Computer Network Design Guide Existing Systems 1 / 6
|
|
- Maximillian Brooks
- 6 years ago
- Views:
Transcription
1 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: First Issued NOTES: The attached guideline should be utilized in the design of modifications to existing computer network systems. ATTACHMENTS: Existing Computer Networking Infrastructure Guidelines, dated Computer Network Design Guide Existing Systems 1 / 6
2 EXISTING COMPUTER NETWORKING INFRASTRUCTURE GUIDELINES PART 1.00 GENERAL 1.01 SCOPE OF GUIDELINES A. The intent of these guidelines is to provide specific requirements for the design and installation and operation of computer networks for Hillsborough County Schools. It is very important for the proper management and maintenance of the School District s computer networks that all the District networks are carefully designed and that proper codes, standards and guidelines are followed in all facilities. These guidelines are not intended to be a system specification and should be used only as a guideline in planning and designing modifications to existing network infrastructure systems. B. Modifications to existing systems shall conform to the requirements for new systems, as described in Standard Document Number Computer Network Design Guideline for New Systems, unless indicated otherwise in this document EXISTING NETWORKS TO REMAIN Existing networks scheduled to remain may be tested by the Contractor prior to commencement of the work. Upon commencement of the work, all existing network components shall be assumed to be fully functional, unless otherwise documented by test results. Upon completion of the work, existing networks shall operate at the same or better capacity than at commencement. Any existing network component damaged during execution of the work shall be repaired or replaced at no additional cost to the Owner EXISTING NETWORKS TO BE REPLACED Replacement of existing infrastructure shall conform to requirements of Standard Document Number Computer Network Design Guideline for New Systems 1.04 EXISTING NETWORKS TO BE EXPANDED OR UPGRADED A. Any moves, adds or changes must follow the installation practices identified in section 1.05 B. All existing labeling must be verified and changed to meet the district s labeling standards for data. C. All existing duplex (2) data drops are to be changed to quad (4) data outlets. D. Existing cabling, data jacks or patch panels that do not meet Category 5E specifications must be replaced by Category 5E certified product. E. In occupied spaces, existing open-style data racks must be replaced by new enclosed data cabinets. If space limitations do not allow for the installation of a new data cabinet, a ventilated enclosure must be built around the existing open-style rack. F. The contractor shall protect existing network electronics by removing and storing them in a secure, clean and dry environment. G. All fiber and copper data runs are to have their own path. At no time will fiber optics or data cable be allowed to run in a path or conduit with other existing cables. If Computer Network Design Guide Existing Systems 2 / 6
3 multiple fibers are to be run in a single 4 conduit, then each fiber must be run in its own innerduct. Innerduct must be a minimum of 1 and must be orange in color. H. At no time is the number of data cables run through a conduit to exceed 40% of the conduit s capacity. I. All fiber must be a home run to MXC. Cross connections are not permitted. J. Any wire mold or surface mounted junction box used on the surface of an interior wall must be attached to the wall by screws. The wire mold must have the capacity to handle six (6) Cat 5E cables for expansion K. Existing and new power poles must be securely anchored to the floor with Tapcons, and be supported above the ceiling by attachment to a permanent, non-moving structure L. Cabling or fiber no longer used do to upgrade or replacement must be removed M. New data racks for an existing network are to be terminated as follows. a. SC type connections are to be used on any new rack and ST at the MXC if the site is ST based and the LIU has the room. b. If the LIU does not have any open space for a new fiber, then an SC style LIU must be used in the rack. c. If there is no room in the rack for another LIU, then the existing LIU must be replaced and all connections will be of SC type connections INSTALLATION PRACTICES A. Routing of Fiber and Data Cabling: In no case will fiber optic cables be permitted to run exposed, and in no case will Category 5 Extended Overhead cabling be permitted to run exposed or to penetrate the exterior envelope of a building. Lashing cables to existing conduits/appurtenances is strictly prohibited. B. Network system design and installation practices must account for proper fire stopping of any penetrations of fire rated assemblies. C. Fire stopping of fire rated assemblies must meet the requirements of UL, NFPA, and all applicable building codes. D. Raceway, cable support and routing requirements: 1. Conduit for fiber optical cable: Fiber optic cabling shall be installed in a raceway, up to the edge of the backboard of the MXC or IXC, at which point it may be exposed only if secure to the backboard. a. Conduits for fiber optic cable shall be two (2) inches, minimum. b. Conduit installed indoors shall be EMT with compression fittings. 2. The raceway is to be routed in concealed, accessible above-ground locations. Where this is determined by the Owner to be inappropriate, raceways may be installed underground and may be direct burial rated Schedule 40 PVC or galvanized rigid steel. A metallic warning tape must be installed twelve inches (12 ) above all PVC. All trenching will be dug by hand at existing facilities, to a depth of thirty-six inches (36 ). Computer Network Design Guide Existing Systems 3 / 6
4 3. Raceways installed in exposed areas subject to potential damage or harsh conditions shall be galvanized rigid steel. All raceways shall be run straight and level. 4. Exposed raceways are not allowable except where conditions do not allow concealed accessible routing, and only where prior approved by the Owner. All surface-mounted conduit shall be installed with 2-hole straps. E. Conduit for UTP 1. UTP cabling installed inside buildings shall be installed in a raceway from the communications outlet up to the ceiling space (above the dropped ceiling). Unless otherwise approved, this raceway shall be a concealed conduit in the wall, minimum ¾. Where allowed in existing buildings, a surface-mounted wiremold type raceway shall be utilized. Surface mounted raceway shall be mechanically fastened to the wall. Adhesive backing alone will not be permitted. 2. Where a dropped ceiling does not exist, the UTP shall be run in EMT, sized as required. 3. Conduit sleeves, two inches (2 ) minimum, shall be provided at all penetrations of fire rated assemblies. All penetrations shall be fire stopped in accordance with an applicable UL Listed firewall penetration detail using UL Listed fire stopping materials and methods. F. UTP Cabling 1. All communications outlets within a building shall be connected to their respective hub via Category 5 Extended Overhead compliant Unshielded Twisted Pair copper cabling. UTP cabling lengths shall not exceed two hundred seventyfive feet (275 ) from the patch panel to the communications outlet. 2. UTP Cable Routing: UTP should be installed over accessible corridor ceilings or along lines that are parallel to the contours of the building. Deviations from straight should be made at right angles. Wall penetrations or floor penetrations shall be made via pre-constructed distribution systems designed to support and protect the cable. 3. UTP cabling may be free-wired where it is routed concealed above an accessible ceiling. Free-run cables shall be bundled and loosely tie-wrapped at a maximum spacing of twenty-four inches (24 ) on center. Use plenum-rated tie wraps in air plenums. 4. Cabling shall be supported to the building structure at a minimum of four foot (4 ) intervals, with J-Hooks or other approved fittings/means. Cabling shall not be supported from the ceiling, ductwork, conduits, piping, or any other non-structural building member. Two inch (2 ) sleeves shall be provided where the cabling exits the ceiling up to the edge of the MXC or IXC backboard. 5. All UTP cabling must maintain a minimum service loop of four feet (4 ) at both ends for serviceability. At workstation end, service loop must be in ceiling at conduit stub up. At data rack, the service loop for all UTP cables will be attached to backboard or ladder of freestanding racks with appropriate support. 6. Refer to the Educational Specification for number and type of drops to be provided in each space. Computer Network Design Guide Existing Systems 4 / 6
5 7. Patch cables to activate all drops are to be supplied by the Contractor. Patch cables are to be delivered to the Owner s representative and a signed receipt obtained by the contractor for submittal with the close-out documents. Receipt must note quantities. a. All cables must be yellow in color for data and blue in color for telephone. b. Lengths must be divided evenly between three feet (3 ) and six feet (6 ) for patch panels. c. The same count must be supplied for workstation cables in ten feet (10 ) lengths. 8. Owner will supply fiber jumpers as type of electronics provided may vary, but all bulk heads (LIUs) are to remain as specified elsewhere. G. Grounding 1. All equipment racks, cable trays, surge suppressors and cabinets shall be bonded to the building grounding electrical system, building structural steel and shall have a supplemental driven ground rod. In addition a bare #6 AWG copper wire shall be carried and routed with the fiber backbone outside of the fiber conduit throughout the campus providing a loss resistance grounding system. H. Labeling and Identification 1. Each cable shall be labeled with a unique identifier. All network system components shall be labeled, including rooms, racks, cabinets, patch panels, individual ports in each patch panel, communications outlets, etc. The system identification administration shall meet the requirements of TIA/EIA All communications outlets shall be labeled using an encoded labeling system with the room number and port number. 3. Each patch panel in the MXC and IXCs shall be labeled sequentially left-to-right, top-to-bottom, with the room number and port letter, such that the ports can be located easily on the panel. I. Fiber Optic Cabling 1. All fibers in each fiber optic cable shall be identified at each end on the interconnect cabinet. Fibers shall be identified with the building number and corresponding 1-12 fiber number. It shall be everywhere in minimum of two inch (2 ) conduit, except where field conditions permit a run into a building of less than fifty feet (50 ). If fiber must be run outside, such as under canopies, the fiber should be Berk-Tek Armor jacket 62.5/125, tight buffered, indoor/outdoor riser rated plenum and supported appropriately. All fiber optic runs must maintain a minimum service loop of four feet (4 ) at both ends for serviceability. The service loop for all fiber will be attached to backboard or ladder support of freestanding racks with appropriate support. J. Aerial Fiber Distribution For Portable Buildings 1. This work is by Owner unless specifically directed otherwise. 2. If directed to provide aerial fiber distribution for portable buildings, provide only aerial-rated outdoor-rated fiber optic cable. Use a 6-count fiber cable to each Computer Network Design Guide Existing Systems 5 / 6
6 portable building. Provide a 6-count fiber cable to the 1 st portable from the nearest IXC. 3. Provide sufficient pole and messenger wire support for the cable. 4. Provide sufficient guying for pole support. Computer Network Design Guide Existing Systems 6 / 6
Tarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationTarget Interface / Construction Compliance Inspection Checklist
TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data
More informationData Cabling / Low Voltage Technology Specifications
P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall
More informationCOMPUTER NETWORK WIRING SYSTEMS FOR PLCs
SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network
More informationOffice of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO
Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note
More informationSECTION COMMON WORK RESULTS FOR COMMUNICATIONS
PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationCOMMON WORK RESULTS FOR COMMUNICATIONS
SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationGovernment of Prince Edward Island Structured Cabling Standards August 24, 2009
Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationSECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC 5-, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC 5-,
More informationNetwork Construction Guide Specification Telecommunications Infrastructure Standards V 2.6
Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12
More informationBROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS
BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS
More informationSPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING
PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationSECTION COMMUNICATIONS BACKBONE CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationAddendum No. 1 January 7, 2015
Addendum No. 1 January 7, 2015 DISTRICT-WIDE WIRELESS UPGRADE AND CABLING: INTERNAL CONNECTIONS E-RATE YEAR 18 - RFP NO. 14-15-103 Below is the list of questions received and clarifications. The color
More informationA. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationSECTION PANELBOARDS
SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.
More informationCopper Riser And Intrabuilding Cabling
Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13
More informationInstallation Notes TII Model 341 Protector
Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationTIA/EIA 568A Sub-system HORIZONTAL CABLING
TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Date: Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of stations meets DD 9, applicable
More informationSpring Test 17 due 06/14/2013
Spring Test 17 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The NEC defines cable as a cylindrical assembly composed of a conductor centered
More informationFIBER OPTIC HARDWARE STEVE PAULOV
C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More informationLACCD IT Design Standards
LACCD IT Design Standards March 1 2009 This document establishes a uniform standard for the design of IT Structured Cabling for LACCD. It ensures a secure, consistent, robust system with physical and low-voltage
More informationClassroom WiFi Network Infrastructure Plan
Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to
More informationDesign Guidelines for Facilities Construction:
Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,
More informationINTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES
INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside
More informationEmery County Senior Center Green River 06/07
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationUMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management
UMass Lowell October 1, 2011 Network and Voice Infrastructure Specifications Version 5.1 Prepared by Network Engineering and Network Project Management TABLE OF CONTENTS NETWORK AND VOICE INFRASTRUCTURE
More informationSECTION TELEPHONE AND COMPUTER CABLING
SECTION 16700 TELEPHONE AND COMPUTER CABLING PART 1 - GENERAL Verify the computer and telephone cabling standards with MINES CCIT and Telecommunications departments. Telephone and computer lines shall
More informationSECTION WIRING DEVICES
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 REFERENCES... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 COORDINATION... 2 PART 2 - PRODUCTS... 2 2.1
More informationANSI/TIA/EIA-568-B Cabling Standard NOTE
95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial
More informationMeter Enclosure and Equipment Standards
Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable
More informationSECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations
SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology
More informationWire Communications Design jfm 07. An Inside Look at Outside Plant
An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure
More informationANSI/TIA/EIA-568-B Cabling Standard
83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on
More informationInstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 InstaPATCH Cu Solution Specification 2 Harness Assembly Design 3
More informationLos Angeles Community College District Design Standards
LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure
More informationSiemon PON Fiber Cabling Solutions
Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility
More informationGeneral. Exterior Cameras. Camera Towers
CAMERAS General This section explains the requirements for interior and exterior cameras. Two basic types of training ranges have cameras: Urban Ranges and Instrumented Training Ranges. Refer to the standard
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 6 APPR:MDW:JVG:06-08-18
More informationOutdoor Risk and Equipment Protection
Outdoor Risk and Equipment Protection The proper use of surge suppressors, lightening arrestors, and weatherproof enclosures are critical protection measures for all outdoor wireless and IP video devices.
More informationFiberSolutions. Fiber Optic Cable & Assembly Solutions
Solutions Optic Cable & Assembly Solutions Solutions MOHAWK FIBER OPTIC CABLE AND ASSEMBLY SOLUTIONS Today s fast paced world places an unyielding burden on data centers to deliver high performance and
More informationSUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT
SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT CAPACITY WITH OPTION TO SEGMENT CHANNELS FIBER CABLE TO UPGRADE CURRENT BUILDING NETWORK
More informationE. Numbering and Labeling Pathway components. In general, pathway components are not labeled.
27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part
More informationTelecommunications Structured Cabling Systems
Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major
More information4100/4120-Series Class A / Class B Zone Modules Installation Instructions
4100/4120-Series Class A / Class B Zone Modules Installation Instructions Introduction This publication describes the installation procedure for the following modules. Model Description Required Back Box
More informationOMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE
OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE The Omega MPP enclosure is based on a 19" frame, with 4 empty module slots for MPP modules. Highly flexible : any mix between twisted pair and optical fiber modules.
More informationBulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010
Ontario Electrical Safety Code - Bulletins 50-1-0 Bulletin 50-1-0 Installation of Solar Photovoltaic Systems Section 50; Rules: 84-020, 84-024, 84-030; Tables 11 and 19 Issued July 2010 Scope (1) Introduction
More informationElement Z General Design Requirements Owner Standards and Other Requirements
Element Z General Design Owner and Other IS Network Services & PART 1 - General Information...2 1.01 Background...2 1.02 Scope...2 1.03 Additions, changes, testing, and acceptance...2 1.04 Special cases
More informationIntroduction to the CRS Back-to-Back System
This chapter provides an overview of the CRS Back-to-Back System and describes what is required to interconnect system components. The chapter covers the following topics: System Overview, page 1 Cabling
More information~::~~ Cabling System Planning and Installation Guide
~::~~ Cabling System Planning and Installation Guide - - - - - - - - - - - - IBM Cabling System Planning and Installation Guide Eighth Edition (October 1987) This is a revision of GA27-3361-6, which is
More informationPoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS
PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS Version 14 November 19, 2014 Digital Realty Table of Contents INTRODUCTION... 3 ACCESS TO THE POP ROOMS, ISP & OSP... 3 PoP- MoP Forms... 3 Who must
More informationThe University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels
More informationTechnology Standards
June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the
More informationCommunications. UNM IT/Telecommunications Guide Specification Communications
The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary
More informationf) Telecommunications Equipment Rooms
SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification
More informationICS Entrance Management Sign Installation Guide. Version 1.0
ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document
More informationSPECIFICATION STANDARD
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationTECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2
document Page 1 of 18 TECHKNOW, INC Kiosk Order Confirmation System INSTALLATION MANUAL Revision Date: July 11, 2012 Part # Version 3.2 Techknow, Inc. 393 Mayfield Road Duncan, SC 29334 www.gotechknow.com
More informationDivision 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More information4100/4120-Series and 4010ES Relay Modules Installation Instructions
4100/4120-Series and 4010ES Relay Modules Installation Instructions Introduction This publication describes the installation procedure for the relay cards listed in the following table. Model Number Description
More informationSECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS
SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS CONTENTS PAGE 1. GENERAL... 5-1 1.1. Introduction... 5-1 1.2. Equipment Layout Requirements... 5-1 2. EQUIPMENT FRAMES... 5-2 2.1. Introduction...
More informationAPC APPLICATION NOTE #133
APPLICATION NOT #133 Cable Trough, Ladder, and Partition Configuration Guide By Bob Oliver Abstract Management of power and data cabling is critical for data center installation and long-term maintenance.
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationInterconnect Product CATALOG Q700
onents.com Interconnect Product CATALOG Q700 Quest Network Quest Network Warranty Products Warranty Que st Technology International Inc., carries a LIFETIME warranty on all Category- Rated link components
More informationGround Power Modules. And Accessories For Healthcare Facilities. Technical Bulletin NAE /
2 Ground Power Modules And Accessories For Healthcare Facilities Technical Bulletin NAE2092320 / 10.2011 Ground Power Modules Hospital grade outlet modules Introduction BENDER series GPM ground and power
More informationANSI/TIA-568-C Cat 6A Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION FARE COLLECTION SYSTEM
SECTION 17830 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for the Ticket Vending Machines (TVMs) and for the Clipper Network Card Interface Devices (CIDs) as a subsystem of the station
More informationPanduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA
Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Figure 1: Industrial Distribution Frame (IDF) Equipment Elevation
More informationCommunications Updated April
27 00 00 Communication 27 05 00 Common Work Results for Communications 1. Purpose a. Coastal Carolina University facilities requiring cabling installation. This document provides the minimum performance
More informationBonding and grounding NETCONNECT copper cabling systems
White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding
More informationSECTION PROJECTOR LIFTS AND MOUNTS. A. Refer to Section [ Submittal Procedures] [Insert section number and title].
(Specifier Note: The purpose of this guide specification is to assist the Specifier in correctly specifying AeroLift motorized projector lifts and their installation. The Specifier needs to edit these
More informationHuron School District Request for Proposal
Huron School District Request for Proposal Allowable Contract Date: January 25, 2017 Bids received after January 25, 2017 may not be considered 32044 Huron River Dr. New Boston, MI 48164 Contact person:
More information9/27/04 cci Cablecom Inc. 1
cci Cablecom Inc. 1 CCI Cablecom Inc. is a privately held, women owned corporation headquartered in Aurora, CO. We manufacture a variety of voice and datacom products. Cable applications Include: Local
More informationFall Test 21 due 12/11/2012
Fall Test 21 due 12/11/2012 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Emergency system transfer equipment, including automatic transfer switches,
More informationMCIWEST G6 TELECOMMUNICATION REQUIREMENTS SECTION (ISP)
Camp Pendleton Requirements Supplement MARINE CORPS INSTALLATIONS WEST MCB CAMP PENDLETON G6 MCIWEST G6 TELECOMMUNICATION REQUIREMENTS SECTION 271500(ISP) Steve Clayton Assistant Chief of Staff, MCIWEST
More informationB E C A U S E Y O U R B U S I N E S S R U N S T H R O U G H U S A BERK-TEK WHITE PAPER. Cabling for. Secure Government Networks.
B E C A U S E Y O U R B U S I N E S S R U N S T H R O U G H U S A BERK-TEK WHITE PAPER Cabling for Secure Government Networks www.berktek.com Cabling for Secure Government Networks Government networks,
More information2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS
NOCCCD Cabling Infrastructure Standards - Page 1 2.3 SCOPE OF WORK MATRI TO BE INCLUDED IN DISTRICT PROJECTS For each project, a Scope of Work Matrix is to be created by the construction manager and updated
More informationCOUNTY OF SAN JOAQUIN
COUNTY OF SAN JOAQUIN General Services Department 44 North San Joaquin Street, Suite 590 Stockton, California 95202-2778 (209) 468-3357, Fax (209) 468-2186 GABRIEL E. KARAM Director Capital Projects Facilities
More informationCabling Solutions Data Center & Local Area Networks
Cabling Solutions Data Center & Local Area Networks R&M About us. «R&M is a leading provider of cabling solutions for high quality communication networks.» R&M (Reichle & De-Massari AG) has developed and
More informationField-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red.
FM45 Connector Cat. 6 A IP20, 4P, TIA 568-A/B, 10x R815651 966704105 10 Stk. 090.7437 / ähnliche Abbildung Instruction manual Field-terminated connector with housing. Color housing: gray (RAL 7042). Color
More informationStructured Cabling Guidelines
Informatics Planning and Services Structured Cabling Guidelines Version 1.7 August 2015 Informatics Planning and Services 1 Version 1.7 TABLE OF CONTENTS SECTION 1 STATEMENT OF PURPOSE... 1 SECTION 2 APPLICABLE
More informationDIVISION 27 COMMUNICATIONS
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS 27 01 00 Operation and Maintenance of Communications Systems 27 01 10 Operation and Maintenance of Structured Cabling and Enclosures 27 01 20 Operation
More informationAT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)
AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T
More informationREQUEST FOR PROPOSAL:
REQUEST FOR PROPOSAL: FIBER CABLING INSTALLATION TO CONNECT SIX ADDITIONAL VIEWING STATIONS AT THE EMERGENCY OPERATION CENTER (EOC) WITH THE REGIONAL VIDEO COMMAND CENTER (RVCC) VIDEO FEED I. DESCRIPTION
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationFOSC 400 Closures and Accessories 2015 ORDERING GUIDE 1ST EDITION
Closures and Accessories 2015 ORDERING GUIDE 1ST EDITION Contents How to Order FOSC 400 Closures 3 How to Order Accessories for the FOSC 400 Closures 5 Other FOSC Fiber Optic Splice Closures 9 Product
More informationEhresman Associates, Inc. architects engineers
Architects 803 West Big Beaver, Suite 350 Troy, MI 48084 Wright & Hunter Technology Advisors 818 West 11 Mile Road Royal Oak, MI 48067 Peter Basso Associates Inc Mechanical/Electrical Engineers 5145 Livernois,
More information