1 Rolf Brink Founder/CEO
2 COPYRIGHT 2017 BY ASPERITAS Asperitas, Robertus Nurksweg 5, 2033AA Haarlem, The Netherlands Information in this document can be freely used and distributed for internal use only. Copying or re-distribution for commercial use is strictly prohibited without written permission from Asperitas. If you would like to use the original powerpoint version of this document, you can send an to: FOR MORE INFORMATION, FEEDBACK OR TO SUGGEST IMPROVEMENTS FOR THIS DOCUMENT, PLEASE SEND YOUR SUGGESTIONS OR INQUIRIES TO:
3 THE DATACENTRE OF THE FUTURE A DATACENTRE IS NOT ABOUT ICT, POWER, COOLING OR SECURITY. IT IS NOT EVEN ABOUT SCALE OR AVAILABILITY OF THESE SYSTEMS. IT IS ABOUT THE AVAILABILITY OF INFORMATION
4 THE CHALLENGES INCREASE IN INFORMATION FOOTPRINT DEMAND FOR HIGH DENSITY CLOUD CONSOLIDATION OF POWER DEMAND OVERLOADING OF OUTDATED POWER GRID GLOBAL NETWORK LOAD CREATING EXERGY
5 ENERGY FOOTPRINT OF INFORMATION FACILITIES Datacentres, Server rooms, Network hubs etc. Estimated 4% Global Electricity Production (25 PWh) 4% = 1 PWh Wh (10 15 )
6 EXPLANATION PREVIOUS SLIDE (ENERGY FOOTPRINT) There is no real data available which can substantiate any sort of claim to the percentage mentioned. It is a very rough estimate for a global scale. The fact that the information is unavailable, is part of the problem. You cannot solve the problem which cannot be identified. The only available source for a global figure is the European Commission where Neelie Kroes mentioned datacentres being responsible for 2% of the global electrical energy production and ICT in general being responsible for 8-10%. (2012)
7 GLOBAL PUE: APPROX. 1.7 UPS/Nobreak 2% Other 2% Global estimated PUE breakdown Cooling 37% ICT 59% Fans (20%) 10% Information (65%) 40% Power supply (15%) 9%
8 EXPLANATION PREVIOUS SLIDE (GLOBAL PUE ESTIMATE) There is no real data available which can substantiate any sort of claim to the percentages mentioned. Everything is a very rough estimate for a global scale. For both the Power supply and Fans percentages, the estimates are based on the following factors: Most datacentres (colo) have no control over the internal temperature management of the IT. Environmental temperatures in datacentres are usually too high for optimal power efficiency of IT. IT is in general greatly under-utilised (30% is already high in many cloud environments, corporate IT in colo is often worse) which creates a very high overhead for both the PSU and fans. Most cloud and corporate backoffice platforms are running on inefficient, cheap IT hardware which is driven by CAPEX as opposed to OPEX. Reason for this is that power consumption is not part of the IT budget. Virtually all high density cloud environments (5-10 kw/rack) are based on 1U servers. These are the least efficient when it comes to fan overhead.
9 ACTUAL INFORMATION EFFICIENCY Actual efficiency 1000 TWh total energy Actual cooling: 471 TWh Actual power loss: 112 TWh 112 TJ/s Other overhead: 17 TWh 17 TJ/s Energy for information: 400 TWh 400TJ/s Information 40% Cooling + IT fans 47% 1000 TWh/400TWh PUE equivalent: 2.5 Other 2% UPS+IT Power supply 11%
10 ENERGY TRANSFORMATION Global thermal energy production by Information J or 1.9 EJ (10 18 ) (529 TJ/s*3600): Energy for heat rejection EXERGY DESTRUCTION: Wh
11 WHAT IF INFORMATION FACILITIES COULD... EXCLUDE COOLING INSTALLATIONS REDUCE IT OVERHEAD BALANCE THE POWER GRID REDUCE THE DATA NETWORK LOAD BECOME ENERGY PRODUCERS
12 COOLING THE CLOUD 1 MW critical load, ΔT of 10 C Thermal production: 1MJ/s 1 C rise with air: 1005 J/kg C * kg/l = J/L/s 1MJ/s requires: J/(10 C *1.2 J) 83333L/s AIR
13 83333 L/s AIR VS WATER 1 MJ/s Water required for ΔT of 10 C 4187 J/kg C * 1 kg/l = 4187 J/L/s per 1 C 10 C with 1 MJ/s: 24 L/s Liquid can travel 200 TIMES THE DISTANCE with same thermal losses THE DATACENTER OF THE FUTURE: 6 L/s AND IS AN ENERGY PRODUCER...
14 EXPLANATION PREVIOUS SLIDES (WATER VS AIR) For simplicity, the identical ΔT is maintained for both approaches. After feedback from reviewers and the audience of Datacentre Transformation Manchester, the comparison was raised to 10 C Air will usually allow the ΔT to become higher than 10 C, although due to poor utilization, this is not always achieved. In CRAC water circuits, the ΔT is usually below 10 C.
15 THE WRONG QUESTION DON T ASK WHICH TECHNOLOGY TO USE CHOOSE BETWEEN AIR OR LIQUID THEN COMBINE LIQUID TECHNOLOGIES
16 TLC - IMMERSED COMPUTING 100% Removal of heat from the IT Highest IT efficiency by eliminated fans No air required Level of intelligence Management control and insight Automatic optimisation of the water circuit Optimised for high density cloud/hpc nodes Varying servers Flexible IT hardware Feed: C / 55 C Extreme / max ΔT 10 C
17 DLC - DIRECT-TO-CHIP LIQUID COOLING Removes heat from hottest parts of the IT Increased IT efficiency by reduced fan power Requires additional cooling (ILC) Level of intelligence Management control and insight Automatic optimisation of the water circuit Optimised for HPC racks with identical nodes Very high temperature chips High density computing Feed: C / max ΔT 15 C
18 ILC - (ACTIVE) REAR DOOR COOLING 100% Removal of heat from the IT Small IT efficiency by assisted circulation Acts as air handler in the room Level of intelligence Management control and insight Automatic optimisation of the water circuit Optimised for IT with limited liquid compatibility Storage Network Legacy systems and high maintenance servers Feed: C / 28 C Extreme / max ΔT 12 C
19 OPTIMISING LIQUID INFRASTRUCTURES TECHNOLOGY NORMAL INLET OUTLET CRAC (generic) 6-18 C C ILC (U-Systems) C C DLC (Asetek) C C TLC (Asperitas) C C TECHNOLOGY EXTREME INLET OUTLET CRAC (generic) 21 C 30 C ILC (U-Systems) 28 C 32 C DLC (Asetek) 45 C 65 C TLC (Asperitas) 55 C 65 C
20 INCREASING ΔT WITH TEMPERATURE CHAINING Serial implementation of the infrastructure 17 C CRAC Parallel ILC Parallel TLC & DLC paired TLC & DLC paired Facility output +5 C Output 22 C +6 C Output 28 C +16 C Output 44 C +16 C Output 60 C 60 C CREATE HIGH T 3-stage cooling for low water volume Down to 35 C, free-air Between C, adiabatic Below 28 C, chiller USABLE HEAT
21 TEMPERATURE CHAINING EXAMPLE Closed room 3-stage configuration ILC setup maintains air temperature Water volume decreased by 85% ΔT 6 C : 29.9 L/s ΔT 40 C : 4.5 L/s Cooling options Closed cooling circuit with pumps and coolers Closed cooling circuit with pumps and reuse behind Heat Exchanger Open cooling circuit with external water source supplied for reuse 120 kw ILC +6 C Facility input 20 C +6 C +5 C +8 C +7 C +2 C +5 C +7 C +5 C +9 C +8 C +4 C +6 C Stage 1 ILC 26 C +8 C +5 C +7 C +6 C +2 C +7 C +9 C +5 C +3 C +2 C +6 C +7 C 400 kw TLC 40 kw DLC +19 C Stage 2 DLC & TLC +5 C +6 C +6 C +7 C +6 C +6 C +6 C +6 C +7 C +4 C +3 C +6 C 45 C 160 kw TLC 60 kw DLC +15 C +7 C +10 C +7 C +9 C +17 C +12 C +14 C +16 C +7 C +8 C +6 C +7 C Stage 3 Optimised DLC&TLC Facility output 60 C
22 REUSE MICRO INFRASTRUCTURE Micro datacentre or server room Open water circuit Reusable requirement: 65 C Variable volume Feedback loop for constant temperature 51 C +7 C +7 C Variable temp Facility input 5-40 C Constant temp Facility output 65 C
23 TEMPERATURE CHAINING IMPACT L/s AIR VS WATER 1 MJ/s Water required for ΔT of 40 C 4187 J/kg C * 1 kg/l = 4187 J/L per 1 C 40 C with 1 MJ/s: 6 L/s
24 DATACENTRE DESIGN DESIGNED FOR AIR Cooling options: 100% Chillers 100% Free air/adiabatic + 100% Chillers (off) High volume, low T (5-20 C) Fluid handling Spacious high capacity air ducting Air filtration Hot/Cold aisle separation Information density (avg) 1,5 kw/m 2 Concrete floor + Raised floors Power UPS (IT only): 100% Gensets (facility): 100% DESIGNED FOR MIXED LIQUID Cooling options: External cold water supply by reuser 100% Free air/adiabatic + 5% chillers Low volume, high T (20+ C) Fluid handling Normal capacity water circuit Water quality management Minimal fresh-air ventilation Information density (mixed) 12 kw/m 2 Bare concrete floor Power (compared to air) UPS (IT only): 90% Gensets: 60%
25 SITE PLANNING AND QUALIFICATION Minimised energy footprint Minimised installations requirements Flexibility by minimal environmental impact FOCUS ON 24/7 HEAT CONSUMERS
26 REDEFINING THE LANDSCAPE Large facilities Core Datacentres On the edge of urban areas Distributed micro facilities Edge nodes Inside the urban area Energy balancing Distributed minimised power load Focus on heat reuse
27 DISTRIBUTED MICRO EDGE NODES kw EDGE ENERGY REUSE Spas, swimming pools (100% reuse) Hospitals, hotels with hot water loops (100% reuse) Urban fish/vegetable farms with aquaponics (100% reuse) District heating (100% reuse) Aquifers for heat storage (75% reuse) Water mains (29% reuse) Canals, lakes and sewage (exergy destruction) Edge of network, within urban areas IoT capture and processing Data caching (Netflix, Youtube, etc.) Localised cloud services (SaaS, Paas, IaaS) Minimised facilities External cooling input 24/7 energy rejection for reuse Geo redundant Tesla Powerpack for controlled failover District data hub
28 CORE DATACENTRES Industrial scale reuse infrastructures 100% 24/7 heat reuse Agriculture Spas Cooking, pressurising, sterilisation, bleaching Distillation, concentrating, drying or Kilning Chemical Large facilities No-break systems Limited cooling infrastructure 24/7 information availability Edge management Replicated Edge back-end Communication hub Exergy destruction Rivers/ocean Liquid-to-air rejection
29 EDGE MANAGEMENT Emerging platforms for decentralised cluster management Integration with energy and heat management CLOUD CUSTOMERS CLOUD DEMAND.ware HARDWARE INSTALLATION Q.RADS, O.MAR, AIC24 HEAT DEMAND CUSTOMERS COMPUTING JOBS COMPUTING RESULTS CLOUD DEMAND DISTRIBUTION MANAGEMENT FOR HEATING INFORMATION HARDWARE JOB SCHEDULING HEAT DEMAND COMPUTING JOBS COMPUTING RESULTS Free and green heat.rads
30 LIQUID INFORMATION FACILITIES Reduced or eliminated technical installations Cooling No-break Reduced build cost No raised floors Reduced space for fluid handling Increased, distributed power density Reduced m 2 Reduced operational cost Reduced maintenance on installations High IT density Higher specs IT hardware, also for cloud Reduced software cost
31 LIQUID IS COMING HOW TO PREPARE? Design for water (redundant) to IT Sufficient ability to distribute piping to whitespace Plan for reusable heat Plan for liquid way of work IT maintenance rooms for wet equipment Staff training for liquid management Proper supplies and tooling
32 WHAT NEEDS TO BE DONE? Focus on heat consumption without dependency Not with an invoice Free cooling guarantee UPS/Nobreak 2% Other 2% PUE inefficiency Government involvement Incentives Intermediate for (industrial) heat reuse Information footprint as part of district planning More (low grade) heating networks Cooling 37% ICT 59% Fans (20%) 10% Information (65%) 40% Power supply (15%) 9% Focus on TCO, not CAPEX PUE need for a new easy metric PUE figures are widely manipulated PUE discourages IT efficiency It needs to give insight in actual inefficiency FEAR OF WATER
33 THE DATACENTRE OF THE FUTURE? THE FUTURE IS NOW!
+31 88 96 000 00 www.asperitas.com ASPERITAS COMPANY Privately owned and funded Rolf Brink/Markus Mandemaker History Aecorsis BV founded in 2014 Modernising the marine industry Micro datacentre for marine
More informationIN COLLABORATION WITH
WHITEPAPER THE DATACENTRE OF THE FUTURE IN COLLABORATION WITH ROLF BRINK, CEO www.asperitas.com A DATACENTRE IS NOT ABOUT ICT, POWER, COOLING OR SECURITY. IT IS NOT EVEN ABOUT SCALE OR AVAILABILITY OF
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationHPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas
HPC/Advanced Cooling Track Advanced Cooling Optimising for immersion Rolf Brink/CEO/Asperitas Rolf.Brink@ocproject.net +31 88 96 000 00 www.asperitas.com IMMERSED COMPUTING : AIC24 100% Removal of heat
More informationResults of Study Comparing Liquid Cooling Methods
School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationWHITEPAPER IMMERSED COMPUTING ROLF BRINK, CEO.
WHITEPAPER IMMERSED COMPUTING ROLF BRINK, CEO www.asperitas.com IMMERSED COMPUTING BY ASPERITAS A concept driven by sustainability, efficiency and flexibility. Using the most efficient model for operating
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationCapacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.
Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment
More informationCOOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS
COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS Dr Jon Summers Scientific Leader in Data Centers Part-time Academic in Thermofluids at the
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More informationCase Study: Energy Systems Integration Facility (ESIF)
Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case
More informationOne Stop Cooling Solution. Ben Tam Business Development Manager
One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One
More informationINSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE
INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationServer room guide helps energy managers reduce server consumption
Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More informationHow much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)
How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationCase Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services
Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services EMEA Roll-out 2 Main Mirror UK Swindon/Newbury area (15,000m 2 ) Germany Russelsheim(main)/
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationDATA CENTER LIQUID COOLING
DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More informationWhite paper adaptive IT infrastructures
Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More informationHybrid Warm Water Direct Cooling Solution Implementation in CS300-LC
Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement
More informationYour data center s hidden source of revenue
WHITEPAPER Your data center s hidden source of revenue Harvesting heat from data centers with Low Speed Ventilation server coolers February 2016 Contents 1. Introduction...2 2. Challenges...3 3. Heat harvesting
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationSaving Energy with Free Cooling and How Well It Works
Saving Energy with Free Cooling and How Well It Works Brent Draney HPC Facility Integration Lead Data Center Efficiency Summit 2014-1 - NERSC is the primary computing facility for DOE Office of Science
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationCAS 2K13 Sept Jean-Pierre Panziera Chief Technology Director
CAS 2K13 Sept. 2013 Jean-Pierre Panziera Chief Technology Director 1 personal note 2 Complete solutions for Extreme Computing b ubullx ssupercomputer u p e r c o p u t e r suite s u e Production ready
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationRemote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products
Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationMaking the impossible data center a reality.
United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental
More informationTopics. CIT 470: Advanced Network and System Administration. Google DC in The Dalles. Google DC in The Dalles. Data Centers
CIT 470: Advanced Network and System Administration Data Centers Topics Data Center: A facility for housing a large amount of computer or communications equipment. 1. Racks 2. Power 3. PUE 4. Cooling 5.
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationProduct Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Product Guide Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. www.coolitsystems.com Phone: +1 403.235.4895 The Future of Data Center Cooling
More informationData Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology
Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If
More informationAlgorithms, System and Data Centre Optimisation for Energy Efficient HPC
2015-09-14 Algorithms, System and Data Centre Optimisation for Energy Efficient HPC Vincent Heuveline URZ Computing Centre of Heidelberg University EMCL Engineering Mathematics and Computing Lab 1 Energy
More informationCharles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by:
Charles Nolan Director IT Infrastructure, UNSW Do more with less with your data centre A customer s perspective Brought to you by: Today s Enterprise Data Centre Doing more with less High Density Data
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationEnergy Usage in Cloud Part2. Salih Safa BACANLI
Energy Usage in Cloud Part2 Salih Safa BACANLI Cooling Virtualization Energy Proportional System Conclusion Cooling After servers, the second largest consumer of power in a data center is the cooling system.(kava,
More informationPower Monitoring in the Data Centre
Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationIT COOLING DATA CENTER COOLING THE MILESTONE OF GREEN DATA CENTER COOLING TECHNOLOGY
IT COOLING DATA CENTER COOLING THE MILESTONE OF GREEN DATA CENTER COOLING TECHNOLOGY IT COOLING RC for IT COOLING RC approach for perfect data center cooling THE FUTURE OF DATA CENTERS BRINGS BOTH ADVANCED
More information