DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
|
|
- Jemimah Alexina Conley
- 6 years ago
- Views:
Transcription
1 DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP
2 Agenda Problem: Quick fixes can prevent long-term data center energy savings Overview of typical data center energy use 1. Identifying energy usage 2. ASHRAE TC 9.9 Changes 3. Overview of refrigeration cycle Impact of Raising Set-points 1. Efficiency Improvement 2. Capacity Increase 3. Economizer effectiveness 4. Air Flow Reduction 5. Case Study 6. Q&A
3 Problem: Quick fixes can prevent long-term data center energy savings Non-uniform temperature in the Data Centers leads to Hot/Cold Spots Hot spots increase risk of IT equipment failures Quick Fix : set average data center temperature lower than ASHRAE TC9.9 Guidelines (65-80 F) Disadvantages to quick fix : 1. Increase PUE 2. Increase energy consumption 3. Increase operating costs
4 Power Utilization Effectiveness (PUE) PUE = Total Power / IT Power Total Power = IT power, PDU/UPS losses, Lighting Power and HVAC Power IT Power = Servers, Storage and computing support equipment HVAC Power = Fan power, cooling power, pumps, heat rejection PUE is yardstick to compare data centers energy efficiency performance Average data center today operates with PUE of 1.4 to 2.2 based on Willdan s observation Very efficient data center operate at a PUE of 1.1 or better
5 Average Data Center Energy Use Cooling energy accounts for 20-50% of total energy usage Strategy to Improve Cooling energy efficiency: 1. Lower PUE of whole data center 2. Save operational costs
6 ASHRAE TC Environmental Guidelines for Datacom Equipment Temperature and Humidity Settings Recommended by ASHRAE TC 9.9 Ranges Temperature Moisture 2004 Version 2008 Version Low End 20 C (68 F) 18 C (64.4 F) High End 25 C (77 F) 27 C (80.6 F) Low End 40% RH 5.5 C DP (41.9 F) 60% RH & 15 C DP High End 55% RH (59 F DP) Raised temperature set points on high end from 77 F to 80.6 F Relative Humidity limits were also raised Significant testing determined for any class of server equipment this temperature range are safe and minimal failure due to temperature and humidity
7 Data Center Cooling Equipment WATER COOLED CHILLERS CRAC OR CRAH AIR COOLED CHILLERS
8 Refrigeration Vapor Compression Cycle Four main components: 1. Compressor (1-2) 2. Condenser (2-5) 3. Expansion Device (5-6) 4. Evaporator (6-1)
9 Raising Evaporator Stpt Reduces Compressor work Vapor compression cycle with temperature rise for R-22
10 Refrigerants and Compressor Efficiency Refrigerant Case Set Point ( F) Evap in/out ( F) COP Efficiency (kw/ton) % Improvement COP kw/ton R-22 Baseline % 1.63% Proposed R-134a Baseline % 1.56% Proposed R-123 Baseline % 1.87% Proposed R-407a Baseline % 1.33% Proposed R-410a Baseline % 2.06% Proposed Percent improvements of compressor Coefficient of Performance (COP) and kw/ton for refrigerants per every F
11 Impacts of raising evaporator supply temperature (Example R-22 Refrigerant) Refrigeration Effect BTU/lb or Capacity in Tons Ref. Heat Capacity Ton/CFM Raising evaporator supply temperature: 1. Increases cooling capacity 2. Improves efficiency 3. Increases heat capacity of the refrigerant Evaporator Supply Temp F 0 Ref. Effect BTU/lb Capacity in Tons Ref. Heat Capacity Ton/CFM
12 60-ton MultiStack chiller with 20-ton modules EER and Capacity in Tons Efficiency (kw/ton) Raising evaporator temperature: 1. Increases capacity 2. Improves Energy Efficiency Ratio (EER) 3. Improves kw/ton efficiency CHWS F Capacity in Tons EER Eff. kw/ton 0.60
13 400-ton Daikin magnetic bearing water-cooled chiller Chiller Efficiency kw/ton Ton, Water-Cooled Magnetic Bearing Chiller Percentage Part Load 400 ton Water cooled Magnetic Bearing Daikin Chiller Selected % part load efficiencies at variety of CHWS Temp F Efficiency kw/ton Vs % Part Loads CHWS 42 F kw/ton CHWS 45 F kw/ton CHWS 48 F kw/ton CHWS 44 F kw/ton CHWS 46 F kw/ton CHWS 50 F kw/ton
14 170-ton Daikin air-cooled screw chiller Chiller Efficiency kw/ton Ton Air-Cooled Screw Chiller 170-ton air cooled Daikin Screw Pathfinder Chiller Selected % part load efficiencies at variety of CHWS Temp F Efficiency kw/ton Vs % part load Percentage Part Load CHWS 42 F kw/ton CHWS 44 F kw/ton CHWS 46F kw/ton CHWS 48F kw/ton CHWS 50F kw/ton
15 Raising evaporator temperature increases air-side economizer hours Ideal conditions for air-side economizers (Courtesy of U.S. Dept. of Energy and The Green Grid)
16 Raising evaporator temperature increases water-side economizer hours Ideal conditions for water-side economizers (Courtesy of U.S. Dept. of Energy and The Green Grid)
17 Increase economizer hours by increasing set points US Cities with OA Temp 40 F-50 F Chart demonstrates # of hours climate zones 40 F to 50 F, which are equivalent to increased hours for water-side economizers for different cities When space set point rise, SAT or CHWS temp increase linearly Economizer can start at relatively higher temp than standard SAT or chilled water temp for more hours
18 Sensible Cooling Capacity Sensible Cooling Capacity (BTU/Hr) = 1.08 x Airflow (CFM) x (RAT ( F) SAT ( F)) Sensible loads dominate in Data Centers Airflow containment increases RAT temperature Raising space temperature set point enables the supply-fan variable-frequency device (VFD) to operate at reduced speed Increased Delta T (difference between RAT and SAT) reduces air flow requirements, which enables reduced VFD speed or turn off units completely
19 Summary of advantages of raising set points Advantages of raising data center and mission critical temperature set-points 1. Increased cooling equipment capacity 2. Improved cooling equipment efficiency 3. Increased economizer hours for cooling system with economizer capabilities 4. Reduced supply fan speeds for CRAC/CRAHs with VFD supply fans
20 Willdan Case Study Project basics: 124,000 sq.ft. raised floor data center Thirty-four (34) 120-ton rooftop split units with 50 HP supply air fans (VFD), Two (2), 24 ton air cooled DX CRAC units. Cold air is supplied via under-floor plenum and discharged through raised floor diffusers and returned via ceiling plenum Problem: Warmer return air mixes with cold or supply air creating hot and cold spots resulting in a very small delta T and uneven room air distribution
21 List of Energy Efficiency Measures (EEMs) Solution: Install containment solution, increasing return air temperature and allowing SAT to be raised Results: Improved mechanical cooling efficiency Reduced VFD fan speeds Increasing set points allows economizer lock out to be raised which increases economizer hours and reduces mechanical cooling for the data center Approximately 7% electric energy saving, 3.5 million kwh saving, $ 254k saved per year, $ 245k paid out as incentive
22 Pre and post case mechanical load vs. OAT 3,500 3,000 Mechanical Load (kw) vs. OAT ( F) y = x R² = Mechanical Load (kw) 2,500 2,000 1,500 y = x R² = y = x R² = ,000 y = x R² = OAT ( F) Pre-M&V Mechanical Load Post-M&V Mechnaical Load Pre-M&V Mechanical Load (Partial-Econ)
23 Pre and post case compressor amps vs. OAT Compressor Amps vs. OAT ( F) Compressor Amps 2,400 2,200 2,000 1,800 1,600 1,400 1,200 1, OAT ( F) Pre-M&V Compressor Amps Post-M&V Compressor Amps
24 Pre and post case PUE vs. OAT
25 Conclusion 1. Raising the set point in the data center has many advantages. 2. The most important data center temperature: rack/server inlet temperature 3. Increasing the data center space temperature should be carried out in conjunction with air flow management 4. Raising the set point increases the cooling capacity of equipment and provides for load growth. 5. Higher space temperature set points increase available economizer hours for both air-side and waterside economizers. 6. The cooling system design should be carefully evaluated before making changes.
26 Q & A Questions????????
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationImplications of Current Thermal Guidelines
Copyright 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission from ASHRAE Journal/High Performing Buildings. This material may not be copied
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationEvaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building
Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Dhayanandh Murugan 1, Gabrielle Viola McMorrow 1, Dr.Liping Wang 1, Greenberg Steve 2 1 University of Wyoming,
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationTop 10 energy conservation measures for data centers. Presented by: Michael G. Bushell, P.E. Willdan Energy Solutions Chicago, Illinois
Top 10 energy conservation measures for data centers Presented by: Michael G. Bushell, P.E. Willdan Energy Solutions Chicago, Illinois December 11, 2014 Top 10 energy conservation measures for data centers
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationWhat s New for Data Centers in Title Jeff Stein, PE Taylor Engineering
What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationData Center Energy and Cost Saving Evaluation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.
More informationZTE ZXCR Series DX In-Row Air Conditioning Product Description
ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase
More informationHVAC System Energy Savings Opportunities
HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationDEDICATED HEAT RECOVERY UNIT (DHRC)
DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationWHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net
Digi-RTU WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationR4 Ventures LLC White Paper
R4 Ventures LLC PR ODUCT IN HARD COPY OR DIGITAL FORM. ALL OFFENDERS WILL BE SUED IN A COURT OF LAW. R4 Ventures LLC White Paper Comparison of energy consumption in kw per ton of cooling Real Time Data
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationIT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw
IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable
More informationAir-Side Economizer Cycles Applied to the Rejection of Data Center Heat
Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation Founded in 1955 Manufacturing & Sales Locations
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationCOOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS
COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS Dr Jon Summers Scientific Leader in Data Centers Part-time Academic in Thermofluids at the
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationCLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES
CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES DATA CENTER NEEDS A MINUTE IN THE LIFE OF INTERNET Evolving technology has created the necessity for ever greater exchange of data, increasing
More informationImpact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency
Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency White Paper 135 Revision 3 by John Niemann, Kevin Brown, and Victor Avelar Executive summary Both hot-air and cold-air
More informationBest Practices Guide for Energy-Efficient Data Center Design
FEDERAL ENERGY MANAGEMENT PROGRAM Best Practices Guide for Energy-Efficient Data Center Design Revised March 2011 Prepared by the National Renewable Energy Laboratory (NREL), a national laboratory of the
More informationTrailblazer AGZ-E air-cooled scroll chillers
Trailblazer AGZ-E air-cooled scroll chillers 30 to 240 tons with Variable Speed Condenser Fan Technology The right features, the right value, right now Intelligent Equipment AGZ-E 30 to 161 RapidRestore
More informationEnergy Efficiency Retrofit Technologies for RTUs
Energy Efficiency Retrofit Technologies for RTUs POTENTIAL RTU RETROFITS Retrofits proven to increase the energy efficiency and reduce operating costs Stated Goals of RTU Retrofit development (DOE): Optimize
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationAIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants
AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants By: David Schurk DES., CEM., LEED AP., CDSM., SFP. Heat Transfer Solutions, Director of Healthcare Accounts The air-cooled
More informationCHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM
CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable) Commercial Buildings New or Existing Institutional Buildings: Educational Facilities New
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationSilicon Valley Power Data Center Program Rebate Application
Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account
More informationYour data center s hidden source of revenue
WHITEPAPER Your data center s hidden source of revenue Harvesting heat from data centers with Low Speed Ventilation server coolers February 2016 Contents 1. Introduction...2 2. Challenges...3 3. Heat harvesting
More informationMOLLIER DIAGRAM CAN BE IMPROVED!
MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationPrecision Cooling Mission Critical Air Handling Units
M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly
More informationWHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net
WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve the
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationOptimiz Chilled January 25, 2013
Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationSecond Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer
Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE 90.1-2016 Revisions to Waterside Economizer March 15, 2017 Stefan Gracik 510-663-2070 sgracik@integralgroup.com Agenda 1. Background
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationPresentation. Guaranteed Energy Savings Performance Project
Presentation Guaranteed Energy Savings Performance Project Greg Spiro, PE, CEM, LEED-AP Georgia Institute of Technology Senior Mechanical Engineer Facilities Design & Construction 470-351-9867151 6th Street
More informationData Center Heat Rejection
This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.munters.us.
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationWaterside Economizing in Data Centers: Design and Control Considerations
2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional reproduction,
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationOptimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC
Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationOptimizing Laboratory Controls through Fault Detection and Diagnostics Software. Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM
Optimizing Laboratory Controls through Fault Detection and Diagnostics Software Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM Overview What are EIS & FDD Tools? Data Connection Methods
More informationFive Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationSTATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016
STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationEnergy Engineering: Tools and Trends
Energy Engineering: Tools and Trends AEE Northeast Ohio Chapter Meeting March 27, 2008 1 Introduction Background and Experience Energy Engineer for Trane 20 years in HVAC Industry Equipment design and
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationDEEMED SAVINGS TECHNICAL ASSUMPTIONS
Program: Description: Prescriptive rebates will be offered for new cooling equipment. Rebates may be dependent on equipment size or load that is offset and on meeting minimum efficiency requirements. Additional
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationPrescriptive Program Rebate Application
Prescriptive Program Internal use only Xcel Energy OID Check the appropriate program box for your rebate. Cooling Data center efficiency FSO (Fluid System Optimization) Foodservice equipment Heating Lighting
More informationAchieving Energy Efficiency in Data Centers
Achieving Energy Efficiency in Data Centers This document was specifically prepared to aid utility account managers who are working with C&I customers. Any other use of this material (in whole or in part)
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationRittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy
Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationDATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise
DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise TWO STAGE POWER DISTRIBUTION Executive Summary Today s data centers are changing rapidly, and it is more important than ever
More information