approves Application No and grants ATCO the following approvals: Substation Permit and Licence No. U February 19, 2014, to construct and operate the Dawes 2011S substation as set out in Appendix 1. Substation Permit and Licence No. U February 19, 2014, to alter and operate the Algar 875S substation as set out in Appendix 2. Transmission Line Permit and Licence No. U February 19, 2014, to alter and operate transmission line 9L07 as set out in Appendix 3. Transmission Line Permit and Licence No. U February 19, 2014, to alter and operate transmission line 9L89 as set out in Appendix 4. Transmission Line Permit and Licence No. U February 19, 2014, to alter and operate transmission line 7L194 as set out in Appendix 5. Transmission Line Permit and Licence No. U February 19, 2014, to alter and operate transmission line 7L170 as set out in Appendix The appendices will be distributed separately. Dated on February 19, AUC Decision (February 19, 2014) 5

8 The Alberta Utilities Commission (original signed by) Tudor Beattie, QC Commission Member 6 AUC Decision (February 19, 2014)

Alberta Electric System Operator Secord 2005S Substation Needs Identification Document

Alberta Electric System Operator Secord 2005S Substation Needs Identification Document Decision 2014-271 Alberta Electric System Operator Needs Identification Document Facility Application September 24, 2014 The Alberta Utilities Commission Decision 2014-271: Alberta Electric System Operator

More information

Decision D ATCO Electric Ltd. Crystal Lake 722S Substation Telecommunications Tower Replacement

Decision D ATCO Electric Ltd. Crystal Lake 722S Substation Telecommunications Tower Replacement Decision 21617-D01-2016 Crystal Lake 722S Substation October 5, 2016 Alberta Utilities Commission Decision 21617-D01-2016 Crystal Lake 722S Substation Proceeding 21617 Application 21617-A001 October 5,

More information

ENMAX Power Corporation

ENMAX Power Corporation Decision 22769-D01-2017 Transmission Lines 138-1.80L and 138-1.81L September 15, 2017 Alberta Utilities Commission Decision 22769-D01-2017 Transmission Lines 138-1.80L and 138-1.81L Proceeding 22769 Application

More information

ENMAX Generation Portfolio Inc.

ENMAX Generation Portfolio Inc. Decision 22192-D01-2017 ENMAX Generation Portfolio Inc. September 5, 2017 Alberta Utilities Commission Decision 22192-D01-2017 ENMAX Generation Portfolio Inc. Proceeding 22192 Application 22192-A002 September

More information

Ells River Substation Telecommunication Tower

Ells River Substation Telecommunication Tower January 2013 Why are you receiving this project information package? We are advising neighbouring landholders, agencies and other interested parties about plans to construct the Ells River substation telecommunication

More information

Vegreville Office Telecommunication Tower Replacement

Vegreville Office Telecommunication Tower Replacement Project Need and Details March 2012 If approved, the proposed Vegreville Office Telecommunication Tower Replacement will be located on the current tower site at 6502-55 Avenue in the Town of Vegreville.

More information

Benbow 397S Substation Upgrade Needs Identification Document

Benbow 397S Substation Upgrade Needs Identification Document APPENDIX C AESO PIP Benbow 397S Substation Upgrade Needs Identification Document 1.0 Participant Involvement Program (PIP) From June to December 2015, the AESO conducted a Participant Involvement Program

More information

AESO PARTICIPANT INVOLVEMENT PROGRAM (PIP)

AESO PARTICIPANT INVOLVEMENT PROGRAM (PIP) APPENDIX B AESO PARTICIPANT INVOLVEMENT PROGRAM (PIP) Sunnybrook and Livock Substation Modifications Needs Identification Document 1.0 Participant Involvement Program From May 2015 to August 2015, the

More information

STRATHCONA AREA TRANSMISSION UPGRADE PROJECT

STRATHCONA AREA TRANSMISSION UPGRADE PROJECT STRATHCONA AREA TRANSMISSION UPGRADE PROJECT September 2017 ProjeCt InFormation You are receiving this information because you are a landowner, resident, business owner, or occupant of property near a

More information

APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE:

APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE: APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE: New 240 kv Montana Alberta Tie Ltd. (MATL) Substation 120S and Reconfigure 240kV Transmission Line 923L AltaLink Management Ltd. 2611 3 rd

More information

PARTICIPANT INVOLVEMENT PROGRAM

PARTICIPANT INVOLVEMENT PROGRAM ATTACHMENT 3 PARTICIPANT INVOLVEMENT PROGRAM Southern Alberta Transmission Reinforcement Amendment Needs Identification Document Approval Amendment 1.0 Participant Involvement Program From July to December

More information

Jenner Wind Energy Connection Needs Identification Document

Jenner Wind Energy Connection Needs Identification Document APPENDIX C AESO PIP Jenner Wind Energy Connection Needs Identification Document 1.0 Participant Involvement Program (PIP) From November 2015 to May 2016, the AESO conducted a participant involvement program

More information

MFC Power General Partner Ltd.,

MFC Power General Partner Ltd., Decision 21950-D01-2016 Preferential Sharing of Records Between, MFC Power Limited Partnership, URICA Energy Real Time Ltd., and URICA Asset Optimization Ltd. October 12, 2016 Alberta Utilities Commission

More information

User Guide. March 2017

User Guide. March 2017 User Guide March 2017 Alberta Utilities Commission efiling System User Guide Fifth Avenue Place Fourth Floor, 425 First Street S.W. Calgary, Alberta T2P 3L8 Phone: 403-592-4500 Email: info@auc.ab.ca www.auc.ab.ca

More information

CITY OF VAUGHAN EXTRACT FROM COUNCIL MEETING MINUTES OF SEPTEMBER 25, 2012

CITY OF VAUGHAN EXTRACT FROM COUNCIL MEETING MINUTES OF SEPTEMBER 25, 2012 CITY OF VAUGHAN EXTRACT FROM COUNCIL MEETING MINUTES OF SEPTEMBER 25, 2012 Item 23, Report No. 33, of the Committee of the Whole, which was adopted without amendment by the Council of the City of Vaughan

More information

Alberta Reliability Standards Compliance Monitoring Program. Version 1.1

Alberta Reliability Standards Compliance Monitoring Program. Version 1.1 Version 1.1 Effective: January 14, 2011 Table of Contents 1. Introduction... 1 2. Purpose... 1 3. Applicability... 1 4. Definitions... 1 5. Compliance Monitoring Overview... 2 6. Monitoring Tools... 1

More information

CITY OF GRA DE PRAIRIE SUBDIVISIO A D DEVELOPME T APPEAL BOARD AGE DA

CITY OF GRA DE PRAIRIE SUBDIVISIO A D DEVELOPME T APPEAL BOARD AGE DA CITY OF GRA DE PRAIRIE SUBDIVISIO A D DEVELOPME T APPEAL BOARD AGE DA SEPTEMBER 19, 2012 AT 9:00 AM FIRST FLOOR, ORTH CO FERE CE ROOM CITY HALL 10205 98 STREET ATTE DEES Councillor J. Croken L. Coulter

More information

July 1, 1999 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION

July 1, 1999 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION Donald A. Fellows, Jr. Manager of Revenue and Tariffs July 1, 1999 (U 338-E) PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION SUBJECT: Notice of Proposed Construction of Facilities

More information

Standard CIP Cyber Security Critical Cyber Asset Identification

Standard CIP Cyber Security Critical Cyber Asset Identification Standard CIP 002 1 Cyber Security Critical Cyber Asset Identification Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed

More information

Standard CIP Cyber Security Critical Cyber Asset Identification

Standard CIP Cyber Security Critical Cyber Asset Identification Standard CIP 002 1 Cyber Security Critical Cyber Asset Identification Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed

More information

CAW Clean Wind Energy Project

CAW Clean Wind Energy Project Prepared by: M.K. Ince and Associates Ltd. September 19, 2012 Amended March 11, 2013 Table of Contents 1 INTRODUCTION... 1 2 PURPOSE... 1 3 COMPLAINT RESPONSE PROTOCOL... 1 3.1 COMPLAINT INITIATION...

More information

Protocol and Guideline for Establishing Wireless Telecommunication Facilities Within City of Brampton

Protocol and Guideline for Establishing Wireless Telecommunication Facilities Within City of Brampton Protocol and Guideline for Establishing Wireless Telecommunication Facilities Within City of Brampton (February 2002) (Revised, January 2011) Council approval CW062-2011 (Revised, February 2011) revisions

More information

CITY OF TORONTO TELECOMMUNICATION TOWER AND ANTENNA PROTOCOL (Industry Canada Local Land-use Authority Consultation)

CITY OF TORONTO TELECOMMUNICATION TOWER AND ANTENNA PROTOCOL (Industry Canada Local Land-use Authority Consultation) Attachment 1: Approved Telecommunications Protocol (Adopted by City Council - March 3, 4 and 5, 2008) CITY OF TORONTO TELECOMMUNICATION TOWER AND ANTENNA PROTOCOL (Industry Canada Local Land-use Authority

More information

Project Data Update Package Instruction Manual (PDUP-IM)

Project Data Update Package Instruction Manual (PDUP-IM) Project Data Update Package Instruction Manual (PDUP-IM) Date: April 11, 2018 Prepared by: Reviewed by: Approved by: Khalid Rafiq, P. Eng. Modelling Engineer, Transmission Project Delivery Christopher

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ) ) ) ) ) ) )

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ) ) ) ) ) ) ) BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA In the Matter of the Application of SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E For a Permit to Construct Electrical Facilities With Voltages

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA In the Matter of the Application of SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) for a Permit to Construct Electrical Facilities: Cerritos

More information

Downtown Boise Multimodal Center

Downtown Boise Multimodal Center Treasure Valley High Capacity Transit Study Downtown Boise Multimodal Center Environmental Assessment June 2009 Prepared by the Federal Transit Administration and Valley Regional Transit. U.S. Department

More information

Stem Beach Solar 1041 Application

Stem Beach Solar 1041 Application Stem Beach Solar 1041 Application September 18 th, 2018 By: Stem Beach Solar LLC, Invenergy LLC 1401 17 th Street, Ste 1100 Denver, Colorado 80202 For: Pueblo County Agenda 1. About Invenergy 2. Project

More information

SECTIONS II - VIII QUANTITY, FORM, AND FILING REQUIREMENTS APPLICATION FILING FEES NOTICE TO COMMUNITY ORGANIZATIONS NOTICE IN UTILITY BILLS

SECTIONS II - VIII QUANTITY, FORM, AND FILING REQUIREMENTS APPLICATION FILING FEES NOTICE TO COMMUNITY ORGANIZATIONS NOTICE IN UTILITY BILLS SECTIONS II - VIII QUANTITY, FORM, AND FILING REQUIREMENTS APPLICATION FILING FEES PROOF OF SERVICE NOTICE TO COMMUNITY ORGANIZATIONS PUBLIC NOTICE NOTICE IN UTILITY BILLS NOTICE OF OWNERS OF PROPERTY

More information

Content Copy Of Original

Content Copy Of Original Content Copy Of Original Ministry of the Environment and Climate Change Ministère de l Environnement et de l Action en matière de changement climatique Hydro One Networks Inc. 483 Bay St 14th Floor, South

More information

REAL-TIME MONITORING DATA SPECIFICATION

REAL-TIME MONITORING DATA SPECIFICATION REAL-TIME MONITORING DATA SPECIFICATION Version 1 December 9, 2016 Revision History Version Date Reviewer Revisions 1 11/1/16 Mansion Hudson Initial document 1 Contents 1. DOCUMENT REVIEW... 3 2. DEFINITIONS...

More information

Budget Review Process (BRP) Preliminary List of Business Initiatives. Stakeholder Meeting April 10, 2017

Budget Review Process (BRP) Preliminary List of Business Initiatives. Stakeholder Meeting April 10, 2017 2017-18 Budget Review Process (BRP) Preliminary List of Business Initiatives Stakeholder Meeting April 10, 2017 Purpose / Agenda The purpose of this presentation is to: Provide stakeholders with a BRP

More information

System Impact Study for Power Supply 400 MW Import on the EAL BCHA Path

System Impact Study for Power Supply 400 MW Import on the EAL BCHA Path System Impact Study for Power Supply 400 MW Import on the EAL BCHA Path Report No: NPP2000-21 September 13, 2001 Network Performance Planning Department T&D Engineering Executive Summary BC Hydro Power

More information

Standard CIP Cyber Security Critical Cyber As s et Identification

Standard CIP Cyber Security Critical Cyber As s et Identification A. Introduction 1. Title: Cyber Security Critical Cyber Asset Identification 2. Number: CIP-002-4 3. Purpose: NERC Standards CIP-002-4 through CIP-009-4 provide a cyber security framework for the identification

More information

ARLINGTON COUNTY, VIRGINIA

ARLINGTON COUNTY, VIRGINIA ARLINGTON COUNTY, VIRGINIA County Board Agenda Item Meeting of December 12, 2015 DATE: December 1, 2015 SUBJECT: SP-84-U-15-1 USE PERMIT ASSOCIATED WITH A SITE PLAN for a telecommunications facility; located

More information

Self-Certification Tutorial. Version 1.0 April 2013

Self-Certification Tutorial. Version 1.0 April 2013 Version 1.0 April 2013 The PLAN At the end of this tutorial, you will be able to: 1. Describe the purposes of Self-Certification 2. Identify deadlines 3. Describe the use of the Self-Certification template

More information

From: Laura Manz, Vice President of Market & Infrastructure Development

From: Laura Manz, Vice President of Market & Infrastructure Development California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Laura Manz, Vice President of Market & Infrastructure Development Date: May 8, 2009 Re: Decision for Conditional

More information

REGULATORY FRAMEWORK FOR THE ACTIVITY OF MOBILE VIRTUAL NETWORK OPERATORS (MVNO)

REGULATORY FRAMEWORK FOR THE ACTIVITY OF MOBILE VIRTUAL NETWORK OPERATORS (MVNO) http://www.anacom.pt/template31.jsp?categoryid=235163 Determination of 9.2.2007 REGULATORY FRAMEWORK FOR THE ACTIVITY OF MOBILE VIRTUAL NETWORK OPERATORS (MVNO) A. Framework 1. Within the scope of relevant

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

Standard CIP Cyber Security Critical Cyber As s et Identification

Standard CIP Cyber Security Critical Cyber As s et Identification A. Introduction 1. Title: Cyber Security Critical Cyber Asset Identification 2. Number: CIP-002-4 3. Purpose: NERC Standards CIP-002-4 through CIP-009-4 provide a cyber security framework for the identification

More information

Discussion Guide. Benvoulin Substation Project.

Discussion Guide. Benvoulin Substation Project. Discussion Guide Benvoulin Substation Project A Growing Region South Central Kelowna has experienced substantial growth over the last ten years. FortisBC is enhancing the electrical power supply system

More information

CIP Standards Development Overview

CIP Standards Development Overview CIP Standards Development Overview CSSDTO706 Meeting with FERC Technical Staff July 28, 2011 Objectives Historical Timeline CIP-002-4 CIP-005-4 CIP Version 5 2 Project 2008-06 Overview FERC Order 706 SDT

More information

Standards Authorization Request Form

Standards Authorization Request Form Standards Authorization Request Form When completed, email this form to: sarcomm@nerc.com NERC welcomes suggestions to improve the reliability of the bulk power system through improved reliability standards.

More information

Part F. Stakeholder Consultation

Part F. Stakeholder Consultation Part F Stakeholder Consultation TABLE OF CONTENTS Page F. STAKEHOLDER CONSULTATION... 1 F.1 INTRODUCTION... 1 F.2 PROGRAM HISTORY... 1 F.3 OBJECTIVES... 1 F.4 APPROACH... 2 F.5 IDENTIFICATION OF COMMUNITIES

More information

EBR Application for Review Request to Review Environmental Compliance Approval Cruickshank Construction Limited Elginburg Quarry, Kingston

EBR Application for Review Request to Review Environmental Compliance Approval Cruickshank Construction Limited Elginburg Quarry, Kingston EBR Application for Review Request to Review Environmental Compliance Approval Cruickshank Construction Limited Elginburg Quarry, Kingston Decision Summary EBRO File No.: 16EBR001.R Issue: The Ministry

More information

City of Winter Garden REQUEST FOR PROPOSAL RFP CR Mail and Fulfillment Services LEGAL ADVERTISEMENT CITY OF WINTER GARDEN

City of Winter Garden REQUEST FOR PROPOSAL RFP CR Mail and Fulfillment Services LEGAL ADVERTISEMENT CITY OF WINTER GARDEN City of Winter Garden REQUEST FOR PROPOSAL Mail and Fulfillment Services LEGAL ADVERTISEMENT CITY OF WINTER GARDEN REQUEST FOR PROPOSAL (RFP) NO. CR18-001 FOR A VENDOR TO PROVIDE DOMESTIC AND INTERNATIONAL

More information

DATE: April 8, 2013 REPORT NO. CD TYPE OF REPORT CONSENT ITEM [ ] ITEM FOR CONSIDERATION [ X ]

DATE: April 8, 2013 REPORT NO. CD TYPE OF REPORT CONSENT ITEM [ ] ITEM FOR CONSIDERATION [ X ] DATE: April 8, 2013 REPORT NO. CD2013-040 TO: FROM: Chair and Members Committee of the Whole Community Services Gregory Dworak, General Manager Community Services 1.0 TYPE OF REPORT CONSENT ITEM [ ] ITEM

More information

Standard CIP 005 4a Cyber Security Electronic Security Perimeter(s)

Standard CIP 005 4a Cyber Security Electronic Security Perimeter(s) A. Introduction 1. Title: Cyber Security Electronic Security Perimeter(s) 2. Number: CIP-005-4a 3. Purpose: Standard CIP-005-4a requires the identification and protection of the Electronic Security Perimeter(s)

More information

Written Testimony of Rick Gonzales Senior Vice President and Chief Operating Officer New York Independent System Operator

Written Testimony of Rick Gonzales Senior Vice President and Chief Operating Officer New York Independent System Operator Assembly Standing Committee on Energy Kevin A. Cahill, Chairman Assembly Standing Committee on Corporations, Authorities and Commissions James F. Brennan, Chairman Assembly Standing Committee on Cities

More information

ARLINGTON COUNTY, VIRGINIA

ARLINGTON COUNTY, VIRGINIA ARLINGTON COUNTY, VIRGINIA County Board Agenda Item Meeting of June 18, 2016 DATE: June 7, 2016 SUBJECT: U-3279-11-1 USE PERMIT AMENDMENT to add an antenna and equipment to an existing telecommunications

More information

Information Document PRC-001-AB3-1.1(ii) Protection System Coordination ID # RS

Information Document PRC-001-AB3-1.1(ii) Protection System Coordination ID # RS Information Documents are not authoritative. Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between an Information Document

More information

REVISION HISTORY DATE AMENDMENT DESCRIPTION OF AMENDMENT

REVISION HISTORY DATE AMENDMENT DESCRIPTION OF AMENDMENT REVISION HISTORY DATE AMENDMENT DESCRIPTION OF AMENDMENT IFC SERVICE DESCRIPTION 17 OCTOBER 2016 Page 1 of 9 SERVICE DESCRIPTION 2-14: INTERNATIONAL FALCON CONNECTION SERVICE (IFC Service) 1. THE SERVICE

More information

RECORD OF PRE-APPLICATION MEETING FOR THE PROPOSED SANRAL PROJECT TO WIDEN THE N3 (AND PORTION OF N2) BETWEEN DURBAN AND PIETERMARITZBURG

RECORD OF PRE-APPLICATION MEETING FOR THE PROPOSED SANRAL PROJECT TO WIDEN THE N3 (AND PORTION OF N2) BETWEEN DURBAN AND PIETERMARITZBURG RECORD OF PRE-APPLICATION MEETING FOR THE PROPOSED SANRAL PROJECT TO WIDEN THE N3 (AND PORTION OF N2) BETWEEN DURBAN AND PIETERMARITZBURG Date: 25 th July 2016 Location: Department of Environmental Affairs,Environmental

More information

Physical Security Reliability Standard Implementation

Physical Security Reliability Standard Implementation Physical Security Reliability Standard Implementation Attachment 4b Action Information Background On March 7, 2014, the Commission issued an order directing NERC to submit for approval, within 90 days,

More information

Provision of Network Information to System Management (RC_2014_10)

Provision of Network Information to System Management (RC_2014_10) Rule Change Notice Provision of Network Information to System Management (RC_2014_10) This notice is given under clause 2.5.7 of the Wholesale Electricity Market Rules (Market Rules). Submitter: Kate Ryan,

More information

Guidance of NOP Certification system Page 1/8

Guidance of NOP Certification system Page 1/8 Page 1/8 I. Introduction A. Regulation Since October 21, 2002, The USDA implemented its organic regulations for the production, labeling, and inspection of organic products: the National Organic Program

More information

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO PREPARED BY: System Management (WA) DOCUMENT REF: SO_OP_WA_3805 VERSION: 1.0 EFFECTIVE DATE: 13/10/2017 STATUS: FINAL Approved for distribution

More information

Generation, Transmission, and End User Facilities

Generation, Transmission, and End User Facilities Procedures for Interconnection of Generation, Transmission, and End User To the Grand River Dam Authority Transmission System Table of Contents GRDA/SPP Interaction... 3 Standards... 3 Generation... 3

More information

Gatekeeper and Notice Requirements For Direct Electronic Access and Routing Arrangements

Gatekeeper and Notice Requirements For Direct Electronic Access and Routing Arrangements Rules Notice Technical UMIR Please distribute internally to: Institutional Legal and Compliance Senior Management Trading Desk Contact: Naomi Solomon Senior Policy Counsel, Market Regulation Policy Telephone:

More information

NERC Relay Loadability Standard Reliability Standards Webinar November 23, 2010

NERC Relay Loadability Standard Reliability Standards Webinar November 23, 2010 Transmission Relay Loadability FERC Order 733 Project 2010-1313 NERC Relay Loadability Standard Reliability Standards Webinar November 23, 2010 Project Overview 2 Standards Involved PRC-023-2 Transmission

More information

APPENDIX E: DRAFT INITIAL STUDY/MITIGATED NEGATIVE DECLARATION COMMENT LETTERS AND RESPONSES

APPENDIX E: DRAFT INITIAL STUDY/MITIGATED NEGATIVE DECLARATION COMMENT LETTERS AND RESPONSES APPENDIX E: DRAFT INITIAL STUDY/MITIGATED NEGATIVE DECLARATION COMMENT LETTERS AND RESPONSES P AGE 129 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-8 A-9 B-1 B-2 B-3 B-4 B-6 B-5 March 24, 2015 Scott Johnson Community

More information

CHARTER TOWNSHIP OF ALLENDALE, OTTAWA COUNTY, MICHIGAN WIRELESS COMMUNICATION FACILITIES APPLICATION

CHARTER TOWNSHIP OF ALLENDALE, OTTAWA COUNTY, MICHIGAN WIRELESS COMMUNICATION FACILITIES APPLICATION CHARTER TOWNSHIP OF ALLENDALE, OTTAWA COUNTY, MICHIGAN WIRELESS COMMUNICATION FACILITIES APPLICATION This application is to be completed in compliance with Article 25 of the Charter Township of Allendale

More information

North Gila-Imperial Valley #2 Transmission Project

North Gila-Imperial Valley #2 Transmission Project North Gila-Imperial Valley #2 Transmission Project WECC 2015 Annual Progress Report Submitted by: Southwest Transmission Partners, LLC. ISSUED: March 4, 2015 Table of Contents I. Introduction---------------------------------------------------------------

More information

South West Scotland Renewables Connection Project Environmental Statement Scoping Report Executive Summary

South West Scotland Renewables Connection Project Environmental Statement Scoping Report Executive Summary South West Scotland Renewables Connection Project Environmental Statement Scoping Report Executive Summary September 2007 EXECUTIVE SUMMARY Background This Environmental Impact Assessment (EIA) Scoping

More information

Introduction to Generation Availability Data System (GADS) Wind Reporting

Introduction to Generation Availability Data System (GADS) Wind Reporting Introduction to Generation Availability Data System (GADS) Wind Reporting Registration and Reporting Fundamentals Donna Pratt, Performance Analysis Manager-Data Analytics NERC Webinar April 26, 2017 Topics

More information

Consideration of Issues and Directives Project Modeling Data (MOD B) October 7, 2013

Consideration of Issues and Directives Project Modeling Data (MOD B) October 7, 2013 Project 2010-03 Modeling Data (MOD B) October 7, 2013 Para 290. Project 2010-03 - Modeling Data The Commission directs public utilities, working through NERC, to modify the reliability standards MOD- 010

More information

ADDENDUM # 3. To prospective Proposers on RFI # 55144: Solar Energy Development and Community Solar at JFK Long-Term Parking Lot:

ADDENDUM # 3. To prospective Proposers on RFI # 55144: Solar Energy Development and Community Solar at JFK Long-Term Parking Lot: PROCUREMENT DEPARTMENT 4 WORLD TRADE CENTER 150 GREENWICH STREET, 21ST FL. NEW YORK, NY 10007 12/7/2018 ADDENDUM # 3 To prospective Proposers on RFI # 55144: Solar Energy Development and Community Solar

More information

Critical Cyber Asset Identification Security Management Controls

Critical Cyber Asset Identification Security Management Controls Implementation Plan Purpose On January 18, 2008, FERC (or Commission ) issued Order. 706 that approved Version 1 of the Critical Infrastructure Protection Reliability Standards, CIP-002-1 through CIP-009-1.

More information

Re: Filing of Windstream's Comments to Notice of Proposed Rulemaking; Case No. NNTRC

Re: Filing of Windstream's Comments to Notice of Proposed Rulemaking; Case No. NNTRC New Mexico Office of External Affairs 1660 Old Pecos Trail- Suite D Santa Fe; NM 87505 1:505.9559700 f:505.955.9699 windstream September 19, 2011 Executive Director Navajo Nation Telecommunications Regulatory

More information

IMPLEMENTATION OF THE FULL LIBERALIZATION OF THE LOCAL FIXED TELECOMMUNICATIONS NETWORK SERVICES MARKET FROM 1 JANUARY Consultation Paper

IMPLEMENTATION OF THE FULL LIBERALIZATION OF THE LOCAL FIXED TELECOMMUNICATIONS NETWORK SERVICES MARKET FROM 1 JANUARY Consultation Paper IMPLEMENTATION OF THE FULL LIBERALIZATION OF THE LOCAL FIXED TELECOMMUNICATIONS NETWORK SERVICES MARKET FROM 1 JANUARY 2003 Consultation Paper A. Introduction Following the "1998 Review of Fixed Telecommunications"

More information

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO PREPARED BY: System Management (WA) DOCUMENT REF: SO_OP_WA_3805 VERSION: 1.0 EFFECTIVE DATE: 13/10/2017 STATUS: DRAFT FOR CONSULTATION Approved

More information

NOTICE OF APPLICATION AND WRITTEN HEARING

NOTICE OF APPLICATION AND WRITTEN HEARING Ontario Energy Board Commission de l énergie de l Ontario EB-2012-0305 NOTICE OF APPLICATION AND WRITTEN HEARING Application by Hydro One Networks Inc. and Kitchener-Wilmot Hydro Inc. for Licence Amendments

More information

Cyber Security Reliability Standards CIP V5 Transition Guidance:

Cyber Security Reliability Standards CIP V5 Transition Guidance: Cyber Security Reliability Standards CIP V5 Transition Guidance: ERO Compliance and Enforcement Activities during the Transition to the CIP Version 5 Reliability Standards To: Regional Entities and Responsible

More information

NERC Transmission Availability Data System (TADS): Element Identifier Data Submission Addendum

NERC Transmission Availability Data System (TADS): Element Identifier Data Submission Addendum Transmission Availability Data System (TADS) Element Identifier Data Submission Addendum May 28, 2013 3353 Peachtree Road NE NERC Transmission Availability Data System (TADS): Element Identifier Data Submission

More information

Network Configuration Document Selection for New Substations Framework

Network Configuration Document Selection for New Substations Framework Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA In the Matter of the Application of SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) for a Permit to Construct Electrical Facilities: Eldorado-Lugo-Mohave

More information

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation Small Generator Interconnection Facilities Study Report Completed for ( Interconnection Customer ) Proposed Interconnection Pavant substation Original report dated February 17, 2016 Revised March 11, 2016

More information

B-1-1. Janet L. Fraser Director, Regulatory Affairs Phone: Fax:

B-1-1. Janet L. Fraser Director, Regulatory Affairs Phone: Fax: B-- Janet L. Fraser Director, Regulatory Affairs Phone: 0-- Fax: 0-- E-mail: janet.fraser@bctc.com October 00 Ms. Erica Hamilton Commission Secretary British Columbia Utilities Commission 00 Howe Street,

More information

Standard COM-002-2a Communications and Coordination

Standard COM-002-2a Communications and Coordination A. Introduction 1. Title: Communication and Coordination 2. Number: COM-002-2a 3. Purpose: To ensure Balancing Authorities, Transmission Operators, and Generator Operators have adequate communications

More information

(a) Discourages obtrusive Telecommunication Facilities within or adjacent to Residential Areas, Heritage Areas and Environmentally Sensitive Areas;

(a) Discourages obtrusive Telecommunication Facilities within or adjacent to Residential Areas, Heritage Areas and Environmentally Sensitive Areas; POLICY NUMBER: C471C REFERENCE: ADOPTED BY: City Council City Council 1997 07 15 C471A January 23, 2013 City Council 1998 07 07 C471A SUPERSEDES: City Council 2006 05 09 C471B C471B PREPARED BY: Sustainable

More information

Cooperation with other Certification Systems

Cooperation with other Certification Systems ISCC 254 Cooperation with other Certification Systems Cooperation with other Certification Systems ISCC 11-01-14 V 1.16 11-01-14 Copyright notice ISCC 2010 This ISCC document is protected by copyright.

More information

Standards Authorization Request Form

Standards Authorization Request Form Standards Authorization Request Form When completed, email this form to: sarcomm@nerc.com NERC welcomes suggestions to improve the reliability of the bulk power system through improved reliability standards.

More information

DARRYL CARTER &COMPANY Barristers & Solicitors

DARRYL CARTER &COMPANY Barristers & Solicitors Darryl Carter, a.c. (also of the California Bar) Mikle L. Carter Jennifer Wilkie DARRYL CARTER &COMPANY Barristers & Solicitors C11-1 103,10134-97 Avenue Grande Prairie, Alberta T8V7X6 Phone (780) 882-7296

More information

Environmental Impact Questionnaire

Environmental Impact Questionnaire Community Development Department 11 English Street Petaluma, CA 94952 Phone: 707-778-4301 Email: cdd@ci.petaluma.ca.us Web: www.cityofpetaluma.net/cdd Building Geographic Information Systems Housing Neighborhood

More information

/Internet Random Moment Sampling. STATE OF ALASKA Department of Health and Social Services Division of Public Assistance

/Internet Random Moment Sampling. STATE OF ALASKA Department of Health and Social Services Division of Public Assistance E-mail/Internet Random Moment Sampling STATE OF ALASKA Department of Health and Social Services Division of Public Assistance RMS Training Objectives Goal: Upon completion of this training session, participants

More information

European Code of Conduct on Data Centre Energy Efficiency

European Code of Conduct on Data Centre Energy Efficiency EUROPEAN COMMISSION DIRECTORATE-GENERAL JOINT RESEARCH CENTRE Institute for Energy and Transport Renewable Energy Unit European Code of Conduct on Data Centre Energy Efficiency Introductory guide for applicants

More information

Response to Wood Buffalo Wildfire KPMG Report. Alberta Municipal Affairs

Response to Wood Buffalo Wildfire KPMG Report. Alberta Municipal Affairs Response to Wood Buffalo Wildfire KPMG Report Alberta Municipal Affairs Background To ensure continuous enhancement and improvement of Alberta s public safety system, the Alberta Emergency Management Agency

More information

GC0102 Mod Title: EU Connection Codes GB Implementation Mod 3

GC0102 Mod Title: EU Connection Codes GB Implementation Mod 3 Stage 01: Modification Proposal Grid Code GC0102 Mod Title: EU Connection Codes GB Implementation Mod 3 Purpose of Modification: This modification (3/4) will set out within the Grid Code the following

More information

DESCRIPTION OF COST ALLOCATION METHODOLOGY

DESCRIPTION OF COST ALLOCATION METHODOLOGY Filed: September, 00 EB-00-00 Exhibit G Schedule Page of 0 DESCRIPTION OF COST ALLOCATION METHODOLOGY.0 INTRODUCTION This schedule provides an overview of the cost allocation methodology used to allocate

More information

Ministry of Energy, Mines and Petroleum Resources. Guide to Acquiring Crown Petroleum and Natural Gas Tenures

Ministry of Energy, Mines and Petroleum Resources. Guide to Acquiring Crown Petroleum and Natural Gas Tenures Ministry of Energy, Mines and Petroleum Resources Guide to Acquiring Crown Petroleum and Natural Gas Tenures March 2018 1 Summary of Revisions Effective date Section Description March 2018 Reconfigured

More information

Supplemental Information

Supplemental Information Retirement of NPCC Directory# 3 Supplemental Information On April 1, 2015, NPCC Directory# 3 was retired upon the effective date of PRC-005-2 Protection System Maintenance which is subject to a 12 year

More information

DR and EE Standards for SCE Buildings

DR and EE Standards for SCE Buildings Design & Engineering Services DR and EE Standards for SCE Buildings Prepared by: Design & Engineering Services Customer Service Business Unit Southern California Edison December 2011 Acknowledgements Southern

More information

Standard CIP Cyber Security Security Management Controls

Standard CIP Cyber Security Security Management Controls A. Introduction 1. Title: Cyber Security Security Management Controls 2. Number: CIP-003-4 3. Purpose: Standard CIP-003-4 requires that Responsible Entities have minimum security management controls in

More information

Malibu Civic Center Stakeholders Meeting. October 25, 2012

Malibu Civic Center Stakeholders Meeting. October 25, 2012 Malibu Civic Center Stakeholders Meeting October 25, 2012 Malibu Civic Center Stakeholders Meeting 1. RWQCB Agenda 2. Wastewater Facility Design 3. Formation of the Community Facilities District (CFD)

More information

TELECOMMUNICATIONS ACCESS POLICY 2011

TELECOMMUNICATIONS ACCESS POLICY 2011 TELECOMMUNICATIONS ACCESS POLICY 2011 The Vice Chancellor and Principal, as delegate of the Senate of the University of Sydney, adopts the following policy. Dated: 31 January 2011 Signature: Name: Michael

More information

Scottish and Southern Electricity Networks

Scottish and Southern Electricity Networks Scottish and Southern Electricity Net Who we are Our licence stipulates that we must develop and maintain an efficient, co-ordinated and economical system of electricity transmission. What is the difference

More information

Screening Procedures for Access to ISO Register of Transmission Facilities and Entitlements

Screening Procedures for Access to ISO Register of Transmission Facilities and Entitlements Screening Procedures for Access to ISO Register of Transmission Facilities and Entitlements In accordance with the Federal Energy Regulatory Commission (FERC) order issued on January 24, 2003 (as modified

More information

Purpose. ERO Enterprise-Endorsed Implementation Guidance

Purpose. ERO Enterprise-Endorsed Implementation Guidance Lesson Learned CIP Version 5 Transition Program CIP-002-5.1 Requirement R1: Impact Rating of Generation Resource Shared BES Cyber Systems Version: January 29, 2015 Authorized by the Standards Committee

More information

Guideline 8: Submitting Electronic Funds Transfer Reports to FINTRAC

Guideline 8: Submitting Electronic Funds Transfer Reports to FINTRAC Guideline 8: Submitting Electronic Funds Transfer Reports to FINTRAC Guideline 8: Submitting Electronic Funds Transfer Reports to FINTRAC November 2004 This replaces the previous version of Guideline 8:

More information

ANNUAL ACCESSIBILITY STATUS REPORT

ANNUAL ACCESSIBILITY STATUS REPORT The Ontarians with Disabilities Act, 2001 The Accessibility for Ontarians with Disabilities Act, 2005 ANNUAL ACCESSIBILITY STATUS REPORT 2017 Township Council Accessibility Policy C-PD-03 Administrative

More information