1 Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014
2 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data centers recommended 70-90F inlet temp range Feb 2010: DOE Best Practices Guide for Energy- Efficient Data Center Design recommended 80.6F June 2011: Dell report on temperature sweet spot was 75-80F Typical server fans consume 8W at low speed and only 16W at high speed Low speed at 78F or below; high speed at 95F (35C) Intel suggests that most air-cooled platforms are designed to work at 35C inlet
3 Concerns with Higher Temperature Equipment failure rate increases with inlet temperature HDDs and fans have highest failure rates due to higher temps Degraded disc drive throughput due to vibration from fans IT equipment fans speed up and get noisy redundancy of drives and SSDs can reduce
4 Higher Densities Force Higher Inlet Temps Power trends in Watts/ft2 of Equipment (ASHRAE)
5 Benefits of Higher Supply Temperature Higher Delta T = higher cooling system efficiency and Capacity Reduced cooling system CapEx Reduced cooling system energy use can lower utility usage and demand charges Higher power densities reduce cooling redundancy and will force higher supply air temps using lower density cooling systems, so get used to it!
6
7 It s All Energy, so Focus is on Optimization With each 1F degree rise in supply air temps reduces HVAC energy by 2-3% Server fans = 1-4% and up to 15% of server load Typical mechanical loads are 25% of total data center electrical load Server fan speeds typically speed up at 78F If server leakage current rises at 38+C/100F, than maintain that, with 3-5C efficiency of heat exchange, that s still 90-95F inlet supply temp
8
9 Additional Way to Efficiency in Google Data Centers Economization: Water towers, outside air and water sources for cooling Servers use minimum amount of fan power Components designed to operate efficiently from idle to full capacity or usage Result: Data center fleet average PUE reduced from ~1.22 (2008) to 1.12 (Q2 2014)
10
11 Facebook Data Centers Initial Operating ranges: 18 C to 27 C and 65% max RH Revised Maximum Operating ranges: 29 C & 90% RH (depending upon location) Current design standard is to provide 85F supply for people comfort even though servers can handle 95F Result: Prineville full load PUE 1.07
12
13
14 Dell Study on Composite Server Power to Temperature
15 Dell Comparison of IT & Cooling Power
16 Total Power with IT Equipment circa 2007
17 Hardware Continues to Increase Inlet Temp Ideal range was with circa 2007 IT equipment It appears that improved server thermal design may have shifted the sweet spot to just above 80F (27C) For economized cooling systems, the ideal temp would happen somewhere above 100F (38C) There really is not a sweet-spot temperature while economizing; just follow the ambient to the temperature your are comfortable with.
18 Why Add a Compressor Cooling System? At 27C, majority of data center locations would be economizing 90% of the time, so why add a cooling system for only 10% of the time? Trade off is $100/MW of IT load in energy vs $1,500 MW in CapEx of cooling system
19 Examples of CapEx Savings Case PUE Supply Air Supply Water Energy Costs Chiller Size First Time Cost C F C F ($0.05 / kwh) tons Chiller+Generator A: Air Cooled $2,350,000 2,250 $4,500,000 B: Air Cooled $2,320, C: Water Cooled 1.15 n/a n/a 8 46 $2,270,000 2,250 $4,500,000 D: Water Cooled 1.11 n/a n/a $2,180, E: CRAY Units $2,530,000 2,250 $4,500,000
20 Example of exhaust temperature rise
21 Hardware Supports Higher Temperatures Hardware manufactures balance higher CapEx with larger heat sinks and fans vs higher OpEx with higher fan horsepower Most manufacturers have settled at about 77F/25C as the balance point Hardware of today is better designed to for Temp ranges and higher supply air temps Most manufacturers support 35C or greater
22 Maximum temperature rating benchmarking survey results (ASHRAE)
23 Intel Data Center in a Box 900 servers 10 month test Servers operating at 90% utilization 1,000 SF trailer in Santa Fe, New Mexico ½ - Standard DX Cooling ½ - Outside air up to 90F No humidity control Low quality residential air filter RH Varied 4% to 90% Servers covered in a layer of dust Air-economized trailer = 74% reduction in cooling Air-side economizers 91 percent of the time Savings $2.87 million on cooling energy for a 10MW datacenter
24 Microsoft Data Center in a Tent Inside the tent, five HP DL585s (already past useful life) ran from Nov 2007 to June 2008 Results: Water dripped onto the rack and the server A windstorm blew a section of fence onto the rack An itinerant leaf was sucked onto the server fascia ZERO failures and 100% uptime
25 Focus on The Correct Goal ASHRAE is not server manufacturers ASHRAE creates guidelines, not hard rules Run your data center to provide your IT needs at the lowest TCO Above air inlet temperature 23 C, the speed of the air moving device increases in speed to maintain fairly constant component temperatures and in this case inlet temperature changes have little- tono effect on component temperatures and thereby no affect on reliability since component temperatures are not affected by ambient temperature changes. ASHRAE
26 Goals Minimize OpEx: Server load + mechanical load + accelerated hardware replacements due to thermal failures Lower CapEx by reducing cooling system costs Design to meet conditions with lowest TCO (OpEx and CapEx) Maintain satisfactory acoustic limits Maintain satisfactory hardware failure rates Reduce disc drive throughput degradation
27 Optimize Supply Temperatures What is ideal temp range that reduces TCO: CapEx and OpEx Balance IT and infrastructure loads for lowest power load Turn off chillers and run on water econ or air econ Have no compression-based chilling at all avoid CapEx Reduce compressor-based cooling can reduce vibration and thus extend hardware life and disc through-put
28 Solutions Throttle down or turn off hardware when temps are warm The probability of failure of redundant data centers simultaneous with one throttled down is very low Use carbon racks instead of metal to reduce vibration Run inlet supply temps at or just below server fanspeed threshold most of the time Determine time over threshold and calculate TCO and IT capacity at higher temps and design for optimum
29 Solutions Monitor, evaluate, calculate, optimize and repeat continuously and autonomously Ambient conditions, workloads and IT hardware are all dynamic Remove either the server fans or the data center fans Servers have more fan horsepower than needed Reduce vibration by locating AC systems outside of IT rooms and use lower power draw and lower fan speed systems Adjust air supply temps to keep fan speeds and cooling systems running at optimum efficiency
30 KC Mares #KCMares Thank you
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationCase study on Green Data Center. Reliance Jio Infocomm Limited
Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center
More informationThe End of Redundancy. Alan Wood Sun Microsystems May 8, 2009
The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands
More informationEnergy Efficiency and CHP Opportunities for Data Centers
Energy Efficiency and CHP Opportunities for Data Centers Webinar #2: Understanding Energy Efficiency Concepts and Technologies for Data Centers The 2nd in a 4-Part Series of Educational Webinars Targeting
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationInternet Scale Infrastructure Innovation
Compute Summit Internet Scale Infrastructure Innovation Open Compute Summit 2011 James Hamilton VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog:
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationDATA CENTER LIQUID COOLING
DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid
More informationCRAH Retrofit and Energy Savings Project
CRAH Retrofit and Energy Savings Project Danny Johnson Director, Technical Operations Silicon Valley Leadership Group - Data Center Efficiency Summit October 24, 2012 2260 E. El Segundo Boulevard - A Digital
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More informationWhy would you want to use outdoor air for data center cooling?
Dell Fresh Air 2.0: Frequently Asked Questions Achieve improved data center efficiency and powerful enterprise performance you have come to expect from Dell, by deploying Dell Fresh Air hardware. Competitively
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationCase Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services
Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services EMEA Roll-out 2 Main Mirror UK Swindon/Newbury area (15,000m 2 ) Germany Russelsheim(main)/
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationUC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012
UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A 004 11 JUNE 2012 TABLE OF CONTENTS Abstract...3 Introduction...3 Methodology...4
More informationData Center Trends and Challenges
Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to
More informationInternet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011
Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011 James Hamilton, 2011/10/24 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationGreen IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies
Green IT Finding Practical Infrastructure Planning and Facilities Dan Francis dfrancis@ipf.msu.edu David Graff dsgraff@ipf.msu.edu William Lakos wjlakos@ipf.msu.edu 1 2 MSU Historical Energy Efficiency
More informationHybrid Warm Water Direct Cooling Solution Implementation in CS300-LC
Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationCase Study: Energy Systems Integration Facility (ESIF)
Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case
More informationWater-Cooling and its Impact on Performance and TCO
Water-Cooling and its Impact on Performance and TCO Matthew T. Ziegler Director, HPC and AI WW BU System Strategy and Architecture mziegler@lenovo.com 2016 Lenovo Internal. All rights reserved. 1 Agenda
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationHow Intel Technologies & High Temperature Data Centers saves Energy and Money.
Intel Intelligent Power Management Intel How Intel Technologies & High Temperature Data Centers saves Energy and Money. Power Thermal savings through the use of Intel s Intelligent Power Management in
More informationWhat s New for Data Centers in Title Jeff Stein, PE Taylor Engineering
What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationCase study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence
Case study: Energy efficiency improvements in a legacy data centre Robert Tozer Director Opera>onal Intelligence Objec>ves First improve air management Air supply temperature to servers Lower temperature
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationChiller Replacement and System Strategy. Colin Berry Account Manager
Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit
More informationΕΠΛ372 Παράλληλη Επεξεργάσια
ΕΠΛ372 Παράλληλη Επεξεργάσια Warehouse Scale Computing and Services Γιάννος Σαζεϊδης Εαρινό Εξάμηνο 2014 READING 1. Read Barroso The Datacenter as a Computer http://www.morganclaypool.com/doi/pdf/10.2200/s00193ed1v01y200905cac006?cookieset=1
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationData centers control: challenges and opportunities
1 Data centers control: challenges and opportunities Damiano Varagnolo Luleå University of Technology Aug. 24th, 2015 First part: what is a datacenter and what is its importance in our society Data centers
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationWhite paper adaptive IT infrastructures
Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:
More informationCapacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.
Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationAPC APPLICATION NOTE #114
APPLICATION NOT #4 Using the Rack Air Containment System with the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC00 and ACSC0) is a self-contained air conditioner for server
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationHow High-Density Colocation and Enhanced Visibility Improve Business Performance
How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications
More informationData Center Energy and Cost Saving Evaluation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.
More informationSIFMA Technology Management Conference. Data Center Efficiency
SIFMA Technology Management Conference June 20, 2007 Data Center Efficiency Presented by Julius Neudorfer In deciding how to best implement a strategy for supporting critical data systems, Data Center
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationDCIM Data Center Infrastructure Management
DCIM Data Center Infrastructure Management Part 2 Implementation Challenges & Strategic Advantages - Predictive Analysis August 8, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Implementation
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationFCU (FREE COOLING UNIT)
FCU (FREE COOLING UNIT) FCU reduces the AC running hours on the telecom site Controller Features: Can control upto two AC and one free cooling unit Temperature control Humidity sensor Structural Features:
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationOperation Guide CT100
Operation Guide CT100 PG 1 The CT100 communicating Z-Wave thermostat operates via a high-quality, easy-to-use touch screen. To set or adjust your CT100, simply touch your finger firmly to the screen. The
More informationTopics. CIT 470: Advanced Network and System Administration. Google DC in The Dalles. Google DC in The Dalles. Data Centers
CIT 470: Advanced Network and System Administration Data Centers Topics Data Center: A facility for housing a large amount of computer or communications equipment. 1. Racks 2. Power 3. PUE 4. Cooling 5.
More informationMaking the impossible data center a reality.
United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationCOST EFFICIENCY VS ENERGY EFFICIENCY. Anna Lepak Universität Hamburg Seminar: Energy-Efficient Programming Wintersemester 2014/2015
COST EFFICIENCY VS ENERGY EFFICIENCY Anna Lepak Universität Hamburg Seminar: Energy-Efficient Programming Wintersemester 2014/2015 TOPIC! Cost Efficiency vs Energy Efficiency! How much money do we have
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationHow much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)
How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationLiebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers
Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to
More informationData Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology
Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If
More informationDominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas
One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering
More information