14:00-15:00 THE AIR OF A DATA CENTER

Size: px
Start display at page:

Download "14:00-15:00 THE AIR OF A DATA CENTER"

Transcription

1 14:00-15:00 THE AIR OF A DATA CENTER Morgan Ledner, Global Data Center Manager, Volvo IT, Sweden

2 Morgan Ledner

3 Cooling and environment From the perspective of a data center provider Environmental issues / energy consumption in data centers Practical issues as a part of the reality in data centers

4 3 data centers in Gothenburg 7000m 2 Bild: Goteborgsfotografen.se

5 Our customers = High demand Automotive Industry/ Manufacturing Retail, wholesale Service sector Banking, Financial Services & Insurance Government, Education, Non-Profit Audi BMW Ford GKN Rolls Royce Saab Parts Volvo Cars Volvo Group Arkema Assa Abloy Eiffage Finnveden Bulten Gambro Picanol Sandvik SCA SKF Toyota Material Handling Auchan Elektroskandia ICA Canal+ DinEl Fraikin GE Healthcare Securitas YIT Allianz Banque Accord If Old Mutual Skandia Storebrand Volvofinans Volvo Financial Services City of Gothenburg City of Stockholm SPV Kem One 5

6 Data Center business Availability High investmet cost High runtime cost High maintenance cost

7 Availability & Tier Cost Uptime architecture for % = $ kw Uptime architecture for 99.98% = 5000 $ kw Uptime architecture for 99.7% Uptime architecture for 99.6% = $ kw = $ kw +/- 30%

8 Tripple Condenser banks N+1 Quintet of compressors N+2 Compressor 450kVA Compressor 450kVA Compressor 450kVA Compressor 450kVA Compressor 450kVA TANK TANK Sea cooling N+1 8 MW DATA CENTER Heat exhanger Double piping CRACK CRACK CRACK N+2 crack in each DC Room

9 Overall Redundancy strategy Data building 3 Diesel Power External Power CPU POWER CPU Data builiding 1 Data building 2 Volvo IT Innovation Centre, 2008 Magnus.Holmqvist@volvo.com WLAN Customer 9

10 Environmental issues Energy consumption in data centers

11 You are what you are

12 Volvo Group core value since 1972: Care for the Environment Volvo now believes it is responsible not only for ensuring that its products are a functional means of transport, but also for ensuring that they function in a wider context in our environment. Among the actions: 1976 Volvo unveils first 3-way catalytic converter, Lambda Sond, eliminates 95% of harmful emissions 1983 Volvo decision on an Environmental policy 1988 Volvo Environment Prize founded 1989 Volvo appointed an internal environmental auditor. The company aims to meet and preferably surpass all eco-legislation around the world Volvo presented a unique database for chemical use known as MOTIV, introducing blacklistning Volvo revealed its environmentally optimised ECT (Environmental Concept Truck), 2000 Volvo launch Euro 3 incentive engines 2002 Volvo signs UN Global Compact 2005 Volvo takes the lead to create the first CO2-neutral vehicle plant in the world - achieved Volvo creates the fist momentanious ce

13 Always moving forwards to sustainable solutions powered by VOLVO We can be the GREEN choise Author name, department name, date #

14 Green IT - How to define? Creating computers? - Raw materials, production process.. Running data - Power to run it, Power for Cooling Scrapping computers? - Dumping electronics.. Green IT = SAVING COST!

15 Benefits of Green IT Financial Operational Social Cost savings from more efficient energy use Operational savings More computing performance per kilowatt Flexible infrastructure Verifiable energy conservation Improves image of your company

16 Datacenter & energy Total use of electricity per year: 17 MWh Datacenter 1 Air cooling: 8.1 MWh Datacenter 2 water cooling: 8.9 MWh

17 Runtime (US$10K) $1100 Average Data center cost $1000 Investmens Runtime cost, (electric and support cost) $800 $600 $400 $200 $0

18 No. of server Result of changes 21 o Servers +40% 29 o Temp. +39% Energy +6%

19 Where the energy is consumed IT equipment 40-50% Lighting 1-2% Cooling 40-55% UPS 5-9%

20 Warning! PUE Most energy efficient Objective Average Least energy efficient

21 Practical issues of the reality in data centers

22 Volvo IT

23 Cold row compartment Volvo IT Morgan Ledner, DC management-2

24 Blind plates Blind panels Popular version: Easy to mount Easy to adjust size Light weight Sheep Volvo IT Morgan Ledner, DC management-2

25 Average room Air temp 28 C Volvo IT

26 Air flow management Doubble area tail Full perforated tail Volvo IT Morgan Ledner, DC management-2

27 Row capping Close aisle Volvo IT Morgan Ledner, DC management-2

28 Floor sponge /grommets & The hunt for bypass air Volvo IT Morgan Ledner, DC management-2

29 Testing & results Low Floor totop difference High return temperature Good airflow... Low CRAC speed High cooling media temperature More free cooling...11month/year Volvo IT Morgan Ledner, DC management-2

30 Challanges New server technology = higher Delta C High density equippment, hot spots Outsourcing & Cloud services Volvo IT Morgan Ledner, DC management-2

31 Author name, department name, date #

32 VOLVO INFORMATION TECHNOLOGY Author name, department name, date #

33 NATURA 2000 Author name, department name, date #

34 Marinebiologist investigation 2004 & 2006 Citation: - The conclution from the marinbiology investigation is that no negative concequences have been found. - The investigations most interessting observation is that the totala regroth of the valuable Nating-vegetation in Arendals lagoon. - The re-stablishing of Nating within the south lagoon is an occurrence that is considered to have a great value for the marine wildlife in the area. HydroGIS AB Lars-Harry Jenneborg Marinbiologist Author name, department name, date #

35 May you all live well and prosper Author name, department name, date #

HCL. Morgan Ledner Global Data Center Manager HCL / Volvo IT. Volvo Information Technology

HCL. Morgan Ledner Global Data Center Manager HCL / Volvo IT. Volvo Information Technology HCL Morgan Ledner Global Data Center Manager HCL / Volvo IT Cooling and environment in a DC From the perspective of a data center provider and the challenges Environmental issues / energy consumption in

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. TelecityGroup Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

Trends and legislations in the data center industry. Pär Åberg - Business Development Manager - Swegon

Trends and legislations in the data center industry. Pär Åberg - Business Development Manager - Swegon Trends and legislations in the data center industry Pär Åberg - Business Development Manager - Swegon DC Fastest growing industry in the world 2 Fast and furious 3 IT services in the driving seat of the

More information

EP s approach to Power & Energy efficiency in DCs & paradigms

EP s approach to Power & Energy efficiency in DCs & paradigms DG for Innovation and Technological Support EP s approach to Power & Energy efficiency in DCs & paradigms Presentation Presentation subtitle subtitle or lead-in or lead-in that says that what says what

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Indirect Adiabatic and Evaporative Data Centre Cooling

Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

DATA CENTRE & COLOCATION

DATA CENTRE & COLOCATION DATA CENTRE & COLOCATION RISING DEMAND FOR HOSTED SERVICES When it comes to hosted IT infrastructure, organisations are looking for highly resilient, highly available and highly scalable facilities at

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Charles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by:

Charles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by: Charles Nolan Director IT Infrastructure, UNSW Do more with less with your data centre A customer s perspective Brought to you by: Today s Enterprise Data Centre Doing more with less High Density Data

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Indirect Adiabatic and Evaporative Data Center Cooling

Indirect Adiabatic and Evaporative Data Center Cooling Indirect Adiabatic and Evaporative Data Center Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced technology

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Enabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific

Enabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific Enabling Business Critical Continuity for Unified Communications Andy Liu Product Manager, Asia Pacific Emerson Creating Technology and Solutions for a World in Action #1 AC & DC Power System #1 OEM Embedded

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

ZTE ZXCR Series DX In-Row Air Conditioning Product Description

ZTE ZXCR Series DX In-Row Air Conditioning Product Description ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

1008 kw, Tier 2, Chilled Water, ft 2

1008 kw, Tier 2, Chilled Water, ft 2 [eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65

More information

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

LCP Hybrid Efficient performance with heat pipe technology

LCP Hybrid Efficient performance with heat pipe technology LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail. Powered by TCPDF (www.tcpdf.org) This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail. Zhang, Xiaojing; Lindberg, Theresa;

More information

DATA CENTER COLOCATION BUILD VS. BUY

DATA CENTER COLOCATION BUILD VS. BUY DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

Converged Power Solutions. Data center power reinvented

Converged Power Solutions. Data center power reinvented Converged Power Solutions Data center power reinvented always on anywhere anytime With Eltek s Converged Power Solutions, the next generation power solution for data centers is here. It offers unmatched

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

Innovative Data Center Energy Efficiency Solutions

Innovative Data Center Energy Efficiency Solutions Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal

More information

The Trusted Brand of Datacenters

The Trusted Brand of Datacenters The Trusted Brand of Datacenters Telehouse worldwide High Security Datacenters Defense level security Access control Higly protected environment Watch out for the missile Experience Bespoke fitout Dedicated

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

Munters Data Center Cooling Solutions. Simon Young & Craig MacFadyen Munters Data Centers

Munters Data Center Cooling Solutions. Simon Young & Craig MacFadyen Munters Data Centers Munters Data Center Cooling Solutions 1 Simon Young & Craig MacFadyen Munters Data Centers Introduction Vision Your Perfect Climate Mission Munters' mission is to be a globally leading supplier of energy

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

LG CNS Global Cloud Data Center

LG CNS Global Cloud Data Center LG CNS Global Cloud Data Center Are your digital assets vital to your business growth? Then, let LG CNS manage it for you Solution For further information, please contact: datacenter@lgcns.com www.lgcns.com/en

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2 [Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and

More information

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft. [Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

The Evolving Data Center

The Evolving Data Center The Evolving Data Center Dominic Loh Product Manager, Power Quality, APAC Data Centers are enabling global growth Proliferation of mobile computing Digitalization of everything Big Data 2 Evolution of

More information

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary.

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary. How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter Summary Diesel Rotary UPS (DRUPS) systems are best in class regarding energy

More information

White paper adaptive IT infrastructures

White paper adaptive IT infrastructures Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

One Stop Cooling Solution. Ben Tam Business Development Manager

One Stop Cooling Solution. Ben Tam Business Development Manager One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One

More information

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers TM PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable

More information

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC) How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity

More information

Trends in Data Center Energy Efficiency

Trends in Data Center Energy Efficiency Trends in Data Center Energy Efficiency Presented by: Todd Boucher Better Building by Design 2012 1 Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

5.2 MW, Pod-based build, Chilled Water, ft 2

5.2 MW, Pod-based build, Chilled Water, ft 2 [Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration

More information

How High-Density Colocation and Enhanced Visibility Improve Business Performance

How High-Density Colocation and Enhanced Visibility Improve Business Performance How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications

More information

Data Center Infrastructure Management (DCIM) By Jesse Zhuo

Data Center Infrastructure Management (DCIM) By Jesse Zhuo Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Maximising Energy Efficiency and Validating Decisions with Romonet s Analytics Platform. About Global Switch. Global Switch Sydney East

Maximising Energy Efficiency and Validating Decisions with Romonet s Analytics Platform. About Global Switch. Global Switch Sydney East Maximising Energy Efficiency and Validating Decisions with Romonet s Analytics Platform Case Study - Global Switch Sydney East About Global Switch Global Switch is a leading owner, operator and developer

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

Beyond BREEAM Excellent DCs. Cobalt Data Centre Campus

Beyond BREEAM Excellent DCs. Cobalt Data Centre Campus Beyond BREEAM Excellent DCs Cobalt Data Centre Campus Campus Location - Newcastle Campus Site Plan Data Centre 2 Data Centre 1 Data Centre 3 Cobalt Business Park Power Delivery to Site National Grid Tynemouth

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Data Centre Solutions Expertly Engineered Indirect Adiabatic and Evaporative

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies About Upsite Technologies Upsite Technologies, Inc., a pioneer, and industry thought leader specializing in data center airflow management, provides a full suite of products and services designed to enable

More information

Chiller Replacement and System Strategy. Colin Berry Account Manager

Chiller Replacement and System Strategy. Colin Berry Account Manager Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information