1 95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial Building Standard for Telecommunications Pathways and Spaces. The purpose of the ANSI/TIA/EIA-569-A Standard is to provide a flexible and standardized support system for a structured cabling system, along with the detail necessary to design and build these facilities. The detail pertains to both single and multitenant buildings. NOTE This 569-A document is especially important because network managers, architects, and even cable installers often don t give enough forethought to the spaces and infrastructure that will support structured-cabling systems or data-communications equipment.

2 96 Chapter 2 Cabling Specifications and Standards Though repetitive to large degree with respect to ANSI/TIA/EIA-568-B, ANSI/TIA/EIA- 569-A does define and detail pathways and spaces used by a commercial cabling system. The elements defined include: Entrance facility Equipment room Main terminal space Telecommunications rooms Horizontal pathways Backbone pathways Work areas WARNING When planning telecommunications pathways and spaces, make sure you allow for future growth. ANSI/TIA/EIA-569-A provides some common design considerations for the entrance facility, equipment room, and telecommunications rooms with respect to construction, environmental considerations, and environmental controls: The door (without sill) should open outward, slide sideways, or be removable. It should be fitted with a lock and be a minimum of 36 inches (.91 meters) wide by 80 inches (2 meters) high. Electrical power should be supplied by a minimum of two dedicated 120V-20A nominal, nonswitched, AC-duplex electrical outlets. Each outlet should be on separate branch circuits. The equipment room may have additional electrical requirements based on the telecommunications equipment that will be supported there (such as LAN servers, hubs, PBXs, or UPS systems). Sufficient lighting should be provided (500 lx or 50-foot candles). The light switches should be located near the entrance door. Grounding should be provided and used per ANSI/TIA/EIA-607 (the Commercial Building Grounding and Bonding Requirements for Telecommunications Standard) and either the NEC or local code, whichever takes precedence. These areas should not have false (drop) ceilings. Slots and sleeves that penetrate firewalls or that are used for riser cables should be firestopped per the applicable codes.

3 97 Separation of horizontal and backbone pathways from sources of electromagnetic interference (EMI) must be maintained per NEC Article Metallic raceways and conduits should be grounded. Based on our own experiences, we recommend the following: Equip all telecommunications rooms, the entrance facility, and the equipment room with electrical surge suppression and a UPS (uninterruptible power supply) that will supply that area with at least 15 minutes of standby AC power in the event of a commercial power failure. Equip these areas with standby lighting that will last for at least an hour if the commercial power fails. Make sure that these areas are sufficiently separated from sources of EMI such as antennas, medical equipment, elevators, motors, and generators. Keep a flashlight or chargeable light in an easy-to-find place in each of these areas in case the commercial power fails and the battery-operated lights run down. NOTE For full information, consult the ANSI/TIA/EIA-569-A Standard, which may be purchased through Global Engineering Documents on the Web at Entrance Facility The location of the entrance facility is usually either on the first floor or in the basement of a building and must take into consideration the requirements of the telecommunications services required and other utilities (such as CATV, water, and electrical power). ANSI/TIA/EIA-569-A specifies the following design considerations for an entrance facility: When security, continuity, or other needs dictate, an alternate entrance facility may need to be provided. One wall at a minimum should have 3 /4-inch (20 mm) A-C plywood. It should be a dry area not subject to flooding. It should be as close to the actual entrance pathways (where the cables enter the building) as possible. Equipment not relating to the support of the entrance facility should not be installed there. WARNING The entrance facility should not double as a storage room or janitor s closet.

4 98 Chapter 2 Cabling Specifications and Standards Work: Bad Equipment-Room Design One company we are familiar with spent nearly a million dollars designing and building a hightech equipment room, complete with raised floors, cabling facilities, power conditioning, backup power, and HVAC. The room was designed to be a showcase for its voice and computer systems. On the delivery day, much of the HVAC equipment could not be moved into the room because of lack of clearance in the outside hallway. Several walls had to be torn out (including the wall of an adjacent tenant) to move the equipment into the room. Another company located its equipment room in a space that used to be part of a telecommunications room. The space had core holes drilled to the floor above, but the holes had not been filled in after the previous tenant vacated. The company installed its computer equipment but did not have the core holes filled. A few months later, a new tenant on the second floor had a contractor fill the holes. The contractor s workers poured nearly a ton of concrete down the core and on top of the computer equipment in the room below before someone realized the hole was not filling up. Many organizations have experienced the pain of flooding from above. One company s computer room was directly below bathrooms. An overflowing toilet caused hundreds of gallons of water to spill down into the computer room. Don t let this kind of disaster occur in your equipment rooms! Main-Terminal Space The main-terminal space is a facility that is commonly a shared space in a multitenant building. The main cross-connects are in this room. This room is generally a combination of an equipment room and a telecommunications room, though the TIA/EIA specifies that the design for a main-terminal space should follow the design considerations laid out for an equipment room. Customer equipment may or may not be located here. However, our opinion is that it is not desirable to locate your own equipment in a room shared with other tenants. One reason is that you may have to get permission from the building manager to gain access to this facility. Equipment Room Considerations to think about when designing an equipment room include the following: Environmental controls must be present to provide HVAC at all times. A temperature range of degrees Fahrenheit (or degrees Celsius) should be maintained, along with percent relative humidity. An air-filtering system should be installed to protect against pollution and contaminants such as dust. Seismic and vibration precautions should be taken. The ceiling should be at least 8.0 feet (2.4 meters) high.

5 99 A double door is recommended. (See also door design considerations at the beginning of section ANSI/TIA/EIA-569-A. ) The entrance area to the equipment room should be large enough to allow delivery of large equipment. The room should be above water level to minimize danger of flooding. The backbone pathways should terminate in the equipment room. In a smaller building, the entrance facility and equipment room may be combined into a single room. Telecommunications Rooms Here are some design considerations for telecommunications rooms, suggested by the ANSI/ TIA/EIA-569-A: Each floor of a building should have at least one telecommunications room, depending on the distance to the work areas. The rooms should be close enough to the areas being served so that the horizontal cable does not exceed a maximum of 90 meters (as specified by the ANSI/TIA/EIA-568-B Standard). Environmental controls are required to maintain a temperature that is the same as adjacent office areas. Positive pressure should be maintained in the telecommunications rooms, with a minimum of one air change per hour (or per local code). Ideally, closets should stack on top of one another in a multifloor building. Then, backbone cabling (sometimes called vertical or riser cable) between the closets merely goes straight up or down. Two walls of the telecommunications room must have 3 /4-inch (20 mm) A-C plywood mounted on the walls, and the plywood should be 8.0 feet (2.4 meters) high. Vibration and seismic requirements should be taken into consideration for the room and equipment installed there. Two closets on the same floor must be interconnected with a minimum of one 78(3) tradesize conduit or equivalent pathway. The 78(3) trade-size conduit has a sleeve size of 78 mm or 3 inches. Horizontal Pathways The horizontal pathways are the paths that horizontal cable takes between the wiring closet and the work area. The most common place in which horizontal cable is routed is in the space between the structural ceiling and the false (or drop) ceiling. Hanging devices such as J hooks should be secured to the structural ceiling to hold the cable. The cable should be supported at

6 100 Chapter 2 Cabling Specifications and Standards intervals not greater than 60 inches. For long runs, this interval should be varied slightly so that structural harmonics (regular physical anomalies that may coincide with transmission frequency intervals) are not created in the cable, which could affect transmission performance. Shake, Rattle, and Roll A company that Jim worked for was using metal racks and shelving in the equipment rooms and telecommunications rooms. The metal racks were not bolted to the floors or supported from the ceiling. During the 1989 San Francisco earthquake, these racks all collapsed forward, taking with them hubs, LAN servers, tape units, UPSes, and disk subsystems. Had the racks been secured to the wall and ceilings, some or all of the equipment would have been saved. If you live in an area prone to earthquakes, be sure to take seismic precautions. NOTE Cable installers often install cable directly on the upper portion of false ceiling. This is a poor installation practice because cable could then also be draped across fluorescent lights, power conduits, and air-conditioning ducts. In addition, the weight of cables could collapse the false ceiling. Some local codes may not permit communications cable to be installed without conduit, hangers, trays, or some other type of pathway. WARNING In buildings where the ceiling space is also used as part of the environmental air-handling system (i.e., as an air return), plenum-rated cable must be installed in accordance with Article 800 of the NEC. Other common types of horizontal pathways include conduit and trays (or wireways). Trays are metal or plastic structures that the cable is laid into when it is installed. The trays can be rigid or flexible. Conduit can be metal or plastic tubing and is usually rigid but can also be flexible (in the case of fiber-optic cable, the flexible tubing is sometimes called inner duct). Both conduit and trays are designed to keep the cable from resting on top of the false ceiling or being exposed if the ceiling is open. Other types of horizontal pathways include the following: Access floor, which is found in raised-floor computer rooms. The floor tile rests on pedestals, and each tile can be removed with a special tool. Some manufacturers make cablemanagement systems that can be used in conjunction with access floors. Under floor or trenches, which are in concrete floors. They are usually covered with metal and can be accessed by pulling the metal covers off.

7 101 Perimeter pathways, which are usually made of plastic or metal and are designed to mount on walls, floors, or ceilings. A pathway contains one or more cables. Many vendors make pathway equipment (see Chapter 5 for more information). When designing or installing horizontal pathways, keep the following considerations in mind: Horizontal pathways are not allowed in elevator shafts. Make sure that the pathways will support the weight of the cable you plan to run and that they meet seismic requirements. Horizontal pathways should be grounded. Horizontal pathways should not be routed through areas that may collect moisture. KEY TERM drawstring A drawstring is a small nylon cord inserted into a conduit when the conduit is installed; it assists with pulling cable through. Larger conduits will have multiple drawstrings.

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site preparation guide This guide is designed to assist local on-site contacts to understand what you will need to accomplish in preparation

More information

Network+ Guide to Networks 7 th Edition

Network+ Guide to Networks 7 th Edition Network+ Guide to Networks 7 th Edition Chapter 4 Structured Cabling and Networking Elements 2016 Cengage Learning. May not be scanned, copied or duplicated, or posted to a publicly accessible website,

More information

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site Preparation Guide 2017 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered

More information

Newark, Delaware Architectural Engineering Senior Thesis Portfolio

Newark, Delaware Architectural Engineering Senior Thesis Portfolio Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should

More information

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide This guide is designed to assist local on-site contacts to understand what you will need to

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before

More information

Cabling a Data Center to TIA-942 Standard

Cabling a Data Center to TIA-942 Standard Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T

More information

Los Angeles Community College District Design Standards

Los Angeles Community College District Design Standards LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure

More information

Wire Communications Design jfm 07. An Inside Look at Outside Plant

Wire Communications Design jfm 07. An Inside Look at Outside Plant An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure

More information

f) Telecommunications Equipment Rooms

f) Telecommunications Equipment Rooms SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines

SYSTIMAX GigaSPEED Xpress Solution Design Guidelines Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien

More information

SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS

SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS CONTENTS PAGE 1. GENERAL... 5-1 1.1. Introduction... 5-1 1.2. Equipment Layout Requirements... 5-1 2. EQUIPMENT FRAMES... 5-2 2.1. Introduction...

More information

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6 Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12

More information

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology

More information

Communications. UNM IT/Telecommunications Guide Specification Communications

Communications. UNM IT/Telecommunications Guide Specification Communications The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary

More information

Tier IV Standards as Specified in the TIA 942 Document

Tier IV Standards as Specified in the TIA 942 Document S No Architectural Proximity of visitor parking to data 18.3 m / 60 ft minimum separation with physical barriers to prevent vehicles from 1 center perimeter building walls driving closer 2 Building Construction

More information

TIA/EIA 568A Sub-system HORIZONTAL CABLING

TIA/EIA 568A Sub-system HORIZONTAL CABLING TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,

More information

AT&T Switched Ethernet Service SM

AT&T Switched Ethernet Service SM Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a

More information

Data Center Design and the ANSI/TIA-942 Standard

Data Center Design and the ANSI/TIA-942 Standard Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications

More information

Telecommunications Structured Cabling Systems

Telecommunications Structured Cabling Systems Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major

More information

2 Telecommunications Data Center Facility Requirements

2 Telecommunications Data Center Facility Requirements Generic Requirements for Telecommunications Data Center Equipment and Spaces GR-3160-CORE Table of Contents Table of Contents Generic Requirements Notice of Disclaimer..................... iii Preface...........................................

More information

Element Z General Design Requirements Owner Standards and Other Requirements

Element Z General Design Requirements Owner Standards and Other Requirements Element Z General Design Owner and Other IS Network Services & PART 1 - General Information...2 1.01 Background...2 1.02 Scope...2 1.03 Additions, changes, testing, and acceptance...2 1.04 Special cases

More information

Site Preparation for ClearCube Installation. Rev. F

Site Preparation for ClearCube Installation. Rev. F Site Preparation for ClearCube Installation Rev. F EXECUTIVE SUMMARY Because of the centralized nature of the ClearCube architecture, installation of the system requires a certain degree of site preparation.

More information

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS May 1, 2016 Reviewers should - Be aware that these checklists are not allinclusive but only provide important review items. Reviewers should - Use Checklists

More information

WiredScore Report. Tanfield. 1 Tanfield, Edinburgh, EH3 5DA. Audit Reported Points. Building Connectivity 37 / 45. Building Infrastructure 28 / 41

WiredScore Report. Tanfield. 1 Tanfield, Edinburgh, EH3 5DA. Audit Reported Points. Building Connectivity 37 / 45. Building Infrastructure 28 / 41 WiredScore Report Tanfield 1 Tanfield Edinburgh, EH3 5DA Building Location Building Profile Address: 1 Tanfield, Edinburgh, EH3 5DA Rentable Sqft(k): 191 Section Audit Reported Points Building Connectivity

More information

FIBER OPTIC HARDWARE STEVE PAULOV

FIBER OPTIC HARDWARE STEVE PAULOV C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

Fall Test 21 due 12/11/2012

Fall Test 21 due 12/11/2012 Fall Test 21 due 12/11/2012 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Emergency system transfer equipment, including automatic transfer switches,

More information

Site Preparation CHAPTER

Site Preparation CHAPTER CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

User s Manual. LumiVision series. A Designer s X-ray film illuminator. Walnut, CA U.S.A. By LCD TV Technology

User s Manual. LumiVision series. A Designer s X-ray film illuminator. Walnut, CA U.S.A. By LCD TV Technology User s Manual A Designer s X-ray film illuminator By LCD TV Technology series Point A Technologies, Inc. Walnut, CA U.S.A. FCC RF INTERFERENCE STATEMENT NOTE: This equipment has been tested and found to

More information

DIVISION 27 COMMUNICATIONS

DIVISION 27 COMMUNICATIONS DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS 27 01 00 Operation and Maintenance of Communications Systems 27 01 10 Operation and Maintenance of Structured Cabling and Enclosures 27 01 20 Operation

More information

ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY

ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY ARCHITECTURAL GUIDELINES FOR INSTRUCTIONAL TECHNOLOGY Introduction A classroom is measured by its effectiveness in facilitating the exchange of information. The following general guidelines have been developed

More information

PN Telecommunications Infrastructure Standard for Data Centers Draft 2.0 July 9, 2003

PN Telecommunications Infrastructure Standard for Data Centers Draft 2.0 July 9, 2003 0 NOTICE: PN--00 Telecommunications Infrastructure Standard for Data Centers Draft.0 July, 00 0 This contribution has been prepared to assist the TR- Standards Committee. It is offered to the Committee

More information

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC.

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. 1.01 General Requirements This section details general requirements for plenum sound masking installations. 1.1 Contract

More information

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS

More information

RFP Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service

RFP Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service RFP 2017 845 Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service Version 1 Contents Project objectives... 1 Background... 1 Scope... 1 Timeframe and Cost... 4 Stakeholders, roles and responsibilities...

More information

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions HP UPS R/T3000 G2 Installation Instructions Overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower design and offers power protection for loads up to a maximum of 3300 VA/3000 W

More information

PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS

PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS Version 14 November 19, 2014 Digital Realty Table of Contents INTRODUCTION... 3 ACCESS TO THE POP ROOMS, ISP & OSP... 3 PoP- MoP Forms... 3 Who must

More information

Technology Standards

Technology Standards June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the

More information

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017. Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations

More information

Checklist for building an edge data center

Checklist for building an edge data center Checklist for building an edge data center Building an edge data center to provide a cloud computing environment within a service provider central office can be a complex endeavor. It requires lots of

More information

SECTION TELEPHONE AND COMPUTER CABLING

SECTION TELEPHONE AND COMPUTER CABLING SECTION 16700 TELEPHONE AND COMPUTER CABLING PART 1 - GENERAL Verify the computer and telephone cabling standards with MINES CCIT and Telecommunications departments. Telephone and computer lines shall

More information

Classroom WiFi Network Infrastructure Plan

Classroom WiFi Network Infrastructure Plan Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to

More information

Maximizing Pathways in The Outside Plant

Maximizing Pathways in The Outside Plant Maximizing Pathways in The Outside Plant OSP Pathways Underground (Inside Conduit) Direct-buried Aerial ANSI Standards ANSI/TIA-758-A Customer Owned Outside Plant Telecommunications Cabling Standard ANSI

More information

Avanti HP Series Centrifuges Preinstallation

Avanti HP Series Centrifuges Preinstallation J3HP-TB-001AC May 2009 Avanti HP Series Centrifuges Preinstallation INTRODUCTION Purchase of an Avanti HP series high performance centrifuge includes installation and Basic Instrument Training for two

More information

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS

More information

Design Guidelines for Facilities Construction:

Design Guidelines for Facilities Construction: Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,

More information

E-Series Site Preparation Guide

E-Series Site Preparation Guide E-Series Site Preparation Guide September 2017 215-11797_A0 doccomments@netapp.com Table of Contents 3 Contents Deciding whether to use this guide... 10 Specifications of the model 3040 40U cabinet...

More information

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

User Manual & Modem Installation Guide

User Manual & Modem Installation Guide ..... digital July 2005 Draft Version 07012005 whirlwind 99 Ling Road Rochester, NY 14612 Telephone: 888.733.4396 Fax: 585.865.8930 Email: sales@whirlwindusa.com Technical Support: techsupport@whirlwindusa.com

More information

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network

More information

Spring Test 9 due 05/11/2013

Spring Test 9 due 05/11/2013 Spring Test 9 due 05/11/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A grounding electrode is. a. a solid conductor b. a circuit conductor that

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Data Cabling / Low Voltage Technology Specifications

Data Cabling / Low Voltage Technology Specifications P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO/IEC 18010 2002 AMENDMENT 1 2005-12 Amendment 1 Information technology Pathways and spaces for customer premises cabling IEC 2005 Droits de reproduction réservés Copyright - all

More information

COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Current Control Houses

Current Control Houses Current Control Houses Building Shielding db Type Example 0 Transparent Wood 5 Poor Masonry 10 Moderate Concrete 20 Good Metal Siding 30 Metal All-Metal Current Control Houses Points of Entry Electrical

More information

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC ::

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC :: Module Title Duration : Course CTDC : Certified TIA-942 Design Consultant : 3 days Course Description Data centres are at the core of many organisations. Downtime of the data centre could lead to major

More information

CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program

CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program F.A.R.B Case Study F.A.R.B Software Development, LTD.: Network Design and Implementation CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program Overview Students completing this case study should

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

Peter Sharp RCDD IBI Group

Peter Sharp RCDD IBI Group Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member

More information

LifeSize ClearSea Installation Guide August 2012

LifeSize ClearSea Installation Guide August 2012 LifeSize ClearSea Installation Guide August 2012 LifeSize ClearSea LifeSize ClearSea Virtual Machine LifeSize ClearSea Installation Guide 2 LifeSize ClearSea This guide describes how to install and configure

More information

350 East Plumeria Drive San Jose, CA USA May

350 East Plumeria Drive San Jose, CA USA May Installation Guide 350 East Plumeria Drive San Jose, CA 95134 USA May 2012 201-15135-02 NETGEAR, Inc. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored

More information

G5 PDU Installation Guide

G5 PDU Installation Guide G5 PDU Installation Guide 1 Contents Before You Begin... 3 Overview... 3 Important Safety Information... 3 Required Tools... 5 Section 1 Introduction... 6 Classification Overview... 6 Features... 7 Form

More information

350 East Plumeria Drive San Jose, CA USA February

350 East Plumeria Drive San Jose, CA USA February Installation Guide 350 East Plumeria Drive San Jose, CA 95134 USA February 2013 201-15135-03 Support Thank you for selecting NETGEAR products. After installing your device, locate the serial number on

More information

17. Microwave Collocation 17.1 General

17. Microwave Collocation 17.1 General Original Page 1 17.1 General 17.1.1 General A. Unless otherwise specified herein, general regulations contained in Sections 1 through 4 and Sections 14 and 15 apply in addition to the regulations contained

More information

ICS Entrance Management Sign Installation Guide. Version 1.0

ICS Entrance Management Sign Installation Guide. Version 1.0 ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document

More information

Dell Networking S4100-ON Series. Set-Up Guide

Dell Networking S4100-ON Series. Set-Up Guide Dell Networking S4100-ON Series Set-Up Guide Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either

More information

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications

More information

10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter. AMG9011G-H (-40 to 75C) User Manual

10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter. AMG9011G-H (-40 to 75C) User Manual 10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter AMG9011G-H (-40 to 75C) User Manual www.amgsystems.com Content Overview...1 Introduction... 1

More information

NZQA unit standard version 2 Page 1 of 5

NZQA unit standard version 2 Page 1 of 5 Page 1 of 5 Title Demonstrate knowledge of installation practices and procedures for telecommunications network equipment Level 3 Credits 10 Purpose This unit standard covers the installation of basic

More information

S5048F-ON. Set-up Guide

S5048F-ON. Set-up Guide S5048F-ON Set-up Guide Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either potential damage to

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

The Riser as a Contract Document. Peter Sharp, RCDD

The Riser as a Contract Document. Peter Sharp, RCDD The Riser as a Contract Document Peter Sharp, RCDD IBI Group 1 1 Who am I? Presenter Credentials Electrical Engineer Specialties in communications, electronics and computer sciences, In practice for 40

More information

Communication

Communication 27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and

More information

Leveraging Fiber Properties to Our Advantage

Leveraging Fiber Properties to Our Advantage Leveraging Fiber Properties to Our Advantage Agenda Fiber Properties Air Blown Fiber Components How It Works Design Considerations We Treat Fiber like Copper We add layers of sheathing and pull it through

More information

With the publication. Make the right connection: Bonding a shielded system. installation

With the publication. Make the right connection: Bonding a shielded system. installation Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being

More information

General. Exterior Cameras. Camera Towers

General. Exterior Cameras. Camera Towers CAMERAS General This section explains the requirements for interior and exterior cameras. Two basic types of training ranges have cameras: Urban Ranges and Instrumented Training Ranges. Refer to the standard

More information

GEU Port Gigabit Switch

GEU Port Gigabit Switch GEU-0522 5-Port Gigabit Switch Table Of Contents 1. INTRODUCTION... 3 1.1 Product Briefs... 3 1.2 Product Features... 3 1.3 Hardware Introduction... 4 2. CONNECTING THE SWITCH... 5 2.1 Package Contents...

More information

/STE BuyLine Pathways floor & wiring

/STE BuyLine Pathways floor & wiring 09 69 00/STE BuyLine 7003 Pathways floor & wiring Floor & Wiring Here s the basis of a flexible, high-performance workplace. Where technology adapts with ease. Where the infrastructure operates more cost-effectively

More information

PIX 515/515E. PIX 515/515E Product Overview CHAPTER

PIX 515/515E. PIX 515/515E Product Overview CHAPTER CHAPTER 4 PIX 515/515E This chapter describes how to install the PIX 515/515E, and includes the following sections: PIX 515/515E Product Overview Installing a PIX 515/515E PIX 515/515E Feature Licenses

More information

InnoMedia ESBC B. Quick Install Guide. 1

InnoMedia ESBC B. Quick Install Guide.   1 InnoMedia ESBC 9378-4B Quick Install Guide www.innomedia.com 1 Table of Contents Introduction 2 Package Contents 2 CAUTION 2 Installation 3 Wall-Mounting Instructions 5 Troubleshooting 6 Appendix A. LED

More information

Cable TV, Broadband, Telephone, and Security

Cable TV, Broadband, Telephone, and Security Chapter 7 Cable TV, Broadband, Telephone, and Security Because of the increasingly widespread use of communications and security systems over the past two decades, electricians have been called upon to

More information

Legal Aid Ontario IT Standards & Guidelines for LAO Branch and Clinic Offices

Legal Aid Ontario IT Standards & Guidelines for LAO Branch and Clinic Offices Legal Aid Ontario IT Standards & Guidelines for LAO Branch and Clinic Offices Prepared by: LAO IT-Operations Group July 8, 2015 Revision: 1.1 Table of Contents 1. Introduction... 2 1.1 Functions of a Server

More information

Infrastructure Checklist

Infrastructure Checklist Infrastructure Checklist Prepared By: Neville Turbit Version 1.0 1 Feb 09 Table of Contents Document Origin... 2 Change History... 2 Overview... 3 Points to Consider... 4 Document Origin o. Author Department

More information

KM-4800w. Installation Guide

KM-4800w. Installation Guide KM-4800w Installation Guide TABLE OF CONTENTS page 1 Installation Requirements 2 2 Unpacking 3 2. 1 Unpacking 3 2. 2 Confirmation of Accessories 5 3 Leveling the Machine 7 4 Setup of the Roll Deck 9 5

More information

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled. 27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information