MTEP16 South SPM #3 MISO Louisiana Project Information

Size: px
Start display at page:

Download "MTEP16 South SPM #3 MISO Louisiana Project Information"

Transcription

1 MTEP16 South SPM #3 MISO Louisiana Project Information 3 rd South Sub-regional Planning Meeting August 25, 2016

2 NERC TPL Contingency Categories TPL Category Old TPL Category Description BES Level Acceptable Mitigation Physical Upgrade Required? P0 A System intact EHV, HV Yes No Load Shed or Redispatch Allowed? P1 B Single contingency (Fault of a shunt device- fixed, switched or SVC/STATCOM is new) EHV, HV Yes No P2 C1, C2 Single event which may result in multiple element outage. Open line w/o fault, bus section fault, internal breaker fault EHV HV Yes No No Yes P3 C3 Loss of generator unit followed by system adjustments + P1. No load shed is allowed EHV, HV Yes Yes P4 C Fault + stuck breaker events EHV HV P5 N/A Fault + relay failure to operate (new) EHV HV P6 C3 Two overlapping singles (not generator) EHV, HV No Yes P7 C4, C5 Common tower outages; loss of bipolar DC EHV, HV No Yes Yes No Yes No No Yes No Yes Please refer to BPM 020 for additional details on acceptable mitigation 2

3 Entergy Louisiana, Entergy New Orleans, Cleco Power, City of Alexandria, Lafayette Utility Systems Identified Needs LA-08 LA-22 TO reliability project proposed Need + Project LA-38 LA-05 LA-06 LA-07 LA-28 LA-31 LA-15 LA-16 LA-17 LA-13 LA-14 LA-18 LA-19 LA-20 LA-21 LA-25 LA-11 LA-12 LA-27 LA-36 LA-23 LA-37 LA-38 LA-39 LA-40 LA-41 LA-09 LA-24 LA-29 LA-10 LA-26 LA-30 LA-04 LA-32 LA-01 LA-02 LA-03 LA-33 LA-34 LA-35 A detailed list of needs is tabulated in spreadsheet Issues_Tracker_SOUTH_SSPM3.xlsx MISO, using Ventyx Velocity Suite

4 Entergy Louisiana, Entergy New Orleans, Cleco Power, City of Alexandria, Lafayette Utility Systems Identified Needs MISO reliability need under evaluation LA-42 LA-46 LA-48 LA-39 LA-40 LA-41 LA-44 A detailed list of needs is tabulated in spreadsheet Issues_Tracker_SOUTH_SSPM3.xlsx MISO, using Ventyx Velocity Suite

5 Open Issues Under Discussion Criteria Violation ID Number of Criteria violations Contingency Category Thermal Violations Gen Load Shed Redispatch (MW) (MW) Comment LA-44 6 P Future MTEP17 project will address this issue. LA-46 2 P Future MTEP17 project will address this issue. Future MTEP17 project will address this issue. EHV LA P options being considered. LA-39 1 P Occurs in the near-term model. Coordination LA-41 3 P7 0 0 between regional transmission owners to solve LA-42 1 P these issues is ongoing. Criteria Violation ID Number of Criteria violations Contingency Category Voltage Violations Gen Load Shed Redispatch (MW) (MW) Comment LA P Future MTEP17 project will address this issue. LA-40 1 P Future MTEP17 project will address this issue. A list of needs is tabulated in spreadsheet Issues_Tracker_South_SSPM3.xlsx 5

6 Entergy Louisiana and Entergy New Orleans MTEP16 Project Review 3 rd South Sub-regional Planning Meeting August 25, 2016

7 Entergy Louisiana, Entergy Gulf States, Entergy New Orleans: MTEP16 Targeted Appendix A Project Summary by Count 5 4 $1M- $1M-5M $5M+ Estimated Project Cost Range BRP 4 5 Other Entergy Louisiana, Entergy Gulf States and Entergy New Orleans have a total of 68 projects submitted to the MTEP16 cycle 45 projects are targeted for Appendix A in MTEP16 ($417.5 M) Of these 45 projects: 27 have an estimated cost greater than $5 M 9 have an estimated cost between $1M-$5 M 9 have an estimated cost lower than $1 M Of these 45 projects: 26 Baseline Reliability 19 Other 23 projects added to Appendix B in MTEP16 ($281.8 M) 5 projects in Appendix B from previous MTEP ($34 M) 7

8 Entergy Louisiana, Entergy New Orleans : MTEP16 Targeted Appendix A Project Summary by Estimated In-Service Date $216.1 M 8 $124.3 M $20.2 M 2 11 $0.715 M $56.2 M Estimated In-Service Date BRP Other 8

9 ELL P4634: Ninemile to Westwego 115 kv Line Upgrade MISO identified issues addressed by 4634 Issue Tracker ID LA-01: Open Breaker Contingency Near term, 107% of Emergency Rating Project Description (13-ELL-006) Re-conductor the existing Ninemile to Westwego115 kv line to achieve a minimum rating of 320 MVA. Estimated Cost $9.03 M Expected ISD June 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP mi MISO, using Ventyx Velocity Suite

10 ELL P4639: Ninemile to Harvey 115 kv Line Upgrade MISO identified issues addressed by 4639 Issue Tracker ID LA-02: Single Line Contingency Near term, 102% of Emergency Rating Project Description (14-ELL-006) Re-conductor the existing Ninemile to Harvey 115 kv line to achieve a minimum rating of 320 MVA. Estimated Cost $15.12 M Expected ISD June 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP mi MISO, using Ventyx Velocity Suite

11 ENOI P9805: Reconductor Patterson to Pontchartrain Park 115 kv Line MISO identified issues addressed by 9805 Issue Tracker ID LA-03: Avenue C Pontchartrain Park Paterson Open Breaker Contingency Near term, 97% of Emergency Rating Project Description (16-ENO-001) Paris Pauger Reconductor the Patterson to Pontchartrain Park 115 kv line. Estimated Cost Labarre $11.9 M Expected ISD Southport December 1, 2018 Ninemile Project Type Baseline Reliability Target Appendix A in MTEP16 MISO, using Ventyx Velocity Suite

12 ELL P9801: North Norco 115 kv Capacitor Bank Addition MISO identified issues addressed by 9801 Issue Tracker ID LA-04: Single Line Contingency Near term, Vpu Project Description (16-ELL-004) Add a capacitor bank to the North Norco substation. Estimated Cost $ 1.8 M Expected ISD December 1, 2017 Project Type Baseline Reliability Target Appendix A in MTEP16 Waterford Little Gypsy Claytonia Vpu Norco Vpu Ormond Vpu MISO, using Ventyx Velocity Suite

13 ELL P10008: Nelson to Menena New 230 kv Line MISO identified issues addressed by Flows exceeding the Nelson Michigan 230kV circuit emergency rating as identified in MTEP15 deliverability analysis for Nelson generation. Sulphur Lane Nelson Project Description (15-EGL-023) Construct new 230 kv line from Nelson to Menena substation. 5 mi. Michigan Estimated Cost PPG $15.5 M Expected ISD Patton Carlyss Menena June 1, 2020 Project Type Baseline Reliability Project Target Appendix A in MTEP16 MISO, using Ventyx Velocity Suite

14 ELL P7949: Solac 230/69 kv Autotransformer #1 and #2 Upgrade MISO identified issues addressed by 7949 Issue Tracker ID LA-05: Single Transformer Contingency Near term, 106% of Emergency Rating Project Description (15-EGL-010) Replace both 230/69 kv Autotransformers with 300MVA units. Estimated Cost $ 8.46 M Expected ISD June 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP16 106% MISO, using Ventyx Velocity Suite

15 ELL P7950: East Broad to Ford 69 kv Line Upgrade MISO identified issues addressed by 7950 Issue Tracker ID LA-06: Single Line Contingency Near term, 103% of Emergency Rating Project Description (15-EGL-011) Re-conductor East Broad to Ford 69 kv line. Estimated Cost $ 1.5 M Expected ISD June 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP16 103% 1.5 mi MISO, using Ventyx Velocity Suite

16 ELL P7952: Solac to Contraband 69 kv Line Upgrade MISO identified issues addressed by 7952 Issue Tracker ID LA-07: Single Line Contingency Near term, 98% of Emergency Rating Project Description (15-EGL-012) Re-conductor Contraband to Solac 69 kv line. Estimated Cost $ 4.1 M Expected ISD June 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP16 98% 4.4 mi MISO, using Ventyx Velocity Suite

17 ELL P9771, P9772, P9773, P9774, P9775, P9776, P9777, P9778: Southwest Louisiana Project Phase 1 MISO identified issues addressed by Issue Tracker ID LA-13 to LA-19: Single Line, Single Transformer and Open Breaker Contingencies Near term, Long Term 95% to 186% of Emergency Rating Local Area Network: Southwest Louisiana Approximately 100 mile of 69kV transmission line between Lake Charles Bulk and Jennings substations The network spans approximately 30 miles Primarily supplied by 138/69 kv taps at Lake Charles Bulk and Jennings 30 mi MISO, using Ventyx Velocity Suite

18 ELL P9771, P9772, P9773, P9774, P9775, P9776, P9777, P9778, P9782: Southwest Louisiana Project Phase 1 Project Description Construct new Jefferson Davis 138/69 kv substation Construct a new line from Colonial Welsh Tap to the new Jefferson Davis 138 kv station Build a new 69 kv line from Jefferson Davis to Carter substation Construct a new double circuit 69kV line from Jeff Davis to a point due south of Compton and cut into the Compton to Roanoke 69kV circuit. Estimated Cost $76.6 M Expected ISD June 1, 2019 Project Type Baseline Reliability Project Target Appendix A in MTEP16 Jeff Davis MISO, using Ventyx Velocity Suite

19 ELL P9779: Southwest Louisiana Project Phase 2 MISO identified issues addressed by 9779 Issue Tracker ID LA-20: Single Line Contingency Near term, 98% of Emergency Rating Project Description (16-EGL-013) Reconductor the Carter to Serpent 69 kv line (16 mi). Estimated Cost $19.2 M Expected ISD December 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP16 98% Elton MISO, using Ventyx Velocity Suite

20 ELL P9780: Southwest Louisiana Project Phase 3 MISO identified issues addressed by 9780 Issue Tracker ID LA-21: Single Line Contingency Near term, 94% of Emergency Rating Project Description (16-EGL-014) Reconductor the Compton to Elton 69 kv line (11.5 mi) Estimated Cost $12.8 M Expected ISD December 1, 2019 Project Type Baseline Reliability Project Target Appendix A in MTEP16 Carter Serpent 94% MISO, using Ventyx Velocity Suite

21 ELL P9682: Vienna - Trussel Crossing Line Upgrade MISO identified issues addressed by 9682 Issue Tracker ID LA-08: Sarepta Single Line Contingency Near term, 90% of Emergency Rating Project Description (16-ELN-001) Upgrade the Vienna - Trussel Crossing 115 kv line to a minimum of 260MVA. Minden Trussel Crossing 90% Vienna Estimated Cost Ada $8.8 M Expected ISD June 1, 2020 Sailes Project Type Baseline Reliability Project Target Appendix A in MTEP16 MISO, using Ventyx Velocity Suite

22 ELL P9763: Baker to Blount 69kV Line Upgrade MISO identified issues addressed by 9763 Issue Tracker ID LA-09: Single Line Contingency Near term, 111% of Emergency Rating Project Description (16-EGL-004) Upgrade the rating on the Baker to Blount 69 kv line by upgrading the conductor and substation equipment Estimated Cost $5.2 M Expected ISD June 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP16 Port Hudson Zachary 3.8 mi Dixie Baker Baker 111% Blount MISO, using Ventyx Velocity Suite

23 ELL P9765: Harelson to Line 369 Tap 69kV Line Upgrade MISO identified issues addressed by 9765 Line Tap 369 Issue Tracker ID LA-10: Single Line Contingency Near term, 114% of Emergency Rating Sharp 114% Lively Flannery Gloria Project Description (16-EGL-006) 3.5 mi Reconductor the Harelson to Line 369 Tap 69 kv line Harrelson Estimated Cost $3.2 M Expected ISD December 1, 2018 Project Type Baseline Reliability Project Target Appendix A in MTEP16 MISO, using Ventyx Velocity Suite

24 ELLP9788: Port Barre 69 kv Capacitor Bank MISO identified issues addressed by 9788 Plaisance Issue Tracker ID LA-11: Single Transformer Contingency Near term, 0.88 Vpu Project Description (16-EGL-022) Port Barre 0.88 Vpu Install a capacitor bank at the Port Barre substation Estimated Cost Westfork Guidry Street South Park Champagne 0.88 Vpu $800,000 Expected ISD Colton June 1, 2018 Project Type Wells Baseline Reliability Project Target Appendix A in MTEP16 MISO, using Ventyx Velocity Suite

25 ELL P9795: Nesser 69 kv Capacitor Bank MISO identified issues addressed by 9795 Issue Tracker ID LA-12: Open Breaker Contingency Near term, 0.89 Vpu Project description (16-EGL-033) Add a capacitor bank to the Nesser 69 kv substation Estimated Cost $ 1.1 M Expected ISD December 1, 2017 Project Type Baseline Reliability Project Target Appendix A in MTEP16 Dawson Creek Ward Creek Nesser 0.89 Vpu Harrelson Gloria Jones Creek 0.91 Vpu MISO, using Ventyx Velocity Suite

26 ELL, ENOI: Projects Driven by New Load Addition Target Appendix A 9684 A 9686 A 9690 A A A A ID Project Name Description Expected ISD Cadeville (16-ELN-004): New Distribution Substation Lake Providence (16-ELN-005): New Distribution Substation Hodge (16-ELN-010): Replace Existing Substation Swisco (16-EGL-026): Construct New Substation Thompson Road (16-EGL-027): Construct New Substation Lowe Grout Road (16-EGL-028): Construct New Substation LAGEN Holly Ridge (16-ELN- 011) Construct New Substation Construct a new radial 115 kv transmission line (approx. 15 mi.) to a new 115 kv substation in the Cadeville area to serve area load Construct a new radial 115 kv transmission line (approx. 10 mi.) to the Lake Providence area to serve area load Construct a new 230 kv substation to serve area load in the Hodge area. Construct a new 138 kv substation to serve area load on the Mossville to Carlyss 138 kv line Construct a new 230 kv substation to serve area load on the Patton to Carlyss 230 kv line Construct a new 138 kv substation to serve area load on the Lake Charles to Jennings 138 kv line Construct a new 115/13.8 kv distribution serving substation on the Oak Ridge - Dunn 115 kv transmission line in North Central Louisiana Cost 6/1/2018 $41.6 M 6/1/2020 $31.8 M 12/1/2018 $14.1 M 6/1/2017 $8.2 M 6/1/2018 $9.2 M 6/1/2019 $7 M 12/31/2016 $254,000 26

27 ELL, ENOI: Projects Driven by New Load Addition Target Appendix A A ID Project Name Description Expected ISD Fleur 230 kv Substation: New Substation Sadie 230 kv: Construct New Substation Construct a new 230 kv substation on the Oakville to Alliance 230 kv transmission line. This substation will be the primary feed to a customer in the area. Load will move from other substations in the area. Rebuild the Ninemile to Barataria 115 kv line. Construct a new 230 kv substation on the PPG to Rosebluff 230 kv line. Cost 12/31/2018 $42.7 M 6/1/2018 $24,814, A A Big Lake 230 kv: Construct New Substation Menena 230 kv: Construct New Substation Construct a new 230 kv substation on the Vincent to Graywood 230 kv line. Industrial Customer Connection This is a customer driven project to install a new 230 kv substation on the PPG to Rose Bluff 230 kv line. 6/1/2019 $28,000, /1/2017 $7,290,000 27

28 ELL, ENOI: Substation Equipment Upgrades Target Appendix A 9770 A 9787 A 9786 A 9794 A ID Project Name Description Expected ISD A A A Goosport to L673 TP 69 kv (16-EGL-011): Upgrade Station Equipment Air Products to Giegy 138kV (16-EGL-021): Upgrade Substation Equipment Nelson 138 kv Breaker Failure Project (16-EGL-020) Port Hudson Station 138 kv Substation Equipment Upgrade (16-EGL-032) Coly 230 kv: Breaker Addition (16-EGL-037) Tiger 230 kv: Breaker Addition (16-EGL-038) Harelson 230 kv: Breaker Addition (16-EGL-039) Willow Glen 500/138 kv Auto: Adjust Taps Upgrade the substation equipment at Goosport to increase the rating of the line Upgrade substation equipment on the Air Products and Giegy terminals to increase the rating of the line Add L-274, L-654, L-656 and L-698 to the double bus double breaker scheme at Nelson. Upgrade substation equipment at Port Hudson 138 kv. Cost 11/18/2016 $145,205 6/1/2016 $300,000 6/1/2017 $1.1 M 6/1/2018 $101,000 Add a breaker at the Coly 230 kv substation. 6/1/2018 $1.7 M Add a 230 kv breaker at the Tiger substation. 6/1/2018 $1.7 M Add a breaker at the Harelson 230 kv substation. 6/1/2018 $1.7 M Changing the position of the de-energized tap changer to 500kV (3/C) from 487.5kV (2/B). 12/1/2016 $15,027 28

29 ELL, ENOI: Projects Driven by Short Circuit Interrupting Capacity Target Appendix A 9847 A 9848 A 9849 ID Project Name Description Expected ISD ELL Underrated Breaker Project (16-EGL-030-1): Mossville 69 kv Breaker ELL Underrated Breaker Project (16-EGL-030-2): Mossville 69 kv Breaker ELL Underrated Breaker Project (16-EGL-030-3): Carlyss 69 kv Breaker 7840 Breaker number at the Mossville 69 kv substation will be replace due to the short circuit analysis. Breaker at the Mossville 69 kv substation will be replaced due to the short circuit analysis. Breaker number 7840 at the Carlyss 69 kv substation will be replace due to the short circuit analysis. 12/1/ /1/ /1/2017 Cost $700,000 29

30 Cleco Power, LLC MTEP16 Project Review 3 rd South Sub-regional Planning Meeting August 25, 2016

31 Cleco Power: MTEP16 Targeted Appendix A Project Summary by Count 3 1 Cleco Power has a total of 6 projects submitted to the MTEP16 cycle 4 projects are targeted for Appendix A in MTEP16 ($6.0 M) Of these 3 projects: 1 has an estimated cost between $1M- $5 M 3 have an estimated cost lower than $1 M 2 projects added to Appendix B in MTEP16 ($127.5 M) 2 projects remaining in Appendix B from previous MTEP ($23.5 M) < $1M $1M-5M Estimated Project Cost Range BRP Other All Cleco Target Appendix A Projects have an expected in-service date in

32 Cleco: Projects Driven by New Load Addition Appendix ID Project Name Description Expected ISD Cost Tap the existing 230 kv line from Dolet A 9542 Dolet Hills Mine Line Tap Hills to Mansfield Compressor to serve existing load which is moving its operations. 12/1/2016 $5 M 32

33 Cleco: Substation Equipment Upgrades Appendix ID Project Name Description Expected ISD Cost A 9713 Dolet Hills Breaker Replacements Replace one of the 345 kv Breakers at Dolet Hills. 11/1/2016 $295,000 A 9715 Wax Lake Cap Switcher Replacements Replace Manually Operated Switches at Wax Lake with Cap Switchers 10/1/2016 $406,000 A Hopkins Breaker Addition Add a second Breaker in Series with Hopkins Breaker /1/2016 $300,000 33

34 Lafayette Utilities System MTEP16 Project Review 3 rd South Sub-regional Planning Meeting August 25, 2016

35 Lafayette Utilities System: MTEP16 Targeted Appendix A Project Summary by Count Lafayette Utilities Systems has one project submitted to the MTEP16 cycle The project is targeted for Appendix A in MTEP16 ($4.2 M) Estimated cost between $1M-$5 M Baseline Reliability 1 0 projects added to Appendix B in MTEP16 0 projects remaining in Appendix B from previous MTEP $1M-5M Estimated Project Cost Range BRP Other All Lafayette Utilities System Target Appendix A Projects have an expected in-service date in

36 LUS P8821: Northeast to Peck 69 kv Line MISO identified issues addressed by 8821 Issue Tracker ID LA-37: Generation Unit + Transformer contingency Near term, 105% of Emergency Rating Project description Construct new 69kv line from Northeast to Peck substations. Estimated Cost Northeast $4.2 M Expected ISD Pont Des Mouton 5 mi December 31, 2019 Project Type Baseline Reliability Project Scott Labbe Bonin 105% Peck Target Appendix Elks A in MTEP16 Flanders MISO, using Ventyx Velocity Suite

37 City of Alexandria MTEP16 Project Review 3 rd South Sub-regional Planning Meeting August 25, 2016

38 City of Alexandria: MTEP16 Targeted Appendix A Project Summary by Count $830,000 2 City of Alexandria has a total of 2 projects submitted to the MTEP16 cycle 2 projects are targeted for Appendix A in MTEP16 0 projects are moving to Appendix B 0 projects are staying in Appendix B Estimated Project Cost Range BRP Other All City of Alexandria Target Appendix A Projects have an expected in-service date in

39 CoA: MTEP16 Target Appendix A Projects Age Related Replacements Prj ID Project Name Project Type Description MISO Identified Need Estimated Cost ($M) Expected ISD Hunter to Downtown 138 kv Line Upgrade Other Reliability Reconductor the existing Hunter - Downtown 138kV transmission line. LA-38 $340,000 7/1/ Prescott to Sterx 138 kv Line Upgrade Other Reliability Reconductor the existing Hunter - Downtown 138kV transmission line. None $490,000 7/1/

40 Contact Information Edin Habibovic Manager Expansion Planning, Southern Region Jason VanHuss Expansion Planning Engineer, Southern Region 40

Monthly Long Term Transmission Plan Project Status Report

Monthly Long Term Transmission Plan Project Status Report Operating Company EAI EMI ELL ENOI ETI ALL Major Updates 2 projects in service 2 projects in service 2 projects in service, 7 projects cancelled No major changes 2 projects in service, 4 projects cancelled

More information

Monthly Long Term Transmission Plan Project Status Report

Monthly Long Term Transmission Plan Project Status Report Operating Company EAI EMI ELL ENOI ETI ALL Major Updates 2 projects in service No major changes 2 project in service, 1 new project No major changes No major changes 4 projects in service, 1 new project

More information

Feasibility Study on Load Flow and Short Circuit Project

Feasibility Study on Load Flow and Short Circuit Project Feasibility Study on Load Flow and Short Circuit Project 101813-01 Prepared by: Transmission Planning Department Cleco Corporation, Inc. 2180 St. Landry Hwy P.O. Box 70 St. Landry, LA 71367 Final November

More information

Local Area Studies Update - PACW Kevin Putnam

Local Area Studies Update - PACW Kevin Putnam Transmission Planning Attachment K Q5 Public Input Meeting Local Area Studies Update - PACW Kevin Putnam March 23, 2017 Hermiston-Pendleton-Enterprise Study Finding Report Jerry Vang PAGE 3 Hermiston-Pendleton

More information

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Small Generator Interconnection System Impact Study Report. Completed For Q0047 Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection

More information

ATC Zone 2 Projects Update U.P. Energy Summit

ATC Zone 2 Projects Update U.P. Energy Summit ATC Zone 2 Projects Update U.P. Energy Summit Brett French Regional Manager of External Relations Michigan October 16, 2012 Helping to keep the lights on, businesses running and communities strong Project

More information

Year Assessment Preliminary Solutions

Year Assessment Preliminary Solutions 2016 10-Year Assessment Preliminary Solutions Stakeholder and Customer Presentation May 26, 2016 Jeremy Voigt Purpose Summarize Asset Renewal Solution Identification Process Summarize Preliminary Changes

More information

Generation Interconnection Feasibility Study Report

Generation Interconnection Feasibility Study Report Project 76 Generation Interconnection Feasibility Study Report December 21, 2007 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Network Resource Interconnection

More information

Sub Regional RTEP Committee Mid-Atlantic First Energy MAAC

Sub Regional RTEP Committee Mid-Atlantic First Energy MAAC Sub Regional RTEP Committee Mid-Atlantic First Energy MAAC September 21, 2018 Penelec Transmission Zone Need Number: PN-2018-001 Consider upgrading transmission line equipment (switches, conductor, splices,

More information

2009 SPP TransCanada Pipeline Study Report

2009 SPP TransCanada Pipeline Study Report 2009 SPP TransCanada Pipeline Study Report SPP Engineering Department, Planning Section PUBLISHED: 7/9/2009 LATEST REVISION: 7/9/2009 Copyright 2009 by Southwest Power Pool, Inc. All rights reserved. Table

More information

2018 General Rate Case. Transmission & Distribution (T&D) Volume 3 R System Planning

2018 General Rate Case. Transmission & Distribution (T&D) Volume 3 R System Planning Application No.: Exhibit No.: Witnesses: A.1-0- SCE-0, Vol. 0 R E. Takayesu A (U -E) 01 General Rate Case Transmission & Distribution (T&D) Volume R System Planning Before the nd Errata Public Utilities

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic October 27, 2010 2010 RTEP Baseline Analysis Update Potential loss of load exceeding 300 MW for the loss of the Smithburg Englishtown 230 kv and Raritan River Deep

More information

Sub Regional RTEP Committee Western Region ATSI

Sub Regional RTEP Committee Western Region ATSI Sub Regional RTEP Committee Western Region ATSI January 11, 2019 1 ATSI Supplemental Needs PJM 2018 ATSI-2019-001 Operational Flexibility and Efficiency Infrastructure Resilience Global Considerations

More information

Interconnection of Navajo-Gallup Water Supply Project Electrical Transmission Facilities. Non-Tariff System Impact Study

Interconnection of Navajo-Gallup Water Supply Project Electrical Transmission Facilities. Non-Tariff System Impact Study Interconnection of Navajo-Gallup Water Supply Project Electrical Transmission Facilities Non-Tariff System Impact Study March 204 Prepared by: Utility System Efficiencies, Inc (USE) Under Contract with:

More information

TSR A & B - FACILITIES STUDY REPORT

TSR A & B - FACILITIES STUDY REPORT TSR-11-0502A & B - FACILITIES STUDY REPORT Transmission Service Request No. TSR-11-0502A&B 2 x 25 MW Wind Energy Generating Facilities From POI on Gladstone Walsenburg 230 kv Line to Ojo Substation 345

More information

SRP Ten Year Transmission Plan

SRP Ten Year Transmission Plan 2018 SRP Ten Year Transmission Plan 2018-2027 Prepared for the Arizona Corporation Commission January 2018 Docket No. E-00000D-17-0001 Page1 Page1 Table of Contents 1. Introduction... 1 2. Planning Organizations...

More information

About Georgia Transmission Corporation (GTC)

About Georgia Transmission Corporation (GTC) About Georgia Transmission Corporation (GTC) Transmission-only, not-for-profit cooperative Formed in March 1997 from the restructuring of Oglethorpe Power Corporation (OPC) GTC provides network transmission

More information

Interconnection Feasibility Study Report GIP-IR377-FEAS-R1

Interconnection Feasibility Study Report GIP-IR377-FEAS-R1 Interconnection Feasibility Study Report GIP-IR377-FEAS-R1 Generator Interconnection Request 377 40 MW Wind Generating Facility Renfrew, NS Mar. 6, 2012 Control Centre Operations Nova Scotia Power Inc.

More information

2016 Fall ITO Stakeholder Meeting. Topics in Operations

2016 Fall ITO Stakeholder Meeting. Topics in Operations 2016 Fall ITO Stakeholder Meeting Topics in Operations 11/17/2016 TOP-003-3 Requirement R1. Each Transmission Operator shall maintain a documented specification for the data necessary for it to perform

More information

The Narragansett Electric Company. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No Testimony of. Todd G. Kopoyan, P.E.

The Narragansett Electric Company. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No Testimony of. Todd G. Kopoyan, P.E. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No. 0 Testimony of Todd G. Kopoyan, P.E. February 0, 00 0 0 INTRODUCTION Q. Please state your name and business address. A. My name is

More information

1. Description of purpose/cause of hold/curtailment: Flowgate 6023 flow gate consists of the following elements.

1. Description of purpose/cause of hold/curtailment: Flowgate 6023 flow gate consists of the following elements. MISO Investigation Report on the NERC TLR Level 5 Event North Platte Stockville 115kV for the loss of the Gentleman Red Willow 345kV Flowgate 6023 August 22 nd / 23 rd, 2002 Report issued: September 3

More information

Planning for the Future

Planning for the Future Gas/Electric Partnership Conference Planning for the Future February 1, 2018 Entergy Texas, Inc. Entergy Texas, Inc. Staci Meyer Manager, Resource Planning Jeff Dicharry Manager, Transmission Planning

More information

Dominion Supplemental Projects

Dominion Supplemental Projects Dominion Supplemental Projects Transmission Expansion Advisory Committee October 11, 2018 Needs Need Number: DOM-2018-0017 Meeting Date: 10/11/2018 Process Stage: NEED Supplemental Project Driver: Customer

More information

Smart Distribution Technology

Smart Distribution Technology Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications

More information

Tim Lynch October 24, NYSEG/RGE 2013 Local Transmission Plan System Planning

Tim Lynch October 24, NYSEG/RGE 2013 Local Transmission Plan System Planning Tim Lynch October 24, 2013 NYSEG/RGE 2013 Local Transmission Plan System Planning New York State Electric & Gas (NYSEG) NYSEG serves 877,000 electricity customers across 20,000 square miles of upstate

More information

Supplemental Information

Supplemental Information Retirement of NPCC Directory# 3 Supplemental Information On April 1, 2015, NPCC Directory# 3 was retired upon the effective date of PRC-005-2 Protection System Maintenance which is subject to a 12 year

More information

MISO Investigation Report on the NERC TLR Level 5 Event Alliant Energy Flowgate 14266: Wisdom-Triboji 161kV flo Sherco #3 June 11, 2007

MISO Investigation Report on the NERC TLR Level 5 Event Alliant Energy Flowgate 14266: Wisdom-Triboji 161kV flo Sherco #3 June 11, 2007 MISO Investigation Report on the NERC TLR Level 5 Event Alliant Energy Flowgate 14266: Wisdom-Triboji 161kV flo Sherco #3 June 11, 2007 Report submitted to NERC on: July 12, 2007. This report is submitted

More information

Generation Interconnection Feasibility Study Report

Generation Interconnection Feasibility Study Report Project #169 Generation Interconnection Feasibility Study Report 7/2/2014 Regional Electric Transmission Planning TABLE OF CONTENTS Executive Summary... 3 Generator and Interconnection Data... 5 Study

More information

Blackstart Hardware-in-the-loop Relay Testing Platform

Blackstart Hardware-in-the-loop Relay Testing Platform 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Blackstart Hardware-in-the-loop Relay Testing Platform R. LIU R. SUN M. TANIA Washington

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

Opening. 2013/2014 Transmission Planning Process Stakeholder Meeting. Tom Cuccia Sr. Stakeholder Engagement and Policy Specialist November 20-21, 2013

Opening. 2013/2014 Transmission Planning Process Stakeholder Meeting. Tom Cuccia Sr. Stakeholder Engagement and Policy Specialist November 20-21, 2013 Opening 2013/2014 Transmission Planning Process Stakeholder Meeting Tom Cuccia Sr. Stakeholder Engagement and Policy Specialist November 20-21, 2013 Yesterday s Agenda November 20 th Topic Opening Introduction

More information

MISO-PJM Cross-Border Planning. February 19, 2014 MISO-PJM JCM

MISO-PJM Cross-Border Planning. February 19, 2014 MISO-PJM JCM MISO-PJM Cross-Border Planning February 19, 2014 MISO-PJM JCM Planning Issues at the Seam 2 Background JOA Historical and Projected Congestion Study - 2012 to 2014 Future Scenario based 80+ major project

More information

ITC Facility Connection Requirements for Generation, Transmission and End-User Facilities Connected to the ITC Holdings Transmission Systems

ITC Facility Connection Requirements for Generation, Transmission and End-User Facilities Connected to the ITC Holdings Transmission Systems ITC Facility Connection Requirements for Generation, Transmission and End-User Facilities Connected to the ITC Holdings Transmission Systems Category: Planning Type: Policy Eff. Date/Rev. # 06/19/2017

More information

(801) Spanish Fork Power. 860 East 4500 South Suite 312 Salt Lake City, UT 84107

(801) Spanish Fork Power. 860 East 4500 South Suite 312 Salt Lake City, UT 84107 (801) 288-4033 info@comlinkls.com Spanish Fork Power 860 East 4500 South Suite 312 Salt Lake City, UT 84107 S P A N I S H F O R K C I T Y Municipal Power Substation Siting & Capital Project Study October

More information

NERC Event Analysis Update Webinar. Hassan Hamdar Chair, Event Analysis Subcommittee October 20, 2016

NERC Event Analysis Update Webinar. Hassan Hamdar Chair, Event Analysis Subcommittee October 20, 2016 NERC Event Analysis Update Webinar Hassan Hamdar Chair, Event Analysis Subcommittee October 20, 2016 Webinar Agenda ERO Event Analysis Process Update Lesson Learned Presentation from Entity ERO Lessons

More information

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing

More information

ITC HOLDINGS, CORP. Edison Electric Institute 9

ITC HOLDINGS, CORP. Edison Electric Institute 9 ITC HOLDINGS, CORP. Company Background: ITC Holdings, Corp. is in the business of investing in electricity transmission infrastructure as a means to improve electric reliability, connect renewable energy

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

345kV Transmission Line Thermal Uprating Using Connector Shunts

345kV Transmission Line Thermal Uprating Using Connector Shunts 345kV Transmission Line Thermal Uprating Using Connector Shunts Douglas P. Harms, P.E. Sr. Consulting Engineer Transmission Engineering CenterPoint Energy (Ret.) Presented At The 46 th Annual Transmission

More information

PRC Coordination of Protection Systems for Performance During Faults

PRC Coordination of Protection Systems for Performance During Faults PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To

More information

INTERCONNECTION FACILITIES STUDY REPORT

INTERCONNECTION FACILITIES STUDY REPORT Interconnection Request No. TI-08-0312 INTERCONNECTION FACILITIES STUDY REPORT Prepared by Tri-State Generation and Transmission Association, Inc. 1 of 7 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES

More information

KEY. PPA has been approved (if required) and has Sanction

KEY. PPA has been approved (if required) and has Sanction KEY Status Description Project is under consideration as possible solution to a Concept need, but little or no analysis is available National Grid has internally detemined that the project is an appropriate

More information

XXXXX XXXX Wind Generation Project

XXXXX XXXX Wind Generation Project A subsidiary of Pinnacle West Capital Corporation XXXXX XXXX Wind Generation Project XXXX XXXXX XXXXXXX Co., Inc. Interconnection System Impact Study Final Report Prepared By Arizona Public Service Company

More information

Transmission Expansion Advisory Committee JCPL Supplemental Projects

Transmission Expansion Advisory Committee JCPL Supplemental Projects Transmission Expansion Advisory Committee JCPL Supplemental Projects April 11, 2019 Needs Stakeholders must submit any comments within 10 days of this meeting in order to provide time necessary to consider

More information

Requirements for Data for Power System Modeling and Analysis (MOD-032-1) Arizona Public Service Company

Requirements for Data for Power System Modeling and Analysis (MOD-032-1) Arizona Public Service Company Requirements for Data for Power System Modeling and Analysis (MOD-032-1) Arizona Public Service Company December 29, 2016 APS Requirements for Data for Power System Modeling and Analysis Table of Contents

More information

Washington City. September Capital Facilities Plan- Electrical

Washington City. September Capital Facilities Plan- Electrical Washington City Capital Facilities Plan- Electrical September 2007 Intermountain Consumer Professional Engineers, Inc. 1145 East South Union Avenue Midvale, Utah 84047 (801) 255-1111 TABLE OF CONTENTS

More information

Q44 Generation Interconnection

Q44 Generation Interconnection A subsidiary of Pinnacle West Capital Corporation Q44 Generation Interconnection Interconnection Facilities Study APS Contract No. 52129 By Arizona Public Service Company Transmission Planning August 19,

More information

2012 Grid Assessment Results CAISO Stakeholder Meeting September 26-27, 2012

2012 Grid Assessment Results CAISO Stakeholder Meeting September 26-27, 2012 2012 Grid Assessment Results CAISO Stakeholder Meeting September 26-27, 2012 2006 San Diego Gas & Electric Company. All copyright and trademark rights reserved. Agenda Introduction 2012 Grid Assessment

More information

REAL-TIME MONITORING DATA SPECIFICATION

REAL-TIME MONITORING DATA SPECIFICATION REAL-TIME MONITORING DATA SPECIFICATION Version 1 December 9, 2016 Revision History Version Date Reviewer Revisions 1 11/1/16 Mansion Hudson Initial document 1 Contents 1. DOCUMENT REVIEW... 3 2. DEFINITIONS...

More information

P. O. Box 52025, MS POB100 Phoenix, Arizona (602) Feb 9, 2018

P. O. Box 52025, MS POB100 Phoenix, Arizona (602) Feb 9, 2018 P. O. Box 52025, MS POB100 Phoenix, Arizona 85072-2025 (602) 236-8788 philip.augustin@srpnet.com Feb 9, 2018 Peter Mackin Chair, WECC Studies Subcommittee Utility System Efficiencies, Inc. Phone: (916)

More information

Interconnection and Transmission

Interconnection and Transmission Interconnection and Transmission Gary L. Brown, P.E. Director of Energy Development Gary@ZGlobal.biz 916-985-9461 Kevin Coffee Energy Management Committee Meeting Irvine, California August 26, 2015 Interconnection

More information

Cherrywood Circuit Breaker Incident - December 12, 2005

Cherrywood Circuit Breaker Incident - December 12, 2005 Public IESO_REP_0316 Cherrywood Circuit Breaker Incident - December 12, 2005 Public IESO_REP_0316 Document ID IESO_REP_0316 Document Name Cherrywood Circuit Breaker Incident - December 12, 2005 Issue Issue

More information

Generation, Transmission, and End User Facilities

Generation, Transmission, and End User Facilities Procedures for Interconnection of Generation, Transmission, and End User To the Grand River Dam Authority Transmission System Table of Contents GRDA/SPP Interaction... 3 Standards... 3 Generation... 3

More information

INTERCONNECTION FACILITIES STUDY REPORT

INTERCONNECTION FACILITIES STUDY REPORT INTERCONNECTION FACILITIES STUDY REPORT NORTHEAST WYOMING 250MW GENERATOR Prepared on Behalf of the Transmission Provider: Basin Electric Power Cooperative Transmission Black Hills Power Transmission December

More information

Order No Assessment of Protection System Single Points of Failure Based on the Section 1600 Data Request. September, 2015

Order No Assessment of Protection System Single Points of Failure Based on the Section 1600 Data Request. September, 2015 Order No. 754 Assessment of Protection System Single Points of Failure Based on the Section 1600 Data Request System Protection and Control Subcommittee (SPCS) and System Modeling and Analysis Subcommittee

More information

NERC Relay Loadability Standard Reliability Standards Webinar November 23, 2010

NERC Relay Loadability Standard Reliability Standards Webinar November 23, 2010 Transmission Relay Loadability FERC Order 733 Project 2010-1313 NERC Relay Loadability Standard Reliability Standards Webinar November 23, 2010 Project Overview 2 Standards Involved PRC-023-2 Transmission

More information

System Studies for American Transmission Co. s Benson Lake SVC Project

System Studies for American Transmission Co. s Benson Lake SVC Project Helping to keep the lights on, businesses running and communities strong System Studies for American Transmission Co. s Benson Lake SVC Project Adam Manty, Transmission Planning Engineer, ATC Outline Introduction

More information

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer ) Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original

More information

BESNet User Manual. Exception Request Preparation for Registered Entities. June 29, 2014 Version 1-2

BESNet User Manual. Exception Request Preparation for Registered Entities. June 29, 2014 Version 1-2 Table of Contents BESNet User Manual Exception Request Preparation for Registered Entities June 29, 2014 Version 1-2 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com

More information

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10, Sacramento Municipal Utility District SMUD May 10, 2010 1 SMUD Facts and Figures 900 Sq. Miles Service Area 585,500 Customers 1.4 million Area Population 10 Bulk Substations 473 Miles of Transmission Lines

More information

Memorandum. This memorandum requires Committee action.

Memorandum. This memorandum requires Committee action. California Independent System Operator Corporation Memorandum To: ISO Operations Committee From: Dariush Shirmohammadi, Director of Regional Transmission - South Armando Perez, VP, Planning & Infrastructure

More information

ENMAX Power Corporation

ENMAX Power Corporation Decision 22769-D01-2017 Transmission Lines 138-1.80L and 138-1.81L September 15, 2017 Alberta Utilities Commission Decision 22769-D01-2017 Transmission Lines 138-1.80L and 138-1.81L Proceeding 22769 Application

More information

SMALL GENERATING FACILITY PRE-APPLICATION REPORT REQUEST FORM

SMALL GENERATING FACILITY PRE-APPLICATION REPORT REQUEST FORM SMALL GENERATING FACILITY PRE-APPLICATION REPORT REQUEST FORM 1. Instructions By completing this request form, an Interconnection Customer may request a preapplication report from the NYISO regarding the

More information

Unofficial Comment Form 1st Draft of PRC-005-3: Protection System and Automatic Reclosing Maintenance (Project )

Unofficial Comment Form 1st Draft of PRC-005-3: Protection System and Automatic Reclosing Maintenance (Project ) Unofficial Comment Form 1st Draft of PRC-005-3: Protection System and Automatic Reclosing Maintenance (Project 2007-17.2) Please DO NOT use this form for submitting comments. Please use the electronic

More information

Appendix A Existing Surface Utilities

Appendix A Existing Surface Utilities Appendix A Existing Surface Utilities PRELIMINARY INFRASTRUCTURE STUDY PROPOSED DUSEL SITE GILES COUNTY, VIRGINIA Prepared for: Kimballton Deep Underground Science and Engineering Laboratory Kimballton

More information

NERC Transmission Availability Data System (TADS): Element Identifier Data Submission Addendum

NERC Transmission Availability Data System (TADS): Element Identifier Data Submission Addendum Transmission Availability Data System (TADS) Element Identifier Data Submission Addendum May 28, 2013 3353 Peachtree Road NE NERC Transmission Availability Data System (TADS): Element Identifier Data Submission

More information

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation Small Generator Interconnection Facilities Study Report Completed for ( Interconnection Customer ) Proposed Interconnection Pavant substation Original report dated February 17, 2016 Revised March 11, 2016

More information

TUCSON ELECTRIC POWER COMPANY TEN YEAR PLAN FOR YEARS

TUCSON ELECTRIC POWER COMPANY TEN YEAR PLAN FOR YEARS TEN YEAR PLAN FOR YEARS 2012-2021 SUBMITTED TO THE ARIZONA CORPORATION COMMISSION JANUARY 2012 DOCKET NO: E-00000D-11-0017 CONTENTS INTRODUCTION... 3 Tortolita 500/138kV Transformer T3... 13 Vail 345/138kV

More information

Year Assessment Preliminary Needs

Year Assessment Preliminary Needs 2018 10-Year Assessment Preliminary Needs Stakeholder and Customer Presentation March 1, 2018 Jeremy Voigt Purpose Key Study Assumptions Reminder Summarize Preliminary Changes to Needs Solicit Input on

More information

Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids

Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids Enrico Ragaini (ABB Low Voltage Products), Alexandre Oudalov (ABB Corporate Research), ISGT Europe 2012, Berlin Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids

More information

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Revised: July 12, 2013 Introduction The following information includes requests for clarification

More information

Public Service Company of New Mexico

Public Service Company of New Mexico Public Service Company of New Mexico Open Transmission Planning Meeting November 2, 2017 Albuquerque, NM INTRODUCTION Public Stakeholder Meeting Order 890 Objective to improve transparency and stakeholder

More information

Southern Company Smart Grid

Southern Company Smart Grid Southern Company Smart Grid Smart Grid Investment Grant Update July 25, 2011 Southern Company Southern Company is one of the nations largest generators of electricity Has 4.4 million retail customers across

More information

Southwest Power Pool Independent Coordinator of Transmission RELIABILITY PLAN for Entergy in the Southeastern Electric Reliability Council September

Southwest Power Pool Independent Coordinator of Transmission RELIABILITY PLAN for Entergy in the Southeastern Electric Reliability Council September Southwest Power Pool Independent Coordinator of Transmission RELIABILITY PLAN for Entergy in the Southeastern Electric Reliability Council September 23, 2009 TABLE OF CONTENTS INTRODUCTION A. RESPONSIBILITIES

More information

Memorandum. This memorandum requires Board action. EXECUTIVE SUMMARY

Memorandum. This memorandum requires Board action. EXECUTIVE SUMMARY California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Keith Casey, Vice President, Market & Infrastructure Development Date: May 21, 2014 Re: Decision on interconnection

More information

Transmission Register PTO Admin User Manual. Version 1.0

Transmission Register PTO Admin User Manual. Version 1.0 Transmission Register PTO Admin User Manual Version 1.0 Table of Contents 1. INTRODUCTION... 3 1.1. Purpose...3 1.2. Scope...3 1.3. Definitions...3 2. COMPONENTS HOMEPAGE... 6 2.1. Find Components...6

More information

XXXX. Bear Creek Hydro Generation Project. Interconnection Facilities Study

XXXX. Bear Creek Hydro Generation Project. Interconnection Facilities Study XXXX Bear Creek Hydro Generation Project Interconnection Facilities Study Report No. SPA 2005-33 August 2005 System Planning (Lower Mainland & Vancouver Island) British Columbia Transmission Corporation

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

Development trends in Substation Design

Development trends in Substation Design Development trends in Substation Design on behalf of SC B3 Hans-Erik Olovsson Convenor Activity Area 1 (AA1) «Substation concepts and development» hans-erik.olovsson@se.abb.com 1 Agenda Evolution of primary

More information

FINAL FACILITIES STUDY-NRG-PID195-BC2-U4

FINAL FACILITIES STUDY-NRG-PID195-BC2-U4 TRANSMISSION /SUBSTATION PROJECTS COMPANY: ENTERGY TRANSMISSION CUSTOMER: NRG-ENERGY EJO#: F4PPGS0315 FINAL FACILITIES STUDY-NRG-PID195-BC2-U4 FOR 230KV T-LINE INTERCONNECTION Revision: ICT Rev Issue Date

More information

N-1-1 Reactive Upgrades

N-1-1 Reactive Upgrades N-1-1 Reactive Upgrades Previous Analysis Discussed at November 2011 TEAC Voltage collapse for multiple 500 kv N-1-1 contingency pairs A number of reactive upgrade locations evaluated to determine a optimal

More information

Arizona Public Service Company Ten-Year Transmission System Plan Docket No. E-00000D

Arizona Public Service Company Ten-Year Transmission System Plan Docket No. E-00000D (.laps Lisa Malagon Leader Federal and State Compliance Mail Station 9704 PO Box 53999 Phoenix, Arizona 85072-3999 Tel 602-250- 5671 Elisa.Malagon@aps.com January 31, 2014 Docket Control Arizona Corporation

More information

HVDC in CSG Challenges and Solutions

HVDC in CSG Challenges and Solutions HVDC in CSG Challenges and Solutions LI, Licheng lilc@csg.cn LI, Peng lipeng@csg.cn China Southern Power Grid Co., Ltd June 2013 1 Outline I. Overview of CSG II. Overview of HVDC&UHVDC in CSG III. Challenges

More information

Critical Asset Identification Methodology. William E. McEvoy Northeast Utilities

Critical Asset Identification Methodology. William E. McEvoy Northeast Utilities Critical Asset Identification Methodology William E. McEvoy Northeast Utilities Disclaimer This NPCC TFIST workshop provides a forum for the presentation and discussion of member experience in the implementation

More information

Project Modifications to BAL Frequency Response and Frequency Bias Setting. Industry Webinar December 18, 2018

Project Modifications to BAL Frequency Response and Frequency Bias Setting. Industry Webinar December 18, 2018 Project 2017-01 Modifications to BAL-003-1.1 Frequency Response and Frequency Bias Setting Industry Webinar December 18, 2018 Administrative Items North American Electric Reliability Corporation (NERC)

More information

PacifiCorp Transmission Technical Workshop

PacifiCorp Transmission Technical Workshop PacifiCorp Transmission Technical Workshop RFP Attachment 20 February 22, 2012 Presented by PacifiCorp Transmission PacifiCorp Transmission Update Integrated Resource Plan Attachment 20 Point of Receipt

More information

WORKPAPERS TO PREPARED DIRECT TESTIMONY OF DAVID BUCZKOWSKI ON BEHALF OF SOUTHERN CALIFORNIA GAS COMPANY BEFORE THE PUBLIC UTILITIES

WORKPAPERS TO PREPARED DIRECT TESTIMONY OF DAVID BUCZKOWSKI ON BEHALF OF SOUTHERN CALIFORNIA GAS COMPANY BEFORE THE PUBLIC UTILITIES Application of SOUTHERN CALIFORNIA GAS ) COMPANY for authority to update its gas ) requirement and base rates ) effective January 1, 2019 (U 904-G) ) Application No. 17-10- Exhibit No.: (SCG-11-CWP) WORKPAPERS

More information

APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE:

APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE: APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE: New 240 kv Montana Alberta Tie Ltd. (MATL) Substation 120S and Reconfigure 240kV Transmission Line 923L AltaLink Management Ltd. 2611 3 rd

More information

System Impact Study for Power Supply 400 MW Import on the EAL BCHA Path

System Impact Study for Power Supply 400 MW Import on the EAL BCHA Path System Impact Study for Power Supply 400 MW Import on the EAL BCHA Path Report No: NPP2000-21 September 13, 2001 Network Performance Planning Department T&D Engineering Executive Summary BC Hydro Power

More information

Generator Interconnection Impact Study Report Pamlico County, NC 200 MW Wind Farm Queue #281

Generator Interconnection Impact Study Report Pamlico County, NC 200 MW Wind Farm Queue #281 Generator Interconnection Impact Study Report Pamlico County, NC 200 MW Wind Farm Queue #281 June 6, 2012, Inc. PURPOSE The purpose of this impact study is to assess the impacts of a wind farm interconnection

More information

Outage Management System Pilot Roll-out: Division User Manual

Outage Management System Pilot Roll-out: Division User Manual Outage Management System Pilot Roll-out: Division User Manual February 2017 Table of Contents 1. Outage Management System... 2 1.1. Overall Objective... 2 1.2. Outage Categories... 2 1.3. Division User

More information

Toronto Hydro-Electric System Limited EB Exhibit G1 Tab 1 Schedule 1 ORIGINAL Page 1 of 15 SMART GRID PLAN

Toronto Hydro-Electric System Limited EB Exhibit G1 Tab 1 Schedule 1 ORIGINAL Page 1 of 15 SMART GRID PLAN EB-00-0 Exhibit G Tab Schedule Page of 0 SMART GRID PLAN INTRODUCTION This Exhibit presents THESL s plans for development of the smart grid in keeping with the Green Energy and Green Economy Act, 00 (

More information

Unused Generation Capacity Study Scope. Informational Analysis

Unused Generation Capacity Study Scope. Informational Analysis Unused Generation Capacity Study Scope Informational Analysis MISO Jan 9, 2014 Table of Contents 1.0 Project Overview... 3 2.0 Scope of Work... 4 2.1 Phase 1 - Preliminary Analysis... 5 2.2 Phase 2 System

More information

Transmission Planning Attachment K Public Input Meeting

Transmission Planning Attachment K Public Input Meeting Transmission Planning Attachment K Public Input Meeting FERC Order 1000, 2018-19 Biennial Planning Cycle Quarter 2 Meeting June 14, 2018 PAGE 2 Agenda Pacific Time Topic Presenter 9:00 9:05 Greetings and

More information

ASPEN Software - Introduction

ASPEN Software - Introduction ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical

More information

WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1

WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1 WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1 A. Introduction 1. Title: Steady State and Dynamic Data Requirements 2. Number: MOD-(11 and 13)-WECC-CRT-1.1 3. Purpose: To establish the consistent data requirements

More information

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Automation in Large Urban Power Distribution System Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Need for Automation and Current trends Automation Systems and Functionality

More information

G. Larry Clark Principal Engineer Power Delivery Alabama Power Company, A Southern Company

G. Larry Clark Principal Engineer Power Delivery Alabama Power Company, A Southern Company 2014 IEEE PES T&D Conference & Exposition Chicago, IL April 15, 2014 Panel Session: Technologies for Advanced Volt/VAR Control Implementation Volt/VAR Control as Part of an Integrated Distribution Management

More information

Updates and Modifications to Report

Updates and Modifications to Report QUARTERLY COMPLIANCE REPORT (JANUARY 2017) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision

More information