Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011
|
|
- Emmeline Meryl Rose
- 6 years ago
- Views:
Transcription
1 Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011 James Hamilton, 2011/10/24 VP & Distinguished Engineer, Amazon Web Services web: mvdirona.com/jrh/work blog: perspectives.mvdirona.com
2 Agenda Quickening Pace Infrastructure Innovation Influence of Cloud computing Power Distribution Cooling & Building Designs Networking & Server Innovation Talk does not necessarily represent positions of current or past employers 2011/10/24 2
3 Pace of Innovation Datacenter pace of innovation increasing More innovation in last 5 years than previous 15 Driven by cloud services & extraordinary-scale internet applications like search Cost of infrastructure dominates service cost Not just a cost center High focus on infrastructure innovation Driving down cost Increasing aggregate reliability Reducing resource consumption footprint 2011/10/24 3
4 Perspective on Scaling Each day Amazon Web Services adds enough new capacity to support all of Amazon.com s global infrastructure through the company s first 5 years, when it was a $2.76B annual revenue enterprise 2011/10/24 4
5 Where Does the Money Go? Assumptions: Facility: ~$88M for 8MW critical power Servers: $1.45k each Commercial Power: ~$0.07/kWhr Power Usage Effectiveness: % 13% Monthly Costs 4% Servers 57% Networking Equipment Power Distribution & Cooling Power 8% Other Infrastructure 3yr server & 10 yr infrastructure amortization Observations: 31% costs functionally related to power (trending up while server costs down) Networking high at 8% of overall costs & 19% of total server cost (often more) From: /10/27 5
6 Agenda Quickening Pace Infrastructure Innovation Influence of Cloud computing Power Distribution Cooling & Building Designs Networking & Server Innovation 2011/10/24 6
7 208V Power Distribution High Voltage Utility Distribution ~11% lost in distribution.997*.94*.98*.98*.99 = 89% IT Load (servers, storage, Net, ) Generators UPS & Gen often on 480V 115kv Sub-station 13.2kv UPS: Rotary or Battery Transformers Transformers ~1% loss in switch gear & conductors 13.2kv 13.2kv 480V 0.3% loss 99.7% efficient 6% loss 94% efficient, ~97% available 2% loss 98% efficient 2% loss 98% efficient Note: Two more levels of power conversion at server 2011/10/27 7
8 Removing Power Conversions Remove final conversion prior to server 480VAC line-to-neutral yields 277VAC 400VAC line-to-neutral yields 230VAC Both good but later supports standard PSUs Another option is HVDC distribution 400DC an interesting option Improved efficiency but higher capital cost 2011/10/27 8
9 Power Distribution Efficiency Summary 2 more power conversions at servers 5. Power Supply: often under 80% at typical load 6. On board voltage regulators (VRMs or VRDs) Rules to minimize power distribution losses: Oversell power (more load than provisioned power) Avoid conversions (fewer & better) Increase efficiency of conversions High voltage as close to load as possible Size voltage regulators to load & use efficient parts High voltage direct current a small potential gain 2011/10/27 9
10 Agenda Quickening Pace Infrastructure Innovation Influence of Cloud computing Power Distribution Cooling & Building Designs Networking & Server Innovation 2011/10/
11 Cold Hot Blow down & Evaporative Loss at 8MW facility: ~200,000 gal/day Cooling Tower CWS Pump Mechanical Systems Heat Exchanger (Water-Side Economizer) A/C Condenser A/C Compressor Primary Pump A/C Evaporator 20% of total power Server fans 6 to 9W each Diluted Hot/Cold Mix leakage cold fans Overall Mechanical Losses ~22% Computer Room Air Handler Air Impeller 2011/10/
12 Hot Aisle Containment Intel Facebook Open Compute Intel WriteLine 2011/10/
13 ASHRAE 2008 Recommendations ASHRAE 2008 Allowable Class 1 ASHRAE 2008 Recommended Class F 59F-90F 2011/10/
14 ASHRAE 2011 Recommendations ASHRAE 2011 Allowable Class 1 89F-95F ASHRAE 2011 Recommended Class 1 81F 64-81F 59F-90F 2011/10/
15 Network Equipment Building Standard NEBS Telco Standard (~1970) ASHRAE 2011 Allowable Class 1 89F-95F ASHRAE 2011 Recommended Class 1 81F ASHRAE 2008 Allowable Class 1 ASHRAE 2008 Recommended Class F 59F-90F 2011/10/
16 Most Datacenters Still Run Cold Most datacenters run down in this range 89F-95F 81F ASHRAE 2008 Recommended Class 1 ~77F 64-81F 59F-90F 2011/10/
17 Air Cooling Component temps specs higher than historically hottest place on earth Al Aziziyah, Libya: 136F/58C (1922) Just a mechanical engineering problem More air or better mechanical designs Tradeoff: semi-conductor leakage & power to move more air vs cooling savings Currently available equipment temp limits: 40C/104F: CloudRack C2 & most net gear 35C/95F: Most of the server industry Memory: 3W - 20W Temp Spec: 85C-105C Hard Drives: 7W- 25W Temp Spec: 50C-60C Processors/Chipset: 40W - 200W I/O: 5W - 25W Thanks to Ty Schmitt& Giovanni Coglitore Temp Spec: 60C-70C Temp Spec: 50C-60C 2011/10/
18 Innovative Shell Designs Evaporative cooling only High pressure misting on right Damp media design below Full building ductless cooling Facebook Prineville above & below EcoCooling 2011/10/
19 Modular and Pre-fab DC Designs Microsoft ITPAC Fast & economic deployments Sub-1.2 PUE designs Air-side economized In some cases no mechanical cooling ISO standard shipping containers offered by Dell, HP, SGI, IBM, Amazon Perdix 2011/10/
20 Cooling Looking Forward River water or lake water cooling Google Belgium & Finland, Deepgreen Switzerland Not new: Toronto metro area cooling Water direct to the rack IBM idataplex Water direct to components Done before 80 s IBM S/ x & 3090 series Again when heat densities climb back to that level Direct on component spray cooling 2011/10/
21 Agenda Quickening Pace Infrastructure Innovation Influence of Cloud computing Power Distribution Cooling & Building Designs Networking & Server Innovation 2011/10/
22 Sea Change in Networking Current networks over-subscribed Forces workload placement restrictions Goal: all points in datacenter equidistant Mainframe model goes commodity Competition at each layer over vertical integ. Get onto networking on Moore s Law path ASIC port count growth at near constant cost Competition: Broadcom, Marvell, Fulcrum, 2011/10/
23 Software Defined Networking Metering Routing QOS Monitoring Network Operating System (Onix) Openflow Simple Packet Forwarding Hardware Nick McKeown Openflow Simple Packet Forwarding Hardware Openflow Simple Packet Forwarding Hardware Distributed control plane with central control Research examples: VL2, PortLand, & others Openflow Simple Packet Forwarding Hardware Onix/OpenFlow gaining industry support & traction quickly Openflow Simple Packet Forwarding Hardware 2011/10/
24 Server Innovation Removing all unnecessary cost & power Omit lid, Depop board, efficient components, 12V-only PSUs Form factor: fractional RU & multi-server modules Shared power supplies N supplies for M servers Run supplies at most efficient load Shared large back-of-rack fans Cell phone technology predicts future server generations Super high-density storage platforms Increasing server to disk ratio for cold storage Soon: ARM architecture, low power servers, multiple servers on board, proprietary net fabric 2011/10/
Internet Scale Infrastructure Innovation
Compute Summit Internet Scale Infrastructure Innovation Open Compute Summit 2011 James Hamilton VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog:
More informationCloud Computing Economies of Scale
Cloud Computing Economies of Scale AWS Executive Symposium 2010 James Hamilton, 2010/7/15 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog: perspectives.mvdirona.com
More informationCloud Computing Economics
Cloud Computing Economics Cloud for the Enterprise 2010 James Hamilton, 2010/11/11 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog: perspectives.mvdirona.com
More informationInfrastructure Innovation Opportunities Y Combinator 2013
Infrastructure Innovation Opportunities Y Combinator 2013 James Hamilton, 2013/1/22 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog: perspectives.mvdirona.com
More informationInternet Scale Storage
Internet Scale Storage SIGMOD 2011 James Hamilton, 2011/6/14 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog: perspectives.mvdirona.com Agenda Cloud
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationTechnology Changes in Data Centers
Technology Changes in Data Centers Mark Murrill Emerson Network Power TFI Conference, January 2014 Austin, TX 1 Agenda Market trends and impact on data center design Convergence around traditional telecom
More informationWhy Scale Matters & How the Cloud Really is Different
Why Scale Matters & How the Cloud Really is Different James Hamilton, AWS VP & Distinguished Engineer SPOT205: November 23, 2013 2013 Amazon.com, Inc. and its affiliates. All rights reserved. May not be
More informationTopics. CIT 470: Advanced Network and System Administration. Google DC in The Dalles. Google DC in The Dalles. Data Centers
CIT 470: Advanced Network and System Administration Data Centers Topics Data Center: A facility for housing a large amount of computer or communications equipment. 1. Racks 2. Power 3. PUE 4. Cooling 5.
More informationCompute Engineering Workshop March 9, 2015 San Jose
Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud
More informationE f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n
E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationData Center Trends and Challenges
Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to
More informationMicrosoft s Cloud. Delivering operational excellence in the cloud Infrastructure. Erik Jan van Vuuren Azure Lead Microsoft Netherlands
Microsoft s Cloud Delivering operational excellence in the cloud Infrastructure Erik Jan van Vuuren Azure Lead Microsoft Netherlands 4 Megatrends are driving a revolution 44% of users (350M people) access
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationGreen IT Project: The Business Case
Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationWarehouse-Scale Computers to Exploit Request-Level and Data-Level Parallelism
Warehouse-Scale Computers to Exploit Request-Level and Data-Level Parallelism The datacenter is the computer Luiz Andre Barroso, Google (2007) Outline Introduction to WSCs Programming Models and Workloads
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationCommunity Driven Innovation and Sustainability. Revolutionary IT Infrastructures
Community Driven Innovation and Sustainability. Revolutionary IT Infrastructures Why we do it? Hyper-scale environments are the breeding grounds for new technologies, business models and ideas. The business
More informationEvolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development
Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC Introduction
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationGreening Terremark Data Centers
Technical & Financial Analysis July 2010 Greening Terremark Data Centers Author: David Floyer Wikibon.org Executive Summary On the Wikibon blog is a picture story of the world s 10 largest data centers.
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationServer room guide helps energy managers reduce server consumption
Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,
More informationSession 6: Data Center Energy Management Strategies
Session 6: Data Center Energy Management Strategies Data Center Energy Use and Opportunities: Applying Best Practices to meet Executive Order Requirements Dale Sartor, PE Lawrence Berkeley National Laboratory
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationReduced and Alternative Energy for Cloud and Telephony Applications
Reduced and Alternative Energy for Cloud and Telephony Applications James Hughes, Fellow Cloud Computing www.huawei.com Agenda Energy usage in a Telco Trends and direction Energy usage in data centers
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationConstru January 15, 2013
Use of Modula ar Design and its Relation to Energy Performance and Constru uction Costs January 15, 2013 The data center designerr and user now have a very wide range of modular options available with
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationPackaging of New Servers - energy efficiency aspects-
Packaging of New Servers - energy efficiency aspects- Roger Schmidt, IBM Fellow Chief Engineer, Data Center Energy Efficiency Many slides provided by Ed Seminaro Chief Architect of HPC Power6 & 7 1 st
More informationJason Waxman General Manager High Density Compute Division Data Center Group
Jason Waxman General Manager High Density Compute Division Data Center Group Today 2015 More Users Only 25% of the world is Internet connected today 1 New technologies will connect over 1 billion additional
More informationΕΠΛ372 Παράλληλη Επεξεργάσια
ΕΠΛ372 Παράλληλη Επεξεργάσια Warehouse Scale Computing and Services Γιάννος Σαζεϊδης Εαρινό Εξάμηνο 2014 READING 1. Read Barroso The Datacenter as a Computer http://www.morganclaypool.com/doi/pdf/10.2200/s00193ed1v01y200905cac006?cookieset=1
More informationDATA CENTER COLOCATION BUILD VS. BUY
DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationLecture 7: Data Center Networks
Lecture 7: Data Center Networks CSE 222A: Computer Communication Networks Alex C. Snoeren Thanks: Nick Feamster Lecture 7 Overview Project discussion Data Centers overview Fat Tree paper discussion CSE
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More informationContinuity Insights Chicago: Evolving Data Center Trends & Design Standards. 19 June Jose Hernandez, 30+ years of design/build experience
Continuity Insights Chicago: Evolving Data Center Trends & Design Standards Technology Management, Inc. 1911 Rohlwing Rd., Suite E Rolling Meadows, IL 60008 847 394 8900 19 June 2013 www.tmiamerica.com
More informationGreen Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex
Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,
More informationZTE ZXCR Series DX In-Row Air Conditioning Product Description
ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase
More informationUCS M-Series + Citrix XenApp Optimizing high density XenApp deployment at Scale
In Collaboration with Intel UCS M-Series + Citrix XenApp Optimizing high density XenApp deployment at Scale Aniket Patankar UCS Product Manager May 2015 Cisco UCS - Powering Applications at Every Scale
More informationGreen IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies
Green IT Finding Practical Infrastructure Planning and Facilities Dan Francis dfrancis@ipf.msu.edu David Graff dsgraff@ipf.msu.edu William Lakos wjlakos@ipf.msu.edu 1 2 MSU Historical Energy Efficiency
More informationDriving Business Value through Enterprise Agreements and Partnering
Driving Business Value through Enterprise Agreements and Partnering Presented by Dwayne Presenter Kalma Name/s and Tyler Duncan Agenda Introductions The Partnership Team: ebay, Dell, and OSIsoft Background
More informationWater-Cooling and its Impact on Performance and TCO
Water-Cooling and its Impact on Performance and TCO Matthew T. Ziegler Director, HPC and AI WW BU System Strategy and Architecture mziegler@lenovo.com 2016 Lenovo Internal. All rights reserved. 1 Agenda
More informationInnovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation
Innovative Data Center Efficiency Techniques Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation 1 Alternate titles.. Crisis or opportunity? Never build a new data center! Improve
More informationTECHNOLOGIES CO., LTD.
A Fresh Look at HPC HUAWEI TECHNOLOGIES Francis Lam Director, Product Management www.huawei.com WORLD CLASS HPC SOLUTIONS TODAY 170+ Countries $74.8B 2016 Revenue 14.2% of Revenue in R&D 79,000 R&D Engineers
More informationCase study on Green Data Center. Reliance Jio Infocomm Limited
Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center
More informationGreen Computing and Sustainability
Green Computing and Sustainability Damien Lecarpentier (CSC) einfranet Workshop, Brussels, 15th April 2010 CSC Tieteen tietotekniikan keskus Oy CSC IT Center for Science Ltd. 1 Green Computing: a hot topic
More informationCSE 124: THE DATACENTER AS A COMPUTER. George Porter November 20 and 22, 2017
CSE 124: THE DATACENTER AS A COMPUTER George Porter November 20 and 22, 2017 ATTRIBUTION These slides are released under an Attribution-NonCommercial-ShareAlike 3.0 Unported (CC BY-NC-SA 3.0) Creative
More informationData Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology
Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationData Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations
Data Center Design and Energy Management Steve Knipple CTO / VP Engineering & Operations August 1, 2013 Agenda Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More informationIT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day
IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationDominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas
One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering
More information40,000 TRANSFORM INFRASTRUCTURE AT THE EDGE. Introduction. Exploring the edge. The digital universe is doubling every two years
TRANSFORM INFRASTRUCTURE AT THE EDGE Dell EMC enables robust, efficient edge computing virtually anywhere with micro Modular Data Centers Introduction Edge computing is becoming one of the biggest buzzwords
More informationPartner Introduction
P R E S E N T S Partner Introduction September 16, 2013 Today s Agenda The Market Opportunity The Cooling Capacity Factor (CCF) New service Benefits to Upsite Partners How to Sell Launch Plan & Support
More informationCS 61C: Great Ideas in Computer Architecture (Machine Structures) Lecture 17 Datacenters and Cloud Compu5ng
CS 61C: Great Ideas in Computer Architecture (Machine Structures) Lecture 17 Datacenters and Cloud Compu5ng Instructor: Dan Garcia h;p://inst.eecs.berkeley.edu/~cs61c/ 2/28/13 1 In the news Google disclosed
More informationPhil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical
E n g i n e e r i n g W o r k s h o p : A d v a n c e d C o o l i n g S o l v i n g t h e E n e r g y C h a l l e n g e t h r o u g h I n n o v a t i o n s i n D a t a C e n t e r C o o l i n g 3m.com/immersion
More informationCase Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services
Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services EMEA Roll-out 2 Main Mirror UK Swindon/Newbury area (15,000m 2 ) Germany Russelsheim(main)/
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends
ABB Automation & Power World: April 18-21, 2011 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing Trends May 10, 2011 Slide 1 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing
More informationInnovative Data Center Energy Efficiency Solutions
Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationRunning Your Data Center Under Ideal Temperature Conditions
TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationSTULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling
STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued
More informationThe End of Redundancy. Alan Wood Sun Microsystems May 8, 2009
The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationCharles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by:
Charles Nolan Director IT Infrastructure, UNSW Do more with less with your data centre A customer s perspective Brought to you by: Today s Enterprise Data Centre Doing more with less High Density Data
More information